You are on page 1of 12

Compact Integrated

Distribution Substation
(CIDS)
1- INTRODUCTION
SAVE SPACE
2.5m2 footprint for CIDS up to 630kVA.

SAVE THE ENVIRONMENT


No SF6, No PCB.

SAVE MONEY
Save up to 50% from conventional package substation with housing.

ENSURE SAFETY FOR PUBLIC


No exposed live parts.

ENSURE SAFETY FROM FIRE


If filled with flame retardant fluid.

2
2- DESCRIPTION
The CIDS is a compact fully integrated outdoor package substation with medium
voltage equipment, transformer, and low voltage equipment. The package
substation is completely manufactured and assembled ready for installation on site.
It ensures a high level of protection against access to live parts with a protection
degree of IP 54 according to IEC 60529.

The operation and control is achieved from the front of the unit, with separate
compartments for medium voltage and low voltage sections. Four lifting lugs
located on the upper part enable the lifting of the complete unit easily.

2.1. Major Benefits


2.1.1. Compact design-Reduced footprint
Reduction of space requirement.
Reduction of footprint.
2.1.2. Cost Savings
Minimum installation and maintenance labor costs.
Minimum civil work; no building or vault structure.
No need for main low voltage circuit breaker.
2.1.3. Operational Integrity
Components are assembled and tested as an integral unit at the factory.
Access to all elements of control and protection in one casing.
2.1.4. Safety
Live parts inside the secure enclosure are hidden from the public and
environment.
If filled with flame retardant fluid, risk of transformer fire is greatly reduced due to
high fire and flash points.
2.1.5. Environmental Integrity
Low profile design requires minimum real estate.
Dielectric fluid replaces ozone-depleting SF6 gas, currently used in RMU switching
modules.

3
2.2. Main Components
2.2.1. Enclosure
Single compact enclosure housing the transformer, medium voltage and low voltage
sections.
The is designed to be installed outdoor, with a protection degree of IP 54 according
to IEC 60529
2.2.2. Low voltage section
This section can be designed and manufactured according to the needs of each
customer. Basic equipment includes:
Low voltage bushings
Three current transformers
Four outgoing circuits by fuse links
Three ammeters
One voltmeter + one selector switch
Optional:
Circuit breakers instead of fuse links
Multifunction electronic meter
2.2.3. Medium voltage section
It includes the following components:
Plug-in bushings
Two sectionalizing switches for incoming and outgoing lines with earthling facility
Main interrupter for protection against overloads and secondary short circuits
Backup fuses for protection against internal faults
Tap changer for voltage control (off-load)
Voltage presence indicators
Hotstick for sectionalizing switch operation
Optional:
Earth fault and short circuit indicators
2.2.4. Transformer section
It includes the core and the windings of the transformer.

4
Fig 1 Plug-in bushing Fig 2 Three phase load break Fig 3 Back-up current limiting Fig 4 Main interrupter
sectionalizing switch fuse

Plug-in bushing (Fig 1)


Built in capacitive point for voltage presence detection.
Three phase loadbreak sectionalizing switch (Fig 2)
Make-Before-Break operation.
Silver plated copper contacts.
Open/Close/Earth positions.
Back-Up current limiting fuse(Fig 3)
For transformer internal faults.
Protects and isolates faulty equipment.
Coordinated with main interrupter (4), gives full range of fault protection.
Main interrupter (Fig 4)
Current and temperature sensitive protective device.
Protects from overloads and secondary faults.
Three phase trip, externally resettable.
Insulating fluid
Standard mineral PCB free oil according to IEC 60296.
Optional: fire resistant high fire point organic or synthetic fluid.

5
Fig 5 Lifting Lugs Fig 6 Name Plate + Fig 7 Mimic and labels Fig 8 Three phase main
single line diagram interrupter

2.3. CIDS Single Line Diagram

1
A
Source

2
Open
Closed

Earth
3 4 Transformer
Coil

LV
B
Source

Closed
Open 5
Earth
LV
Panel

6
Fig 9 Off load tap changer Fig 10 LV porcelain Fig 11 Medium voltage Fig 12 Pressure Fig 13 Dielectric
bushings screened bushings relief valve level indicator

2.4. Technical Data


GENERAL
Design ambient temperature 40C
Frequency 50Hz or 60Hz

TRANSFORMER 250kVA 400kVA 630kVA


Rated voltages
Primary highest voltage 12kV /17.5kV/24kV
Rated secondary voltage From 231V up to 433V
Vector group Dyn11
Lightning impulse voltage (primary) 75kV/95kV/125kV
Industrial frequency withstand during 1 min (primary) 28kV/38kV/50kV
Off load tap changer (5 positions) 2x2.5%
No load losses 445W 840W 920W
Load losses 2715W 3950W 6020W
Short circuit impedance 4.00% 4.00% 4.00%
ACCORDING TO IEC 60076 STANDARD

MEDIUM VOLTAGE
Rated short duration admissible current 16kA
Sectionalizing switch for input-output and ground
Highest voltage level 12kV /17.5kV/24kV
Rated direct current 630A for 12kV primary
400A for 17.5kV and 24kV primary
Fuses
Highest voltage level 24kV
Maximum interrupting current 50kA rms
Plug-in bushings, 6 in loop
Highest voltage level 24kV
Rated direct current 630A
ACCORDING TO IEC 60298 STANDARD

LOW VOLTAGE
Rated voltage From 231V up to 433V
Rated current Up to 1000A (according to transformer rating)
Short time current (1s) 25kA
Earthing Neutral solidly earthed
Industrial frequency withstand during 1 min 2.5kV
Lightning impulse withstand test 6kV
ACCORDING TO IEC 60439 STANDARD

For 1000kVA please consult us


For other requirements than the above table, please consult us

7
Fig 14 Line Sectionalizing Fig 15 Led ( voltage indicator) Fig 16 Elbow Connector Fig 17 Grounding terminals
switch and earth controls

2.5. Dimensions and Weights

Ma n u fa c tu re d b y Ma te l e c s .a.l

MATELEC s.a.l
Made in Lebanon
E ma il : ma te le c@ ma te le cg ro up.com
P .O.B o x : 1 2 J b e i l - L e b a non
Tel : +9 61 9 6 20 920
Fax : +9 61 9 6 20 9 34/35

A1 A2 B1 B2 C1 C2

A S ecti onal iz ing


S wi tch

a
b
F use
C c B M agneX

a b c n

L1 L2

E
F
A B

C D
H
G

Total
Rating -A- -B- -C- -D- -E- -F- -G- -H- Weight
kVA mm mm mm mm mm mm mm mm Kg
250 1230 850 2080 1230 1975 715 1117 813 2550
400 1230 850 2080 1230 1975 715 1117 813 2900
630 1230 850 2080 1230 1975 715 1117 813 3250
Dimensions and weights are approximate and may change according to specifications.

8
Fig 18 Medium voltage cable Fig 19 Insulated device for Fig 20 Medium voltage Fig 21 Low voltage
support + clamps drive (Hotstick) compartment compartment

1 2 3 4 5 6 7 8 9 10 26

11

12 MATELEC
s.a.
Ma
de l A1
nLe
ba
ino
n M
aO.
Em
P.
Te
A2 xct
Bo1:ur
i96
l:x:
Fa
B1B2 ed
ymat
ilMatel
el
ec
20
+
0 nufa
.a.l
l:be
@m s9 920
-atel
ec
gr
ou
p.
co
Lem
banon
12
934/3
5
C1
C2 b6
J
62
CacA
bB Fu Sct
se
Maion
al
iz
in
gw
it
ch
gneX e
a bcn
13

14

L1 L2
15

16
22
17

18 23
19 24

20

18 25

21

1. Lifting Lugs (Fig 5) 14. Line Sectionalizing switch and earth controls (Fig 14)
2. Dielectric refill plug 15. Led ( voltage indicator) (Fig 15)
3. Name Plate + single line diagram (Fig 6) 16. Medium voltage screened bushings (Fig 11)
4. Mimic and labels (Fig 7) 17. Elbow Connector (Fig 16)
5. Three phase main interrupter (Fig 8) 18. Grounding terminals (Fig 17)
6. Off load tap changer (Fig 9) 19. Medium voltage cable support + clamps (Fig 18)
7. LV porcelain bushings (Fig 10) 20. Medium voltage compartment (Fig 20)
8. Power meter (Optional) 21. Rollers
9. Current Transformers 22. Fuses
10. Power Meter Protection Fuses (optional) 23. Low voltage compartment (Fig 21)
11. Pressure relief valve (Fig 12) 24. Low voltage cable support + clamps
12. Dielectric level indicator (Fig 13) 25. Drainage and sampling device
13. Blocking device 26. Insulated device for drive (Hotstick) (Fig 19)

9
ELECTRICAL EQUIPMENT INDUSTRIES COMPANY LTD.
P.O.Box 850175 Amman 11185
Amman, Jordan
Tel: (962) 6 5727861/2
Fax: (962) 6 5727863
E-mail: electric@wanadoo.jo

INTERNATIONAL TRANSFORMERS MATELEC LTD.


10th of Ramadan City, Egypt
Tel: (20) 2 4149004 - 2901795
Fax: (20) 2 4155614
E-mail: itm.office@link.net

MATELEC S.A.L.
Amchit - Ghorfine
P.O.Box 12 Jbeil - Lebanon
Tel: (961) 9 620920
Fax: (961) 9 620934/5
E-mail: matelec@matelecgroup.com

SAUDI MATELEC CO. FOR INDUSTRIES LTD.


Dabab Street, Dabab Bldg, 3rd floor, Office N 10
P.O.Box 52114, Riyadh 11563
Riyadh, Kingdom of Saudi Arabia
Tel: (966) 1 4029909
Fax: (966) 1 4024280
E-mail: agos@saudimatelec.com.sa

TRANSFO MATELEC S.A.


ZI de Briangaud
35600 Redon, France
Tel: (33) 2 99711650
Fax: (33) 2 99721700
E-mail: info@transfo-matelec.fr
MATELEC GROUP
Amchit - Ghorfine - P.O.Box: 12 Jbeil - Lebanon
Tel: (961) 9 620 920 - Fax: (961) 9 620 934/5
E-mail: matelec@matelecgroup.com
www.matelecgroup.com

You might also like