You are on page 1of 142

BALLOREX venturi

4.1 Introduction

4.1.1 Balancing of heating and cooling systems


BROEN BALLOREX Venturi is a range of manual balancing valves used in water-based heating and cooling systems
to ensure an evenly distributed flow in individual risers and terminal units. Applications are typically central, district
heating or cooling systems as well as fan coil units in multi-storey and high-rise buildings.

The BROEN BALLOREX Venturi valve is compact having flow measuring, regulation and isolation functions all in one
unit. The range consists of valves in sizes DN 15-50, manufactured in dezincification resistant brass (DR), to valves in sizes
DN 65-600, manufactured in steel.

The clever design enables the BROEN BALLOREX Venturi to have consistent measuring accuracy within +/- 3%, which
makes the BROEN BALLOREX Venturi more accurate compared to other commissioning valves in the market.

The BROEN BALLOREX Venturi has an accuracy within +/- 3%.


Other commissioning valves have an accuracy within +/- 15% down to
+/- 5% depending on the setting of the valve.
Typical VODRV valve accuracy

BALLOREX Venturi accuracy

Typical VODRV valve accuracy

Because of the higher accuracy and low loss characteristics, the BROEN BALLOREX Venturi is more efficient and provides
reduced energy consumption when heating and cooling systems are balanced.

4.1.2 BALLOREX Venturi benefits


Extensive product range from DN 15-600
Constant measuring accuracy better than +/- 3%
Measuring system insensitive to system debris
One constant Kv-value indicated on handle
Simultaneous measuring and regulation
Setting fast and easy using an Allen key
Digital setting scale precise and easy to read
No change in setting when isolated and reopened
Isolation simply done using the -turn handle
Easy identification of open or isolated position
Free dimensioning software at www.venturivalves.com
No need for 3-5 DN straight piping when installed
Installation directly onto bends, reducers and flexible hoses
Installation can be done in all needed positions
Prefabricated insulation is fast and easy to apply
Insulation is possible before doing commissioning

4.1
BALLOREX Venturi
4.2 Flow measuring
4.2.1 Direct flow measurement
A unique feature of BROEN BALLOREX Venturi is the integrated Venturi measuring orifice which allows direct flow
measurement at any time. With direct flow measurement, actual flow rates can be measured for precise balancing and
correct documentation.

Trouble shooting becomes considerably easier saving time. Just connect a flow meter, enter the fixed
Kv-value of the integrated Venturi orifice, and the flow will be directly displayed on the flowmeter at an accuracy of +/- 3%.

4.2
BALLOREX venturi
4.2 Flow measuring

4.2.2 Venturi principle


The integrated Venturi enables direct flow measuring. Direct flow measurement allows precise valve setting and easy
trouble shooting.

The Venturi exploits Bernoullis Principle:


A fluid speeds up as it moves through a constricted space. As the speed of the fluid increases, its pressure drops.

In the Venturi the pressure drop across the orifice is measured


where the pressure is at its highest and lowest, respectively. The
trumpet shape of the Venturi recovers a substantial part of the
pressure, which provides a strong measuring signal at a low total
pressure drop.

Low speed - High pressure High speed - Low pressure

Direct flow measurement is not affected by the changing of the valve setting since the Kv-value between the measuring
points remains constant. The Kv-value is changed elsewhere in the valve to regulate the flow.

P - Venturi P - valve
Measured signal across Total pressure drop across the open valve.
Venturi orifice. Part of the pressure is recovered by the
Strong signal gives high Venturi.
accuracy measurement.

Flow equation

Q = Kv * p

Q: The flow [m3/h] to be calculated.

Kv: The Venturi coefficient which defines the flow capacity through the Venturi. It is determined by the smallest diameter in
the Venturi and remains constant during the setting of the flow.

P: Differential pressure measured across the Venturi orifice.

On a flow meter the Venturis Kv-value is entered once, and the flow will be displayed directly on the flow meter. If the valve
setting is changed, the new flow will be displayed directly since the Kv-value across the measuring points remains constant
and only the differential pressure changes.

4.2
BALLOREX Venturi
4.3 Product properties
4.3.1 Design
The regulation of the BALLOREX Venturi is done by setting the spindle that operates independently of the shut off
function. In that way the valve setting is kept intact when the valve is isolated and re-opened.

The differential pressure is measured across the Venturi orifice where the Kv-value is constant and not affected when the
setting is changed. Compared to variable orifice double regulating valves it means that on the BALLOREX Venturi valves,
you only have to enter the Kv-value once into the flowmeter. On the VODRVs the Kv-value is changed every time the
setting is adjusted. The new setting is read from the handle scale and entered into the flowmeter every time a new flow has
to be measured.

A) Venturi measuring orifice

B) Ball for isolation

C) Regulation needle

D) Handle to shut off valve

E) Operation of regulation needle

F) Test points for flow meter connection

A B C

4.3
BALLOREX venturi
4.3 Product properties
4.3.2 Sizing & selection
Selecting the right valve dimension is simple when using BALLOREX Venturi.

Once the design flow has been calculated, a valve with a flow range that fits the required design flow rate is selected.
Also keep in mind to select a valve that can provide the required total pressure loss.

Example
Heating system for a room of 37 m x 14 m

Heat loss: 40 W/m2


Supply side temperature: 80C
Return side temperature: 60C

Calculation of flow rate:


Q: Design flow m3/h
: Heat loss [kW] (room)
ts: Media temperature, supply side
tr: Media temperature, return side

Q = x 0,861* / t (ts- tr)


*Factor for converting kW to kcal/h

Q = (0,04 x (37 x 14)) x 0,86 / (80-60)


Q = 0,890 m3/h | 0,247 l/s | 890 l/h

Bar kPa Pressure drop across valve


1 100

0
n 0.
0,7 70 itio
Pos
0,6 60
Measuring signal
0,5 50
n 1.0 n 2.0 n 3.0 n 4.0
itio itio itio itio .0
0,4 40 Pos Pos Pos Pos itio
n5
Pos
0,3 30 .0
n6
itio
Pos .0
n7
itio
0,2 20 Pos n 8.0
itio
Pos ion 9.9
it
Pos

0,1 10

0,07 7
0,06 6
0,05 5

0,04 4

0,03 3 Flow rate


0,075 0,09 0,1 0,2 0,3 0,325 l/s

270 324 360 720 1080 1170 l/h

0,247 l/s
Example
A BALLOREX Venturi DN 20S has a flow rate of 0,247 l/s and a setting on the handle scale of 7.0.
The pressure drop across the complete valve (14 kPa) is read on the Y-axis intersection between the curve for setting
7.0 and flow rate 0,247 l/s.
The red curve is the Venturi measuring signal which indicates what differential pressure should be measured across the
Venturi orifice for a given flow.
The Venturi signal in the example given corresponding to 0,247 l/s, is found via the red curve ( 33 kPa).

4.3
BALLOREX Venturi
4.3 Product properties
4.3.3 Installation

The BALLOREX Venturi valves are easily installed.


No upstream or downstream straight pipe lengths
are required, so bends, reducers, flexible hoses, etc.
can be mounted directly on the valve.


Due to its clever design BALLOREX Venturi can
be oriented in all positions 360 around the pipe
axis, without debris corrupting the flow
measurements.

4.3
BALLOREX venturi
4.3 Product properties
4.3.4 Valve setting
The setting of the valve is easily done with an Allen key.

Connect the flow meter to the valve and select Venturi type/enter the Venturi Kv-value, that is printed on the valve
handle. Turn the pre-setting tool until the flow meter displays the required flow rate.

Compared to variable orifice double regulating valves it means that on the BALLOREX Venturi valves, you only have to
enter the Kv-value once into the flowmeter.

Kv-values vs. pre-setting values


BALLOREX Venturi DN 15 - 50 5.0 6.0 7.0 8.0 9.0 9.9 Specific valve settings

0,1 0,2 0,3 0,4 0,5 0,6 0,7 0,8 0,9 1,0 2,0 3,0 4,0 5,0 6,0 7,0 8,0 9,0 10 20 30

DN 50 0.0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 9.9

DN 40 0.0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 9.9

DN 32 0.0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 9.9
0.0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 9.9
DN 25
0.0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.9

0.0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 9.9
DN 20 0.0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 9.9
1.0 2.0 3.0 4.0 5.0 6 9.9

1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 9.9
DN 15 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 9.9
3.0 4.0 5.0 6.0 7.0 9.9

0,1 0,2 0,3 0,4 0,5 0,6 0,7 0,8 0,9 1,0 2,0 3,0 4,0 5,0 6,0 7,0 8,0 9,0 10 20 30
Kv-value
0,34

Example 1:
A customer needs a valve which can deliver a Kv-Value of 2.0.
The diagram shown above indicates that this is provided by; DN 15H, DN 20S, DN 20H and even DN 25S. DN 25H would
be too close to fully closed when providing Kv 2.0, and the risk is that the right flow rate cannot be reached.

Example 2:
A customer has a Venturi DN 15L installed and set for 5.0.
He would like to know the Kv-Value at the given setting. The table indicates an approximate Kv-value of 0,34 m3/h.

You will find the above diagram together with other examples in the appendix at the end of this chapter (section 4.12).

4.3
BALLOREX Venturi
4.3 Product properties
4.3.5 Commissioning
For commissioning BALLOREX Venturi it is recommendeded to use the proportional method.

The proportional method has significant advantages in terms of trouble shooting, since only approx. 10% of the time
required to commission an installation is actually used working with the balancing valves.
In practice approx. 90% of the time is spent on trouble shooting to find out what is wrong elsewhere in the installation.

For more detailed information about the commissioning procedure, see chapter 3.

4.3
BALLOREX venturi
4.4 Product data sheets - FODRV female
4.4.1 Product finder

DN 50H

DN 40H

DN 25H / DN 32H

DN 20H / DN 25S

DN 15H / DN 20S

DN 15S / DN 20L

DN 15L

DN 15UL

0.005 0.007 0.009 0.01 0.02 0.03 0.04 0.06 0.08 0.1 0.2 0.3 0.4 0.5 0.6 0.8 1.0 2.0 3.0 4.0 l/s
36 72 108 144 216 288 360 720 1,080 1,440 1,800 2,160 2,880 3,600 7,200 10,800 14,400 l/h

Flow rate

Flow range Dimension Section


l/s l/h
0.0076 - 0.035 27 - 126 DN 15UL 4.4.2
0.0172 - 0.074 62 - 266 DN 15L 4.4.2
DN 15S 4.4.2
0.036 - 0.148 130 - 530
DN 20L 4.4.3
DN 15H 4.4.2
0.074 - 0.325 267 - 1,170
DN 20S 4.4.3
DN 20H 4.4.3
0.142 - 0.60 511 - 2,170
DN 25S 4.4.4
DN 25H 4.4.4
0.29 - 1.25 1,044 - 4,500
DN 32H 4.4.5
0.44 - 1.88 1,584 - 6,760 DN 40H 4.4.6
0.82 - 3.51 2,952 - 12,630 DN 50H 4.4.7

4.4
4.4 Data sheet

BALLOREX Venturi

4.4.2 DN 15 female/female

94mm Specifications
Max. temperature 120C
Min. temperature -20C
Max. pressure 25 bar
76mm Press ends 16 bar
Marking on valve (Handle) DN, flow-version, Kvm (Kv-measuring)
(Valve body) DN, PN, flow direction, BROEN
Connection Female thread ISO 7/1 parallel
75mm Valve housing DR Brass CW602N CuZn36Pb2As
140mm Ball & needle DR Brass CW602N (chrome plated)
Valve handle Polyamide (PA6.6 30%GF)
Sealings O-rings EPDM
Gaskets PTFE
Test point sealing EPDM

Nom. Flow range


BROEN No. Dimension
Inch l/s l/h

4350000U-001003 DN 15UL 1/2 0.0076 - 0.035 27 - 126

4350000L-001003 DN 15L 1/2 0.0172 - 0.074 62 - 266

4350000S-001003 DN 15S 1/2 0.036 - 0.148 130 - 530

4350000H-001003 DN 15H 1/2 0.074 - 0.325 267 - 1,170

Accessories
BROEN No. Dimension Description

83504006-000003 15 mm x 1/2
Pre-sealed press adaptors (2 pcs), max 16 bar
83504007-000003 18 mm x 1/2

96M0240-000005 DN 15 BALLOREX Venturi - Insulation jacket

High capacity drain valve (Kv 4,5)


43500200-001003 DN 15
1/2 female/female threaded connection

4.4
BALLOREX Venturi

DN 15UL - Ultra low flow


Bar kPa Pressure drop across valve
1 100

0.7 70
0.6 60
Measuring signal
0.5 50

0.4 40

0.3 30

0.2 20 1.0
on
siti
Po

0.1 10
.9
0.08 8 n9
sitio
0.07 7 7.0 Po
2.0 3.0 4.0
n
sitio
on on on 6.0 Po
0.06 6 siti siti siti ion
Po Po Po io n5
.0 Posit
0.05 5 Posit

0.04 4

0.03 3

0.02 2

0.01 1
Flow rate
0.005 0.006 0.007 0.008 0.009 0.01 0.02 0.03 0.035 l/s

18.0 21.6 25.2 28.8 32.4 36.0 72.0 108.0 126.0 l/h

The X-axis indicates the recommended flow range of the valve.

The black curves are used to determine the total pressure drop across the valve at a specific handle scale setting and a
given flow rate.

The red curve is the Venturi measuring signal which indicates what differential pressure should be measured across the
Venturi orifice for a given flow.

4.4
Flow Diagram

BALLOREX Venturi

DN 15L - Low flow


Bar kPa Pressure drop across valve
1 100

0.7 70
.0
n1
0.6 60
sitio Measuring signal
0.5 50 Po

0.4 40

0.3 30

0.2 20
2.0 3.0 4.0 5.0 6.0 7.0 .9
tion tion tion tion tion ition ion 9
Posi Posi Posi Posi Posi s
Po Pos t
i

0.1 10

0.08 8
0.07 7
0.06 6
0.05 5

0.04 4

0.03 3

0.02 2

0.01 1 Flow rate


0.01 0.02 0.03 0.04 0.05 0.06 0.074 l/s

36 72 108 144 180 216 266.4 l/h

The X-axis indicates the recommended flow range of the valve.

The black curves are used to determine the total pressure drop across the valve at a specific handle scale setting and a
given flow rate.

The red curve is the Venturi measuring signal which indicates what differential pressure should be measured across the
Venturi orifice for a given flow.

4.4
Flow Diagram

BALLOREX Venturi

DN 15S - Standard flow


Bar kPa Presssure drop across valve
1 100

0.7 70
0.6 60
0.5 50 Measuring signal
0.0 ion2.0 3.0 4.0
sitio
n
osit ion ion
0.4 40 po P Posit Posit
6.0
0.3 30 ition
Pos
7.0
0.2 20 ition
Pos
8.0
ition
Pos
9.9
0.1 10 ition
Pos
0.08 8
0.07 7
0.06 6
0.05 5
0.04 4

0.03 3 Flow rate


0.036 0.04 0.05 0.06 0.07 0.08 0.09 0.1 0.148 l/s

129.6 144 180 216 252 288 324 360 532.8 l/h

The X-axis indicates the recommended flow range of the valve.

The black curves are used to determine the total pressure drop across the valve at a specific handle scale setting and a given
flow rate.

The red curve is the Venturi measuring signal which indicates what differential pressure should be measured across the
Venturi orifice for a given flow.

4.4
Flow Diagram

BALLOREX Venturi

DN 15H - High flow


Bar kPa Pressure drop across valve

1 100

0.7 70
0.6 60
Measuring signal
0.5 50
n 0.0 n 2.0 n 3.0 n 4.0 n 5.0 n 6.0
itio itio itio itio itio itio
0.4 40 Pos Pos Pos Pos Pos Pos .0
n8
itio
Pos
0.3 30 .0
n9
itio
Pos .9
n9
itio
Pos
0.2 20

0.1 10

0.08 8
0.07 7
0.06 6
0.05 5

0.04 4

0.03 3 Flow rate


0.074 0.08 0.09 0.1 0.2 0.3 0.325 l/s

266 288 324 360 720 1080 1170 l/h

The X-axis indicates the recommended flow range of the valve.

The black curves are used to determine the total pressure drop across the valve at a specific handle scale setting and a given
flow rate.

The red curve is the Venturi measuring signal which indicates what differential pressure should be measured across the
Venturi orifice for a given flow.

4.4
Flow Diagram

4.4
4.4 Data sheet

BALLOREX Venturi

4.4.3 DN 20 female/female

100mm Specifications
Max. temperature 120C
Min. temperature -20C
Max. pressure 25 bar
79mm Press ends 16 bar
Marking on valve (Handle) DN, flow-version, Kvm (Kv-measuring)
(Valve body) DN, PN, flow direction, BROEN
Connection Female thread ISO 7/1 parallel
Valve housing DR Brass CW602N CuZn36Pb2As
75mm
Ball & needle DR Brass CW602N (chrome plated)
144mm
Valve handle Polyamide (PA6.6 30%GF)
Sealings O-rings EPDM
Gaskets PTFE
Test point sealing EPDM

Nom. Flow range


BROEN No. Dimension
Inch l/s l/h

4450000L-001003 DN 20L 3/4 0.036 - 0.148 130 - 530

4450000S-001003 DN 20S 3/4 0.074 - 0.325 267 - 1,170

4450000H-001003 DN 20H 3/4 0.142 - 0.603 511 -2,170

Accessories
BROEN No. Dimension Description
84504006-000003 15 mm x 3/4
84504007-000003 18 mm x 3/4 Pre-sealed press adaptors (2 pcs), max. 16 bar
84504008-000003 22 mm x 3/4

96M0241-000005 DN 20 BALLOREX Venturi - Insulation jacket

High capacity drain valve (Kv 4,5)


44500200-001003 DN 20
1/2 female/female threaded connection

4.4
Flow Diagram

BALLOREX Venturi

DN 20L - Low flow


Bar kPa Pressure drop across valve

1 100

0.7 70
0.6 60
0.5 50 Measuring signal
itio n 1.0 ition 2.0 ition 3.0
0.4 40 Pos Pos Pos
4.0
ition
0.3 30 Pos
5.0
ition
Pos
6.0
ition
0.2 20
Pos 7 .0
ition
Pos 9 .9
itio n
Pos
0.1 10

0.08 8
0.07 7
0.06 6
0.05 5

0.04 4

0.03 3 Flow rate


0.036 0.04 0.05 0.06 0.07 0.08 0.09 0.1 0.148 l/s

130 144 180 216 252 288 324 360 530 l/h

The X-axis indicates the recommended flow range of the valve.

The black curves are used to determine the total pressure drop across the valve at a specific handle scale setting and a
given flow rate.

The red curve is the Venturi measuring signal which indicates what differential pressure should be measured across the
Venturi orifice for a given flow.

See example on data sheet 4.4.3 for DN 20S.

4.4
Flow Diagram

BALLOREX Venturi

DN 20S - Standard flow


Bar kPa Pressure drop across valve
1 100

0
n 0.
itio
0.7 70 Pos
0.6 60
Measuring signal
0.5 50
1 .0 .0 3 .0 4.0
tion n2 tion tion
Pos
i itio Pos
i
Pos
i n5
.0
0.4 40 Pos itio
Pos
0.3 30 .0
n6
itio
Pos . 0
n7
itio
0.2 20 Pos n 8.0
itio
Pos ion 9.9
s it
Po

0.1 10

0.07 7
0.06 6
0.05 5

0.04 4

0.03 3 Flow rate


0.075 0.09 0.1 0.2 0.3 0.325 l/s

270 324 360 720 0.247 1,080 1,170 l/h

The X-axis indicates the recommended flow range of the valve.

The black curves are used to determine the total pressure drop across the valve at a specific handle scale setting and a
given flow rate.

The red curve is the Venturi measuring signal which indicates what differential pressure should be measured across the
Venturi orifice for a given flow.

Example

A BALLOREX Venturi DN 20S has a flow rate of 0,247 l/s and a setting on the handle scale of 7.0.
The pressure drop across the complete valve (14 kPa) is read on the Y-axis intersection between the curve for setting
7.0 and flow rate 0,247 l/s.

The Venturi signal that corresponds to 0,247 l/s is found via the red curve ( 33 kPa).

4.4
Flow Diagram

BALLOREX Venturi

DN 20H - High flow


Bar kPa Pressure drop across valve
1 100

0.7 70
0.6 60
Measuring signal
0.5 50
.0 1.0 2.0 n3.0 4.0 .0
n0 tion tion tion n5
sitio Pos
i
Pos
i sitio i sitio 6.0
0.4 40 Po Po Pos Po itio
n
Pos
0
0.3 30 n 7.
itio
Pos
0
n 8.
itio
0.2 20 Pos
0
n 9.
itio
Pos . 9
n9
itio
Pos
0.1 10

0.07 7
0.06 6
0.05 5

0.04 4

0.03 3 Flow rate


0.142 0.2 0.3 0.4 0.5 0.603 l/s

511.2 720 1,080 1,440 1,800 2,170 l/h

The X-axis indicates the recommended flow range of the valve.

The black curves are used to determine the total pressure drop across the valve at a specific handle scale setting and a
given flow rate.

The red curve is the Venturi measuring signal which indicates what differential pressure should be measured across the
Venturi orifice for a given flow.

See example on data sheet 4.4.3 for DN 20S.

4.4
4.4 Data sheet

BALLOREX Venturi

4.4.4 DN 25 female/female

112mm Specifications
Max. temperature 120C
Min. temperature -20C
Max. pressure 25 bar
83mm Press ends 16 bar
Marking on valve (Handle) DN, flow-version, Kvm (Kv-measuring)
(Valve body) DN, PN, flow direction, BROEN
Connection Female thread ISO 7/1 parallel
75mm
Valve housing DR Brass CW602N CuZn36Pb2As
150mm
Ball & needle DR Brass CW602N (chrome plated)
Valve handle Polyamide (PA6.6 30%GF)
Sealings O-rings EPDM
Gaskets PTFE
Test point sealing EPDM

Nom. Flow range


BROEN No. Dimension
Inch l/s l/h

4550000S-001003 DN 25S 1 0.142 - 0.603 511 - 2,170

4550000H-001003 DN 25H 1 0.29 - 1.25 1,044 - 4,500

Accessories
BROEN No. Dimension Description

96M0242-000005 DN 25 BALLOREX Venturi - Insulation jacket

High capacity drain valve (Kv 4.5)


45500200-001003 DN 25
1/2 female/female threaded connection

4.4
Flow Diagram

BALLOREX Venturi

DN 25S - Standard flow


Bar kPa Pressure drop across valve

1 100

0.7 70
0.6 60
0.5 50 Measuring signal
n0 .0 n 1.0 n2.0 n3 .0 .0
0.4 40
Positio Po sitio Po sitio Po sitio ition 4
Pos
0.3 30
5.0
ition
Pos
0.2 20 6.0
ition
Pos
7.0
ition
Pos .0
8
0.1 10 ition
Pos .9
9
tion
0.07 7 Posi

0.05 5
0.04 4

0.03 3 Flow rate


0.14 0.2 0.3 0.4 0.5 0.603 l/s

504 720 1,080 1,440 1,800 2,170 l/h

DN 25H - High flow


Bar kPa Pressure drop across valve
1 100

0.7 70
0.6 60
0 0 0
n 0. n 1. n 2. n 3.
0
n 4.
0
n 5.
0 Measuring signal
0.5 50 itio itio itio itio itio itio
Pos Pos Pos Pos Pos Pos .0
iti on 6
0.4 40 Pos
0
n 7.
0.3 30 itio
Pos
0
n 8.
0.2 20 itio
Pos
0
n 9.
itio
Pos ion 9.9
it
Pos
0.1 10

0.07 7
0.06 6

0.05 5
0.04 4

0.03 3 Flow rate


0.29 0.4 0.5 0.6 0.7 0.8 0.9 1 1.25 l/s

1,044 1,440 1,800 2,160 2,520 2,880 3,240 3,600 4,500 l/h

The X-axis indicates the recommended flow range of the valve.

The black curves are used to determine the total pressure drop across the valve at a specific handle scale setting
and a given flow rate.

The red curve is the Venturi measuring signal which indicates what differential pressure should be measured
across the Venturi orifice for a given flow.

See example on data sheet 4.4.3 for DN 20S.

4.4
BALLOREX Venturi

4.4.5 DN 32 female/female

130mm
Specifications
Max. temperature 120C
Min. temperature -20C
Max. pressure 25 bar
109mm Press ends 16 bar
Marking on valve (Handle) DN, flow-version, Kvm (Kv-measuring)
(Valve body) DN, PN, flow direction, BROEN
Connection Female thread ISO 7/1 parallel
122mm Valve housing DR Brass CW602N CuZn36Pb2As
208mm Ball & needle DR Brass CW602N (chrome plated)
Valve handle Polyamide (PA6.6 30%GF)
Sealings O-rings EPDM
Gaskets PTFE
Test point sealing EPDM

Nom. Flow range


BROEN No. Dimension
Inch l/s l/h

4650000H-001003 DN 32H 1 1/4 0.29 - 1.25 1,044 - 4,500

Accessories
BROEN No. Dimension Description

96M0243-000005 DN 32 BALLOREX Venturi - Insulation jacket

4.4
Flow Diagram

BALLOREX Venturi

DN 32H - High Flow


Bar kPa Pressure drop across valve

1 100

0.7 70
0.6 60
Measuring signal
0.5 50

0.4 40 0 0 0 0
n 0.
0 n 1. n 2.
0 n 3. n 4. n 5. 0
itio Pos
itio itio itio itio
Pos
itio n 6.
Pos Pos Pos Pos itio
0.3 30 Pos
0
n 7.
itio
0.2 20 Pos
0
n 8.
itio
Pos 0
n 9.
itio
Pos n 9.9
itio
0.1 10 Pos

0.07 7
0.06 6
0.05 5

0.04 4

0.03 3 Flow rate


0.290 0.4 0.5 0.6 0.7 0.8 0.9 1 1.25 l/s

1,044 1,440 1,800 2,160 2,520 2,880 3,240 3,600 4,500 l/h

The X-axis indicates the recommended flow range of the valve.

The black curves are used to determine the total pressure drop across the valve at a specific handle scale setting
and a given flow rate.

The red curve is the Venturi measuring signal which indicates what differential pressure should be measured
across the Venturi orifice for a given flow.

4.4
BALLOREX Venturi

4.4.6 DN 40 female/female

140mm
Specifications
Max. temperature 120C
Min. temperature -20C
Max. pressure 25 bar
113mm Press ends 16 bar
Marking on valve (Handle) DN, flow-version, Kvm (Kv-measuring)
(Valve body) DN, PN, flow direction, BROEN
Connection Female thread ISO 7/1 parallel
122mm Valve housing DR Brass CW602N CuZn36Pb2As
213mm Ball & needle DR Brass CW602N (chrome plated)
Valve handle Polyamide (PA6.6 30%GF)
Sealings O-rings EPDM
Gaskets PTFE
Test point sealing EPDM

Nom. Flow range


BROEN No. Dimension
Inch l/s l/h

4750000H-001003 DN 40H 1 1/2 0.44 - 1.88 1,584 - 6,760

Accessories
BROEN No. Dimension Description

96M0244-000005 DN 40 BALLOREX Venturi - Insulation jacket

4.4
Flow Diagram

BALLOREX Venturi

DN 40H - High flow


Bar kPa
Pressure drop across valve
1 100

0.7 70
0.6 60
Measuring signal
0.5 50
n0 .0 1.0 2. 0 .0 4.0
ition n3 ition
0.4 40 sitio Pos ition sitio Pos 5.0
Po Pos Po
ition
Pos
0.3 30
6.0
ition
Pos
0.2 20 7.0
ition
Pos
8.0
ition
Pos
9.0
ition
0.1 10 Pos 9.9
ition
Pos
0.07 7
0.06 6
0.05 5

0.04 4

0.03 3 Flow rate


0.44 0.5 0.6 0.7 0.8 0.9 1 1.88 l/s

1,584 1,800 2,160 2,520 2,880 3,240 3,600 6,768 l/h

The X-axis indicates the recommended flow range of the valve.

The black curves are used to determine the total pressure drop across the valve at a specific handle scale setting
and a given flow rate.

The red curve is the Venturi measuring signal which indicates what differential pressure should be measured
across the Venturi orifice for a given flow.

See example on data sheet 4.4.3 for DN 20S.

4.4
BALLOREX Venturi

4.4.7 DN 50 female/female

156mm
Specifications
Max. temperature 120C
Min. temperature -20C
Max. pressure 25 bar
120mm Press ends 16 bar
Marking on valve (Handle) DN, flow-version, Kvm (Kv-measuring)
(Valve body) DN, PN, flow direction, BROEN
Connection Female thread ISO 7/1 parallel
122mm Valve housing DR Brass CW602N CuZn36Pb2As
221mm Ball & needle DR Brass CW602N (chrome plated)
Valve handle Polyamide (PA6.6 30%GF)
Sealings O-rings EPDM
Gaskets PTFE
Test point sealing EPDM

Nom. Flow range


BROEN No. Dimension
Inch l/s l/h

4850000H-001003 DN 50H 2 0.82 - 3.51 2,952 - 12,630

Accessories
BROEN No. Dimension Description

96M0245-000005 DN 50 BALLOREX Venturi - Insulation jacket

4.4
Flow Diagram

BALLOREX Venturi

DN 50H - High flow


Bar kPa Pressure drop across valve
1 100

0.7 70
0.6 60
Measuring signal
0.5 50
0.4 40
0.0 1.0 2.0 3.0 4.0 5.0 6.0
ition ition ition ition ition ition ition
Pos Pos Pos Pos Pos Pos Pos
0.3 30
7.0
ition
Pos
8.0
0.2 20
ition
Pos
9.0
ition
Pos
9.9
ition
Pos
0.1 10

0.07 7
0.06 6
0.05 5

0.04 4

0.03 3 Flow rate


0.82 0.9 1 2 3 3.51 l/s

2,952 3,240 3,600 7,200 10,800 12,636 l/h

The X-axis indicates the recommended flow range of the valve.

The black curves are used to determine the total pressure drop across the valve at a specific handle scale setting
and a given flow rate.

The red curve is the Venturi measuring signal which indicates what differential pressure should be measured
across the Venturi orifice for a given flow.

See example on data sheet 4.4.3 for DN 20S.

4.4
BALLOREX Venturi

4.5
BALLOREX venturi
4.5 Product data sheets - FODRV compression
4.5.1 Product finder

DN 50H

DN 40H

DN 25H / DN 32H

DN 20H / DN 25S

DN 15H / DN 20S

DN 15S / DN 20L

DN 15L

DN 15UL

0.005 0.007 0.009 0.01 0.02 0.03 0.04 0.06 0.08 0.1 0.2 0.3 0.4 0.5 0.6 0.8 1.0 2.0 3.0 4.0 l/s
36 72 108 144 216 288 360 720 1,080 1,440 1,800 2,160 2,880 3,600 7,200 10,800 14,400 l/h

Flow rate

Flow range Dimension Section


l/s l/h
0.0076 - 0.035 27 - 126 DN 15LU 4.4.2
0.0172 - 0.074 62 - 266 DN 15L 4.4.2
DN 15S 4.4.2
0.036 - 0.148 130 - 530
DN 20L 4.4.3
DN 15H 4.4.2
0.074 - 0.325 267 - 1,170
DN 20S 4.4.3
DN 20H 4.4.3
0.142 - 0.60 511 - 2170
DN 25S 4.4.4
DN 25H 4.4.4
0.29 - 1.25 1,044 - 4,500
DN 32H 4.4.5
0.44 - 1.88 1,584 - 6,760 DN 40H 4.4.6
0.82 - 3.51 2,952 - 12,630 DN 50H 4.4.7

4.5
BALLOREX Venturi

4.5.2 DN 15 compression/compression

99mm
Specifications
Max. temperature 120C
Min. temperature -20C
76mm Max. pressure 5 bar
Marking on valve (Handle) DN, flow-version, Kvm (Kv-measuring)
(Valve body) DN, PN, flow direction, BROEN
Connection Compression EN 1254-2
75mm Valve housing DR Brass CW602N CuZn36Pb2As
164mm Ball & needle DR Brass CW602N (chrome plated)
Valve handle Polyamide (PA6.6 30%GF)
Sealings O-rings EPDM
Gaskets PTFE
Test point sealing EPDM

Compression connections are not recommendeded for cooling applications.


Instead press or threaded connection are recommended.

Nom. Flow range


BROEN No. Dimension
Inch l/s l/h

435010UL-001063 DN 15UL 15 mm 0.0076 - 0.05 27 - 126

4350100L-001063 DN 15L 15 mm 0.0172 - 0.074 62 - 266

4350100S-001063 DN 15S 15 mm 0.036 - 0.148 130 - 530

4350100H-001063 DN 15H 15 mm 0.074 - 0.325 267 - 1,170

Accessories
BROEN No. Dimension Description

96M0240-000005 DN 15 BALLOREX Venturi - Insulation jacket

4.5
Flow Diagram

BALLOREX Venturi

DN 15UL - Ultra low flow


Bar kPa
1 100
Pressure drop across valve

0.7 70
0.6 60
0.5 50 Measuring signal
0.4 40

0.3 30

0.2 20
1.0
on
siti
Po

0.1 10

0.08 8
.9
0.07 7 n9
itio
7.0 Pos
0.06 6 2.0 3.0 4.0 sition
on on on 6.0 Po
0.05 5 siti siti siti ion
Po Po Po n 5.0 Posit
sitio
Po
0.04 4

0.03 3

0.02 2

0.01 1

Flow rate
0.005 0.006 0.007 0.008 0.009 0.01 0.02 0.03 0.035 l/s

The X-axis indicates the recommended flow range of the valve.

The black curves are used to determine the total pressure drop across the valve at a specific handle scale setting, and a
given flow rate.

The red curve is the Venturi measuring signal, which indicates what differential pressure should be measured across the
Venturi orifice for a given flow.

See example on data sheet 4.4.3. for DN 20S.

4.5
Flow Diagram

BALLOREX Venturi

DN 15L - Low flow


Bar kPa Pressure drop across valve
1 100

0.7 70 .0
n1
0.6 60
sitio Measuring signal
0.5 50
Po

0.4 40

0.3 30

0.2 20
2.0 3.0 4.0 5.0 6.0 7.0 .9
tion tion tion tion tion ition ion 9
Posi Posi Posi Posi Posi s
Po Pos t
i

0.1 10

0.08 8
0.07 7
0.06 6
0.05 5

0.04 4

0.03 3

0.02 2

0.01 1 Flow rate


0.01 0.02 0.03 0.04 0.05 0.06 0.074 l/s

36 72 108 144 180 216 267 l/h

The X-axis indicates the recommended flow range of the valve.

The black curves are used to determine the total pressure drop across the valve at a specific handle scale setting
and a given flow rate.

The red curve is the Venturi measuring signal which indicates what differential pressure should be measured
across the Venturi orifice for a given flow.

See example on data sheet 4.4.3 for DN 20S.

4.5
Flow Diagram

BALLOREX Venturi

DN 15S - Standard flow


Bar kPa Presssure drop across valve
1 100

0.7 70
0.6 60
0.5 50 Measuring signal
0.0 2.0 3.0 4.0
ition ition ition ition
0.4 40 pos Pos Pos Pos
6.0
0.3 30 ition
Pos
7.0
0.2 20 ition
Pos
8.0
ition
Pos
9.9
0.1 10 ition
Pos
0.08 8
0.07 7
0.06 6
0.05 5

0.04 4

0.03 3 Flow rate


0.036 0.04 0.05 0.06 0.07 0.08 0.09 0.1 0.148 l/s

130 144 180 216 252 288 324 360 530 l/h

The X-axis indicates the recommended flow range of the valve.

The black curves are used to determine the total pressure drop across the valve at a specific handle scale setting, and a
given flow rate.

The red curve is the Venturi measuring signal, which indicates what differential pressure should be measured across the
Venturi orifice for a given flow.

See example on data sheet 4.4.3. for DN 20S.

4.5
Flow Diagram

BALLOREX Venturi

DN 15H - High flow


Bar kPa Pressure drop across valve

1 100

0.7 70
0.6 60
Measuring signal
0.5 50
.0 2.0 3.0 4.0 5.0 .0
n0 n n n n n6
itio itio itio itio itio itio
0.4 40 Pos Pos Pos Pos Pos Pos .0
n8
itio
0.3 30 Pos
.0
n9
itio
Pos .9
n9
0.2 20 itio
Pos

0.1 10

0.08 8
0.07 7
0.06 6
0.05 5

0.04 4

0.03 3 Flow rate


0.074 0.08 0.09 0.1 0.2 0.3 0.325 l/s

267 288 324 360 720 1,080 1,170 l/h

The X-axis indicates the recommended flow range of the valve.

The black curves are used to determine the total pressure drop across the valve at a specific handle scale setting and a
given flow rate.

The red curve is the Venturi measuring signal which indicates what differential pressure should be measured across the
Venturi orifice for a given flow.

See example on data sheet 4.4.3 for DN 20S.

4.5
Flow Diagram

4.5
BALLOREX Venturi

4.5.3 DN 20 compression/compression

105mm
Specifications
Max. temperature 120C
Min. temperature -20C
79mm Max. pressure 5 bar
Marking on valve (Handle) DN, flow-version, Kvm (Kv-measuring)
(Valve body) DN, PN, flow direction, BROEN
Connection Compression EN 1254-2
75mm Valve housing DR Brass CW602N CuZn36Pb2As
170mm Ball & needle DR Brass CW602N (chrome plated)
Valve handle Polyamide (PA6.6 30%GF)
Sealings O-rings EPDM
Gaskets PTFE
Test point sealing EPDM

Compression connections are not recommendeded for cooling applications.


Instead press or threaded connection are recommended.

Nom. Flow range


BROEN No. Dimension
Inch l/s l/h

4450100L-001063 DN 20L 22 mm 0.036 - 0.148 130 - 530

4450100S-001063 DN 20S 22 mm 0.074 - 0.325 267 - 1,170

4450100H-001063 DN 20H 22 mm 0.142 - 0.603 511 - 2,170

Accessories
BROEN No. Dimension Description

96M0241-000005 DN 20 BALLOREX Venturi - Insulation jacket

4.5
Flow Diagram

BALLOREX Venturi

DN 20L - Low flow


Bar kPa Pressure drop across valve

1 100

0.7 70
0.6 60
0.5 50 Measuring signal
1.0 2.0 3.0
ition ition ition
0.4 40 Pos Pos Pos
4.0
ition
0.3 30 Pos
5.0
ition
Pos
6.0
ition
0.2 20
Pos 7 .0
ition
Pos 9 .9
itio n
Pos
0.1 10

0.08 8
0.07 7
0.06 6
0.05 5

0.04 4

0.03 3
Flow rate
0.036 0.04 0.05 0.06 0.07 0.08 0.09 0.1 0.148 l/s

130 144 180 216 252 288 324 360 530 l/h

The X-axis indicates the recommended flow range of the valve.

The black curves are used to determine the total pressure drop across the valve at a specific handle scale setting and a
given flow rate.

The red curve is the Venturi measuring signal which indicates what differential pressure should be measured across the
Venturi orifice for a given flow.

See example on data sheet 4.4.3 for DN 20S.

4.5
BALLOREX Venturi

DN 20S Standard flow


Bar kPa Pressure drop across valve
1 100

0
n 0.
itio
0.7 70
Pos
0.6 60
Measuring signal
0.5 50
.0 2.0 3.0 .0
n1 n n n4
itio itio itio itio .0
0.4 40 Pos Pos Pos Pos itio
n5
Pos
0.3 30 .0
n6
itio
Pos .0
n7
itio
0.2 20 Pos n 8.0
itio
Pos ion 9.9
it
Pos

0.1 10

0.07 7
0.06 6
0.05 5

0.04 4

0.03 3
Flow rate
0.075 0.09 0.1 0.2 0.3 0.325 l/s

270 324 360 720 1,080 1,170 l/h

The X-axis indicates the recommended flow range of the valve.

The black curves are used to determine the total pressure drop across the valve at a specific handle scale setting, and a
given flow rate.

The red curve is the Venturi measuring signal, which indicates what differential pressure should be measured across the
Venturi orifice for a given flow.

See example on data sheet 4.4.3. for DN 20S.

4.5
Flow Diagram

BALLOREX Venturi

DN 20H - High flow


Bar kPa Pressure drop across valve
1 100

0.7 70
0.6 60
Measuring signal
0.5 50
0 0 0 0
ion 0. ion 1. ion 2.
0
ion 3. io n 4.
0
ion 5. .0
0.4 40 Posit P osit Posit P osit Posit Posit iti on 6
Pos
0
0.3 30 n 7.
itio
Pos
0
n 8.
itio
0.2 20 Pos
0
n 9.
itio
Pos 9 .9
n
itio
Pos
0.1 10

0.07 7
0.06 6
0.05 5

0.04 4

0.03 3 Flow rate


0.142 0.2 0.3 0.4 0.5 0.603 l/s

511 720 1,080 1,440 1,800 2,170 l/h

The X-axis indicates the recommended flow range of the valve.

The black curves are used to determine the total pressure drop across the valve at a specific handle scale setting and a
given flow rate.

The red curve is the Venturi measuring signal which indicates what differential pressure should be measured across the
Venturi orifice for a given flow.

See example on data sheet 4.4.3 for DN 20S.

4.5
BALLOREX Venturi

4.5.4 DN 25 compression/compression

118mm Specifications
Max. temperature 120C
Min. temperature -20C
Max. pressure 5 bar
83mm
Marking on valve (Handle) DN, flow-version, Kvm (Kv-measuring)
(Valve body) DN, PN, flow direction, BROEN
Connection Compression EN 1254-2
Valve housing DR Brass CW602N CuZn36Pb2As
75mm Ball & needle DR Brass CW602N (chrome plated)
Valve handle Polyamide (PA6.6 30%GF)
177mm
Sealings O-rings EPDM
Gaskets PTFE
Test point sealing EPDM

Compression connections are not recommendeded for cooling applications.


Instead press or threaded connection are recommended.

Nom. Flow range


BROEN No. Dimension
Inch l/s l/h

4550100S-001063 DN 25S 28 mm 0.142 - 0.603 511 - 2,170

4550100H-001063 DN 25H 28 mm 0.29 - 1.25 1,044 - 4,500

Accessories
BROEN No. Dimension Description

96M0242-000005 DN 25 BALLOREX Venturi - Insulation jacket

4.5
Flow Diagram

BALLOREX Venturi

DN 25S - Standard flow


Bar kPa Pressure drop across valve
1 100

0.7 70
0.6 60
0.5 50
Measuring signal
0.0 1.0 2.0 3.0 .0
sitio
n ion sitio
n
sitio
n
on 4
0.4 40
Po Posit Po Po iti
Pos
0.3 30
5.0
ition
Pos
0.2 20
6.0
ition
Pos
7.0
ition
Pos
8.0
0.1 10 ition
Pos
9.9
tion
0.07 7 Posi

0.05 5

0.04 4

0.03 3
Flow rate
0.14 0.2 0.3 0.4 0.5 0.603 l/s

504 720 1,080 1,440 1,800 2,171 l/h

DN 25H - High flow


Bar kPa Pressure drop across valve
1 100

0.7 70
0.6 60
0 0 0
n 0. n 1. n 2. n 3.
0
n 4.
0
n 5.
0 Measuring signal
0.5 50 itio itio itio itio itio itio
Pos Pos Pos Pos Pos Pos 6.0
n
0.4 40 Po sitio
0
n 7.
0.3 30 itio
Pos
0
n 8.
itio
0.2 20 Pos
0
n 9.
itio
Pos ion 9.9
it
Pos
0.1 10

0.07 7
0.06 6
0.05 5

0.04 4

Flow rate
0.03 3
0.29 0.4 0.5 0.6 0.7 0.8 0.9 1 1.25 l/s

1044 1440 1800 2160 2520 2880 3240 3600 4500 l/h

The X-axis indicates the recommended flow range of the valve.

The black curves are used to determine the total pressure drop across the valve at a specific handle scale setting and a
given flow rate.

The red curve is the Venturi measuring signal which indicates what differential pressure should be measured across the
Venturi orifice for a given flow.

See example on data sheet 4.4.3 for DN 20S.

4.5
BALLOREX Venturi

4.5.5 DN 32 compression/compression

135mm
Specifications
Max. temperature 120C
Min. temperature -20C
109mm Max. pressure 5 bar
Marking on valve (Handle) DN, flow-version, Kvm (Kv-measuring)
(Valve body) DN, PN, flow direction, BROEN
Connection Compression EN 1254-2
122mm
Valve housing DR Brass CW602N CuZn36Pb2As
241mm Ball & needle DR Brass CW602N (chrome plated)
Valve handle Polyamide (PA6.6 30%GF)
Sealings O-rings EPDM
Gaskets PTFE
Test point sealing EPDM

Compression connections are not recommendeded for cooling applications.


Instead press or threaded connection are recommended.

Nom. Flow range


BROEN No. Dimension
Inch l/s l/h

4650100H-001063 DN 32H 35 mm 0.29 - 1.25 1,044 - 4,500

Accessories
BROEN No. Dimension Description

96M0243-000005 DN 32 BALLOREX Venturi - Insulation jacket

4.5
Flow Diagram

BALLOREX Venturi

DN 32H - High flow


Bar kPa Pressure drop across valve

1 100

0.7 70
0.6 60
Measuring signal
0.5 50

0.4 40 0 0
0 0
n 0.
0 n 1. n 2.
0 n 3. n 4. n 5. 0
itio Pos
itio itio itio itio
Pos
itio n 6.
Pos Pos Pos Pos itio
0.3 30 Pos
0
n 7.
itio
0.2 20 Pos
0
n 8.
itio
Pos 0
n 9.
itio
Pos n 9.9
it i o
0.1 10 Pos

0.07 7
0.06 6
0.05 5

0.04 4

0.03 3 Flow rate


0.290 0.4 0.5 0.6 0.7 0.8 0.9 1 1.25 l/s

1,044 1,440 1,800 2,160 2,520 2,880 3,240 3,600 4,500 l/h

The X-axis indicates the recommended flow range of the valve.

The black curves are used to determine the total pressure drop across the valve at a specific handle scale setting and a
given flow rate.

The red curve is the Venturi measuring signal which indicates what differential pressure should be measured across the
Venturi orifice for a given flow.

See example on data sheet 4.4.3 for DN 20S.


BALLOREX Venturi

4.5.6 DN 40 compression/compression

149mm
Specifications
Max. temperature 120C
Min. temperature -20C
113mm Max. pressure 5 bar
Marking on valve (Handle) DN, flow-version, Kvm (Kv-measuring)
(Valve body) DN, PN, flow direction, BROEN
Connection Compression EN 1254-2
122mm
Valve housing DR Brass CW602N CuZn36Pb2As
253mm Ball & needle DR Brass CW602N (chrome plated)
Valve handle Polyamide (PA6.6 30%GF)
Sealings O-rings EPDM
Gaskets PTFE
Test point sealing EPDM

Compression connections are not recommendeded for cooling applications.


Instead press or threaded connection are recommended.

Nom. Flow range


BROEN No. Dimension
Inch l/s l/h

4750100H-001063 DN 40H 42 mm 0.44 - 1.88 1,584 - 6,760

Accessories
BROEN No. Dimension Description

96M0244-000005 DN 40 BALLOREX Venturi - Insulation jacket

4.5
Flow Diagram

BALLOREX Venturi

DN 40H - High flow


Bar kPa Pressure drop across valve
1 100

0.7 70
0.6 60
Measuring signal
0.5 50
n 0.0 n1.0
n2.0 n 3.0 n4.0
0.4 40
Positio Positio sitio Positio Positio 5.0
Po ition
Pos
0.3 30
6.0
ition
Pos
0.2 20 7.0
ition
Pos
8.0
ition
Pos
9.0
ition
0.1 10 Pos 9.9
ition
Pos
0.07 7
0.06 6
0.05 5

0.04 4

0.03 3 Flow rate


0.44 0.5 0.6 0.7 0.8 0.9 1 1.88 l/s

1,584 1,800 2,160 2,520 2,880 3,240 3,600 6,760 l/h

The X-axis indicates the recommended flow range of the valve.

The black curves are used to determine the total pressure drop across the valve at a specific handle scale setting and a
given flow rate.

The red curve is the Venturi measuring signal which indicates what differential pressure should be measured across the
Venturi orifice for a given flow.

See example on data sheet 4.4.3 for DN 20S.

4.5
BALLOREX Venturi

4.5.7 DN 50 compression/compression

167mm
Specifications
Max. temperature 120C
Min. temperature -20C
120mm Max. pressure 5 bar
Marking on valve (Handle) DN, flow-version, Kvm (Kv-measuring)
(Valve body) DN, PN, flow direction, BROEN
Connection Compression EN 1254-2
122mm
Valve housing DR Brass CW602N CuZn36Pb2As
265mm Ball & needle DR Brass CW602N (chrome plated)
Valve handle Polyamide (PA6.6 30%GF)
Sealings O-rings EPDM
Gaskets PTFE
Test point sealing EPDM

Compression connections are not recommendeded for cooling applications.


Instead press or threaded connection are recommended.

Nom. Flow range


BROEN No. Dimension
Inch l/s l/h

4850100H-001063 DN 50H 54 mm 0.82 - 3.51 2,952 - 12,630

Accessories
BROEN No. Dimension Description

96M0245-000005 DN 50 BALLOREX Venturi - Insulation jacket

4.5
Flow Diagram

BALLOREX Venturi

DN 50H - High flow


Bar kPa Pressure drop across valve
1 100

0.7 70
0.6 60
Measuring signal
0.5 50
0.4 40
0.0 1.0 2.0 3.0 4.0 5.0 6.0
ition ition ition ition ition ition ition
0.3 30 Pos Pos Pos Pos Pos Pos Pos
7.0
ition
Pos
8.0
ition
0.2 20
Pos
9.0
ition
Pos .9
9
ition
0.1 10
Pos

0.07 7
0.06 6
0.05 5

0.04 4

0.03 3 Flow rate


0.82 0.9 1 2 3 3.51 l/s

2,952 3,240 3,600 7,200 10,800 12,630 l/h

The X-axis indicates the recommended flow range of the valve.

The black curves are used to determine the total pressure drop across the valve at a specific handle scale setting and a
given flow rate.

The red curve is the Venturi measuring signal which indicates what differential pressure should be measured across the
Venturi orifice for a given flow.

See example on data sheet 4.4.3 for DN 20S.

4.5
BALLOREX Venturi
BALLOREX venturi
4.6 Product data sheets - FODRV flange
4.6.1 Product finder

DN300

DN 250

DN 200

DN 150

DN 125

DN 100

DN 80

DN 65

1 2 3 4 5 6 7 8 9 10 20 30 40 50 60 70 80 90 100 200 300 l/s


3.6 7.2 10.8 14.4 18.0 21.6 28.8 36.0 72.0 108 144 180 216 288 360 720 1,080 m3/h

Flow range Dimension Section

l/s m3/h

1.8 - 7 6.48 - 25.2 DN65 4.6.2

3.5 - 15 12.6 - 54.0 DN80 4.6.3

6.2 - 26 22.3 - 93.6 DN100 4.6.4

9 - 40 32.4 - 144 DN125 4.6.5

16.8 - 57 60.5 - 205 DN150 4.6.6

28 - 100 101 - 360 DN200 4.6.7

Note!
Dimensions 350 - 600 available on request.

4.6
BALLOREX Venturi

4.6.2 DN 65 flange/flange

160mm Specifications
Max. temperature 120C
Min. temperature -20C
269mm Max. pressure 16 bar
Marking on valve (Venturi pipe) DN, maximum temperature and flow
direction (Butterfly gearbox) Valve type, DN and Kvm
Connection Flange: BS 4504 - PN16
Venturi pipe Carbon steel
182mm 185mm
Butterfly valve body Cast iron, fully lugged (ASTMA A126 KL.B)
Disc Stainless steel (ASTM A351)
Shaft Stainless steel (ASTM A276)
Test points DR Brass CW602N CuZn36Pb2As
Sealings EPDM and NBR 1

Nom. Flow range


BROEN No. Dimension
Inch l/s m3/h

3937000-680009 DN 65 2 1/2 1.8 - 7 6.48 - 25.2

4.6
Flow Diagram

BALLOREX Venturi

DN 65 flange/flange
Bar kPa Pressure drop across valve
1 100

0.7 70
0.6 60
0.5 50
1.5 2.0 2.5 Measuring signal
ition ition ition
0.4 40
Pos Pos Pos
3.0
ition
0.3 30 Pos

3.5
0.2 20 ition
Pos
4.0
ition
Pos 4.5
ition
Pos 6.0
0.1 10 ition
Pos
0.07 7
0.06 6
0.05 5
0.04 4

0.03 3 Flow rate


1.8 2 3 4 5 6 7 l/s

6.48 7.2 10.8 14.4 18 21.6 25.2 m3/h

The X-axis indicates the recommended flow range of the valve.

The black curves are used to determine the total pressure drop across the valve at a specific handle scale setting and a
given flow rate.

The red curve is the Venturi measuring signal which indicates what differential pressure should be measured across the
Venturi orifice for a given flow.

See example on data sheet 4.4.3 for DN 20S.

4.6
BALLOREX Venturi

4.6.3 DN 80 flange/flange

160mm Specifications
Max. temperature 120C
Min. temperature -20C
275mm Max. pressure 16 bar
Marking on valve (Venturi pipe) DN, maximum temperature and flow
direction (Butterfly gearbox) Valve type, DN and Kvm
Connection Flange: BS 4504 - PN16
Venturi pipe Carbon steel
99mm
Butterfly valve body Cast iron, fully lugged (ASTMA A126 KL.B)
249mm 200mm
Disc Stainless steel (ASTM A351)
Shaft Stainless steel (ASTM A276)
76mm Test points DR Brass CW602N CuZn36Pb2As
Sealings EPDM and NBR 1

75mm

164mm

Nom. Flow range


BROEN No. Dimension
Inch l/s m3/h

3937600-680009 DN 80 3 3.5 - 15 12.6 - 54

4.6
Flow Diagram

BALLOREX Venturi

DN 80 flange/flange
Bar kPa Pressure drop across valve
1 100

1.5 2.0 2.5


0.7 70 ition ition ition
0.6 60 Pos Pos Pos 3.0
ition Measuring signal
0.5 50 Pos
0.4 40
3.5
ition
0.3 30 Pos
4.0
ition
0.2 20 Pos
4.5
ition
Pos .0
5
ition
Pos
6.0
0.1 10 ition
Pos
0.07 7
0.06 6
0.05 5

0.04 4

0.03 3 Flow rate


3.5 4 5 6 7 8 9 10 15 l/s

12.6 14.4 18 21.6 25.2 28.8 32.4 36 54 m3/h

The X-axis indicates the recommended flow range of the valve.

The black curves are used to determine the total pressure drop across the valve at a specific handle scale setting and a
given flow rate.

The red curve is the Venturi measuring signal which indicates what differential pressure should be measured across the
Venturi orifice for a given flow.

See example on data sheet 4.4.3 for DN 20S.

4.6
BALLOREX Venturi

4.6.4 DN 100 flange/flange

160mm
Specifications
Max. temperature 120C
Min. temperature -20C
Max. pressure 16 bar
297mm
Marking on valve (Venturi pipe) DN, maximum temperature and flow
direction (Butterfly gearbox) Valve type, DN and Kvm
Connection Flange: BS 4504 - PN16
Venturi pipe Carbon steel
Butterfly valve body Cast iron, fully lugged (ASTMA A126 KL.B)
325mm 220mm Disc Stainless steel (ASTM A351)
Shaft Stainless steel (ASTM A276)
Test points DR Brass CW602N CuZn36Pb2As
Sealings EPDM and NBR 1

Nom. Flow range


BROEN No. Dimension
Inch l/s m3/h

3938200-680009 DN 100 4 6.2 - 26 22.3 - 93.6

4.6
Flow Diagram

BALLOREX Venturi

DN 100 flange/flange
Bar kPa Pressure drop across valve

1 100

0.7 70
0.6 60
Measuring signal
0.5 50

0.4 40

0.3 30
.0 .5
n3 n3
itio itio .5
Pos Pos itio
n4
0.2 20 Pos

.0
n5
itio
Pos
0.1 10

0.07 7 .0
n6
itio
0.06 6 Pos
0.05 5

0.04 4

0.03 3 Flow rate


6.2 7 8 9 10 20 26 l/s

22.3 25.2 28.8 32.4 36 72 93.6 m3/h

The X-axis indicates the recommended flow range of the valve.

The black curves are used to determine the total pressure drop across the valve at a specific handle scale setting and a
given flow rate.

The red curve is the Venturi measuring signal which indicates what differential pressure should be measured across the
Venturi orifice for a given flow.

See example on data sheet 4.4.3 for DN 20S.

4.6
BALLOREX Venturi

4.6.5 DN 125 flange/flange

160mm Specifications
Max. temperature 120C
Min. temperature -20C
307mm Max. pressure 16 bar
Marking on valve (Venturi pipe) DN, maximum temperature and flow
direction (Butterfly gearbox) Valve type, DN and Kvm
Connection Flange: BS 4504 - PN16
Venturi pipe Carbon steel
341mm 250mm
Butterfly valve body Cast iron, fully lugged (ASTMA A126 KL.B)
Disc Stainless steel (ASTM A351)
Shaft Stainless steel (ASTM A276)
Test points DR Brass CW602N CuZn36Pb2As
Sealings EPDM and NBR 1

Nom. Flow range


BROEN No. Dimension
Inch l/s m3/h

3938800-680009 DN 125 5 1/2 9 - 40 32.4 - 144

4.6
Flow Diagram

BALLOREX Venturi

DN 125 flange/flange
Bar kPa Pressure drop across valve
1 100

0.7 70
0.6 60 Measuring signal
0.5 50
0.4 40
2.5 3.0
ition ition
0.3 30 Pos Pos 4.0
ition
Pos
0.2 20
4.5
ition
Pos
5.0
ition
0.1 10 Pos
6.0
ition
0.07 7 Pos
0.06 6
0.05 5
0.04 4

0.03 3 Flow rate


9 10 20 30 40 l/s

32.4 36 72 108 144 m3/h

The X-axis indicates the recommended flow range of the valve.

The black curves are used to determine the total pressure drop across the valve at a specific handle scale setting and a
given flow rate.

The red curve is the Venturi measuring signal which indicates what differential pressure should be measured across the
Venturi orifice for a given flow.

See example on data sheet 4.4.3 for DN 20S.

4.6
BALLOREX Venturi

4.6.6 DN 150 flange/flange

160mm Specifications
Max. temperature 120C
Min. temperature -20C
320mm Max. pressure 16 bar
Marking on valve (Venturi pipe) DN, maximum temperature and flow
direction (Butterfly gearbox) Valve type, DN and Kvm
Connection Flange: BS 4504 - PN16
Venturi pipe Carbon steel
354mm 285mm
Butterfly valve body Cast iron, fully lugged (ASTMA A126 KL.B)
Disc Stainless steel (ASTM A351)
Shaft Stainless steel (ASTM A276)
Test points DR Brass CW602N CuZn36Pb2As
Sealings EPDM and NBR 1

Nom. Flow range


BROEN No. Dimension
Inch l/s m3/h

3939400-680009 DN 150 6 16.8 - 57 60.5 - 205

4.6
Flow Diagram

BALLOREX Venturi

DN 150 flange/flange
Bar kPa Pressure drop across valve

1 100
.0
ion 2
0.7 70 Posit

0.5 50
0.4 40
Measuring signal
0.3 30
.5 3.0 3.5 n4 .0
ion 2 Position ition ositio
Posit Pos P
0.2 20

.5
ion 4
Posit

0.1 10
.0
ion 5
0.07 7 Posit

0.05 5
.0
0.04 4 ion 6
Posit
0.03 3 Flow rate
16.8 20 30 40 50 57 l/s

60.5 72 108 144 180 205 m3/h

The X-axis indicates the recommended flow range of the valve.

The black curves are used to determine the total pressure drop across the valve at a specific handle scale setting and a
given flow rate.

The red curve is the Venturi measuring signal which indicates what differential pressure should be measured across the
Venturi orifice for a given flow.

See example on data sheet 4.4.3 for DN 20S.

4.6
BALLOREX Venturi

4.6.7 DN 200 flange/flange

150mm Specifications
Max. temperature 120C
Min. temperature -20C
354mm Max. pressure 16 bar
Marking on valve (Venturi pipe) DN, maximum temperature and flow
direction (Butterfly gearbox) Valve type, DN and Kvm
Connection Flange: BS 4504 - PN16
Venturi pipe Carbon steel
378mm 340mm
Butterfly valve body Cast iron, fully lugged (ASTMA A126 KL.B)
Disc Stainless steel (ASTM A351)
Shaft Stainless steel (ASTM A276)
Test points DR Brass CW602N CuZn36Pb2As
Sealings EPDM and NBR 1

Nom. Flow range


BROEN No. Dimension
Inch l/s m3/h

3940000-680009 DN 200 8 28 - 100 101 - 360

4.6
Flow Diagram

BALLOREX Venturi

DN 200 flange/flange
Bar kPa Pressure drop across valve

1 100

0.7 70

0.5 50
.0 .5
ion 2
.5
ion 3 ion 3
0.4 40 Posit Posit Posit Measuring signal
io n 4.0
0.3 30 Posit

0.2 20
.5
ion 4
Posit

0.1 10
.0
ion 5
0.07 7 Posit

0.05 5
0.04 4
.0
ion 6
0.03 3 Posit Flow rate
28 30 40 50 60 70 80 90 100 l/s

101 108 144 180 216 252 288 324 360 m3/h

The X-axis indicates the recommended flow range of the valve.

The black curves are used to determine the total pressure drop across the valve at a specific handle scale setting and a
given flow rate.

The red curve is the Venturi measuring signal which indicates what differential pressure should be measured across the
Venturi orifice for a given flow.

See example on data sheet 4.4.3 for DN 20S.

4.6
BALLOREX Venturi

4.6.8 DN 250 flange/flange

190mm Specifications
Max. temperature 120C
Min. temperature -20C
445mm Max. pressure 16 bar
Marking on valve (Venturi pipe) DN, maximum temperature and flow
direction (Butterfly gearbox) Valve type, DN and Kvm
Connection Flange: BS 4504 - PN16
Venturi pipe Carbon steel
411mm 405mm
Butterfly valve body Cast iron, fully lugged (ASTMA A126 KL.B)
Disc Stainless steel (ASTM A351)
Shaft Stainless steel (ASTM A276)
Test points DR Brass CW602N CuZn36Pb2As
Sealings EPDM and NBR 1

Nom. Flow range


BROEN No. Dimension
Inch l/s m3/h

3940600-680009 DN 250 10 41 - 157 148 - 565

4.6
Flow Diagram

BALLOREX Venturi

DN 250 flange/flange
Bar kPa Pressure drop across valve
1 100

0.7 70

0.5 50 .0
ion 2 ion 2
.5
ion 3
.0
ion 3
.5
0.4 40 Posit Posit Posit Posit
Measuring signal

0.3 30 .0
ion 4
Posit
0.2 20
.5
ion 4
Posit

0.1 10
.0
ion 5
Posit
0.07 7

.0
0.05 5 ion 6
Posit
0.04 4
0.03 3 Flow rate
41 50 60 70 80 90 100 157 l/s

148 180 216 252 288 324 360 565 m3/h

The X-axis indicates the recommended flow range of the valve.

The black curves are used to determine the total pressure drop across the valve at a specific handle scale setting and a
given flow rate.

The red curve is the Venturi measuring signal which indicates what differential pressure should be measured across the
Venturi orifice for a given flow.

See example on data sheet 4.4.3 for DN 20S.

4.6
BALLOREX Venturi

4.6.9 DN 300 flange/flange

190mm Specifications
Max. temperature 120C
Min. temperature -20C
490mm Max. pressure 16 bar
Marking on valve (Venturi pipe) DN, maximum temperature and flow
direction (Butterfly gearbox) Valve type, DN and Kvm
Connection Flange: BS 4504 - PN16
Venturi pipe Carbon steel
Butterfly valve body Cast iron, fully lugged (ASTMA A126 KL.B)
465mm 460mm
Disc Stainless steel (ASTM A351)
Shaft Stainless steel (ASTM A276)
Test points DR Brass CW602N CuZn36Pb2As
Sealings EPDM and NBR 1

Nom. Flow range


BROEN No. Dimension
Inch l/s m3/h

3941200-680009 DN 300 12 72 - 226 259 - 814

4.6
Flow Diagram

BALLOREX Venturi

DN 300 flange/flange
Bar kPa Pressure drop across valve
1 100

0.7 70

0.5 50
0.4 40

0.3 30 Measuring signal


.5 .0 .5 .0
ion 1 ion 2 ion 2 ion 3
Posit Posit Posit Posit
0.2 20
n 4.0
Positio

0.1 10 .5
ion 4
Posit
0.07 7
.0
ion 5
0.05 5 Posit
0.04 4

0.03 3 Flow rate


72 80 90 100 200 226 l/s

259 288 324 360 720 814 m3/h

The X-axis indicates the recommended flow range of the valve.

The black curves are used to determine the total pressure drop across the valve at a specific handle scale setting and a
given flow rate.

The red curve is the Venturi measuring signal which indicates what differential pressure should be measured across the
Venturi orifice for a given flow.

See example on data sheet 4.4.3 for DN 20S.

4.6
BALLOREX Venturi
BALLOREX venturi
4.7 Product data sheets - FODRV extended D

4.7.1 Product finder DN 250

DN 200

DN 150

DN 125

DN 100

DN 80

DN 65

1 2 3 4 5 6 7 8 9 10 20 30 40 50 60 70l/s 80 90 100
3.6 7.2 10.8 14.4 18 21.6 28.8 36 72 108 144 180 216 m3/h

252000
288000
324000
360000
Flow range Dimension Section

l/s m3/h

1.8 - 7 6.48 - 25.2 DN65 4.7.2

3.5 - 15 12.6 - 54 DN80 4.7.3

6.2 - 26 22.3 - 93.6 DN100 4.7.4

9 - 40 32.4 - 144 DN125 4.7.5

16.8 - 57 60.5 - 205 DN150 4.7.6

4.7
BALLOREX Venturi

4.7.2 DN 65 extended flange/flange

Specifications
Max. temperature 120C
Min. temperature -20C
Max. pressure 16 bar
Marking on valve (Venturi pipe) DN, maximum temperature and flow
direction (Butterfly gearbox) Valve type, DN and Kvm
Connection Flange: BS 4504 - PN16
Venturi pipe Carbon steel
455mm Butterfly valve body Cast iron, fully lugged (ASTMA A126 KL.B)
Disc Stainless steel (ASTM A351)
160mm
Shaft Stainless steel (ASTM A276)
Test points DR Brass CW602N CuZn36Pb2As
Sealings EPDM and NBR 1

269mm

185mm

Nom. Flow range


BROEN No. Dimension
Inch l/s m3/h

3937000-680009 DN 65 2 1/2 1.8 - 7 6.48 - 25.2

4.7
Flow Diagram

BALLOREX Venturi

DN 65 extended flange/flange
Bar kPa Pressure drop across valve
1 100

0.7 70
0.6 60
0.5 50
1.5 2.0 2.5 Measuring signal
ition ition ition
0.4 40
Pos Pos Pos
3.0
ition
0.3 30 Pos

3.5
0.2 20 ition
Pos
4.0
ition
Pos 4.5
ition
Pos 6.0
0.1 10 ition
Pos
0.07 7
0.06 6
0.05 5

0.04 4

0.03 3 Flow rate


1.8 2 3 4 5 6 7 l/s

6.48 7.2 10.8 14.4 18 21.6 25.2 m3/h

The X-axis indicates the recommended flow range of the valve.

The black curves are used to determine the total pressure drop across the valve at a specific handle scale setting and a
given flow rate.

The red curve is the Venturi measuring signal which indicates what differential pressure should be measured across the
Venturi orifice for a given flow.

See example on data sheet 4.4.3 for DN 20S.

4.7
BALLOREX Venturi

4.7.3 DN 80 extended flange/flange

Specifications
Max. temperature 120C
Min. temperature -20C
Max. pressure 16 bar
Marking on valve (Venturi pipe) DN, maximum temperature and flow
direction (Butterfly gearbox) Valve type, DN and Kvm
Connection Flange: BS 4504 - PN16
Venturi pipe Carbon steel
570mm Butterfly valve body Cast iron, fully lugged (ASTMA A126 KL.B)
Disc Stainless steel (ASTM A351)
160mm
Shaft Stainless steel (ASTM A276)
Test points DR Brass CW602N CuZn36Pb2As
Sealings EPDM and NBR 1
275mm

200mm

Nom. Flow range


BROEN No. Dimension
Inch l/s m3/h

3937600-680009 DN 80 3 3.5 - 15 12.6 - 54.0

4.7
Flow Diagram

BALLOREX Venturi

DN 80 extended flange/flange
Bar kPa Pressure drop across valve
1 100

0.7 70 1.5 2.0 2.5


ition ition ition
0.6 60 Pos Pos Pos 3.0
ition Measuring signal
0.5 50 Pos
0.4 40
3.5
ition
0.3 30 Pos
4.0
ition
0.2 20 Pos
4.5
ition
Pos .0
5
ition
Pos
6.0
0.1 10 ition
Pos
0.07 7
0.06 6
0.05 5

0.04 4

0.03 3 Flow rate


3.5 4 5 6 7 8 9 10 15 l/s

12.6 14.4 18 21.6 25.2 28.8 32.4 36 54.0 m3/h

The X-axis indicates the recommended flow range of the valve.

The black curves are used to determine the total pressure drop across the valve at a specific handle scale setting and a
given flow rate.

The red curve is the Venturi measuring signal which indicates what differential pressure should be measured across the
Venturi orifice for a given flow.

See example on data sheet 4.4.3 for DN 20S.

4.7
BALLOREX Venturi

4.7.4 DN 100 extended flange/flange

Specifications
Max. temperature 120C
Min. temperature -20C
Max. pressure 16 bar
Marking on valve (Venturi pipe) DN, maximum temperature and flow
direction (Butterfly gearbox) Valve type, DN and Kvm
Connection Flange: BS 4504 - PN16
Venturi pipe Carbon steel
735mm Butterfly valve body Cast iron, fully lugged (ASTMA A126 KL.B)
Disc Stainless steel (ASTM A351)
160mm Shaft Stainless steel (ASTM A276)
Test points DR Brass CW602N CuZn36Pb2As
Sealings EPDM and NBR 1

297mm

220mm

Nom. Flow range


BROEN No. Dimension
Inch l/s m3/h

3938200-680009 DN 100 4 6.2 - 26 22.3 - 93.6

4.7
Flow Diagram

BALLOREX Venturi

DN 100 extended flange/flange


Bar kPa Pressure drop across valve

1 100

0.7 70
0.6 60
Measuring signal
0.5 50

0.4 40

0.3 30
.0 .5
n3 n3
itio itio .5
Pos Pos itio
n4
0.2 20 Pos

.0
n5
itio
Pos
0.1 10

0.07 7 .0
n6
itio
0.06 6
Pos
0.05 5

0.04 4

0.03 3 Flow rate


6.2 7 8 9 10 20 26 l/s

22.3 25.2 28.8 32.4 36 72 93.6 m3/h

The X-axis indicates the recommended flow range of the valve.

The black curves are used to determine the total pressure drop across the valve at a specific handle scale setting and a
given flow rate.

The red curve is the Venturi measuring signal which indicates what differential pressure should be measured across the
Venturi orifice for a given flow.

See example on data sheet 4.4.3 for DN 20S.

4.7
BALLOREX Venturi

4.7.5 DN 125 extended flange/flange

Specifications
Max. temperature 120C
Min. temperature -20C
Max. pressure 16 bar
Marking on valve (Venturi pipe) DN, maximum temperature and flow
direction (Butterfly gearbox) Valve type, DN and Kvm
Connection Flange: BS 4504 - PN16
Venturi pipe Carbon steel
865mm Butterfly valve body Cast iron, fully lugged (ASTMA A126 KL.B)
Disc Stainless steel (ASTM A351)
160mm Shaft Stainless steel (ASTM A276)
Test points DR Brass CW602N CuZn36Pb2As
Sealings EPDM and NBR 1

307mm

250mm

Nom. Flow range


BROEN No. Dimension
Inch l/s m3/h

3938800-680009 DN 125 5 9.0 - 40 32.4 - 144

4.7
Flow Diagram

BALLOREX Venturi

DN 125 extended flange/flange


Bar kPa Pressure drop across valve
1 100

0.7 70
0.6 60 Measuring signal
0.5 50
0.4 40
2.5 3.0
ition ition
0.3 30 Pos Pos 4.0
ition
Pos
0.2 20
4.5
ition
Pos
5.0
ition
0.1 10 Pos
6.0
ition
0.07 7 Pos
0.06 6
0.05 5
0.04 4

0.03 3 Flow rate


9 10 20 30 40 l/s

32.4 36 72 108 144 m3/h

The X-axis indicates the recommended flow range of the valve.

The black curves are used to determine the total pressure drop across the valve at a specific handle scale setting and a
given flow rate.

The red curve is the Venturi measuring signal which indicates what differential pressure should be measured across the
Venturi orifice for a given flow.

See example on data sheet 4.4.3 for DN 20S.

4.7
BALLOREX Venturi

4.7.6 DN 150 extended flange/flange

Specifications
Max. temperature 120C
Min. temperature -20C
Max. pressure 16 bar
Marking on valve (Venturi pipe) DN, maximum temperature and flow
direction (Butterfly gearbox) Valve type, DN and Kvm
Connection Flange: BS 4504 - PN16
Venturi pipe Carbon steel
1010mm Butterfly valve body Cast iron, fully lugged (ASTMA A126 KL.B)
Disc Stainless steel (ASTM A351)
160mm
Shaft Stainless steel (ASTM A276)
Test points DR Brass CW602N CuZn36Pb2As
Sealings EPDM and NBR 1

320mm

285mm

Nom. Flow range


BROEN No. Dimension
Inch l/s m3/h

3939400-680009 DN 150 6 16.8 - 57 60.5 - 205

4.7
Flow Diagram

BALLOREX Venturi

DN 150 extended flange/flange


Bar kPa Pressure drop across valve

1 100
.0
ion 2
0.7 70 Posit
0.6 60
0.5 50
0.4 40
Measuring signal
0.3 30
.5 3.0 3.5 n4 .0
ion 2 Position ition ositio
Posit Pos P
0.2 20

.5
ion 4
Posit

0.1 10
.0
ion 5
0.07 7 Posit
0.06 6
0.05 5
.0
ion 6
0.04 4
Posit
0.03 3 Flow rate
16.8 20 30 40 50 57 l/s

60.5 72 108 144 180 205 m3/h

The X-axis indicates the recommended flow range of the valve.

The black curves are used to determine the total pressure drop across the valve at a specific handle scale setting and a
given flow rate.

The red curve is the Venturi measuring signal which indicates what differential pressure should be measured across the
Venturi orifice for a given flow.

See example on data sheet 4.4.3 for DN 20S.

4.7
BALLOREX Venturi
BALLOREX venturi
4.8 Product data sheets - DRV female
4.8.1 Product finder

DN 50S

DN 40S

DN 32S

DN 25S

DN 20S

DN 20L

DN 15S

DN 15L

Kv-value
0.08 0.1 0.2 0.3 0.4 0.6 0.8 1 2 3 4 5 6 8 10 20 30 40

Capacity
Dimension Section
[Kv-value]
0.083 - 1.62 DN 15L 4.8.2
0.261 - 2.11 DN 15S 4.8.2
0.1 - 4.26 DN 20L 4.8.3
0.325 - 4.81 DN 20S 4.8.3
0.921 - 9.94 DN 25S 4.8.4
1.95 - 13.3 DN 32S 4.8.5
2.6 - 23.3 DN 40S 4.8.6
5.37 - 35.3 DN 50S 4.8.7

4.8
BALLOREX Venturi

4.8.2 DN 15 female/female

57mm Specifications
Max. temperature 135C
Min. temperature -20C
Max. pressure 25 bar
Press ends 16 bar
76mm Marking on valve (Handle) DN, flow-version
(Valve body) DN, PN, BROEN
Connection Female thread ISO 7/1 parallel
Valve housing DR Brass CW602N CuZn36Pb2As
Ball & needle DR Brass CW602N (chrome plated)
75mm Valve handle Polyamide (PA6.6 30%GF)
104mm Sealings O-rings EPDM
Gaskets PTFE

Nom. Kv
BROEN No. Dimension
Inch [m3/h]

4350010L-001003 DN 15L 1/2 1.62

4350010S-001003 DN 15S 1/2 2.11

Accessories
BROEN No. Dimension Description

83504006-000003 15 mm x 1/2
Pre-sealed press adaptors (2 pcs), max 16 bar
83504007-000003 18 mm x 1/2

High capacity drain valve (Kv 4.5)


43500200-001003 DN 15
1/2 female/female threaded connection

4.8
Flow Diagram

BALLOREX Venturi

Bar kPa Pressure drop across valve DN 15L - Low flow


1 100

0.7 70
0.6 60
0.5 50
0.4 40

0.3 30

0.2 20 9.9
0.0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 on
n n n n n n n n n n iti
itio itio io it io it io io io io io io s
it it it it it it Po
Pos Pos P os Pos Pos P os os os os os
P P P P

0.1 10
0.08 8
0.07 7
0.06 6
0.05 5
0.04 4

0.03 3

0.02 2

0.01 1 Flow rate

0.008 0.01 0.02 0.03 0.04 0.05 0.06 0.08 0.1 0.2 l/s

28 36 72 108 144 180 216 288 360 720 l/h

Position 0.0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 9.9

Kv 0.083 0.095 0.159 0.248 0.365 0.519 0.712 0.932 1.16 1.40 1.62

Bar kPa Pressure drop across valve DN 15S - Standard flow


1 100

0.7 70
0.6 60
0.5 50
0.4 40

0.3 30

0.2 20
0.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 9.9
n n n n n
on ion io i on ion io itio on io io
sit
i sit os
it sit sit it os iti sit sit
Po Po Po os P Po
s
Po Po
Po P P

0.1 10
0.08 8
0.07 7
0.06 6
0.05 5
0.04 4

0.03 3

0.02 2

0.01 1 Flow rate

0.02 0.03 0.04 0.06 0.08 0.1 0.2 0.3 0.4 0.5 l/s

72 108 144 216 288 360 720 1,080 1,440 1,800 l/h

Position 0.0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 9.9

Kv 0.261 0.267 0.334 0.449 0.601 0.785 1.00 1.26 1.55 1.86 2.11

4.8
BALLOREX Venturi

4.8.3 DN 20 female/female

62mm Specifications
Max. temperature 135C
Min. temperature -20C
Max. pressure 25 bar
Press ends 16 bar
79mm Marking on valve (Handle) DN, flow-version
(Valve body) DN, PN, BROEN
Connection Female thread ISO 7/1 parallel
Valve housing DR Brass CW602N CuZn36Pb2As
75mm
Ball & needle DR Brass CW602N (chrome plated)
Valve handle Polyamide (PA6.6 30%GF)
106mm
Sealings O-rings EPDM
Gaskets PTFE

Nom. Kv
BROEN No. Dimension
Inch [m3/h]

4450010L-001003 DN 20L 3/4 4.26

4450010H-001003 DN 20S 3/4 4.81

Accessories
BROEN No. Dimension Description
84504006-000003 15 mm x 3/4
84504007-000003 18 mm x 3/4 Pre-sealed press adaptors (2 pcs), max 16 bar
84504008-000003 22 mm x 3/4

High capacity drain valve (Kv 4.5)


44500200-001003 DN 20
3/4 female/female threaded connection

4.8
Flow Diagram

BALLOREX Venturi

Bar kPa Pressure drop across valve DN 20L - Low flow


1 100 0
0.
n
io
sit
0.7 70 Po
0.6 60
0.5 50
0.4 40

0.3 30

0.2 20 0 0
0 0 3. 5. 0 0 0 0 9
1. 2. n 4.
0
n 6. 7. 8. 9. 9.
n n io n io n n n n n
io io it io it it io io io io io
os
it
os
it os it os os sit sit sit sit
P P P P os P P Po Po Po Po

0.1 10
0.08 8
0.07 7
0.06 6
0.05 5
0.04 4

0.03 3

0.02 2

0.01 1 Flow rate


0.02 0.03 0.04 0.06 0.08 0.1 0.2 0.3 0.4 0.5 l/s

72 108 144 216 188 360 720 1,080 1,440 1,800 l/h

Position 0.0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 9.9

Kv 0.094 0.250 0.541 0.870 1.22 1.60 2.03 2.53 3.07 3.67 4.26

Bar

1
kPa

100
Pressure drop across valve DN 20S - Standard flow
0,7 70
0,6 60
0,5 50
0,4 40

0,3 30

0,2 20 0 0 9
0 0 2. 3. 0 0 0 0 0 0
0. 1. 4. 5. 6. 7. 8. 9. 9.
on on on on on on on on on on on
s iti s iti siti s iti siti siti s iti s iti siti s iti s iti
Po Po Po Po Po Po Po Po Po Po Po

0,1 10
0,08 8
0,07 7
0,06 6
0,05 5
0,04 4

0,03 3

0,02 2

0,01 1
Flow rate

0.03 0.04 0.06 0.08 0.1 0.2 0.3 0.4 0.7 l/s

108 144 216 288 360 720 1,080 1,440 2,520 l/h

Position 0.0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 9.9

Kv 0.325 0.494 0.778 1.12 1.50 1.93 2.41 2.93 3.48 4.10 4.81

4.8
BALLOREX Venturi

4.8.4 DN 25 female/female

75mm Specifications
Max. temperature 135C
Min. temperature -20C
Max. pressure 25 bar
Press ends 16 bar
83mm Marking on valve (Handle) DN, flow-version
(Valve body) DN, PN, BROEN
Connection Female thread ISO 7/1 parallel
Valve housing DR Brass CW602N CuZn36Pb2As
75mm
Ball & needle DR Brass CW602N (chrome plated)
Valve handle Polyamide (PA6.6 30%GF)
113mm
Sealings O-rings EPDM
Gaskets PTFE

Nom. Kv
BROEN No. Dimension
Inch [m3/h]

4550010S-001003 DN 25S 1 9.94

Accessories
BROEN No. Dimension Description

High capacity drain valve (Kv 4.5)


45500200-001003 DN 25
1 female/female threaded connection

4.8
Flow Diagram

BALLOREX Venturi

DN 25S - Standard flow


Bar kPa Pressure drop across valve

1 100

0.7 70
0.6 60
0.5 50

0.4 40

0.3 30

0.2 20
0.0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 9.9
ion io
n ion ion ion io
n ion ion ion ion ion
sit sit sit sit sit sit sit sit sit sit sit
Po Po Po Po Po Po Po Po Po Po Po

0.1 10

0.08 8
0.07 7
0.06 6
0.05 5

0.04 4

0.03 3

0.02 2

0.01 1 Flow rate

0.08 0.1 0.2 0.3 0.4 0.5 0.6 0.8 1 2 l/s

288 360 720 1080 1440 1,080 2,160 2,880 3,600 7,200 l/h

Position 0.0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 9.9

Kv 0.921 1.26 1.86 2.58 3.38 4.24 5.21 6.29 7.49 8.78 9.94

4.8
BALLOREX Venturi

4.8.5 DN 32 female/female

88mm Specifications
Max. temperature 135C
Min. temperature -20C
Max. pressure 25 bar
Press ends 16 bar
109mm Marking on valve (Handle) DN, flow-version
(Valve body) DN, PN, BROEN
Connection Female thread ISO 7/1 parallel
Valve housing DR Brass CW602N CuZn36Pb2As
122mm
Ball & needle DR Brass CW602N (chrome plated)
Valve handle Polyamide (PA6.6 30%GF)
166mm
Sealings O-rings EPDM
Gaskets PTFE

Nom. Kv
BROEN No. Dimension
Inch m3/h

4650010S-001003 DN 32S 1 1/4 13.3

4.8
Flow Diagram

BALLOREX Venturi

DN 32H - High flow


Bar kPa Pressure drop across valve
1 100

0.7 70
0.6 60
0.5 50
0.4 40

0.3 30

0.2 20

0.1 10

0.08 8
0.07 7
0.06 6
0.05 5
0.0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 9.9
n n n n n n n n
0.04 4 ion ion ion itio itio itio
itio itio itio itio itio
sit sit sit os os os os os os os os
Po Po Po P P P P P P P P
0.03 3

0.02 2

0.01 1 Flow rate


0.1 0.2 0.3 0.4 0.5 0.6 0.8 1 2 l/s

360 720 1,080 1,440 1,800 2,160 2,880 3,600 7,200 l/h

Position 0.0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 9.9

Kv 1.95 2.32 3.05 3.97 5.00 6.12 7.36 8.70 10.1 11.7 13.3

4.8
BALLOREX Venturi

4.8.6 DN 40 female/female

98mm Specifications
Max. temperature 135C
Min. temperature -20C
Max. pressure 25 bar
Press ends 16 bar
113mm Marking on valve (Handle) DN, flow-version
(Valve body) DN, PN, BROEN
Connection Female thread ISO 7/1 parallel
Valve housing DR Brass CW602N CuZn36Pb2As
Ball & needle DR Brass CW602N (chrome plated)
122mm
Valve handle Polyamide (PA6.6 30%GF)
171mm
Sealings O-rings EPDM
Gaskets PTFE

Nom. Kv
BROEN No. Dimension
Inch [m3/h]

4750010S-001003 DN 40S 1 1/2 23.3

4.8
Flow Diagram

BALLOREX Venturi

DN 40S - Standard flow


Bar kPa Pressure drop across valve
1 100

0.7 70
0.6 60
0.5 50

0.4 40

0.3 30

0.2 20

0.1 10

0.08 8
0.07 7
0.06 6
0.05 5

0.04 4
0.0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 9.9
n n n n n n n
ion ion ion itio ion itio itio
itio itio itio itio
0.03 3 sit sit sit os sit os os os os os os
Po Po Po P Po P P P P P P

0.02 2

0.01 1 Flow rate


0.1 0.2 0.3 0.4 0.5 0.6 0.8 1 2 3 l/s

360 720 108 144 1,800 2,160 2,880 3,600 7,200 10,800 l/h

Position 0.0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 9.9

Kv 2.60 3.48 4.86 6.50 8.31 10.3 12.4 14.6 17.1 20.0 23.3

4.8
BALLOREX Venturi

4.8.7 DN 50 female/female

115mm Specifications
Max. temperature 135C
Min. temperature -20C
Max. pressure 25 bar
Press ends 16 bar
120mm Marking on valve (Handle) DN, flow-version
(Valve body) DN, PN, BROEN
Connection Female thread ISO 7/1 parallel
Valve housing DR Brass CW602N CuZn36Pb2As
122mm
Ball & needle DR Brass CW602N (chrome plated)
Valve handle Polyamide (PA6.6 30%GF)
180mm
Sealings O-rings EPDM
Gaskets PTFE

Nom. Kv
BROEN No. Dimension
Inch [m3/h]

4850010S-001003 DN 50S 2 35.3

4.8
Flow Diagram

BALLOREX Venturi

DN 50S - Standard flow


Bar kPa Pressure drop across valve

1 100

0.7 70
0.6 60
0.5 50

0.4 40

0.3 30

0.2 20

0.1 10

0.08 8
0.07 7
0.0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 9.9
0.06 6 on n n n n n n n
i ion itio itio itio ion itio itio itio io ion
sit sit sit it sit
0.05 5 Po os os os os os os os
Po P P P Po P P P P Po
0.04 4

0.03 3

0.02 2

0.01 1 Flow rate


0.3 0.4 0.5 0.6 0.8 1 2 3 4 5 6 8 l/s

108 144 180 216 288 360 720 1,080 1,440 2,160 2,880 l/h

Position 0.0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 9.9

Kv 5.37 6.95 9.25 11.6 14.0 16.8 20.0 23.4 26.9 30.7 35.3

4.8
BALLOREX Venturi
BALLOREX venturi
4.9 Product data sheets - DRV compression
4.9.1 Product finder

DN 50S

DN 40S

DN 32S

DN 25S

DN 20S

DN 20L

DN 15S

DN 15L

Kv-value
0.08 0.1 0.2 0.3 0.4 0.6 0.8 1 2 3 4 5 6 8 10 20 30 40

Capacity
Dimension Section
[Kv-value]
0.083 - 1.62 DN 15L 4.9.2
0.261 - 2.11 DN 15S 4.9.2
0.1 - 4.26 DN 20L 4.9.3
0.325 - 4.81 DN 20S 4.9.3
0.921 - 9.94 DN 25S 4.9.4
1.95 - 13.3 DN 32S 4.9.5
2.6 - 23.3 DN 40S 4.9.6
5.37 - 35.3 DN 50S 4.9.7

4.9
BALLOREX Venturi

4.9.2 DN 15 compression/compression

62mm
Specifications
Max. temperature 135C
Min. temperature -20C
Max. pressure 5 bar
Marking on valve (Handle) DN, flow-version
76mm (Valve body) DN, PN, BROEN
Connection Compression EN 1254-2
Valve housing DR Brass CW602N CuZn36Pb2As
Ball & needle DR Brass CW602N (chrome plated)
75mm Valve handle Polyamide (PA6.6 30%GF)
Sealings O-rings EPDM
128mm
Gaskets PTFE

Compression connections are not recommendeded for cooling applications.
Instead press or threaded connection are recommended.

Nom. Kv
BROEN No. Dimension
Inch [m3/h]
4350110L-001063 DN 15L 15 mm 1,62
4350110S-001063 DN 15S 15 mm 2,11

Accessories
BROEN No. Dimension Description

High capacity drain valve (Kv 4.5)


43500200-001003 DN 15
1/2 female/female threaded connection

4.9
Flow Diagram

BALLOREX Venturi

Bar kPa Pressure drop across valve DN 15L - Low flow


1 100

0.7 70
0.6 60
0.5 50
0.4 40

0.3 30

0.2 20 9.9
0.0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 n
on on n on on n n n n n io
iti iti itio iti iti it io it io itio itio itio sit
s s os Po
s s os os os os os Po
Po Po P Po P P P P P

0.1 10
0.08 8
0.07 7
0.06 6
0.05 5
0.04 4

0.03 3

0.02 2

0.01 1 Flow rate

0.008 0.01 0.02 0.03 0.04 0.05 0.06 0.08 0.1 0.2 l/s

28 36 72 108 144 180 216 288 360 720 l/h

Position 0.0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 9.9

Kv 0.083 0.095 0.159 0.248 0.365 0.519 0.712 0.932 1.16 1.40 1.62

Bar kPa Pressure drop across valve DN 15S - Standard flow


1 100

0.7 70
0.6 60
0.5 50
0.4 40

0.3 30

0.2 20
0.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 9.9
on
n n n n n on n n n
i itio it io
itio itio it io siti itio itio
sit
io
sit os os os os os Po os os
Po P P P P P P P Po

0.1 10
0.08 8
0.07 7
0.06 6
0.05 5
0.04 4

0.03 3

0.02 2

0.01 1 Flow rate

0.02 0.03 0.04 0.06 0.08 0.1 0.2 0.3 0.4 0.5 l/s

72 108 144 216 288 360 720 1,080 1,440 1,800 l/h

Position 0.0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 9.9

Kv 0.261 0.267 0.334 0.449 0.601 0.785 1.00 1.26 1.55 1.86 2.11

4.9
BALLOREX Venturi

4.9.3 DN 20 compression/compression

67mm
Specifications
Max. temperature 135C
Min. temperature -20C
Max. pressure 5 bar
Marking on valve (Handle) DN, flow-version
79mm (Valve body) DN, PN, BROEN
Connection Compression EN 1254-2
Valve housing DR Brass CW602N CuZn36Pb2As
Ball & needle DR Brass CW602N (chrome plated)
75mm Valve handle Polyamide (PA6.6 30%GF)
Sealings O-rings EPDM
132mm
Gaskets PTFE

Compression connections are not recommendeded for cooling applications.
Instead press or threaded connection are recommended.

Nom. Kv
BROEN No. Dimension
Inch [m3/h]
4450110L-001063 DN 20L 22 mm 4.26

4450110S-001063 DN 20S 22 mm 4.81

Accessories
BROEN No. Dimension Description

High capacity drain valve for BALLOREX Venturi (Kv 4.5)


44500200-001003 DN 20
3/4 female/female threaded connection

4.9
Flow Diagram

BALLOREX Venturi

Bar kPa Pressure drop across valve DN 20L - Low flow


1 100 0
0.
on
s iti
0.7 70 Po
0.6 60
0.5 50
0.4 40

0.3 30

0.2 20 0 0
0 0 3. 5. 0 0 0 0 9
1. 2. n 4.
0
n 6. 7. 8. 9. 9.
n n io n io n n n n n
io io it io it it io io io io io
os
it
os
it os it os os sit sit sit sit
P P P P os P P Po Po Po Po

0.1 10
0.08 8
0.07 7
0.06 6
0.05 5
0.04 4

0.03 3

0.02 2

0.01 1 Flow rate

0.02 0.03 0.04 0.06 0.08 0.1 0.2 0.3 0.4 0.5 l/s

72 108 144 216 188 360 720 1,080 1,440 1,800 l/h

Position 0.0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 9.9

Kv 0.094 0.250 0.541 0.870 1.22 1.60 2.03 2.53 3.07 3.67 4.26

Bar kPa Pressure drop across valve DN 20S - Standard flow


1 100

0.7 70
0.6 60
0.5 50
0.4 40

0.3 30

0.2 20 0 0 9
0 0 2. 3. 0 0 0 0 0 0
0. 1. 4. 5. 6. 7. 8. 9. 9.
on on on on on on on on on on on
s iti siti siti siti siti siti s iti siti siti s iti s iti
Po Po Po Po Po Po Po Po Po Po Po

0.1 10
0.08 8
0.07 7
0.06 6
0.05 5
0.04 4

0.03 3

0.02 2

0.01 1 Flow rate

0.03 0.04 0.06 0.08 0.1 0.2 0.3 0.4 0.7 l/s

108 144 216 288 360 720 1,080 1,440 2,520 l/h

Position 0.0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 9.9

Kv 0.325 0.494 0.778 1.12 1.50 1.93 2.41 2.93 3.48 4.10 4.81

4.9
BALLOREX Venturi

4.9.4 DN 25 compression/compression

81mm
Specifications
Max. temperature 135C
Min. temperature -20C
Max. pressure 5 bar
Marking on valve (Handle) DN, flow-version
83mm (Valve body) DN, PN, BROEN
Connection Compression EN 1254-2
Valve housing DR Brass CW602N CuZn36Pb2As
Ball & needle DR Brass CW602N (chrome plated)
75mm Valve handle Polyamide (PA6.6 30%GF)
Sealings O-rings EPDM
140mm
Gaskets PTFE

Compression connections are not recommendeded for cooling applications.
Instead press or threaded connection are recommended.

Nom. Kv
BROEN No. Dimension
Inch [m3/h]

4550110S-001063 DN 25S 28 mm 9.94

Accessories
BROEN No. Dimension Description

High capacity drain valve for BALLOREX Venturi (Kv 4,5)


45500200-001003 DN 25
1 female/female threaded connection

4.9
Flow Diagram

BALLOREX Venturi

DN 25S - Standard flow


Bar kPa Pressure drop across valve

1 100

0.7 70
0.6 60
0.5 50

0.4 40

0.3 30

0.2 20
0.0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 9.9
ion io
n ion ion ion io
n ion ion ion ion ion
sit sit sit sit sit sit sit sit sit sit sit
Po Po Po Po Po Po Po Po Po Po Po

0.1 10

0.08 8
0.07 7
0.06 6
0.05 5

0.04 4

0.03 3

0.02 2

0.01 1 Flow rate

0.08 0.1 0.2 0.3 0.4 0.5 0.6 0.8 1 2 l/s

288 360 720 1080 1,440 1,080 2,160 2,880 3,600 7,200 l/h

Position 0.0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 9.9

Kv 0.921 1.26 1.86 2.58 3.38 4.24 5.21 6.29 7.49 8.78 9.94

4.9
BALLOREX Venturi

4.9.5 DN 32 compression/compression

93mm
Specifications
Max. temperature 135C
Min. temperature -20C
Max. pressure 5 bar
Marking on valve (Handle) DN, flow-version
109mm (Valve body) DN, PN, BROEN
Connection Compression EN 1254-2
Valve housing DR Brass CW602N CuZn36Pb2As
Ball & needle DR Brass CW602N (chrome plated)
122mm Valve handle Polyamide (PA6.6 30%GF)
Sealings O-rings EPDM
199mm
Gaskets PTFE

Compression connections are not recommendeded for cooling applications.
Instead press or threaded connection are recommended.

Nom. Kv
BROEN No. Dimension
Inch [m3/h]

4650110S-001063 DN 32S 35 mm 13.3

4.9
Flow Diagram

BALLOREX Venturi

DN 32S - Standard flow


Bar kPa Pressure drop across valve
1 100

0.7 70
0.6 60
0.5 50
0.4 40

0.3 30

0.2 20

0.1 10

0.08 8
0.07 7
0.06 6
0.05 5
0.0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 9.9
n n n n n n n n
0.04 4 ion ion ion itio itio itio
itio itio itio it io itio
sit sit sit os os os os os os os os
Po Po Po P P P P P P P P
0.03 3

0.02 2

0.01 1 Flow rate


0,1 0.2 0.3 0.4 0.5 0.6 0.8 1 2 l/s

360 720 1,080 1,440 1,800 2,160 2,880 3,600 7,200 l/h

Position 0.0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 9.9

Kv 1.95 2.32 3.05 3.97 5.00 6.12 7.36 8.70 10.1 11.7 13.3

4.9
BALLOREX Venturi

4.9.6 DN 40 compression/compression

107mm
Specifications
Max. temperature 135C
Min. temperature -20C
Max. pressure 5 bar
Marking on valve (Handle) DN, flow-version
113mm (Valve body) DN, PN, BROEN
Connection Compression EN 1254-2
Valve housing DR Brass CW602N CuZn36Pb2As
Ball & needle DR Brass CW602N (chrome plated)
122mm Valve handle Polyamide (PA6.6 30%GF)
Sealings O-rings EPDM
211mm
Gaskets PTFE

Compression connections are not recommendeded for cooling applications.
Instead press or threaded connection are recommended.

Nom. Kv
BROEN No. Dimension
Inch [m3/h]

4750110S-001063 DN 40S 42 mm 23.3

4.9
Flow Diagram

BALLOREX Venturi

DN 40S - Standard flow


Bar kPa Pressure drop across valve
1 100

0.7 70
0.6 60
0.5 50

0.4 40

0.3 30

0.2 20

0.1 10

0.08 8
0.07 7
0.06 6
0.05 5

0.04 4
0.0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 9.9
n n n n n n n
ion ion ion itio ion itio itio
itio itio itio itio
0.03 3 sit sit sit os sit os os os os os os
Po Po Po P Po P P P P P P

0.02 2

0.01 1 Flow rate


0.1 0.2 0.3 0.4 0.5 0.6 0.8 1 2 3 l/s

360 720 108 144 1,800 2,160 2,880 3,600 7,200 10,800 l/h

Position 0.0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 9.9

Kv 2.60 3.48 4.86 6.50 8.31 10.3 12.4 14.6 17.1 20.0 23.3

4.9
BALLOREX Venturi

4.9.7 DN 50 compression/compression

126mm
Specifications
Max. temperature 135C
Min. temperature -20C
Max. pressure 5 bar
Marking on valve (Handle) DN, flow-version
120mm (Valve body) DN, PN, BROEN
Connection Compression EN 1254-2
Valve housing DR Brass CW602N CuZn36Pb2As
Ball & needle DR Brass CW602N (chrome plated)
122mm Valve handle Polyamide (PA6.6 30%GF)
Sealings O-rings EPDM
224mm
Gaskets PTFE

Compression connections are not recommendeded for cooling applications.
Instead press or threaded connection are recommended.

Nom. Kv
BROEN No. Dimension
Inch m3/h

4850110S-001063 DN 50S 54 mm 35.3

4.9
Flow Diagram

BALLOREX Venturi

DN 50S - Standard flow


Bar kPa Pressure drop across valve

1 100

0.7 70
0.6 60
0.5 50

0.4 40

0.3 30

0.2 20

0.1 10

0.08 8
0.07 7
0.0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 9.9
0.06 6 on n n n n n n n
i ion itio itio itio ion itio itio itio io ion
sit sit sit it sit
0.05 5 Po os os os os os os os
Po P P P Po P P P P Po
0.04 4

0.03 3

0.02 2

0.01 1 Flow rate


0.3 0.4 0.5 0.6 0.8 1 2 3 4 5 6 8 l/s

108 144 180 216 288 360 720 1,080 1,440 2,160 2,880 l/h

Position 0.0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 9.9

Kv 5.37 6.95 9.25 11.6 14.0 16.8 20.0 23.4 26.9 30.7 35.3

4.9
BALLOREX Venturi
BALLOREX venturi
4.10 Product data sheets - DRV flange
4.10.1 Product finder

DN 300

DN 250

DN 200

DN 150

DN 125

DN 100

DN 80

DN 65

1 2 3 4 5 6 8 10 20 30 40 50 60 80 100 200 300 400 600 800 1000 l/s

3.6 7.2 10.8 14.4 18.0 21.6 28.8 36 72 108 144 180 216 288 360 720 1,080 1,440 2,160 2,880 3,600 m3/h

Capacity
Dimension Section
[Kv-value]
18.34 - 148 DN 65 4.10.2
28.3 - 237 DN 80 4.10.3
14.1 - 603 DN 100 4.10.4
30.5 - 888 DN 125 4.10.5
71.9 - 2,340 DN 150 4.10.6
127 - 2,845 DN 200 4.10.7
234 - 4,549 DN 250 4.10.8
819 - 7,761 DN 300 4.10.9

Note!
Dimensions DN 350 - 600 are available on request.

4.10
BALLOREX Venturi

4.10.2 DN 65 flange/flange

Specifications
160mm Max. temperature 120C
Min. temperature -20C
Max. pressure PN 16
Marking on valve (Butterfly gearbox) Valve type, DN and Kvm
269mm Connection Flange: BS 4504 - PN16
Butterfly valve body Cast iron, fully lugged (ASTMA A126 KL.B)
185mm Disc Stainless steel (ASTM A351)
45mm
Shaft Stainless steel (ASTM A276)
Sealings EPDM and NBR 1

Nom. Kv
BROEN No. Dimension
Inch [m3/h]

3937310-080009 DN 65 2 1/2 1.48

4.10
Flow Diagram

BALLOREX Venturi

DN 65 flange/flange
Bar kPa Pressure drop across valve

1 100

0.7 70
0.6 60
0.5 50

0.4 40

0.3 30

0.2 20
5 0 5 0 5 0 0
2.
0 2. 3. 3. 4. 4. 5. 6.
n io
n io
n
io
n
io
n
io
n on on
sit
io
sit sit sit sit sit is ti siti
Po Po Po Po Po Po Po Po

0.1 10

0.08 8
0.07 7
0.06 6
0.05 5

0.04 4

0.03 3

0.02 2

0.01 1 Flow rate


1 2 3 4 5 6 8 10 20 30 l/s

0.36 0.72 1.08 1.44 1.8 2.16 2.88 3.6 7.2 10.8 m3/h

Position 2 3 4 5 6

Kv 18.34 45.9 92.5 136 148

Note!
Settings below 2 are not recommended.

4.10
BALLOREX Venturi

4.10.3 DN 80 flange/flange

Specifications
160mm Max. temperature 120C
Min. temperature -20C
Max. pressure PN 16
Marking on valve (Butterfly gearbox) Valve type, DN and Kvm
275mm
Connection Flange: BS 4504 - PN16
Butterfly valve body Cast iron, fully lugged (ASTMA A126 KL.B)
200mm
Disc Stainless steel (ASTM A351)
46mm Shaft Stainless steel (ASTM A276)
Sealings EPDM and NBR 1

Nom. Kv
BROEN No. Dimension
Inch [m3/h]

3937910-080009 DN 80 3 2.37

4.10
Flow Diagram

BALLOREX Venturi

DN 80 flange/flange
Bar kPa Pressure drop across valve

1 100

0.7 70
0.6 60
0.5 50

0.4 40

0.3 30
2.0 2.5 3.0 3.5 4.0 4.5 5.0
n n n n n n n
itio itio it io itio itio it io itio
Pos P os Pos Pos Pos Pos Pos
0.2 20

0.1 10

0.08 8
0.07 7
0.06 6
0.05 5

0.04 4

0.03 3

0.02 2

0.01 1 Flow rate


2 3 4 5 6 8 10 20 30 40 50 l/s

0.72 1.08 1.44 1.8 2.16 2.88 3.6 7.2 10.8 14.4 18 m3/h

Position 2 3 4 5 6

Kv 28.3 62.5 128 222 237

Note!
Settings below 2 are not recommended.

4.10
BALLOREX Venturi

4.10.4 DN 100 flange/flange

Specifications
160mm Max. temperature 120C
Min. temperature -20C
Max. pressure PN 16
Marking on valve (Butterfly gearbox) Valve type, DN and Kvm
297mm Connection Flange: BS 4504 - PN16
Butterfly valve body Cast iron, fully lugged (ASTMA A126 KL.B)
220mm Disc Stainless steel (ASTM A351)
99mm
Shaft Stainless steel (ASTM A276)
52mm
Sealings EPDM and NBR 1

76mm

75mm

164mm

Nom. Kv
BROEN No. Dimension
Inch [m3/h]

3938510-080009 DN 100 4 6.03

4.10
Flow Diagram

BALLOREX Venturi

DN 100 flange/flange
Bar kPa Pressure drop across valve
1 100

0.7 70
0.6 60
0.5 50
2.0 2.5 3.0 3.5 4.0 4.5 5.0
0.4 40 io
n
io
n ion io
n
io
n on ion
sit sit sit sit sit s iti sit
Po Po Po Po Po Po Po
0.3 30

5.5
0.2 20 i on
sit
Po

0
6.
n
it io
0.1 10 Pos
0.08 8
0.07 7
0.06 6
0.05 5

0.04 4

0.03 3

0.02 2

0.01 1 Flow rate

2 3 4 5 6 8 10 20 30 40 50 60 l/s

0.72 1.08 1.44 1.8 2.16 2.88 3.6 7.2 10.8 14.4 18 21.6 m3/h

Position 2 3 4 5 6

Kv 14.1 58.3 139 315 603

Note!
Settings below 2 are not recommended.

4.10
BALLOREX Venturi

4.10.5 DN 125 flange/flange

Specifications
160mm
Max. temperature 120C
Min. temperature -20C
Max. pressure PN 16
Marking on valve (Butterfly gearbox) Valve type, DN and Kvm
307mm Connection Flange: BS 4504 - PN16
Butterfly valve body Cast iron, fully lugged (ASTMA A126 KL.B)
250mm Disc Stainless steel (ASTM A351)
Shaft Stainless steel (ASTM A276)
55mm
Sealings EPDM and NBR 1

Nom. Kv
BROEN No. Dimension
Inch [m3/h]

3939110-080009 DN 125 5 8.88

4.10
Flow Diagram

BALLOREX Venturi

DN 125 flange/flange
Bar kPa Pressure drop across valve
1 100

0.7 70
0.6 60
0.5 50

0.4 40

0.3 30
2.0 2.5 3.0 3.5 4.0 4.5
ion ion ion ion ion ion
sit sit sit sit sit sit 5.0
0.2 20 Po Po Po Po Po Po on
i
sit
Po

0.1 10 6.0
i on
sit
0.08 8 Po
0.07 7
0.06 6
0.05 5

0.04 4

0.03 3

0.02 2

0.01 1 Flow rate


3 4 5 6 8 10 20 30 40 50 60 80 l/s

1.08 1.44 1.8 2.16 2.88 3.6 7.2 10.8 14.4 18 21.6 28.8 m3/h

Position 2 3 4 5 6

Kv 30.5 121 275 610 888

Note!
Settings below 2 are not recommended.

4.10
BALLOREX Venturi

4.10.6 DN 150 flange/flange

Specifications
160mm
Max. temperature 120C
Min. temperature -20C
Max. pressure PN 16
Marking on valve (Butterfly gearbox) Valve type, DN and Kvm
320mm Connection Flange: BS 4504 - PN16
Butterfly valve body Cast iron, fully lugged (ASTMA A126 KL.B)
285mm Disc Stainless steel (ASTM A351)
Shaft Stainless steel (ASTM A276)
56mm
Sealings EPDM and NBR 1

Nom. Kv
BROEN No. Dimension
Inch [m3/h]

3939710-080009 DN 150 6 2.34

4.10
Flow Diagram

BALLOREX Venturi

DN 150 flange/flange
Bar kPa Pressure drop across valve
1 100

0.7 70
0.6 60
0.5 50

0.4 40

0.3 30
2.0 2.5 3.0 3.5 4.0 4.5 5.0
on io
n ion on ion io
n
io
n
s iti sit sit s iti sit sit sit
0.2 20 Po Po Po Po Po Po Po

0.1 10
6.0
n
0.08 8 it io
0.07 7 P os
0.06 6
0.05 5

0.04 4

0.03 3

0.02 2

0.01 1 Flow rate


7 10 20 30 40 50 60 80 100 200 l/s

2.52 3.6 7.2 10.8 14.4 18 21.6 28.8 36 72 m3/h

Position 2 3 4 5 6

Kv 71.9 201 396 1288 2341

Note!
Settings below 2 are not recommended.

4.10
BALLOREX Venturi

4.10.7 DN 200 flange/flange

Specifications
150mm
Max. temperature 120C
Min. temperature -20C
Max. pressure PN 16
Marking on valve (Butterfly gearbox) Valve type, DN and Kvm
354mm Connection Flange: BS 4504 - PN16
Butterfly valve body Cast iron, fully lugged (ASTMA A126 KL.B)
340mm Disc Stainless steel (ASTM A351)
Shaft Stainless steel (ASTM A276)
60mm
Sealings EPDM and NBR 1

Nom. Kv
BROEN No. Dimension
Inch [m3/h]

3940210-080009 DN 200 8 2.85

4.10
Flow Diagram

BALLOREX Venturi

DN 200 flange/flange
Bar kPa Pressure drop across valve

1 100

0.7 70
0.6 60
0.5 50

0.4 40

0.3 30

0.2 20

0.1 10

0.08 8 2.0 2.5 3.0 3.5 4.0 4.5 5.0


on on n n
0.07 7 i ion ion ion i itio itio
sit sit sit sit sit os os
0.06 6 Po Po Po Po Po P P 6.0
n
itio
0.05 5 Pos
0.04 4

0.03 3

0.02 2

0.01 1 Flow rate


8 10 20 30 40 50 60 80 100 200 l/s

2.88 3.6 7.2 10.8 14.4 18 21.6 28.8 36 72 m3/h

Position 2 3 4 5 6

Kv 127 353 726 1806 2845

Note!
Settings below 2 are not recommended.

4.10
BALLOREX Venturi

4.10.8 DN 250 flange/flange

Specifications
Max. temperature 120C
190mm
Min. temperature -20C
Max. pressure PN 16
Marking on valve (Butterfly gearbox) Valve type, DN and Kvm
445mm Connection Flange: BS 4504 - PN16
Butterfly valve body Cast iron, fully lugged (ASTMA A126 KL.B)
405mm
Disc Stainless steel (ASTM A351)
Shaft Stainless steel (ASTM A276)
68mm Sealings EPDM and NBR 1

Nom. Kv
BROEN No. Dimension
Inch [m3/h]

3940810-080009 DN 250 10 4.55

4.10
Flow Diagram

BALLOREX Venturi

DN 250 flange/flange
Bar kPa Pressure drop across valve
1 100

0.7 70
0.6 60
0.5 50

0.4 40

0.3 30

0.2 20
2.5 3.0 3.5 4.0 4.5 5.0 6.
0
0

on
2.

ion i ion ion io


n ion ion
n

sit sit sit sit sit sit sit


io

Po
sit

Po Po Po Po Po Po
Po

0.1 10

0.08 8
0.07 7
0.06 6
0.05 5

0.04 4

0.03 3

0.02 2

0.01 1 Flow rate


20 30 40 60 80 100 200 300 400 600 l/s

7.2 10.8 14.4 21.6 28.8 36 72 10.8 14.4 21.6 m3/h

Position 2 3 4 5 6

Kv 234 642 1513 3297 4549

Note!
Settings below 2 are not recommended.

4.10
BALLOREX Venturi

4.10.9 DN 300 +flange/flange

Specifications
190mm Max. temperature 120C
Min. temperature -20C
Max. pressure PN 16
Marking on valve (Butterfly gearbox) Valve type, DN and Kvm
490mm Connection Flange: BS 4504 - PN16
Butterfly valve body Cast iron, fully lugged (ASTMA A126 KL.B)
460mm Disc Stainless steel (ASTM A351)
Shaft Stainless steel (ASTM A276)
78mm
Sealings EPDM and NBR 1

Nom. Kv
BROEN No. Dimension
Inch [m3/h]

3941410-080009 DN 300 12 7.77

4.10
Flow Diagram

BALLOREX Venturi

DN 300 flange/flange
Bar kPa Pressure drop across valve
1 100

0.7 70
0.6 60
0.5 50

0.4 40

0.3 30

0.2 20
1.5 2.0 2.5 3.0 3.5 4.0 4.5 5.0 6.0
on on on on n n
i ion i i ion ion i itio itio
sit sit sit sit sit sit sit os os
Po Po Po Po Po Po Po P P

0.1 10

0.08 8
0.07 7
0.06 6
0.05 5

0.04 4

0.03 3

0.02 2

0.01 1 Flow rate

40 50 60 80 100 200 300 400 600 800 1000 l/s

14.4 18 21.6 28.8 36 72 108 144 216 288 360 m3/h

Position 2 3 4 5 6

Kv 819 1422 2537 5331 7761

Note!
Settings below 2 are not recommended.

4.10
BALLOREX Venturi
4.11 Applications
The BALLOREX Venturi is a manual balancing valve with distinct advantages, such as direct flow measurement, flexible
installation and easy flow setting. The BALLOREX Venturi can be used in numerous types of applications. The most common
ones are illustrated below.

BMS

Manual balancing on terminal units with 2-port control valves


When proportionally balanced, the BALLOREX Venturi valves will provide hydronic balance and ensure that all terminal
units have sufficient flow in maximum load situations.

A 2-port control valve connected to the BMS is installed to control the flow.

4.11
BALLOREX venturi
4.11 Applications

Manual balancing on terminal units


with 3-port control valves

When proportionally balanced, the


BALLOREX Venturi valves will provide
hydronic balance and ensure that all
terminal units have sufficient flow in
maximum load situations.

The DRV-type valve is used to equalize


the pressure drop across the terminal
unit and to provide the right control
BMS authority to the 3-port valve.

A 3-port control valve connected to


the BMS is installed to control the flow.

One pipe heating system


The BALLOREX Venturi installed on
the riser in a one pipe heating system
to ensure all users have sufficient
flow and good thermal comfort.

4.11
BALLOREX Venturi
4.11 Applications

BMS

Under floor heating

In an underfloor heating system BALLOREX Venturi will ensure that all circuits have sufficient flow in maximum load
situations.
Actuators connected to the BMS control the flow in each room.

4.11
Kv-values vs. pre-setting values
5.0 6.0 7.0 8.0 9.0 9.9 Specific valve settings
BALLOREX Venturi DN 15 - 50
0,1 0,2 0,3 0,4 0,5 0,6 0,7 0,8 0,9 1,0 2,0 3,0 4,0 5,0 6,0 7,0 8,0 9,0 10 20 30

DN 50 0.0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 9.9

DN 40 0.0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 9.9

DN 32 0.0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 9.9
0.0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 9.9
DN 25
0.0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.9

0.0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 9.9
DN 20 0.0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 9.9
BALLOREX venturi
4.12 Conversion charts

1.0 2.0 3.0 4.0 5.0 6 9.9

1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 9.9
DN 15 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 9.9
3.0 4.0 5.0 6.0 7.0 9.9

0,1 0,2 0,3 0,4 0,5 0,6 0,7 0,8 0,9 1,0 2,0 3,0 4,0 5,0 6,0 7,0 8,0 9,0 10 20 30
Kv-value

4.12
4.12
Kv- converter Danfoss MSV BD LENO to BALLOREX Venturi

1 2 3 4 5 6 7 8 9 10
DN 50
0.0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 9.9

DN 40 1 2 3 4 5 6 7 8 9 10
0.0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 9.9

1 2 3 4 5 6 7 8 9 10
DN 32
0.0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 9.9
1 2 3 4 5 6 7
DN 25 0.0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 9.9
BALLOREX Venturi
4.12 Conversion charts

0.0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.9

1 2 3 4 5 6 7
0.0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 9.9
DN 20 0.0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 9.9
1.0 2.0 3.0 4.0 5.0 6 9.9
1 2 3 4 5 6 7
1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 9.9
DN 15 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 9.9
3.0 4.0 5.0 6.0 7.0 9.9
DN 10 1 2 3 4 5 6 7

0,1 0,2 0,3 0,4 0,5 0,6 0,7 0,8 0,9 1,0 2,0 3,0 4,0 5,0 6,0 7,0 8,0 9,0 10 20 30 40
Kv-value
5.0 6.0 7.0 8.0 9.0 9.9 BROEN BALLOREX Venturi
4 5 6 7 Oventrop Hydrocontrol R

Specific valve settings


Kv- converter MMA STV to BALLOREX Venturi

1 2 3 4 5 6 7 8 9 10
DN 50
0.0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 9.9

DN 40 1 2 3 4 5 6 7 8 9 10
BALLOREX venturi

0.0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 9.9
4.12 Conversion charts

1 2 3 4 5 6 7 8 9 10
DN 32
0.0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 9.9
1 2 3 4 5 6 7
DN 25 0.0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 9.9
0.0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.9

1 2 3 4 5 6 7
0.0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 9.9
DN 20 0.0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 9.9
1.0 2.0 3.0 4.0 5.0 6 9.9
1 2 3 4 5 6 7
1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 9.9
DN 15 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 9.9
3.0 4.0 5.0 6.0 7.0 9.9
DN 10 1 2 3 4 5 6 7

0,1 0,2 0,3 0,4 0,5 0,6 0,7 0,8 0,9 1,0 2,0 3,0 4,0 5,0 6,0 7,0 8,0 9,0 10 20 30 40
Kv-value
5.0 6.0 7.0 8.0 9.0 9.9 BROEN BALLOREX Venturi
4 5 6 7 Oventrop Hydrocontrol R

Specific valve settings

4.12
4.12
Kv- converter Oventrop Hydrocontrol R to BALLOREX Venturi

1 2 3 4 5 6 7 8 9 10
DN 50
0.0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 9.9

DN 40 1 2 3 4 5 6 7 8 9 10
0.0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 9.9

1 2 3 4 5 6 7 8 9 10
DN 32
0.0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 9.9
BALLOREX Venturi

1 2 3 4 5 6 7
4.12 Conversion charts

DN 25 0.0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 9.9
0.0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.9

1 2 3 4 5 6 7
0.0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 9.9
DN 20 0.0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 9.9
1.0 2.0 3.0 4.0 5.0 6 9.9
1 2 3 4 5 6 7
1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 9.9
DN 15 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 9.9
3.0 4.0 5.0 6.0 7.0 9.9
DN 10 1 2 3 4 5 6 7

0,1 0,2 0,3 0,4 0,5 0,6 0,7 0,8 0,9 1,0 2,0 3,0 4,0 5,0 6,0 7,0 8,0 9,0 10 20 30 40
Kv-value
5.0 6.0 7.0 8.0 9.0 9.9 BROEN BALLOREX Venturi
4 5 6 7 Oventrop Hydrocontrol R

Specific valve settings


Kv- converter TA STAD to BALLOREX Venturi
0,1 0,2 0,3 0,4 0,5 0,6 0,7 0,8 0,9 1,0 2,0 3,0 4,0 5,0 6,0 7,0 8,0 9,0 10 20 30

2.0 2.5 3.0 3.5 4.0


DN 50
0.0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 9.9
BALLOREX venturi
4.12 Conversion charts

2.0 2.5 3.0 3.5 4.0


DN 40 0.0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 9.9

2.0 2.5 3.0 3.5 4.0


DN 32
0.0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 9.9
2.0 2.5 3.0 3.5 4.0
0.0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 9.9
DN 25
0.0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.9

2.0 2.5 3.0 3.5 4.0


DN 20 0.0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 9.9
0.0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 9.9
1.0 2.0 3.0 4.0 5.0 6 9.9
1.5 2.0 2.5 3.0 3.5 4.0
1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 9.9
DN 15 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 9.9
3.0 4.0 5.0 6.0 7.0 9.9
DN 15 1.5 2.0 2.5 3.0 3.5 4.0

0,1 0,2 0,3 0,4 0,5 0,6 0,7 0,8 0,9 1,0 2,0 3,0 4,0 5,0 6,0 7,0 8,0 9,0 10 20 30
Kv-value 5.0 6.0 7.0 8.0 9.0 9.9 BROEN BALLOREX Venturi
2.5 3.0 3.5 4.0 TA STAD

Specific valve settings

4.12
BALLOREX Venturi
4.13 Mounting instructions DN 15 - 50
Make sure the dimension of the balancing valve
corresponds to the design flow.

An arrow on BALLOREX Venturi FODRV housing


indicates the flow direction to be respected.

DRV type valve can be installed regardless of flow


direction.

BALLOREX Venturi can be orientated 3600 a round pipe


axis.

Installation space required to ensure 900 isolation.

4.13
BALLOREX venturi
4.13 Mounting instructions DN 15 - 50
0xDN straight piping required.

Bends, flexible hoses, etc., can be mounted directly on


the valve.

5 x DN straight piping when valve is mounted directly


after the pump.

Make sure loose hemp is not hanging into the pipe.

Deburring of pipe ends.

4.13
BALLOREX Venturi
4.13 Mounting instructions DN 15 - 50
Connect flow meter and select valve / enter Venturi Kv
(printed on handle) on the flow meter.

Setting the valve is easily done with an Allen key.


Adjust the valve until the required flow is displayed.

4.13
BALLOREX venturi
4.14 Mounting instructions DN 65 - 300
FODRV BALLOREX Venturi FODRV must be installed so that the
flow direction is as indicated by the direction arrow on the
valve body.

DRV BALLOREX Venturi DRV can be installed regardless of the


flow direction.

FODRV BALLOREX Venturi FODRV can be installed with the


gearbox pointing in any direction. However, if the gearbox
is mounted pointing down, it is assumed that there are no
impurities in the system to affect the performance of the
valve. If there is a risk of impurities, it is recommended to
install the gearbox in an angle of 60 to 300 degrees.
60 300
0

DRV BALLOREX VENTURI DRV can be installed with the


gearbox pointing in any direction.

4.14
BALLOREX Venturi
4.14 Mounting instructions DN 65 - 300

FODRV STANDARD It is recommended to have a straight pipe length of


minimum 5 x pipe diameter (DN) in front of the valve (up-
stream).
There are no minimum requirements for straight lengths
5 x DN 0 x DN of pipe after the valve (downstream).

FODRV EXTENDED There are no minimum lengths of straight pipe in front of


or after the BALLOREX Venturi FODRV model extended.
0 x DN

0 x DN

FODRV STANDARD If a pump is installed immediately in front of the valve


(commissioning valve installed on flow), a straight pipe of
10 x pipe diameter (DN) is required. No requirements for
straight pipe sections after the valve.
10 x DN
0 x DN

FODRV EXTENDED If a pump is installed immediately in front of the valve


(commissioning valve installed on flow), a straight pipe
of 5 x pipe diameter (DN) is required. No requirements for
straight pipe sections after the valve.

5 x DN 0 x DN

4.14
BALLOREX venturi
4.14 Mounting instructions DN 65 - 300

The flow rate through the BALLOREX Venturi FODRV can


be measured with the BROEN Flowmeter or other types of
manometers. BALLOREX Venturi FODRV is supplied with
two P/T plugs to measure the differential pressure across
the Venturi. By measuring the differential pressure the flow
rate can be calculated.

The flow rate can be adjusted by rotating the handle of the


gearbox. The flow rate increases by rotating the handle to
the left (anti-clockwise) and is reduced by rotating it to the
right (clockwise).

4.14
BALLOREX Venturi
4.15 Correction for glycolic mixtures
When glycol is added to the water the density of the media changes. This also affects the measuring of differential
pressure on all types of balancing valves.

For exact measurements the equivalent flow to be calculated into the flow-equation:

P x water 20C
Q = Kv
water/glycol mixture

Kv = Kv-value of Venturi orifice [m3/(h bar)]


= Media density [kg/m3]
Q = Flow [ m3/h ]
P = Differential pressure signal across Venturi orifice [bar]

To compensate for a given glycol content the equivalent flow to be measured is calculated. For this purpose the density
of the water/glycol mixture at a given temperature is required.

Example
A cooling system with a media temperature of -2C has a content of 30% ethylene glycol. In the table on the next page
the graph for 30% crosses -2C on the X-axis where the density of 1052 kg/m3 is read on the Y-axis.

Find the media temperature on the X-axis (example -2 C). Find the intersection with the medias glycol concentration
(example 30%). Read the density vertically on the Y-axis (example 1052 kg/m3).

A valve has a design flow of 0,854 m3/h, a Kv-value of 1,56 and measures P of 0,3 bar.

Inserted in the flow equation, the equivalent flow, to be measured on the valve to compensate for glycol density, is
calculated:

0,3 x 998
Qequivalent = 1,56 = 0,832 m3/h
1052

4.15
BALLOREX venturi
4.15 Correction for glycolic mixtures
Density correction for ethylene glycol* water mixtures

Fluid density [kg/m3]


1090

1080

1070

1060

1050 1052 kg/m3


1040

1030

1020 50% Glycol

1010 40% Glycol

1000
30% Glycol

990
20% Glycol
980
-2 C
970 10% Glycol

960
0%
-20 -10 0 10 20 30 40 50 60 70 80 90 100
Fluid temperature [oC]

Densitiy correction for propylene glycol* water mixtures

Fluid density [kg/m3]


1060

1050

1040

1030

1020

1010

1000

990

50% Glycol
980
40% Glycol
30% Glycol

970 20% Glycol

10% Glycol
960
0%
-20 -10 0 10 20 30 40 50 60 70 80 90 100
Fluid temperature [o C]

* The densities are average values for ethylene and propylene glycols used by ASHRAE (American Society of Heating, Refrigerating, and
Air-Conditioning Engineers).

4.15
BALLOREX Venturi
4.15 Correction for glycolic mixtures
Flow correction factors
In the diagram on the following pages the various densities have been converted into correction factors that can be
multiplied directly by the design flow rate.

Example
A cooling system with a media temperature of -2C has a content of 30% ethylene glycol. In the table on the next page
the graph for 30% crosses -2C on the X-axis where the density correction factor indicates 0,974 on the Y-axis.

The valve has a design flow rate of 0,854 m3/h, and the equivalent flow to be measured:

Qequivalent) is: 0,854 m3/h x 0,974 = 0,832 m3/h

4.15
BALLOREX venturi
4.15 Correction for glycolic mixtures

Flow correction factors for ethylene glycol* water mixtures


Flow correction factor
1,035

1,03

1,025

1,02 0% Glycol

1,015
10% Glycol
1,01

1,005 20% Glycol

1 30% Glycol
0,995
40% Glycol
0,99
50% Glycol
0,985
60% Glycol
0,98

0,975
0,974
0,97

0,965

0,96

0,955

0,95
-2 C
0,945
-20 -10 0 10 20 30 40 50 60 70 80 90 100
Fluid temperature oC

Flow correction factors for propylene glycol* water mixtures


Flow correction factor
0% Glycol
1,02
10% Glycol
1,015
20% Glycol
30% Glycol
1,01 40% Glycol
50% Glycol
60% Glycol
1,005

0,995

0,99

0,985

0,98

0,975

0,97

0,965
-20 -10 0 10 20 30 40 50 60 70 80 90 100
Fluid temperature oC

*The densities are average values for ethylene and propylene glycols used by ASHRAE (American Society of Heating, Refrigerating, and
Air-Conditioning Engineers).

4.15