4.1 Introduction
The BROEN BALLOREX Venturi valve is compact having flow measuring, regulation and isolation functions all in one
unit. The range consists of valves in sizes DN 15-50, manufactured in dezincification resistant brass (DR), to valves in sizes
DN 65-600, manufactured in steel.
The clever design enables the BROEN BALLOREX Venturi to have consistent measuring accuracy within +/- 3%, which
makes the BROEN BALLOREX Venturi more accurate compared to other commissioning valves in the market.
Because of the higher accuracy and low loss characteristics, the BROEN BALLOREX Venturi is more efficient and provides
reduced energy consumption when heating and cooling systems are balanced.
4.1
BALLOREX Venturi
4.2 Flow measuring
4.2.1 Direct flow measurement
A unique feature of BROEN BALLOREX Venturi is the integrated Venturi measuring orifice which allows direct flow
measurement at any time. With direct flow measurement, actual flow rates can be measured for precise balancing and
correct documentation.
Trouble shooting becomes considerably easier saving time. Just connect a flow meter, enter the fixed
Kv-value of the integrated Venturi orifice, and the flow will be directly displayed on the flowmeter at an accuracy of +/- 3%.
4.2
BALLOREX venturi
4.2 Flow measuring
Direct flow measurement is not affected by the changing of the valve setting since the Kv-value between the measuring
points remains constant. The Kv-value is changed elsewhere in the valve to regulate the flow.
P - Venturi P - valve
Measured signal across Total pressure drop across the open valve.
Venturi orifice. Part of the pressure is recovered by the
Strong signal gives high Venturi.
accuracy measurement.
Flow equation
Q = Kv * p
Kv: The Venturi coefficient which defines the flow capacity through the Venturi. It is determined by the smallest diameter in
the Venturi and remains constant during the setting of the flow.
On a flow meter the Venturis Kv-value is entered once, and the flow will be displayed directly on the flow meter. If the valve
setting is changed, the new flow will be displayed directly since the Kv-value across the measuring points remains constant
and only the differential pressure changes.
4.2
BALLOREX Venturi
4.3 Product properties
4.3.1 Design
The regulation of the BALLOREX Venturi is done by setting the spindle that operates independently of the shut off
function. In that way the valve setting is kept intact when the valve is isolated and re-opened.
The differential pressure is measured across the Venturi orifice where the Kv-value is constant and not affected when the
setting is changed. Compared to variable orifice double regulating valves it means that on the BALLOREX Venturi valves,
you only have to enter the Kv-value once into the flowmeter. On the VODRVs the Kv-value is changed every time the
setting is adjusted. The new setting is read from the handle scale and entered into the flowmeter every time a new flow has
to be measured.
C) Regulation needle
A B C
4.3
BALLOREX venturi
4.3 Product properties
4.3.2 Sizing & selection
Selecting the right valve dimension is simple when using BALLOREX Venturi.
Once the design flow has been calculated, a valve with a flow range that fits the required design flow rate is selected.
Also keep in mind to select a valve that can provide the required total pressure loss.
Example
Heating system for a room of 37 m x 14 m
0
n 0.
0,7 70 itio
Pos
0,6 60
Measuring signal
0,5 50
n 1.0 n 2.0 n 3.0 n 4.0
itio itio itio itio .0
0,4 40 Pos Pos Pos Pos itio
n5
Pos
0,3 30 .0
n6
itio
Pos .0
n7
itio
0,2 20 Pos n 8.0
itio
Pos ion 9.9
it
Pos
0,1 10
0,07 7
0,06 6
0,05 5
0,04 4
0,247 l/s
Example
A BALLOREX Venturi DN 20S has a flow rate of 0,247 l/s and a setting on the handle scale of 7.0.
The pressure drop across the complete valve (14 kPa) is read on the Y-axis intersection between the curve for setting
7.0 and flow rate 0,247 l/s.
The red curve is the Venturi measuring signal which indicates what differential pressure should be measured across the
Venturi orifice for a given flow.
The Venturi signal in the example given corresponding to 0,247 l/s, is found via the red curve ( 33 kPa).
4.3
BALLOREX Venturi
4.3 Product properties
4.3.3 Installation
Due to its clever design BALLOREX Venturi can
be oriented in all positions 360 around the pipe
axis, without debris corrupting the flow
measurements.
4.3
BALLOREX venturi
4.3 Product properties
4.3.4 Valve setting
The setting of the valve is easily done with an Allen key.
Connect the flow meter to the valve and select Venturi type/enter the Venturi Kv-value, that is printed on the valve
handle. Turn the pre-setting tool until the flow meter displays the required flow rate.
Compared to variable orifice double regulating valves it means that on the BALLOREX Venturi valves, you only have to
enter the Kv-value once into the flowmeter.
0,1 0,2 0,3 0,4 0,5 0,6 0,7 0,8 0,9 1,0 2,0 3,0 4,0 5,0 6,0 7,0 8,0 9,0 10 20 30
DN 50 0.0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 9.9
DN 40 0.0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 9.9
DN 32 0.0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 9.9
0.0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 9.9
DN 25
0.0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.9
0.0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 9.9
DN 20 0.0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 9.9
1.0 2.0 3.0 4.0 5.0 6 9.9
1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 9.9
DN 15 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 9.9
3.0 4.0 5.0 6.0 7.0 9.9
0,1 0,2 0,3 0,4 0,5 0,6 0,7 0,8 0,9 1,0 2,0 3,0 4,0 5,0 6,0 7,0 8,0 9,0 10 20 30
Kv-value
0,34
Example 1:
A customer needs a valve which can deliver a Kv-Value of 2.0.
The diagram shown above indicates that this is provided by; DN 15H, DN 20S, DN 20H and even DN 25S. DN 25H would
be too close to fully closed when providing Kv 2.0, and the risk is that the right flow rate cannot be reached.
Example 2:
A customer has a Venturi DN 15L installed and set for 5.0.
He would like to know the Kv-Value at the given setting. The table indicates an approximate Kv-value of 0,34 m3/h.
You will find the above diagram together with other examples in the appendix at the end of this chapter (section 4.12).
4.3
BALLOREX Venturi
4.3 Product properties
4.3.5 Commissioning
For commissioning BALLOREX Venturi it is recommendeded to use the proportional method.
The proportional method has significant advantages in terms of trouble shooting, since only approx. 10% of the time
required to commission an installation is actually used working with the balancing valves.
In practice approx. 90% of the time is spent on trouble shooting to find out what is wrong elsewhere in the installation.
For more detailed information about the commissioning procedure, see chapter 3.
4.3
BALLOREX venturi
4.4 Product data sheets - FODRV female
4.4.1 Product finder
DN 50H
DN 40H
DN 25H / DN 32H
DN 20H / DN 25S
DN 15H / DN 20S
DN 15S / DN 20L
DN 15L
DN 15UL
0.005 0.007 0.009 0.01 0.02 0.03 0.04 0.06 0.08 0.1 0.2 0.3 0.4 0.5 0.6 0.8 1.0 2.0 3.0 4.0 l/s
36 72 108 144 216 288 360 720 1,080 1,440 1,800 2,160 2,880 3,600 7,200 10,800 14,400 l/h
Flow rate
4.4
4.4 Data sheet
BALLOREX Venturi
4.4.2 DN 15 female/female
94mm Specifications
Max. temperature 120C
Min. temperature -20C
Max. pressure 25 bar
76mm Press ends 16 bar
Marking on valve (Handle) DN, flow-version, Kvm (Kv-measuring)
(Valve body) DN, PN, flow direction, BROEN
Connection Female thread ISO 7/1 parallel
75mm Valve housing DR Brass CW602N CuZn36Pb2As
140mm Ball & needle DR Brass CW602N (chrome plated)
Valve handle Polyamide (PA6.6 30%GF)
Sealings O-rings EPDM
Gaskets PTFE
Test point sealing EPDM
Accessories
BROEN No. Dimension Description
83504006-000003 15 mm x 1/2
Pre-sealed press adaptors (2 pcs), max 16 bar
83504007-000003 18 mm x 1/2
4.4
BALLOREX Venturi
0.7 70
0.6 60
Measuring signal
0.5 50
0.4 40
0.3 30
0.2 20 1.0
on
siti
Po
0.1 10
.9
0.08 8 n9
sitio
0.07 7 7.0 Po
2.0 3.0 4.0
n
sitio
on on on 6.0 Po
0.06 6 siti siti siti ion
Po Po Po io n5
.0 Posit
0.05 5 Posit
0.04 4
0.03 3
0.02 2
0.01 1
Flow rate
0.005 0.006 0.007 0.008 0.009 0.01 0.02 0.03 0.035 l/s
18.0 21.6 25.2 28.8 32.4 36.0 72.0 108.0 126.0 l/h
The black curves are used to determine the total pressure drop across the valve at a specific handle scale setting and a
given flow rate.
The red curve is the Venturi measuring signal which indicates what differential pressure should be measured across the
Venturi orifice for a given flow.
4.4
Flow Diagram
BALLOREX Venturi
0.7 70
.0
n1
0.6 60
sitio Measuring signal
0.5 50 Po
0.4 40
0.3 30
0.2 20
2.0 3.0 4.0 5.0 6.0 7.0 .9
tion tion tion tion tion ition ion 9
Posi Posi Posi Posi Posi s
Po Pos t
i
0.1 10
0.08 8
0.07 7
0.06 6
0.05 5
0.04 4
0.03 3
0.02 2
The black curves are used to determine the total pressure drop across the valve at a specific handle scale setting and a
given flow rate.
The red curve is the Venturi measuring signal which indicates what differential pressure should be measured across the
Venturi orifice for a given flow.
4.4
Flow Diagram
BALLOREX Venturi
0.7 70
0.6 60
0.5 50 Measuring signal
0.0 ion2.0 3.0 4.0
sitio
n
osit ion ion
0.4 40 po P Posit Posit
6.0
0.3 30 ition
Pos
7.0
0.2 20 ition
Pos
8.0
ition
Pos
9.9
0.1 10 ition
Pos
0.08 8
0.07 7
0.06 6
0.05 5
0.04 4
129.6 144 180 216 252 288 324 360 532.8 l/h
The black curves are used to determine the total pressure drop across the valve at a specific handle scale setting and a given
flow rate.
The red curve is the Venturi measuring signal which indicates what differential pressure should be measured across the
Venturi orifice for a given flow.
4.4
Flow Diagram
BALLOREX Venturi
1 100
0.7 70
0.6 60
Measuring signal
0.5 50
n 0.0 n 2.0 n 3.0 n 4.0 n 5.0 n 6.0
itio itio itio itio itio itio
0.4 40 Pos Pos Pos Pos Pos Pos .0
n8
itio
Pos
0.3 30 .0
n9
itio
Pos .9
n9
itio
Pos
0.2 20
0.1 10
0.08 8
0.07 7
0.06 6
0.05 5
0.04 4
The black curves are used to determine the total pressure drop across the valve at a specific handle scale setting and a given
flow rate.
The red curve is the Venturi measuring signal which indicates what differential pressure should be measured across the
Venturi orifice for a given flow.
4.4
Flow Diagram
4.4
4.4 Data sheet
BALLOREX Venturi
4.4.3 DN 20 female/female
100mm Specifications
Max. temperature 120C
Min. temperature -20C
Max. pressure 25 bar
79mm Press ends 16 bar
Marking on valve (Handle) DN, flow-version, Kvm (Kv-measuring)
(Valve body) DN, PN, flow direction, BROEN
Connection Female thread ISO 7/1 parallel
Valve housing DR Brass CW602N CuZn36Pb2As
75mm
Ball & needle DR Brass CW602N (chrome plated)
144mm
Valve handle Polyamide (PA6.6 30%GF)
Sealings O-rings EPDM
Gaskets PTFE
Test point sealing EPDM
Accessories
BROEN No. Dimension Description
84504006-000003 15 mm x 3/4
84504007-000003 18 mm x 3/4 Pre-sealed press adaptors (2 pcs), max. 16 bar
84504008-000003 22 mm x 3/4
4.4
Flow Diagram
BALLOREX Venturi
1 100
0.7 70
0.6 60
0.5 50 Measuring signal
itio n 1.0 ition 2.0 ition 3.0
0.4 40 Pos Pos Pos
4.0
ition
0.3 30 Pos
5.0
ition
Pos
6.0
ition
0.2 20
Pos 7 .0
ition
Pos 9 .9
itio n
Pos
0.1 10
0.08 8
0.07 7
0.06 6
0.05 5
0.04 4
130 144 180 216 252 288 324 360 530 l/h
The black curves are used to determine the total pressure drop across the valve at a specific handle scale setting and a
given flow rate.
The red curve is the Venturi measuring signal which indicates what differential pressure should be measured across the
Venturi orifice for a given flow.
4.4
Flow Diagram
BALLOREX Venturi
0
n 0.
itio
0.7 70 Pos
0.6 60
Measuring signal
0.5 50
1 .0 .0 3 .0 4.0
tion n2 tion tion
Pos
i itio Pos
i
Pos
i n5
.0
0.4 40 Pos itio
Pos
0.3 30 .0
n6
itio
Pos . 0
n7
itio
0.2 20 Pos n 8.0
itio
Pos ion 9.9
s it
Po
0.1 10
0.07 7
0.06 6
0.05 5
0.04 4
The black curves are used to determine the total pressure drop across the valve at a specific handle scale setting and a
given flow rate.
The red curve is the Venturi measuring signal which indicates what differential pressure should be measured across the
Venturi orifice for a given flow.
Example
A BALLOREX Venturi DN 20S has a flow rate of 0,247 l/s and a setting on the handle scale of 7.0.
The pressure drop across the complete valve (14 kPa) is read on the Y-axis intersection between the curve for setting
7.0 and flow rate 0,247 l/s.
The Venturi signal that corresponds to 0,247 l/s is found via the red curve ( 33 kPa).
4.4
Flow Diagram
BALLOREX Venturi
0.7 70
0.6 60
Measuring signal
0.5 50
.0 1.0 2.0 n3.0 4.0 .0
n0 tion tion tion n5
sitio Pos
i
Pos
i sitio i sitio 6.0
0.4 40 Po Po Pos Po itio
n
Pos
0
0.3 30 n 7.
itio
Pos
0
n 8.
itio
0.2 20 Pos
0
n 9.
itio
Pos . 9
n9
itio
Pos
0.1 10
0.07 7
0.06 6
0.05 5
0.04 4
The black curves are used to determine the total pressure drop across the valve at a specific handle scale setting and a
given flow rate.
The red curve is the Venturi measuring signal which indicates what differential pressure should be measured across the
Venturi orifice for a given flow.
4.4
4.4 Data sheet
BALLOREX Venturi
4.4.4 DN 25 female/female
112mm Specifications
Max. temperature 120C
Min. temperature -20C
Max. pressure 25 bar
83mm Press ends 16 bar
Marking on valve (Handle) DN, flow-version, Kvm (Kv-measuring)
(Valve body) DN, PN, flow direction, BROEN
Connection Female thread ISO 7/1 parallel
75mm
Valve housing DR Brass CW602N CuZn36Pb2As
150mm
Ball & needle DR Brass CW602N (chrome plated)
Valve handle Polyamide (PA6.6 30%GF)
Sealings O-rings EPDM
Gaskets PTFE
Test point sealing EPDM
Accessories
BROEN No. Dimension Description
4.4
Flow Diagram
BALLOREX Venturi
1 100
0.7 70
0.6 60
0.5 50 Measuring signal
n0 .0 n 1.0 n2.0 n3 .0 .0
0.4 40
Positio Po sitio Po sitio Po sitio ition 4
Pos
0.3 30
5.0
ition
Pos
0.2 20 6.0
ition
Pos
7.0
ition
Pos .0
8
0.1 10 ition
Pos .9
9
tion
0.07 7 Posi
0.05 5
0.04 4
0.7 70
0.6 60
0 0 0
n 0. n 1. n 2. n 3.
0
n 4.
0
n 5.
0 Measuring signal
0.5 50 itio itio itio itio itio itio
Pos Pos Pos Pos Pos Pos .0
iti on 6
0.4 40 Pos
0
n 7.
0.3 30 itio
Pos
0
n 8.
0.2 20 itio
Pos
0
n 9.
itio
Pos ion 9.9
it
Pos
0.1 10
0.07 7
0.06 6
0.05 5
0.04 4
1,044 1,440 1,800 2,160 2,520 2,880 3,240 3,600 4,500 l/h
The black curves are used to determine the total pressure drop across the valve at a specific handle scale setting
and a given flow rate.
The red curve is the Venturi measuring signal which indicates what differential pressure should be measured
across the Venturi orifice for a given flow.
4.4
BALLOREX Venturi
4.4.5 DN 32 female/female
130mm
Specifications
Max. temperature 120C
Min. temperature -20C
Max. pressure 25 bar
109mm Press ends 16 bar
Marking on valve (Handle) DN, flow-version, Kvm (Kv-measuring)
(Valve body) DN, PN, flow direction, BROEN
Connection Female thread ISO 7/1 parallel
122mm Valve housing DR Brass CW602N CuZn36Pb2As
208mm Ball & needle DR Brass CW602N (chrome plated)
Valve handle Polyamide (PA6.6 30%GF)
Sealings O-rings EPDM
Gaskets PTFE
Test point sealing EPDM
Accessories
BROEN No. Dimension Description
4.4
Flow Diagram
BALLOREX Venturi
1 100
0.7 70
0.6 60
Measuring signal
0.5 50
0.4 40 0 0 0 0
n 0.
0 n 1. n 2.
0 n 3. n 4. n 5. 0
itio Pos
itio itio itio itio
Pos
itio n 6.
Pos Pos Pos Pos itio
0.3 30 Pos
0
n 7.
itio
0.2 20 Pos
0
n 8.
itio
Pos 0
n 9.
itio
Pos n 9.9
itio
0.1 10 Pos
0.07 7
0.06 6
0.05 5
0.04 4
1,044 1,440 1,800 2,160 2,520 2,880 3,240 3,600 4,500 l/h
The black curves are used to determine the total pressure drop across the valve at a specific handle scale setting
and a given flow rate.
The red curve is the Venturi measuring signal which indicates what differential pressure should be measured
across the Venturi orifice for a given flow.
4.4
BALLOREX Venturi
4.4.6 DN 40 female/female
140mm
Specifications
Max. temperature 120C
Min. temperature -20C
Max. pressure 25 bar
113mm Press ends 16 bar
Marking on valve (Handle) DN, flow-version, Kvm (Kv-measuring)
(Valve body) DN, PN, flow direction, BROEN
Connection Female thread ISO 7/1 parallel
122mm Valve housing DR Brass CW602N CuZn36Pb2As
213mm Ball & needle DR Brass CW602N (chrome plated)
Valve handle Polyamide (PA6.6 30%GF)
Sealings O-rings EPDM
Gaskets PTFE
Test point sealing EPDM
Accessories
BROEN No. Dimension Description
4.4
Flow Diagram
BALLOREX Venturi
0.7 70
0.6 60
Measuring signal
0.5 50
n0 .0 1.0 2. 0 .0 4.0
ition n3 ition
0.4 40 sitio Pos ition sitio Pos 5.0
Po Pos Po
ition
Pos
0.3 30
6.0
ition
Pos
0.2 20 7.0
ition
Pos
8.0
ition
Pos
9.0
ition
0.1 10 Pos 9.9
ition
Pos
0.07 7
0.06 6
0.05 5
0.04 4
The black curves are used to determine the total pressure drop across the valve at a specific handle scale setting
and a given flow rate.
The red curve is the Venturi measuring signal which indicates what differential pressure should be measured
across the Venturi orifice for a given flow.
4.4
BALLOREX Venturi
4.4.7 DN 50 female/female
156mm
Specifications
Max. temperature 120C
Min. temperature -20C
Max. pressure 25 bar
120mm Press ends 16 bar
Marking on valve (Handle) DN, flow-version, Kvm (Kv-measuring)
(Valve body) DN, PN, flow direction, BROEN
Connection Female thread ISO 7/1 parallel
122mm Valve housing DR Brass CW602N CuZn36Pb2As
221mm Ball & needle DR Brass CW602N (chrome plated)
Valve handle Polyamide (PA6.6 30%GF)
Sealings O-rings EPDM
Gaskets PTFE
Test point sealing EPDM
Accessories
BROEN No. Dimension Description
4.4
Flow Diagram
BALLOREX Venturi
0.7 70
0.6 60
Measuring signal
0.5 50
0.4 40
0.0 1.0 2.0 3.0 4.0 5.0 6.0
ition ition ition ition ition ition ition
Pos Pos Pos Pos Pos Pos Pos
0.3 30
7.0
ition
Pos
8.0
0.2 20
ition
Pos
9.0
ition
Pos
9.9
ition
Pos
0.1 10
0.07 7
0.06 6
0.05 5
0.04 4
The black curves are used to determine the total pressure drop across the valve at a specific handle scale setting
and a given flow rate.
The red curve is the Venturi measuring signal which indicates what differential pressure should be measured
across the Venturi orifice for a given flow.
4.4
BALLOREX Venturi
4.5
BALLOREX venturi
4.5 Product data sheets - FODRV compression
4.5.1 Product finder
DN 50H
DN 40H
DN 25H / DN 32H
DN 20H / DN 25S
DN 15H / DN 20S
DN 15S / DN 20L
DN 15L
DN 15UL
0.005 0.007 0.009 0.01 0.02 0.03 0.04 0.06 0.08 0.1 0.2 0.3 0.4 0.5 0.6 0.8 1.0 2.0 3.0 4.0 l/s
36 72 108 144 216 288 360 720 1,080 1,440 1,800 2,160 2,880 3,600 7,200 10,800 14,400 l/h
Flow rate
4.5
BALLOREX Venturi
4.5.2 DN 15 compression/compression
99mm
Specifications
Max. temperature 120C
Min. temperature -20C
76mm Max. pressure 5 bar
Marking on valve (Handle) DN, flow-version, Kvm (Kv-measuring)
(Valve body) DN, PN, flow direction, BROEN
Connection Compression EN 1254-2
75mm Valve housing DR Brass CW602N CuZn36Pb2As
164mm Ball & needle DR Brass CW602N (chrome plated)
Valve handle Polyamide (PA6.6 30%GF)
Sealings O-rings EPDM
Gaskets PTFE
Test point sealing EPDM
Accessories
BROEN No. Dimension Description
4.5
Flow Diagram
BALLOREX Venturi
0.7 70
0.6 60
0.5 50 Measuring signal
0.4 40
0.3 30
0.2 20
1.0
on
siti
Po
0.1 10
0.08 8
.9
0.07 7 n9
itio
7.0 Pos
0.06 6 2.0 3.0 4.0 sition
on on on 6.0 Po
0.05 5 siti siti siti ion
Po Po Po n 5.0 Posit
sitio
Po
0.04 4
0.03 3
0.02 2
0.01 1
Flow rate
0.005 0.006 0.007 0.008 0.009 0.01 0.02 0.03 0.035 l/s
The black curves are used to determine the total pressure drop across the valve at a specific handle scale setting, and a
given flow rate.
The red curve is the Venturi measuring signal, which indicates what differential pressure should be measured across the
Venturi orifice for a given flow.
4.5
Flow Diagram
BALLOREX Venturi
0.7 70 .0
n1
0.6 60
sitio Measuring signal
0.5 50
Po
0.4 40
0.3 30
0.2 20
2.0 3.0 4.0 5.0 6.0 7.0 .9
tion tion tion tion tion ition ion 9
Posi Posi Posi Posi Posi s
Po Pos t
i
0.1 10
0.08 8
0.07 7
0.06 6
0.05 5
0.04 4
0.03 3
0.02 2
The black curves are used to determine the total pressure drop across the valve at a specific handle scale setting
and a given flow rate.
The red curve is the Venturi measuring signal which indicates what differential pressure should be measured
across the Venturi orifice for a given flow.
4.5
Flow Diagram
BALLOREX Venturi
0.7 70
0.6 60
0.5 50 Measuring signal
0.0 2.0 3.0 4.0
ition ition ition ition
0.4 40 pos Pos Pos Pos
6.0
0.3 30 ition
Pos
7.0
0.2 20 ition
Pos
8.0
ition
Pos
9.9
0.1 10 ition
Pos
0.08 8
0.07 7
0.06 6
0.05 5
0.04 4
130 144 180 216 252 288 324 360 530 l/h
The black curves are used to determine the total pressure drop across the valve at a specific handle scale setting, and a
given flow rate.
The red curve is the Venturi measuring signal, which indicates what differential pressure should be measured across the
Venturi orifice for a given flow.
4.5
Flow Diagram
BALLOREX Venturi
1 100
0.7 70
0.6 60
Measuring signal
0.5 50
.0 2.0 3.0 4.0 5.0 .0
n0 n n n n n6
itio itio itio itio itio itio
0.4 40 Pos Pos Pos Pos Pos Pos .0
n8
itio
0.3 30 Pos
.0
n9
itio
Pos .9
n9
0.2 20 itio
Pos
0.1 10
0.08 8
0.07 7
0.06 6
0.05 5
0.04 4
The black curves are used to determine the total pressure drop across the valve at a specific handle scale setting and a
given flow rate.
The red curve is the Venturi measuring signal which indicates what differential pressure should be measured across the
Venturi orifice for a given flow.
4.5
Flow Diagram
4.5
BALLOREX Venturi
4.5.3 DN 20 compression/compression
105mm
Specifications
Max. temperature 120C
Min. temperature -20C
79mm Max. pressure 5 bar
Marking on valve (Handle) DN, flow-version, Kvm (Kv-measuring)
(Valve body) DN, PN, flow direction, BROEN
Connection Compression EN 1254-2
75mm Valve housing DR Brass CW602N CuZn36Pb2As
170mm Ball & needle DR Brass CW602N (chrome plated)
Valve handle Polyamide (PA6.6 30%GF)
Sealings O-rings EPDM
Gaskets PTFE
Test point sealing EPDM
Accessories
BROEN No. Dimension Description
4.5
Flow Diagram
BALLOREX Venturi
1 100
0.7 70
0.6 60
0.5 50 Measuring signal
1.0 2.0 3.0
ition ition ition
0.4 40 Pos Pos Pos
4.0
ition
0.3 30 Pos
5.0
ition
Pos
6.0
ition
0.2 20
Pos 7 .0
ition
Pos 9 .9
itio n
Pos
0.1 10
0.08 8
0.07 7
0.06 6
0.05 5
0.04 4
0.03 3
Flow rate
0.036 0.04 0.05 0.06 0.07 0.08 0.09 0.1 0.148 l/s
130 144 180 216 252 288 324 360 530 l/h
The black curves are used to determine the total pressure drop across the valve at a specific handle scale setting and a
given flow rate.
The red curve is the Venturi measuring signal which indicates what differential pressure should be measured across the
Venturi orifice for a given flow.
4.5
BALLOREX Venturi
0
n 0.
itio
0.7 70
Pos
0.6 60
Measuring signal
0.5 50
.0 2.0 3.0 .0
n1 n n n4
itio itio itio itio .0
0.4 40 Pos Pos Pos Pos itio
n5
Pos
0.3 30 .0
n6
itio
Pos .0
n7
itio
0.2 20 Pos n 8.0
itio
Pos ion 9.9
it
Pos
0.1 10
0.07 7
0.06 6
0.05 5
0.04 4
0.03 3
Flow rate
0.075 0.09 0.1 0.2 0.3 0.325 l/s
The black curves are used to determine the total pressure drop across the valve at a specific handle scale setting, and a
given flow rate.
The red curve is the Venturi measuring signal, which indicates what differential pressure should be measured across the
Venturi orifice for a given flow.
4.5
Flow Diagram
BALLOREX Venturi
0.7 70
0.6 60
Measuring signal
0.5 50
0 0 0 0
ion 0. ion 1. ion 2.
0
ion 3. io n 4.
0
ion 5. .0
0.4 40 Posit P osit Posit P osit Posit Posit iti on 6
Pos
0
0.3 30 n 7.
itio
Pos
0
n 8.
itio
0.2 20 Pos
0
n 9.
itio
Pos 9 .9
n
itio
Pos
0.1 10
0.07 7
0.06 6
0.05 5
0.04 4
The black curves are used to determine the total pressure drop across the valve at a specific handle scale setting and a
given flow rate.
The red curve is the Venturi measuring signal which indicates what differential pressure should be measured across the
Venturi orifice for a given flow.
4.5
BALLOREX Venturi
4.5.4 DN 25 compression/compression
118mm Specifications
Max. temperature 120C
Min. temperature -20C
Max. pressure 5 bar
83mm
Marking on valve (Handle) DN, flow-version, Kvm (Kv-measuring)
(Valve body) DN, PN, flow direction, BROEN
Connection Compression EN 1254-2
Valve housing DR Brass CW602N CuZn36Pb2As
75mm Ball & needle DR Brass CW602N (chrome plated)
Valve handle Polyamide (PA6.6 30%GF)
177mm
Sealings O-rings EPDM
Gaskets PTFE
Test point sealing EPDM
Accessories
BROEN No. Dimension Description
4.5
Flow Diagram
BALLOREX Venturi
0.7 70
0.6 60
0.5 50
Measuring signal
0.0 1.0 2.0 3.0 .0
sitio
n ion sitio
n
sitio
n
on 4
0.4 40
Po Posit Po Po iti
Pos
0.3 30
5.0
ition
Pos
0.2 20
6.0
ition
Pos
7.0
ition
Pos
8.0
0.1 10 ition
Pos
9.9
tion
0.07 7 Posi
0.05 5
0.04 4
0.03 3
Flow rate
0.14 0.2 0.3 0.4 0.5 0.603 l/s
0.7 70
0.6 60
0 0 0
n 0. n 1. n 2. n 3.
0
n 4.
0
n 5.
0 Measuring signal
0.5 50 itio itio itio itio itio itio
Pos Pos Pos Pos Pos Pos 6.0
n
0.4 40 Po sitio
0
n 7.
0.3 30 itio
Pos
0
n 8.
itio
0.2 20 Pos
0
n 9.
itio
Pos ion 9.9
it
Pos
0.1 10
0.07 7
0.06 6
0.05 5
0.04 4
Flow rate
0.03 3
0.29 0.4 0.5 0.6 0.7 0.8 0.9 1 1.25 l/s
1044 1440 1800 2160 2520 2880 3240 3600 4500 l/h
The black curves are used to determine the total pressure drop across the valve at a specific handle scale setting and a
given flow rate.
The red curve is the Venturi measuring signal which indicates what differential pressure should be measured across the
Venturi orifice for a given flow.
4.5
BALLOREX Venturi
4.5.5 DN 32 compression/compression
135mm
Specifications
Max. temperature 120C
Min. temperature -20C
109mm Max. pressure 5 bar
Marking on valve (Handle) DN, flow-version, Kvm (Kv-measuring)
(Valve body) DN, PN, flow direction, BROEN
Connection Compression EN 1254-2
122mm
Valve housing DR Brass CW602N CuZn36Pb2As
241mm Ball & needle DR Brass CW602N (chrome plated)
Valve handle Polyamide (PA6.6 30%GF)
Sealings O-rings EPDM
Gaskets PTFE
Test point sealing EPDM
Accessories
BROEN No. Dimension Description
4.5
Flow Diagram
BALLOREX Venturi
1 100
0.7 70
0.6 60
Measuring signal
0.5 50
0.4 40 0 0
0 0
n 0.
0 n 1. n 2.
0 n 3. n 4. n 5. 0
itio Pos
itio itio itio itio
Pos
itio n 6.
Pos Pos Pos Pos itio
0.3 30 Pos
0
n 7.
itio
0.2 20 Pos
0
n 8.
itio
Pos 0
n 9.
itio
Pos n 9.9
it i o
0.1 10 Pos
0.07 7
0.06 6
0.05 5
0.04 4
1,044 1,440 1,800 2,160 2,520 2,880 3,240 3,600 4,500 l/h
The black curves are used to determine the total pressure drop across the valve at a specific handle scale setting and a
given flow rate.
The red curve is the Venturi measuring signal which indicates what differential pressure should be measured across the
Venturi orifice for a given flow.
4.5.6 DN 40 compression/compression
149mm
Specifications
Max. temperature 120C
Min. temperature -20C
113mm Max. pressure 5 bar
Marking on valve (Handle) DN, flow-version, Kvm (Kv-measuring)
(Valve body) DN, PN, flow direction, BROEN
Connection Compression EN 1254-2
122mm
Valve housing DR Brass CW602N CuZn36Pb2As
253mm Ball & needle DR Brass CW602N (chrome plated)
Valve handle Polyamide (PA6.6 30%GF)
Sealings O-rings EPDM
Gaskets PTFE
Test point sealing EPDM
Accessories
BROEN No. Dimension Description
4.5
Flow Diagram
BALLOREX Venturi
0.7 70
0.6 60
Measuring signal
0.5 50
n 0.0 n1.0
n2.0 n 3.0 n4.0
0.4 40
Positio Positio sitio Positio Positio 5.0
Po ition
Pos
0.3 30
6.0
ition
Pos
0.2 20 7.0
ition
Pos
8.0
ition
Pos
9.0
ition
0.1 10 Pos 9.9
ition
Pos
0.07 7
0.06 6
0.05 5
0.04 4
The black curves are used to determine the total pressure drop across the valve at a specific handle scale setting and a
given flow rate.
The red curve is the Venturi measuring signal which indicates what differential pressure should be measured across the
Venturi orifice for a given flow.
4.5
BALLOREX Venturi
4.5.7 DN 50 compression/compression
167mm
Specifications
Max. temperature 120C
Min. temperature -20C
120mm Max. pressure 5 bar
Marking on valve (Handle) DN, flow-version, Kvm (Kv-measuring)
(Valve body) DN, PN, flow direction, BROEN
Connection Compression EN 1254-2
122mm
Valve housing DR Brass CW602N CuZn36Pb2As
265mm Ball & needle DR Brass CW602N (chrome plated)
Valve handle Polyamide (PA6.6 30%GF)
Sealings O-rings EPDM
Gaskets PTFE
Test point sealing EPDM
Accessories
BROEN No. Dimension Description
4.5
Flow Diagram
BALLOREX Venturi
0.7 70
0.6 60
Measuring signal
0.5 50
0.4 40
0.0 1.0 2.0 3.0 4.0 5.0 6.0
ition ition ition ition ition ition ition
0.3 30 Pos Pos Pos Pos Pos Pos Pos
7.0
ition
Pos
8.0
ition
0.2 20
Pos
9.0
ition
Pos .9
9
ition
0.1 10
Pos
0.07 7
0.06 6
0.05 5
0.04 4
The black curves are used to determine the total pressure drop across the valve at a specific handle scale setting and a
given flow rate.
The red curve is the Venturi measuring signal which indicates what differential pressure should be measured across the
Venturi orifice for a given flow.
4.5
BALLOREX Venturi
BALLOREX venturi
4.6 Product data sheets - FODRV flange
4.6.1 Product finder
DN300
DN 250
DN 200
DN 150
DN 125
DN 100
DN 80
DN 65
l/s m3/h
Note!
Dimensions 350 - 600 available on request.
4.6
BALLOREX Venturi
4.6.2 DN 65 flange/flange
160mm Specifications
Max. temperature 120C
Min. temperature -20C
269mm Max. pressure 16 bar
Marking on valve (Venturi pipe) DN, maximum temperature and flow
direction (Butterfly gearbox) Valve type, DN and Kvm
Connection Flange: BS 4504 - PN16
Venturi pipe Carbon steel
182mm 185mm
Butterfly valve body Cast iron, fully lugged (ASTMA A126 KL.B)
Disc Stainless steel (ASTM A351)
Shaft Stainless steel (ASTM A276)
Test points DR Brass CW602N CuZn36Pb2As
Sealings EPDM and NBR 1
4.6
Flow Diagram
BALLOREX Venturi
DN 65 flange/flange
Bar kPa Pressure drop across valve
1 100
0.7 70
0.6 60
0.5 50
1.5 2.0 2.5 Measuring signal
ition ition ition
0.4 40
Pos Pos Pos
3.0
ition
0.3 30 Pos
3.5
0.2 20 ition
Pos
4.0
ition
Pos 4.5
ition
Pos 6.0
0.1 10 ition
Pos
0.07 7
0.06 6
0.05 5
0.04 4
The black curves are used to determine the total pressure drop across the valve at a specific handle scale setting and a
given flow rate.
The red curve is the Venturi measuring signal which indicates what differential pressure should be measured across the
Venturi orifice for a given flow.
4.6
BALLOREX Venturi
4.6.3 DN 80 flange/flange
160mm Specifications
Max. temperature 120C
Min. temperature -20C
275mm Max. pressure 16 bar
Marking on valve (Venturi pipe) DN, maximum temperature and flow
direction (Butterfly gearbox) Valve type, DN and Kvm
Connection Flange: BS 4504 - PN16
Venturi pipe Carbon steel
99mm
Butterfly valve body Cast iron, fully lugged (ASTMA A126 KL.B)
249mm 200mm
Disc Stainless steel (ASTM A351)
Shaft Stainless steel (ASTM A276)
76mm Test points DR Brass CW602N CuZn36Pb2As
Sealings EPDM and NBR 1
75mm
164mm
4.6
Flow Diagram
BALLOREX Venturi
DN 80 flange/flange
Bar kPa Pressure drop across valve
1 100
0.04 4
The black curves are used to determine the total pressure drop across the valve at a specific handle scale setting and a
given flow rate.
The red curve is the Venturi measuring signal which indicates what differential pressure should be measured across the
Venturi orifice for a given flow.
4.6
BALLOREX Venturi
160mm
Specifications
Max. temperature 120C
Min. temperature -20C
Max. pressure 16 bar
297mm
Marking on valve (Venturi pipe) DN, maximum temperature and flow
direction (Butterfly gearbox) Valve type, DN and Kvm
Connection Flange: BS 4504 - PN16
Venturi pipe Carbon steel
Butterfly valve body Cast iron, fully lugged (ASTMA A126 KL.B)
325mm 220mm Disc Stainless steel (ASTM A351)
Shaft Stainless steel (ASTM A276)
Test points DR Brass CW602N CuZn36Pb2As
Sealings EPDM and NBR 1
4.6
Flow Diagram
BALLOREX Venturi
DN 100 flange/flange
Bar kPa Pressure drop across valve
1 100
0.7 70
0.6 60
Measuring signal
0.5 50
0.4 40
0.3 30
.0 .5
n3 n3
itio itio .5
Pos Pos itio
n4
0.2 20 Pos
.0
n5
itio
Pos
0.1 10
0.07 7 .0
n6
itio
0.06 6 Pos
0.05 5
0.04 4
The black curves are used to determine the total pressure drop across the valve at a specific handle scale setting and a
given flow rate.
The red curve is the Venturi measuring signal which indicates what differential pressure should be measured across the
Venturi orifice for a given flow.
4.6
BALLOREX Venturi
160mm Specifications
Max. temperature 120C
Min. temperature -20C
307mm Max. pressure 16 bar
Marking on valve (Venturi pipe) DN, maximum temperature and flow
direction (Butterfly gearbox) Valve type, DN and Kvm
Connection Flange: BS 4504 - PN16
Venturi pipe Carbon steel
341mm 250mm
Butterfly valve body Cast iron, fully lugged (ASTMA A126 KL.B)
Disc Stainless steel (ASTM A351)
Shaft Stainless steel (ASTM A276)
Test points DR Brass CW602N CuZn36Pb2As
Sealings EPDM and NBR 1
4.6
Flow Diagram
BALLOREX Venturi
DN 125 flange/flange
Bar kPa Pressure drop across valve
1 100
0.7 70
0.6 60 Measuring signal
0.5 50
0.4 40
2.5 3.0
ition ition
0.3 30 Pos Pos 4.0
ition
Pos
0.2 20
4.5
ition
Pos
5.0
ition
0.1 10 Pos
6.0
ition
0.07 7 Pos
0.06 6
0.05 5
0.04 4
The black curves are used to determine the total pressure drop across the valve at a specific handle scale setting and a
given flow rate.
The red curve is the Venturi measuring signal which indicates what differential pressure should be measured across the
Venturi orifice for a given flow.
4.6
BALLOREX Venturi
160mm Specifications
Max. temperature 120C
Min. temperature -20C
320mm Max. pressure 16 bar
Marking on valve (Venturi pipe) DN, maximum temperature and flow
direction (Butterfly gearbox) Valve type, DN and Kvm
Connection Flange: BS 4504 - PN16
Venturi pipe Carbon steel
354mm 285mm
Butterfly valve body Cast iron, fully lugged (ASTMA A126 KL.B)
Disc Stainless steel (ASTM A351)
Shaft Stainless steel (ASTM A276)
Test points DR Brass CW602N CuZn36Pb2As
Sealings EPDM and NBR 1
4.6
Flow Diagram
BALLOREX Venturi
DN 150 flange/flange
Bar kPa Pressure drop across valve
1 100
.0
ion 2
0.7 70 Posit
0.5 50
0.4 40
Measuring signal
0.3 30
.5 3.0 3.5 n4 .0
ion 2 Position ition ositio
Posit Pos P
0.2 20
.5
ion 4
Posit
0.1 10
.0
ion 5
0.07 7 Posit
0.05 5
.0
0.04 4 ion 6
Posit
0.03 3 Flow rate
16.8 20 30 40 50 57 l/s
The black curves are used to determine the total pressure drop across the valve at a specific handle scale setting and a
given flow rate.
The red curve is the Venturi measuring signal which indicates what differential pressure should be measured across the
Venturi orifice for a given flow.
4.6
BALLOREX Venturi
150mm Specifications
Max. temperature 120C
Min. temperature -20C
354mm Max. pressure 16 bar
Marking on valve (Venturi pipe) DN, maximum temperature and flow
direction (Butterfly gearbox) Valve type, DN and Kvm
Connection Flange: BS 4504 - PN16
Venturi pipe Carbon steel
378mm 340mm
Butterfly valve body Cast iron, fully lugged (ASTMA A126 KL.B)
Disc Stainless steel (ASTM A351)
Shaft Stainless steel (ASTM A276)
Test points DR Brass CW602N CuZn36Pb2As
Sealings EPDM and NBR 1
4.6
Flow Diagram
BALLOREX Venturi
DN 200 flange/flange
Bar kPa Pressure drop across valve
1 100
0.7 70
0.5 50
.0 .5
ion 2
.5
ion 3 ion 3
0.4 40 Posit Posit Posit Measuring signal
io n 4.0
0.3 30 Posit
0.2 20
.5
ion 4
Posit
0.1 10
.0
ion 5
0.07 7 Posit
0.05 5
0.04 4
.0
ion 6
0.03 3 Posit Flow rate
28 30 40 50 60 70 80 90 100 l/s
101 108 144 180 216 252 288 324 360 m3/h
The black curves are used to determine the total pressure drop across the valve at a specific handle scale setting and a
given flow rate.
The red curve is the Venturi measuring signal which indicates what differential pressure should be measured across the
Venturi orifice for a given flow.
4.6
BALLOREX Venturi
190mm Specifications
Max. temperature 120C
Min. temperature -20C
445mm Max. pressure 16 bar
Marking on valve (Venturi pipe) DN, maximum temperature and flow
direction (Butterfly gearbox) Valve type, DN and Kvm
Connection Flange: BS 4504 - PN16
Venturi pipe Carbon steel
411mm 405mm
Butterfly valve body Cast iron, fully lugged (ASTMA A126 KL.B)
Disc Stainless steel (ASTM A351)
Shaft Stainless steel (ASTM A276)
Test points DR Brass CW602N CuZn36Pb2As
Sealings EPDM and NBR 1
4.6
Flow Diagram
BALLOREX Venturi
DN 250 flange/flange
Bar kPa Pressure drop across valve
1 100
0.7 70
0.5 50 .0
ion 2 ion 2
.5
ion 3
.0
ion 3
.5
0.4 40 Posit Posit Posit Posit
Measuring signal
0.3 30 .0
ion 4
Posit
0.2 20
.5
ion 4
Posit
0.1 10
.0
ion 5
Posit
0.07 7
.0
0.05 5 ion 6
Posit
0.04 4
0.03 3 Flow rate
41 50 60 70 80 90 100 157 l/s
The black curves are used to determine the total pressure drop across the valve at a specific handle scale setting and a
given flow rate.
The red curve is the Venturi measuring signal which indicates what differential pressure should be measured across the
Venturi orifice for a given flow.
4.6
BALLOREX Venturi
190mm Specifications
Max. temperature 120C
Min. temperature -20C
490mm Max. pressure 16 bar
Marking on valve (Venturi pipe) DN, maximum temperature and flow
direction (Butterfly gearbox) Valve type, DN and Kvm
Connection Flange: BS 4504 - PN16
Venturi pipe Carbon steel
Butterfly valve body Cast iron, fully lugged (ASTMA A126 KL.B)
465mm 460mm
Disc Stainless steel (ASTM A351)
Shaft Stainless steel (ASTM A276)
Test points DR Brass CW602N CuZn36Pb2As
Sealings EPDM and NBR 1
4.6
Flow Diagram
BALLOREX Venturi
DN 300 flange/flange
Bar kPa Pressure drop across valve
1 100
0.7 70
0.5 50
0.4 40
0.1 10 .5
ion 4
Posit
0.07 7
.0
ion 5
0.05 5 Posit
0.04 4
The black curves are used to determine the total pressure drop across the valve at a specific handle scale setting and a
given flow rate.
The red curve is the Venturi measuring signal which indicates what differential pressure should be measured across the
Venturi orifice for a given flow.
4.6
BALLOREX Venturi
BALLOREX venturi
4.7 Product data sheets - FODRV extended D
DN 200
DN 150
DN 125
DN 100
DN 80
DN 65
1 2 3 4 5 6 7 8 9 10 20 30 40 50 60 70l/s 80 90 100
3.6 7.2 10.8 14.4 18 21.6 28.8 36 72 108 144 180 216 m3/h
252000
288000
324000
360000
Flow range Dimension Section
l/s m3/h
4.7
BALLOREX Venturi
Specifications
Max. temperature 120C
Min. temperature -20C
Max. pressure 16 bar
Marking on valve (Venturi pipe) DN, maximum temperature and flow
direction (Butterfly gearbox) Valve type, DN and Kvm
Connection Flange: BS 4504 - PN16
Venturi pipe Carbon steel
455mm Butterfly valve body Cast iron, fully lugged (ASTMA A126 KL.B)
Disc Stainless steel (ASTM A351)
160mm
Shaft Stainless steel (ASTM A276)
Test points DR Brass CW602N CuZn36Pb2As
Sealings EPDM and NBR 1
269mm
185mm
4.7
Flow Diagram
BALLOREX Venturi
DN 65 extended flange/flange
Bar kPa Pressure drop across valve
1 100
0.7 70
0.6 60
0.5 50
1.5 2.0 2.5 Measuring signal
ition ition ition
0.4 40
Pos Pos Pos
3.0
ition
0.3 30 Pos
3.5
0.2 20 ition
Pos
4.0
ition
Pos 4.5
ition
Pos 6.0
0.1 10 ition
Pos
0.07 7
0.06 6
0.05 5
0.04 4
The black curves are used to determine the total pressure drop across the valve at a specific handle scale setting and a
given flow rate.
The red curve is the Venturi measuring signal which indicates what differential pressure should be measured across the
Venturi orifice for a given flow.
4.7
BALLOREX Venturi
Specifications
Max. temperature 120C
Min. temperature -20C
Max. pressure 16 bar
Marking on valve (Venturi pipe) DN, maximum temperature and flow
direction (Butterfly gearbox) Valve type, DN and Kvm
Connection Flange: BS 4504 - PN16
Venturi pipe Carbon steel
570mm Butterfly valve body Cast iron, fully lugged (ASTMA A126 KL.B)
Disc Stainless steel (ASTM A351)
160mm
Shaft Stainless steel (ASTM A276)
Test points DR Brass CW602N CuZn36Pb2As
Sealings EPDM and NBR 1
275mm
200mm
4.7
Flow Diagram
BALLOREX Venturi
DN 80 extended flange/flange
Bar kPa Pressure drop across valve
1 100
0.04 4
The black curves are used to determine the total pressure drop across the valve at a specific handle scale setting and a
given flow rate.
The red curve is the Venturi measuring signal which indicates what differential pressure should be measured across the
Venturi orifice for a given flow.
4.7
BALLOREX Venturi
Specifications
Max. temperature 120C
Min. temperature -20C
Max. pressure 16 bar
Marking on valve (Venturi pipe) DN, maximum temperature and flow
direction (Butterfly gearbox) Valve type, DN and Kvm
Connection Flange: BS 4504 - PN16
Venturi pipe Carbon steel
735mm Butterfly valve body Cast iron, fully lugged (ASTMA A126 KL.B)
Disc Stainless steel (ASTM A351)
160mm Shaft Stainless steel (ASTM A276)
Test points DR Brass CW602N CuZn36Pb2As
Sealings EPDM and NBR 1
297mm
220mm
4.7
Flow Diagram
BALLOREX Venturi
1 100
0.7 70
0.6 60
Measuring signal
0.5 50
0.4 40
0.3 30
.0 .5
n3 n3
itio itio .5
Pos Pos itio
n4
0.2 20 Pos
.0
n5
itio
Pos
0.1 10
0.07 7 .0
n6
itio
0.06 6
Pos
0.05 5
0.04 4
The black curves are used to determine the total pressure drop across the valve at a specific handle scale setting and a
given flow rate.
The red curve is the Venturi measuring signal which indicates what differential pressure should be measured across the
Venturi orifice for a given flow.
4.7
BALLOREX Venturi
Specifications
Max. temperature 120C
Min. temperature -20C
Max. pressure 16 bar
Marking on valve (Venturi pipe) DN, maximum temperature and flow
direction (Butterfly gearbox) Valve type, DN and Kvm
Connection Flange: BS 4504 - PN16
Venturi pipe Carbon steel
865mm Butterfly valve body Cast iron, fully lugged (ASTMA A126 KL.B)
Disc Stainless steel (ASTM A351)
160mm Shaft Stainless steel (ASTM A276)
Test points DR Brass CW602N CuZn36Pb2As
Sealings EPDM and NBR 1
307mm
250mm
4.7
Flow Diagram
BALLOREX Venturi
0.7 70
0.6 60 Measuring signal
0.5 50
0.4 40
2.5 3.0
ition ition
0.3 30 Pos Pos 4.0
ition
Pos
0.2 20
4.5
ition
Pos
5.0
ition
0.1 10 Pos
6.0
ition
0.07 7 Pos
0.06 6
0.05 5
0.04 4
The black curves are used to determine the total pressure drop across the valve at a specific handle scale setting and a
given flow rate.
The red curve is the Venturi measuring signal which indicates what differential pressure should be measured across the
Venturi orifice for a given flow.
4.7
BALLOREX Venturi
Specifications
Max. temperature 120C
Min. temperature -20C
Max. pressure 16 bar
Marking on valve (Venturi pipe) DN, maximum temperature and flow
direction (Butterfly gearbox) Valve type, DN and Kvm
Connection Flange: BS 4504 - PN16
Venturi pipe Carbon steel
1010mm Butterfly valve body Cast iron, fully lugged (ASTMA A126 KL.B)
Disc Stainless steel (ASTM A351)
160mm
Shaft Stainless steel (ASTM A276)
Test points DR Brass CW602N CuZn36Pb2As
Sealings EPDM and NBR 1
320mm
285mm
4.7
Flow Diagram
BALLOREX Venturi
1 100
.0
ion 2
0.7 70 Posit
0.6 60
0.5 50
0.4 40
Measuring signal
0.3 30
.5 3.0 3.5 n4 .0
ion 2 Position ition ositio
Posit Pos P
0.2 20
.5
ion 4
Posit
0.1 10
.0
ion 5
0.07 7 Posit
0.06 6
0.05 5
.0
ion 6
0.04 4
Posit
0.03 3 Flow rate
16.8 20 30 40 50 57 l/s
The black curves are used to determine the total pressure drop across the valve at a specific handle scale setting and a
given flow rate.
The red curve is the Venturi measuring signal which indicates what differential pressure should be measured across the
Venturi orifice for a given flow.
4.7
BALLOREX Venturi
BALLOREX venturi
4.8 Product data sheets - DRV female
4.8.1 Product finder
DN 50S
DN 40S
DN 32S
DN 25S
DN 20S
DN 20L
DN 15S
DN 15L
Kv-value
0.08 0.1 0.2 0.3 0.4 0.6 0.8 1 2 3 4 5 6 8 10 20 30 40
Capacity
Dimension Section
[Kv-value]
0.083 - 1.62 DN 15L 4.8.2
0.261 - 2.11 DN 15S 4.8.2
0.1 - 4.26 DN 20L 4.8.3
0.325 - 4.81 DN 20S 4.8.3
0.921 - 9.94 DN 25S 4.8.4
1.95 - 13.3 DN 32S 4.8.5
2.6 - 23.3 DN 40S 4.8.6
5.37 - 35.3 DN 50S 4.8.7
4.8
BALLOREX Venturi
4.8.2 DN 15 female/female
57mm Specifications
Max. temperature 135C
Min. temperature -20C
Max. pressure 25 bar
Press ends 16 bar
76mm Marking on valve (Handle) DN, flow-version
(Valve body) DN, PN, BROEN
Connection Female thread ISO 7/1 parallel
Valve housing DR Brass CW602N CuZn36Pb2As
Ball & needle DR Brass CW602N (chrome plated)
75mm Valve handle Polyamide (PA6.6 30%GF)
104mm Sealings O-rings EPDM
Gaskets PTFE
Nom. Kv
BROEN No. Dimension
Inch [m3/h]
Accessories
BROEN No. Dimension Description
83504006-000003 15 mm x 1/2
Pre-sealed press adaptors (2 pcs), max 16 bar
83504007-000003 18 mm x 1/2
4.8
Flow Diagram
BALLOREX Venturi
0.7 70
0.6 60
0.5 50
0.4 40
0.3 30
0.2 20 9.9
0.0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 on
n n n n n n n n n n iti
itio itio io it io it io io io io io io s
it it it it it it Po
Pos Pos P os Pos Pos P os os os os os
P P P P
0.1 10
0.08 8
0.07 7
0.06 6
0.05 5
0.04 4
0.03 3
0.02 2
0.008 0.01 0.02 0.03 0.04 0.05 0.06 0.08 0.1 0.2 l/s
Position 0.0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 9.9
Kv 0.083 0.095 0.159 0.248 0.365 0.519 0.712 0.932 1.16 1.40 1.62
0.7 70
0.6 60
0.5 50
0.4 40
0.3 30
0.2 20
0.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 9.9
n n n n n
on ion io i on ion io itio on io io
sit
i sit os
it sit sit it os iti sit sit
Po Po Po os P Po
s
Po Po
Po P P
0.1 10
0.08 8
0.07 7
0.06 6
0.05 5
0.04 4
0.03 3
0.02 2
0.02 0.03 0.04 0.06 0.08 0.1 0.2 0.3 0.4 0.5 l/s
72 108 144 216 288 360 720 1,080 1,440 1,800 l/h
Position 0.0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 9.9
Kv 0.261 0.267 0.334 0.449 0.601 0.785 1.00 1.26 1.55 1.86 2.11
4.8
BALLOREX Venturi
4.8.3 DN 20 female/female
62mm Specifications
Max. temperature 135C
Min. temperature -20C
Max. pressure 25 bar
Press ends 16 bar
79mm Marking on valve (Handle) DN, flow-version
(Valve body) DN, PN, BROEN
Connection Female thread ISO 7/1 parallel
Valve housing DR Brass CW602N CuZn36Pb2As
75mm
Ball & needle DR Brass CW602N (chrome plated)
Valve handle Polyamide (PA6.6 30%GF)
106mm
Sealings O-rings EPDM
Gaskets PTFE
Nom. Kv
BROEN No. Dimension
Inch [m3/h]
Accessories
BROEN No. Dimension Description
84504006-000003 15 mm x 3/4
84504007-000003 18 mm x 3/4 Pre-sealed press adaptors (2 pcs), max 16 bar
84504008-000003 22 mm x 3/4
4.8
Flow Diagram
BALLOREX Venturi
0.3 30
0.2 20 0 0
0 0 3. 5. 0 0 0 0 9
1. 2. n 4.
0
n 6. 7. 8. 9. 9.
n n io n io n n n n n
io io it io it it io io io io io
os
it
os
it os it os os sit sit sit sit
P P P P os P P Po Po Po Po
0.1 10
0.08 8
0.07 7
0.06 6
0.05 5
0.04 4
0.03 3
0.02 2
72 108 144 216 188 360 720 1,080 1,440 1,800 l/h
Position 0.0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 9.9
Kv 0.094 0.250 0.541 0.870 1.22 1.60 2.03 2.53 3.07 3.67 4.26
Bar
1
kPa
100
Pressure drop across valve DN 20S - Standard flow
0,7 70
0,6 60
0,5 50
0,4 40
0,3 30
0,2 20 0 0 9
0 0 2. 3. 0 0 0 0 0 0
0. 1. 4. 5. 6. 7. 8. 9. 9.
on on on on on on on on on on on
s iti s iti siti s iti siti siti s iti s iti siti s iti s iti
Po Po Po Po Po Po Po Po Po Po Po
0,1 10
0,08 8
0,07 7
0,06 6
0,05 5
0,04 4
0,03 3
0,02 2
0,01 1
Flow rate
0.03 0.04 0.06 0.08 0.1 0.2 0.3 0.4 0.7 l/s
108 144 216 288 360 720 1,080 1,440 2,520 l/h
Position 0.0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 9.9
Kv 0.325 0.494 0.778 1.12 1.50 1.93 2.41 2.93 3.48 4.10 4.81
4.8
BALLOREX Venturi
4.8.4 DN 25 female/female
75mm Specifications
Max. temperature 135C
Min. temperature -20C
Max. pressure 25 bar
Press ends 16 bar
83mm Marking on valve (Handle) DN, flow-version
(Valve body) DN, PN, BROEN
Connection Female thread ISO 7/1 parallel
Valve housing DR Brass CW602N CuZn36Pb2As
75mm
Ball & needle DR Brass CW602N (chrome plated)
Valve handle Polyamide (PA6.6 30%GF)
113mm
Sealings O-rings EPDM
Gaskets PTFE
Nom. Kv
BROEN No. Dimension
Inch [m3/h]
Accessories
BROEN No. Dimension Description
4.8
Flow Diagram
BALLOREX Venturi
1 100
0.7 70
0.6 60
0.5 50
0.4 40
0.3 30
0.2 20
0.0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 9.9
ion io
n ion ion ion io
n ion ion ion ion ion
sit sit sit sit sit sit sit sit sit sit sit
Po Po Po Po Po Po Po Po Po Po Po
0.1 10
0.08 8
0.07 7
0.06 6
0.05 5
0.04 4
0.03 3
0.02 2
288 360 720 1080 1440 1,080 2,160 2,880 3,600 7,200 l/h
Position 0.0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 9.9
Kv 0.921 1.26 1.86 2.58 3.38 4.24 5.21 6.29 7.49 8.78 9.94
4.8
BALLOREX Venturi
4.8.5 DN 32 female/female
88mm Specifications
Max. temperature 135C
Min. temperature -20C
Max. pressure 25 bar
Press ends 16 bar
109mm Marking on valve (Handle) DN, flow-version
(Valve body) DN, PN, BROEN
Connection Female thread ISO 7/1 parallel
Valve housing DR Brass CW602N CuZn36Pb2As
122mm
Ball & needle DR Brass CW602N (chrome plated)
Valve handle Polyamide (PA6.6 30%GF)
166mm
Sealings O-rings EPDM
Gaskets PTFE
Nom. Kv
BROEN No. Dimension
Inch m3/h
4.8
Flow Diagram
BALLOREX Venturi
0.7 70
0.6 60
0.5 50
0.4 40
0.3 30
0.2 20
0.1 10
0.08 8
0.07 7
0.06 6
0.05 5
0.0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 9.9
n n n n n n n n
0.04 4 ion ion ion itio itio itio
itio itio itio itio itio
sit sit sit os os os os os os os os
Po Po Po P P P P P P P P
0.03 3
0.02 2
360 720 1,080 1,440 1,800 2,160 2,880 3,600 7,200 l/h
Position 0.0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 9.9
Kv 1.95 2.32 3.05 3.97 5.00 6.12 7.36 8.70 10.1 11.7 13.3
4.8
BALLOREX Venturi
4.8.6 DN 40 female/female
98mm Specifications
Max. temperature 135C
Min. temperature -20C
Max. pressure 25 bar
Press ends 16 bar
113mm Marking on valve (Handle) DN, flow-version
(Valve body) DN, PN, BROEN
Connection Female thread ISO 7/1 parallel
Valve housing DR Brass CW602N CuZn36Pb2As
Ball & needle DR Brass CW602N (chrome plated)
122mm
Valve handle Polyamide (PA6.6 30%GF)
171mm
Sealings O-rings EPDM
Gaskets PTFE
Nom. Kv
BROEN No. Dimension
Inch [m3/h]
4.8
Flow Diagram
BALLOREX Venturi
0.7 70
0.6 60
0.5 50
0.4 40
0.3 30
0.2 20
0.1 10
0.08 8
0.07 7
0.06 6
0.05 5
0.04 4
0.0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 9.9
n n n n n n n
ion ion ion itio ion itio itio
itio itio itio itio
0.03 3 sit sit sit os sit os os os os os os
Po Po Po P Po P P P P P P
0.02 2
360 720 108 144 1,800 2,160 2,880 3,600 7,200 10,800 l/h
Position 0.0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 9.9
Kv 2.60 3.48 4.86 6.50 8.31 10.3 12.4 14.6 17.1 20.0 23.3
4.8
BALLOREX Venturi
4.8.7 DN 50 female/female
115mm Specifications
Max. temperature 135C
Min. temperature -20C
Max. pressure 25 bar
Press ends 16 bar
120mm Marking on valve (Handle) DN, flow-version
(Valve body) DN, PN, BROEN
Connection Female thread ISO 7/1 parallel
Valve housing DR Brass CW602N CuZn36Pb2As
122mm
Ball & needle DR Brass CW602N (chrome plated)
Valve handle Polyamide (PA6.6 30%GF)
180mm
Sealings O-rings EPDM
Gaskets PTFE
Nom. Kv
BROEN No. Dimension
Inch [m3/h]
4.8
Flow Diagram
BALLOREX Venturi
1 100
0.7 70
0.6 60
0.5 50
0.4 40
0.3 30
0.2 20
0.1 10
0.08 8
0.07 7
0.0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 9.9
0.06 6 on n n n n n n n
i ion itio itio itio ion itio itio itio io ion
sit sit sit it sit
0.05 5 Po os os os os os os os
Po P P P Po P P P P Po
0.04 4
0.03 3
0.02 2
108 144 180 216 288 360 720 1,080 1,440 2,160 2,880 l/h
Position 0.0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 9.9
Kv 5.37 6.95 9.25 11.6 14.0 16.8 20.0 23.4 26.9 30.7 35.3
4.8
BALLOREX Venturi
BALLOREX venturi
4.9 Product data sheets - DRV compression
4.9.1 Product finder
DN 50S
DN 40S
DN 32S
DN 25S
DN 20S
DN 20L
DN 15S
DN 15L
Kv-value
0.08 0.1 0.2 0.3 0.4 0.6 0.8 1 2 3 4 5 6 8 10 20 30 40
Capacity
Dimension Section
[Kv-value]
0.083 - 1.62 DN 15L 4.9.2
0.261 - 2.11 DN 15S 4.9.2
0.1 - 4.26 DN 20L 4.9.3
0.325 - 4.81 DN 20S 4.9.3
0.921 - 9.94 DN 25S 4.9.4
1.95 - 13.3 DN 32S 4.9.5
2.6 - 23.3 DN 40S 4.9.6
5.37 - 35.3 DN 50S 4.9.7
4.9
BALLOREX Venturi
4.9.2 DN 15 compression/compression
62mm
Specifications
Max. temperature 135C
Min. temperature -20C
Max. pressure 5 bar
Marking on valve (Handle) DN, flow-version
76mm (Valve body) DN, PN, BROEN
Connection Compression EN 1254-2
Valve housing DR Brass CW602N CuZn36Pb2As
Ball & needle DR Brass CW602N (chrome plated)
75mm Valve handle Polyamide (PA6.6 30%GF)
Sealings O-rings EPDM
128mm
Gaskets PTFE
Compression connections are not recommendeded for cooling applications.
Instead press or threaded connection are recommended.
Nom. Kv
BROEN No. Dimension
Inch [m3/h]
4350110L-001063 DN 15L 15 mm 1,62
4350110S-001063 DN 15S 15 mm 2,11
Accessories
BROEN No. Dimension Description
4.9
Flow Diagram
BALLOREX Venturi
0.7 70
0.6 60
0.5 50
0.4 40
0.3 30
0.2 20 9.9
0.0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 n
on on n on on n n n n n io
iti iti itio iti iti it io it io itio itio itio sit
s s os Po
s s os os os os os Po
Po Po P Po P P P P P
0.1 10
0.08 8
0.07 7
0.06 6
0.05 5
0.04 4
0.03 3
0.02 2
0.008 0.01 0.02 0.03 0.04 0.05 0.06 0.08 0.1 0.2 l/s
Position 0.0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 9.9
Kv 0.083 0.095 0.159 0.248 0.365 0.519 0.712 0.932 1.16 1.40 1.62
0.7 70
0.6 60
0.5 50
0.4 40
0.3 30
0.2 20
0.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 9.9
on
n n n n n on n n n
i itio it io
itio itio it io siti itio itio
sit
io
sit os os os os os Po os os
Po P P P P P P P Po
0.1 10
0.08 8
0.07 7
0.06 6
0.05 5
0.04 4
0.03 3
0.02 2
0.02 0.03 0.04 0.06 0.08 0.1 0.2 0.3 0.4 0.5 l/s
72 108 144 216 288 360 720 1,080 1,440 1,800 l/h
Position 0.0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 9.9
Kv 0.261 0.267 0.334 0.449 0.601 0.785 1.00 1.26 1.55 1.86 2.11
4.9
BALLOREX Venturi
4.9.3 DN 20 compression/compression
67mm
Specifications
Max. temperature 135C
Min. temperature -20C
Max. pressure 5 bar
Marking on valve (Handle) DN, flow-version
79mm (Valve body) DN, PN, BROEN
Connection Compression EN 1254-2
Valve housing DR Brass CW602N CuZn36Pb2As
Ball & needle DR Brass CW602N (chrome plated)
75mm Valve handle Polyamide (PA6.6 30%GF)
Sealings O-rings EPDM
132mm
Gaskets PTFE
Compression connections are not recommendeded for cooling applications.
Instead press or threaded connection are recommended.
Nom. Kv
BROEN No. Dimension
Inch [m3/h]
4450110L-001063 DN 20L 22 mm 4.26
Accessories
BROEN No. Dimension Description
4.9
Flow Diagram
BALLOREX Venturi
0.3 30
0.2 20 0 0
0 0 3. 5. 0 0 0 0 9
1. 2. n 4.
0
n 6. 7. 8. 9. 9.
n n io n io n n n n n
io io it io it it io io io io io
os
it
os
it os it os os sit sit sit sit
P P P P os P P Po Po Po Po
0.1 10
0.08 8
0.07 7
0.06 6
0.05 5
0.04 4
0.03 3
0.02 2
0.02 0.03 0.04 0.06 0.08 0.1 0.2 0.3 0.4 0.5 l/s
72 108 144 216 188 360 720 1,080 1,440 1,800 l/h
Position 0.0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 9.9
Kv 0.094 0.250 0.541 0.870 1.22 1.60 2.03 2.53 3.07 3.67 4.26
0.7 70
0.6 60
0.5 50
0.4 40
0.3 30
0.2 20 0 0 9
0 0 2. 3. 0 0 0 0 0 0
0. 1. 4. 5. 6. 7. 8. 9. 9.
on on on on on on on on on on on
s iti siti siti siti siti siti s iti siti siti s iti s iti
Po Po Po Po Po Po Po Po Po Po Po
0.1 10
0.08 8
0.07 7
0.06 6
0.05 5
0.04 4
0.03 3
0.02 2
0.03 0.04 0.06 0.08 0.1 0.2 0.3 0.4 0.7 l/s
108 144 216 288 360 720 1,080 1,440 2,520 l/h
Position 0.0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 9.9
Kv 0.325 0.494 0.778 1.12 1.50 1.93 2.41 2.93 3.48 4.10 4.81
4.9
BALLOREX Venturi
4.9.4 DN 25 compression/compression
81mm
Specifications
Max. temperature 135C
Min. temperature -20C
Max. pressure 5 bar
Marking on valve (Handle) DN, flow-version
83mm (Valve body) DN, PN, BROEN
Connection Compression EN 1254-2
Valve housing DR Brass CW602N CuZn36Pb2As
Ball & needle DR Brass CW602N (chrome plated)
75mm Valve handle Polyamide (PA6.6 30%GF)
Sealings O-rings EPDM
140mm
Gaskets PTFE
Compression connections are not recommendeded for cooling applications.
Instead press or threaded connection are recommended.
Nom. Kv
BROEN No. Dimension
Inch [m3/h]
Accessories
BROEN No. Dimension Description
4.9
Flow Diagram
BALLOREX Venturi
1 100
0.7 70
0.6 60
0.5 50
0.4 40
0.3 30
0.2 20
0.0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 9.9
ion io
n ion ion ion io
n ion ion ion ion ion
sit sit sit sit sit sit sit sit sit sit sit
Po Po Po Po Po Po Po Po Po Po Po
0.1 10
0.08 8
0.07 7
0.06 6
0.05 5
0.04 4
0.03 3
0.02 2
288 360 720 1080 1,440 1,080 2,160 2,880 3,600 7,200 l/h
Position 0.0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 9.9
Kv 0.921 1.26 1.86 2.58 3.38 4.24 5.21 6.29 7.49 8.78 9.94
4.9
BALLOREX Venturi
4.9.5 DN 32 compression/compression
93mm
Specifications
Max. temperature 135C
Min. temperature -20C
Max. pressure 5 bar
Marking on valve (Handle) DN, flow-version
109mm (Valve body) DN, PN, BROEN
Connection Compression EN 1254-2
Valve housing DR Brass CW602N CuZn36Pb2As
Ball & needle DR Brass CW602N (chrome plated)
122mm Valve handle Polyamide (PA6.6 30%GF)
Sealings O-rings EPDM
199mm
Gaskets PTFE
Compression connections are not recommendeded for cooling applications.
Instead press or threaded connection are recommended.
Nom. Kv
BROEN No. Dimension
Inch [m3/h]
4.9
Flow Diagram
BALLOREX Venturi
0.7 70
0.6 60
0.5 50
0.4 40
0.3 30
0.2 20
0.1 10
0.08 8
0.07 7
0.06 6
0.05 5
0.0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 9.9
n n n n n n n n
0.04 4 ion ion ion itio itio itio
itio itio itio it io itio
sit sit sit os os os os os os os os
Po Po Po P P P P P P P P
0.03 3
0.02 2
360 720 1,080 1,440 1,800 2,160 2,880 3,600 7,200 l/h
Position 0.0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 9.9
Kv 1.95 2.32 3.05 3.97 5.00 6.12 7.36 8.70 10.1 11.7 13.3
4.9
BALLOREX Venturi
4.9.6 DN 40 compression/compression
107mm
Specifications
Max. temperature 135C
Min. temperature -20C
Max. pressure 5 bar
Marking on valve (Handle) DN, flow-version
113mm (Valve body) DN, PN, BROEN
Connection Compression EN 1254-2
Valve housing DR Brass CW602N CuZn36Pb2As
Ball & needle DR Brass CW602N (chrome plated)
122mm Valve handle Polyamide (PA6.6 30%GF)
Sealings O-rings EPDM
211mm
Gaskets PTFE
Compression connections are not recommendeded for cooling applications.
Instead press or threaded connection are recommended.
Nom. Kv
BROEN No. Dimension
Inch [m3/h]
4.9
Flow Diagram
BALLOREX Venturi
0.7 70
0.6 60
0.5 50
0.4 40
0.3 30
0.2 20
0.1 10
0.08 8
0.07 7
0.06 6
0.05 5
0.04 4
0.0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 9.9
n n n n n n n
ion ion ion itio ion itio itio
itio itio itio itio
0.03 3 sit sit sit os sit os os os os os os
Po Po Po P Po P P P P P P
0.02 2
360 720 108 144 1,800 2,160 2,880 3,600 7,200 10,800 l/h
Position 0.0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 9.9
Kv 2.60 3.48 4.86 6.50 8.31 10.3 12.4 14.6 17.1 20.0 23.3
4.9
BALLOREX Venturi
4.9.7 DN 50 compression/compression
126mm
Specifications
Max. temperature 135C
Min. temperature -20C
Max. pressure 5 bar
Marking on valve (Handle) DN, flow-version
120mm (Valve body) DN, PN, BROEN
Connection Compression EN 1254-2
Valve housing DR Brass CW602N CuZn36Pb2As
Ball & needle DR Brass CW602N (chrome plated)
122mm Valve handle Polyamide (PA6.6 30%GF)
Sealings O-rings EPDM
224mm
Gaskets PTFE
Compression connections are not recommendeded for cooling applications.
Instead press or threaded connection are recommended.
Nom. Kv
BROEN No. Dimension
Inch m3/h
4.9
Flow Diagram
BALLOREX Venturi
1 100
0.7 70
0.6 60
0.5 50
0.4 40
0.3 30
0.2 20
0.1 10
0.08 8
0.07 7
0.0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 9.9
0.06 6 on n n n n n n n
i ion itio itio itio ion itio itio itio io ion
sit sit sit it sit
0.05 5 Po os os os os os os os
Po P P P Po P P P P Po
0.04 4
0.03 3
0.02 2
108 144 180 216 288 360 720 1,080 1,440 2,160 2,880 l/h
Position 0.0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 9.9
Kv 5.37 6.95 9.25 11.6 14.0 16.8 20.0 23.4 26.9 30.7 35.3
4.9
BALLOREX Venturi
BALLOREX venturi
4.10 Product data sheets - DRV flange
4.10.1 Product finder
DN 300
DN 250
DN 200
DN 150
DN 125
DN 100
DN 80
DN 65
3.6 7.2 10.8 14.4 18.0 21.6 28.8 36 72 108 144 180 216 288 360 720 1,080 1,440 2,160 2,880 3,600 m3/h
Capacity
Dimension Section
[Kv-value]
18.34 - 148 DN 65 4.10.2
28.3 - 237 DN 80 4.10.3
14.1 - 603 DN 100 4.10.4
30.5 - 888 DN 125 4.10.5
71.9 - 2,340 DN 150 4.10.6
127 - 2,845 DN 200 4.10.7
234 - 4,549 DN 250 4.10.8
819 - 7,761 DN 300 4.10.9
Note!
Dimensions DN 350 - 600 are available on request.
4.10
BALLOREX Venturi
4.10.2 DN 65 flange/flange
Specifications
160mm Max. temperature 120C
Min. temperature -20C
Max. pressure PN 16
Marking on valve (Butterfly gearbox) Valve type, DN and Kvm
269mm Connection Flange: BS 4504 - PN16
Butterfly valve body Cast iron, fully lugged (ASTMA A126 KL.B)
185mm Disc Stainless steel (ASTM A351)
45mm
Shaft Stainless steel (ASTM A276)
Sealings EPDM and NBR 1
Nom. Kv
BROEN No. Dimension
Inch [m3/h]
4.10
Flow Diagram
BALLOREX Venturi
DN 65 flange/flange
Bar kPa Pressure drop across valve
1 100
0.7 70
0.6 60
0.5 50
0.4 40
0.3 30
0.2 20
5 0 5 0 5 0 0
2.
0 2. 3. 3. 4. 4. 5. 6.
n io
n io
n
io
n
io
n
io
n on on
sit
io
sit sit sit sit sit is ti siti
Po Po Po Po Po Po Po Po
0.1 10
0.08 8
0.07 7
0.06 6
0.05 5
0.04 4
0.03 3
0.02 2
0.36 0.72 1.08 1.44 1.8 2.16 2.88 3.6 7.2 10.8 m3/h
Position 2 3 4 5 6
Note!
Settings below 2 are not recommended.
4.10
BALLOREX Venturi
4.10.3 DN 80 flange/flange
Specifications
160mm Max. temperature 120C
Min. temperature -20C
Max. pressure PN 16
Marking on valve (Butterfly gearbox) Valve type, DN and Kvm
275mm
Connection Flange: BS 4504 - PN16
Butterfly valve body Cast iron, fully lugged (ASTMA A126 KL.B)
200mm
Disc Stainless steel (ASTM A351)
46mm Shaft Stainless steel (ASTM A276)
Sealings EPDM and NBR 1
Nom. Kv
BROEN No. Dimension
Inch [m3/h]
3937910-080009 DN 80 3 2.37
4.10
Flow Diagram
BALLOREX Venturi
DN 80 flange/flange
Bar kPa Pressure drop across valve
1 100
0.7 70
0.6 60
0.5 50
0.4 40
0.3 30
2.0 2.5 3.0 3.5 4.0 4.5 5.0
n n n n n n n
itio itio it io itio itio it io itio
Pos P os Pos Pos Pos Pos Pos
0.2 20
0.1 10
0.08 8
0.07 7
0.06 6
0.05 5
0.04 4
0.03 3
0.02 2
0.72 1.08 1.44 1.8 2.16 2.88 3.6 7.2 10.8 14.4 18 m3/h
Position 2 3 4 5 6
Note!
Settings below 2 are not recommended.
4.10
BALLOREX Venturi
Specifications
160mm Max. temperature 120C
Min. temperature -20C
Max. pressure PN 16
Marking on valve (Butterfly gearbox) Valve type, DN and Kvm
297mm Connection Flange: BS 4504 - PN16
Butterfly valve body Cast iron, fully lugged (ASTMA A126 KL.B)
220mm Disc Stainless steel (ASTM A351)
99mm
Shaft Stainless steel (ASTM A276)
52mm
Sealings EPDM and NBR 1
76mm
75mm
164mm
Nom. Kv
BROEN No. Dimension
Inch [m3/h]
4.10
Flow Diagram
BALLOREX Venturi
DN 100 flange/flange
Bar kPa Pressure drop across valve
1 100
0.7 70
0.6 60
0.5 50
2.0 2.5 3.0 3.5 4.0 4.5 5.0
0.4 40 io
n
io
n ion io
n
io
n on ion
sit sit sit sit sit s iti sit
Po Po Po Po Po Po Po
0.3 30
5.5
0.2 20 i on
sit
Po
0
6.
n
it io
0.1 10 Pos
0.08 8
0.07 7
0.06 6
0.05 5
0.04 4
0.03 3
0.02 2
2 3 4 5 6 8 10 20 30 40 50 60 l/s
0.72 1.08 1.44 1.8 2.16 2.88 3.6 7.2 10.8 14.4 18 21.6 m3/h
Position 2 3 4 5 6
Note!
Settings below 2 are not recommended.
4.10
BALLOREX Venturi
Specifications
160mm
Max. temperature 120C
Min. temperature -20C
Max. pressure PN 16
Marking on valve (Butterfly gearbox) Valve type, DN and Kvm
307mm Connection Flange: BS 4504 - PN16
Butterfly valve body Cast iron, fully lugged (ASTMA A126 KL.B)
250mm Disc Stainless steel (ASTM A351)
Shaft Stainless steel (ASTM A276)
55mm
Sealings EPDM and NBR 1
Nom. Kv
BROEN No. Dimension
Inch [m3/h]
4.10
Flow Diagram
BALLOREX Venturi
DN 125 flange/flange
Bar kPa Pressure drop across valve
1 100
0.7 70
0.6 60
0.5 50
0.4 40
0.3 30
2.0 2.5 3.0 3.5 4.0 4.5
ion ion ion ion ion ion
sit sit sit sit sit sit 5.0
0.2 20 Po Po Po Po Po Po on
i
sit
Po
0.1 10 6.0
i on
sit
0.08 8 Po
0.07 7
0.06 6
0.05 5
0.04 4
0.03 3
0.02 2
1.08 1.44 1.8 2.16 2.88 3.6 7.2 10.8 14.4 18 21.6 28.8 m3/h
Position 2 3 4 5 6
Note!
Settings below 2 are not recommended.
4.10
BALLOREX Venturi
Specifications
160mm
Max. temperature 120C
Min. temperature -20C
Max. pressure PN 16
Marking on valve (Butterfly gearbox) Valve type, DN and Kvm
320mm Connection Flange: BS 4504 - PN16
Butterfly valve body Cast iron, fully lugged (ASTMA A126 KL.B)
285mm Disc Stainless steel (ASTM A351)
Shaft Stainless steel (ASTM A276)
56mm
Sealings EPDM and NBR 1
Nom. Kv
BROEN No. Dimension
Inch [m3/h]
4.10
Flow Diagram
BALLOREX Venturi
DN 150 flange/flange
Bar kPa Pressure drop across valve
1 100
0.7 70
0.6 60
0.5 50
0.4 40
0.3 30
2.0 2.5 3.0 3.5 4.0 4.5 5.0
on io
n ion on ion io
n
io
n
s iti sit sit s iti sit sit sit
0.2 20 Po Po Po Po Po Po Po
0.1 10
6.0
n
0.08 8 it io
0.07 7 P os
0.06 6
0.05 5
0.04 4
0.03 3
0.02 2
Position 2 3 4 5 6
Note!
Settings below 2 are not recommended.
4.10
BALLOREX Venturi
Specifications
150mm
Max. temperature 120C
Min. temperature -20C
Max. pressure PN 16
Marking on valve (Butterfly gearbox) Valve type, DN and Kvm
354mm Connection Flange: BS 4504 - PN16
Butterfly valve body Cast iron, fully lugged (ASTMA A126 KL.B)
340mm Disc Stainless steel (ASTM A351)
Shaft Stainless steel (ASTM A276)
60mm
Sealings EPDM and NBR 1
Nom. Kv
BROEN No. Dimension
Inch [m3/h]
4.10
Flow Diagram
BALLOREX Venturi
DN 200 flange/flange
Bar kPa Pressure drop across valve
1 100
0.7 70
0.6 60
0.5 50
0.4 40
0.3 30
0.2 20
0.1 10
0.03 3
0.02 2
Position 2 3 4 5 6
Note!
Settings below 2 are not recommended.
4.10
BALLOREX Venturi
Specifications
Max. temperature 120C
190mm
Min. temperature -20C
Max. pressure PN 16
Marking on valve (Butterfly gearbox) Valve type, DN and Kvm
445mm Connection Flange: BS 4504 - PN16
Butterfly valve body Cast iron, fully lugged (ASTMA A126 KL.B)
405mm
Disc Stainless steel (ASTM A351)
Shaft Stainless steel (ASTM A276)
68mm Sealings EPDM and NBR 1
Nom. Kv
BROEN No. Dimension
Inch [m3/h]
4.10
Flow Diagram
BALLOREX Venturi
DN 250 flange/flange
Bar kPa Pressure drop across valve
1 100
0.7 70
0.6 60
0.5 50
0.4 40
0.3 30
0.2 20
2.5 3.0 3.5 4.0 4.5 5.0 6.
0
0
on
2.
Po
sit
Po Po Po Po Po Po
Po
0.1 10
0.08 8
0.07 7
0.06 6
0.05 5
0.04 4
0.03 3
0.02 2
Position 2 3 4 5 6
Note!
Settings below 2 are not recommended.
4.10
BALLOREX Venturi
Specifications
190mm Max. temperature 120C
Min. temperature -20C
Max. pressure PN 16
Marking on valve (Butterfly gearbox) Valve type, DN and Kvm
490mm Connection Flange: BS 4504 - PN16
Butterfly valve body Cast iron, fully lugged (ASTMA A126 KL.B)
460mm Disc Stainless steel (ASTM A351)
Shaft Stainless steel (ASTM A276)
78mm
Sealings EPDM and NBR 1
Nom. Kv
BROEN No. Dimension
Inch [m3/h]
4.10
Flow Diagram
BALLOREX Venturi
DN 300 flange/flange
Bar kPa Pressure drop across valve
1 100
0.7 70
0.6 60
0.5 50
0.4 40
0.3 30
0.2 20
1.5 2.0 2.5 3.0 3.5 4.0 4.5 5.0 6.0
on on on on n n
i ion i i ion ion i itio itio
sit sit sit sit sit sit sit os os
Po Po Po Po Po Po Po P P
0.1 10
0.08 8
0.07 7
0.06 6
0.05 5
0.04 4
0.03 3
0.02 2
Position 2 3 4 5 6
Note!
Settings below 2 are not recommended.
4.10
BALLOREX Venturi
4.11 Applications
The BALLOREX Venturi is a manual balancing valve with distinct advantages, such as direct flow measurement, flexible
installation and easy flow setting. The BALLOREX Venturi can be used in numerous types of applications. The most common
ones are illustrated below.
BMS
A 2-port control valve connected to the BMS is installed to control the flow.
4.11
BALLOREX venturi
4.11 Applications
4.11
BALLOREX Venturi
4.11 Applications
BMS
In an underfloor heating system BALLOREX Venturi will ensure that all circuits have sufficient flow in maximum load
situations.
Actuators connected to the BMS control the flow in each room.
4.11
Kv-values vs. pre-setting values
5.0 6.0 7.0 8.0 9.0 9.9 Specific valve settings
BALLOREX Venturi DN 15 - 50
0,1 0,2 0,3 0,4 0,5 0,6 0,7 0,8 0,9 1,0 2,0 3,0 4,0 5,0 6,0 7,0 8,0 9,0 10 20 30
DN 50 0.0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 9.9
DN 40 0.0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 9.9
DN 32 0.0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 9.9
0.0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 9.9
DN 25
0.0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.9
0.0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 9.9
DN 20 0.0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 9.9
BALLOREX venturi
4.12 Conversion charts
1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 9.9
DN 15 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 9.9
3.0 4.0 5.0 6.0 7.0 9.9
0,1 0,2 0,3 0,4 0,5 0,6 0,7 0,8 0,9 1,0 2,0 3,0 4,0 5,0 6,0 7,0 8,0 9,0 10 20 30
Kv-value
4.12
4.12
Kv- converter Danfoss MSV BD LENO to BALLOREX Venturi
1 2 3 4 5 6 7 8 9 10
DN 50
0.0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 9.9
DN 40 1 2 3 4 5 6 7 8 9 10
0.0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 9.9
1 2 3 4 5 6 7 8 9 10
DN 32
0.0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 9.9
1 2 3 4 5 6 7
DN 25 0.0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 9.9
BALLOREX Venturi
4.12 Conversion charts
0.0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.9
1 2 3 4 5 6 7
0.0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 9.9
DN 20 0.0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 9.9
1.0 2.0 3.0 4.0 5.0 6 9.9
1 2 3 4 5 6 7
1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 9.9
DN 15 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 9.9
3.0 4.0 5.0 6.0 7.0 9.9
DN 10 1 2 3 4 5 6 7
0,1 0,2 0,3 0,4 0,5 0,6 0,7 0,8 0,9 1,0 2,0 3,0 4,0 5,0 6,0 7,0 8,0 9,0 10 20 30 40
Kv-value
5.0 6.0 7.0 8.0 9.0 9.9 BROEN BALLOREX Venturi
4 5 6 7 Oventrop Hydrocontrol R
1 2 3 4 5 6 7 8 9 10
DN 50
0.0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 9.9
DN 40 1 2 3 4 5 6 7 8 9 10
BALLOREX venturi
0.0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 9.9
4.12 Conversion charts
1 2 3 4 5 6 7 8 9 10
DN 32
0.0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 9.9
1 2 3 4 5 6 7
DN 25 0.0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 9.9
0.0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.9
1 2 3 4 5 6 7
0.0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 9.9
DN 20 0.0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 9.9
1.0 2.0 3.0 4.0 5.0 6 9.9
1 2 3 4 5 6 7
1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 9.9
DN 15 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 9.9
3.0 4.0 5.0 6.0 7.0 9.9
DN 10 1 2 3 4 5 6 7
0,1 0,2 0,3 0,4 0,5 0,6 0,7 0,8 0,9 1,0 2,0 3,0 4,0 5,0 6,0 7,0 8,0 9,0 10 20 30 40
Kv-value
5.0 6.0 7.0 8.0 9.0 9.9 BROEN BALLOREX Venturi
4 5 6 7 Oventrop Hydrocontrol R
4.12
4.12
Kv- converter Oventrop Hydrocontrol R to BALLOREX Venturi
1 2 3 4 5 6 7 8 9 10
DN 50
0.0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 9.9
DN 40 1 2 3 4 5 6 7 8 9 10
0.0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 9.9
1 2 3 4 5 6 7 8 9 10
DN 32
0.0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 9.9
BALLOREX Venturi
1 2 3 4 5 6 7
4.12 Conversion charts
DN 25 0.0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 9.9
0.0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.9
1 2 3 4 5 6 7
0.0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 9.9
DN 20 0.0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 9.9
1.0 2.0 3.0 4.0 5.0 6 9.9
1 2 3 4 5 6 7
1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 9.9
DN 15 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 9.9
3.0 4.0 5.0 6.0 7.0 9.9
DN 10 1 2 3 4 5 6 7
0,1 0,2 0,3 0,4 0,5 0,6 0,7 0,8 0,9 1,0 2,0 3,0 4,0 5,0 6,0 7,0 8,0 9,0 10 20 30 40
Kv-value
5.0 6.0 7.0 8.0 9.0 9.9 BROEN BALLOREX Venturi
4 5 6 7 Oventrop Hydrocontrol R
0,1 0,2 0,3 0,4 0,5 0,6 0,7 0,8 0,9 1,0 2,0 3,0 4,0 5,0 6,0 7,0 8,0 9,0 10 20 30
Kv-value 5.0 6.0 7.0 8.0 9.0 9.9 BROEN BALLOREX Venturi
2.5 3.0 3.5 4.0 TA STAD
4.12
BALLOREX Venturi
4.13 Mounting instructions DN 15 - 50
Make sure the dimension of the balancing valve
corresponds to the design flow.
4.13
BALLOREX venturi
4.13 Mounting instructions DN 15 - 50
0xDN straight piping required.
4.13
BALLOREX Venturi
4.13 Mounting instructions DN 15 - 50
Connect flow meter and select valve / enter Venturi Kv
(printed on handle) on the flow meter.
4.13
BALLOREX venturi
4.14 Mounting instructions DN 65 - 300
FODRV BALLOREX Venturi FODRV must be installed so that the
flow direction is as indicated by the direction arrow on the
valve body.
4.14
BALLOREX Venturi
4.14 Mounting instructions DN 65 - 300
0 x DN
5 x DN 0 x DN
4.14
BALLOREX venturi
4.14 Mounting instructions DN 65 - 300
4.14
BALLOREX Venturi
4.15 Correction for glycolic mixtures
When glycol is added to the water the density of the media changes. This also affects the measuring of differential
pressure on all types of balancing valves.
For exact measurements the equivalent flow to be calculated into the flow-equation:
P x water 20C
Q = Kv
water/glycol mixture
To compensate for a given glycol content the equivalent flow to be measured is calculated. For this purpose the density
of the water/glycol mixture at a given temperature is required.
Example
A cooling system with a media temperature of -2C has a content of 30% ethylene glycol. In the table on the next page
the graph for 30% crosses -2C on the X-axis where the density of 1052 kg/m3 is read on the Y-axis.
Find the media temperature on the X-axis (example -2 C). Find the intersection with the medias glycol concentration
(example 30%). Read the density vertically on the Y-axis (example 1052 kg/m3).
A valve has a design flow of 0,854 m3/h, a Kv-value of 1,56 and measures P of 0,3 bar.
Inserted in the flow equation, the equivalent flow, to be measured on the valve to compensate for glycol density, is
calculated:
0,3 x 998
Qequivalent = 1,56 = 0,832 m3/h
1052
4.15
BALLOREX venturi
4.15 Correction for glycolic mixtures
Density correction for ethylene glycol* water mixtures
1080
1070
1060
1030
1000
30% Glycol
990
20% Glycol
980
-2 C
970 10% Glycol
960
0%
-20 -10 0 10 20 30 40 50 60 70 80 90 100
Fluid temperature [oC]
1050
1040
1030
1020
1010
1000
990
50% Glycol
980
40% Glycol
30% Glycol
10% Glycol
960
0%
-20 -10 0 10 20 30 40 50 60 70 80 90 100
Fluid temperature [o C]
* The densities are average values for ethylene and propylene glycols used by ASHRAE (American Society of Heating, Refrigerating, and
Air-Conditioning Engineers).
4.15
BALLOREX Venturi
4.15 Correction for glycolic mixtures
Flow correction factors
In the diagram on the following pages the various densities have been converted into correction factors that can be
multiplied directly by the design flow rate.
Example
A cooling system with a media temperature of -2C has a content of 30% ethylene glycol. In the table on the next page
the graph for 30% crosses -2C on the X-axis where the density correction factor indicates 0,974 on the Y-axis.
The valve has a design flow rate of 0,854 m3/h, and the equivalent flow to be measured:
4.15
BALLOREX venturi
4.15 Correction for glycolic mixtures
1,03
1,025
1,02 0% Glycol
1,015
10% Glycol
1,01
1 30% Glycol
0,995
40% Glycol
0,99
50% Glycol
0,985
60% Glycol
0,98
0,975
0,974
0,97
0,965
0,96
0,955
0,95
-2 C
0,945
-20 -10 0 10 20 30 40 50 60 70 80 90 100
Fluid temperature oC
0,995
0,99
0,985
0,98
0,975
0,97
0,965
-20 -10 0 10 20 30 40 50 60 70 80 90 100
Fluid temperature oC
*The densities are average values for ethylene and propylene glycols used by ASHRAE (American Society of Heating, Refrigerating, and
Air-Conditioning Engineers).
4.15
BALLOREX Venturi