You are on page 1of 19

Cable Size Calculations

Calculations Based On Motor HP

Input Data Calculated Values

Motor Voltage (V L-L) 460 Operating Current (A) 7.6

Motor HP 5.00 125% Current per NEC (A) 9.5

Cable Temperature Rating (C) 75 "Zero Length" Cable Size 14 AWG

Ambient Temperature (C) 31-35 Acceptable Voltage Drop (V) 7.97

Cable Length (ft) 500 Recommended Cable Size 12 AWG


Acceptable Voltage Drop (%) 3.0% Actual Voltage Drop (V) 6.46

Actual Voltage Drop (%) 2.4%

Calculations Based On Specified Current

Input Data Calculated Values

Operating Voltage (V L-L) 400 "Zero Length" Cable Size 2 x 500 kcmil

Specified Current (A) 800.0 Acceptable Voltage Drop (V) 6.93


90
Cable Temperature Rating (C) Recommended Cable Size 2 x 500 kcmil
26-30 (std)
Ambient Temperature (C) Actual Voltage Drop (V) 6.12
Cable Length (ft) 306 Actual Voltage Drop (%) 2.7%
Acceptable Voltage Drop (%) 3.0%

Note: Data entry is only possible in areas highlighted in yellow.

Conductor ampacities are based on NEC 2008, Table 310.16 (Not more than 3 current carrying conductors
in racewary).
Conductor impedances are based on NEC 2008, Chapter 9, Table 9.

File: 357029324.xls, Sheet: CABLE Calculations 1 of 19 Print Date: 06/05/2017


Rated Currents Vs. HP and Voltage

Voltage
HP 208 230 460 575
0.50 2.4 2.2 1.1 0.9
0.75 3.5 3.2 1.6 1.3
1.00 4.6 4.2 2.1 1.7
1.50 6.6 6 3 2.4
2.00 7.5 6.8 3.4 2.7
3.00 10.6 9.6 4.8 3.9
5.00 16.7 15.2 7.6 6.1
7.50 24.2 22 11 9
10.00 30.8 28 14 11
15.00 46.2 42 21 17
20.00 59.4 54 27 22
25.00 74.8 68 34 27
30.00 88 80 40 32
40.00 114 104 52 41
50.00 143 130 65 52
60.00 169 154 77 62
75.00 211 192 96 77
100.00 273 248 124 99
125.00 343 312 156 125
150.00 396 360 180 144
200.00 528 480 240 192
250.00 #N/A #N/A 302 242
300.00 #N/A #N/A 361 289
350.00 #N/A #N/A 414 336
400.00 #N/A #N/A 477 382
450.00 #N/A #N/A 515 412
500.00 #N/A #N/A 590 472

File: 357029324.xls, Sheet: Motor Table 2 of 19 Print Date: 06/05/2017


Proj. : Date : Feb.3.010
Cable sizing
FR
Calculation : Input

Cable Data: for { Selected Cable } 3 Core 35 mm

Cable Resistance @ 20C /km 0.627


Cable Reactance @ 50 Hz /km 0.086
Cable De-rated Current A 0.027585039
Cable Length Km 0.093
Motor Full Load KW 55
Voltage V 440
Power Factor Cos 0.85
Efficiency Effy. 0.89
Sin 0.527

Results : Results

1) Calculation of Grouping Factors


a) Air temperature - Refere IEC table 52.14
b) Grouping factor - Refere IEC table 52.20
Overall derating factor = C = a x b
Motor Load current Ifl = 15 / (415 x Eff x cos x (3)^.5 )
Cable Ampacity = Ifl /C
Depending on the cable ampacity select the cable size from IEC Table 52.5

P=V*I*cos >>> I = P / V*cos ) =


Full Load Current, (IFL)= 1000 kW / 3 V cos effy. = A 95.40
Minimum no. of cable runs required = 1.1 ie 2 runs 2

2) Voltage drop calculations:


Allowable voltage drop is generally 10%

2.1) Running voltage drop


Volt Drop = 3 IFL L ( R Cos + X Sin ) 100 / n V = V 1.01
Maximum Allowable Volt Drop 2.5% Feeder to Motor (Running)

2.2) Starting voltage drop


Maximum Starting Current (6 Multiple of I FL) 6 times 6
Locked Rotor Starting Current Ist = A 572.39
Starting Power Factor St.Cos 0.3
St.Sin 0.954
Volt Drop (Starting) = 3 IST L ( R CosST + X SinST ) 100 / n V= 2.83

Maximum Allowable Volt Drop 15% Feeder to Motor (Starting)

Recommended number of cables


2 Runs of 3C 35 mm
BUS BAR CALCULATION Sq.mm 0.001550003 Sq.In
Sq.Mils = 0.00064516 Sq.mm
Cross Sectional Area Considerations and Determination INPUT
The required cross sectional area of a copper conductor for a given amperage
requirement and a temperature rise of 30 C max from ambient can be determined by Amp 800.00
the following formula:
N 2
Formula (2.7)
A = 300 x l x [1 + .075 (N - 1)] Sq. Mils = Sq. Mils 258000
Where, Sq.mm 166.5
l = curent in amperes Sq.in. 0.2580
N = number of conductors

For multiple layer bus bars, the cross sectional area calculated for each conductor should
be increased by approximately 7% to account for the decrease in heat dissipation
between conductors. This is already accounted for in formula (2.7) above.

Conductor Thickness and Width Calculations


The width calculation for a given cross sectional area can be determined by selecting an
appropriate standard thickness and using the following formula:

Formula (2.8)
conductor width in inches : w=A /t = Inch 2.774
Where,
A = cross sectional area as calculated from formula (2.7)
t = conductor thickness in inches selected from the list below

Available Standard Alloy 110 Thickness copper conductor:


0.020", 0.032", 0.040", 0.062", 0.093", 0.125", 0.187", 0.250", 0.375", 0.500", 0.750"

For a given cross sectional area and taking into consideration the space and structural
application requirements, the combination of a very thin and wide conductor, or having a
maximum w/t ratio, has the following benefits:
Inductance is minimized; formula (2.5)
Capacitance is maximized; formula (2.4)
Low characteristic impedance

Resistance
Conductor resistance is calculated from the resistivity of the conductor material and the
cross-sectional area of the conductor:
Formula (2.1)
R1 = p / A Milli / foot 0.031
Where,
p = resistivity in ohms x sq mils per foot (from table 3) ( SQmils/ ft) 8.1
A = cross sectional area in sq mils calculated from formula (2.7)

Recalculate the resistance at that temperature to check the impact on bus bar performance.
Formula (2.2)
R2 = R1 [1 + (T2-T1)] ohms/foot 0.402

Where,
R2 = resistance at new temperature in ohms/foot
R1 = resistance at 20 C in ohms/foot
T1 = 20 C 20
T2 = new operating temperature in C 50
= temperature coefficient of resistivity of the material (from table 3) 0.393
Voltage Drop Calculation
The voltage drop can be calculated using Ohm's Law

Formula (2.3)
V = R x l x l , @ 20 C Milli V 7685.58
V = R x l x l , @ 50 C V 98.299
Where,
V = voltage drop in volts in the entire conductor length
R = resistance in ohms/foot as calculated from formula (2.1) or (2.2) 0.031
l = conductor length in feet 306
l = current in amperes given by the amperage requirements of the pplication 800.00
If the voltage drop does not meet the application requirements, consider increasing the
cross sectional area to lower the conductor resistance.

Capacitance

The capacitance is directly proportional to the conductor area and the dielectric constant,
and inversely proportional to the insulation thickenss, as shown by this formla:

Formula (2.4)
C = 0.224 (k) (w) (l) / d picrofards 3879140.4223
microfards 3.8791404223

k = dielectric constant of the insulation used 8.5


w = conductor width in inches 2.774188
l = conductor length in inches 3672
d = thickness of dielectric in inches 0.005

Low inductance is a critical element for controlled and efficient operation of the bus bar as it
Inductance
prevents excessive transient overshoots. The inductance of a two layer bus bar can be
calculated by using this formula:

Formula 2.5)
L = 31.9 (l ) d / w nano Henrys 211.12
Where,
l = length of conductor in inches
d = dielectric thickness in inches
w = conductor width in inches

Characteristic Impedance
Low characteristic impedance improves the bus bar performance for AC loads, or during the
transition when load currents are switching.

Formula (2.6)
= (L/C) = Ohms 0.0073772752
Where,
L = inductance
C = capacitance
Assumption: Effective loss less conductors and dielectric
Cable Ampacity (Table 310-16)

Specified Specified
Motor HP Current Motor HP Current
with with with with
AWG or kcmil 75 75 De-rate 75 De-rate 90 90 De-rate 90 De-rate
4 x 350 1240 1165.6 1240.0 1400 1344.0 1400.0
3 x 500 1140 1071.6 1140.0 1290 1238.4 1290.0
4 x 250 1020 958.8 1020.0 1160 1113.6 1160.0
3 x 350 930 874.2 930.0 1050 1008.0 1050.0
2 x 500 760 714.4 760.0 860 825.6 860.0
3 x 4/0 690 648.6 690.0 780 748.8 780.0
2 x 350 620 582.8 620.0 700 672.0 700.0
2 x 250 510 479.4 510.0 580 556.8 580.0
2 x 4/0 460 432.4 460.0 520 499.2 520.0
500 380 357.2 380.0 430 412.8 430.0
350 310 291.4 310.0 350 336.0 350.0
250 255 239.7 255.0 290 278.4 290.0
4/0 230 216.2 230.0 260 249.6 260.0
3/0 200 188.0 200.0 225 216.0 225.0
2/0 175 164.5 175.0 195 187.2 195.0
1/0 150 141.0 150.0 170 163.2 170.0
1 130 122.2 130.0 150 144.0 150.0
2 115 108.1 115.0 130 124.8 130.0
4 85 79.9 85.0 95 91.2 95.0
6 65 61.1 65.0 75 72.0 75.0
8 50 47.0 50.0 55 52.8 55.0
10 35 32.9 35.0 40 38.4 40.0
12 25 23.5 25.0 30 28.8 30.0
14 20 18.8 20.0 25 24.0 25.0

Applied De-rate factor 0.94 1.00 0.96 1.00

De-rate factors 75 90
21-25 1.05 1.04
26-30 (std) 1.00 1.00
31-35 0.94 0.96
36-40 0.88 0.91
41-45 0.82 0.87
46-50 0.75 0.82
51-55 0.67 0.76

File: 357029324.xls, Sheet: Conductor Tables 6 of 19 Print Date: 06/05/2017


Voltage Drop
60Hz Voltage Drop Based On
Impedance Based On Operating
AWG or kcmil per 1000 ft Motor HP Current Label
4 x 350 0.0150 0.06 3.67 kcmil
3 x 500 0.0167 0.06 4.08 kcmil
4 x 250 0.0183 0.07 4.47 kcmil
3 x 350 0.0200 0.08 4.90 kcmil
2 x 500 0.0250 0.10 6.12 kcmil
3 x 4/0 0.0267 0.10 6.53 AWG
2 x 350 0.0300 0.11 7.34 kcmil
2 x 250 0.0365 0.14 8.94 kcmil
2 x 4/0 0.0400 0.15 9.79 AWG
500 0.0500 0.19 12.24 kcmil
350 0.0600 0.23 14.69 kcmil
250 0.0730 0.28 17.87 kcmil
4/0 0.0800 0.30 19.58 AWG
3/0 0.0940 0.36 23.01 AWG
2/0 0.1100 0.42 26.93 AWG
1/0 0.1300 0.49 31.82 AWG
1 0.1600 0.61 39.17 AWG
2 0.2000 0.76 48.96 AWG
4 0.3000 1.14 73.44 AWG
6 0.4500 1.71 110.16 AWG
8 0.7000 2.66 171.36 AWG
10 1.1000 4.18 269.28 AWG
12 1.7000 6.46 416.16 AWG
14 2.7000 10.26 660.96 AWG

File: 357029324.xls, Sheet: Conductor Tables 7 of 19 Print Date: 06/05/2017


FR Electrical Bus Bar Calculation

Project: Feb.4.2010
Input Data Calculation
Electrical Bus Bar Requirements:
Current Carrying : ( Amps ) 800 @ C max temp ri 30
Mechanical and Physical Requirements:
Product Configuration: Layer ( Feet 2 Rigid Epoxy Glass Board, Edge Potting;
=Shape: Planar; Dimensions: ( Inch) 24
- Conductor Length ( ft ) 306
Wide max 1.5
Application Dependent Parameters: 1. Minimum Voltage drop
2. Max. Capacitance,
3. Minimum Inductance
Materials: Copper alloy 110 , Mylar Tedlar Inner Insulation,;
Termination Method: Threaded Fastener
Mounting Method: Insulated thru holes
Humidity: High humidity environm.
Vibration: Minimum.

Design Parameter Design: Formulas and Tables Used Results


Cross Sectional Area
A= 300 x I x [1 + .075(N-1) ) =
I ( Amps ) 800 A (Sq.in.) = 0.2580
N ( layers ) 2

Conductor w= A / t =
Width(w) & t= Selected thickness values from the avai t ( inch) = 0.093
Thickness(t) Std thickness to get the maximum w / t ratio and practical to th w ( inch ) = 2.77

Thickness (t) 0 .125 0.093 0.062


Width (w) 0.776 1.043 1.564
w / t Ratio 6.20 11.21 25.23
The width requirement is 1.5 max
therefore (1.043/.09 11.22 >Max w (from above 1.56
is the max w / t ratio practical to the application

Resistance R1 = / A R1 = Milli / foot @ 20 C 0.0314


*Sqmil / foot = 8.1
R1= 0.084 Milli Ohms, as calculated above,
A Sqmil = 258000
from Table 3, = 0.393

T1 C = 20
T2 C = 50
R2 = R1 [1+ (T2-T1)] R2 = Milli / foot @ 50 C 0.402

Voltage Drop V = R x x I V= Milli volts @ 20 C 7685.58


(Conductor L.) , f 306
R1 Milli Ohm / foot 0.031
I Amps = 800
(If this voltage drop is too large ,
increase cross sectional area ) R2 = Milli / foot 0.402

V = volts @ 50 C 98.2986

C = 0.224 (k)(w)( ) / d = picofards ###


microfarads 3.8791
K (Dielectric constant Mylar tedlar) Table 4 8.5
Capacitance
w (width)= 2.77
(length)'' inch'' 3672
d (dielectric thickness) 0.005

Inductance L = 31.9 ( ) (d/w) = nano Henrys 211.12


(length)'' inch'' 3672
d (dielectric thickness) 0.005
w (width) 2.77
Wire Size Selection: Adjust Wire Size until resulting Voltage Drop is within acceptable limits.
PROJECT #

HIGH VOLTAGE WIRING TO PUMPS (EACH PUMP)


Wire Size Formula: V = 21.4 x D x I V = Voltage Drop OHM's LAW Voltage Drop = Current (Am
cmil D = distance in feet (from source to device)
I = Current in Amperes
cmil = Size of wire in Circular Mils
Yellow = input data
Green = Auto input data (by formula)

Wire_Conve
AWG
Distance (ft) 30 Feet .00
Voltage In 220 Volts 0
Load 10.00 Estimated Full Load Amperage of single device being powered 01
Wire Size 4 Gage AWG (Reduce AWG number to reduce Voltage Drop) 02
Wire Size #N/A cmil 04
Voltage Drop #N/A Volts 06
Voltage Drop #N/A Percent @ 21.4 x D x I 08
cmil
10
12
Alternate method of calculation: Minor differences are normal 14
Temperature 77 (enter 77 or 149) F 16
Resistance #N/A OHM's 18
Voltage Drop #N/A Percent @ OHM's Law 14.01

Ideal
Ideal Pump
Pump Voltage
Voltage Drop
Drop isis << 2%
2% Minimum conduit size (inches) per number of
Limit
Limit Pump
Pump Voltage
Voltage Drop
Drop toto << 4%
4% max
max Number of wires inside one con
NEC
NEC maximum
maximum permitted
permitted is
is 5%
5% AWG 2 3
.00 1-1/2" 1-1/2"
0 1-1/4" 1-1/2"
Note: All data and formulas are based on 02 1" 1-1/4"
calculations for non-insulated copper wire. 04 1" 1"
For fountain applications, insulation will have 06 3/4" 1"
little effect on voltage drop. 08 1/2" 1/2"
10 1/2" 1/2"
12 1/2" 1/2"

LOW VOLTAGE WIRING FOR LIGHTS


Distance 200 Feet
Lights 12 Total Quantity
Load, each 20 Watts
Volts 14
Current 17.14 Amperes
Wire Size 06 Gage AWG (Reduce AWG number to reduce Voltage Drop)
Wire Size 26,250 cmil
Voltage Drop 2.80 Volts
Volts at J-box 11.20
Voltage Drop 19.97% Percent @ 21.4 x D x I
cmil

PLUS:
Distance 15 Feet
Lights 1 1-Only
Load, each 20 Watts
Volts 11.20 At J-box, from above
Current 1.78 Amperes
Wire Size 06 Gage AWG
Wire Size 26,250 cmil
Voltage Drop 0.02 Volts
Volts at lights 11.18 Volts (12.24 volts will reduce bulb life by 22%)

Voltage Drop 2.82 Volts TOTAL


Voltage Drop 20.12% Percent, TOTAL

Light Lumens: -20% Under Optimum 12V Brightness (25% "Under" is acceptable. "Over" will shorten bul

"if the voltage supplied to an incandescent light bulb drops by 10%, the light output of the bulb will drop by 30%." (Glover, P
" Minus 5% Volts = 16% light loss. Minus 10% Volts = 30% light loss. Minus 15% Volts = 43% light loss (Acme Elect. Co
01, page 96) The light loss/gain (percent) is roughly a 3:1 ratio compared to voltage loss (percent). This is basicly true for Q
"capsules", with the ratio slightly higher (3.1:1) over the range of the first 1-volt drop, then tapering off to about 2.5:1. For our p
consider the 3:1 ratio, (embeded in the above formula) as valid for planning, though slightly conservative.

INSTRUCTIONS:
1. Fill in the yellow-tinted cells with known data. Enter 12-Volts as the initial transformer size. Use our "standard" for the initia
best-guess will do.

3. Adjust the "Wire Size" cell until you have found a wire size that results in an acceptable "Voltage Drop". Be sure to enter th
as shown on the "Wire Conversion Table". This is a "Lookup" table, and may yield incorrect data if the wire size is entered inco
if you enter 8 instead of 08 for the wire size, you will get the same results as entering 14 AWG wire. Very bad!

3. If the wire path will subject it to high temperatures, change the "Temperature" to 149. The resulting "Voltage Drop" will supe
Drop" that was calculated using the common formula (21.4 x D x I)/cmil

4. Wire sizes larger than #6 are a pain to deal with, and will require larger radius sweeps to bring them into the basin. If you h
can play with any of the parameters that you have input. In all cases, reducing the overall distance may allow you to decrease
standard low voltage transformer can be sized to 12, 13 or 14 volts, which allows a lot of latitude on wire size. 16 volt rem
cost about $75, and will allow a huge increase in wire distance, or you may reduce the size of the wire that will be required to d
to the device (be sure, though, that there is no more than 12.5Volts at the lights, otherwise, the life of the lamp will be dramatic
lights, lower voltage gives longer life, but also less light. For better motor longevity, try to keep the motor voltage drop less than
optimum. (There is already a 4% drop between 120V and 115V)

Interesting corollary: If the line voltage doubles (120V > 240V), the voltage drop decreases by 50%. In other words, the same
twice as far as it can carry 120V. This also means that 12Volt can only carry 10% of the distance of 120Volt, given the same g
watts) to calculate the 12V amperage, multiply the 120V amperage by 10

Think of it like this: Major power transmission lines carry something like 21,000 Volts, over long distanced in relatively small wi
true of low voltage, IE: Short distances in relatively large wires.

TRANSFORMER SIZING:
No of lights 12
Lamp voltage 12
Watts/Light 20
Total Watts 240
Volts in 120 "Primary"
Amps Draw 2.00 at control panel light timer
NEC Allownc 20% Required transformer overcapacity
Transformer 0.288 KVA (Min)
ptable limits. See hereunder Instructions

W Voltage Drop = Current (Amps) x Resistance (Ohms)

input data
Auto input data (by formula)

Wire_Conversion Table
cmil Dia (in) Ohms 77F Ohms 149
133,100 0.365 0.079 0.092
105,500 0.325 0.100 0.116
83,690 0.289 0.126 0.146
66,370 0.258 0.159 0.184
41,740 0.204 0.253 0.292
26,250 0.162 0.403 0.465
16,510 0.128 0.641 0.739
10,380 0.102 1.020 1.180
6,530 0.081 1.620 1.870
4,107 0.064 2.580 2.970
2,580 0.051 4.090 4.730
1,620 0.04 6.510 7.510
Input Err Input Err Input Err

m conduit size (inches) per number of type T or TW wires.

Number of wires inside one conduit


4 5 6 7
2" 2" 2-1/2"
2" 2" 2-1/2"
1-1/4" 1-1/2" 2"
1-1/4" 1-1/4" 1-1/2"
1" 1-1/4" 1-1/4"
3/4" 3/4" 1"
1/2" 1/2" 3/4"
1/2" 1/2" 1/2"
Author: Steve Kreck 5/29/03
ptable. "Over" will shorten bulb life)

will drop by 30%." (Glover, Pocket Ref)


3% light loss (Acme Elect. Corp. Catalog PDPD-
ent). This is basicly true for Quartz Halogen
g off to about 2.5:1. For our purposes, just
ervative.

se our "standard" for the initial wire size, or just a

ge Drop". Be sure to enter the wire sizes exactly


if the wire size is entered incorrectly. By example,
re. Very bad!

ulting "Voltage Drop" will supercede the "Voltage

g them into the basin. If you have any options, you


ce may allow you to decrease the wire size. The
tude on wire size. 16 volt remote transformers
e wire that will be required to deliver 12-Volts (+/-)
e of the lamp will be dramatically shortened). For
e motor voltage drop less than 2% below

0%. In other words, the same line can carry 240V


of 120Volt, given the same gage wire. IE, (given

distanced in relatively small wires. The opposite is


AWG Wire Sizes (see table below)
AWG: In the American Wire Gauge (AWG), diameters can be calculated by applying the formula D(AWG)=.00592 ((36-AWG)/39) inch. For the 00, 000,
0000 etc. gauges you use -1, -2, -3, which makes more sense mathematically than "double nought." This means that in American wire gage every 6
gauge decrease gives a doubling of the wire diameter, and every 3 gauge decrease doubles the wire cross sectional area. Similar to dB in signal and
power levels. An approximate form of this formula contributed by Mario Rodriguez is D = .460 * (57/64) (awg +3) or D = .460 * (0.890625)(awg +3).

Metric Wire Gauges (see table below)


Metric Gauge: In the Metric Gauge scale, the gauge is 10 times the diameter in millimeters, so a 50 gauge metric wire would be 5 mm in diameter.
Note that in AWG the diameter goes up as the gauge goes down, but for metric gauges it is the opposite. Probably because of this confusion, most of
the time metric sized wire is specified in millimeters rather than metric gauges.
Load Carrying Capacities (see table below)
The following chart is a guideline of ampacity or copper wire current carrying capacity following the Handbook of Electronic Tables and Formulas for
American Wire Gauge. As you might guess, the rated ampacities are just a rule of thumb. In careful engineering the voltage drop, insulation
temperature limit, thickness, thermal conductivity, and air convection and temperature should all be taken into account. The Maximum Amps for Power
Transmission uses the 700 circular mils per amp rule, which is very very conservative. The Maximum Amps for Chassis Wiring is also a conservative
rating, but is meant for wiring in air, and not in a bundle. For short lengths of wire, such as is used in battery packs you should trade off the resistance
and load with size, weight, and flexibility. NOTE: For installations that need to conform to the National Electrical Code, you must use their guidelines.
Contact your local electrician to find out what is legal!

Maximum Maximum Maximum frequency


Conductor Conductor amps for amps
powerfor 100% skin fordepth for
Diameter chassis transmissi solid conductor
AWG gauge Inches Diameter mm Ohms per 1000 ft. Ohms per km wiring on copper
OOOO 0.46 11.684 0.049 0.16072 380 302 125 Hz
OOO 0.4096 10.40384 0.0618 0.202704 328 239 160 Hz
OO 0.3648 9.26592 0.0779 0.255512 283 190 200 Hz
0 0.3249 8.25246 0.0983 0.322424 245 150 250 Hz
1 0.2893 7.34822 0.1239 0.406392 211 119 325 Hz
2 0.2576 6.54304 0.1563 0.512664 181 94 410 Hz
3 0.2294 5.82676 0.197 0.64616 158 75 500 Hz
4 0.2043 5.18922 0.2485 0.81508 135 60 650 Hz
5 0.1819 4.62026 0.3133 1.027624 118 47 810 Hz
6 0.162 4.1148 0.3951 1.295928 101 37 1100 Hz
7 0.1443 3.66522 0.4982 1.634096 89 30 1300 Hz
8 0.1285 3.2639 0.6282 2.060496 73 24 1650 Hz
9 0.1144 2.90576 0.7921 2.598088 64 19 2050 Hz
10 0.1019 2.58826 0.9989 3.276392 55 15 2600 Hz
11 0.0907 2.30378 1.26 4.1328 47 12 3200 Hz
12 0.0808 2.05232 1.588 5.20864 41 9.3 4150 Hz
13 0.072 1.8288 2.003 6.56984 35 7.4 5300 Hz
14 0.0641 1.62814 2.525 8.282 32 5.9 6700 Hz
15 0.0571 1.45034 3.184 10.44352 28 4.7 8250 Hz
16 0.0508 1.29032 4.016 13.17248 22 3.7 11 k Hz
17 0.0453 1.15062 5.064 16.60992 19 2.9 13 k Hz
18 0.0403 1.02362 6.385 20.9428 16 2.3 17 kHz
19 0.0359 0.91186 8.051 26.40728 14 1.8 21 kHz
20 0.032 0.8128 10.15 33.292 11 1.5 27 kHz
21 0.0285 0.7239 12.8 41.984 9 1.2 33 kHz
22 0.0254 0.64516 16.14 52.9392 7 0.92 42 kHz
23 0.0226 0.57404 20.36 66.7808 4.7 0.729 53 kHz
24 0.0201 0.51054 25.67 84.1976 3.5 0.577 68 kHz
25 0.0179 0.45466 32.37 106.1736 2.7 0.457 85 kHz
26 0.0159 0.40386 40.81 133.8568 2.2 0.361 107 kH
27 0.0142 0.36068 51.47 168.8216 1.7 0.288 130 kHz
28 0.0126 0.32004 64.9 212.872 1.4 0.226 170 kHz
29 0.0113 0.28702 81.83 268.4024 1.2 0.182 210 kHz
30 0.01 0.254 103.2 338.496 0.86 0.142 270 kHz
31 0.0089 0.22606 130.1 426.728 0.7 0.113 340 kHz
32 0.008 0.2032 164.1 538.248 0.53 0.091 430 kHz
Metric 2.0 0.00787 0.2 169.39 555.61 0.51 0.088 440 kHz
33 0.0071 0.18034 206.9 678.632 0.43 0.072 540 kHz
Metric 1.8 0.00709 0.18 207.5 680.55 0.43 0.072 540 kHz
34 0.0063 0.16002 260.9 855.752 0.33 0.056 690 kHz
Metric 1.6 0.0063 0.16002 260.9 855.752 0.33 0.056 690 kHz
35 0.0056 0.14224 329 1079.12 0.27 0.044 870 kHz
Metric 1.4 0.00551 0.14 339 1114 0.26 0.043 900 kHz
36 0.005 0.127 414.8 1360 0.21 0.035 1100 kHz
Metric 1.25 0.00492 0.125 428.2 1404 0.2 0.034 1150 kHz
37 0.0045 0.1143 523.1 1715 0.17 0.0289 1350 kHz
Metric 1.12 0.00441 0.112 533.8 1750 0.163 0.0277 1400 kHz
38 0.004 0.1016 659.6 2163 0.13 0.0228 1750 kHz
Metric 1 0.00394 0.1 670.2 2198 0.126 0.0225 1750 kHz
39 0.0035 0.0889 831.8 2728 0.11 0.0175 2250 kHz
40 0.0031 0.07874 1049 3440 0.09 0.0137 2900 kHz
Electrical Formulas

I = amperes
E = volts
KW = Kilowatts
KVA = kilovolt/amperes
HP = horsepower
% Eff. = percent efficiency
PF = power factor

To Find Single Phase Three Phase Direct Current


AMPERES when KVA is KVA X 1000 KVA X 1000
Not Applicable
known E E X 1.73

AMPERES when horsepower HP X 746 HP X 746 HP X 746


is known
E X % Eff.X PF E X 1.73 X % Eff. X PF E X % Eff.

AMPERES when kilowatts are KW X 1000 KW X 1000 KW X 1000


known
E X PF E X 1.73 X PF E
I X E X PF I X E X 1.73 X PF IXE
KILOWATTS
1000 1000 1000
KILOVOLT/ IXE I X E X 1.73
Not Applicable
AMPERES 1000 1000
I X E X % Eff. X PF I X E X 1.73 X % Eff. X PF I X E X % Eff.
HORSEPOWER
746 746 746
WATTS E X I X PF E X I X 1.73 X PF EXI
Comparison between Bus Bars & cables
AVARI PROJECT
or PVC 6350/11000 volt

Busbar Cables:
One core XLPE Insulated copper cable sizes:
RISER-A: Mr. 3L (mm2) N(mm2)
630A Copper Contact Feeder (3P4W,IP54) 93 300 300
RISER-B:
400A Copper Contact Feeder (3P4W,IP54) 92 150 150
RISER-C:
1000A Copper Contact Feeder (3P4W,IP54) 86 630 630
RISER-D:
400A Copper Contact Feeder (3P4W,IP54) 85 150 150
RISER-E:
800A Copper Contact Feeder (3P4W,IP54) 148 500 500

Result : cables / Risers Only 3LN + PE


RISER-A: 1C300mm2+1C150mm2 M 372 93
RISER-B: 1C150mm2+1C75mm2 M 368 92
RISER-C: 1C630mm2+1C185mm2 M 344 86
RISER-D: 1C150mm2+1C75mm2 M 340 85
RISER-E: 1C500mm2+1C150mm2 M 592 148

Cable tray / Risers Only mat


900x75mm wide cable tray for
m 86 1,611.59
Power
600x75mm wide cable Tray for
m 148 2,993.97
Power
450x75mm wide cable Tray for
m 93 2,398.34
Power
300x75mm wide cable Tray for
m 177 1,817.00
Power

Circuit breaker for Outlet 50 A No. 30 8,500.00


VC 6350/11000 volt

d copper cable sizes: Total Qty


PE(mm2) unit 3L+N PE
150 m 372 93

75 m 368 92

185 m 344 86

75 m 340 85

150 m 592 148

4 1 TOTAL
3 +1+1 3316 807.5 13264 807.5 14071.5 1,308,649.50
3 +1+1 807.5 400 3230 400 3630 333,960.00
3 +1+1 6033 2700 24132 2700 26832 2,307,552.00
3 +1+1 807.5 400 3230 400 3630 308,550.00
3 +1+1 6033 807 24132 807 24939 3,690,972.00
7,949,683.50
total mat install total install OHP Inc.tax Total
138,596.41 322.32 27,719.28 24,947.35 11,475.78 202,738.83 202,738.83
443,106.90 598.79 88,621.38 79,759.24 36,689.25 648,176.77 648,176.77
223,046.07 479.67 44,609.21 40,148.29 18,468.21 326,271.79 326,271.79
321,609.00 363.40 64,321.80 57,889.62 26,629.23 470,449.65 470,449.65
###

255,000.00 ### 51,000.00 45,900.00 21,114.00 373,014.00 373,014.00

9,970,334.54

25% Extra 2,492,583.63

Total 12,462,918.17

You might also like