Page

1.00 COMMON DATA 4

2.00 AMPERE METER 5


A. General 5
B. Construction Data 5
C. Electrical Data 6
D. Other Performance Data 6
E. Supporting Documents 6

3.00 VOLTMETER 7
A. General 7
B. Construction Data 7
C. Electrical Data 8
D. Other Performance Data 8
E. Supporting Documents 8

4.00 WATTMETER 9
A. General 9
B. Construction Data 9
C. Electrical Data 10
D. Other Performance Data 10
E. Supporting Documents 10

5.00 VAR METER 11


A. General 11
B. Construction Data 11
C. Electrical Data 12
D. Other Performance Data 12
E. Supporting Documents 13

_________________________________________________________________________________________________________
____
355102494.xls Page 2 of 19
METERING DEVICES
Analogue Indicating Instruments

Table of Content

Page

6.00 FREQUENCY METER 13


A. General 13
B. Construction Data 13
C. Electrical Data 14
D. Other Performance Data 14
E. Supporting Documents 14

7.00 POWER FACTOR METER 15


A. General 15
B. Construction Data 15
C. Electrical Data 16
D. Other Performance Data 16
E. Supporting Documents 16

8.00 RECORDER 17
A. General 17
B. Construction Data 17
C. Electrical Data 18
D. Other Performance Data 18
E. Supporting Documents 19

_________________________________________________________________________________________________________
____
355102494.xls Page 3 of 19
METERING DEVICES
Analogue Indicating Instruments

Sl. No. REQUIRED TENDERED

1.00 COMMON DATA

1.01 Auxiliary contacts


1.01.1 AC
1.01.1.1 rated voltages V 230

1.01.1.2 number of contacts


1.01.1.2.1 NO No. 2

1.01.1.2.2 NC No. 2

1.01.1.3 rated make, continuously, break current A 10


at 500C, pf = 0.8
1.01.1.4 rated thermal capacity kA

1.01.2 DC
1.01.2.1 rated voltages V 110

1.01.2.2 number of contacts


1.01.2.2.1 NO No. 2

1.01.2.2.2 NC No. 2

1.01.2.3 rated make, continuously, break current A 10


at 500C
1.01.2.4 rated thermal capacity kA

1.02 Frequency Hz 50

1.02.1 variation Hz 45 to 55

1.03 Meter housings


1.03.1 meter base, terminal block, meter & polyamide
terminal cover
1.03.1.1 grade 6.6

1.03.1.2 UV stability
1.03.1.2.1 applicable standards ASTM G53/26/23

1.03.1.3 flame retardant


1.03.1.3.1 applicable standards IEC 60695-2-1
UL 94-VO

1.03.2 degree of protection IP 52

TENDERER`s STAMP SIGNATURE

___________________________________________________________________________________________________________________
355102494.xls

Page 4 of 19
METERING DEVICES
Analogue Indicating Instruments

Sl. No. REQUIRED TENDERED

1.04 Unique identification code provided on each meter yes

2.00 AMPERE METER

A. General
2.01 Manufacturer
2.01.1 name
2.01.2 country of manufacturer
2.02 Applicable standards IEC 60051, 61554

2.03 Type
2.04 Type test
2.04.1 carried out ? yes

2.04.2 date dd-mm-yy

2.04.3 testing laboratory


2.04.3.1 name
2.04.3.2 country

B. Construction Data
2.05 Suppression, if any yes/no

2.06 Instrument is flush mounting type ? yes

2.07 Pointer is knife edge type ? yes

2.08 Glass is anti glare ? yes

2.09 Class <1

2.10 Scale
2.10.1 quadrant (900) yes

2.10.2 sector (600) no

2.10.3 circular (1800) no

2.10.4 linear (2400) no

2.11 Dimensions
2.11.1 length mm 96

TENDERER`s STAMP SIGNATURE

___________________________________________________________________________________________________________________
355102494.xls

Page 5 of 19
METERING DEVICES
Analogue Indicating Instruments

Sl. No. REQUIRED TENDERED

2.11.2 width mm 96

2.12 Weight kg

2.13 Dial is snow white with black numerals ? yes

2.14 Dial is parallax free ? yes

2.15 Means of zero adjustment provided ? yes

2.16 Restorable max. current indicator yes/no

C. Electrical Data
2.17 MV, if applicable
2.17.1 measuring range A

2.17.2 operating current (CT secondary) A 1 or 5

2.18 LV, if applicable


2.18.1 measuring range A

2.18.2 operating voltage Vac N/A

2.18.3 operating current (CT secondary) A 5

2.19 Continuous overcurrent A 1.2 x rated current

2.20 Insulation resistance at 500V M > 20

2.21 Dielectric strength kVac, 1min. 2

2.22 Burden
2.22.1 current path VA <1

2.22.2 voltage path N/A

D. Other Performance Data


2.23 First commercial operation of offered ampere meter
2.2299.1 date dd-mm-yy

2.24 Reference list attached ? yes/no

E. Supporting Documents
2.25 Type test reports enclosed ? yes

2.26 List of minimum testing facilities enclosed ? yes

TENDERER`s STAMP SIGNATURE

___________________________________________________________________________________________________________________
355102494.xls

Page 6 of 19
METERING DEVICES
Analogue Indicating Instruments

Sl. No. REQUIRED TENDERED

2.27 Technical literature enclosed ? yes

2.28 Relevant drawing enclosed ? yes

2.29 Quality assurance plan (QAP) enclosed ? yes

3.00 VOLTMETER

A. General
3.01 Manufacturer
3.01.1 name
3.01.2 country of manufacturer
3.02 Applicable standards IEC 60051, 61554

3.03 Type
3.04 Type test
3.04.1 carried out ? yes

3.04.2 date dd-mm-yy

3.04.3 testing laboratory


3.04.3.1 name
3.04.3.2 country
3.05 Dimensions
3.05.1 length mm

3.05.2 width mm

3.06 Weight kg

B. Construction Data
3.07 Suppression, if any yes/no

3.08 Selector switch provided ? yes/no

3.09 Instrument is flush mounting type ? yes

3.10 Pointer is knife edge type ? yes

3.11 Glass is anti glare ? yes

3.12 Class <1

TENDERER`s STAMP SIGNATURE

___________________________________________________________________________________________________________________
355102494.xls

Page 7 of 19
METERING DEVICES
Analogue Indicating Instruments

Sl. No. REQUIRED TENDERED

3.13 Scale
3.13.1 quadrant (900) yes

3.13.2 sector (600) no

3.13.3 circular (1800) no

3.13.4 linear (2400) no

3.14 Dimensions
3.14.1 length mm

3.14.2 width mm

3.15 Weight kg

3.16 Dial is snow white with black numerals ? yes

3.17 Dial is parallax free ? yes

3.18 Means of zero adjustment provided ? yes

C. Electrical Data
3.19 MV, if applicable
3.19.1 measuring range V

3.19.2 operating voltage Vac 110

3.20 LV, if applicable


3.20.1 measuring range V

3.20.2 operating voltage Vac 400

3.21 Overvoltage V 1.2 x rated voltage

3.22 Insulation resistance at 500V M > 20

3.23 Dielectric strength kVac, 1min. 2

3.24 Burden
3.24.1 current path VA N/A

3.24.2 voltage path VA <1.5

D. Other Performance Data


3.25 First commercial operation of offered ampere meter
3.25.1 date dd-mm-yy

TENDERER`s STAMP SIGNATURE

___________________________________________________________________________________________________________________
355102494.xls

Page 8 of 19
METERING DEVICES
Analogue Indicating Instruments

Sl. No. REQUIRED TENDERED

3.26 Reference list attached ? yes/no

E. Supporting Documents
3.27 Type test reports enclosed ? yes

3.28 List of minimum testing facilities enclosed ? yes

3.29 Technical literature enclosed ? yes

3.30 Relevant drawing enclosed ? yes

3.31 Quality assurance plan enclosed ? yes

4.00 WATTMETER

A. General
4.01 Manufacturer
4.01.1 name
4.01.2 country of manufacturer
4.02 Applicable standards IEC 60051, 61554

4.03 Type
4.04 Type test
4.04.1 carried out ? yes

4.04.2 date dd-mm-yy

4.04.3 testing laboratory


4.04.3.1 name
4.04.3.2 country

B. Construction Data
4.05 Suppression, if any yes/no

4.06 Selector switch provided ? yes

4.07 Instrument is flush mounting type ? yes

4.08 Pointer is knife edge type ? yes

4.09 Glass is anti glare ? yes

TENDERER`s STAMP SIGNATURE

___________________________________________________________________________________________________________________
355102494.xls

Page 9 of 19
METERING DEVICES
Analogue Indicating Instruments

Sl. No. REQUIRED TENDERED

4.10 Class <1

4.11 Scale
4.11.1 quadrant (900) no

4.11.2 sector (600) no

4.11.3 circular (1800) no

4.11.4 linear (2400) yes

4.12 Dimensions
4.12.1 length mm

4.12.2 width mm

4.13 Weight kg

4.14 Dial is snow white with black numerals ? yes

4.15 Dial is parallax free ? yes

4.16 Means of zero adjustment provided ? yes

C. Electrical Data
4.17 MV, if applicable
4.17.1 measuring range (IMPORT-left/EXPORT-right) MW

4.17.2 indication bi-directional

4.17.3 operating voltage Vac 110

4.17.4 operating current (CT secondary) A 1 or 5

4.18 LV, if applicable


4.18.1 measuring range (IMPORT) kW

4.18.2 indication unidirectional

4.18.3 operating voltage Vac 400

4.18.4 operating current (CT secondary) A 5

4.19 Continuous overcurrent A 1.2 x rated current

4.20 Overvoltage V 1.2 x rated voltage

4.21 Insulation resistance at 500V M > 20

4.22 Dielectric strength kVac, 1min. 2

4.23 Burden

TENDERER`s STAMP SIGNATURE

___________________________________________________________________________________________________________________
355102494.xls

Page 10 of 19
METERING DEVICES
Analogue Indicating Instruments

Sl. No. REQUIRED TENDERED

4.23.1 current path VA <5

4.23.2 voltage path VA <2.5

D. Other Performance Data


4.24 First commercial operation of offered ampere meter
4.24.1 date dd-mm-yy

4.25 Reference list attached ? yes/no

E. Supporting Documents
4.26 Type test reports enclosed ? yes

4.27 List of minimum testing facilities enclosed ? yes

4.28 Technical literature enclosed ? yes

4.29 Relevant drawing enclosed ? yes

4.30 Quality assurance plan (QAP) enclosed ? yes

5.00 VAR METER

A. General
5.01 Manufacturer
5.01.1 name
5.01.2 country of manufacturer
5.02 Applicable standards IEC 60051, 61554

5.03 Type
5.04 Type test
5.04.1 carried out ? yes

5.04.2 date dd-mm-yy

5.04.3 testing laboratory


5.04.3.1 name
5.04.3.2 country

B. Construction Data

TENDERER`s STAMP SIGNATURE

___________________________________________________________________________________________________________________
355102494.xls

Page 11 of 19
METERING DEVICES
Analogue Indicating Instruments

Sl. No. REQUIRED TENDERED

5.05 Suppression, if any yes/no

5.06 Instrument is flush mounting type ? yes

5.07 Pointer is knife edge type ? yes

5.08 Glass is anti glare ? yes

5.09 Class <1

5.10 Scale
5.10.1 quadrant (900) no

5.10.2 sector (600) no

5.10.3 circular (1800) no

5.10.4 linear (2400) yes

5.11 Dimensions
5.11.1 length mm

5.11.2 width mm

5.12 Weight kg

5.13 Dial is snow white with black numerals ? yes

5.14 Dial is parallax free ? yes

5.15 Means of zero adjustment provided ? yes

C. Electrical Data
5.16 MV, if applicable
5.16.1 measuring range (IMPORT-left/EXPORT-right) MVAr

5.16.2 indication bi-directional

5.16.3 operating voltage Vac 110

5.16.4 operating current (CT secondary) A 1 or 5

5.17 LV, if applicable


5.17.1 measuring range (IMPORT-left/EXPORT-right) kVAr

5.17.2 indication bi-directional

5.17.3 operating voltage Vac 400

5.17.4 operating current (CT secondary) A 5

5.18 Continuous overcurrent A 1.2 x rated current

TENDERER`s STAMP SIGNATURE

___________________________________________________________________________________________________________________
355102494.xls

Page 12 of 19
METERING DEVICES
Analogue Indicating Instruments

Sl. No. REQUIRED TENDERED

5.19 Overvoltage V 1.2 x rated voltage

5.20 Insulation resistance at 500V M > 20

5.21 Dielectric strength kVac, 1min. 2

5.22 Burden
5.22.1 current path VA <5

5.22.2 voltage path VA <2.5

D. Other Performance Data


5.23 First commercial operation of offered ampere meter
5.23.1 date dd-mm-yy

5.24 Reference list attached ? yes/no

E. Supporting Documents
5.25 Type test reports enclosed ? yes

5.26 List of minimum testing facilities enclosed ? yes

5.27 Technical literature enclosed ? yes

5.28 Relevant drawing enclosed ? yes

5.29 Quality assurance plan (QAP) enclosed ? yes

6.00 FREQUENCY METER

A. General
6.01 Manufacturer
6.01.1 name
6.01.2 country of manufacturer
6.02 Applicable standards IEC 60051, 61554

6.03 Type
6.04 Type test
6.04.1 carried out ? yes

6.04.2 date dd-mm-yy

TENDERER`s STAMP SIGNATURE

___________________________________________________________________________________________________________________
355102494.xls

Page 13 of 19
METERING DEVICES
Analogue Indicating Instruments

Sl. No. REQUIRED TENDERED

6.04.3 testing laboratory


6.04.3.1 name
6.04.3.2 country

B. Construction Data
6.05 Instrument is flush mounting type ? yes

6.06 Indication
6.06.1 pointer yes/no

6.06.2 vibration reed yes/no

6.07 Glass is anti glare yes

6.08 Scale linear

6.09 Dimensions
6.09.1 length mm

6.09.2 height mm

6.10 Weight kg

6.11 Dial is snow white with black scaling ? yes

C. Electrical Data
6.12 MV, if applicable
6.12.1 measuring range Hz 45 to 55

6.12.1.1 resolution Hz 0.5

6.12.2 operating voltage V 110

6.12.3 operating current (CT secondary) A 1 or 5

6.13 LV, if applicable


6.13.1 measuring range Hz 45 to 55

6.13.1.1 resolution Hz 0.5

6.13.2 operating voltage V 400

6.13.3 operating current (CT secondary) A 5

6.14 Continuous overcurrent A 1.2 x rated current

6.15 Overvoltage V 1.2 x rated voltage

TENDERER`s STAMP SIGNATURE

___________________________________________________________________________________________________________________
355102494.xls

Page 14 of 19
METERING DEVICES
Analogue Indicating Instruments

Sl. No. REQUIRED TENDERED

6.16 Insulation resistance at 500V M > 20

6.17 Dielectric strength kVac, 1min. 2

6.18 Burden VA <3

D. Other Performance Data


6.19 First commercial operation of offered ampere meter
6.19.1 date dd-mm-yy

6.20 Reference list attached ? yes/no

E. Supporting Documents
6.21 Type test reports enclosed ? yes

6.22 List of minimum testing facilities enclosed ? yes

6.23 Technical literature enclosed ? yes

6.24 Relevant drawing enclosed ? yes

6.25 Quality assurance plan (QAP) enclosed ? yes

7.00 POWER FACTOR METER

A. General
7.01 Manufacturer
7.01.1 name
7.01.2 country of manufacturer
7.02 Applicable standards IEC 60051, 61554

7.03 Type
7.04 Type test
7.04.1 carried out ? yes

7.04.2 date dd-mm-yy

7.04.3 testing laboratory


7.04.3.1 name
7.04.3.2 country

TENDERER`s STAMP SIGNATURE

___________________________________________________________________________________________________________________
355102494.xls

Page 15 of 19
METERING DEVICES
Analogue Indicating Instruments

Sl. No. REQUIRED TENDERED

B. Construction Data
7.05 Suppression, if any yes/no

7.06 Instrument is flush mounting type ? yes

7.07 Pointer is knife edge type ? yes

7.08 Glass is anti glare ? yes

7.09 Class <1

7.10 Scale
7.10.1 quadrant (900) no

7.10.2 sector (600) no

7.10.3 circular (1800) no

7.10.4 linear (2400) yes

7.11 Dimensions
7.11.1 length mm

7.11.2 width mm

7.12 Weight kg

7.13 Dial is snow white with black numerals ? yes

7.14 Dial is parallax free ? yes

7.15 Means of zero adjustment provided ? yes

C. Electrical Data
7.16 MV, if applicable
7.16.1 measuring range 0.1 lag -1-0.1 lead

7.16.2 operating voltage Vac 110

7.16.3 operating current (CT secondary) A 1 or 5

7.17 LV, if applicable


7.17.1 measuring range 0.1 lag -1-0.1 lead

7.17.2 operating voltage Vac 400

7.17.3 operating current (CT secondary) A 5

7.18 Continuous overcurrent A 1.2 x rated current

7.19 Overvoltage V 1.2 x rated voltage

TENDERER`s STAMP SIGNATURE

___________________________________________________________________________________________________________________
355102494.xls

Page 16 of 19
METERING DEVICES
Analogue Indicating Instruments

Sl. No. REQUIRED TENDERED

7.20 Insulation resistance at 500V M > 20

7.21 Dielectric strength kVac, 1min. 2

7.22 Burden VA <3

D. Other Performance Data


7.23 First commercial operation of offered ampere meter
7.23.1 date dd-mm-yy

7.24 Reference list attached ? yes/no

E. Supporting Documents
7.25 Type test reports enclosed ? yes

7.26 List of minimum testing facilities enclosed ? yes

7.27 Technical literature enclosed ? yes

7.28 Relevant drawing enclosed ? yes

7.29 Quality assurance plan (QAP) enclosed ? yes

8.00 RECORDER

A. General
8.01 Manufacturer
8.01.1 name
8.01.2 country of manufacturer
8.02 Applicable standards IEC 60051, 61554

8.03 Type
8.04 Type test
8.04.1 carried out ? yes

8.04.2 date dd-mm-yy

8.04.3 testing laboratory


8.04.3.1 name
8.04.3.2 country

TENDERER`s STAMP SIGNATURE

___________________________________________________________________________________________________________________
355102494.xls

Page 17 of 19
METERING DEVICES
Analogue Indicating Instruments

Sl. No. REQUIRED TENDERED

B. Construction Data
8.05 Instrument is flush mounting type ? yes

8.06 Class 0.1

8.07 Display
8.07.1 type LCD

8.07.2 number of digits No. 13

8.07.3 resolution
8.07.4 dimensions
8.07.4.1 length mm 80

8.07.4.2 width mm 20

8.07.5 digits
8.07.5.1 height mm 50

8.07.5.2 width mm 10

8.08 Number of channels No. 24

8.09 Self-diagnostic facilities provided yes

8.10 Meter is programmable yes

8.11 Recording colors 6 different

8.12 Dimensions
8.12.1 length mm

8.12.2 width mm

8.12.3 depth mm

8.13 Weight kg

C. Electrical Data
8.14 MV, if applicable
8.14.1 measuring range
8.14.2 indication
8.14.3 operating voltage Vac 110

8.14.4 operating current (CT secondary) A 1 or 5

8.14.5 auxiliary supply voltage Vac 230

TENDERER`s STAMP SIGNATURE

___________________________________________________________________________________________________________________
355102494.xls

Page 18 of 19
METERING DEVICES
Analogue Indicating Instruments

Sl. No. REQUIRED TENDERED

8.15 LV, if applicable


8.15.1 measuring range
8.15.2 indication
8.15.3 operating voltage Vac 400

8.15.4 operating current (CT secondary) A 5

8.15.5 auxiliary supply voltage Vac 230

8.16 Continuous overcurrent A 1.2 x rated current

8.17 Overvoltage V 1.2 x rated voltage

8.18 Insulation resistance at 500V M > 20

8.19 Dielectric strength kVac, 1min. 2

8.20 Input current mAdc 4 to 20

D. Other Performance Data


8.21 First commercial operation of offered ampere meter
8.21.1 date dd-mm-yy

8.22 Reference list attached ? yes/no

E. Supporting Documents
8.23 Type test reports enclosed ? yes

8.24 List of minimum testing facilities enclosed ? yes

8.25 Technical literature enclosed ? yes

8.26 Relevant drawing enclosed ? yes

8.27 Quality assurance plan (QAP) enclosed ? yes

TENDERER`s STAMP SIGNATURE

___________________________________________________________________________________________________________________
355102494.xls

Page 19 of 19
METERING DEVICES
Analogue Indicating Instruments

Sl. No. REQUIRED TENDERED

TENDERER`s STAMP SIGNATURE