You are on page 1of 20

10A

Type C PORCELAIN
Cutouts (Standard, Linkbreak, Loadbreak)
and
Cutout-Arrester Combinations
Catalog 10A October 2015

Phone: 573-682-5521 Email: hpsliterature@hubbell.com Web: hubbellpowersystems.com


October 2015 Page 1
Type C Cutouts

LOADBREAK cutout
with Arc-Chute interrupter,
pages 11-13

LINKBREAK cutout,
pages 8-10

STANDARD cutout,
pages 3-7

Application
The primary purpose of any cutout is to provide protection to
the lines of your system and the various apparatus on those
lines such as transformers and capacitor banks. Chance Type
C cutouts provide reliable protection from low-level overloads
that just melt the fuse link, intermediate faults, and very high
faults, through maximum interrupt capacity.
In addition, Type C cutouts can also be used as a sectionalizing
device. With the use of a portable loadbreak tool, Type C cutouts
can function much like an overhead disconnect switch. A 300
amp disconnect blade is also available for this purpose.

Ratings/Specifications
STANDARD Type C cutouts have maximum design voltage rat-
ings to simplify the confusing ratings of cutouts. There are no
restrictions on application to grounded wye, ungrounded wye,
or delta systems having maximum operating voltages (line-to-
line) equal to or less than the cutout maximum design voltage
rating. (See the LINKBREAK and LOADBREAK cutouts for
CUTOUT-ARRESTER
their specifications.) Interruption tests have been performed
at full system line-to-line voltage. In each voltage class, there Combinations,
are continuous current ratings of 100 amps, 200 amps and 300 page 14
amps. See the table on page 6 for other specifications.

Phone: 573-682-5521 Email: hpsliterature@hubbell.com Web: hubbellpowersystems.com


Page 2 October 2015
Type C STANDARD Cutout

100 Amp Single Vent 200 Amp Single Vent 300 Amp Disconnect
Chance Type C fuseholders are mutually interchangeable with S&C Type XS and ABB Type ICX cutouts.

Quality Construction Insulators


The insulators used on Type C cutouts are a sky-glaze gray.
Efficient Current Transfer The metal to metal leakage distance on the 15 kV cutout
insulator is 8.7 inches (220 mm), 12.6 inches (320 mm) on
The Chance Type C cutout has an all copper current path. All the 27 kV [125 kV LIW (BIL)], 17.3 inches (440 mm) on the
contacts are silver-plated. Terminals are tin-plated bronze 27 kV [150 kV LIW (BIL)], 26 inches (660 mm) on the 36
for use with copper or aluminum conductors. kV [170 kV LIW (BIL)], and 28.4 inches (720 mm) on the 36
kV [170 kV LIW (BIL)].
Loadbreak Hooks
Galvanized steel hooks are standard on all Type C cutouts, Fuseholders
except the arc chute version, for use with a portable loadbreak The solid cap on the single vent fuseholder is silver-plated
tool. These sturdy hooks are mounted on the top support and copper alloy, to provide efficient current transfer. An integral
serve to guide the fuseholder into the latch socket when clos- ring is provided in the top tube casting for opening and clos-
ing at an off-center angle. ing the fuseholder with conventional disconnect tools from
the ground, from a bucket truck or from the pole.
Top Contact The toggle type trunnion casting is a selective silver-
plated bronze for efficient current transfer to the lower
The top contact is attached to the galvanized-steel hood by a
hinge contacts. A cam shaped projection on each side of the
stainless rivet to provide a smooth self-aligning action during
trunnion casting provides high pressure parallel current
closing even in severely corrosive environments. The top con-
paths to the lower contacts. These projections, or pivot pins,
tact provides a socket-type cavity for latching the fuseholder
are cast full round for smooth rotational operation in the
and prevents any possible over-travel of the fuseholder. The
hinge. The link ejector assists in arc interruption during
top contact is made of a highly conductive copper strip with
low fault current or excessive overload conditions. A groove
silver-plated embossments to resist corrosion. The contacts
in the center of the link ejector allows the fuse links pigtail
are held under constant pressure designed to maintain firm
to go directly from the fuse tube to the attachment nut. A
contact with the fuseholder contact surface until fault inter-
curved ejector minimizes bending stresses in the pigtail to
ruption is accomplished.
prevent broken strands. A stainless steel torsion spring on
the link ejector helps to rapidly eject the link from the bore
Hinge of the fuseholder during interruption. The 200 amp link
ejector has a wider groove area and increased spring force
The hinge on the Type C cutout employs large pivot areas for to accommodate the larger links.
the fuseholders trunnion and is cast of a copper alloy chosen
for its strength and corrosion resistance. The hinge contacts The link ejector is pinned to the trunnion casting with a
are highly conductive copper alloy stampings and are plated stainless steel pin to provide resistance to corrosive elements
to assure low resistance current transfer from the trunnion and provide smooth pivotal action. An interlocking feature
casting. The parallel current paths are backed up by high between the link ejector and tube casting prevents excessive
strength cantilever springs and are riveted to the hinge cast- tension on the fuse link during closure, thereby preventing
ings. Fuseholder can be dropped into place and easily lifted link breakage.
up and out. No tricky maneuvering. The link ejector employs a hammer effect to enhance toggle
action of the trunnion during low fault and overload inter-
ruptions, hence dropout action is enhanced. The link ejector
provides sufficient surface area to facilitate re-fusing by
linemen wearing gloves.

Phone: 573-682-5521 Email: hpsliterature@hubbell.com Web: hubbellpowersystems.com


October 2015 Page 3
Type C STANDARD Cutout
PRODUCT FEATURES Extra Corrosion Protection
Type C cutouts are available with stainless steel hood,
Interchangeability brackets, and hardware and copper alloy loadbreak hooks
to offer greater corrosion resistance for environmental areas
Chance was the first to design a cutout that could interchange where corrosion can become a major factor. To order a stain-
fuseholders and mounting assemblies with those of another less steel/copper alloy cutout add the suffix S to the end of
manufacture. Chance Type C fuseholders are mutually the catalog number with the rating specifications desired. In
interchangeable with S&C Type XS and ABB Type ICX cutouts additon, an optional spring assist may be provided to further
(within the same voltage class). enhance the toggle and drop out action in highly corrosive
applications.
Fusetube
The 1/2-inch inside diameter of the Type C cutouts 100 ampere
fusetube increases internal pressure giving superior and
reliable expulsion action. During frequently encountered
intermediate fault ranges this diameter also permits higher
TRV (transient recovery voltage) values to be tolerated. This
small bore design eliminates any concern related to high
impedance phase-to-phase faults on ungrounded wye and
delta systems.

The inside liner is constructed of a synthetic arc-quenching


material. The tube is made of fiberglass which permits the
smaller bore and provides a higher burst strength. It is
protected from the weather and environment by a special
ultra-violet resistant coating.

Also, the Chance fusetube operates with fuselinks from all


major suppliers.

Brackets
C cutouts come packed one per carton including a NEMA
Heavy Duty B bracket with captive 11/2" bolt for crossarm
mounting.

Type X brackets, also for crossarm mounting, provides 25/8"


additional clearance between the crossarm and the cutout.

D brackets are used to mount cutouts and/or arresters


directly to the pole. Three brackets may be used for three-
STANDARD Type C Cutout with
phase application. Type D brackets provide a clean, quick NEMA Type B Bracket Dimensions
mounting without crossarm or special pole bands.
kV
All the above brackets are galvanized steel for long lasting LIW (BIL) A B C D E
service. Cutouts can be ordered without any brackets. 16" 51/2" 103/4" 31/2" 211/2"
110
406 mm 137 mm 273 mm 89 mm 559 mm
Higher Interrupt Capacities 163/8" 71/8" 121/2" 31/8" 263/4"
125
By using a copper arc shortening rod inside the top of the 416 mm 181 mm 318 mm 79 mm 679 mm
fusetube, higher interrupt ratings are obtainable. An arc 163/8" 71/8" 121/2" 31/8" 263/4"
shortening rod is attached to the cap of some fusetubes and 150
416 mm 181 mm 318 mm 79 mm 679 mm
lowers the fuse link within the fusetube. This permits a 171/4" 81/2" 15" 13/4" 321/2"
much shorter arc, resulting in less arc energy, and higher 170
438 mm 216 mm 381 mm 44 mm 826 mm
interrupting capacities.
For 200 A tubes, it allows for full voltage rating.
Terminals
It is necessary to use fuse links with removable buttonheads
Tin-plated bronze parallel groove type terminals are standard
when arc shortening rods are employed.
on Type C cutouts. They can accommodate aluminum or
copper conductor sizes ranging from No. 6 (13.3 mm2) solid
170 kV LIW (BIL) copper through 4/0 (160.6 mm2) ACSR or 250 (167.5 mm2)
A 170 kV BIL Type C cutout is available for use in areas kcmil stranded copper. The parallel groove design is perfect
where the 28.4-inch minimum leakage distance to ground for handling two different sizes of conductor as is the case
is required. See ordering data, page 6. when arresters are being used. Eyebolts are also available.
See ordering data, page 10A-6.

Phone: 573-682-5521 Email: hpsliterature@hubbell.com Web: hubbellpowersystems.com


Page 4 October 2015
Compare Chance quality and technical expertise
Type C STANDARD Cutout
All Type C Cutouts meet or exceed ANSI/NEMA specifications.

TIN-PLATED BRONZE TERMINALS


FOR USE WITH COPPER
COPPER OR ALUMINUM CONDUCTOR
ARC-SHORTENING ROD
(ON SOME RATINGS)

COPPER CURRENT PATH

GALVANIZED-STEEL
ONE PIECE HOOD
BIRD-PROOFED
ONE-PIECE
STAINLESS STEEL SOLID-PORCELAIN
BACKUP SPRING INSULATOR
TO MAINTAIN
CONTACT PRESSURE

SILVER-TO-SILVER
CONTACTS
SYNTHETIC
GALVANIZED STEEL HOOKS FUSE TUBE
FOR LOADBREAK TOOL LINER

CAST BRONZE TOP TUBE CASTING


AND PULL RING

HIGH-STRENGTH FIBERGLASS FUSETUBE


COATED WITH ULTRA-VIOLET INHIBITOR

HOT STICK HOLE IN TRUNNION CASTING

LARGE NUT OR
SS NUT WITH
CLAMP TO FASTEN
FUSELINK WITH-
OUT BREAKING
STRANDS.
CAST BRONZE
LOWER TUBE
CASTING
COPPER
CURRENT PATH
STAINLESS-STEEL
MECHANICAL ASSIST: SPRING ENSURES
PROPER TOGGLE ACTION
FUSEHOLDER IS AVAIL- OF FUSELINK EJECTOR SILVER-TO-SILVER
ABLE WITH A TORSIONAL CONTACTS
SPRING ON TRUNNION TO WITH STAINLESS STEEL
AID DROP OUT OPERATION BACKUP SPRINGS
IN CORROSIVE ENVIRON-
MENTS. CAST BRONZE HINGE
FUSEHOLDER TOGGLE LATCH FOR CORROSION RESISTANCE
LIMITS TENSION OF FUSELINK

Phone: 573-682-5521 Email: hpsliterature@hubbell.com Web: hubbellpowersystems.com


October 2015 Page 5
All Type C Cutouts meet or exceed ANSI/NEMA specifications.

Type C STANDARD Cutout


See page 10A-14 for Arrester Cutout Combinations
Specifications and Ordering Information See page 10A-15 for Accessories.
See page 10A-16 for Complete Catalog Numbering
15 kV - 110 kV LIW (BIL)RUS Listed
*Option Maximum Continuous Interrupt Leakage to Ground Replacement Arc
& Loadbreak Fusetube
*Base suffixes Design Nominal Capacity Metal to Metal *Weight Cap/ Cap Shorten-
Current
Catalog No. below Voltage System Voltage (Amps) (Asym Amps) (minimum) (lb./kg.) Assembly ing Rod
C710112 123 15 kV Thru 14.4 kV 100 10,000 8.7" 220 mm 14.23 /6.45 P7001535P No
C710114 123 15 kV Thru 14.4 kV 100 16,000 8.7" 220 mm 14.43 /6.55 E7001767P Yes
C710143 123 15 kV Thru 14.4 kV 200 12,000 8.7" 220 mm 15.03 /6.82 E7002146P Yes
C710133 123 15 kV Thru 14.4 kV 300 12,000** 8.7" 220 mm 14.53 /6.59 P7001535P N/A

27 kV - 125 kV LIW (BIL)RUS Listed


C710211 123 27 kV 100 8,000 12.6" 320 mm 17.03 / 7.72 P7001535P No
C710213 123 27 kV 100 12,000 12.6" 320 mm 17.03 / 7.72 E7001768P Yes
C710242 123 27 kV Thru 24.9 kV 200 10,000 12.6" 320 mm 17.73 / 8.04 E7002479P Yes
C710243 123 27 kV 200 12,000 12.6" 320 mm 17.73 / 8.04 PSE7002706P Yes
C710233 123 27 kV 300 12,000* 12.6" 320 mm 17.23 / 7.82 P7001535P N/A

27 kV - 150 kV LIW (BIL)RUS Listed


C710311 123 27 kV 100 8,000 17.3" 440 mm 22.63 / 10.26 P7001535P No
No
C710313 123 27 kV 100 12,000 17.3" 440 mm 22.83 / 10.36 E7001768P Yes
Restrictions thru
C710342 123 27 kV
24.9 kV; 26.4
200 10,000 17.3" 440 mm 23.43 / 10.63 E7002479P Yes
C710343 123 27 kV thru 34.5kV 200 12,000 17.3" 440 mm 23.43 / 10.63 PSE7002706P Yes
C710333 123 27 kV 300 12,000* 17.3" 440 mm 23.03 / 10.45 P7001535P N/A

36 kV - 170 kV LIW (BIL)RUS Listed


C710613 123 36 kV Thru 34.5 kV 100 12,000 26" 660 mm 25.43/11.54 E7001743P Yes
No Restrictions
C710643 123 27 kV thru 24.9 kV; 200 12,000 26" 660 mm 25.83/11.72 E7002117P Yes

26.4 thru 34.5 kV
C710633 123 36 kV Thru 34.5 kV 300 12,000** 26" 660 mm 25.43/11.54 P7001535P N/A
NOTE: 26" fuse links are recommended.
36 kV - 170 kV LIW (BIL)RUS Listed
C710713 123 36 kV Thru 34.5 kV 100 12,000 28.4" 720 mm 30.73/13.94 E7001743P Yes
No Restrictions
C710743 123 27 kV thru 24.9 kV; 200 12,000 28.4" 720 mm 31.13/14.12 E7002117P Yes

26.4 thru 34.5 kV
C710733 123 36 kV Thru 34.5 kV 300 12,000** 28.4" 720 mm 30.73/13.94 P7001535P N/A
NOTE: 26" fuse links are recommended.
*Adjust total weight when selecting Options below. **Momentary ratingSolid blade
Must use removable buttonhead fuse links.

For application on single-phase to neutral or three-phase solidly-grounded wye-connected circuits where recovery voltage does not exceed
the maximum-design voltage of the device.
*Option Suffix 1 *Option Suffix 2 *Option Suffix 3
Terminal Variations Bracket Variations Mechanical Assist Fuseholder
Suffix *Weight Suffix *Weight Suffix
Description Description Description
1 (lb./kg.) 2 (lb./kg.) 3
P Parallel-groove clamps 0.33/0.15 NEMA Heavy Duty B bracket Blank No option (may not be
B 2.84/1.29
E Small eyebolts 0.16 /0.07 for crossarm (11/2" bolt) used with Z in Option 2)
L Large eyebolts 0.31/0.14 Extended type bracket for M Mechanical Assist Fuse-
X crossarm (Horizontal section is 3.75/1.70 holder (may not be used
R Lower PG Clamp
Rotated 90
0.33/0.15
25/8" longer than Type B bracket) with Blank in Option 2)
D D-shape bracket (pole) 7.67/3.48
Must specify one selection for Option 1. Fargo cutout cover
No bracket (must be used with M F
Z (may not be used with
in Option 3) Blank in Option 2)
Blank No bracket (cannot use with M in
Option 3) Anti- corrosion stainless
S
V Easy-On bracket (Height: 418" to steel/copper alloy cutout
2.9/1.32
5532", Width: 234" to 4")

Phone: 573-682-5521 Email: hpsliterature@hubbell.com Web: hubbellpowersystems.com


Page 6 October 2015
Type C STANDARD Cutout
Fuseholders and Mounting Assemblies
Ordering Information
15 kV - 110 kV LIW (BIL)
*Cutout Fuse Holder/
Mounting Mounting
Fuseholder/Blade Assembly Base
Base Catalog Catalog Number Blade Weight Assembly
*Catalog Number Weight
Number 100A 200A
C710112 T710112T 1.8 lb. 0.82 kg. 300A
Fuseholders Blade
C710114 T710114T 2.0 lb. 0.91 kg. T7101MM
1.18 kg. 12.9 lb. 5.85 kg.
C710143 T710143T 2.6 lb.
C710133 T710133T 2.1 lb. 0.95 kg. 15 kV


8.7" leakage
Catalog No.
T7101MM
Mounting
Assembly
only

100A 200A 300A


Fuseholders Blade
27 kV-12.6" leakage 27 kV-17.3" leakage
T7102MMPB T7103MMPB

27 kV - 125 kV LIW (BIL)


C710211 T710211T 2.1 lb. 0.95 kg
C710213 T710213T 2.3 lb. 1.14 kg
C710242 T710242T 2.7 lb. 1.22 kg T7102MM 15.6 lb 7.08 kg
C710243 T710243T 2.7 lb. 1.22 kg
C710233 T710342T 2.5 lb. 1.13 kg 100A 200A 300A
Fuseholders Blade
27 kV - 150 kV LIW (BIL)
C710311 T710311T 1.9 lb. 0.86 kg
C710313 T710313T 2.0 lb. 0.91 kg
C710342 T710342T 2.5 lb. 1.13 kg T7103MM 21.3 lb 9.66 kg
C710343 T710343T 2.5 lb. 1.13 kg
C710333 T710333T 2.1 lb. 0.97 kg

36 kV - 170 kV LIW (BIL)


C710613 T710613T 2.8lb. 1.27 kg.
C710643 T710643T 3.2 lb. 1.45 kg. T7106MM 23.4 lb. 10.61 kg.
C710633 T710633T 2.8 lb. 1.27 kg.
NOTE: 26" fuse links are recommended. 36 kV-26" leakage 36 kV-28.4" leakage
36 kV - 170 kV LIW (BIL) T7106MMPB T7107MMPB
C710713 T710713T 2.8lb. 1.27 kg.
C710743 T710743T 3.2 lb. 1.45 kg. T7107MM 28.7 lb. 13.02 kg.
C710733 T710733T 2.8 lb. 1.27 kg.
NOTE: 26" fuse links are recommended.

Universal Cutout Tool


Ideal for Standard and Linkbreak 100 amp fuse
holders (ABB, Chance S&C) to easily lift out, place,
*open and close. Inverted, secure method also fits
Chance Electronic Sectionalizers.
Cat. No. PSC4033484 (Wt. 4 oz.) See Tools Catalog Section 2100.
*When opening a cutout, follow all work rules and OSHA regula-
tions. Not for use with Loadbreak cutouts.

Phone: 573-682-5521 Email: hpsliterature@hubbell.com Web: hubbellpowersystems.com


October 2015 Page 7
Type C 100-Amp LINKBREAK Cutout
15 kv-110 kV LIW (BIL) 22/36.4 kV-150 kV LIW (BIL)
15/27 kV-125 kV LIW (BIL) 22/36.4 kV-170 kV LIW (BIL)
All standard non-loadbreak fuseholders and the linkbreak
fuseholders are interchangeable and fit into both the non-
loadbreak and Type C LINKBREAK cutout mounting
assemblies produced after January 1985. Mounting as-
semblies are same as Type C STANDARD cutouts, shown
on page 10A-7.

Ratings / Specifications
The 15 kV Type C LINKBREAK cutout has a maximum
design voltage rating of 15 kV. There are no voltage restric-
tions on application to grounded wye, ungrounded wye, or
delta systems having maximum operating voltages (line
to line) equal to or less than the cutout maximum design
voltage rating.
The 15/27 and 22/36.4 kV Type C LINKBREAK cutouts have
maximum design slant voltage ratings. These cutouts are
to be used on systems which have phase-to-ground voltages
no greater than the value listed to the left of the slant (/)
and which have phase-to-phase voltages no greater than
the value listed to the right of the slant.
The Type C LINKBREAK cutout is to be used with only
Chance, McGraw-Edison and Kearney fuselinks. S&C
Electric fuselinks and other fuselinks which require more
A sharp downward pull on the lever with a hookstick than 1 inch elongation before breaking must not be used
breaks the fuselink. with the Type C LINKBREAK cutout.
15 kV-110 kV LIW (BIL) unit
Application
The Chance Type C 100 amp LINKBREAK cutout provides
short circuit protection to utility lines with the added feature
of mechanical linkbreak capability in a loadbreaking function.
Linkbreak cutouts provide reliable protection from overloads
that just melt the fuselink through the maximum interrupt
capacity of the fuseholder and also provide inductive and
capacitive loadbreak capability. For loadbreak ratings see
chart, next page.
The unit will also accept the Type C 200 amp non-loadbreak
fuseholder or a 300 amp disconnect blade. Each LINK-
BREAK cutout includes standard loadbreak hooks to use
with portable loadbreak tools. This method is particularly
useful for switching of the 200 amp fuseholder and 300 amp
disconnect blade.

Design / Product Features


Construction and product details shown on page 10A-3 apply
to the LINKBREAK cutout except that the link-ejector on
the linkbreak fuseholder is a copper-alloy casting instead of
a stainless-steel stamping.
The unit utilizes a stainless-steel linkbreak lever to mechani-
cally break fuselink elements thereby obtaining load inter-
ruption within the fuseholder. The long lever is positioned
directly in-line with the cutout, rather than on one side or
in back of the cutout for convenient pull-down operation.
15/27 kV-125 kV LIW (BIL) unit

Phone: 573-682-5521 Email: hpsliterature@hubbell.com Web: hubbellpowersystems.com


Page 8 October 2015
Type C 100-Amp LINKBREAK Cutout
LINKBREAK Cutout with NEMA Type B Bracket
Dimensions
LIW (BIL)
kV A B C D E F
16" 53/8" 103/4" 31/2" 22" 165/8"
110 406 137 273 89 559 422
mm mm mm mm mm mm
163/8" 71/8" 121/2" 31/8" 263/4" 16"
125 416 181 318 79 679 406
mm mm mm mm mm mm
163/8" 71/8" 121/2" 31/8" 263/4" 16"
150 416 181 318 79 679 406
mm mm mm mm mm mm
171/4" 81/2" 15" 13/4" 321/2" 141/2"
170 438 216 381 416 826 368
mm mm mm mm mm mm

Loadbreak Ratings
*Base Cutout kV,
Catalog Nominal Inductive Capacitive
Number System Voltage Amperes Amperes
C720112 14.4 100 100
C720114 14.4 100 100
C720211 24.9 100 100
C720213 24.9 100 100
C720311 34.5 100 50
C720313 34.5 100 50
C720613 34.5 100 50
*Specifications and ordering information on next page.

Limited to grounded-wye systems with grounded-wye
loads.

22/36.4 kV-150 kV LIW (BIL) unit 22/36.4 kV-170 kV LIW (BIL) unit

Phone: 573-682-5521 Email: hpsliterature@hubbell.com Web: hubbellpowersystems.com


October 2015 Page 9
All Type C Cutouts meet or exceed ANSI/NEMA specifications.

Type C 100-Amp LINKBREAK Cutout


*Fuseholders (100 Amp only)
kV Cutout Fuseholder Weight
& BIL Catalog Number Catalog No. lb. kg.
15 kV C720112PB T720112T 2.5 1.13
110 kV BIL C720114PB T720114T 2.7 1.22
15/27 kV C720211PB T720211T 2.7 1.22
125 kV BIL C720213PB T720213T 2.9 1.32
22/36.4 kV C720311PB T720311T 2.7 1.22
150 kV BIL C720313PB T720313T 2.9 1.32
22/36.4 kV C720613PB T720613T 3.5 1.59
170 kV BIL
*Mounting assemblies are same as Type C STANDARD cutouts,
shown on page 10A-7.

110 kV BIL 125 & 150 kV BIL 170 kV BIL


See page 10A-14 for Arrester Cutout Combinations
Specifications and Ordering Information See page 10A-15 for Accessories.
See page 10A-16 for Complete Catalog Numbering
15 kV - 110 kV LIW (BIL)RUS Listed
*Option Maximum Continuous Interrupt Leakage to Ground Replacement Arc
*Base suffixes Design Nominal Current Capacity Metal to Metal *Weight Fusetube Cap/ Shortening
Catalog No. below Voltage System Voltage (Amps) (Asym Amps) (minimum) (lb./kg.) Cap Assembly Rod
C720112 123 15 kV Thru 14.4 kV 100 10,000 8.7" 220 mm 14.53 /6.59 P7001469P No
C720114 123 15 kV Thru 14.4 kV 100 16,000 8.7" 220 mm 14.73 /6.68 E7001784P Yes

15/27 kV - 125 kV LIW (BIL)RUS Listed


No Restrictions 100 8,000 12.6" 320 mm 17.23 /7.82 P7001469P No
C720211 123 15/27 kV
thru 14.9 kV;
C720213 123 15/27 kV 20.8 thru 24.9 kV 100 12,000 12.6" 320 mm 17.43 /7.91 E7001785P Yes

22/36.4 kV - 150 kV LIW (BIL)RUS Listed


No Restrictions 100 8,000 17.3" 440 mm 23.03/10.45 P7001469P No
C720311 123 22/36.4 kV
thru 20.8 kV;
C720313 123 22/36.4 kV 22.8 thru 34.5 kV 100 12,000 17.3" 440 mm 23.23/10.54 E7001785P Yes

22/36.4 kV -170 kV LIW (BIL)RUS Listed


No Restrictions
C720613 123 22/36.4 kV thru 20.8 kV; 100 11,200 26.0" 660 mm 26.13/11.85 PE7001787P Yes

22.8 thru 34.5 kV
NOTE: 26" fuse links are recommended.

Must use removable buttonhead fuse links. *Adjust total weight when selecting Options below.

For application on single-phase to neutral circuits with phase-to-ground voltages not exceeding the value to the left of
the slant; and for application on three-phase solidly-grounded-wye systems with solidly-grounded loads with line-to-line
voltages not exceeding the value to the right of the slant.
*Option Suffix 1 *Option Suffix 2 *Option Suffix 3
Terminal Variations Bracket Variations Mechanical Assist Fuseholder
Suffix *Weight Suffix *Weight Suffix
Description Description Description
1 (lb./kg.) 2 (lb./kg.) 3
P Parallel-groove clamps NEMA Heavy Duty B bracket Blank No option (may not be
0.33/0.15 B 2.84/1.29
E Small eyebolts for crossarm (11/2" bolt) used with Z in Option 2)
0.16 /0.07
L Large eyebolts 0.31/0.14 Extended type bracket for M Mechanical Assist Fuse-
X crossarm (Horizontal section is 3.75/1.70 holder (may not be used
R Lower PG Clamp
Rotated 90
0.33/0.15
25/8" longer than Type B bracket) with Blank in Option 2)
D D-shape bracket (pole) 7.67/3.48 Fargo cutout cover
Must specify one selection for Option 1. No bracket (must be used with M F
Z (may not be used with
in Option 3) Blank in Option 2)
Blank No bracket (cannot use with M in
Option 3) Anti- corrosion stainless
S
steel/copper alloy cutout
V Easy-On bracket (Height: 4 8" to
1
2.9/1.32
5532", Width: 234" to 4")

Phone: 573-682-5521 Email: hpsliterature@hubbell.com Web: hubbellpowersystems.com


Page 10 October 2015
Type C LOADBREAK Cutout
with Arc Chute type interrupter
15 kv 15/27 kV20/34.5 kV
Application
The Type C Loadbreak Cutout is available for application on
15, 25 and 35 kV distribution systems. The addition of the
arc chute expands the flexibility of the Chance protective
devices family by providing loadbreak capability for cutouts
and disconnect solid blade units. The loadbreak cutout pro-
vides short circuit protection to utility lines with the added
feature of a loadbreaking function.
The loadbreak cutout is applicable for transformer and
capacitor bank switching or line sectionalizing. Loadbreak
cutouts provide protection from overloads that just melt the
fuselink through the maximum interrupt capacity of the
fuseholder. They also provide loadbreak capability through
300 amperes.

Design
All design features and most components of the loadbreak
unit are identical to those incorporated in the Type C stan-
dard cutout. The loadbreak portion of the Type C Loadbreak
cutout is a heavy duty, reliable load interrupter that provides
a positive visible loadbreak. A common loadbreak mounting
assembly will accept the Chance Type C 100 amp and 200
amp loadbreak fuseholders or a 300 amp loadbreak discon-
nect blade. The Type C LOADBREAK fuseholder is not de-
signed to be interchangeable with any other manufacturers
cutout.

Ratings/Specifications
The 15kV Type C loadbreak cutout has a maximum design
voltage rating of 15kV. There are no voltage restrictions on
applicaton to grounded wye, ungrounded wye, or delta sys-
tems having maximum operating voltages (line to line) equal
to or less than the cutout maximum design voltage rating.
The 15/27 and 20/34.5 kV Type C loadbreak cutouts have
maximum design slant voltage ratings. These cutouts are
to be used on systems which have phase-to-ground voltages
no greater than the value listed to the left of the slant (/)
and which have phase-to-phase voltages no greater than the
value listed to the right of the slant.
Fuseholders and mounting assemblies from other manu-
facturers' loadbreak cutouts are not interchangeable with
Chance loadbreak cutouts. Likewise, Chance fuseholders
and mountings are not interchangeable with other manu-
facturers' loadbreak cutouts.

Operation
The self-contained loadbreak device enables the lineman to Dimensions
interrupt load current by means of a simple hookstick opera- kV LIW (BIL) A B C D E
tion. To break the current, the lineman inserts a hookstick
into the operating ring and rapidly opens the device. Upon 251/4" 67/8" 103/4" 31/2" 255/8"
opening, a spring-loaded stainless steel blade mechanism 110 642 mm 175 mm 273 mm 89 mm 651 mm
snaps out through a gray arc chute and elongates, cools and
extinguishes the confined arc. The loadbreaking operation 281/4" 85/8" 121/2" 31/8" 307/8"
is independent of the operating speed of the lineman. The 125 719 mm 219 mm 318 mm 79 mm 784 mm
fuse remains undamaged. No special or portable tools are
required to operate the unit. In the open position, the fuse- 281/4" 85/8" 121/2" 31/8" 307/8"
holder or blade hangs in an approximate vertical position 150 719 mm 219 mm 318 mm 79 mm 784 mm
for the visible-break.

Phone: 573-682-5521 Email: hpsliterature@hubbell.com Web: hubbellpowersystems.com


October 2015 Page 11
All Type C Cutouts meet or exceed ANSI/NEMA specifications.

Type C LOADBREAK Cutout


with Arc Chute Interrruper
Specifications and Ordering Information See page 10A-14 for Arrester Cutout Combinations
See page 10A-15 for Accessories.
See page 10A-16 for Complete Catalog Numbering
15 kV - 110 kV LIW (BIL)RUS Listed
Leakage to
Continuous Interrupt Ground Arc
*Option Maximum Nominal & Loadbreak Number Capacity Metal to Replacement Short-
*Base suffixes Design System Current of (Asym Metal *Weight Fusetube Cap/ ening
Catalog No. below Voltage Voltage (Amps) Operations Amps) (minimum) (lb./kg.) Cap Assembly Rod
C730112 123 15 kV Thru 14.4 kV 100 200 10,000 8.7" 220 mm 19.33/8.77 P7001535P No
C730114 123 15 kV Thru 14.4 kV 100 200 16,000 8.7" 220 mm 19.53/8.86 E7001767P Yes
C730143 123 15 kV Thru 14.4 kV 200 200 12,000 8.7" 220 mm 20.13/9.13 E7002146P Yes
C730133 123 15 kV Thru 14.4 kV 300 50 12,000** 8.7" 220 mm 19.63/8.90 P7001535P N/A

15 kV, 110 kV LIW (BIL)


15/27 kV,
125 kV
LIW (BIL)


20/34.5 kV,
150 kV
LIW (BIL)
15/27 kV -125 kV LIW (BIL) RUS Listed
C730211 123 15/27 kV No 100 200 8,000 12.6" 320 mm 21.93 / 9.95 P7001535P No
C730213 123 15/27 kV Restrictions 100 200 12,000 12.6" 320 mm 22.13/10.04 E7001768P Yes
C730242 123 15/27 kV thru 200 200 10,000 12.6" 320 mm 22.83/10.36 E7002479P Yes
C730243 123 15/27 kV 14.4 kV; 20.8 200 200 12,000 12.6" 320 mm 22.83/10.36 PSE7002706 Yes
thru 24.9 kV
C730233 123 15/27 kV 300 50 12,000* 12.6" 320 mm 22.33/10.13 P7001535P N/A

20/34.5 kV -150 kV LIW (BIL)RUS Listed


C730311 123 20/34.5 kV No 100 100 8,000 17.3" 440 mm 27.73/12.58 P7001535P No
Restrictions
thru
C730313 123 20/34.5 kV 14.4 kV; 20.8 100 100 12,000* 17.3" 440 mm 27.93/12.67 E7001768P Yes
thru 34.5 kV
**Momentary ratingSolid blade
Must use removable buttonhead fuse links. *Adjust total weight when selecting Options below.

For application on single-phase to neutral circuits with phase-to-ground voltages not exceeding the value to the left of the slant; and
for application on three-phase solidly-grounded-wye systems with solidly-grounded loads with line-to-line voltages not exceeding the
value to the right of the slant.
*Option Suffix 1 *Option Suffix 2 *Option Suffix 3
Terminal Variations Bracket Variations Mechanical Assist Fuseholder
Suffix *Weight Suffix *Weight Suffix
Description Description Description
1 (lb./kg.) 2 (lb./kg.) 3
P Parallel-groove clamps 0.33/0.15 NEMA Heavy Duty B bracket Blank No option (may not be
B 2.84/1.29
E Small eyebolts 0.16 /0.07 for crossarm (11/2" bolt) used with Z in Option 2)
L Large eyebolts 0.31/0.14 Extended type bracket for M Mechanical Assist Fuse-
X crossarm (Horizontal section is 3.75/1.70 holder (may not be used
R Lower PG Clamp
Rotated 90
0.33/0.15
25/8" longer than Type B bracket) with Blank in Option 2)
D D-shape bracket (pole) 7.67/3.48 Fargo cutout cover (may
Must specify one selection for Option 1. F
Z No bracket (must be used with M not be used with Blank
in Option 3) in Option 2)
Blank No bracket (cannot use with M in
Option 3) S Anti- corrosion stainless
V Easy-On bracket (Height: 418" to 2.9/1.32 steel/copper alloy cutout
5532", Width: 234" to 4")

Phone: 573-682-5521 Email: hpsliterature@hubbell.com Web: hubbellpowersystems.com


Page 12 October 2015
Type C
LOADBREAK Cutout
Fuseholders and Mounting Assemblies
15 kV - 110 kV LIW (BIL)
Cutout Base Fuseholder/ Mounting Mounting
Blade Catalog Fuse Holder/ Assembly Base
Catalog Assembly Weight
Number Blade Weight Catalog Number
Number
C730112 T730112T 3.3 lb. 1.5 kg.
C730114 T730114T 3.5 lb. 1.6 kg. T7301MM
C730143 T730143T 18.6 lb. 8.4 kg.
4.1 lb. 1.9 kg.
C730133 T730133T 3.6 lb. 1.6 kg.

15/27 kV - 125 kV LIW (BIL) 100A 200A 300A


C730211 T730211T 3.6 lb. 1.6 kg
C730213 T730213T 3.8 lb. 1.7 kg
C730242 T730242T 4.4 lb. 2.0 kg T7302MM 20.8 lb 9.4 kg
C730243 T730243T 4.4 lb. 2.0 kg
C730233 T730342T 4.0 lb. 1.8 kg

20/34.5 kV - 150 kV LIW (BIL)


C730311 T730311T 3.6 lb. 1.6 kg
T7303MM 26.6 lb 12.1 kg
C730313 T730313T 3.8 lb. 1.7 kg

Replacement Arc Chute Interrupter: Catalog No. T7300080 (1.2 lb. / 0.54 kg.) 15 kV T7301MMPB

100A 200A 300A


Fuseholders Blade 15/27 kV T7302MMPB 20/34.5 kV T7303MMPB

Phone: 573-682-5521 Email: hpsliterature@hubbell.com Web: hubbellpowersystems.com


October 2015 Page 13
Type C Cutout-Arrester Combinations
Over-the-Arm Type only
Cutout-Arrester
Dimensions
13"
(330 mm)

kV LIW (BIL) E G
110 22" (559 mm) 233/4" (603 mm)
125 263/4" (679 mm) 251/2" (648 mm)
15 kV cutout with direct-connected Ohio Brass large- 150 263/4" (679 mm) 251/2" (648 mm)
block, MOV, polymer 9 kV lightning arrester 170 321/2" (826 mm) 28" (711 mm)

Advantages of combination high performance for the combinations.


Chance cutout-arrester combinations cost less than the total These units include Chance cutouts fitted with only Ohio
cost of separately purchased components. The combination Brass MOV arresters, superseding previous silicon-carbide
units install faster, more economically and take up less space units. For easy conversion to the new arrester designation
in storage, transit and service. Each combined unit takes system, refer to the Cutout Cross-Reference Guide, Bul-
up a minimum of space on the crossarm and has a favorable letin 10-0203.
weight distribution for minimal off-center loading. The field-
proven quality of both cutout and arrester assure consistent
Arrester Manufacturer

Ordering Information
Operating
MCOV Duty Cycle

Metal Oxide Varister (MOV)


To specify a Cutout-Arrester Combination:
Design
1. Select a two-letter designation for the appropriate arrester
Housing
Connection

Polymer
from the shaded section of the Table at left.
kV Rating

Arrester
Method

125 & kV LIW (BIL) 2. Substitute the two letters for the 0 in the Base Catalog
110 150
150 for Cutout No. for the appropriate Cutout listed on page 6, 10 or 12.
9 10 18 27 kV Rating
Small Block
Normal Duty Direct DL DM DN DP
Ohio Brass

5 kA
Large Block
Heavy Duty Direct EL EM EN EP
10 kA

Riser
Pole Direct FL FM FN FP

Phone: 573-682-5521 Email: hpsliterature@hubbell.com Web: hubbellpowersystems.com


Page 14 October 2015
Accessories
Terminal Connectors
Cat. No. Description Wt. (lb./kg.) Min. Order Qty.
T7001325 Parallel-Groove Clamp, tin-plated bronze for No. 6 sol. thru 4/0 ACSR or 250 kcmil stranded 0.33 / 0.15 10
T7001326 Small Eyebolt for No. 8 solid thru 2/0 stranded 0.16 / 0.07 10
T7001327 Large Eyebolt for No. 6 solid thru 4/0 ACSR or 250 kcmil stranded 0.40 / 0.14 10
Mounting Brackets
C2060283 NEMA Heavy Duty B Bracket with 11/2" captive bolt for crossarm mounting 2.84 / 1.29
C2060280 Extended Crossarm Bracket (Horizontal section is 25/8" longer than NEMA B bracket) 3.75 / 1.70
C2060299 D Pole Mounting Bracket 7.67 / 3.48
C2060632 Cutout/Arrester Bracket complete with carriage bolts and backstrap 4.00 / 1.81
PSC2060887 "V" Easy-On bracket (Height: 418" to 5532", Width: 234" to 4") 2.9 / 1.32

Mounting Bracket Dimensions

V
EASY-ON
BRACKET 8.2 IN
208 MM

2.6 IN
67 MM

Fargo Cutout Cover Fastener installation locations


(2 fasteners per assembly)
ONE PIECE WILDLIFE PROTECTOR

Available as an Option on Standard and Linkbreak Type C-Porcelain Cutouts


(see pages 10A-6 and 10A-10), Cover also may be ordered as a separate line
item as Catalog No. CC101. Material: Proprietary low track vinyl that is UV
stabilized for long-term performance. Gray color.

Designed to provide protection for cutouts from accidental contact by squir-


rels, birds or other wildlife.

Universal one-piece design for easy installation or retrofit. Fits Chance 15


kV Standard and Linkbreak Cutouts, both Polymer and Porcelain types.

Universal Cutout Tool


Ideal for Standard and Linkbreak 100 amp fuse holders (ABB,
Chance, S&C) to easily lift out, place, *open and close. Inverted,
secure method also fits Chance Electronic Sectionalizers.

Cat. No. PSC4033484 (Wt. 4 oz.) See Tools Catalog Section 2100.
*When opening a cutout, follow all work rules and OSHA regula-
tions. Not for use with Loadbreak cutouts.

Phone: 573-682-5521 Email: hpsliterature@hubbell.com Web: hubbellpowersystems.com


October 2015 Page 15
Type C Cutouts
Catalog Numbering System
Position 6 - Type C Cutout - kV Rating Position 11, 12 ,13
Standard Linkbreak Loadbreak Blank = No option (may not be used with Z in position 10)
No. Bil kV
100A 200A 300A 100A 100A 200A 300A M = Mechanical Assist Fuseholder (may not be used with Blank in position 10)*
1 110 15 15 15 15 15 15 15 S = Stainless Option*
F = Add Cutout Cover
2 125 27 27 27 15/27 15/27 15/27 15/27
*We recommend ordering option M and S together
3 150 27 27 27 22/36.4 20/24.5
6 170 36 36 36 22/36.4
7 170 36 36 36
1 represents 220 mm Creep Insulator Assembly
2 represents 320 mm Creep Insulator Assembly
3 represents 440 mm Creep Insulator Assembly Position 10 - Bracket Variations
6 represents 660 mm Creep Insulator Assembly
7 represents 720 mm Creep Insulator Assembly
B = NEMA Heavy Duty B bracket for crossarm (1-1/2 bolt)
X = Extended type bracket for crossarm (Horizontal section is 2-5/8
Position 3 - Kind longer than type B bracket)
D = D-shape bracket (pole)
1 = Standard
V = Easy on bracket
2 = Linkbreak
Z = No Bracket (must be used with M in position 11)
3 = Loadbreak
Blank = No bracket (cannot use with M in position 11)

C 7 3 4 5 6 7 8 9 10 11 12 13

Position 4,5 Position 7 - Continuous Current Position 8 - Interrupting or Position 9 - Terminal


1 = 100 Amps (Accepts 1 - 100 Amp links) Momentary Current (Amps) Variations (Tin Plated)
O - No Arrester
3 = 300 Amps solid blade 1 = 8,000 P = Parallel-groove clamps
For cutout arrester
4 = 200 Amps (Accepts 140-200 Amp 2 = 10,000 E = Small eyebolts
combinations, see below for
two letter arrester codes. links) 3 = 12,000 (Must use removable L = Large eyebolts
M = Mounting assembly only buttonhead links) R = 90 deg.
4 = 16,000 (Must use removable T = Fuseholder only (enter T
buttonhead links) in position 1 and leave blank
M = Mounting assembly only positions 10 & 11)
Metal Oxide Varister Operating
Arrester Manufacturer

(MOV) Design
Polymer Housing
MCOV Duty Cycle

Connection

125 kV LIW (BIL)


kV Rating

110 & 150


Arrester
Method

150 for Cutout


9 10 18 27 kV Rating
Small Block
Normal Duty Direct DL DM DN DP
5 kA
Ohio Brass

Large Block
Heavy Duty Direct EL EM EN EP
10 kA
Riser
Pole Direct FL FM FN FP

Phone: 573-682-5521 Email: hpsliterature@hubbell.com Web: hubbellpowersystems.com


Page 16 October 2015
NOTES

Phone: 573-682-5521 Email: hpsliterature@hubbell.com Web: hubbellpowersystems.com


October 2015 Page 17
NOTES

Phone: 573-682-5521 Email: hpsliterature@hubbell.com Web: hubbellpowersystems.com


Page 18 October 2015
NOTES

Phone: 573-682-5521 Email: hpsliterature@hubbell.com Web: hubbellpowersystems.com


October 2015 Page 19
8100 Churchill Avenue Leeds, Alabama 35094 (205) 699-0840

NOTICE: For the latest revision of our Catalog and Literature, click here or visit our web site: www.hubbellpowersystems.com

NOTE: Hubbell has a policy of continuous product improvement. Please visit hubbellpowersystems.com to
confirm current design specifications. Copyright 2015 Hubbell Incorporated

NEVER COMPROMISE
www.hubbellpowersystems.com
Phone: 573-682-5521 Email: hpsliterature@hubbell.com Web: hubbellpowersystems.com
Page 20 October 2015 Catalog 10A October 2015

You might also like