Professional Documents
Culture Documents
Operating Voltage (V L-L) 400 "Zero Length" Cable Size 2 x 500 kcmil
Conductor ampacities are based on NEC 2008, Table 310.16 (Not more than 3 current carrying conductors
in racewary).
Conductor impedances are based on NEC 2008, Chapter 9, Table 9.
Voltage
HP 208 230 460 575
0.50 2.4 2.2 1.1 0.9
0.75 3.5 3.2 1.6 1.3
1.00 4.6 4.2 2.1 1.7
1.50 6.6 6 3 2.4
2.00 7.5 6.8 3.4 2.7
3.00 10.6 9.6 4.8 3.9
5.00 16.7 15.2 7.6 6.1
7.50 24.2 22 11 9
10.00 30.8 28 14 11
15.00 46.2 42 21 17
20.00 59.4 54 27 22
25.00 74.8 68 34 27
30.00 88 80 40 32
40.00 114 104 52 41
50.00 143 130 65 52
60.00 169 154 77 62
75.00 211 192 96 77
100.00 273 248 124 99
125.00 343 312 156 125
150.00 396 360 180 144
200.00 528 480 240 192
250.00 #N/A #N/A 302 242
300.00 #N/A #N/A 361 289
350.00 #N/A #N/A 414 336
400.00 #N/A #N/A 477 382
450.00 #N/A #N/A 515 412
500.00 #N/A #N/A 590 472
Results : Results
For multiple layer bus bars, the cross sectional area calculated for each conductor should
be increased by approximately 7% to account for the decrease in heat dissipation
between conductors. This is already accounted for in formula (2.7) above.
Formula (2.8)
conductor width in inches : w=A /t = Inch 2.774
Where,
A = cross sectional area as calculated from formula (2.7)
t = conductor thickness in inches selected from the list below
For a given cross sectional area and taking into consideration the space and structural
application requirements, the combination of a very thin and wide conductor, or having a
maximum w/t ratio, has the following benefits:
Inductance is minimized; formula (2.5)
Capacitance is maximized; formula (2.4)
Low characteristic impedance
Resistance
Conductor resistance is calculated from the resistivity of the conductor material and the
cross-sectional area of the conductor:
Formula (2.1)
R1 = p / A Milli / foot 0.031
Where,
p = resistivity in ohms x sq mils per foot (from table 3) ( SQmils/ ft) 8.1
A = cross sectional area in sq mils calculated from formula (2.7)
Recalculate the resistance at that temperature to check the impact on bus bar performance.
Formula (2.2)
R2 = R1 [1 + (T2-T1)] ohms/foot 0.402
Where,
R2 = resistance at new temperature in ohms/foot
R1 = resistance at 20 C in ohms/foot
T1 = 20 C 20
T2 = new operating temperature in C 50
= temperature coefficient of resistivity of the material (from table 3) 0.393
Voltage Drop Calculation
The voltage drop can be calculated using Ohm's Law
Formula (2.3)
V = R x l x l , @ 20 C Milli V 7685.58
V = R x l x l , @ 50 C V 98.299
Where,
V = voltage drop in volts in the entire conductor length
R = resistance in ohms/foot as calculated from formula (2.1) or (2.2) 0.031
l = conductor length in feet 306
l = current in amperes given by the amperage requirements of the pplication 800.00
If the voltage drop does not meet the application requirements, consider increasing the
cross sectional area to lower the conductor resistance.
Capacitance
The capacitance is directly proportional to the conductor area and the dielectric constant,
and inversely proportional to the insulation thickenss, as shown by this formla:
Formula (2.4)
C = 0.224 (k) (w) (l) / d picrofards 3879140.4223
microfards 3.8791404223
Low inductance is a critical element for controlled and efficient operation of the bus bar as it
Inductance
prevents excessive transient overshoots. The inductance of a two layer bus bar can be
calculated by using this formula:
Formula 2.5)
L = 31.9 (l ) d / w nano Henrys 211.12
Where,
l = length of conductor in inches
d = dielectric thickness in inches
w = conductor width in inches
Characteristic Impedance
Low characteristic impedance improves the bus bar performance for AC loads, or during the
transition when load currents are switching.
Formula (2.6)
= (L/C) = Ohms 0.0073772752
Where,
L = inductance
C = capacitance
Assumption: Effective loss less conductors and dielectric
Cable Ampacity (Table 310-16)
Specified Specified
Motor HP Current Motor HP Current
with with with with
AWG or kcmil 75 75 De-rate 75 De-rate 90 90 De-rate 90 De-rate
4 x 350 1240 1165.6 1240.0 1400 1344.0 1400.0
3 x 500 1140 1071.6 1140.0 1290 1238.4 1290.0
4 x 250 1020 958.8 1020.0 1160 1113.6 1160.0
3 x 350 930 874.2 930.0 1050 1008.0 1050.0
2 x 500 760 714.4 760.0 860 825.6 860.0
3 x 4/0 690 648.6 690.0 780 748.8 780.0
2 x 350 620 582.8 620.0 700 672.0 700.0
2 x 250 510 479.4 510.0 580 556.8 580.0
2 x 4/0 460 432.4 460.0 520 499.2 520.0
500 380 357.2 380.0 430 412.8 430.0
350 310 291.4 310.0 350 336.0 350.0
250 255 239.7 255.0 290 278.4 290.0
4/0 230 216.2 230.0 260 249.6 260.0
3/0 200 188.0 200.0 225 216.0 225.0
2/0 175 164.5 175.0 195 187.2 195.0
1/0 150 141.0 150.0 170 163.2 170.0
1 130 122.2 130.0 150 144.0 150.0
2 115 108.1 115.0 130 124.8 130.0
4 85 79.9 85.0 95 91.2 95.0
6 65 61.1 65.0 75 72.0 75.0
8 50 47.0 50.0 55 52.8 55.0
10 35 32.9 35.0 40 38.4 40.0
12 25 23.5 25.0 30 28.8 30.0
14 20 18.8 20.0 25 24.0 25.0
De-rate factors 75 90
21-25 1.05 1.04
26-30 (std) 1.00 1.00
31-35 0.94 0.96
36-40 0.88 0.91
41-45 0.82 0.87
46-50 0.75 0.82
51-55 0.67 0.76
Project: Feb.4.2010
Input Data Calculation
Electrical Bus Bar Requirements:
Current Carrying : ( Amps ) 800 @ C max temp ri 30
Mechanical and Physical Requirements:
Product Configuration: Layer ( Feet 2 Rigid Epoxy Glass Board, Edge Potting;
=Shape: Planar; Dimensions: ( Inch) 24
- Conductor Length ( ft ) 306
Wide max 1.5
Application Dependent Parameters: 1. Minimum Voltage drop
2. Max. Capacitance,
3. Minimum Inductance
Materials: Copper alloy 110 , Mylar Tedlar Inner Insulation,;
Termination Method: Threaded Fastener
Mounting Method: Insulated thru holes
Humidity: High humidity environm.
Vibration: Minimum.
Conductor w= A / t =
Width(w) & t= Selected thickness values from the avai t ( inch) = 0.093
Thickness(t) Std thickness to get the maximum w / t ratio and practical to th w ( inch ) = 2.77
T1 C = 20
T2 C = 50
R2 = R1 [1+ (T2-T1)] R2 = Milli / foot @ 50 C 0.402
V = volts @ 50 C 98.2986
Wire_Conve
AWG
Distance (ft) 30 Feet .00
Voltage In 220 Volts 0
Load 10.00 Estimated Full Load Amperage of single device being powered 01
Wire Size 4 Gage AWG (Reduce AWG number to reduce Voltage Drop) 02
Wire Size #N/A cmil 04
Voltage Drop #N/A Volts 06
Voltage Drop #N/A Percent @ 21.4 x D x I 08
cmil
10
12
Alternate method of calculation: Minor differences are normal 14
Temperature 77 (enter 77 or 149) F 16
Resistance #N/A OHM's 18
Voltage Drop #N/A Percent @ OHM's Law 14.01
Ideal
Ideal Pump
Pump Voltage
Voltage Drop
Drop isis << 2%
2% Minimum conduit size (inches) per number of
Limit
Limit Pump
Pump Voltage
Voltage Drop
Drop toto << 4%
4% max
max Number of wires inside one con
NEC
NEC maximum
maximum permitted
permitted is
is 5%
5% AWG 2 3
.00 1-1/2" 1-1/2"
0 1-1/4" 1-1/2"
Note: All data and formulas are based on 02 1" 1-1/4"
calculations for non-insulated copper wire. 04 1" 1"
For fountain applications, insulation will have 06 3/4" 1"
little effect on voltage drop. 08 1/2" 1/2"
10 1/2" 1/2"
12 1/2" 1/2"
PLUS:
Distance 15 Feet
Lights 1 1-Only
Load, each 20 Watts
Volts 11.20 At J-box, from above
Current 1.78 Amperes
Wire Size 06 Gage AWG
Wire Size 26,250 cmil
Voltage Drop 0.02 Volts
Volts at lights 11.18 Volts (12.24 volts will reduce bulb life by 22%)
Light Lumens: -20% Under Optimum 12V Brightness (25% "Under" is acceptable. "Over" will shorten bul
"if the voltage supplied to an incandescent light bulb drops by 10%, the light output of the bulb will drop by 30%." (Glover, P
" Minus 5% Volts = 16% light loss. Minus 10% Volts = 30% light loss. Minus 15% Volts = 43% light loss (Acme Elect. Co
01, page 96) The light loss/gain (percent) is roughly a 3:1 ratio compared to voltage loss (percent). This is basicly true for Q
"capsules", with the ratio slightly higher (3.1:1) over the range of the first 1-volt drop, then tapering off to about 2.5:1. For our p
consider the 3:1 ratio, (embeded in the above formula) as valid for planning, though slightly conservative.
INSTRUCTIONS:
1. Fill in the yellow-tinted cells with known data. Enter 12-Volts as the initial transformer size. Use our "standard" for the initia
best-guess will do.
3. Adjust the "Wire Size" cell until you have found a wire size that results in an acceptable "Voltage Drop". Be sure to enter th
as shown on the "Wire Conversion Table". This is a "Lookup" table, and may yield incorrect data if the wire size is entered inco
if you enter 8 instead of 08 for the wire size, you will get the same results as entering 14 AWG wire. Very bad!
3. If the wire path will subject it to high temperatures, change the "Temperature" to 149. The resulting "Voltage Drop" will supe
Drop" that was calculated using the common formula (21.4 x D x I)/cmil
4. Wire sizes larger than #6 are a pain to deal with, and will require larger radius sweeps to bring them into the basin. If you h
can play with any of the parameters that you have input. In all cases, reducing the overall distance may allow you to decrease
standard low voltage transformer can be sized to 12, 13 or 14 volts, which allows a lot of latitude on wire size. 16 volt rem
cost about $75, and will allow a huge increase in wire distance, or you may reduce the size of the wire that will be required to d
to the device (be sure, though, that there is no more than 12.5Volts at the lights, otherwise, the life of the lamp will be dramatic
lights, lower voltage gives longer life, but also less light. For better motor longevity, try to keep the motor voltage drop less than
optimum. (There is already a 4% drop between 120V and 115V)
Interesting corollary: If the line voltage doubles (120V > 240V), the voltage drop decreases by 50%. In other words, the same
twice as far as it can carry 120V. This also means that 12Volt can only carry 10% of the distance of 120Volt, given the same g
watts) to calculate the 12V amperage, multiply the 120V amperage by 10
Think of it like this: Major power transmission lines carry something like 21,000 Volts, over long distanced in relatively small wi
true of low voltage, IE: Short distances in relatively large wires.
TRANSFORMER SIZING:
No of lights 12
Lamp voltage 12
Watts/Light 20
Total Watts 240
Volts in 120 "Primary"
Amps Draw 2.00 at control panel light timer
NEC Allownc 20% Required transformer overcapacity
Transformer 0.288 KVA (Min)
ptable limits. See hereunder Instructions
input data
Auto input data (by formula)
Wire_Conversion Table
cmil Dia (in) Ohms 77F Ohms 149
133,100 0.365 0.079 0.092
105,500 0.325 0.100 0.116
83,690 0.289 0.126 0.146
66,370 0.258 0.159 0.184
41,740 0.204 0.253 0.292
26,250 0.162 0.403 0.465
16,510 0.128 0.641 0.739
10,380 0.102 1.020 1.180
6,530 0.081 1.620 1.870
4,107 0.064 2.580 2.970
2,580 0.051 4.090 4.730
1,620 0.04 6.510 7.510
Input Err Input Err Input Err
I = amperes
E = volts
KW = Kilowatts
KVA = kilovolt/amperes
HP = horsepower
% Eff. = percent efficiency
PF = power factor
Busbar Cables:
One core XLPE Insulated copper cable sizes:
RISER-A: Mr. 3L (mm2) N(mm2)
630A Copper Contact Feeder (3P4W,IP54) 93 300 300
RISER-B:
400A Copper Contact Feeder (3P4W,IP54) 92 150 150
RISER-C:
1000A Copper Contact Feeder (3P4W,IP54) 86 630 630
RISER-D:
400A Copper Contact Feeder (3P4W,IP54) 85 150 150
RISER-E:
800A Copper Contact Feeder (3P4W,IP54) 148 500 500
75 m 368 92
185 m 344 86
75 m 340 85
4 1 TOTAL
3 +1+1 3316 807.5 13264 807.5 14071.5 1,308,649.50
3 +1+1 807.5 400 3230 400 3630 333,960.00
3 +1+1 6033 2700 24132 2700 26832 2,307,552.00
3 +1+1 807.5 400 3230 400 3630 308,550.00
3 +1+1 6033 807 24132 807 24939 3,690,972.00
7,949,683.50
total mat install total install OHP Inc.tax Total
138,596.41 322.32 27,719.28 24,947.35 11,475.78 202,738.83 202,738.83
443,106.90 598.79 88,621.38 79,759.24 36,689.25 648,176.77 648,176.77
223,046.07 479.67 44,609.21 40,148.29 18,468.21 326,271.79 326,271.79
321,609.00 363.40 64,321.80 57,889.62 26,629.23 470,449.65 470,449.65
###
9,970,334.54
Total 12,462,918.17