You are on page 1of 3

Commissioning Service

Department
Commissioning Standard Test
Formats
Description: TRIP CKT. SUPERVISION XR350 Record No. :
Bay no.: Drawing ref.: Sheet :1 of 3
Contractor : Contract no.: Substation No :

1. GENERAL DATA AND INFORMATION:


Bay no. Serial No.
Bay name Model No. EPXR350S51130606
Make REYROLLE Voltage 125 VDC
No. of
Flag Type SELF RESET 3 NC + 1 NO
Contacts

2. MECHANICAL CHECKS AND VISUAL INSPECTION:

ITEM DESCRIPTION CHECKED


1 Inspect for any physical damage or defects.

2 Check reset operation


Check serial no. of relay matching with serial no. of
3
case

3. ELECTRICAL TESTS:
1 FUNCTION TEST:

ITEM DESCRIPTION CHECKED


1 All contact checked

2 All output contacts resistance checked

3 Flag Operation Checked

2 PICK UP/DROP OFF TEST:

PICK UP DROP OFF


Relay Cut-of
COIL VOLTAGE CURRENT VOLTAGE CURRENT
Terminals Contacts
(V) (mA) (V) (mA)
Coil A 21 22
Coil B 13 14
Coil C 27 28

Operating range : 80 -110 %Vn ( According to relay catalogue )

Tested by: ENG. Witnessed by: ENG.

Signature & Date: Signature & Date:


Commissioning Service
Department
Commissioning Standard Test
Formats
Description: TRIP CKT. SUPERVISION XR350 Record No. :
Bay no.: Drawing ref.: Sheet :2 of 3
Contractor : Contract no.: Substation No :

3 TIMING TEST:

Contacts Pick up Time Resetting Time


COIL
Number (m sec) (m sec)
Coil C

Limits: Resetting Time:> 400 mSec at Vn to 0 ( According to relay catalogue )

4 BURDEN:

Current
Coil Voltage (V) WATTS (W)
(mA)

CB OPEN Coil A

CB CLOSE Coil B

ALARM CIRCUIT Coil C

Limits: CB Open : 1 W , CB Close : 2 W , Alarm Circuit : 4 W ( According to relay


catalogue )

Tested by: ENG. Witnessed by: ENG.

Signature & Date: Signature & Date:


Commissioning Service
Department
Commissioning Standard Test
Formats
Description: TRIP CKT. SUPERVISION XR350 Record No. :
Bay no.: Drawing ref.: Sheet :3 of 3
Contractor : Contract no.: Substation No :

AL-BABTAIN

Tested by: ENG. Witnessed by: ENG.

Signature & Date: Signature & Date: