TABLE 5- PHASE SPACING AND GROUND CLEARANCE FOR STATION CLASS OUTDOOR AIR SWITCHES AND BUS SUPPORTS

ANSI C37.32 - 1996 A.R.C. 21/09/2000


rated Min, Metal to Metal Certerline- to -Centerline phase Spacing 4
rated lightning distance disconnecting vertical break side break All Horn Gap
maximum withstand switches, bus supports Ground Clearance disconnecting Switches (Horizontal Break) Switchwes (vertical
voltage voltage and rigid conductors recommended minimum and Bus Supports disconnecting switches and side break )
line kv rms kv peak inches mm inches mm inches mm inches mm inches mm inches mm
number "1" "2" "3" "4" "5" "6" "7" "8"
1 8.25 95 7 178 7.5 191 6 152 18 457 30 762 36 914
2 15.50 110 12 305 10.0 254 7 178 24 610 30 762 36 914
3 25.60 150 15 381 12.0 305 10 254 30 762 36 914 48 1219
4 38.00 200 18 457 15.0 381 13 330 36 914 48 1219 60 1520
5 48.30 250 21 533 18.0 457 17 432 48 1219 60 1520 72 1829
6 72.50 250 21 533 18.0 457 17 432 48 1219 60 1520 72 1829
7 350 31 787 29.0 737 25 635 60 1520 72 1829 84 2134
8 121.00 350 31 787 29.0 737 25 635 60 1520 72 1829 84 2134
9 450 44 1118 39.0 991 34 864 72 1829 91 2311 103 2616
10 550 53 1346 47.0 1194 42 1067 84 2134 108 2743 120 3048
11 145.00 350 31 787 29.0 737 25 635 60 1524 72 1829 84 2134
12 450 44 1118 39.0 991 34 864 72 1829 91 2311 103 2616
13 550 53 1346 47.0 1194 42 1067 84 2134 108 2743 120 3048
14 650 63 1600 52.5 1333 50 1270 98 2489 132 3353 144 3658
15 169.00 450 44 1118 39.0 991 34 846 72 1829 91 2311 103 2616
16 550 53 1346 47.0 1194 42 1067 84 2134 108 2743 120 3048
17 650 63 1600 52.5 1333 50 1270 98 2489 132 3353 144 3658
18 750 72 1829 61.5 1562 58 1473 108 2743 156 3962 168 4267
19 242.00 550 53 1346 47.0 1194 42 1067 84 2134 108 2743 120 3048
20 650 63 1600 52.5 1333 50 1270 98 2489 132 3353 144 3658
21 750 72 1829 61.5 1562 58 1473 108 2743 156 3962 168 4267
22 900 89 2261 76.0 1930 71 1803 132 3353 192 4877 192 4877
23 1050 105 2667 90.5 2299 83 2108 156 3962 216 5486 216 5486
24 362.00 1050 105 2667 90.5 2299 84 2134 156 3962 216 5486 216 5486
25 1300 110 2794 106.0 2692 104 2642 174 4420 see note 5 see note 5 240 6096
26 550.00 1550 see note 5 see note 5 124 3150 see note 5 see note 5 300 7620
27 1800 see note 5 see note 5 144 3658 see note 5 see note 5 324 8230
28 800.00 2050 see note 5 see note 5 166 4216 see note 5 see note 5 600 15240
NOTES:
1- close lightning arrester coordination may allow fower lightinig impulse values. Traditional values shown in bold fonl.
2- Minimum metal-to-metal distance may be modified providing prooof of performance is substantiated by dielectric tests.
3- Ground clearance for switches with voltages 362 kv and above are based on switching surge voltage levels. Ref to bibliography. Annex C.
4- The phase spacings in columns 6, 7 and 8 are recomended values. Overall width of switch and bus support energized parts, angle of opening of side break switches, etc. May
allow areduction in phase sapcing dependent upon voltage concentration on sharp proyections. Resultant metal-to-metal distances between phase energized parts should not be
less that shown in column 3.
5- values not yet established. TRANSFORMADORES, ASESORIA Y MANTENIMIENTO, S. A.