Professional Documents
Culture Documents
PART 1 - GENERAL
1.01 SUMMARY
1.02 SUBMITTALS
PART 2 - PRODUCTS
2.01 WIRES
A. Wires shall be single conductor type THHN or THWN insulated with polyvinyl chloride
and covered with a protective sheath of nylon, rated at 600 volts. Wires may be operated
at 90 degrees C. maximum continuous conductor temperature in dry locations, and 75
degrees C. in wet locations and shall be listed by UL Standard 83 for thermoplastic
insulated wires, listed by Underwriter's Laboratories (UL) for installation in accordance
with Article 310 of the California Electrical Code (CEC). Conductors shall be solid
copper for 12 AWG and smaller conductors, and stranded copper for 10 AWG and larger
conductors. Conductors shall be insulated with PVC and sheathed with nylon. Wires
shall be identified by surface markings indicating manufacturer's identification, conductor
size and metal, voltage rating, UL symbol, type designations and optional rating.
Indentations for lettering are not permitted. Wires shall be tested in accordance with the
requirements of UL standard for types THWN, or THHN.
2.02 STANDARDS
10/01/2011
PROJECT NAME LOW-VOLTAGE WIRES 600 VOLT AC
SCHOOL NAME 26 0519-1
PART 3 - EXECUTION
3.01 INSTALLATION
A. Wires shall not be installed until debris and moisture is removed from conduits, boxes,
and cabinets. Wires stored at site shall be protected from physical damage until they are
installed and walls are completed.
C. The Project Inspector will observe installation of feeder cables. Notify the Project
Inspector not less than two working days in advance of the proposed time of feeder
installation.
D. At outlets for light, power, and signal equipment, pigtail splices with 8-inch circuit
conductor leads for connection to fixtures, equipment, and devices.
G. Connections to any bussing and high-press cable connectors shall be securely bolted
together with corrosion-resistant plated carbon steel, minimum grade five machine
screws secured with constant pressure-type locking devices.
I. Wire switchboards, panel cabinets, pull boxes, and other cabinets except public address,
shall be neatly grouped and tied in bundles with nylon ties at 10-inch intervals. In
switchboards, panels and terminal blocks, wires shall be fanned out to terminals. If
bundles are longer than 24 inches, a maximum of nine current carrying conductors may
be bundled together.
J. Install conductor lengths with a minimum length within the wiring space. Conductors
must be long enough to reach the terminal location in a manner that avoids strain on the
connecting lug.
10/01/2011
PROJECT NAME LOW-VOLTAGE WIRES 600 VOLT AC
SCHOOL NAME 26 0519-2
K. Maintain the conductor required bending radius.
L. Neutral conductors larger than 6 gage, which are not color identified throughout their
entire length, shall be taped, painted white or natural gray, or taped white where they
appear in switchboards, cabinet, gutters or pull boxes. Neutral conductors 6 gage and
smaller shall be white color identified throughout their entire length.
M. Fire alarm and clock wiring shall be continuous from terminal cabinets or from
equipment to each device. Splices are not permitted between devices and/or terminal
cabinets at junction and pull boxes. Wiring shall be terminated at terminal blocks or
devices only.
N. Wiring systems shall be free from short circuits and grounds, other than required
grounds. The contractor shall be responsible for the testing of feeder and branch circuit
conductors insulation resistance. The insulation of the conductors shall be tested prior to
connections to any panelboards, switchboards, variable frequency drives, lighting control
systems, ballasts, and wiring devices such as but not limited to GFI receptacles, TVSS
receptacles, or equipment. Insulation testing of panelboards and switchboards shall be
independently performed from the insulation testing of any conductors as specified in
other sections of this specification.
b. Test equipment shall be provided with a label stating the date of last
calibration. As a minimum the equipment shall have been calibrated within
the past 12 months.
10/01/2011
PROJECT NAME LOW-VOLTAGE WIRES 600 VOLT AC
SCHOOL NAME 26 0519-3
2. Utilize the services of an approved independent testing laboratory or a qualified
contractors employee (Technician certified in accordance with ANSI/NETA
ETT-2000 Standard for Certification of Electrical Testing Personnel) to perform
megger time-resistance insulation testing of branch circuit conductors. Tests must
be conducted with wires disconnected at both ends.
A. General Wiring:
B. Signal Systems: Wires for signal systems shall be color-coded and installed under
observation of the Project Inspector. Except where otherwise specified, color-coding
shall be as follows:
EDIT NOTE: IN NEW SCHOOLS AND SOME EXISTING SCHOOLS THE
PROGRAM SIGNAL IS THROUGH THE PA SYSTEM; PROGRAM BELLS
ARE NOT PRESENT. DELETE REFERENCE TO PROGRAM BELLS AS
NEEDED.
10/01/2011
PROJECT NAME LOW-VOLTAGE WIRES 600 VOLT AC
SCHOOL NAME 26 0519-4
Program Bells (some existing White (120 volt, common) Black (C.R. program) Blue
secondary schools) (Shop program) Brown (Gym program) Yellow
(Auditorium fire alarm)
Fire Alarm Horns Pink (+) and Gray (-)
Fire Alarm Strobes Orange (+) and Blue (-)
Un-Interruptible 24 Volt Yellow (+) and White (-)
Power (Annunciator, Water Note: A single white wire may be common to both
Flow, and Audible Device)
Interruptible 24 Volt Power Brown (+) and White (-)
(4 wire smoke detectors, Note: A single white wire may be common to both
duct detectors)
Switch-Leg Sprinkler Bell Violet (+) and White (-)
(Between water flow and
audible device)
Door Holding Magnets (Non Black (+) and White (-)
Power Limited)
A. Feeder wires and cables shall be identified at each point the conduit run is broken by a
cabinet, box, gutter, etc. Where terminal ends are available, identification shall be by
means of heat shrink wire markers, which provide terminal strain relief. Markers shall be
by Tyco Electronics, Panduit, Brady Perma-Sleeve, or equal. Identification in other areas
shall be by means of wrap-around tape markers from Tyco Electronics, Panduit, Brady
Perma-Code or equal. Markers shall include feeder designation, size, and description.
A. Splices, joints, and connectors joining conductors in dry and wet locations shall be
covered with insulation equivalent to that provided on conductors. Free ends of
conductors connected to energized sources shall be taped. Voids in irregular connectors
shall be filled with insulating compound before taping. Thermoplastic insulating tape
approved by UL, NRTL, or equal for installation as sole insulation of splices shall be
furnished and shall be installed according to manufacturer's printed specifications.
3.05 PROTECTION
3.06 CLEANUP
A. Remove rubbish, debris and waste materials and legally dispose of off the Project site.
END OF SECTION
10/01/2011
PROJECT NAME LOW-VOLTAGE WIRES 600 VOLT AC
SCHOOL NAME 26 0519-5