NAME1 NAME2 NAME3 NAME4 VALUE


[[RELAY SETUP]]
<PORT SETTING>
- RS232-1 -
Line Speed 19200
Parity Bit NONE
Data Bit 8
Stop Bit 1
Line Type 2
CTS functioON
DCD functi OFF
RTS functio AUTO
CTS Check-5
DCD Time-o5000
TX Post del 50
TX Pre Dela5
- RS232-2 -
Line Speed 19200
Parity Bit NONE
Data Bit 8
Stop Bit 1
Line Type 2
CTS functioON
RTS functio AUTO
DCD functi OFF
CTS Check-5
DCD Time-o5000
TX Post del 50
TX Pre Dela5
- ETHERNET -
IP Address 0
IP Address 0
IP Address 0
IP Address 0
Gateway Ad0
Gateway Ad0
Gateway Ad0
Gateway Ad0
Subnet Mas255.255.255.000
Keep-Alive DISABLE
Keep-Alive 4
Keep-Alive 2
keep-Alive 1
<COMMUNICATION>
- DNP3.0 (1) -
Function DISABLE
Use Port P2-232
Master Add60000
Slave Addr 1
D/L Confir SOME
D/L Retries 2
D/L Timeou55
A/L Retries 1
A/L Timeou 55

Page 1
Primary

SBO Time ( 15
Multiframe 0.10
PowerUp UnENABLE
Unsol Time 5
Unsol Type NOTRIG
Class 1 DISABLE
Class 2 DISABLE
Class 3 DISABLE
Master IP O0
Master IP O0
Master IP O0
Master IP O0
TCP/UDP SeTCP
TCP Port 20000
UDP Port 20000
Keep-Alive 10
Fragment s 2048
Time Reque1440
- DNP3.0 (2) -
Function DISABLE
Use Port P3-232
Master Add60000
Slave Addr 2
D/L Confir SOME
D/L Retries 2
D/L Timeou55
A/L Retries 1
A/L Timeou 55
SBO Time ( 15
Multiframe 0.10
PowerUp UnENABLE
Unsol Time 5
Unsol Type NOTRIG
Class 1 DISABLE
Class 2 DISABLE
Class 3 DISABLE
Master IP O0
Master IP O0
Master IP O0
Master IP O0
TCP/UDP SeTCP
TCP Port 20000
UDP Port 20000
Keep-Alive 10
Fragment s 2048
Time Reque1440
- MODBUS -
Function DISABLE
Use Port P4-TCP
Slave Addr 1
Tx Delay (s 0.005
TCP/UDP SeTCP
TCP Port 502
UDP Port 502

Page 2
Primary

- IEC60870-5-101 -
Function DISABLE
Use Port P2-232
Link Addres1
ASDU Addre1
Cyclic Peri 60
Event Perio15
Retries 0
D/L Confirm15
Max Poll Ti 60
ASDU Addre2
Link Confi ALWAYS
Link Addres1
Rx Frame S261
Rx Frame T 15
Tx Frame S 261
COT Size 1
IOA Size 2
One Char RNO
Frame Repe30
Select Time5
Use cmdAc YES
Use cseAct YES
Send Clock YES
- IEC60870-5-104 -
Function DISABLE
ASDU Addre1
Cyclic Peri 60
t0 Connecti120
t1 Ack (sec 15
t2 SFrame (10
t3 Test (sec20
Event Delay5
TCP Port 2404
Rx Frame S255
Tx Frame S 255
Select Time5
Use cmdAc YES
Use cseAct YES
Send Clock YES
- EVENT&ETC -
AI Event M OFF
SKIP at FaulYES
Fault I EvenYES
BI Event M ALL
BI Queue S 256
AI Event M ALL
AI Queue S 256
CI Event M ALL
CI Queue S 256
AI V Unit 10V
AI P Unit 10K
Daily Max I NO
Daily EnergNO

Page 3
Primary

Event SendLOCAL
Time SynccLOCAL
<COMMON>
- GAS SENSOR -
Sensor Typ NONE
- EVENT RECORDER -
Fault Cycle ON
Length of P 4
Load ProfileON
LP Save Ti 15
- TIME SET -
Time Sync GMT
GMT Sign +
GMT Hour 0
GMT Min 0
- TIME DISPLAY -
Display TypYMD
[[MONITORING SETUP]]
<TRIP/BATTERY TEST>
- TRIP COUNTER -
Function OFF
Relays (00 0000
Counter for10000
Counter Se 77
- BATTERY TEST -
Battery Test0000
<GAS LOW>
- GAS LOW LOCK -
Function DISABLE
<FAULT LOCATOR>
- FAULT LOCATOR -
Function OFF
Length of F 50.0
Z1-Resistiv 10.0
Z1-Inductiv10.0
Z0-Resistiv 10.0
Z0-Inductiv10.0
<DEMAND>
- DEMAND -
Function OFF
Relays (00 0000
Type THM
Time Const 5
Pickup-Pha 600
Pickup-Gro 300
Pickup-NEG600
<RECLOSER WEAR>
- RECLOSER WEAR -
Function ALARM
Pickpu Wear20.0
Rated Volta27
Interrupt R 12.5
Number of 100
Wear Set-A 100.00

Page 4
Primary

Wear Set-B 100.00


Wear Set-C 100.00
<SYNCHRO CHECK>
- SYNCHRO CHECK -
Function OFF
Relays (00 0000
Dead Line 0.50
Live Line M 0.85
Max. Volt D0.10
Max. Angle 15
Max. Freq D2.00
SynchrocheS(CB)
<EXTTRIP & LOCK>
- EXTTRIP & LOCK -
Function DISABLE
Use Input P1
Reset Meth LOCAL ONLY
<LIVE LOAD BLOCKING>
- LIVE LOAD BLOCKING -
Function OFF
Pickup 0.30
Time Delay 1.00
[[SYSTEM SETUP]]
<SYSTEM>
- CURRENT SENSING -
Phase CT Ra1000
Ground CT 1000
SEF CT Rati1000
- LINE VS SENSING -
Connect Ty CVD-W
VT 2nd (V) 84.8
VT Ratio 155.9
- LINE VL SENSING -
Connect Ty CVD-W
VT 2nd (V) 84.8
VT Ratio 155.9
Install Type 3P
- SYSTEM POWER -
Frequency 60
Phase RotatABC
Install Dire NOR
Phase Combabc
- AUTO SETTING GROUP CHANGE -
Function DISABLE
Time (sec) 30
- PANEL SLEEP TIME -
Interval (m 5
<LOOP CONTROL>
- LOOP CONTROL -
Select recl NONE
VRS at Sec VS
VRS to Tie VS
VS Wire 3PN
VL Wire 3PN(NA)

Page 5
Primary

Auto Change OFF


Auto Change OFF
LC Action a DISABLE
LC Action a DISABLE
Open Time 10.00
Auto Restor5.00
Dead Line M50.0
Live Line M 70.0
Dead Line P50.00
LIve Line R 10.00
Dead Line R5.00
Non Reclose10.00
<OPTO INPUT SET>
- INPUT 1 -
Function NONE
Debounce T0.02
- INPUT 2 -
Function NONE
Debounce T0.02
- INPUT 3 -
Function NONE
Debounce T0.02
- INPUT 4 -
Function NONE
Debounce T0.02
- INPUT 5 -
Function NONE
Debounce T0.02
- INPUT 6 -
Function NONE
Debounce T0.02
- INPUT 7 -
Function NONE
Debounce T0.02
- INPUT 8 -
Function NONE
Debounce T0.02
<OUTPUT RELAY SET>
- OUTPUT 1 -
Function NONE
Type S/R LATCH
Pulse Time 0.05
- OUTPUT 2 -
Function NONE
Type S/R LATCH
Pulse Time 0.05
- OUTPUT 3 -
Function NONE
Type S/R LATCH
Pulse Time 0.05
- OUTPUT 4 -
Function NONE
Type S/R LATCH
Pulse Time 0.05

Page 6
Primary

- OUTPUT 5 -
Function NONE
Type S/R LATCH
Pulse Time 0.05
- OUTPUT 6 -
Function NONE
Type S/R LATCH
Pulse Time 0.05
- OUTPUT 7 -
Function NONE
Type S/R LATCH
Pulse Time 0.05
- OUTPUT 8 -
Function NONE
Type S/R LATCH
Pulse Time 0.05
<POWER QUALITY>
- SUPPLY OUTAGE -
Function DISABLE
Duration 60
- SAG -
Function DISABLE
Pickup 0.80
Duration 5
- SWELL -
Function DISABLE
Pickup 1.20
Duration 5
- CURRENT UNBALANCE -
Function DISABLE
Pickup 30
Time Delay 4.0
UB Current 10
- VOLTAGE UNBALANCE -
Function DISABLE
Pickup 30
Time Delay 4.0
[[PROTECTION SETUP]]
<OTHER VIEW>
- OTHER ELEMENT -
Seq Coord OFF
Lockout PrioGND
F/I Reset AUTO
Manual Clos0.00
<DIRECTION ELEMENT>
- PHASE -
Direction T OFF
Max. Torque300
Min. Pol Vol0.20
Block OvercNO
- GROUND -
Direction T OFF
Max. Torque135
Min. Pol Vol0.20

Page 7
Primary

Block OvercNO
- SEF -
Direction T OFF
Max. Torque135
Min. Pol Vol0.20
Block OvercNO
- NEGATIVE -
Direction T OFF
Max. Torque135
Min. Pol Vol0.20
Block OvercNO
<OPERATIONS>
- Lockout -
Phase 4
Ground 4
S.E.F 4
NEG 4
- Fast Curve -
Phase 2
Ground 2
NEG 2
<INTERVALS>
- INTERVAL -
Reclosing T0.60
Reclosing T2.00
Reclosing T15.00
Reclosing T15.00
Reset Timeo30.00
Reset Timeo10.00
Closing Pow60.00
<PICKUP CURRENT>
- PICKUP CURRENT -
Phase 120
Ground 10
S.E.F OFF
NEG Seq OFF
<PHASE/GND/SEF/NEGATIVE>
- PHASE FAST -
Curve Prev OFF
Function TR&AR
Relays (00 0001
Curve IEC-SI
Time Dial 0.10
Time Adder 0.00
Min. Res Ti 0.00
Reset Meth INST
Low Set DT OFF
- PHASE DELAY -
Curve Prev OFF
Function TR&AR
Relays (00 0001
Curve IEC-SI
Time Dial 0.10
Time Adder 0.00

Page 8
Primary

Min. Res Ti 0.00


Reset Meth INST
Low Set DT OFF
- GROUND FAST -
Curve Prev OFF
Function TR&AR
Relays (00 0001
Curve DEF-1S
Time Dial 0.40
Time Adder 0.00
Min. Res Ti 0.00
Reset Meth INST
Low Set DT OFF
- GROUND DELAY -
Curve Prev OFF
Function TR&AR
Relays (00 0001
Curve DEF-1S
Time Dial 0.40
Time Adder 0.00
Min. Res Ti 0.00
Reset Meth INST
Low Set DT OFF
- SEF -
Function TRIP
Relays (00 0000
Time Delays1.00
- NEGATIVE FAST -
Curve Prev 1.00
Function TRIP
Relays (00 0000
Curve ANSI-STI
Time Dial 0.50
Time Adder 0.00
Min. Res Ti 0.00
Reset Meth INST
Low Set DT OFF
- NEGATIVE DELAY -
Curve Prev OFF
Function TRIP
Relays (00 0000
Curve ANSI-VI
Time Dial 3.00
Time Adder 0.00
Min. Res Ti 0.00
Reset Meth INST
Low Set DT OFF
<HIGH CURRENT>
- TRIP-PHASE -
Function TR&AR
Relays (00 0001
Pickup 900
Time Delay 0.10
Active Trip 1

Page 9
Primary

- TRIP-GROUND -
Function TR&AR
Relays (00 0001
Pickup 70
Time Delay 0.20
Active Trip 1
- TRIP-NEGATIVE -
Function OFF
Relays (00 0000
Pickup 4000
Time Delay 0.00
Active Trip OFF
- LOCKOUT-PHASE -
Function TR&AR
Relays (00 0001
Pickup 120
Time Delay 0.10
Active Trip OFF
- LOCKOUT-GROUND -
Function TR&AR
Relays (00 0001
Pickup 10
Time Delay 0.20
Active Trip OFF
- LOCKOUT-NEGATIVE -
Function OFF
Relays (00 0000
Pickup 8000
Time Delay 0.00
Active Trip OFF
<COLD LOAD PICKUP>
- CLPU COMMON -
Function TRIP
Relays (00 0000
Make use I NO
- CLPU-TYPE1 -
Pickup-Pha 120
Pickup-Gro 10
Pickup-SEF 20
Pickup-NEG2000
Outage Tim10.00
RMT Time ( 5.00
RMT-Phase ON
RMT-Groun ON
RMT-SEF ON
RMT-NEG ON
Reset Time 0.60
- CLPU-TYPE2 -
E-CLP Multi OFF
E-CLP Time 10
<VOLTAGE>
- UNDER VOLTAGE 1 -
Function OFF
Relays (00 0000

Page 10
Primary

Pickup 0.70
Time Delay 5.00
Min. Voltag 0.10
Pickup Type1P
- UNDER VOLTAGE 2 -
Function OFF
Relays (00 0000
Pickup 0.70
Time Delay 5.00
Min. Voltag 0.10
Pickup Type1P
- OVER VOLTAGE 1 -
Function OFF
Relays (00 0000
Pickup 1.20
Time Delay 5.00
Pickup Type1P
- OVER VOLTAGE 2 -
Function OFF
Relays (00 0000
Pickup 1.20
Time Delay 5.00
Pickup Type1P
<FREQUENCY>
- FREQUENCY -
Function OFF
Relays (00 0000
Under Picku45.00
Under Trip 2.00
Over Pickup55.00
Over Trip T 6.00
Min. Voltag 0.10
Min. Curren10
Normal Fre OFF
Normal Fre 60.0
<USER CURVE>
- USER CURVE 1 -
Factor a 59.5000
Factor b 2.0000
Factor r 1.8000
Factor rt 59.5000
- USER CURVE 2 -
Factor a 39.8500
Factor b 2.0000
Factor r 0.9500
Factor rt 39.8500
- USER CURVE 3 -
Factor a 59.1000
Factor b 2.0000
Factor r 0.3450
Factor rt 59.1000
- USER CURVE 4 -
Factor a 5.6700
Factor b 2.0000

Page 11
Primary

Factor r 0.0352
Factor rt 5.6700
<LOSS OF PHASE>
- Loss Of Phase -
Function OFF
Relay (000 0000
Pickup 0.30
Time Delay 20.00
<ALARM CURRENT>
- ALARM CURRENT -
Pickup-Pha OFF
Pickup-Gro OFF
Pickup-SEF OFF
Pickup-NEGOFF
Pickup-Tim 1.00
Dropout Ti 1.00

Page 12
Alternate

NAME1 NAME2 NAME3 NAME4 VALUE


[[RELAY SETUP]]
<PORT SETTING>
- RS232-1 -
Line Speed 19200
Parity Bit NONE
Data Bit 8
Stop Bit 1
Line Type 2
CTS functioON
DCD functi OFF
RTS functio AUTO
CTS Check-5
DCD Time-o5000
TX Post del 50
TX Pre Dela5
- RS232-2 -
Line Speed 19200
Parity Bit NONE
Data Bit 8
Stop Bit 1
Line Type 2
CTS functioON
RTS functio AUTO
DCD functi OFF
CTS Check-5
DCD Time-o5000
TX Post del 50
TX Pre Dela5
- ETHERNET -
IP Address 0
IP Address 0
IP Address 0
IP Address 0
Gateway Ad0
Gateway Ad0
Gateway Ad0
Gateway Ad0
Subnet Mas255.255.255.000
Keep-Alive DISABLE
Keep-Alive 4
Keep-Alive 2
keep-Alive 1
<COMMUNICATION>
- DNP3.0 (1) -
Function DISABLE
Use Port P2-232
Master Add60000
Slave Addr 1
D/L Confir SOME
D/L Retries 2
D/L Timeou55
A/L Retries 1
A/L Timeou 55

Page 13
Alternate

SBO Time ( 15
Multiframe 0.10
PowerUp UnENABLE
Unsol Time 5
Unsol Type NOTRIG
Class 1 DISABLE
Class 2 DISABLE
Class 3 DISABLE
Master IP O0
Master IP O0
Master IP O0
Master IP O0
TCP/UDP SeTCP
TCP Port 20000
UDP Port 20000
Keep-Alive 10
Fragment s 2048
Time Reque1440
- DNP3.0 (2) -
Function DISABLE
Use Port P3-232
Master Add60000
Slave Addr 2
D/L Confir SOME
D/L Retries 2
D/L Timeou55
A/L Retries 1
A/L Timeou 55
SBO Time ( 15
Multiframe 0.10
PowerUp UnENABLE
Unsol Time 5
Unsol Type NOTRIG
Class 1 DISABLE
Class 2 DISABLE
Class 3 DISABLE
Master IP O0
Master IP O0
Master IP O0
Master IP O0
TCP/UDP SeTCP
TCP Port 20000
UDP Port 20000
Keep-Alive 10
Fragment s 2048
Time Reque1440
- MODBUS -
Function DISABLE
Use Port P4-TCP
Slave Addr 1
Tx Delay (s 0.005
TCP/UDP SeTCP
TCP Port 502
UDP Port 502

Page 14
Alternate

- IEC60870-5-101 -
Function DISABLE
Use Port P2-232
Link Addres1
ASDU Addre1
Cyclic Peri 60
Event Perio15
Retries 0
D/L Confirm15
Max Poll Ti 60
ASDU Addre2
Link Confi ALWAYS
Link Addres1
Rx Frame S261
Rx Frame T 15
Tx Frame S 261
COT Size 1
IOA Size 2
One Char RNO
Frame Repe30
Select Time5
Use cmdAc YES
Use cseAct YES
Send Clock YES
- IEC60870-5-104 -
Function DISABLE
ASDU Addre1
Cyclic Peri 60
t0 Connecti120
t1 Ack (sec 15
t2 SFrame (10
t3 Test (sec20
Event Delay5
TCP Port 2404
Rx Frame S255
Tx Frame S 255
Select Time5
Use cmdAc YES
Use cseAct YES
Send Clock YES
- EVENT&ETC -
AI Event M OFF
SKIP at FaulYES
Fault I EvenYES
BI Event M ALL
BI Queue S 256
AI Event M ALL
AI Queue S 256
CI Event M ALL
CI Queue S 256
AI V Unit 10V
AI P Unit 10K
Daily Max I NO
Daily EnergNO

Page 15
Alternate

Event SendLOCAL
Time SynccLOCAL
<COMMON>
- GAS SENSOR -
Sensor Typ NONE
- EVENT RECORDER -
Fault Cycle ON
Length of P 4
Load ProfileON
LP Save Ti 15
- TIME SET -
Time Sync GMT
GMT Sign +
GMT Hour 0
GMT Min 0
- TIME DISPLAY -
Display TypYMD
[[MONITORING SETUP]]
<TRIP/BATTERY TEST>
- TRIP COUNTER -
Function OFF
Relays (00 0000
Counter for10000
Counter Se 77
- BATTERY TEST -
Battery Test0000
<GAS LOW>
- GAS LOW LOCK -
Function DISABLE
<FAULT LOCATOR>
- FAULT LOCATOR -
Function OFF
Length of F 50.0
Z1-Resistiv 10.0
Z1-Inductiv10.0
Z0-Resistiv 10.0
Z0-Inductiv10.0
<DEMAND>
- DEMAND -
Function OFF
Relays (00 0000
Type THM
Time Const 5
Pickup-Pha 600
Pickup-Gro 300
Pickup-NEG600
<RECLOSER WEAR>
- RECLOSER WEAR -
Function ALARM
Pickpu Wear20.0
Rated Volta27
Interrupt R 12.5
Number of 100
Wear Set-A 100.00

Page 16
Alternate

Wear Set-B 100.00


Wear Set-C 100.00
<SYNCHRO CHECK>
- SYNCHRO CHECK -
Function OFF
Relays (00 0000
Dead Line 0.50
Live Line M 0.85
Max. Volt D0.10
Max. Angle 15
Max. Freq D2.00
SynchrocheS(CB)
<EXTTRIP & LOCK>
- EXTTRIP & LOCK -
Function DISABLE
Use Input P1
Reset Meth LOCAL ONLY
<LIVE LOAD BLOCKING>
- LIVE LOAD BLOCKING -
Function OFF
Pickup 0.30
Time Delay 1.00
[[SYSTEM SETUP]]
<SYSTEM>
- CURRENT SENSING -
Phase CT Ra1000
Ground CT 1000
SEF CT Rati1000
- LINE VS SENSING -
Connect Ty CVD-W
VT 2nd (V) 84.8
VT Ratio 155.9
- LINE VL SENSING -
Connect Ty CVD-W
VT 2nd (V) 84.8
VT Ratio 155.9
Install Type 3P
- SYSTEM POWER -
Frequency 60
Phase RotatABC
Install Dire NOR
Phase Combabc
- AUTO SETTING GROUP CHANGE -
Function DISABLE
Time (sec) 30
- PANEL SLEEP TIME -
Interval (m 5
<LOOP CONTROL>
- LOOP CONTROL -
Select recl NONE
VRS at Sec VS
VRS to Tie VS
VS Wire 3PN
VL Wire 3PN(NA)

Page 17
Alternate

Auto Change OFF


Auto Change OFF
LC Action a DISABLE
LC Action a DISABLE
Open Time 10.00
Auto Restor5.00
Dead Line M50.0
Live Line M 70.0
Dead Line P50.00
LIve Line R 10.00
Dead Line R5.00
Non Reclose10.00
<OPTO INPUT SET>
- INPUT 1 -
Function NONE
Debounce T0.02
- INPUT 2 -
Function NONE
Debounce T0.02
- INPUT 3 -
Function NONE
Debounce T0.02
- INPUT 4 -
Function NONE
Debounce T0.02
- INPUT 5 -
Function NONE
Debounce T0.02
- INPUT 6 -
Function NONE
Debounce T0.02
- INPUT 7 -
Function NONE
Debounce T0.02
- INPUT 8 -
Function NONE
Debounce T0.02
<OUTPUT RELAY SET>
- OUTPUT 1 -
Function NONE
Type S/R LATCH
Pulse Time 0.05
- OUTPUT 2 -
Function NONE
Type S/R LATCH
Pulse Time 0.05
- OUTPUT 3 -
Function NONE
Type S/R LATCH
Pulse Time 0.05
- OUTPUT 4 -
Function NONE
Type S/R LATCH
Pulse Time 0.05

Page 18
Alternate

- OUTPUT 5 -
Function NONE
Type S/R LATCH
Pulse Time 0.05
- OUTPUT 6 -
Function NONE
Type S/R LATCH
Pulse Time 0.05
- OUTPUT 7 -
Function NONE
Type S/R LATCH
Pulse Time 0.05
- OUTPUT 8 -
Function NONE
Type S/R LATCH
Pulse Time 0.05
<POWER QUALITY>
- SUPPLY OUTAGE -
Function DISABLE
Duration 60
- SAG -
Function DISABLE
Pickup 0.80
Duration 5
- SWELL -
Function DISABLE
Pickup 1.20
Duration 5
- CURRENT UNBALANCE -
Function DISABLE
Pickup 30
Time Delay 4.0
UB Current 10
- VOLTAGE UNBALANCE -
Function DISABLE
Pickup 30
Time Delay 4.0
[[PROTECTION SETUP]]
<OTHER VIEW>
- OTHER ELEMENT -
Seq Coord OFF
Lockout PrioGND
F/I Reset AUTO
Manual Clos0.00
<DIRECTION ELEMENT>
- PHASE -
Direction T OFF
Max. Torque300
Min. Pol Vol0.20
Block OvercNO
- GROUND -
Direction T OFF
Max. Torque135
Min. Pol Vol0.20

Page 19
Alternate

Block OvercNO
- SEF -
Direction T OFF
Max. Torque135
Min. Pol Vol0.20
Block OvercNO
- NEGATIVE -
Direction T OFF
Max. Torque135
Min. Pol Vol0.20
Block OvercNO
<OPERATIONS>
- Lockout -
Phase 4
Ground 4
S.E.F 4
NEG 4
- Fast Curve -
Phase 2
Ground 2
NEG 2
<INTERVALS>
- INTERVAL -
Reclosing T0.60
Reclosing T2.00
Reclosing T15.00
Reclosing T15.00
Reset Timeo30.00
Reset Timeo10.00
Closing Pow60.00
<PICKUP CURRENT>
- PICKUP CURRENT -
Phase 500
Ground 250
S.E.F OFF
NEG Seq OFF
<PHASE/GND/SEF/NEGATIVE>
- PHASE FAST -
Curve Prev OFF
Function TRIP
Relays (00 0000
Curve ANSI-STI
Time Dial 0.50
Time Adder 0.00
Min. Res Ti 0.00
Reset Meth INST
Low Set DT OFF
- PHASE DELAY -
Curve Prev OFF
Function TRIP
Relays (00 0000
Curve ANSI-VI
Time Dial 3.00
Time Adder 0.00

Page 20
Alternate

Min. Res Ti 0.00


Reset Meth INST
Low Set DT OFF
- GROUND FAST -
Curve Prev OFF
Function TRIP
Relays (00 0000
Curve ANSI-STI
Time Dial 0.50
Time Adder 0.00
Min. Res Ti 0.00
Reset Meth INST
Low Set DT OFF
- GROUND DELAY -
Curve Prev OFF
Function TRIP
Relays (00 0000
Curve ANSI-VI
Time Dial 3.00
Time Adder 0.00
Min. Res Ti 0.00
Reset Meth INST
Low Set DT OFF
- SEF -
Function TRIP
Relays (00 0000
Time Delays1.00
- NEGATIVE FAST -
Curve Prev 1.00
Function TRIP
Relays (00 0000
Curve ANSI-STI
Time Dial 0.50
Time Adder 0.00
Min. Res Ti 0.00
Reset Meth INST
Low Set DT OFF
- NEGATIVE DELAY -
Curve Prev OFF
Function TRIP
Relays (00 0000
Curve ANSI-VI
Time Dial 3.00
Time Adder 0.00
Min. Res Ti 0.00
Reset Meth INST
Low Set DT OFF
<HIGH CURRENT>
- TRIP-PHASE -
Function OFF
Relays (00 0000
Pickup 4000
Time Delay 0.00
Active Trip OFF

Page 21
Alternate

- TRIP-GROUND -
Function OFF
Relays (00 0000
Pickup 4000
Time Delay 0.00
Active Trip OFF
- TRIP-NEGATIVE -
Function OFF
Relays (00 0000
Pickup 4000
Time Delay 0.00
Active Trip OFF
- LOCKOUT-PHASE -
Function OFF
Relays (00 0000
Pickup 8000
Time Delay 0.00
Active Trip OFF
- LOCKOUT-GROUND -
Function OFF
Relays (00 0000
Pickup 8000
Time Delay 0.00
Active Trip OFF
- LOCKOUT-NEGATIVE -
Function OFF
Relays (00 0000
Pickup 8000
Time Delay 0.00
Active Trip OFF
<COLD LOAD PICKUP>
- CLPU COMMON -
Function TRIP
Relays (00 0000
Make use I NO
- CLPU-TYPE1 -
Pickup-Pha 2000
Pickup-Gro 2000
Pickup-SEF 20
Pickup-NEG2000
Outage Tim10.00
RMT Time ( 5.00
RMT-Phase ON
RMT-Groun ON
RMT-SEF ON
RMT-NEG ON
Reset Time 0.60
- CLPU-TYPE2 -
E-CLP Multi OFF
E-CLP Time 10
<VOLTAGE>
- UNDER VOLTAGE 1 -
Function OFF
Relays (00 0000

Page 22
Alternate

Pickup 0.70
Time Delay 5.00
Min. Voltag 0.10
Pickup Type1P
- UNDER VOLTAGE 2 -
Function OFF
Relays (00 0000
Pickup 0.70
Time Delay 5.00
Min. Voltag 0.10
Pickup Type1P
- OVER VOLTAGE 1 -
Function OFF
Relays (00 0000
Pickup 1.20
Time Delay 5.00
Pickup Type1P
- OVER VOLTAGE 2 -
Function OFF
Relays (00 0000
Pickup 1.20
Time Delay 5.00
Pickup Type1P
<FREQUENCY>
- FREQUENCY -
Function OFF
Relays (00 0000
Under Picku45.00
Under Trip 2.00
Over Pickup55.00
Over Trip T 6.00
Min. Voltag 0.10
Min. Curren10
Normal Fre OFF
Normal Fre 60.0
<USER CURVE>
- USER CURVE 1 -
Factor a 59.5000
Factor b 2.0000
Factor r 1.8000
Factor rt 59.5000
- USER CURVE 2 -
Factor a 39.8500
Factor b 2.0000
Factor r 0.9500
Factor rt 39.8500
- USER CURVE 3 -
Factor a 59.1000
Factor b 2.0000
Factor r 0.3450
Factor rt 59.1000
- USER CURVE 4 -
Factor a 5.6700
Factor b 2.0000

Page 23
Alternate

Factor r 0.0352
Factor rt 5.6700
<LOSS OF PHASE>
- Loss Of Phase -
Function OFF
Relay (000 0000
Pickup 0.30
Time Delay 20.00
<ALARM CURRENT>
- ALARM CURRENT -
Pickup-Pha OFF
Pickup-Gro OFF
Pickup-SEF OFF
Pickup-NEGOFF
Pickup-Tim 1.00
Dropout Ti 1.00

Page 24
BANK_.3

NAME1 NAME2 NAME3 NAME4 VALUE


[[RELAY SETUP]]
<PORT SETTING>
- RS232-1 -
Line Speed 19200
Parity Bit NONE
Data Bit 8
Stop Bit 1
Line Type 2
CTS functioON
DCD functi OFF
RTS functio AUTO
CTS Check-5
DCD Time-o5000
TX Post del 50
TX Pre Dela5
- RS232-2 -
Line Speed 19200
Parity Bit NONE
Data Bit 8
Stop Bit 1
Line Type 2
CTS functioON
RTS functio AUTO
DCD functi OFF
CTS Check-5
DCD Time-o5000
TX Post del 50
TX Pre Dela5
- ETHERNET -
IP Address 0
IP Address 0
IP Address 0
IP Address 0
Gateway Ad0
Gateway Ad0
Gateway Ad0
Gateway Ad0
Subnet Mas255.255.255.000
Keep-Alive DISABLE
Keep-Alive 4
Keep-Alive 2
keep-Alive 1
<COMMUNICATION>
- DNP3.0 (1) -
Function DISABLE
Use Port P2-232
Master Add60000
Slave Addr 1
D/L Confir SOME
D/L Retries 2
D/L Timeou55
A/L Retries 1
A/L Timeou 55

Page 25
BANK_.3

SBO Time ( 15
Multiframe 0.10
PowerUp UnENABLE
Unsol Time 5
Unsol Type NOTRIG
Class 1 DISABLE
Class 2 DISABLE
Class 3 DISABLE
Master IP O0
Master IP O0
Master IP O0
Master IP O0
TCP/UDP SeTCP
TCP Port 20000
UDP Port 20000
Keep-Alive 10
Fragment s 2048
Time Reque1440
- DNP3.0 (2) -
Function DISABLE
Use Port P3-232
Master Add60000
Slave Addr 2
D/L Confir SOME
D/L Retries 2
D/L Timeou55
A/L Retries 1
A/L Timeou 55
SBO Time ( 15
Multiframe 0.10
PowerUp UnENABLE
Unsol Time 5
Unsol Type NOTRIG
Class 1 DISABLE
Class 2 DISABLE
Class 3 DISABLE
Master IP O0
Master IP O0
Master IP O0
Master IP O0
TCP/UDP SeTCP
TCP Port 20000
UDP Port 20000
Keep-Alive 10
Fragment s 2048
Time Reque1440
- MODBUS -
Function DISABLE
Use Port P4-TCP
Slave Addr 1
Tx Delay (s 0.005
TCP/UDP SeTCP
TCP Port 502
UDP Port 502

Page 26
BANK_.3

- IEC60870-5-101 -
Function DISABLE
Use Port P2-232
Link Addres1
ASDU Addre1
Cyclic Peri 60
Event Perio15
Retries 0
D/L Confirm15
Max Poll Ti 60
ASDU Addre2
Link Confi ALWAYS
Link Addres1
Rx Frame S261
Rx Frame T 15
Tx Frame S 261
COT Size 1
IOA Size 2
One Char RNO
Frame Repe30
Select Time5
Use cmdAc YES
Use cseAct YES
Send Clock YES
- IEC60870-5-104 -
Function DISABLE
ASDU Addre1
Cyclic Peri 60
t0 Connecti120
t1 Ack (sec 15
t2 SFrame (10
t3 Test (sec20
Event Delay5
TCP Port 2404
Rx Frame S255
Tx Frame S 255
Select Time5
Use cmdAc YES
Use cseAct YES
Send Clock YES
- EVENT&ETC -
AI Event M OFF
SKIP at FaulYES
Fault I EvenYES
BI Event M ALL
BI Queue S 256
AI Event M ALL
AI Queue S 256
CI Event M ALL
CI Queue S 256
AI V Unit 10V
AI P Unit 10K
Daily Max I NO
Daily EnergNO

Page 27
BANK_.3

Event SendLOCAL
Time SynccLOCAL
<COMMON>
- GAS SENSOR -
Sensor Typ NONE
- EVENT RECORDER -
Fault Cycle ON
Length of P 4
Load ProfileON
LP Save Ti 15
- TIME SET -
Time Sync GMT
GMT Sign +
GMT Hour 0
GMT Min 0
- TIME DISPLAY -
Display TypYMD
[[MONITORING SETUP]]
<TRIP/BATTERY TEST>
- TRIP COUNTER -
Function OFF
Relays (00 0000
Counter for10000
Counter Se 77
- BATTERY TEST -
Battery Test0000
<GAS LOW>
- GAS LOW LOCK -
Function DISABLE
<FAULT LOCATOR>
- FAULT LOCATOR -
Function OFF
Length of F 50.0
Z1-Resistiv 10.0
Z1-Inductiv10.0
Z0-Resistiv 10.0
Z0-Inductiv10.0
<DEMAND>
- DEMAND -
Function OFF
Relays (00 0000
Type THM
Time Const 5
Pickup-Pha 600
Pickup-Gro 300
Pickup-NEG600
<RECLOSER WEAR>
- RECLOSER WEAR -
Function ALARM
Pickpu Wear20.0
Rated Volta27
Interrupt R 12.5
Number of 100
Wear Set-A 100.00

Page 28
BANK_.3

Wear Set-B 100.00


Wear Set-C 100.00
<SYNCHRO CHECK>
- SYNCHRO CHECK -
Function OFF
Relays (00 0000
Dead Line 0.50
Live Line M 0.85
Max. Volt D0.10
Max. Angle 15
Max. Freq D2.00
SynchrocheS(CB)
<EXTTRIP & LOCK>
- EXTTRIP & LOCK -
Function DISABLE
Use Input P1
Reset Meth LOCAL ONLY
<LIVE LOAD BLOCKING>
- LIVE LOAD BLOCKING -
Function OFF
Pickup 0.30
Time Delay 1.00
[[SYSTEM SETUP]]
<SYSTEM>
- CURRENT SENSING -
Phase CT Ra1000
Ground CT 1000
SEF CT Rati1000
- LINE VS SENSING -
Connect Ty CVD-W
VT 2nd (V) 84.8
VT Ratio 155.9
- LINE VL SENSING -
Connect Ty CVD-W
VT 2nd (V) 84.8
VT Ratio 155.9
Install Type 3P
- SYSTEM POWER -
Frequency 60
Phase RotatABC
Install Dire NOR
Phase Combabc
- AUTO SETTING GROUP CHANGE -
Function DISABLE
Time (sec) 30
- PANEL SLEEP TIME -
Interval (m 5
<LOOP CONTROL>
- LOOP CONTROL -
Select recl NONE
VRS at Sec VS
VRS to Tie VS
VS Wire 3PN
VL Wire 3PN(NA)

Page 29
BANK_.3

Auto Change OFF


Auto Change OFF
LC Action a DISABLE
LC Action a DISABLE
Open Time 10.00
Auto Restor5.00
Dead Line M50.0
Live Line M 70.0
Dead Line P50.00
LIve Line R 10.00
Dead Line R5.00
Non Reclose10.00
<OPTO INPUT SET>
- INPUT 1 -
Function NONE
Debounce T0.02
- INPUT 2 -
Function NONE
Debounce T0.02
- INPUT 3 -
Function NONE
Debounce T0.02
- INPUT 4 -
Function NONE
Debounce T0.02
- INPUT 5 -
Function NONE
Debounce T0.02
- INPUT 6 -
Function NONE
Debounce T0.02
- INPUT 7 -
Function NONE
Debounce T0.02
- INPUT 8 -
Function NONE
Debounce T0.02
<OUTPUT RELAY SET>
- OUTPUT 1 -
Function NONE
Type S/R LATCH
Pulse Time 0.05
- OUTPUT 2 -
Function NONE
Type S/R LATCH
Pulse Time 0.05
- OUTPUT 3 -
Function NONE
Type S/R LATCH
Pulse Time 0.05
- OUTPUT 4 -
Function NONE
Type S/R LATCH
Pulse Time 0.05

Page 30
BANK_.3

- OUTPUT 5 -
Function NONE
Type S/R LATCH
Pulse Time 0.05
- OUTPUT 6 -
Function NONE
Type S/R LATCH
Pulse Time 0.05
- OUTPUT 7 -
Function NONE
Type S/R LATCH
Pulse Time 0.05
- OUTPUT 8 -
Function NONE
Type S/R LATCH
Pulse Time 0.05
<POWER QUALITY>
- SUPPLY OUTAGE -
Function DISABLE
Duration 60
- SAG -
Function DISABLE
Pickup 0.80
Duration 5
- SWELL -
Function DISABLE
Pickup 1.20
Duration 5
- CURRENT UNBALANCE -
Function DISABLE
Pickup 30
Time Delay 4.0
UB Current 10
- VOLTAGE UNBALANCE -
Function DISABLE
Pickup 30
Time Delay 4.0
[[PROTECTION SETUP]]
<OTHER VIEW>
- OTHER ELEMENT -
Seq Coord OFF
Lockout PrioGND
F/I Reset AUTO
Manual Clos0.00
<DIRECTION ELEMENT>
- PHASE -
Direction T OFF
Max. Torque300
Min. Pol Vol0.20
Block OvercNO
- GROUND -
Direction T OFF
Max. Torque135
Min. Pol Vol0.20

Page 31
BANK_.3

Block OvercNO
- SEF -
Direction T OFF
Max. Torque135
Min. Pol Vol0.20
Block OvercNO
- NEGATIVE -
Direction T OFF
Max. Torque135
Min. Pol Vol0.20
Block OvercNO
<OPERATIONS>
- Lockout -
Phase 4
Ground 4
S.E.F 4
NEG 4
- Fast Curve -
Phase 2
Ground 2
NEG 2
<INTERVALS>
- INTERVAL -
Reclosing T0.60
Reclosing T2.00
Reclosing T15.00
Reclosing T15.00
Reset Timeo30.00
Reset Timeo10.00
Closing Pow60.00
<PICKUP CURRENT>
- PICKUP CURRENT -
Phase 500
Ground 250
S.E.F OFF
NEG Seq OFF
<PHASE/GND/SEF/NEGATIVE>
- PHASE FAST -
Curve Prev OFF
Function TRIP
Relays (00 0000
Curve ANSI-STI
Time Dial 0.50
Time Adder 0.00
Min. Res Ti 0.00
Reset Meth INST
Low Set DT OFF
- PHASE DELAY -
Curve Prev OFF
Function TRIP
Relays (00 0000
Curve ANSI-VI
Time Dial 3.00
Time Adder 0.00

Page 32
BANK_.3

Min. Res Ti 0.00


Reset Meth INST
Low Set DT OFF
- GROUND FAST -
Curve Prev OFF
Function TRIP
Relays (00 0000
Curve ANSI-STI
Time Dial 0.50
Time Adder 0.00
Min. Res Ti 0.00
Reset Meth INST
Low Set DT OFF
- GROUND DELAY -
Curve Prev OFF
Function TRIP
Relays (00 0000
Curve ANSI-VI
Time Dial 3.00
Time Adder 0.00
Min. Res Ti 0.00
Reset Meth INST
Low Set DT OFF
- SEF -
Function TRIP
Relays (00 0000
Time Delays1.00
- NEGATIVE FAST -
Curve Prev 1.00
Function TRIP
Relays (00 0000
Curve ANSI-STI
Time Dial 0.50
Time Adder 0.00
Min. Res Ti 0.00
Reset Meth INST
Low Set DT OFF
- NEGATIVE DELAY -
Curve Prev OFF
Function TRIP
Relays (00 0000
Curve ANSI-VI
Time Dial 3.00
Time Adder 0.00
Min. Res Ti 0.00
Reset Meth INST
Low Set DT OFF
<HIGH CURRENT>
- TRIP-PHASE -
Function OFF
Relays (00 0000
Pickup 4000
Time Delay 0.00
Active Trip OFF

Page 33
BANK_.3

- TRIP-GROUND -
Function OFF
Relays (00 0000
Pickup 4000
Time Delay 0.00
Active Trip OFF
- TRIP-NEGATIVE -
Function OFF
Relays (00 0000
Pickup 4000
Time Delay 0.00
Active Trip OFF
- LOCKOUT-PHASE -
Function OFF
Relays (00 0000
Pickup 8000
Time Delay 0.00
Active Trip OFF
- LOCKOUT-GROUND -
Function OFF
Relays (00 0000
Pickup 8000
Time Delay 0.00
Active Trip OFF
- LOCKOUT-NEGATIVE -
Function OFF
Relays (00 0000
Pickup 8000
Time Delay 0.00
Active Trip OFF
<COLD LOAD PICKUP>
- CLPU COMMON -
Function TRIP
Relays (00 0000
Make use I NO
- CLPU-TYPE1 -
Pickup-Pha 2000
Pickup-Gro 2000
Pickup-SEF 20
Pickup-NEG2000
Outage Tim10.00
RMT Time ( 5.00
RMT-Phase ON
RMT-Groun ON
RMT-SEF ON
RMT-NEG ON
Reset Time 0.60
- CLPU-TYPE2 -
E-CLP Multi OFF
E-CLP Time 10
<VOLTAGE>
- UNDER VOLTAGE 1 -
Function OFF
Relays (00 0000

Page 34
BANK_.3

Pickup 0.70
Time Delay 5.00
Min. Voltag 0.10
Pickup Type1P
- UNDER VOLTAGE 2 -
Function OFF
Relays (00 0000
Pickup 0.70
Time Delay 5.00
Min. Voltag 0.10
Pickup Type1P
- OVER VOLTAGE 1 -
Function OFF
Relays (00 0000
Pickup 1.20
Time Delay 5.00
Pickup Type1P
- OVER VOLTAGE 2 -
Function OFF
Relays (00 0000
Pickup 1.20
Time Delay 5.00
Pickup Type1P
<FREQUENCY>
- FREQUENCY -
Function OFF
Relays (00 0000
Under Picku45.00
Under Trip 2.00
Over Pickup55.00
Over Trip T 6.00
Min. Voltag 0.10
Min. Curren10
Normal Fre OFF
Normal Fre 60.0
<USER CURVE>
- USER CURVE 1 -
Factor a 59.5000
Factor b 2.0000
Factor r 1.8000
Factor rt 59.5000
- USER CURVE 2 -
Factor a 39.8500
Factor b 2.0000
Factor r 0.9500
Factor rt 39.8500
- USER CURVE 3 -
Factor a 59.1000
Factor b 2.0000
Factor r 0.3450
Factor rt 59.1000
- USER CURVE 4 -
Factor a 5.6700
Factor b 2.0000

Page 35
BANK_.3

Factor r 0.0352
Factor rt 5.6700
<LOSS OF PHASE>
- Loss Of Phase -
Function OFF
Relay (000 0000
Pickup 0.30
Time Delay 20.00
<ALARM CURRENT>
- ALARM CURRENT -
Pickup-Pha OFF
Pickup-Gro OFF
Pickup-SEF OFF
Pickup-NEGOFF
Pickup-Tim 1.00
Dropout Ti 1.00

Page 36
BANK_.4

NAME1 NAME2 NAME3 NAME4 VALUE


[[RELAY SETUP]]
<PORT SETTING>
- RS232-1 -
Line Speed 19200
Parity Bit NONE
Data Bit 8
Stop Bit 1
Line Type 2
CTS functioON
DCD functi OFF
RTS functio AUTO
CTS Check-5
DCD Time-o5000
TX Post del 50
TX Pre Dela5
- RS232-2 -
Line Speed 19200
Parity Bit NONE
Data Bit 8
Stop Bit 1
Line Type 2
CTS functioON
RTS functio AUTO
DCD functi OFF
CTS Check-5
DCD Time-o5000
TX Post del 50
TX Pre Dela5
- ETHERNET -
IP Address 0
IP Address 0
IP Address 0
IP Address 0
Gateway Ad0
Gateway Ad0
Gateway Ad0
Gateway Ad0
Subnet Mas255.255.255.000
Keep-Alive DISABLE
Keep-Alive 4
Keep-Alive 2
keep-Alive 1
<COMMUNICATION>
- DNP3.0 (1) -
Function DISABLE
Use Port P2-232
Master Add60000
Slave Addr 1
D/L Confir SOME
D/L Retries 2
D/L Timeou55
A/L Retries 1
A/L Timeou 55

Page 37
BANK_.4

SBO Time ( 15
Multiframe 0.10
PowerUp UnENABLE
Unsol Time 5
Unsol Type NOTRIG
Class 1 DISABLE
Class 2 DISABLE
Class 3 DISABLE
Master IP O0
Master IP O0
Master IP O0
Master IP O0
TCP/UDP SeTCP
TCP Port 20000
UDP Port 20000
Keep-Alive 10
Fragment s 2048
Time Reque1440
- DNP3.0 (2) -
Function DISABLE
Use Port P3-232
Master Add60000
Slave Addr 2
D/L Confir SOME
D/L Retries 2
D/L Timeou55
A/L Retries 1
A/L Timeou 55
SBO Time ( 15
Multiframe 0.10
PowerUp UnENABLE
Unsol Time 5
Unsol Type NOTRIG
Class 1 DISABLE
Class 2 DISABLE
Class 3 DISABLE
Master IP O0
Master IP O0
Master IP O0
Master IP O0
TCP/UDP SeTCP
TCP Port 20000
UDP Port 20000
Keep-Alive 10
Fragment s 2048
Time Reque1440
- MODBUS -
Function DISABLE
Use Port P4-TCP
Slave Addr 1
Tx Delay (s 0.005
TCP/UDP SeTCP
TCP Port 502
UDP Port 502

Page 38
BANK_.4

- IEC60870-5-101 -
Function DISABLE
Use Port P2-232
Link Addres1
ASDU Addre1
Cyclic Peri 60
Event Perio15
Retries 0
D/L Confirm15
Max Poll Ti 60
ASDU Addre2
Link Confi ALWAYS
Link Addres1
Rx Frame S261
Rx Frame T 15
Tx Frame S 261
COT Size 1
IOA Size 2
One Char RNO
Frame Repe30
Select Time5
Use cmdAc YES
Use cseAct YES
Send Clock YES
- IEC60870-5-104 -
Function DISABLE
ASDU Addre1
Cyclic Peri 60
t0 Connecti120
t1 Ack (sec 15
t2 SFrame (10
t3 Test (sec20
Event Delay5
TCP Port 2404
Rx Frame S255
Tx Frame S 255
Select Time5
Use cmdAc YES
Use cseAct YES
Send Clock YES
- EVENT&ETC -
AI Event M OFF
SKIP at FaulYES
Fault I EvenYES
BI Event M ALL
BI Queue S 256
AI Event M ALL
AI Queue S 256
CI Event M ALL
CI Queue S 256
AI V Unit 10V
AI P Unit 10K
Daily Max I NO
Daily EnergNO

Page 39
BANK_.4

Event SendLOCAL
Time SynccLOCAL
<COMMON>
- GAS SENSOR -
Sensor Typ NONE
- EVENT RECORDER -
Fault Cycle ON
Length of P 4
Load ProfileON
LP Save Ti 15
- TIME SET -
Time Sync GMT
GMT Sign +
GMT Hour 0
GMT Min 0
- TIME DISPLAY -
Display TypYMD
[[MONITORING SETUP]]
<TRIP/BATTERY TEST>
- TRIP COUNTER -
Function OFF
Relays (00 0000
Counter for10000
Counter Se 77
- BATTERY TEST -
Battery Test0000
<GAS LOW>
- GAS LOW LOCK -
Function DISABLE
<FAULT LOCATOR>
- FAULT LOCATOR -
Function OFF
Length of F 50.0
Z1-Resistiv 10.0
Z1-Inductiv10.0
Z0-Resistiv 10.0
Z0-Inductiv10.0
<DEMAND>
- DEMAND -
Function OFF
Relays (00 0000
Type THM
Time Const 5
Pickup-Pha 600
Pickup-Gro 300
Pickup-NEG600
<RECLOSER WEAR>
- RECLOSER WEAR -
Function ALARM
Pickpu Wear20.0
Rated Volta27
Interrupt R 12.5
Number of 100
Wear Set-A 100.00

Page 40
BANK_.4

Wear Set-B 100.00


Wear Set-C 100.00
<SYNCHRO CHECK>
- SYNCHRO CHECK -
Function OFF
Relays (00 0000
Dead Line 0.50
Live Line M 0.85
Max. Volt D0.10
Max. Angle 15
Max. Freq D2.00
SynchrocheS(CB)
<EXTTRIP & LOCK>
- EXTTRIP & LOCK -
Function DISABLE
Use Input P1
Reset Meth LOCAL ONLY
<LIVE LOAD BLOCKING>
- LIVE LOAD BLOCKING -
Function OFF
Pickup 0.30
Time Delay 1.00
[[SYSTEM SETUP]]
<SYSTEM>
- CURRENT SENSING -
Phase CT Ra1000
Ground CT 1000
SEF CT Rati1000
- LINE VS SENSING -
Connect Ty CVD-W
VT 2nd (V) 84.8
VT Ratio 155.9
- LINE VL SENSING -
Connect Ty CVD-W
VT 2nd (V) 84.8
VT Ratio 155.9
Install Type 3P
- SYSTEM POWER -
Frequency 60
Phase RotatABC
Install Dire NOR
Phase Combabc
- AUTO SETTING GROUP CHANGE -
Function DISABLE
Time (sec) 30
- PANEL SLEEP TIME -
Interval (m 5
<LOOP CONTROL>
- LOOP CONTROL -
Select recl NONE
VRS at Sec VS
VRS to Tie VS
VS Wire 3PN
VL Wire 3PN(NA)

Page 41
BANK_.4

Auto Change OFF


Auto Change OFF
LC Action a DISABLE
LC Action a DISABLE
Open Time 10.00
Auto Restor5.00
Dead Line M50.0
Live Line M 70.0
Dead Line P50.00
LIve Line R 10.00
Dead Line R5.00
Non Reclose10.00
<OPTO INPUT SET>
- INPUT 1 -
Function NONE
Debounce T0.02
- INPUT 2 -
Function NONE
Debounce T0.02
- INPUT 3 -
Function NONE
Debounce T0.02
- INPUT 4 -
Function NONE
Debounce T0.02
- INPUT 5 -
Function NONE
Debounce T0.02
- INPUT 6 -
Function NONE
Debounce T0.02
- INPUT 7 -
Function NONE
Debounce T0.02
- INPUT 8 -
Function NONE
Debounce T0.02
<OUTPUT RELAY SET>
- OUTPUT 1 -
Function NONE
Type S/R LATCH
Pulse Time 0.05
- OUTPUT 2 -
Function NONE
Type S/R LATCH
Pulse Time 0.05
- OUTPUT 3 -
Function NONE
Type S/R LATCH
Pulse Time 0.05
- OUTPUT 4 -
Function NONE
Type S/R LATCH
Pulse Time 0.05

Page 42
BANK_.4

- OUTPUT 5 -
Function NONE
Type S/R LATCH
Pulse Time 0.05
- OUTPUT 6 -
Function NONE
Type S/R LATCH
Pulse Time 0.05
- OUTPUT 7 -
Function NONE
Type S/R LATCH
Pulse Time 0.05
- OUTPUT 8 -
Function NONE
Type S/R LATCH
Pulse Time 0.05
<POWER QUALITY>
- SUPPLY OUTAGE -
Function DISABLE
Duration 60
- SAG -
Function DISABLE
Pickup 0.80
Duration 5
- SWELL -
Function DISABLE
Pickup 1.20
Duration 5
- CURRENT UNBALANCE -
Function DISABLE
Pickup 30
Time Delay 4.0
UB Current 10
- VOLTAGE UNBALANCE -
Function DISABLE
Pickup 30
Time Delay 4.0
[[PROTECTION SETUP]]
<OTHER VIEW>
- OTHER ELEMENT -
Seq Coord OFF
Lockout PrioGND
F/I Reset AUTO
Manual Clos0.00
<DIRECTION ELEMENT>
- PHASE -
Direction T OFF
Max. Torque300
Min. Pol Vol0.20
Block OvercNO
- GROUND -
Direction T OFF
Max. Torque135
Min. Pol Vol0.20

Page 43
BANK_.4

Block OvercNO
- SEF -
Direction T OFF
Max. Torque135
Min. Pol Vol0.20
Block OvercNO
- NEGATIVE -
Direction T OFF
Max. Torque135
Min. Pol Vol0.20
Block OvercNO
<OPERATIONS>
- Lockout -
Phase 4
Ground 4
S.E.F 4
NEG 4
- Fast Curve -
Phase 2
Ground 2
NEG 2
<INTERVALS>
- INTERVAL -
Reclosing T0.60
Reclosing T2.00
Reclosing T15.00
Reclosing T15.00
Reset Timeo30.00
Reset Timeo10.00
Closing Pow60.00
<PICKUP CURRENT>
- PICKUP CURRENT -
Phase 500
Ground 250
S.E.F OFF
NEG Seq OFF
<PHASE/GND/SEF/NEGATIVE>
- PHASE FAST -
Curve Prev OFF
Function TRIP
Relays (00 0000
Curve ANSI-STI
Time Dial 0.50
Time Adder 0.00
Min. Res Ti 0.00
Reset Meth INST
Low Set DT OFF
- PHASE DELAY -
Curve Prev OFF
Function TRIP
Relays (00 0000
Curve ANSI-VI
Time Dial 3.00
Time Adder 0.00

Page 44
BANK_.4

Min. Res Ti 0.00


Reset Meth INST
Low Set DT OFF
- GROUND FAST -
Curve Prev OFF
Function TRIP
Relays (00 0000
Curve ANSI-STI
Time Dial 0.50
Time Adder 0.00
Min. Res Ti 0.00
Reset Meth INST
Low Set DT OFF
- GROUND DELAY -
Curve Prev OFF
Function TRIP
Relays (00 0000
Curve ANSI-VI
Time Dial 3.00
Time Adder 0.00
Min. Res Ti 0.00
Reset Meth INST
Low Set DT OFF
- SEF -
Function TRIP
Relays (00 0000
Time Delays1.00
- NEGATIVE FAST -
Curve Prev 1.00
Function TRIP
Relays (00 0000
Curve ANSI-STI
Time Dial 0.50
Time Adder 0.00
Min. Res Ti 0.00
Reset Meth INST
Low Set DT OFF
- NEGATIVE DELAY -
Curve Prev OFF
Function TRIP
Relays (00 0000
Curve ANSI-VI
Time Dial 3.00
Time Adder 0.00
Min. Res Ti 0.00
Reset Meth INST
Low Set DT OFF
<HIGH CURRENT>
- TRIP-PHASE -
Function OFF
Relays (00 0000
Pickup 4000
Time Delay 0.00
Active Trip OFF

Page 45
BANK_.4

- TRIP-GROUND -
Function OFF
Relays (00 0000
Pickup 4000
Time Delay 0.00
Active Trip OFF
- TRIP-NEGATIVE -
Function OFF
Relays (00 0000
Pickup 4000
Time Delay 0.00
Active Trip OFF
- LOCKOUT-PHASE -
Function OFF
Relays (00 0000
Pickup 8000
Time Delay 0.00
Active Trip OFF
- LOCKOUT-GROUND -
Function OFF
Relays (00 0000
Pickup 8000
Time Delay 0.00
Active Trip OFF
- LOCKOUT-NEGATIVE -
Function OFF
Relays (00 0000
Pickup 8000
Time Delay 0.00
Active Trip OFF
<COLD LOAD PICKUP>
- CLPU COMMON -
Function TRIP
Relays (00 0000
Make use I NO
- CLPU-TYPE1 -
Pickup-Pha 2000
Pickup-Gro 2000
Pickup-SEF 20
Pickup-NEG2000
Outage Tim10.00
RMT Time ( 5.00
RMT-Phase ON
RMT-Groun ON
RMT-SEF ON
RMT-NEG ON
Reset Time 0.60
- CLPU-TYPE2 -
E-CLP Multi OFF
E-CLP Time 10
<VOLTAGE>
- UNDER VOLTAGE 1 -
Function OFF
Relays (00 0000

Page 46
BANK_.4

Pickup 0.70
Time Delay 5.00
Min. Voltag 0.10
Pickup Type1P
- UNDER VOLTAGE 2 -
Function OFF
Relays (00 0000
Pickup 0.70
Time Delay 5.00
Min. Voltag 0.10
Pickup Type1P
- OVER VOLTAGE 1 -
Function OFF
Relays (00 0000
Pickup 1.20
Time Delay 5.00
Pickup Type1P
- OVER VOLTAGE 2 -
Function OFF
Relays (00 0000
Pickup 1.20
Time Delay 5.00
Pickup Type1P
<FREQUENCY>
- FREQUENCY -
Function OFF
Relays (00 0000
Under Picku45.00
Under Trip 2.00
Over Pickup55.00
Over Trip T 6.00
Min. Voltag 0.10
Min. Curren10
Normal Fre OFF
Normal Fre 60.0
<USER CURVE>
- USER CURVE 1 -
Factor a 59.5000
Factor b 2.0000
Factor r 1.8000
Factor rt 59.5000
- USER CURVE 2 -
Factor a 39.8500
Factor b 2.0000
Factor r 0.9500
Factor rt 39.8500
- USER CURVE 3 -
Factor a 59.1000
Factor b 2.0000
Factor r 0.3450
Factor rt 59.1000
- USER CURVE 4 -
Factor a 5.6700
Factor b 2.0000

Page 47
BANK_.4

Factor r 0.0352
Factor rt 5.6700
<LOSS OF PHASE>
- Loss Of Phase -
Function OFF
Relay (000 0000
Pickup 0.30
Time Delay 20.00
<ALARM CURRENT>
- ALARM CURRENT -
Pickup-Pha OFF
Pickup-Gro OFF
Pickup-SEF OFF
Pickup-NEGOFF
Pickup-Tim 1.00
Dropout Ti 1.00

Page 48
BANK_.5

NAME1 NAME2 NAME3 NAME4 VALUE


[[RELAY SETUP]]
<PORT SETTING>
- RS232-1 -
Line Speed 19200
Parity Bit NONE
Data Bit 8
Stop Bit 1
Line Type 2
CTS functioON
DCD functi OFF
RTS functio AUTO
CTS Check-5
DCD Time-o5000
TX Post del 50
TX Pre Dela5
- RS232-2 -
Line Speed 19200
Parity Bit NONE
Data Bit 8
Stop Bit 1
Line Type 2
CTS functioON
RTS functio AUTO
DCD functi OFF
CTS Check-5
DCD Time-o5000
TX Post del 50
TX Pre Dela5
- ETHERNET -
IP Address 0
IP Address 0
IP Address 0
IP Address 0
Gateway Ad0
Gateway Ad0
Gateway Ad0
Gateway Ad0
Subnet Mas255.255.255.000
Keep-Alive DISABLE
Keep-Alive 4
Keep-Alive 2
keep-Alive 1
<COMMUNICATION>
- DNP3.0 (1) -
Function DISABLE
Use Port P2-232
Master Add60000
Slave Addr 1
D/L Confir SOME
D/L Retries 2
D/L Timeou55
A/L Retries 1
A/L Timeou 55

Page 49
BANK_.5

SBO Time ( 15
Multiframe 0.10
PowerUp UnENABLE
Unsol Time 5
Unsol Type NOTRIG
Class 1 DISABLE
Class 2 DISABLE
Class 3 DISABLE
Master IP O0
Master IP O0
Master IP O0
Master IP O0
TCP/UDP SeTCP
TCP Port 20000
UDP Port 20000
Keep-Alive 10
Fragment s 2048
Time Reque1440
- DNP3.0 (2) -
Function DISABLE
Use Port P3-232
Master Add60000
Slave Addr 2
D/L Confir SOME
D/L Retries 2
D/L Timeou55
A/L Retries 1
A/L Timeou 55
SBO Time ( 15
Multiframe 0.10
PowerUp UnENABLE
Unsol Time 5
Unsol Type NOTRIG
Class 1 DISABLE
Class 2 DISABLE
Class 3 DISABLE
Master IP O0
Master IP O0
Master IP O0
Master IP O0
TCP/UDP SeTCP
TCP Port 20000
UDP Port 20000
Keep-Alive 10
Fragment s 2048
Time Reque1440
- MODBUS -
Function DISABLE
Use Port P4-TCP
Slave Addr 1
Tx Delay (s 0.005
TCP/UDP SeTCP
TCP Port 502
UDP Port 502

Page 50
BANK_.5

- IEC60870-5-101 -
Function DISABLE
Use Port P2-232
Link Addres1
ASDU Addre1
Cyclic Peri 60
Event Perio15
Retries 0
D/L Confirm15
Max Poll Ti 60
ASDU Addre2
Link Confi ALWAYS
Link Addres1
Rx Frame S261
Rx Frame T 15
Tx Frame S 261
COT Size 1
IOA Size 2
One Char RNO
Frame Repe30
Select Time5
Use cmdAc YES
Use cseAct YES
Send Clock YES
- IEC60870-5-104 -
Function DISABLE
ASDU Addre1
Cyclic Peri 60
t0 Connecti120
t1 Ack (sec 15
t2 SFrame (10
t3 Test (sec20
Event Delay5
TCP Port 2404
Rx Frame S255
Tx Frame S 255
Select Time5
Use cmdAc YES
Use cseAct YES
Send Clock YES
- EVENT&ETC -
AI Event M OFF
SKIP at FaulYES
Fault I EvenYES
BI Event M ALL
BI Queue S 256
AI Event M ALL
AI Queue S 256
CI Event M ALL
CI Queue S 256
AI V Unit 10V
AI P Unit 10K
Daily Max I NO
Daily EnergNO

Page 51
BANK_.5

Event SendLOCAL
Time SynccLOCAL
<COMMON>
- GAS SENSOR -
Sensor Typ NONE
- EVENT RECORDER -
Fault Cycle ON
Length of P 4
Load ProfileON
LP Save Ti 15
- TIME SET -
Time Sync GMT
GMT Sign +
GMT Hour 0
GMT Min 0
- TIME DISPLAY -
Display TypYMD
[[MONITORING SETUP]]
<TRIP/BATTERY TEST>
- TRIP COUNTER -
Function OFF
Relays (00 0000
Counter for10000
Counter Se 77
- BATTERY TEST -
Battery Test0000
<GAS LOW>
- GAS LOW LOCK -
Function DISABLE
<FAULT LOCATOR>
- FAULT LOCATOR -
Function OFF
Length of F 50.0
Z1-Resistiv 10.0
Z1-Inductiv10.0
Z0-Resistiv 10.0
Z0-Inductiv10.0
<DEMAND>
- DEMAND -
Function OFF
Relays (00 0000
Type THM
Time Const 5
Pickup-Pha 600
Pickup-Gro 300
Pickup-NEG600
<RECLOSER WEAR>
- RECLOSER WEAR -
Function ALARM
Pickpu Wear20.0
Rated Volta27
Interrupt R 12.5
Number of 100
Wear Set-A 100.00

Page 52
BANK_.5

Wear Set-B 100.00


Wear Set-C 100.00
<SYNCHRO CHECK>
- SYNCHRO CHECK -
Function OFF
Relays (00 0000
Dead Line 0.50
Live Line M 0.85
Max. Volt D0.10
Max. Angle 15
Max. Freq D2.00
SynchrocheS(CB)
<EXTTRIP & LOCK>
- EXTTRIP & LOCK -
Function DISABLE
Use Input P1
Reset Meth LOCAL ONLY
<LIVE LOAD BLOCKING>
- LIVE LOAD BLOCKING -
Function OFF
Pickup 0.30
Time Delay 1.00
[[SYSTEM SETUP]]
<SYSTEM>
- CURRENT SENSING -
Phase CT Ra1000
Ground CT 1000
SEF CT Rati1000
- LINE VS SENSING -
Connect Ty CVD-W
VT 2nd (V) 84.8
VT Ratio 155.9
- LINE VL SENSING -
Connect Ty CVD-W
VT 2nd (V) 84.8
VT Ratio 155.9
Install Type 3P
- SYSTEM POWER -
Frequency 60
Phase RotatABC
Install Dire NOR
Phase Combabc
- AUTO SETTING GROUP CHANGE -
Function DISABLE
Time (sec) 30
- PANEL SLEEP TIME -
Interval (m 5
<LOOP CONTROL>
- LOOP CONTROL -
Select recl NONE
VRS at Sec VS
VRS to Tie VS
VS Wire 3PN
VL Wire 3PN(NA)

Page 53
BANK_.5

Auto Change OFF


Auto Change OFF
LC Action a DISABLE
LC Action a DISABLE
Open Time 10.00
Auto Restor5.00
Dead Line M50.0
Live Line M 70.0
Dead Line P50.00
LIve Line R 10.00
Dead Line R5.00
Non Reclose10.00
<OPTO INPUT SET>
- INPUT 1 -
Function NONE
Debounce T0.02
- INPUT 2 -
Function NONE
Debounce T0.02
- INPUT 3 -
Function NONE
Debounce T0.02
- INPUT 4 -
Function NONE
Debounce T0.02
- INPUT 5 -
Function NONE
Debounce T0.02
- INPUT 6 -
Function NONE
Debounce T0.02
- INPUT 7 -
Function NONE
Debounce T0.02
- INPUT 8 -
Function NONE
Debounce T0.02
<OUTPUT RELAY SET>
- OUTPUT 1 -
Function NONE
Type S/R LATCH
Pulse Time 0.05
- OUTPUT 2 -
Function NONE
Type S/R LATCH
Pulse Time 0.05
- OUTPUT 3 -
Function NONE
Type S/R LATCH
Pulse Time 0.05
- OUTPUT 4 -
Function NONE
Type S/R LATCH
Pulse Time 0.05

Page 54
BANK_.5

- OUTPUT 5 -
Function NONE
Type S/R LATCH
Pulse Time 0.05
- OUTPUT 6 -
Function NONE
Type S/R LATCH
Pulse Time 0.05
- OUTPUT 7 -
Function NONE
Type S/R LATCH
Pulse Time 0.05
- OUTPUT 8 -
Function NONE
Type S/R LATCH
Pulse Time 0.05
<POWER QUALITY>
- SUPPLY OUTAGE -
Function DISABLE
Duration 60
- SAG -
Function DISABLE
Pickup 0.80
Duration 5
- SWELL -
Function DISABLE
Pickup 1.20
Duration 5
- CURRENT UNBALANCE -
Function DISABLE
Pickup 30
Time Delay 4.0
UB Current 10
- VOLTAGE UNBALANCE -
Function DISABLE
Pickup 30
Time Delay 4.0
[[PROTECTION SETUP]]
<OTHER VIEW>
- OTHER ELEMENT -
Seq Coord OFF
Lockout PrioGND
F/I Reset AUTO
Manual Clos0.00
<DIRECTION ELEMENT>
- PHASE -
Direction T OFF
Max. Torque300
Min. Pol Vol0.20
Block OvercNO
- GROUND -
Direction T OFF
Max. Torque135
Min. Pol Vol0.20

Page 55
BANK_.5

Block OvercNO
- SEF -
Direction T OFF
Max. Torque135
Min. Pol Vol0.20
Block OvercNO
- NEGATIVE -
Direction T OFF
Max. Torque135
Min. Pol Vol0.20
Block OvercNO
<OPERATIONS>
- Lockout -
Phase 4
Ground 4
S.E.F 4
NEG 4
- Fast Curve -
Phase 2
Ground 2
NEG 2
<INTERVALS>
- INTERVAL -
Reclosing T0.60
Reclosing T2.00
Reclosing T15.00
Reclosing T15.00
Reset Timeo30.00
Reset Timeo10.00
Closing Pow60.00
<PICKUP CURRENT>
- PICKUP CURRENT -
Phase 500
Ground 250
S.E.F OFF
NEG Seq OFF
<PHASE/GND/SEF/NEGATIVE>
- PHASE FAST -
Curve Prev OFF
Function TRIP
Relays (00 0000
Curve ANSI-STI
Time Dial 0.50
Time Adder 0.00
Min. Res Ti 0.00
Reset Meth INST
Low Set DT OFF
- PHASE DELAY -
Curve Prev OFF
Function TRIP
Relays (00 0000
Curve ANSI-VI
Time Dial 3.00
Time Adder 0.00

Page 56
BANK_.5

Min. Res Ti 0.00


Reset Meth INST
Low Set DT OFF
- GROUND FAST -
Curve Prev OFF
Function TRIP
Relays (00 0000
Curve ANSI-STI
Time Dial 0.50
Time Adder 0.00
Min. Res Ti 0.00
Reset Meth INST
Low Set DT OFF
- GROUND DELAY -
Curve Prev OFF
Function TRIP
Relays (00 0000
Curve ANSI-VI
Time Dial 3.00
Time Adder 0.00
Min. Res Ti 0.00
Reset Meth INST
Low Set DT OFF
- SEF -
Function TRIP
Relays (00 0000
Time Delays1.00
- NEGATIVE FAST -
Curve Prev 1.00
Function TRIP
Relays (00 0000
Curve ANSI-STI
Time Dial 0.50
Time Adder 0.00
Min. Res Ti 0.00
Reset Meth INST
Low Set DT OFF
- NEGATIVE DELAY -
Curve Prev OFF
Function TRIP
Relays (00 0000
Curve ANSI-VI
Time Dial 3.00
Time Adder 0.00
Min. Res Ti 0.00
Reset Meth INST
Low Set DT OFF
<HIGH CURRENT>
- TRIP-PHASE -
Function OFF
Relays (00 0000
Pickup 4000
Time Delay 0.00
Active Trip OFF

Page 57
BANK_.5

- TRIP-GROUND -
Function OFF
Relays (00 0000
Pickup 4000
Time Delay 0.00
Active Trip OFF
- TRIP-NEGATIVE -
Function OFF
Relays (00 0000
Pickup 4000
Time Delay 0.00
Active Trip OFF
- LOCKOUT-PHASE -
Function OFF
Relays (00 0000
Pickup 8000
Time Delay 0.00
Active Trip OFF
- LOCKOUT-GROUND -
Function OFF
Relays (00 0000
Pickup 8000
Time Delay 0.00
Active Trip OFF
- LOCKOUT-NEGATIVE -
Function OFF
Relays (00 0000
Pickup 8000
Time Delay 0.00
Active Trip OFF
<COLD LOAD PICKUP>
- CLPU COMMON -
Function TRIP
Relays (00 0000
Make use I NO
- CLPU-TYPE1 -
Pickup-Pha 2000
Pickup-Gro 2000
Pickup-SEF 20
Pickup-NEG2000
Outage Tim10.00
RMT Time ( 5.00
RMT-Phase ON
RMT-Groun ON
RMT-SEF ON
RMT-NEG ON
Reset Time 0.60
- CLPU-TYPE2 -
E-CLP Multi OFF
E-CLP Time 10
<VOLTAGE>
- UNDER VOLTAGE 1 -
Function OFF
Relays (00 0000

Page 58
BANK_.5

Pickup 0.70
Time Delay 5.00
Min. Voltag 0.10
Pickup Type1P
- UNDER VOLTAGE 2 -
Function OFF
Relays (00 0000
Pickup 0.70
Time Delay 5.00
Min. Voltag 0.10
Pickup Type1P
- OVER VOLTAGE 1 -
Function OFF
Relays (00 0000
Pickup 1.20
Time Delay 5.00
Pickup Type1P
- OVER VOLTAGE 2 -
Function OFF
Relays (00 0000
Pickup 1.20
Time Delay 5.00
Pickup Type1P
<FREQUENCY>
- FREQUENCY -
Function OFF
Relays (00 0000
Under Picku45.00
Under Trip 2.00
Over Pickup55.00
Over Trip T 6.00
Min. Voltag 0.10
Min. Curren10
Normal Fre OFF
Normal Fre 60.0
<USER CURVE>
- USER CURVE 1 -
Factor a 59.5000
Factor b 2.0000
Factor r 1.8000
Factor rt 59.5000
- USER CURVE 2 -
Factor a 39.8500
Factor b 2.0000
Factor r 0.9500
Factor rt 39.8500
- USER CURVE 3 -
Factor a 59.1000
Factor b 2.0000
Factor r 0.3450
Factor rt 59.1000
- USER CURVE 4 -
Factor a 5.6700
Factor b 2.0000

Page 59
BANK_.5

Factor r 0.0352
Factor rt 5.6700
<LOSS OF PHASE>
- Loss Of Phase -
Function OFF
Relay (000 0000
Pickup 0.30
Time Delay 20.00
<ALARM CURRENT>
- ALARM CURRENT -
Pickup-Pha OFF
Pickup-Gro OFF
Pickup-SEF OFF
Pickup-NEGOFF
Pickup-Tim 1.00
Dropout Ti 1.00

Page 60
BANK_.6

NAME1 NAME2 NAME3 NAME4 VALUE


[[RELAY SETUP]]
<PORT SETTING>
- RS232-1 -
Line Speed 19200
Parity Bit NONE
Data Bit 8
Stop Bit 1
Line Type 2
CTS functioON
DCD functi OFF
RTS functio AUTO
CTS Check-5
DCD Time-o5000
TX Post del 50
TX Pre Dela5
- RS232-2 -
Line Speed 19200
Parity Bit NONE
Data Bit 8
Stop Bit 1
Line Type 2
CTS functioON
RTS functio AUTO
DCD functi OFF
CTS Check-5
DCD Time-o5000
TX Post del 50
TX Pre Dela5
- ETHERNET -
IP Address 0
IP Address 0
IP Address 0
IP Address 0
Gateway Ad0
Gateway Ad0
Gateway Ad0
Gateway Ad0
Subnet Mas255.255.255.000
Keep-Alive DISABLE
Keep-Alive 4
Keep-Alive 2
keep-Alive 1
<COMMUNICATION>
- DNP3.0 (1) -
Function DISABLE
Use Port P2-232
Master Add60000
Slave Addr 1
D/L Confir SOME
D/L Retries 2
D/L Timeou55
A/L Retries 1
A/L Timeou 55

Page 61
BANK_.6

SBO Time ( 15
Multiframe 0.10
PowerUp UnENABLE
Unsol Time 5
Unsol Type NOTRIG
Class 1 DISABLE
Class 2 DISABLE
Class 3 DISABLE
Master IP O0
Master IP O0
Master IP O0
Master IP O0
TCP/UDP SeTCP
TCP Port 20000
UDP Port 20000
Keep-Alive 10
Fragment s 2048
Time Reque1440
- DNP3.0 (2) -
Function DISABLE
Use Port P3-232
Master Add60000
Slave Addr 2
D/L Confir SOME
D/L Retries 2
D/L Timeou55
A/L Retries 1
A/L Timeou 55
SBO Time ( 15
Multiframe 0.10
PowerUp UnENABLE
Unsol Time 5
Unsol Type NOTRIG
Class 1 DISABLE
Class 2 DISABLE
Class 3 DISABLE
Master IP O0
Master IP O0
Master IP O0
Master IP O0
TCP/UDP SeTCP
TCP Port 20000
UDP Port 20000
Keep-Alive 10
Fragment s 2048
Time Reque1440
- MODBUS -
Function DISABLE
Use Port P4-TCP
Slave Addr 1
Tx Delay (s 0.005
TCP/UDP SeTCP
TCP Port 502
UDP Port 502

Page 62
BANK_.6

- IEC60870-5-101 -
Function DISABLE
Use Port P2-232
Link Addres1
ASDU Addre1
Cyclic Peri 60
Event Perio15
Retries 0
D/L Confirm15
Max Poll Ti 60
ASDU Addre2
Link Confi ALWAYS
Link Addres1
Rx Frame S261
Rx Frame T 15
Tx Frame S 261
COT Size 1
IOA Size 2
One Char RNO
Frame Repe30
Select Time5
Use cmdAc YES
Use cseAct YES
Send Clock YES
- IEC60870-5-104 -
Function DISABLE
ASDU Addre1
Cyclic Peri 60
t0 Connecti120
t1 Ack (sec 15
t2 SFrame (10
t3 Test (sec20
Event Delay5
TCP Port 2404
Rx Frame S255
Tx Frame S 255
Select Time5
Use cmdAc YES
Use cseAct YES
Send Clock YES
- EVENT&ETC -
AI Event M OFF
SKIP at FaulYES
Fault I EvenYES
BI Event M ALL
BI Queue S 256
AI Event M ALL
AI Queue S 256
CI Event M ALL
CI Queue S 256
AI V Unit 10V
AI P Unit 10K
Daily Max I NO
Daily EnergNO

Page 63
BANK_.6

Event SendLOCAL
Time SynccLOCAL
<COMMON>
- GAS SENSOR -
Sensor Typ NONE
- EVENT RECORDER -
Fault Cycle ON
Length of P 4
Load ProfileON
LP Save Ti 15
- TIME SET -
Time Sync GMT
GMT Sign +
GMT Hour 0
GMT Min 0
- TIME DISPLAY -
Display TypYMD
[[MONITORING SETUP]]
<TRIP/BATTERY TEST>
- TRIP COUNTER -
Function OFF
Relays (00 0000
Counter for10000
Counter Se 77
- BATTERY TEST -
Battery Test0000
<GAS LOW>
- GAS LOW LOCK -
Function DISABLE
<FAULT LOCATOR>
- FAULT LOCATOR -
Function OFF
Length of F 50.0
Z1-Resistiv 10.0
Z1-Inductiv10.0
Z0-Resistiv 10.0
Z0-Inductiv10.0
<DEMAND>
- DEMAND -
Function OFF
Relays (00 0000
Type THM
Time Const 5
Pickup-Pha 600
Pickup-Gro 300
Pickup-NEG600
<RECLOSER WEAR>
- RECLOSER WEAR -
Function ALARM
Pickpu Wear20.0
Rated Volta27
Interrupt R 12.5
Number of 100
Wear Set-A 100.00

Page 64
BANK_.6

Wear Set-B 100.00


Wear Set-C 100.00
<SYNCHRO CHECK>
- SYNCHRO CHECK -
Function OFF
Relays (00 0000
Dead Line 0.50
Live Line M 0.85
Max. Volt D0.10
Max. Angle 15
Max. Freq D2.00
SynchrocheS(CB)
<EXTTRIP & LOCK>
- EXTTRIP & LOCK -
Function DISABLE
Use Input P1
Reset Meth LOCAL ONLY
<LIVE LOAD BLOCKING>
- LIVE LOAD BLOCKING -
Function OFF
Pickup 0.30
Time Delay 1.00
[[SYSTEM SETUP]]
<SYSTEM>
- CURRENT SENSING -
Phase CT Ra1000
Ground CT 1000
SEF CT Rati1000
- LINE VS SENSING -
Connect Ty CVD-W
VT 2nd (V) 84.8
VT Ratio 155.9
- LINE VL SENSING -
Connect Ty CVD-W
VT 2nd (V) 84.8
VT Ratio 155.9
Install Type 3P
- SYSTEM POWER -
Frequency 60
Phase RotatABC
Install Dire NOR
Phase Combabc
- AUTO SETTING GROUP CHANGE -
Function DISABLE
Time (sec) 30
- PANEL SLEEP TIME -
Interval (m 5
<LOOP CONTROL>
- LOOP CONTROL -
Select recl NONE
VRS at Sec VS
VRS to Tie VS
VS Wire 3PN
VL Wire 3PN(NA)

Page 65
BANK_.6

Auto Change OFF


Auto Change OFF
LC Action a DISABLE
LC Action a DISABLE
Open Time 10.00
Auto Restor5.00
Dead Line M50.0
Live Line M 70.0
Dead Line P50.00
LIve Line R 10.00
Dead Line R5.00
Non Reclose10.00
<OPTO INPUT SET>
- INPUT 1 -
Function NONE
Debounce T0.02
- INPUT 2 -
Function NONE
Debounce T0.02
- INPUT 3 -
Function NONE
Debounce T0.02
- INPUT 4 -
Function NONE
Debounce T0.02
- INPUT 5 -
Function NONE
Debounce T0.02
- INPUT 6 -
Function NONE
Debounce T0.02
- INPUT 7 -
Function NONE
Debounce T0.02
- INPUT 8 -
Function NONE
Debounce T0.02
<OUTPUT RELAY SET>
- OUTPUT 1 -
Function NONE
Type S/R LATCH
Pulse Time 0.05
- OUTPUT 2 -
Function NONE
Type S/R LATCH
Pulse Time 0.05
- OUTPUT 3 -
Function NONE
Type S/R LATCH
Pulse Time 0.05
- OUTPUT 4 -
Function NONE
Type S/R LATCH
Pulse Time 0.05

Page 66
BANK_.6

- OUTPUT 5 -
Function NONE
Type S/R LATCH
Pulse Time 0.05
- OUTPUT 6 -
Function NONE
Type S/R LATCH
Pulse Time 0.05
- OUTPUT 7 -
Function NONE
Type S/R LATCH
Pulse Time 0.05
- OUTPUT 8 -
Function NONE
Type S/R LATCH
Pulse Time 0.05
<POWER QUALITY>
- SUPPLY OUTAGE -
Function DISABLE
Duration 60
- SAG -
Function DISABLE
Pickup 0.80
Duration 5
- SWELL -
Function DISABLE
Pickup 1.20
Duration 5
- CURRENT UNBALANCE -
Function DISABLE
Pickup 30
Time Delay 4.0
UB Current 10
- VOLTAGE UNBALANCE -
Function DISABLE
Pickup 30
Time Delay 4.0
[[PROTECTION SETUP]]
<OTHER VIEW>
- OTHER ELEMENT -
Seq Coord OFF
Lockout PrioGND
F/I Reset AUTO
Manual Clos0.00
<DIRECTION ELEMENT>
- PHASE -
Direction T OFF
Max. Torque300
Min. Pol Vol0.20
Block OvercNO
- GROUND -
Direction T OFF
Max. Torque135
Min. Pol Vol0.20

Page 67
BANK_.6

Block OvercNO
- SEF -
Direction T OFF
Max. Torque135
Min. Pol Vol0.20
Block OvercNO
- NEGATIVE -
Direction T OFF
Max. Torque135
Min. Pol Vol0.20
Block OvercNO
<OPERATIONS>
- Lockout -
Phase 4
Ground 4
S.E.F 4
NEG 4
- Fast Curve -
Phase 2
Ground 2
NEG 2
<INTERVALS>
- INTERVAL -
Reclosing T0.60
Reclosing T2.00
Reclosing T15.00
Reclosing T15.00
Reset Timeo30.00
Reset Timeo10.00
Closing Pow60.00
<PICKUP CURRENT>
- PICKUP CURRENT -
Phase 500
Ground 250
S.E.F OFF
NEG Seq OFF
<PHASE/GND/SEF/NEGATIVE>
- PHASE FAST -
Curve Prev OFF
Function TRIP
Relays (00 0000
Curve ANSI-STI
Time Dial 0.50
Time Adder 0.00
Min. Res Ti 0.00
Reset Meth INST
Low Set DT OFF
- PHASE DELAY -
Curve Prev OFF
Function TRIP
Relays (00 0000
Curve ANSI-VI
Time Dial 3.00
Time Adder 0.00

Page 68
BANK_.6

Min. Res Ti 0.00


Reset Meth INST
Low Set DT OFF
- GROUND FAST -
Curve Prev OFF
Function TRIP
Relays (00 0000
Curve ANSI-STI
Time Dial 0.50
Time Adder 0.00
Min. Res Ti 0.00
Reset Meth INST
Low Set DT OFF
- GROUND DELAY -
Curve Prev OFF
Function TRIP
Relays (00 0000
Curve ANSI-VI
Time Dial 3.00
Time Adder 0.00
Min. Res Ti 0.00
Reset Meth INST
Low Set DT OFF
- SEF -
Function TRIP
Relays (00 0000
Time Delays1.00
- NEGATIVE FAST -
Curve Prev 1.00
Function TRIP
Relays (00 0000
Curve ANSI-STI
Time Dial 0.50
Time Adder 0.00
Min. Res Ti 0.00
Reset Meth INST
Low Set DT OFF
- NEGATIVE DELAY -
Curve Prev OFF
Function TRIP
Relays (00 0000
Curve ANSI-VI
Time Dial 3.00
Time Adder 0.00
Min. Res Ti 0.00
Reset Meth INST
Low Set DT OFF
<HIGH CURRENT>
- TRIP-PHASE -
Function OFF
Relays (00 0000
Pickup 4000
Time Delay 0.00
Active Trip OFF

Page 69
BANK_.6

- TRIP-GROUND -
Function OFF
Relays (00 0000
Pickup 4000
Time Delay 0.00
Active Trip OFF
- TRIP-NEGATIVE -
Function OFF
Relays (00 0000
Pickup 4000
Time Delay 0.00
Active Trip OFF
- LOCKOUT-PHASE -
Function OFF
Relays (00 0000
Pickup 8000
Time Delay 0.00
Active Trip OFF
- LOCKOUT-GROUND -
Function OFF
Relays (00 0000
Pickup 8000
Time Delay 0.00
Active Trip OFF
- LOCKOUT-NEGATIVE -
Function OFF
Relays (00 0000
Pickup 8000
Time Delay 0.00
Active Trip OFF
<COLD LOAD PICKUP>
- CLPU COMMON -
Function TRIP
Relays (00 0000
Make use I NO
- CLPU-TYPE1 -
Pickup-Pha 2000
Pickup-Gro 2000
Pickup-SEF 20
Pickup-NEG2000
Outage Tim10.00
RMT Time ( 5.00
RMT-Phase ON
RMT-Groun ON
RMT-SEF ON
RMT-NEG ON
Reset Time 0.60
- CLPU-TYPE2 -
E-CLP Multi OFF
E-CLP Time 10
<VOLTAGE>
- UNDER VOLTAGE 1 -
Function OFF
Relays (00 0000

Page 70
BANK_.6

Pickup 0.70
Time Delay 5.00
Min. Voltag 0.10
Pickup Type1P
- UNDER VOLTAGE 2 -
Function OFF
Relays (00 0000
Pickup 0.70
Time Delay 5.00
Min. Voltag 0.10
Pickup Type1P
- OVER VOLTAGE 1 -
Function OFF
Relays (00 0000
Pickup 1.20
Time Delay 5.00
Pickup Type1P
- OVER VOLTAGE 2 -
Function OFF
Relays (00 0000
Pickup 1.20
Time Delay 5.00
Pickup Type1P
<FREQUENCY>
- FREQUENCY -
Function OFF
Relays (00 0000
Under Picku45.00
Under Trip 2.00
Over Pickup55.00
Over Trip T 6.00
Min. Voltag 0.10
Min. Curren10
Normal Fre OFF
Normal Fre 60.0
<USER CURVE>
- USER CURVE 1 -
Factor a 59.5000
Factor b 2.0000
Factor r 1.8000
Factor rt 59.5000
- USER CURVE 2 -
Factor a 39.8500
Factor b 2.0000
Factor r 0.9500
Factor rt 39.8500
- USER CURVE 3 -
Factor a 59.1000
Factor b 2.0000
Factor r 0.3450
Factor rt 59.1000
- USER CURVE 4 -
Factor a 5.6700
Factor b 2.0000

Page 71
BANK_.6

Factor r 0.0352
Factor rt 5.6700
<LOSS OF PHASE>
- Loss Of Phase -
Function OFF
Relay (000 0000
Pickup 0.30
Time Delay 20.00
<ALARM CURRENT>
- ALARM CURRENT -
Pickup-Pha OFF
Pickup-Gro OFF
Pickup-SEF OFF
Pickup-NEGOFF
Pickup-Tim 1.00
Dropout Ti 1.00

Page 72