CALCULO DE LA RED DE TIERRAS PARA SISTEMA TRIFASICO, CON UNA CAPACIDAD INSTALADA
(O BANCO DE TRANSFORMACION ) EN SUBESTACION DE 1500 KVA., A 23000 V., 3F, 3H, 60Hz.
OBJETIVOS :
PROCEDIMIENTO DE CALCULO :
CONSIDERACIONES Y ABREVIATURAS :
Df = 1.051
Cp = 1.00
IG = ( Cp Df Ig )
IG = 2215.28 A.
Factor = 6.60
Ar = IG x FACTOR
Ar = 2215.28 x 6.60
Ar = 14620.83 Cmils.
K = [ - s ] [ + s ]
K = -0.9771
6 n
Cs = [1 0.96 ] 1+ 2 E K 1 + 2n hs 0.08 = 0.5805
1
CALCULO DE POTENCIALES TOLERABLES.
Na = 4.00
Nb = 5.00
Nv = 6.00
La = 12.40
Lb = 7.35
Lv = 3.05
D = 3.10
A = ( La Lb ) m.
A = 91.14 m.
Lc = ( Na La ) + ( Nb Lb )
Lc = 86.35 m.
Lr = ( Nv Lv ) m.
Lr = 18.29 m.
L = [ Lc + ( 1.15 Lr ) ] m.
L = 107.38 m.
Ns = MAXIMO DE Na o Nb
Ns = 5.00
CALCULO DE Ks PARA POTENCIAL DE PASO.
Ns-2
Ks = 0.4393
Kis = 1.516
Es = Ks Kis IG L
Es = 742.29
Nm = ( 20.00 )^ = 4.47
Nm = 4.47
CALCULO DE Kh.
Kh = [ 1 + ( h ho ) ]
Kh = 1.26
COMO NUESTRA MALLA CUENTA CON ELECTRODOS EN LAS ESQUINAS Kii = 1.0000
Kii = [ 1 ( ( 2 Nm )^ ( 2 Nm ) ) ] =
CALCULO DE Kim
Kim = 1.4248
CALCULO DE Km
Km = [ 1 2 ] [ In { ( D 16h d ) + ( ( D + 2h) 8D d ) - ( h 4d ) }
+ { ( Kii Kh ) ln ( 8 ( 2 ( Nm-1) ) ) } ] =
Km = 0.6565
Em = ( Km Kii IG ) ( L )
Em = 732
Rg = [ ( 1 L ) + { ( 1 ( 20 A )^ ) } { 1 + ( 1 ( ( 1 + h ) ( 20 A )^ ) ) } ]
Rg = 3.4574
CONCLUSION :
PROYECTO : CONGRESS
R=
R= + =
4xr L
R10.00
+ =
4xr L
0 m. x 7.35 m. = 91.14 m.
ES EN LA FORMULA :
54.03 54.03
+ = 3.01 OHMS.
21.56 107.38
R10.00
DESCRIPCION : CANTIDAD
VARILLAS
ENTERRADAS = 6.00
CONDUCTORES
PARALELOS = 4.00
CONDUCTORES
TRANSVERSALES = 5.00
LONGITUD TOTAL DE
CONDUCTORES = 21.03 m.+ 49.60 m.+ 36.75 m.= 107.3
AL DE CONDUCTORES ENTERRADOS
ANALISIS :