You are on page 1of 7

S

LOCAL EXISTENTE

M
kw

CAJA DE 3 Va a alimentador del


POSTE EXISTENTE MEDIDORES
ANDEN
operador de red en
AE306-1

en cable cu 3X6+8 AWG 15


CL 127D BIS NO 88C - 07 ml
1 varilla de 5/8"x2.44m cu
R < 25 ohmios
capacete y tensor de
acometidas
CL 127D BIS

CONTIENE: FECHA: DE::


ING. MAURICIO MOLINA
26/02/2016
CC: 79.786.381
MAT. CN205 - 33470
PLANTA 101 1 7
ESCALA:

FIRMA: DIBUJO: 1:75


______________________________ ING. MAURICIO MOLINA

ARCHIVO:
PL-ELECTRICO
S

S S2

S
S

CONTIENE: FECHA: DE::


ING. MAURICIO MOLINA
PLANTA NIVEL 2 AP 26/02/2016
CC: 79.786.381
MAT. CN205 - 33470 201 2 7
ESCALA:

FIRMA: DIBUJO: 1:50


______________________________ ING. MAURICIO MOLINA

ARCHIVO:
PL-ELECTRICO
SS

S2

CONTIENE: FECHA: DE::


ING. MAURICIO MOLINA
PLANTA NIVEL 3 AP 26/02/2016
CC: 79.786.381
MAT. CN205 - 33470 301 3 7
ESCALA:

FIRMA: DIBUJO: 1:50


______________________________ ING. MAURICIO MOLINA

ARCHIVO:
PL-ELECTRICO
CONVENCIONES

1. LA ALTURA DE TOMAS DE :

-LAVADORA Y NEVERA A 0.80m


-TOMAS GENERALES 0,30m NIVEL DEL PISO
ACABADO.

2, ALTURA DE INTERRUPTORES:
-TODOS A 1.00 m

S
S2
S2 PARA INTEMPERIE.

5. ALTURA DE TOMAS DE EXTRACTOR = 1.60M

KW
M EXCEPTO DONDE SE INDIQUE OTRO TIPO.

9. TODOS LOS CONDUCTORES SON DE CALIBRE No.12AWG,


EXCEPTO DONDE SE INDIQUE OTRO CALIBRE.

ING. MAURICIO MOLINA CONTIENE: FECHA: DE::

CONVENCIONES 26/02/2016
CC: 79.786.381
MAT. CN205 - 33470
4 7
ESCALA:
FIRMA: DIBUJO: SIN
______________________________ ING. MAURICIO MOLINA

ARCHIVO:
PL-ELECTRICO
TRANSFORMADOR EXISTENTE OPERADOR DE RED 208/120V

6 THWN CU
1" IMC
15ml
8 THWN CU

CAJA DE MEDIDORES AM-1


AE306-1

3X63A

In= 44.41A
12x2mm 208V 3F, 5H

8 8 8
8 8 8
MEDIDORES
3F
CUENTA
1F
CUENTA 1F

Kwh EXISTENTE Kwh EXISTENTE Kwh


1823115-2 2398409-1

3X50A 1X50A 1X50A

12x2mm 8 8
TIERRA 8
8 8 8
VARILLA COBRE 10 10 10
DE 5/8" x 2.40m
R < 25 OHM 5 ml 9 ml 11 ml

TABLERO

PISO 101 201 301


CARGA INSTALADA (KVA) 9 3 4 16
CARGA DEMANDADA (KVA) 9 3 4 16
CARGA DIVERSIFICADA (KVA) 9 3 4 16

CONTIENE: FECHA: DE::


ING. MAURICIO MOLINA
DIAGRAMA UNIFILAR 26/02/2016
CC: 79.786.381
MAT. CN205 - 33470
5 7
ESCALA:
FIRMA: DIBUJO: SIN
______________________________ ING. MAURICIO MOLINA

ARCHIVO:
PL-ELECTRICO
DIAGRAMA UNIFILAR ACOMETIDA

EXISTENTE 208/120V

15 ML

ARMARIO 3 MEDIDORES CAPACETE Y TUBO IMC 1" D


TC
M
AE306-1

8 CU

3X8+8 THW+10T CU 1X8+8 THW+10T CU


TUBO PVC 1" TUBO PVC 1"
POZO INSPECCIONABLE CON 5 ML 11 ML
VARILLA DE PUESTA A TIERRA
101 301

1X8+8 THW+10T CU
TUBO PVC 1"
9ML

201

TABLERO DE DISTRIBUCION DEL USUARIO

ING. MAURICIO MOLINA CONTIENE: FECHA: DE::

DIAGRAMA UNIFILAR 26/02/2016


CC: 79.786.381
MAT. CN205 - 33470 ACOMETIDA 6 7
ESCALA:
FIRMA: DIBUJO: SIN
______________________________ ING. MAURICIO MOLINA

ARCHIVO:
PL-ELECTRICO
Conductor de tierra en cobre
Tapa de concreto con desnudo calibre 8 AWG
marco electrosoldada
Marco
Ladrillo tolete
electrosoldado recocido trabado
Anclaje del marco o vaciado
Concreto 175 Kg/ en concreto
(2500 PSI)M ezcla 1:3:3 Tubo PVC 1/2"

0.60 mts
Conector
de tornillo

Corte -AA-

Varilla de tierra copper


5
8 "x2,4mts

Planta marco y tapa Planta caja y muros


Pase en ducto
PVC .

P 20mm
mortero 1:5
0.4 0.4
Muro en ladrillo
tolete recocido o vaciado
en concreto de acabado
similar al piso existente

Marco

CONTIENE: FECHA: DE::


ING. MAURICIO MOLINA
DETALLE DE PUESTA 26/02/2016
CC: 79.786.381
MAT. CN205 - 33470 A TIERRA 7 7
ESCALA:

FIRMA: DIBUJO: SIN


______________________________ ING. MAURICIO MOLINA

ARCHIVO:
PL-ELECTRICO