Shawmut Design & Construction TRANSMITTAL

3 East 54th Street 8th Floor


New York NY 10022 No. TR0137
USA

PROJECT: Columbia U- SOJ Construction DATE: 02/03/2014


TO: LewisTsurumakiLewis Architects RE: HVAC Controls Package
227 W 28th St 7th Floor
New York NY 10001
USA

ATTN: Keith Greenwald JOB: 130557


WE ARE SENDING: SUBMITTED FOR: ACTION TAKEN:
Shop Drawings Approval Approved as Submitted
Letter Your Use Approved as Noted
Prints As Requested Returned After Loan
Change Order Review and Comment Resubmit
Plans Submit
Samples SENT VIA: Returned
Specifications Attached Separate Cover Returned for Corrections
Other: Due Date: 02/10/2014
Submittal: Other:

Line Item Package Code Rev. Qty Date Description Status


1 Submittal 020-230000 3 02/03/2014 HVAC Controls Package For Review and
Approval

REMARKS:

CC:

Signed:
Patrick Dougherty
Columbia University
Graduate School of Journalism
Brown Institute for Media Innovation
Columbia University
2950 Broadway
New York, NY 10027

Integrated Building Systems Building


Automation and Temperature Controls:
Controls Submittal

Updated Checked
Rev Date TAC Job # Description by by
1 11/25/13 NC13N2951 Submittal FS AMP
2 1/2/14 NC13N2951 Revised to Resubmit YBS AMP
Columbia University
Graduate School of Journalism
Brown Institute for Media Innovation
Columbia University
2950 Broadway
New York, NY 10027

Controls Drawings

Schneider Electric Phone +1 201-348-9240


210 Meadowlands Parkway Fax +1 201-348-9530
Secaucus, NJ 07094 Web www.schneider-electic.com
Columbia University-
Graduate School of Journalism
Brown Institute for Media Innovation
Columbia University
2950 Broadway
New York, NY 10027

Building Automation System


H-000: Communication Riser
Schneider
Electric Job Updated Checked
Rev. Date Number Description by by
1 11/25/13 NC13N2951 Submittal FS AMP
2 1/2/14 NC13N2951 Revised to Resubmit YBS AMP
Title Page
Drawing Index:

Communication Riser
Page 1
Page 0
Architect: LTL
2950 Broadway

Contractor: Giachetti
Engineer: Buro Happold
H-000 Communication Riser

Project Number: NC13N2951


NJ/NY
Secaucus, NJ 07094
Main: (201) 348-9240
Service: 1-800-785-8637
210 Meadowlands Parkway

Job Number Columbia University - Graduate


Architect: LTL
NC13N2951 School of Journalism (BIMI)
Engineer: Buro Happold
Revision: SUBMITTAL
2950 Broadway # Change: Date:
File Name Last Saved Contractor: Giachetti 1 Record Drawing 11/25/2013
Table of 2 Revised to Resubmit 1/2/2014
1/2/2014 New York, NY 10027 Designed by: FS Date: 11/22/2013
Contents.vsd 3 These drawings and designs are the property of Schneider
Sheet Number Last Printed Software by: Date: Electric. Their use or reproduction without prior consent of
4
the company is strictly forbidden.
Title Page Checked by: AMP Date: 11/22/2013 5
0 1/2/2014
Electric. Their use or reproduction without prior consent of
Communication Riser

These drawings and designs are the property of Schneider

the company is strictly forbidden.


B3865-V B3865-V B3865-V B3865-V

11/25/2013
SE7300F5045B SE7300F5045B

1/2/2014
SE7300F5045B SE7300F5045B
VAV-M201A VAV-201AB

Date:
VAV-201B VAV-202 FCU-S1 FCU-S2 FCU-S3 FCU-S4

SUBMITTAL

Revised to Resubmit
Record Drawing
SE7300F5045B SE7300F5045B SE7300F5045B SE7300F5045B SE7300F5045B SE7300F5045B SE7300F5045B SE7300F5045B

# Change:
Revision:
FCU-N4 FCU-N3 FCU-N2 FCU-N1 FCU-E3 FCU-E2 FCU-E1 FCU-S5

1
2
3
4
5
Date: 11/22/2013

11/22/2013
200 Level

Buro Happold

Date:
Date:
Ethernet Tie into Existing BMS Network Bacnet MS-TP

Giachetti

AMP
Ethernet Tie into Existing Fire Alarm System

LTL

FS Designed by:
Software by:
Checked by:
AHU-1E Panel

Contractor:
Engineer:
Located in Level 100

Architect:
30X36X10

Columbia University - Graduate


School of Journalism (BIMI)

Communication Riser
New York, NY 10027
2950 Broadway
B3865-V B3865-V B3865-V B3865-V SE7300F5045B
bCX-CR-8-INF b3920-1E
b3920 VAV-201N VAV-201S VAV-201C VAV-M201C FCU-IT

100 Level

1/2/2014

1/2/2014
Last Printed
Last Saved
NC13N2951
Job Number
Note: Coordinate thermostat Legend:

Riser Submittal
Comm
placements with landlord and

1.vsd
Sheet Number
BACnet MS/TP

File Name

1
construction manager

OF
H-000

Rev
Ethernet

1
Columbia University-
Graduate School of Journalism
Brown Institute for Media Innovation
Columbia University
2950 Broadway
New York, NY 10027

Building Automation System


H-001: Air Handling Unit
Schneider
Electric Job Updated Checked
Rev. Date Number Description by by
1 11/25/13 NC13N2951 Submittal FS AMP
2 1/2/14 NC13N2951 Revised to Resubmit YBS AMP
Legend

AHU Flow
Title Page

Panel Layout
AHU Wiring 2
AHU Wiring 1
System Sequence
Drawing Index:

Total Bill of Materials


Page 7
Page 6
Page 5
Page 4
Page 3
Page 2
Page 1
Page 0
Architect: LTL
2950 Broadway

Contractor: Giachetti
Engineer: Buro Happold
H-001 Air Handling Unit

Project Number: NC13N2951


NJ/NY
Secaucus, NJ 07094
Main: (201) 348-9240
Service: 1-800-785-8637
210 Meadowlands Parkway

Job Number Columbia University - Graduate


Architect: LTL
NC13N2951 School of Journalism (BIMI)
Engineer: Buro Happold
Revision: SUBMITTAL
2950 Broadway # Change: Date:
File Name Last Saved Contractor: Giachetti 1 Record Drawing 11/25/2013
Table of 2 Revised to Resubmit 1/2/2014
1/2/2014 New York, NY 10027 Designed by: FS Date: 11/22/2013
Contents.vsd 3 These drawings and designs are the property of Schneider
Sheet Number Last Printed Software by: Date: Electric. Their use or reproduction without prior consent of
4
the company is strictly forbidden.
Title Page Checked by: AMP Date: 11/22/2013 5
0 1/2/2014
Symbol Legend General Notes Detail Name

Electric. Their use or reproduction without prior consent of


These drawings and designs are the property of Schneider
Input/Output Blocks Damper or Valve Actuator

the company is strictly forbidden.


1. All room thermostats/sensors/controllers shall be installed at 60" above fixed floor for ADD Color 3-Letter 2-Letter 1-Letter
compliance for new installations. For replacement of existing devices, leave sufficient rolled
coil of wire above the ceiling should the device need to be moved down to meet this Black BLK BK b
SaTmp Software Object Name Brown BRN BR n
00_00 BK
CV1 requirement in the future.
24N 1 COM
UI# COM
24H RD 2 + Red RED RD r
HOT
WH Y1
INPUT
2. All sensor or thermostat pulls that are new require 1 extra conductor to be pulled as well Orange ORG OR o
Termination
from Controller Controller for future use. The shield/drain is not suitable for a conductor. Yellow YEL YL y
UI# SaTmp Designator
COM AO2 Green GRN GN g
COM 00_00
00_00 3. All panel keys will be collected daily and removed from the panels installed. These keys
Blue BLU BU u
ClgVlv Software Object Name are to be giving to the Energy Solutions Site Supervisor.
Violet VIO VL v
Termination

11/25/2013
Controller Designator Gray GRY GY a

1/2/2014
from Controller 4. All thermowells shall be filled with heat conductive compound that is provided.
UI# SaTmp
White WHT WH w

Date:
COM 00_00
5. Wiring Terminations designated as X or XX indicate information was unavailable at time Gold GLD GL d

SUBMITTAL
of submittal. Please inform Schneider Electric before making field terminations. Silver SLV SV s
Pink PNK PK p
6. Remote control devices, not in local panels, shall be accessible for adjustment and
Temperature
Temperature Temperature Temperature Temperature Temperature service - below 7' above fixed floor whenever possible or as shown on the provided
Sensor, Bulb
Sensor, Duct Probe Sensor, Immersion Sensor, Averaging Sensor, Outside Air Sensor, Room Construction prints. 1-Letter abbreviations used for color of stripe on
(Strap-On)
SaTmp HwSTmp MaTmp RmTmp DxSucTmp wire. (WH/o = White wire with orange stripe)

Revised to Resubmit
00_00 00_00 00_00 00_00 00_00 7. Only prints marked Construction are to be used during installation. If the prints are not
OaTmp

Record Drawing
UI# COM UI# COM UI# COM UI# COM UI# COM marked Construction, the installer will correct any discrepancies between prints used and
00_00
RD BK RD BK RD BK
UI# COM
RD BK RD BK
Construction at no cost to Schneider Electric.

# Change:
TS# TS# TS# TS# TS#

Revision:
RD BK
TS# 8. All new BAS controller panels shall have a dedicated 120Vac power source. This source
shall be located and marked in the electrical panel as well as on the control prints returned to
Schneider Electric for Record prints.

1
2
3
4
5
Hydronic Heating Hydronic Cooling 9. Installer responsible for maintaining existing safeties into new BAS control electrically or
Gas Heating Current Sensor Pressure Sensor Pressure Switch pnuematically connected.
Coil Coil
SaFanStat SaStP
Gas 00_00 00_00 10. See Division 23 09 15 00 for any additional information on installation standards.

Date: 11/22/2013

11/22/2013
NO COM UI# COM

Htg + - NC C
LO HI LO HI
NO COM PS1 PS1
CSR1

Wiring Legend

Buro Happold

Date:
Date:
Low Voltage (50 volts or less) control wiring for inputs and outputs shall be 18 AWG or larger rated for 600-volt service. Terminate any

Giachetti
HeatPump or Dual shields or drains for input/outputs at the controller only. See Section 4.2 for additional details.
DX Cooling Electric Heating Smoke Detector Transformer Filter
Pipe Coil

AMP
LTL
1 Stage Indicates need for conduit to be ran by installer. Distances noted on plans are approximate values.

FS
Elect FILTER
D

Designed by:
Software by:
Checked by:
+
_ SD2

Contractor:
Engineer:
X

Architect:
Se
Pri
Htg c
XFR1

Ethernet
Ethernet Wiring: Unless stated differently by the client or the Schneider Electric Site Supervisor, network cable shall meet or exceed all

Columbia University - Graduate


School of Journalism (BIMI)
requirements of Category 5 cable as specified in ANSI/TIA/EAI 568-A. No other devices other than stated in these Construction
drawings will be added to or removed from the clients Ethernet backbone or WAN.

New York, NY 10027


Chiller Boiler Cooling Tower Pump Heat Exchanger L.

2950 Broadway

Legend
MS/TP BACnet or I/Net Wiring: Wiring to be installed using 24 AWG 7/26 Bare Copper 2 conductor stranded, 7/32 drain wire, 12.5
MS/TP pF/ft @ 1 KHz nominal UL TYPE CMP/CL3P 24 AWG. Maximum length is 4000' or 110 controllers. End of Line resistor (120 1/4W)
CHILLE
R CHWP01 to be installed at both ends of network segments. All communication cabling to be installed in a daisy chain configuration, no Ts are
Boiler #1
Heat permitted. Shield on communication cable is to remain continuous and grounded only at a controller. Polarity of the wires must be
Exchanger observed. Splicing of communication cable is not permitted. Cable can be purchase through Schneider Electric using this part number:
WBAC-4-242P-OR-SP

LON or FFT-10 Wiring to be installed using Level IV network cable. Level IV network cable is 22 AWG 7/30 Bare Copper, 2 conductor
FTT-10
VFD Motor Starter 3-way Valve 2-way Valve Fan Damper stranded, with or without a 7/32 drain wire, 17 pF/ft, and impedance of 100 ohm (1-20MHz) nominal UL TYPE SUBJECT 444, CMP.

1/2/2014

1/2/2014
Last Printed
Last Saved
The same cable shall be used through out the project to avoid impedance issues. Maximum length is 4600' or 55 controllers without
use of repeater. Terminator to be installed at both ends of network segments. All LON/FFT-10 cabling to be installed in a daisy chain
See Valve Schedule D1 D1
configuration (not FTT-10A). This cable is not to run in the same conduit with power for more than 5'. Splicing of communication

NC13N2951
CV1 CV1 CV1
N.O. N.O. cable is not permitted. Cable can be purchase through Schneider Electric using this part number: WLON-3-221P-BL-BX

Job Number
VFD STARTER
A AB N.O. N.C.

File AHU-EF
B

Submittal Rev
Number
Name

7
1.vsd
L3 L2 L1 L3 L2 L1

OF
480 VAC 480 VAC

Sheet
H-001

1
Floor Plan Legend is independent, please refer to Legend on that Page
Electric. Their use or reproduction without prior consent of
Sequence of Operation

These drawings and designs are the property of Schneider

the company is strictly forbidden.


13. The outdoor air damper shall be set AT 500 cfm minimum, (controlled by local CO2 sensors,
Air Handling Unit (AHU-1E)
refer to DVC), with design values at 1000 cfm for normal operation, 2000 cfm for event
1. The BMS contractor shall provide DDC controls for complete stand-alone
operation, and 3000 cfm for air economizer. It shall be open only at occupied periods.
operation. The BMS contractor shall connect the DDC controller to the BMS
Manual override at BMS and local DDC panel shall be provided for event operation.
network for point monitoring and control from the operator interface. Provide
Flow measurement of outside air shall be provided to BMS.
one DDC controller and space sensor per system.
14. When the supply air fan is off, the outdoor air and exhaust air dampers shall
2. Supply and return air duct smoke detectors shall stop the fan upon the presence
close and the return air damper shall open. All associated discharge air dampers
of smoke through the fire alarm system.
shall close, the cooling shall be off. The heat coil valve shall be controlled to
3. Low temperature detector (freeze stat), mounted upstream of the

11/25/2013
maintain 45F plenum temperatures.

1/2/2014
cooling/heating coils, shall stop the fans when the cooling coil entering

Date:
15. Monitor differential pressures across filter and annunciate alarm when
temperature falls below 35F (adj.), for 3 minutes (adj. 0-15 minutes at time

SUBMITTAL
differentia pressure set point is exceeded.
delay relay in control panel). Chilled water valve shall close, heating valve shall
16. If the supply fan fails to operate an alarm shall be annunciated at the BMS and
open. Freeze stats shall automatically reset when temperature rises above trip
dampers shall be indexed to their normal off positions.
set point. If 3 (adj.) freeze stat shutdowns occur within 15 minutes (adj.), unit
17. The Fire Alarm System shall signal the BMS when a fire alarm is present.
shall be commended off until reset from BMS computer.
When the floor/area the fans serves is in alarm, the FAS shall shut down the

Revised to Resubmit
4. For fans greater than 2,000 cfm, provide a high discharge static pressure
fans and close all dampers. Upon fire alarm reset all fans shall sequentially start

Record Drawing
switch if dampers are located upstream of the fan and/or a low static pressure
and operate in the normal mode.
switch if dampers are located downstream of the fan to prevent mechanical

# Change:
18. Demand Ventilation controls (DCV):

Revision:
damage if a damper fails to open. The switch shall stop the fan when duct
Upon a rise in zone CO2 concentration above set-point, the minimum occupied
pressure exceeds design. The fan shall remain off until the pressure switch is
airflow set-point at the zone VAV terminal shall first be reset from the design

1
2
3
4
5
reset.
minimum up to a ventilation override maximum value, 700 ppm (adj).
5. The AHU shall be started by the BMS based upon a start time optimization
program, time of day schedule, or manual command. Upon a command to start, Upon continued call for ventilation (based on continued rise in critical zone CO2
all associated dampers shall open and prove open through damper mounted concentration with VAV terminal at ventilation override maximum setpoint,

Date: 11/22/2013

11/22/2013
limit switch then the supply and return fans shall start. The outdoor air damper then increase the AHU minimum outdoor air rate (damper position) to design
and exhaust air damper shall be closed. minimum.
6. The AHU supply fan shall start and slowly ramp up to speed control set point.
The supply fan variable speed drive shall be controlled to maintain the supply

Buro Happold

Date:
Date:
static pressure set point, as sensed at a point 2/3 downstream of the supply fan. Propeller Exhaust Fan (EF-1)

Giachetti
7. The set point temperature noted in the schedule sheet for unit operation. The 1. As the space pressure sensor increases above the set point of 0.1 / WG ( Adj)
discharge set point (adjustable) for the air handling unit is presently set at

AMP
compare to outdoor pressure, the exhaust fan shall turn on.

LTL

FS Designed by:
Software by:
Checked by:
54.1 F DB / 53.9 F WB

Contractor:
Engineer:
Architect:
8. Morning Warm-up: The system shall be indexed to morning warm-up mode if Condensate pump
the return air temperature is below 60F (adj.) during start-up. The heating coil 1. BMS Contractor shall furnish, install and wire DDC controls and connection to

Columbia University - Graduate


valve shall be controlled to maintain discharge air set point 80F (adj.). Then it the BMS.

School of Journalism (BIMI)


shall be indexed to the occupied mode. 2. Pump shall operate automatically based on the built-in sensor for the water

New York, NY 10027

System Sequence
9. Morning Cool-down: The system shall be indexed to morning cool-down mode level inside tank.

2950 Broadway
if the return air temperature is above (80F adj.) during start-up. The cooling 3. If the pump fails to operate an alarm shall be annunciated at the BMS. AHU-1E
coil valve shall be controlled to maintain discharge air set point 54F (adj.). and FCU-IT served by the condensate pump shall be shut down.
Then it shall be indexed to the occupied mode.
10. Occupied Mode: The supply fan shall run continuously. The interlinked outdoor
air damper, the return and exhaust air dampers shall move to the fixed positions.
11. Unoccupied Heating: During unoccupied periods if the space temperature falls
below the unoccupied setback set point (60F adj.) the AHU shall cycle on and
the heating coil valve shall be controlled to maintain the space temperature at

1/2/2014

1/2/2014
Last Printed
Last Saved
setpoint .
12. Unoccupied Cooling: During unoccupied periods if the space temperature rises

NC13N2951
above the unoccupied setup set point (80F adj.) the AHU shall cycle on and the

Job Number
cooling coil valve shall be controlled to maintain the space temperature at 80F

File AHU-EF

Submittal Rev
(adj).

Number
Name

7
1.vsd
OF
Sheet
H-001

2
Electric. Their use or reproduction without prior consent of
These drawings and designs are the property of Schneider
AHU FLOW DIAGRAM

the company is strictly forbidden.


Typical of 1
2 EaFan EX-DPS
(AHU-1E)
AHU-1E
IN11 RET
(EF-1)
(P-1)
N.O. COM
Outdoor Air
DPS

EXDpr
AHU-#RATmp AHU-#RACO2
AHU-1E
AHU-1E AHU-1E
Space V12 GND
IN1 RET IN6 RET PWR

11/25/2013
1/2/2014
GND XFR
24H 1
4 DmpCmd

Date:
M M GRN WHT CO2 COM PWR
Exhaust Fan TS-D CO2

SUBMITTAL
EA N.C. N.C. RA

EF-#Sts IN14 EXDpr RAFSD


CSR2
AHU-1E RET See Damper Schedule See Damper Schedule
EF-#SS NO2

Revised to Resubmit
AHU-1E COM2

Record Drawing
EF-FailAlm IN3
xPUI4-1 RET
AHU-#RADpr

# Change:
EFSpd V15

Revision:
AHU-1E
AHU-1E GND VFD
N.O. GND V13
EF-#EmgStop -

M
by FAS Contractor -

1
2
3
4
5
RADpr
2 EFDPS R2 See Damper Schedule

L1 L2 L3
120 VAC
ETD500-6
OADpr

Date: 11/22/2013

11/22/2013
AHU-#OATmp FilterDPS FilterDPS AHU-#PHCTmp 1 SaFan SF-#LoTmp AHU-#CCTmp 3 SaFan SF-#DPSHi AHU-#SaTmp AHU-#StPrs Note: Location of static
AHU-1E
AHU-1E xPUI4-1 AHU-1E AHU-1E AHU-1E AHU-1E AHU-1E AHU-1E AHU-1E pressure to be 2/3 downstream
V14 GND
IN5 RET IN2 RET IN10 RET IN2 RET IN9 RET IN3 RET IN12 RET IN4 RET IN13 RET of the supply fan.
OA-AFMS
AHU-1E
GRN WHT M IN16 RET High
NO C
Low High
NO C
Low
GRN WHT M1 L1 GRN WHT
Supply Fan
N.C. COM GRN WHT + -
TS-D DPS1 DPS1 TS-Avg LoTmp TS-Avg DPS2 TS-D StP

Buro Happold

Date:
Date:
OA N.C. SA

Giachetti
PRE-FILTER FILTER

AMP
OADpr IN15 SF-#Sts

LTL
CSR3

FS
See Damper Schedule RET AHU-1E
AFS
HWS CHWS NO3 SF-#SS

Designed by:
Software by:
Checked by:
COM3 AHU-1E

Contractor:
Engineer:
Architect:
V16 SF-#Spd
GND AHU-1E
See Valve Schedule IN4 SFSpdFdbk
AB A AB A
HWR CHWR RET xPUI4-1
See Valve Schedule

Columbia University - Graduate


CHWRVlv IN1 SF-Fail
HWRVlv

School of Journalism (BIMI)


(NC) VFD RET xPUI4-2
(NO)
- SF-#EmgStop

New York, NY 10027


AHU-#HWVlv AHU-#CHWVlv - by FAS Contractor
AHU-1E

2950 Broadway
AHU-1E
V11 GND V10 GND

AHU Flow
R1 LoTmp 1 SFDPS 3

DprCmd 4

Condensate
Pump
L3 L2 L1
Condensate Out 120 VAC

IN1 CondPmpSts
CSR4
RET XPUI4-1

RmTmp
AHU-1E STARTER AHU-1E
IN17 RET SPWR Device Qty Part Number Description Manufacturer
120 VAC ----------------------------------------------------------------------------------------------------------------------------------------------------

1/2/2014

1/2/2014
Last Printed
Last Saved
L3 L2 L1 Electrical
IN RET SPWR CO2 1 VER-CDE CO2 SENSOR DUCT Veris Industries
TS1 CSR4 1 VER-H608 CURRENT SWITCH N.O. SPLIT CORE Veris Industries
CSR1-3 3 VER-H904 VFD CURRENT SWITCH N.O. SPLIT Veris Industries

NC13N2951
DPS 1 KEL-AFS-222 .05-12IN DIFF PRESS SWITCH Cleveland Controls [AFS-222]

Job Number
DPS1 2 KEL-AFS-262 .05-2IN PRESS SWITCH Cleveland Controls [AFS-262]
DPS2 1 KEL-AFS-460 .4-12IN SPST SWITCH W/MAN RES Cleveland Controls [AFS-460]

File AHU-EF

Submittal Rev
DPS1_1 4 KEL-A-302-K STATIC PRESSURE TIP 1/4 BARB Kele [A-302-K]

Number
LoTmp 1 JON-A70HA-1 ELECTRIC TEMP CONTROL 4 WIRE Johnson Controls

Name

7
1.vsd
StP 1 KEL-M267-MR3-C DP XMTR 0-5IN WC LOW AIR Setra Sensing Solutions
TS1 1 TTS-SD-LCD-1 SMART SENSOR, LCD DISPLAY, 10K Schneider Electric [TTS-SD-LCD-1]

OF
Sheet
TS-Avg 2 ETA500-12 TEMP SENSOR AVERAGE 12' 10K T3 Schneider Electric [ETA500-12]

H-001

3
TS-D 3 ETD500-6 TEMP SENSOR DUCT WBOX 10KT3 6" Schneider Electric [ETD500-6]
AIR HANDLING UNIT 1E WIRING DETAIL 1

Electric. Their use or reproduction without prior consent of


These drawings and designs are the property of Schneider
Typical of 1

the company is strictly forbidden.


13 R1 14 X1
(AHU-1E/EF-1/P-1) 5 9 T2-1
Unit Heater
Start/Stop
T2-2
(Page 1 of 2) R1-1 Terminal blocks
AHU-1E
X1 Located in AHU-1E Exhaust Fan VFD
Schneider Electric 13 R2 14

T2-3 Exhaust Fan


AC
b3920 DIGITAL
OUTPUTS
5 9
T2-4 Start/Stop
POWER
R2-1
NC1 81
1 GND 115-120 VAC 1 COM1 80 X2
SS:UH-SS
XFR N1 2 N/- NO1 79 13 R3 14 X1 Located in AHU-1E Supply Fan VFD
1 H1 3 L/+ NC2 78
5 9 T2-5 Supply Fan

11/25/2013
2 COM2 77 X2

1/2/2014
SS:EF-#SS T2-6 Start/Stop
SERVICE NO2 76 R3-1

Date:
PORT NC3 75
3 COM3 74 X2
To: Next Controller SS:SF-#SS

SUBMITTAL
RS-485 NO3 73
13 R4 14 X1
4 + NC4 72
From: Previous Controller Condensate
Return Air + T1-1 5 - 4 COM4 71 X2 5 9 T2-11
R1:CondPSS Pump
Temperature - T1-2 6 SHLD NO4 70 T2-12
R4-1 Start/Stop
NC5 69

Heating Coil + T1-3 UNIVERSAL 5 COM5 68 X2


HWVlv:UH-HWVlv
INPUTS NO5 67 Unit Heater Hot
Temperature - T1-4 T2-9 Com
7 RET NC6 66 Water Valve
TS-D:AHU-#RATmp HWVlv:RAFSD X1 T2-10
X2 Hot

Revised to Resubmit
8 IN1 6 COM6 65 (NO)
Cooling Coil + T1-5 9 IN2 NO6 64
TS-Avg:AHU-#PHCTmp

Record Drawing
Temperature - T1-6 Off On NC7 63 X1 T2-7
10 RET IN1
7 COM7 62 FSD Cmd
TS-Avg:AHU-#CCTmp T2-8
IN2
11 IN3 NO7 61
Supply Air + T1-7

# Change:
IN3
12 IN4 NC8 60

Revision:
Temperature - T1-8 TS-D:AHU-#SaTmp IN4
8 COM8 59
IN5
13 RET NO8 58
TS-D:AHU-#OATmp IN6
14 IN5
Outside Air + T1-9

1
2
3
4
5
IN7
15 IN6 ANALOG
Temperature - T1-10 CO2:AHU-#RACO2 IN8 OUTPUTS
X2
16 RET I9 57
+ T1-11 17 IN7 9 V9 56 T2-13 B 1 Chilled Water
- T1-12 18 IN8 GND 55 X1 T2-14 R 2 Control Valve
Return Air CO2 CSR1:UH-Sts
T2-15 (NC)
24(+) T1-13 I10 54 W 3
24(-) T1-14 19 RET 10 V10 53
LoTmp:SF-#LoTmp CHWVlv:AHU-#CHWVlv
X2 X1 20 IN9 GND 52 X2

Date: 11/22/2013

11/22/2013
21 IN10 I11 51
B 1
DPS1:FilterDPS T2-16 Hot Water
Unit Heater + T1-15 Off On 11 V11 50
IN9 HWVlv:AHU-#HWVlv X1 T2-17 R 2 Control Valve
Temperature - T1-16 22 RET GND 49
DPS:EX-#DPSHi IN10 T2-18 W 3 (NO)
23 IN11 I12 48
IN11
24 IN12 12 V12 47
DPS:SF-#DPSHi IN12 Damper:EXDpr X2
Unit Heater Fan NO T1-17 GND 46
IN13 T2-19 B 1 Exhaust Air

Buro Happold
Status COM T1-18 25 RET I13 45

Date:
Date:
StP:AHU-#StPrs
26 IN13 IN14
13 V13 44 X1 T2-20 R 2 Damper
X2 IN15 Damper:AHU-#RADpr
27 IN14 GND 43 T2-21 W 3 (NC)
CSR1:EF-#Sts

Giachetti
IN16
NO T1-19 I14 42
Low Temp
COM T1-20 13 R5 14 X1 28 RET 14 V14 41 X2
CSR1:SF-#Sts Damper:OADpr

AMP
29 IN15 GND 40
B 1

LTL
T2-22 Return Air

FS
5 9 30 IN16 I15 39
AFMS:OA-AFMS X1 T2-23 R 2 Damper
R5-1 15 V15 38
Speed:EF-#Spd T2-24 W 3 (NO)
31 SPWR GND 37

Designed by:
X1

Software by:
Checked by:
A This Page

Contractor:
R6-1
R5-2 TS1:RmTmp 32 RET I16 36
X2

Engineer:
Architect:
33 IN17 16 V16 35
NO T1-21 Speed:SF-#Spd
T2-25 B 1 Outside Air
Dirty Filter Alarm SMART GND 34
COM T1-22 SENSOR X1 T2-26 R 2 Damper
T2-27 W 3 (NC)
Exhaust Fan NC T1-23 X2

Columbia University - Graduate


High DPS COM T1-24 13 R6 14 X1

School of Journalism (BIMI)


Located in AHU-1E Exhaust Fan VFD

New York, NY 10027


R6-1 T2-28 Exhaust Fan
Supply Fan NC T1-25 X2 To Expansion Modules on Next Page T2-29 VFD Speed

2950 Broadway

AHU Wiring 1
High DPS COM T1-26 13 R7 14 X1 (No field wiring required.)

5 9
Located in AHU-1E Supply Fan VFD
R7-1
A This Page B This Page T2-30 Supply Fan
R7-2 T2-31 VFD Speed

Located in AHU-1E Supply Fan VFD


X2 X1
B This Page T2-32 Supply Fan
T2-33 VFD Safety Circuit
+ T1-27 A(+) A(+)
Static Pressure X2
- T1-28 A(-) IIM-1 A(-)

1/2/2014

1/2/2014
Exhaust Fan NO T1-29

Last Printed
Last Saved
Status COM T1-30

Supply Fan NO T1-31

NC13N2951
Status COM T1-32

Job Number
AHU-1E

File AHU-EF

Submittal Rev
+ T1-33 B(+) B(+) Device Qty Part Number Description Manufacturer
Outside Air - T1-34 B(-) IIM-1 B(-)

Number
----------------------------------------------------------------------------------------------------------------------------------------------------

Name
Flow Measure +24 T1-35 X1

7
1.vsd
Panel
-24 T1-36 X2
AHU-1E 1 b3920 b3920, 16 UI, 8 DO, 8AO, 1 Sma Schneider Electric [b3920]

OF
Sheet
R1-7 7 KEL-RH2B-ULAC24V RELAY W/LIGHT 24V IDEC [RH2B-ULAC24V]

H-001

4
+24 T1-37 R1-7_1 1 KEL-SH2B-05 DPDT RELAY SOCKET DIN RAIL MTD IDEC [SH2B-05]
Room Temp - T1-38
+ T1-39
AIR HANDLING UNIT 1E WIRING DETAIL 1

Electric. Their use or reproduction without prior consent of


These drawings and designs are the property of Schneider
Typical of 1

the company is strictly forbidden.


(AHU-1E/EF-1/P-1)
(Page 2 of 2)

From main b3920 controller on previous page


(No field wiring required.)

11/25/2013
1/2/2014
Date:
Schneider Electric

SUBMITTAL
UNIVERSAL
INPUTS
xPUI4
Supply Fan NO T1-40 1 RET
CSR2:CondPmpSts
Status COM T1-41 2 IN1
3 IN2
DPS1:FilterDPS Off On
Dirty Pre-Filter NO T1-42 IN1
Alarm COM T1-43 4 RET IN2
Failure:EF-FailAlm
5 IN3 IN3
NO T1-44

Revised to Resubmit
EA Fan Failure 6 IN4 IN4
COM T1-45 Speed:SFSpdFdbk

Record Drawing
SF Speed + T1-46
Feedback - T1-47

# Change:
Revision:
xPUI4-1

1
2
3
4
5
Schneider Electric
UNIVERSAL
INPUTS
xPUI4
NO T1-48 1 RET

Date: 11/22/2013

11/22/2013
SA Fan Failure Failure:SF-Fail
COM T1-49 2 IN1
3 IN2
Off On
T1-50 IN1
Spare
T1-51 4 RET IN2
5 IN3 IN3
T1-52
Spare 6 IN4 IN4
T1-53

Buro Happold

Date:
Date:
T1-54
Spare
T1-55

Giachetti
TRANSFORMER WIRING DETAIL

AMP
Typical of 1 Unit

LTL

FS
xPUI4-2 (AHU-1E)

Designed by:
Software by:
Checked by:
Contractor:
Transformer Details

Engineer:
Architect:
120vac, Plug, b3920 controller
24vac
and 175VA field transformer. X1

Columbia University - Graduate


XMR1 X1

School of Journalism (BIMI)


CB5
120vac
X2

New York, NY 10027


GND G
Pri Sec X2
G

2950 Broadway

AHU Wiring 2
120N N N1
N
120H H
BACnet CNTRL 32N CB1

CB2 H1
Schneider Electric CB3
bCX1 CB4
ETHERNET UL Panel Details
INPUT
POWER Max Voltage: 120 vac / 60 Hz
SERVICE
G GND 24 VAC
PORT SSCR: 10 kA
XFR 24N N N/- Total FLA: 6.54 A

1/2/2014

1/2/2014
1 24H L L/+ 12-28 VDC RS-485

Last Printed
Last Saved
CB 1 = 8.00 A (MAIN) AHU-1E
SHLD S CB 2 = 5.00 A (PLUG) Device Qty Part Number Description Manufacturer
- -
CB 3 = 1.00 A (CONTROLLER) ----------------------------------------------------------------------------------------------------------------------------------------------------
From: Previous Controller
+ +
Panel
CB 4 = 2 A (120/24VAC)

NC13N2951
COMM To: Next Controller CB 5 = 8.00 A (24VAC TRANS) bCX1 1 BCX1-CR-32 BACnet CNTRL 32N Schneider Electric

Job Number
PORT1 XMR1 1 VER-X150CAA TRANSFORMR CTRL 120V/24V 150VA Veris Industries [X150CAA]
RS-232

File AHU-EF

Submittal Rev
RS-232

Number
AHU-1E-XP

Name

7
1.vsd
Device Qty Part Number Description Manufacturer
----------------------------------------------------------------------------------------------------------------------------------------------------

OF
Sheet
Panel

H-001
bCX1

5
xPUI4-1-2 2 xPUI4 XP EXP MODULE - 4 UI Schneider Electric
BCX1-CR-32
43.00 x 1.00
PANDUIT

27.00 x 1.00
27.00 x 1.00

25.00 x 1.00
T2
T1

UL Tag
1
1

50

40

36.20 x 1.00
PANDUIT

1" Free Space

13.00 x 1.00
1" Free Space

1" Free Space 1" Free Space

ON

OFF

8A
CB- 5
b3920

bCX1

PANDUIT
PANDUIT
PANDUIT

xPUI4
xPUI4

PANDUIT

24V

120V
150 VA
Panel Layout

1" Free Space 1" Free Space

ON
1" Free Space

OFF
ON

OFF
ON

OFF
1" Free Space

ON

OFF

2A 1 A 5 A 8 A
CB- 4 CB- 3 CB- 2 CB- 1
36.00 x 1.00
PANDUIT
Space Space Space Space Space Space Space
1" Free 1" Free 1" Free 1" Free 1" Free 1" Free 1" Free
4.75 x 1.00

DIN1
TDR
10.25 x 1.25
IIM-1

PANDUIT

R7 R6 R5 R4 R3 R2 R1
Space Space Space Space Space Space Space
1" Free 1" Free 1" Free 1" Free 1" Free 1" Free 1" Free

43.00 x 1.00
CP1 PANDUIT
CP1
Panel
Device
AHU-1E
Qty Part Number

1 UNM-SCH303610RC
Description

ENCL 30X36X10 RECS GRY CVR


----------------------------------------------------------------------------------------------------------------------------------------------------
Manufacturer

Unity Manufacturing

Job Number Columbia University - Graduate


Architect: LTL
NC13N2951 School of Journalism (BIMI)
Engineer: Buro Happold
Revision: SUBMITTAL
2950 Broadway # Change: Date:
H-001 Name
File AHU-EF Last Saved Contractor: Giachetti 1 Record Drawing 11/25/2013
Submittal Rev 1/2/2014 New York, NY 10027 Designed by: FS Date: 11/22/2013 2 Revised to Resubmit 1/2/2014
3 These drawings and designs are the property of Schneider
1.vsd
Sheet Number Last Printed Software by: Date: Electric. Their use or reproduction without prior consent of
4
the company is strictly forbidden.
Panel Layout Checked by: AMP Date: 11/22/2013 5
6 OF 7 1/2/2014
Electric. Their use or reproduction without prior consent of
These drawings and designs are the property of Schneider
Total Bill of Materials

the company is strictly forbidden.


AHU-1E
Device Qty Part Number Description Vendor
----------------------------------------------------------------------------------------------------------------------------------------------------

11/25/2013
Electrical

1/2/2014
CO2 1 VER-CDE CO2 SENSOR DUCT Schneider Electric

Date:
CSR4 1 VER-H608 CURRENT SWITCH N.O. SPLIT CORE Schneider Electric

SUBMITTAL
CSR1-3 3 VER-H904 VFD CURRENT SWITCH N.O. SPLIT Schneider Electric
DPS 1 KEL-AFS-222 .05-12IN DIFF PRESS SWITCH Schneider Electric
DPS1 2 KEL-AFS-262 .05-2IN PRESS SWITCH Schneider Electric
DPS2 1 KEL-AFS-460 .4-12IN SPST SWITCH W/MAN RES Schneider Electric
DPS1_1 4 KEL-A-302-K STATIC PRESSURE TIP 1/4 BARB Schneider Electric
LoTmp 1 JON-A70HA-1 ELECTRIC TEMP CONTROL 4 WIRE Schneider Electric

Revised to Resubmit
StP 1 KEL-M267-MR3-C DP XMTR 0-5IN WC LOW AIR Schneider Electric
TS1 1 TTS-SD-LCD-1 SMART SENSOR, LCD DISPLAY, 10K Schneider Electric

Record Drawing
TS-Avg 2 ETA500-12 TEMP SENSOR AVERAGE 12' 10K T3 Schneider Electric
TS-D 3 ETD500-6 TEMP SENSOR DUCT WBOX 10KT3 6" Schneider Electric

# Change:
Revision:
Panel
AHU-1E 1 b3920 b3920, 16 UI, 8 DO, 8AO, 1 Sma Schneider Electric

1
2
3
4
5
bCX1 1 BCX1-CR-32 BACnet CNTRL 32N Schneider Electric
R1-7 7 KEL-RH2B-ULAC24V RELAY W/LIGHT 24V Schneider Electric
R1-7_1 1 KEL-SH2B-05 DPDT RELAY SOCKET DIN RAIL MTD Schneider Electric
XMR1 1 VER-X150CAA TRANSFORMR CTRL 120V/24V 150VA Schneider Electric

Date: 11/22/2013

11/22/2013
AHU-1E-XP
Device Qty Part Number Description Vendor
----------------------------------------------------------------------------------------------------------------------------------------------------
Panel
xPUI4-1-2 2 xPUI4 XP EXP MODULE - 4 UI Schneider Electric

Buro Happold

Date:
Date:
Giachetti
Default

AMP
Device Qty Part Number Description Vendor

LTL

FS
----------------------------------------------------------------------------------------------------------------------------------------------------

Designed by:
Software by:
Checked by:
Contractor:
CP1 1 UNM-SCH304810RC ENCL 30X48X10 RECS GRY CVR Schneider Electric

Engineer:
Architect:
Columbia University - Graduate
School of Journalism (BIMI)

Total Bill of Materials


New York, NY 10027
2950 Broadway
1/2/2014

1/2/2014
Last Printed
Last Saved
NC13N2951
Job Number

File AHU-EF

Submittal Rev
Number
Name

7
1.vsd
OF
Sheet
H-001

7
Columbia University-
Graduate School of Journalism
Brown Institute for Media Innovation
Columbia University
2950 Broadway
New York, NY 10027

Building Automation System


H-002: Single Duct Variable Air Volume Units
Schneider
Electric Job Updated Checked
Rev. Date Number Description by by
1 11/25/13 NC13N2951 Submittal FS AMP
2 1/2/14 NC13N2951 Revised to Resubmit YBS AMP
Legend
Title Page

Total BOM
Drawing Index:

VAV System Diagram


VAV Controller I/O Wiring
Page 1

Page 4
Page 3
Page 2
Page 0
Architect: LTL
2950 Broadway

Contractor: Giachetti
Engineer: Buro Happold
H-002 Variable Air Volume Units

Project Number: NC13N2951


NJ/NY
Secaucus, NJ 07094
Main: (201) 348-9240
Service: 1-800-785-8637
210 Meadowlands Parkway

Job Number Columbia University - Graduate


Architect: LTL
NC13N2951 School of Journalism (BIMI)
Engineer: Buro Happold
Revision: SUBMITTAL
2950 Broadway # Change: Date:
File Name Last Saved Contractor: Giachetti 1 Record Drawing 11/25/2013
Table of 2 Revised to Resubmit 1/2/2014
1/2/2014 New York, NY 10027 Designed by: FS Date: 11/22/2013
Contents.vsd 3 These drawings and designs are the property of Schneider
Sheet Number Last Printed Software by: Date: Electric. Their use or reproduction without prior consent of
4
the company is strictly forbidden.
Title Page Checked by: AMP Date: 11/22/2013 5
0 1/2/2014
Symbol Legend General Notes Detail Name

Electric. Their use or reproduction without prior consent of


These drawings and designs are the property of Schneider
Input/Output Blocks Damper or Valve Actuator

the company is strictly forbidden.


1. All room thermostats/sensors/controllers shall be installed at 60" above fixed floor for ADD Color 3-Letter 2-Letter 1-Letter
compliance for new installations. For replacement of existing devices, leave sufficient rolled
coil of wire above the ceiling should the device need to be moved down to meet this Black BLK BK b
SaTmp Software Object Name Brown BRN BR n
00_00 BK
CV1 requirement in the future.
24N 1 COM
UI# COM
24H RD 2 + Red RED RD r
HOT
WH Y1
INPUT
2. All sensor or thermostat pulls that are new require 1 extra conductor to be pulled as well Orange ORG OR o
Termination
from Controller Controller for future use. The shield/drain is not suitable for a conductor. Yellow YEL YL y
UI# SaTmp Designator
COM AO2 Green GRN GN g
COM 00_00
00_00 3. All panel keys will be collected daily and removed from the panels installed. These keys
Blue BLU BU u
ClgVlv Software Object Name are to be giving to the Energy Solutions Site Supervisor.
Violet VIO VL v
Termination

11/25/2013
Controller Designator Gray GRY GY a

1/2/2014
from Controller 4. All thermowells shall be filled with heat conductive compound that is provided.
UI# SaTmp
White WHT WH w

Date:
COM 00_00
5. Wiring Terminations designated as X or XX indicate information was unavailable at time Gold GLD GL d

SUBMITTAL
of submittal. Please inform Schneider Electric before making field terminations. Silver SLV SV s
Pink PNK PK p
6. Remote control devices, not in local panels, shall be accessible for adjustment and
Temperature
Temperature Temperature Temperature Temperature Temperature service - below 7' above fixed floor whenever possible or as shown on the provided
Sensor, Bulb
Sensor, Duct Probe Sensor, Immersion Sensor, Averaging Sensor, Outside Air Sensor, Room Construction prints. 1-Letter abbreviations used for color of stripe on
(Strap-On)
SaTmp HwSTmp MaTmp RmTmp DxSucTmp wire. (WH/o = White wire with orange stripe)

Revised to Resubmit
00_00 00_00 00_00 00_00 00_00 7. Only prints marked Construction are to be used during installation. If the prints are not
OaTmp

Record Drawing
UI# COM UI# COM UI# COM UI# COM UI# COM marked Construction, the installer will correct any discrepancies between prints used and
00_00
RD BK RD BK RD BK
UI# COM
RD BK RD BK
Construction at no cost to Schneider Electric.

# Change:
TS# TS# TS# TS# TS#

Revision:
RD BK
TS# 8. All new BAS controller panels shall have a dedicated 120Vac power source. This source
shall be located and marked in the electrical panel as well as on the control prints returned to
Schneider Electric for Record prints.

1
2
3
4
5
Hydronic Heating Hydronic Cooling 9. Installer responsible for maintaining existing safeties into new BAS control electrically or
Gas Heating Current Sensor Pressure Sensor Pressure Switch pnuematically connected.
Coil Coil
SaFanStat SaStP
Gas 00_00 00_00 10. See Division 23 09 15 00 for any additional information on installation standards.

Date: 11/22/2013

11/22/2013
NO COM UI# COM

Htg + - NC C
LO HI LO HI
NO COM PS1 PS1
CSR1

Wiring Legend

Buro Happold

Date:
Date:
Low Voltage (50 volts or less) control wiring for inputs and outputs shall be 18 AWG or larger rated for 600-volt service. Terminate any

Giachetti
HeatPump or Dual shields or drains for input/outputs at the controller only. See Section 4.2 for additional details.
DX Cooling Electric Heating Smoke Detector Transformer Filter
Pipe Coil

AMP
LTL
1 Stage Indicates need for conduit to be ran by installer. Distances noted on plans are approximate values.

FS
Elect FILTER
D

Designed by:
Software by:
Checked by:
+
_ SD2

Contractor:
Engineer:
X

Architect:
Se
Pri
Htg c
XFR1

Ethernet
Ethernet Wiring: Unless stated differently by the client or the Schneider Electric Site Supervisor, network cable shall meet or exceed all

Columbia University - Graduate


School of Journalism (BIMI)
requirements of Category 5 cable as specified in ANSI/TIA/EAI 568-A. No other devices other than stated in these Construction
drawings will be added to or removed from the clients Ethernet backbone or WAN.

New York, NY 10027


Chiller Boiler Cooling Tower Pump Heat Exchanger L.

2950 Broadway

Legend
MS/TP BACnet or I/Net Wiring: Wiring to be installed using 24 AWG 7/26 Bare Copper 2 conductor stranded, 7/32 drain wire, 12.5
MS/TP pF/ft @ 1 KHz nominal UL TYPE CMP/CL3P 24 AWG. Maximum length is 4000' or 110 controllers. End of Line resistor (120 1/4W)
CHILLE
R CHWP01 to be installed at both ends of network segments. All communication cabling to be installed in a daisy chain configuration, no Ts are
Boiler #1
Heat permitted. Shield on communication cable is to remain continuous and grounded only at a controller. Polarity of the wires must be
Exchanger observed. Splicing of communication cable is not permitted. Cable can be purchase through Schneider Electric using this part number:
WBAC-4-242P-OR-SP

LON or FFT-10 Wiring to be installed using Level IV network cable. Level IV network cable is 22 AWG 7/30 Bare Copper, 2 conductor
FTT-10
VFD Motor Starter 3-way Valve 2-way Valve Fan Damper stranded, with or without a 7/32 drain wire, 17 pF/ft, and impedance of 100 ohm (1-20MHz) nominal UL TYPE SUBJECT 444, CMP.

1/2/2014

1/2/2014
Last Printed
Last Saved
The same cable shall be used through out the project to avoid impedance issues. Maximum length is 4600' or 55 controllers without
use of repeater. Terminator to be installed at both ends of network segments. All LON/FFT-10 cabling to be installed in a daisy chain
See Valve Schedule D1 D1
configuration (not FTT-10A). This cable is not to run in the same conduit with power for more than 5'. Splicing of communication

NC13N2951
CV1 CV1 CV1
N.O. N.O. cable is not permitted. Cable can be purchase through Schneider Electric using this part number: WLON-3-221P-BL-BX

Job Number
VFD STARTER
A AB N.O. N.C.
B

Submittal Rev
VAV

Number
File Name

4
1.vsd
L3 L2 L1 L3 L2 L1

OF
H-002
480 VAC 480 VAC

Sheet

1
Floor Plan Legend is independent, please refer to Legend on that Page
Electric. Their use or reproduction without prior consent of
These drawings and designs are the property of Schneider
VAV System Diagram

the company is strictly forbidden.


(Typical Of 8)
VAV-201N
VAV-201S
VAV-202
VAV-201AB
VAV-M201C
VAV-201C

11/25/2013
1/2/2014
Date:
VAV-M201A

SUBMITTAL
VAV-M201B

VAV
AFS Box
b3865-V Built in Actuator on

Revised to Resubmit
(HIGH) (LOW) VAV Controller

Record Drawing
Air from AHU Supply Air to Room

# Change:
Revision:
AFS

1
2
3
4
5
By Box MFGR RmTmp
b3865-V
IN5 RET PWR

1/4" Tubing
IN RET SPWR
TS1

Date: 11/22/2013

11/22/2013
To VP Sensor on
VAV Box Sequence of Operations VAV Controller

1. BMS Contractor shall furnish all controls to air terminal device manufacturer
for factory installation and adjustment. Coordinate factory mounting and wiring

Buro Happold

Date:
Date:
of controller, actuator, and transformer with the VAV box manufacturer. The

Giachetti
BMS contractor shall be responsible for furnishing, installing, and wiring any

AMP
controls not furnished, installed, or wired by others that are required for an

LTL

FS
operational system.

Designed by:
Software by:
Checked by:
Contractor:
Engineer:
Architect:
2. Provide one local DDC controller for each VAV box.

3. The VAV box should be indexed off when the local Air Handling Unit that the

Columbia University - Graduate


School of Journalism (BIMI)
VAV box is serving is indexed off or is in the unoccupied mode. When the

VAV System Diagram


New York, NY 10027
VAV box is indexed off the damper shall be fully closed

2950 Broadway
4. The VAV box should be indexed on when the Air Handling Unit that the VAV
box is serving is indexed on in the occupied mode. When the VAV box is
indexed on the damper shall modulate to maintain the set point of the zone
temperature.

5. The VAV box controller shall be set a min set point at 50% design value as per
schedule.

1/2/2014

1/2/2014
Last Printed
Last Saved
6. Thermostat: electronic type with temperature set-point display in Fahrenheit
and Celsius.

NC13N2951
Job Number

Submittal Rev
7. Provide sensor for ventilation air flow measurement and DCV option.

VAV

Number
VAV

File Name

4
1.vsd
Device Qty Part Number Description Manufacturer
----------------------------------------------------------------------------------------------------------------------------------------------------

OF
H-002
8. The VAV box shall annunciate an alarm to the BMS when the air flow is

Sheet
Electrical

2
TS1 8 TTS-SD-LCD-1 SMART SENSOR, LCD DISPLAY, 10K Schneider Electric
greater than 15% above design value or below the minimum airflow set point.
Electric. Their use or reproduction without prior consent of
These drawings and designs are the property of Schneider
VAV Controller I/O Diagram

the company is strictly forbidden.


b3865, 4 UI, 1 Airflow, 1 IBS

( - inch tubing to AFMS by VAV box manufacturer)


Schneider Electric
b3865-V
To: To Next
(LOW) RS-485

11/25/2013
AFS:AFS

1/2/2014
IN1
IN2
IN3
IN4
(HIGH) + 18
From: From Previous
On - 17

Date:
1 IN1 Off SHLD 16
VAV Power Supply Panel Layout

SUBMITTAL
2 IN2
3 RET SERVICE
UNIVERSAL PORT
INPUTS
4 IN3 1'-0"
5 IN4
6 RET

SPWR T1-1 7 SPWR


SMART
COM T1-2 TS1:RmTmp 8 RET
SENSOR
REF 15

Revised to Resubmit
NO T1-3 9 IN5 DIGITAL OUT5 14
OUTPUTS OUT4 13

Record Drawing
24H 10 24VAC OUT3 12
24 VAC
11 GND
From PSH40A40AB10 Panel
24N +

# Change:
Pri Sec
SEE DETAIL#1,2 on page 3

Revision:
XMR1 COM
DAMPER
GND COM 10"
- 4 1/2"

1
2
3
4
5
EN
CL

Date: 11/22/2013

11/22/2013
Buro Happold

Date:
Date:
1 PSH40A40A Transformer Wiring Detail 2 PSH40A40A Transformer Wiring Detail

Giachetti
PSH40A40AB10 Panel 1 PSH40A40AB10 Panel 2

AMP
LTL
(Located on Level 200)

FS
(Located on Level 100)

Designed by:
Software by:
Checked by:
Contractor:
Engineer:
Architect:
Columbia University - Graduate

VAV Controller I/O Wiring


School of Journalism (BIMI)

New York, NY 10027


2950 Broadway
10 10 10 10
To: VAV-201C controller To: VAV-201N controller To: VAV-M201B controller To: VAV-M201A controller
11 11 11 11

24V 24V 24V 24V


10 10 10 10
To: VAV-M201C controller GND GND To: VAV-201S controller To: VAV-202 controller GND GND To: VAV-201AB controller
11 11 11 11

120VAC 120VAC
(by others) (by others)

1/2/2014

1/2/2014
Last Printed
Last Saved
VAV

NC13N2951
Device Qty Part Number Description Manufacturer

Job Number
----------------------------------------------------------------------------------------------------------------------------------------------------
Electrical

Submittal Rev
ENCL 2 KEL-SC12106 12X10X6 SCREW COVER ENCLOSURE Kele

VAV

Number
XMR2 2 KEL-PSH40A40AB10 POWER SUPPLY Functional Devices [PSH40A40AB10]

File Name

4
1.vsd
XMR1 8 VER-X020ADA Transformer: 20 VA, 24 VAC, 1H Veris Industries

OF
H-002

Sheet
Other

3
b3865-V 8 b3865-V b3865, 4 UI, 1 Airflow, 1 IBS Schneider Electric
TS1
VAV

Other
ENCL

XMR1
XMR2
Device

b3865-V
Electrical

8
b3865-V
Qty Part Number

2 KEL-SC12106

8 VER-X020ADA
8 TTS-SD-LCD-1
2 KEL-PSH40A40AB10
Description

POWER SUPPLY
Total Bill of Materials

b3865, 4 UI, 1 Airflow, 1 IBS


Transformer: 20 VA, 24 VAC, 1H
SMART SENSOR, LCD DISPLAY, 10K
12X10X6 SCREW COVER ENCLOSURE Kele
Vendor
----------------------------------------------------------------------------------------------------------------------------------------------------

Schneider Electric

Schneider Electric
Schneider Electric
Schneider Electric

Job Number Columbia University - Graduate


Architect: LTL
NC13N2951 School of Journalism (BIMI)
Engineer: Buro Happold
Revision: SUBMITTAL
2950 Broadway # Change: Date:
File Name
H-002 VAV Last Saved Contractor: Giachetti 1 Record Drawing 11/25/2013
Submittal Rev 1/2/2014 New York, NY 10027 Designed by: FS Date: 11/22/2013 2 Revised to Resubmit 1/2/2014
3 These drawings and designs are the property of Schneider
1.vsd
Sheet Number Last Printed Software by: Date: Electric. Their use or reproduction without prior consent of
4
the company is strictly forbidden.
Total BOM Checked by: AMP Date: 11/22/2013 5
4 OF 4 1/2/2014
Columbia University-
Graduate School of Journalism
Brown Institute for Media Innovation
Columbia University
2950 Broadway
New York, NY 10027

Building Automation System


H-003: Fan Coil Units
Schneider
Electric Job Updated Checked
Rev. Date Number Description by by
1 11/25/13 NC13N2951 Submittal FS AMP
2 1/2/14 NC13N2951 Revised to Resubmit YBS AMP
Legend
Title Page

Total BOM
System Diagram
System Sequence
Drawing Index:

FCU-IT Controller Wiring


FCU-E/N/S Controller Wiring
Page 5
Page 4
Page 3
Page 2
Page 1

Page 6
Page 0
Architect: LTL
2950 Broadway

Contractor: Giachetti
H-003 Fan Coil Units

Engineer: Buro Happold

Project Number: NC13N2951


NJ/NY
Secaucus, NJ 07094
Main: (201) 348-9240
Service: 1-800-785-8637
210 Meadowlands Parkway

Job Number Columbia University - Graduate


Architect: LTL
NC13N2951 School of Journalism (BIMI)
Engineer: Buro Happold
Revision: SUBMITTAL
2950 Broadway # Change: Date:
File Name Last Saved Contractor: Giachetti 1 Record Drawing 11/25/2013
Table of 2 Revised to Resubmit 1/2/2014
1/2/2014 New York, NY 10027 Designed by: FS Date: 11/22/2013
Contents.vsd 3 These drawings and designs are the property of Schneider
Sheet Number Last Printed Software by: Date: Electric. Their use or reproduction without prior consent of
4
the company is strictly forbidden.
Title Page Checked by: AMP Date: 11/22/2013 5
0 1/2/2014
Symbol Legend General Notes Detail Name

Electric. Their use or reproduction without prior consent of


These drawings and designs are the property of Schneider
Input/Output Blocks Damper or Valve Actuator

the company is strictly forbidden.


1. All room thermostats/sensors/controllers shall be installed at 60" above fixed floor for ADD Color 3-Letter 2-Letter 1-Letter
compliance for new installations. For replacement of existing devices, leave sufficient rolled
coil of wire above the ceiling should the device need to be moved down to meet this Black BLK BK b
SaTmp Software Object Name Brown BRN BR n
00_00 BK
CV1 requirement in the future.
24N 1 COM
UI# COM
24H RD 2 + Red RED RD r
HOT
WH Y1
INPUT
2. All sensor or thermostat pulls that are new require 1 extra conductor to be pulled as well Orange ORG OR o
Termination
from Controller Controller for future use. The shield/drain is not suitable for a conductor. Yellow YEL YL y
UI# SaTmp Designator
COM AO2 Green GRN GN g
COM 00_00
00_00 3. All panel keys will be collected daily and removed from the panels installed. These keys
Blue BLU BU u
ClgVlv Software Object Name are to be giving to the Energy Solutions Site Supervisor.
Violet VIO VL v
Termination

11/25/2013
Controller Designator Gray GRY GY a

1/2/2014
from Controller 4. All thermowells shall be filled with heat conductive compound that is provided.
UI# SaTmp
White WHT WH w

Date:
COM 00_00
5. Wiring Terminations designated as X or XX indicate information was unavailable at time Gold GLD GL d

SUBMITTAL
of submittal. Please inform Schneider Electric before making field terminations. Silver SLV SV s
Pink PNK PK p
6. Remote control devices, not in local panels, shall be accessible for adjustment and
Temperature
Temperature Temperature Temperature Temperature Temperature service - below 7' above fixed floor whenever possible or as shown on the provided
Sensor, Bulb
Sensor, Duct Probe Sensor, Immersion Sensor, Averaging Sensor, Outside Air Sensor, Room Construction prints. 1-Letter abbreviations used for color of stripe on
(Strap-On)
SaTmp HwSTmp MaTmp RmTmp DxSucTmp wire. (WH/o = White wire with orange stripe)

Revised to Resubmit
00_00 00_00 00_00 00_00 00_00 7. Only prints marked Construction are to be used during installation. If the prints are not
OaTmp

Record Drawing
UI# COM UI# COM UI# COM UI# COM UI# COM marked Construction, the installer will correct any discrepancies between prints used and
00_00
RD BK RD BK RD BK
UI# COM
RD BK RD BK
Construction at no cost to Schneider Electric.

# Change:
TS# TS# TS# TS# TS#

Revision:
RD BK
TS# 8. All new BAS controller panels shall have a dedicated 120Vac power source. This source
shall be located and marked in the electrical panel as well as on the control prints returned to
Schneider Electric for Record prints.

1
2
3
4
5
Hydronic Heating Hydronic Cooling 9. Installer responsible for maintaining existing safeties into new BAS control electrically or
Gas Heating Current Sensor Pressure Sensor Pressure Switch pnuematically connected.
Coil Coil
SaFanStat SaStP
Gas 00_00 00_00 10. See Division 23 09 15 00 for any additional information on installation standards.

Date: 11/22/2013

11/22/2013
NO COM UI# COM

Htg + - NC C
LO HI LO HI
NO COM PS1 PS1
CSR1

Wiring Legend

Buro Happold

Date:
Date:
Low Voltage (50 volts or less) control wiring for inputs and outputs shall be 18 AWG or larger rated for 600-volt service. Terminate any

Giachetti
HeatPump or Dual shields or drains for input/outputs at the controller only. See Section 4.2 for additional details.
DX Cooling Electric Heating Smoke Detector Transformer Filter
Pipe Coil

AMP
LTL
1 Stage Indicates need for conduit to be ran by installer. Distances noted on plans are approximate values.

FS
Elect FILTER
D

Designed by:
Software by:
Checked by:
+
_ SD2

Contractor:
Engineer:
X

Architect:
Se
Pri
Htg c
XFR1

Ethernet
Ethernet Wiring: Unless stated differently by the client or the Schneider Electric Site Supervisor, network cable shall meet or exceed all

Columbia University - Graduate


School of Journalism (BIMI)
requirements of Category 5 cable as specified in ANSI/TIA/EAI 568-A. No other devices other than stated in these Construction
drawings will be added to or removed from the clients Ethernet backbone or WAN.

New York, NY 10027


Chiller Boiler Cooling Tower Pump Heat Exchanger L.

2950 Broadway

Legend
MS/TP BACnet or I/Net Wiring: Wiring to be installed using 24 AWG 7/26 Bare Copper 2 conductor stranded, 7/32 drain wire, 12.5
MS/TP pF/ft @ 1 KHz nominal UL TYPE CMP/CL3P 24 AWG. Maximum length is 4000' or 110 controllers. End of Line resistor (120 1/4W)
CHILLE
R CHWP01 to be installed at both ends of network segments. All communication cabling to be installed in a daisy chain configuration, no Ts are
Boiler #1
Heat permitted. Shield on communication cable is to remain continuous and grounded only at a controller. Polarity of the wires must be
Exchanger observed. Splicing of communication cable is not permitted. Cable can be purchase through Schneider Electric using this part number:
WBAC-4-242P-OR-SP

LON or FFT-10 Wiring to be installed using Level IV network cable. Level IV network cable is 22 AWG 7/30 Bare Copper, 2 conductor
FTT-10
VFD Motor Starter 3-way Valve 2-way Valve Fan Damper stranded, with or without a 7/32 drain wire, 17 pF/ft, and impedance of 100 ohm (1-20MHz) nominal UL TYPE SUBJECT 444, CMP.

1/2/2014

1/2/2014
Last Printed
Last Saved
The same cable shall be used through out the project to avoid impedance issues. Maximum length is 4600' or 55 controllers without
use of repeater. Terminator to be installed at both ends of network segments. All LON/FFT-10 cabling to be installed in a daisy chain
See Valve Schedule D1 D1
configuration (not FTT-10A). This cable is not to run in the same conduit with power for more than 5'. Splicing of communication

NC13N2951
CV1 CV1 CV1
N.O. N.O. cable is not permitted. Cable can be purchase through Schneider Electric using this part number: WLON-3-221P-BL-BX

Job Number
VFD STARTER
A AB N.O. N.C.
B

Submittal Rev
FCU

Number
File Name

5
1.vsd
L3 L2 L1 L3 L2 L1

OF
H-003
480 VAC 480 VAC

Sheet

1
Floor Plan Legend is independent, please refer to Legend on that Page
Electric. Their use or reproduction without prior consent of
Sequence of Operation

These drawings and designs are the property of Schneider

the company is strictly forbidden.


Fan Coil Unit (FCU-IT)

1. BMS Contractor shall furnish, install and wire DDC controls and connection to

11/25/2013
1/2/2014
the BMS.

Date:
SUBMITTAL
2. A space temperature sensor shall control the FCUs heating valve, cooling
valve, and fan shall cycle on.
NOTE: According to the mechanical schedule, FCU-IT only has a cooling valve.

3. Furnish a leak detector in the drip pan under the FCU. Upon detection of water

Revised to Resubmit
the FCU shall shut down and an alarm shall be annunciated to the BMS.

Record Drawing
# Change:
4. If the supply fan fails to operate an alarm shall be annunciated at the BMS and

Revision:
dampers shall be indexed to their normal off positions.

1
2
3
4
5
Date: 11/22/2013

11/22/2013
Fan Coil Unit (FCU-N/S/E)

Buro Happold

Date:
Date:
1. BMS Contractor shall furnish, install and wire DDC controls and connection to

Giachetti
the BMS and local DDC controller.

AMP
LTL

FS
2. During occupied period, wall mounted FCU temperature sensors shall control

Designed by:
Software by:
Checked by:
the FCUs heating valve, or cooling valve, and fan shall remain on to maintain

Contractor:
Engineer:
Architect:
the setpoint.
Design room temperature: 70 deg F: winter & 75 deg F: summer adjustable

Columbia University - Graduate


School of Journalism (BIMI)
3. During un-occupied period, wall mounted zoned temperature sensors shall

New York, NY 10027

System Sequence
control the FCUs heating valve, or cooling valve, and fan shall cycle on to

2950 Broadway
maintain the setpoint.
Design room temperature: 60 deg F: winter & 80 deg F: summer adjustable

4. BMS and local DDC controller shall provide manual override.

5. Furnish a leak detector in the drip pan under the FCU. Upon detection of water
the FCU shall shut down and an alarm shall be annunciated to the BMS.

1/2/2014

1/2/2014
Last Printed
Last Saved
6. If the supply fan fails to operate an alarm shall be annunciated at the BMS and
dampers shall be indexed to their normal off positions.

NC13N2951
Job Number

Submittal Rev
FCU

Number
File Name

5
1.vsd
OF
H-003

Sheet

2
FAN COIL UNIT (COOLING ONLY) FLOW DIAGRAM

Electric. Their use or reproduction without prior consent of


These drawings and designs are the property of Schneider
Typical of 1

the company is strictly forbidden.


FCU-IT

11/25/2013
1/2/2014
RA SA

Date:
SUBMITTAL
CHWRCtrlVlv BI1 FanSts
CSR1
SE7300-1 SCOM SE7300-1
AO1 BO5
BO5 FanSS
STARTER R1
BO5 SE7300-1 SE7300F5045B
See Valve Schedule CtrlVlv SpTemp
L3 L2 L1 SE7300-1
CHWR 120 VAC
A AB + -

Revised to Resubmit
(NC)

Record Drawing
CHWS
+ -
LD TS1
SE7300-1

# Change:
Revision:
BI2 SCOM PWR
24N 1
24H XFMR
NO COM PWR

1
2
3
4
5
Leak
Drip Pan
Condensate
Pump

Condensate Out

NOTE: Condensate Pump serving AHU-1E and FCU-IT

Date: 11/22/2013

11/22/2013
Wiring to b3920 shown on AHU-1E Submittal page 4

FAN COIL UNIT (COOLING & HEATING) FLOW DIAGRAM


Typical of 12

Buro Happold

Date:
Date:
(3) FCU-E

Giachetti
(4) FCU-N

AMP
LTL

FS
(5) FCU-S

Designed by:
Software by:
Checked by:
Contractor:
Engineer:
Architect:
Columbia University - Graduate
RA SA

School of Journalism (BIMI)


SE7300F5045B
SpTemp

New York, NY 10027


SE7300-2

System Diagram
HWRCtrlVlv CHWRCtrlVlv BI1 FanSts + -

2950 Broadway
CSR1
SE7300-2 SE7300-2 SCOM SE7300-2
AO2 BO5 AO1 BO5
BO5 FanSS + -
STARTER R1
BO5 SE7300-2 TS1
See Valve Schedule CtrlVlv See Valve Schedule CtrlVlv
L3 L2 L1
HWR CHWR 120 VAC
A AB A AB
(NO) (NC)
HWS CHWS

LD FCU (Cooling Only)

1/2/2014

1/2/2014
Last Printed
Last Saved
SE7300-2 Device Qty Part Number Description Manufacturer
BI2 SCOM ----------------------------------------------------------------------------------------------------------------------------------------------------
24N 1 Electrical
24H XFMR CSR1 1 VER-H600 CURRENT SWITCH N.O. SPLIT CORE Veris Industries

NC13N2951
NO COM PWR Leak 1 LT-410 SPOT LEAK DETECTOR Kele

Job Number
Leak

Submittal Rev
Drip Pan FCU (Heating & Cooling)

FCU

Number
Device Qty Part Number Description Manufacturer

File Name

5
1.vsd
----------------------------------------------------------------------------------------------------------------------------------------------------
Electrical

OF
H-003

Sheet
CSR1 12 VER-H600 CURRENT SWITCH N.O. SPLIT CORE Veris Industries

3
Leak 12 LT-410 SPOT LEAK DETECTOR Kele
FCU CONTROLLER

Electric. Their use or reproduction without prior consent of


These drawings and designs are the property of Schneider

the company is strictly forbidden.


Typical of 1
FCU-IT
No Panel Required. Thermostat is Wall Mounted

11/25/2013
1/2/2014
Date:
SUBMITTAL
1 X2
XFR X1
X2 10-30 VAC/DC
Start/Stop:FanSS
WHT/YEL R1 WHT/BLU X1

Revised to Resubmit
WHT/BLK

Record Drawing
120 VAC
1 2 3 4 5 6 7 8 ORG YEL
To Starter

24V+
MFS

24V-

# Change:
BO5
BO5
HFS

LFS
Terminal blocks

Revision:
R1-1

Schneider

1
2
3
4
5
Electric
SE7300F5045B
BACNET FAN COIL CONTROLLER
SE7300-1
SE7300F5045B
+
From: Previous Device

Date: 11/22/2013

11/22/2013
-
REF
To: Next Device

SCOM
AO2
AO1

UI3
BI1

BI2
RS
9 10 11 12 13 14 15 16
X2

Buro Happold

Date:
Date:
1 B
Chilled Water
2 R X1

Giachetti
Control Valve
3 W CtrlVlv:CHWRCtrlVlv NO
Leak:LD
COM

AMP
CSR1:FanSts

LTL
24(+)

FS
NO 24(-)
COM

Designed by:
X1 X2

Software by:
Checked by:
Contractor:
Engineer:
Architect:
Columbia University - Graduate

FCU-IT Controller Wiring


School of Journalism (BIMI)

New York, NY 10027


2950 Broadway
1/2/2014

1/2/2014
Last Printed
Transformer Details

Last Saved
24VAC
X1
24vac

NC13N2951
Panel # ___ COM
X2

Job Number
CB # ___ Pri
XMR2
Sec

FCU (Cooling Only)

Submittal Rev
Device Qty Part Number Description Manufacturer

FCU

Number
----------------------------------------------------------------------------------------------------------------------------------------------------

File Name

5
1.vsd
GND Electrical
120vac R1 1 VER-V100 RELAY ENC SPDT 10-30AC/DC, 120 Veris Industries [V100]

OF
120 N

H-003
(From FCU)

Sheet
120 H SE7300-1 1 SE7300F5045B BACNET FAN COIL CONTROLLER Schneider Electric [SE7300F5045B]

4
XMR2 1 VER-X050CEB TRANSFRMR CTRL MULTI/120V 50VA Veris Industries [X050CEB]
Electric. Their use or reproduction without prior consent of
FCU CONTROLLER

These drawings and designs are the property of Schneider

the company is strictly forbidden.


Typical of 12
(3) FCU-E
(4) FCU-N
(5) FCU-S
No Panel Required. Thermostat is Wall Mounted

11/25/2013
1/2/2014
Date:
SUBMITTAL
1 X2
XFR X1
X2 10-30 VAC/DC
Start/Stop:FanSS
WHT/YEL R1 WHT/BLU X1
WHT/BLK

120 VAC

Revised to Resubmit
1 2 3 4 5 6 7 8 ORG YEL To Starter
Terminal blocks

Record Drawing
24V+
MFS

24V-
BO5
BO5
HFS

LFS
R1-1

# Change:
Revision:
Schneider
Electric
SE7300F5045B

1
2
3
4
5
BACNET FAN COIL CONTROLLER
SE7300-2
SE7300F5045B
+
From: Previous Device
-
REF
To: Next Device

Date: 11/22/2013

11/22/2013
SCOM
AO2
AO1

UI3
BI1

BI2
RS
9 10 11 12 13 14 15 16
X2
1 B
Hot Water
Control Valve 2 R X1
3 W

Buro Happold
CtrlVlv:HWRCtrlVlv

Date:
Date:
CtrlVlv:CHWRCtrlVlv NO
Leak:LD
X2 COM
1 B CSR1:FanSts

Giachetti
Chilled Water 24(+)
Control Valve
2 R X1 24(-)
3 W

AMP
LTL
X1 X2

FS
NO

Designed by:
COM

Software by:
Checked by:
Contractor:
Engineer:
Architect:

FCU-E/N/S Controller Wiring


Columbia University - Graduate
School of Journalism (BIMI)

New York, NY 10027


2950 Broadway
1/2/2014

1/2/2014
Last Printed
Last Saved
Transformer Details
24VAC
X1
24vac

NC13N2951
Panel # ___ COM
X2

Job Number
CB # ___ Pri
XMR2
Sec
FCU (Heating & Cooling)

Submittal Rev
Device Qty Part Number Description Manufacturer

FCU

Number
----------------------------------------------------------------------------------------------------------------------------------------------------

File Name

5
1.vsd
GND Electrical
120vac R1 12 VER-V100 RELAY ENC SPDT 10-30AC/DC, 120 Veris Industries [V100]

OF
H-003
120 N
(From FCU)

Sheet
SE7300-2 12 SE7300F5045B BACNET FAN COIL CONTROLLER Schneider Electric [SE7300F5045B]
120 H

5
XMR2 12 VER-X050CEB TRANSFRMR CTRL MULTI/120V 50VA Veris Industries [X050CEB]
Electric. Their use or reproduction without prior consent of
Total Bill of Materials

These drawings and designs are the property of Schneider

the company is strictly forbidden.


11/25/2013
1/2/2014
Date:
SUBMITTAL

Revised to Resubmit
Record Drawing
# Change:
Revision:

1
2
3
4
5
FCU (Cooling Only)
Device Qty Part Number Description Vendor
----------------------------------------------------------------------------------------------------------------------------------------------------
Electrical
CSR1 1 VER-H600 CURRENT SWITCH N.O. SPLIT CORE Schneider Electric
Leak 1 LT-410 SPOT LEAK DETECTOR Schneider Electric
R1 1 VER-V100 RELAY ENC SPDT 10-30AC/DC, 120 Schneider Electric

Date: 11/22/2013

11/22/2013
SE7300-1 1 SE7300F5045B BACNET FAN COIL CONTROLLER Schneider Electric
XMR2 1 VER-X050CEB TRANSFRMR CTRL MULTI/120V 50VA Schneider Electric

FCU (Heating & Cooling)


Device Qty Part Number Description Vendor
----------------------------------------------------------------------------------------------------------------------------------------------------

Buro Happold

Date:
Date:
Electrical
CSR1 12 VER-H600 CURRENT SWITCH N.O. SPLIT CORE Schneider Electric
Leak 12 LT-410 SPOT LEAK DETECTOR Schneider Electric

Giachetti
R1 12 VER-V100 RELAY ENC SPDT 10-30AC/DC, 120 Schneider Electric
SE7300-2 12 SE7300F5045B BACNET FAN COIL CONTROLLER Schneider Electric

AMP
XMR2 12 VER-X050CEB TRANSFRMR CTRL MULTI/120V 50VA Schneider Electric

LTL

FS Designed by:
Software by:
Checked by:
Contractor:
Engineer:
Architect:
Columbia University - Graduate
School of Journalism (BIMI)

New York, NY 10027


2950 Broadway

Total BOM
1/2/2014

1/2/2014
Last Printed
Last Saved
NC13N2951
Job Number

Submittal Rev
FCU

Number
File Name

5
1.vsd
OF
H-003

Sheet

6
Columbia University-
Graduate School of Journalism
Brown Institute for Media Innovation
Columbia University
2950 Broadway
New York, NY 10027

Building Automation System


H-004: Hot Water Unit Heater
Schneider
Electric Job Updated Checked
Rev. Date Number Description by by
1 11/25/13 NC13N2951 Submittal FS AMP
2 1/2/14 NC13N2951 Revised to Resubmit YBS AMP
Legend
Title Page

System Diagram
Drawing Index:

Page 2
Page 1
Page 0
Architect: LTL
2950 Broadway

Contractor: Giachetti
Engineer: Buro Happold
H-004 Hot Water Unit Heater

Project Number: NC13N2951


NJ/NY
Secaucus, NJ 07094
Main: (201) 348-9240
Service: 1-800-785-8637
210 Meadowlands Parkway

Job Number Columbia University - Graduate


Architect: LTL
NC13N2951 School of Journalism (BIMI)
Engineer: Buro Happold
Revision: SUBMITTAL
2950 Broadway # Change: Date:
File Name Last Saved Contractor: Giachetti 1 Record Drawing 11/25/2013
Table of 2 Revised to Resubmit 1/2/2014
1/2/2014 New York, NY 10027 Designed by: FS Date: 11/22/2013
Contents.vsd 3 These drawings and designs are the property of Schneider
Sheet Number Last Printed Software by: Date: Electric. Their use or reproduction without prior consent of
4
the company is strictly forbidden.
Title Page Checked by: AMP Date: 11/22/2013 5
0 1/2/2014
Symbol Legend General Notes Detail Name

Electric. Their use or reproduction without prior consent of


These drawings and designs are the property of Schneider
Input/Output Blocks Damper or Valve Actuator

the company is strictly forbidden.


1. All room thermostats/sensors/controllers shall be installed at 60" above fixed floor for ADD Color 3-Letter 2-Letter 1-Letter
compliance for new installations. For replacement of existing devices, leave sufficient rolled
coil of wire above the ceiling should the device need to be moved down to meet this Black BLK BK b
SaTmp Software Object Name Brown BRN BR n
00_00 BK
CV1 requirement in the future.
24N 1 COM
UI# COM
24H RD 2 + Red RED RD r
HOT
WH Y1
INPUT
2. All sensor or thermostat pulls that are new require 1 extra conductor to be pulled as well Orange ORG OR o
Termination
from Controller Controller for future use. The shield/drain is not suitable for a conductor. Yellow YEL YL y
UI# SaTmp Designator
COM AO2 Green GRN GN g
COM 00_00
00_00 3. All panel keys will be collected daily and removed from the panels installed. These keys
Blue BLU BU u
ClgVlv Software Object Name are to be giving to the Energy Solutions Site Supervisor.
Violet VIO VL v
Termination

11/25/2013
Controller Designator Gray GRY GY a

1/2/2014
from Controller 4. All thermowells shall be filled with heat conductive compound that is provided.
UI# SaTmp
White WHT WH w

Date:
COM 00_00
5. Wiring Terminations designated as X or XX indicate information was unavailable at time Gold GLD GL d

SUBMITTAL
of submittal. Please inform Schneider Electric before making field terminations. Silver SLV SV s
Pink PNK PK p
6. Remote control devices, not in local panels, shall be accessible for adjustment and
Temperature
Temperature Temperature Temperature Temperature Temperature service - below 7' above fixed floor whenever possible or as shown on the provided
Sensor, Bulb
Sensor, Duct Probe Sensor, Immersion Sensor, Averaging Sensor, Outside Air Sensor, Room Construction prints. 1-Letter abbreviations used for color of stripe on
(Strap-On)
SaTmp HwSTmp MaTmp RmTmp DxSucTmp wire. (WH/o = White wire with orange stripe)

Revised to Resubmit
00_00 00_00 00_00 00_00 00_00 7. Only prints marked Construction are to be used during installation. If the prints are not
OaTmp

Record Drawing
UI# COM UI# COM UI# COM UI# COM UI# COM marked Construction, the installer will correct any discrepancies between prints used and
00_00
RD BK RD BK RD BK
UI# COM
RD BK RD BK
Construction at no cost to Schneider Electric.

# Change:
TS# TS# TS# TS# TS#

Revision:
RD BK
TS# 8. All new BAS controller panels shall have a dedicated 120Vac power source. This source
shall be located and marked in the electrical panel as well as on the control prints returned to
Schneider Electric for Record prints.

1
2
3
4
5
Hydronic Heating Hydronic Cooling 9. Installer responsible for maintaining existing safeties into new BAS control electrically or
Gas Heating Current Sensor Pressure Sensor Pressure Switch pnuematically connected.
Coil Coil
SaFanStat SaStP
Gas 00_00 00_00 10. See Division 23 09 15 00 for any additional information on installation standards.

Date: 11/22/2013

11/22/2013
NO COM UI# COM

Htg + - NC C
LO HI LO HI
NO COM PS1 PS1
CSR1

Wiring Legend

Buro Happold

Date:
Date:
Low Voltage (50 volts or less) control wiring for inputs and outputs shall be 18 AWG or larger rated for 600-volt service. Terminate any

Giachetti
HeatPump or Dual shields or drains for input/outputs at the controller only. See Section 4.2 for additional details.
DX Cooling Electric Heating Smoke Detector Transformer Filter
Pipe Coil

AMP
LTL
1 Stage Indicates need for conduit to be ran by installer. Distances noted on plans are approximate values.

FS
Elect FILTER
D

Designed by:
Software by:
Checked by:
+
_ SD2

Contractor:
Engineer:
X

Architect:
Se
Pri
Htg c
XFR1

Ethernet
Ethernet Wiring: Unless stated differently by the client or the Schneider Electric Site Supervisor, network cable shall meet or exceed all

Columbia University - Graduate


School of Journalism (BIMI)
requirements of Category 5 cable as specified in ANSI/TIA/EAI 568-A. No other devices other than stated in these Construction
drawings will be added to or removed from the clients Ethernet backbone or WAN.

New York, NY 10027


Chiller Boiler Cooling Tower Pump Heat Exchanger L.

2950 Broadway

Legend
MS/TP BACnet or I/Net Wiring: Wiring to be installed using 24 AWG 7/26 Bare Copper 2 conductor stranded, 7/32 drain wire, 12.5
MS/TP pF/ft @ 1 KHz nominal UL TYPE CMP/CL3P 24 AWG. Maximum length is 4000' or 110 controllers. End of Line resistor (120 1/4W)
CHILLE
R CHWP01 to be installed at both ends of network segments. All communication cabling to be installed in a daisy chain configuration, no Ts are
Boiler #1
Heat permitted. Shield on communication cable is to remain continuous and grounded only at a controller. Polarity of the wires must be
Exchanger observed. Splicing of communication cable is not permitted. Cable can be purchase through Schneider Electric using this part number:
WBAC-4-242P-OR-SP

LON or FFT-10 Wiring to be installed using Level IV network cable. Level IV network cable is 22 AWG 7/30 Bare Copper, 2 conductor
FTT-10
VFD Motor Starter 3-way Valve 2-way Valve Fan Damper stranded, with or without a 7/32 drain wire, 17 pF/ft, and impedance of 100 ohm (1-20MHz) nominal UL TYPE SUBJECT 444, CMP.

1/2/2014

1/2/2014
Last Printed
Last Saved
The same cable shall be used through out the project to avoid impedance issues. Maximum length is 4600' or 55 controllers without
use of repeater. Terminator to be installed at both ends of network segments. All LON/FFT-10 cabling to be installed in a daisy chain
See Valve Schedule D1 D1
configuration (not FTT-10A). This cable is not to run in the same conduit with power for more than 5'. Splicing of communication

NC13N2951
CV1 CV1 CV1
N.O. N.O. cable is not permitted. Cable can be purchase through Schneider Electric using this part number: WLON-3-221P-BL-BX

Job Number
VFD STARTER
A AB N.O. N.C.
B

Submittal Rev
EUH

Number
File Name

2
1.vsd
L3 L2 L1 L3 L2 L1

OF
H-004
480 VAC 480 VAC

Sheet

1
Floor Plan Legend is independent, please refer to Legend on that Page
Electric. Their use or reproduction without prior consent of
These drawings and designs are the property of Schneider
UNIT HEATER FLOW DIAGRAM

the company is strictly forbidden.


Typical of 1
(UH-1)
Note: I/O points are terminated on AHU-1E controller.

11/25/2013
1/2/2014
RA SA

Date:
SUBMITTAL
IN7 FanSts
CSR1
RET AHU-1E

NO1 FanSS
STARTER R1
COM1 AHU-1E
HWS
L3 L2 L1
120 VAC

Revised to Resubmit
HWRCtrlVlv
AHU-1E

Record Drawing
V9 GND TTS-S-1
SpTemp
AHU-1E

# Change:
IN6 RET

Revision:
See Valve Schedule CtrlVlv
HWR
A AB
(NO) + -

1
2
3
4
5
SpTemp

Sequence Of Operations

Date: 11/22/2013

11/22/2013
Hot Water Unit Heater

Buro Happold

Date:
Date:
1. BMS Contractor shall furnish, install and wire DDC controls and connection to
the BMS.

Giachetti

AMP
LTL

FS
2. A space temperature sensor shall control the heating valve and fan shall cycle
on.

Designed by:
Software by:
Checked by:
Contractor:
Engineer:
Architect:
3. If the supply fan fails to operate an alarm shall be annunciated at the BMS.

Columbia University - Graduate


School of Journalism (BIMI)

New York, NY 10027

System Diagram
2950 Broadway
NOTE: See AHU Submittal page 4 for actual AHU-1E Controller Wiring Diagram
UH Wiring Detail

NO1
FanSS COM1 X2

NO1 13 R1 14 X1

5 9 T2-1 To Starter
R1-1 T2-2
+ T1-7 RET Terminal blocks
SpTemp
- T1-8 IN7

1/2/2014

1/2/2014
Last Printed
Last Saved
IN8
NO T1-7 FanSts AHU-1E
COM T1-8
CONTROLLER Unit Heaters

NC13N2951
Device Qty Part Number Description Manufacturer

Job Number
----------------------------------------------------------------------------------------------------------------------------------------------------
Electrical

Submittal Rev
CSR1 1 VER-H600 CURRENT SWITCH N.O. SPLIT CORE Veris Industries

EUH

Number
SpTemp 1 TTS-S-1 TEMP SENSOR 4" ROOM 10K T3 Schneider Electric [TTS-S-1]

File Name

2
Com

1.vsd
COM5 T2-9 Hot Water Valve
HWRCtrlVlv NO5 Panel

OF
T2-10

H-004
X2 X1 Hot

Sheet
R1 1 KEL-RH1B-ULAC24V SPDT RELAY W/ LIGHT 24VAC IDEC [RH1B-ULAC24V]

2
R1_1 1 KEL-SH1B-05 SPDT RELAY SOCKET DIN RAIL MTD IDEC [SH1B-05]
Columbia University-
Graduate School of Journalism
Brown Institute for Media Innovation
Columbia University
2950 Broadway
New York, NY 10027

Building Automation System


H-005: Fire/Smoke Dampers
Schneider
Electric Job Updated Checked
Rev. Date Number Description by by
1 11/22/13 NC13N2951 Submittal FS AMP
2 1/2/14 NC13N2951 Revised to Resubmit YBS AMP
Legend
Title Page

FSD Riser
System Sequence
Drawing Index:

Page 3
Page 2
Page 1
Page 0
Architect: LTL
2950 Broadway

Contractor: Giachetti
Engineer: Buro Happold
H-005 Fire/Smoke Dampers

Project Number: NC13N2951


NJ/NY
Secaucus, NJ 07094
Main: (201) 348-9240
Service: 1-800-785-8637
210 Meadowlands Parkway

Job Number Columbia University - Graduate


Architect: LTL
NC13N2951 School of Journalism (BIMI)
Engineer: Buro Happold
Revision: SUBMITTAL
2950 Broadway # Change: Date:
File Name Last Saved Contractor: Giachetti 1 Record Drawing 11/25/2013
Table of 2 Revised to Resubmit 1/2/2014
1/2/2014 New York, NY 10027 Designed by: FS Date: 11/22/2013
Contents.vsd 3 These drawings and designs are the property of Schneider
Sheet Number Last Printed Software by: Date: Electric. Their use or reproduction without prior consent of
4
the company is strictly forbidden.
Title Page Checked by: AMP Date: 11/22/2013 5
0 1/2/2014
Symbol Legend General Notes Detail Name

Electric. Their use or reproduction without prior consent of


These drawings and designs are the property of Schneider
Input/Output Blocks Damper or Valve Actuator

the company is strictly forbidden.


1. All room thermostats/sensors/controllers shall be installed at 60" above fixed floor for ADD Color 3-Letter 2-Letter 1-Letter
compliance for new installations. For replacement of existing devices, leave sufficient rolled
coil of wire above the ceiling should the device need to be moved down to meet this Black BLK BK b
SaTmp Software Object Name Brown BRN BR n
00_00 BK
CV1 requirement in the future.
24N 1 COM
UI# COM
24H RD 2 + Red RED RD r
HOT
WH Y1
INPUT
2. All sensor or thermostat pulls that are new require 1 extra conductor to be pulled as well Orange ORG OR o
Termination
from Controller Controller for future use. The shield/drain is not suitable for a conductor. Yellow YEL YL y
UI# SaTmp Designator
COM AO2 Green GRN GN g
COM 00_00
00_00 3. All panel keys will be collected daily and removed from the panels installed. These keys
Blue BLU BU u
ClgVlv Software Object Name are to be giving to the Energy Solutions Site Supervisor.
Violet VIO VL v
Termination

11/25/2013
Controller Designator Gray GRY GY a

1/2/2014
from Controller 4. All thermowells shall be filled with heat conductive compound that is provided.
UI# SaTmp
White WHT WH w

Date:
COM 00_00
5. Wiring Terminations designated as X or XX indicate information was unavailable at time Gold GLD GL d

SUBMITTAL
of submittal. Please inform Schneider Electric before making field terminations. Silver SLV SV s
Pink PNK PK p
6. Remote control devices, not in local panels, shall be accessible for adjustment and
Temperature
Temperature Temperature Temperature Temperature Temperature service - below 7' above fixed floor whenever possible or as shown on the provided
Sensor, Bulb
Sensor, Duct Probe Sensor, Immersion Sensor, Averaging Sensor, Outside Air Sensor, Room Construction prints. 1-Letter abbreviations used for color of stripe on
(Strap-On)
SaTmp HwSTmp MaTmp RmTmp DxSucTmp wire. (WH/o = White wire with orange stripe)

Revised to Resubmit
00_00 00_00 00_00 00_00 00_00 7. Only prints marked Construction are to be used during installation. If the prints are not
OaTmp

Record Drawing
UI# COM UI# COM UI# COM UI# COM UI# COM marked Construction, the installer will correct any discrepancies between prints used and
00_00
RD BK RD BK RD BK
UI# COM
RD BK RD BK
Construction at no cost to Schneider Electric.

# Change:
TS# TS# TS# TS# TS#

Revision:
RD BK
TS# 8. All new BAS controller panels shall have a dedicated 120Vac power source. This source
shall be located and marked in the electrical panel as well as on the control prints returned to
Schneider Electric for Record prints.

1
2
3
4
5
Hydronic Heating Hydronic Cooling 9. Installer responsible for maintaining existing safeties into new BAS control electrically or
Gas Heating Current Sensor Pressure Sensor Pressure Switch pnuematically connected.
Coil Coil
SaFanStat SaStP
Gas 00_00 00_00 10. See Division 23 09 15 00 for any additional information on installation standards.

Date: 11/22/2013

11/22/2013
NO COM UI# COM

Htg + - NC C
LO HI LO HI
NO COM PS1 PS1
CSR1

Wiring Legend

Buro Happold

Date:
Date:
Low Voltage (50 volts or less) control wiring for inputs and outputs shall be 18 AWG or larger rated for 600-volt service. Terminate any

Giachetti
HeatPump or Dual shields or drains for input/outputs at the controller only. See Section 4.2 for additional details.
DX Cooling Electric Heating Smoke Detector Transformer Filter
Pipe Coil

AMP
LTL
1 Stage Indicates need for conduit to be ran by installer. Distances noted on plans are approximate values.

FS
Elect FILTER
D

Designed by:
Software by:
Checked by:
+
_ SD2

Contractor:
Engineer:
X

Architect:
Se
Pri
Htg c
XFR1

Ethernet
Ethernet Wiring: Unless stated differently by the client or the Schneider Electric Site Supervisor, network cable shall meet or exceed all

Columbia University - Graduate


School of Journalism (BIMI)
requirements of Category 5 cable as specified in ANSI/TIA/EAI 568-A. No other devices other than stated in these Construction
drawings will be added to or removed from the clients Ethernet backbone or WAN.

New York, NY 10027


Chiller Boiler Cooling Tower Pump Heat Exchanger L.

2950 Broadway

Legend
MS/TP BACnet or I/Net Wiring: Wiring to be installed using 24 AWG 7/26 Bare Copper 2 conductor stranded, 7/32 drain wire, 12.5
MS/TP pF/ft @ 1 KHz nominal UL TYPE CMP/CL3P 24 AWG. Maximum length is 4000' or 110 controllers. End of Line resistor (120 1/4W)
CHILLE
R CHWP01 to be installed at both ends of network segments. All communication cabling to be installed in a daisy chain configuration, no Ts are
Boiler #1
Heat permitted. Shield on communication cable is to remain continuous and grounded only at a controller. Polarity of the wires must be
Exchanger observed. Splicing of communication cable is not permitted. Cable can be purchase through Schneider Electric using this part number:
WBAC-4-242P-OR-SP

LON or FFT-10 Wiring to be installed using Level IV network cable. Level IV network cable is 22 AWG 7/30 Bare Copper, 2 conductor
FTT-10
VFD Motor Starter 3-way Valve 2-way Valve Fan Damper stranded, with or without a 7/32 drain wire, 17 pF/ft, and impedance of 100 ohm (1-20MHz) nominal UL TYPE SUBJECT 444, CMP.

1/2/2014

1/2/2014
Last Printed
Last Saved
The same cable shall be used through out the project to avoid impedance issues. Maximum length is 4600' or 55 controllers without
use of repeater. Terminator to be installed at both ends of network segments. All LON/FFT-10 cabling to be installed in a daisy chain
See Valve Schedule D1 D1
configuration (not FTT-10A). This cable is not to run in the same conduit with power for more than 5'. Splicing of communication

NC13N2951
CV1 CV1 CV1
N.O. N.O. cable is not permitted. Cable can be purchase through Schneider Electric using this part number: WLON-3-221P-BL-BX

Job Number
VFD STARTER
A AB N.O. N.C.
B

Submittal Rev
FSD

Number
File Name

5
1.vsd
L3 L2 L1 L3 L2 L1

OF
H-006
480 VAC 480 VAC

Sheet

1
Floor Plan Legend is independent, please refer to Legend on that Page
Electric. Their use or reproduction without prior consent of
Sequence of Operation

These drawings and designs are the property of Schneider

the company is strictly forbidden.


13. The outdoor air damper shall be set AT 500 cfm minimum, (controlled by local CO2 sensors,
Air Handling Unit (AHU-1E)
refer to DVC), with design values at 1000 cfm for normal operation, 2000 cfm for event
1. The BMS contractor shall provide DDC controls for complete stand-alone
operation, and 3000 cfm for air economizer. It shall be open only at occupied periods.
operation. The BMS contractor shall connect the DDC controller to the BMS
Manual override at BMS and local DDC panel shall be provided for event operation.
network for point monitoring and control from the operator interface. Provide
Flow measurement of outside air shall be provided to BMS.
one DDC controller and space sensor per system.
14. When the supply air fan is off, the outdoor air and exhaust air dampers shall
2. Supply and return air duct smoke detectors shall stop the fan upon the presence
close and the return air damper shall open. All associated discharge air dampers
of smoke through the fire alarm system.
shall close, the cooling shall be off. The heat coil valve shall be controlled to

11/25/2013
3. Low temperature detector (freeze stat), mounted upstream of the

1/2/2014
maintain 45F plenum temperatures.
cooling/heating coils, shall stop the fans when the cooling coil entering

Date:
15. Monitor differential pressures across filter and annunciate alarm when

SUBMITTAL
temperature falls below 35F (adj.), for 3 minutes (adj. 0-15 minutes at time
differentia pressure set point is exceeded.
delay relay in control panel). Chilled water valve shall close, heating valve shall
16. If the supply fan fails to operate an alarm shall be annunciated at the BMS and
open. Freeze stats shall automatically reset when temperature rises above trip
dampers shall be indexed to their normal off positions.
set point. If 3 (adj.) freeze stat shutdowns occur within 15 minutes (adj.), unit
17. The Fire Alarm System shall signal the BMS when a fire alarm is present.
shall be commended off until reset from BMS computer.
When the floor/area the fans serves is in alarm, the FAS shall shut down the

Revised to Resubmit
4. For fans greater than 2,000 cfm, provide a high discharge static pressure
fans and close all dampers. Upon fire alarm reset all fans shall sequentially start

Record Drawing
switch if dampers are located upstream of the fan and/or a low static pressure
and operate in the normal mode.
switch if dampers are located downstream of the fan to prevent mechanical

# Change:
Revision:
18. Demand Ventilation controls (DCV):
damage if a damper fails to open. The switch shall stop the fan when duct
Upon a rise in zone CO2 concentration above set-point, the minimum occupied
pressure exceeds design. The fan shall remain off until the pressure switch is

1
2
3
4
5
airflow set-point at the zone VAV terminal shall first be reset from the design
reset.
minimum up to a ventilation override maximum value, 700 ppm (adj).
5. The AHU shall be started by the BMS based upon a start time optimization
program, time of day schedule, or manual command. Upon a command to start, Upon continued call for ventilation (based on continued rise in critical zone CO2
all associated dampers shall open and prove open through damper mounted concentration with VAV terminal at ventilation override maximum setpoint,

Date: 11/22/2013

11/22/2013
limit switch then the supply and return fans shall start. The outdoor air damper then increase the AHU minimum outdoor air rate (damper position) to design
and exhaust air damper shall be closed. minimum.
6. The AHU supply fan shall start and slowly ramp up to speed control set point.
The supply fan variable speed drive shall be controlled to maintain the supply

Buro Happold

Date:
Date:
static pressure set point, as sensed at a point 2/3 downstream of the supply fan. Propeller Exhaust Fan (EF-1)

Giachetti
7. The set point temperature noted in the schedule sheet for unit operation. The 1. As the space pressure sensor increases above the set point of 0.1 / WG ( Adj)

AMP
discharge set point (adjustable) for the air handling unit is presently set at

LTL
compare to outdoor pressure, the exhaust fan shall turn on.

FS Designed by:
Software by:
Checked by:
Contractor:
54.1 F DB / 53.9 F WB

Engineer:
Architect:
8. Morning Warm-up: The system shall be indexed to morning warm-up mode if Condensate pump
the return air temperature is below 60F (adj.) during start-up. The heating coil 1. BMS Contractor shall furnish, install and wire DDC controls and connection to

Columbia University - Graduate


valve shall be controlled to maintain discharge air set point 80F (adj.). Then it the BMS.

School of Journalism (BIMI)


shall be indexed to the occupied mode. 2. Pump shall operate automatically based on the built-in sensor for the water

New York, NY 10027

System Sequence
level inside tank.

2950 Broadway
9. Morning Cool-down: The system shall be indexed to morning cool-down mode
if the return air temperature is above (80F adj.) during start-up. The cooling 3. If the pump fails to operate an alarm shall be annunciated at the BMS. AHU-1E
coil valve shall be controlled to maintain discharge air set point 54F (adj.). and FCU-IT served by the condensate pump shall be shut down.
Then it shall be indexed to the occupied mode.
10. Occupied Mode: The supply fan shall run continuously. The interlinked outdoor
air damper, the return and exhaust air dampers shall move to the fixed positions.
11. Unoccupied Heating: During unoccupied periods if the space temperature falls
below the unoccupied setback set point (60F adj.) the AHU shall cycle on and
the heating coil valve shall be controlled to maintain the space temperature at

1/2/2014

1/2/2014
Last Printed
Last Saved
setpoint .
12. Unoccupied Cooling: During unoccupied periods if the space temperature rises

NC13N2951
above the unoccupied setup set point (80F adj.) the AHU shall cycle on and the

Job Number
cooling coil valve shall be controlled to maintain the space temperature at 80F

Submittal Rev
FSD

Number
(adj).

File Name

5
1.vsd
OF
H-006

Sheet

2
Level 100
Level 200

Network
Tie to BMS

FSD-100-1
BACNet

FSD-100-2
BACNet

FSD-100-3
FSD Riser

BACNet
FSD-200-1
BACNet

FSD-100-4
BACNet
FSD-200-2
BACNet

FSD-100-5
BACNet
FSD-200-3
BACNet

FSD-100-6

There are no Parts in the Bill of Material

Job Number Columbia University - Graduate


Architect: LTL
NC13N2951 School of Journalism (BIMI)
Engineer: Buro Happold
Revision: SUBMITTAL
2950 Broadway # Change: Date:
File Name
H-006 FSD Last Saved Contractor: Giachetti 1 Record Drawing 11/25/2013
Submittal Rev 1/2/2014 New York, NY 10027 Designed by: FS Date: 11/22/2013 2 Revised to Resubmit 1/2/2014
3 These drawings and designs are the property of Schneider
1.vsd
Sheet Number Last Printed Software by: Date: Electric. Their use or reproduction without prior consent of
4
the company is strictly forbidden.
System Diagram Checked by: AMP Date: 11/22/2013 5
3 OF 5 1/2/2014
Columbia University-
Graduate School of Journalism
Brown Institute for Media Innovation
Columbia University
2950 Broadway
New York, NY 10027

Building Automation System


Valve & Damper Schedules
Schneider
Electric Job Updated Checked
Rev. Date Number Description by by
1 11/25/13 NC13N2951 Submittal FS AMP
2 1/2/14 NC13N2951 Revised to Resubmit YBS AMP
Project Name: Columbia U Grad School Of Journalism B
Project Number: NC13N2951
Owner: Columbia University
Phone: (201) 348 - 9240 Engineer: Buro Happold Consulting Engineers, PC
Facsimile: (201) 348 - 9530 Contractor: Giachetti Plumbing & Heating

GENERAL NOTES: SHEET METAL CONTRACTOR Damper Shipping Information:


THE DAMPER SIZES ONLY HAVE TO BE CHECKED Ship to:
MANUFACTURER WILL AND CONFIRMED.
DEDUCT 1/4" FROM THE Page 1 of 1 N.O. = NORMALLY OPEN
CONFIRMED SIZES FOR Date
D t 1/2/2014 N.C.
N C = NORMALLY CLOSED
INSTALLATION Confirmed by: Revision # Rev 2 PAR. = PARALLEL BLADES
CLEARANCE Dated: Mark Shipment: Drawing By OPP. = OPPOSED BLADES

AUTOMATIC TEMPERATURE CONTROL DAMPER SCHEDULE


# #
MECHANICAL SUBMITTED SIZE TORQUE CONTROL ACTUATOR
DAMPER DAMPER
DRAWING WIDTH HEIGHT SECTION SECTION BLADE MODEL REQ'D MODEL CONTROL CONTROL POS. FAIL-SAFE TORQUE NOTES
ITEM TAG ID REFERENCE SERVICE QTY (inches) (inches) S WIDE S HIGH ACTION MFG. NUMBER (IN.LB.) QTY MFG. NUMBER SIGNAL VOLTAGE FDBK POSITION (IN.LB.) CFM
1 AHU1OADpr M-100, M-600 AHU 1 E OA 1 30 24 1 1 N/A BY OTHERS - 5 1 Belimo TFB24-SR 2-10 VDC 24V N NC 22 3000
2 AHU1EADpr M-100, M-601 AHU 1 E EA 1 32 32 1 1 N/A BY OTHERS - 7 1 Belimo TFB24-SR 2-10 VDC 24V N NC 22 3000
3 AHU1RADpr M-100, M-600 AHU 1 E RA 1 32 32 1 1 N/A BY OTHERS - 7 1 Belimo TFB24-SR 2-10 VDC 24V N NO 22 2000

NOTES 1. ACTUATOR FIELD MOUNTED 3. INTERLOCK W/ FAN CONTROL CIRCUIT


2. HARD-WIRE INTERLOCK W/ VFD 4. HARDWIRE INTERLOCK W/ STARTER
Company: Schneider Electric Project Name: Columbia U Grad School of Journalism BIMI Date: 1/2/2014

Project Number: NC13N2951 Revision #: Rev 2


Owner: Columbia University Approved: AMP
Phone: (201) 348 - 9240 Engineer: Buro Happold Consulting Engineers, PC
Fax: (201) 348 - 9530 Contractor: Giachetti Plumbing & Heating

VALVE PRESSURE DROP (PSI) TO BE USED IN H2O CALCULATIONS: 5.0 STEAM INLET PRESSURE (PSIG) TO BE USED IN STEAM APPLICATIONS: 5.0

AUTOMATIC TEMPERATURE CONTROL VALVE SCHEDULE (PLEASE SEE INSTALLATION NOTES)


PART # SPRING POS. VLV. VLV. PIPE VLV. CONN. FLOW VALVE CV ACT. PRESS. CLOSE OFF (PSI)
ITEM SYSTEM TAG QTY SERVICE VALVE ASSEMBLY ACTUATOR RANGE POSIT. TYPE SIZE SIZE ACTION TYPE GPM #/HR CALC. ACT. DROP (PSI) STEM UP STEM DN
1 AHU-1 CHWR Ahu1ChwrVlv 1 1st Fl & Mezz BEL-B219 TFRB24-SR 2-10 VDC N 2 Way Straight 3/4" 1-1/2" Fails Normally Open Screwed 22.00 9.84 10.0 4.84 200 200
2 AHU-1 HWR Ahu1HwrVlv 1 1st Fl & Mezz BEL-B212 TFRB24-SR 2-10 VDC N 2 Way Straight 1/2" 1" Fails Normally Open Screwed 5.80 2.59 3.0 3.74 200 200
3 UH-1 HWR Uh1HwrIsoVlv 1 MER, L100 BEL-B217 TFRB24-SR 2-10 VDC N 2 Way Straight 3/4" Fails Normally Open Screwed 0.56 0.25 4.7 0.01 200 200
4 FCU-IT CHWR FcuItChwrVlv 1 Cellar, IT Rm, In MER BEL-B210 TFRB24-SR 2-10 VDC N 2 Way Straight 1/2" 1" Fails Normally Open Screwed 2.63 1.18 1.2 4.80 200 200
5 FCU-N1 CHWR FcuN1ChwrVlv 1 1st Fl. North Faade BEL-B207 TFRB24-SR 2-10 VDC N 2 Way Straight 1/2" 3/4" Fails Normally Open Screwed 0.38 0.17 0.3 1.60 200 200
6 FCU-N2 CHWR FcuN2ChwrVlv 1 1st Fl. North Faade BEL-B207 TFRB24-SR 2-10 VDC N 2 Way Straight 1/2" 3/4" Fails Normally Open Screwed 0.38 0.17 0.3 1.60 200 200
7 FCU-N3 CHWR FcuN3ChwrVlv 1 1st Fl. North Faade BEL-B207 TFRB24-SR 2-10 VDC N 2 Way Straight 1/2" 3/4" Fails Normally Open Screwed 0.38 0.17 0.3 1.60 200 200
8 FCU-N4 CHWR FcuN4ChwrVlv 1 1st Fl. North Faade BEL-B207 TFRB24-SR 2-10 VDC N 2 Way Straight 1/2" 3/4" Fails Normally Open Screwed 0.38 0.17 0.3 1.60 200 200
9 FCU-E1 CHWR FcuE1ChwrVlv 1 1st Fl. East Faade BEL-B208 TFRB24-SR 2-10 VDC N 2 Way Straight 1/2" 3/4" Fails Normally Open Screwed 0.75 0.34 0.5 2.66 200 200
10 FCU-E2 CHWR FcuE2ChwrVlv 1 1st Fl. East Faade BEL-B208 TFRB24-SR 2-10 VDC N 2 Way Straight 1/2" 3/4" Fails Normally Open Screwed 0.75 0.34 0.5 2.66 200 200
11 FCU-E3 CHWR FcuE3ChwrVlv 1 1st Fl. East Faade BEL-B208 TFRB24-SR 2-10 VDC N 2 Way Straight 1/2" 3/4" Fails Normally Open Screwed 0.75 0.34 0.5 2.66 200 200
12 FCU-S1 CHWR FcuS1ChwrVlv 1 1st Fl. South Faade BEL-B208 TFRB24-SR 2-10 VDC N 2 Way Straight 1/2" 3/4" Fails Normally Open Screwed 0.75 0.34 0.5 2.66 200 200
13 FCU-S2 CHWR FcuS2ChwrVlv 1 1st Fl. South Faade BEL-B208 TFRB24-SR 2-10 VDC N 2 Way Straight 1/2" 3/4" Fails Normally Open Screwed 0.75 0.34 0.5 2.66 200 200
14 FCU-S3 CHWR FcuS3ChwrVlv 1 1st Fl. South Faade BEL-B208 TFRB24-SR 2-10 VDC N 2 Way Straight 1/2" 3/4" Fails Normally Open Screwed 0.75 0.34 0.5 2.66 200 200
15 FCU-S4 CHWR FcuS4ChwrVlv 1 1st Fl. South Faade BEL-B208 TFRB24-SR 2-10 VDC N 2 Way Straight 1/2" 3/4" Fails Normally Open Screwed 0.75 0.34 0.5 2.66 200 200
16 FCU-S5 CHWR FcuS5ChwrVlv 1 1st Fl. South Faade BEL-B208 TFRB24-SR 2-10 VDC N 2 Way Straight 1/2" 3/4" Fails Normally Open Screwed 0.75 0.34 0.5 2.66 200 200
17 FCU-N1
FCU N1 HWR FcuN1HwrVlv
F N1H Vl 1 1st Fl. N
1 t Fl North Faade
th F d BEL-B207
BEL B207 TFRB24-SR
TFRB24 SR 2-10
2 10 VDC N 2W
Way St
Straight
i ht 1/2" 3/4" Fails
F il NNormally
ll OOpen Screwed
S d 0.32
0 32 0.14 0.3
03 1.14 200 200
18 FCU-N2 HWR FcuN2HwrVlv 1 1st Fl. North Faade BEL-B207 TFRB24-SR 2-10 VDC N 2 Way Straight 1/2" 3/4" Fails Normally Open Screwed 0.32 0.14 0.3 1.14 200 200
19 FCU-N3 HWR FcuN3HwrVlv 1 1st Fl. North Faade BEL-B207 TFRB24-SR 2-10 VDC N 2 Way Straight 1/2" 3/4" Fails Normally Open Screwed 0.32 0.14 0.3 1.14 200 200
20 FCU-N4 HWR FcuN4HwrVlv 1 1st Fl. North Faade BEL-B207 TFRB24-SR 2-10 VDC N 2 Way Straight 1/2" 3/4" Fails Normally Open Screwed 0.32 0.14 0.3 1.14 200 200
21 FCU-E1 HWR FcuE1HwrVlv 1 1st Fl. East Faade BEL-B207 TFRB24-SR 2-10 VDC N 2 Way Straight 1/2" 3/4" Fails Normally Open Screwed 0.35 0.16 0.3 1.36 200 200
22 FCU-E2 HWR FcuE2HwrVlv 1 1st Fl. East Faade BEL-B207 TFRB24-SR 2-10 VDC N 2 Way Straight 1/2" 3/4" Fails Normally Open Screwed 0.35 0.16 0.3 1.36 200 200
23 FCU-E3 HWR FcuE3HwrVlv 1 1st Fl. East Faade BEL-B207 TFRB24-SR 2-10 VDC N 2 Way Straight 1/2" 3/4" Fails Normally Open Screwed 0.35 0.16 0.3 1.36 200 200
24 FCU-S1 HWR FcuS1HwrVlv 1 1st Fl. South Faade BEL-B207 TFRB24-SR 2-10 VDC N 2 Way Straight 1/2" 3/4" Fails Normally Open Screwed 0.32 0.14 0.3 1.14 200 200
25 FCU-S2 HWR FcuS2HwrVlv 1 1st Fl. South Faade BEL-B207 TFRB24-SR 2-10 VDC N 2 Way Straight 1/2" 3/4" Fails Normally Open Screwed 0.32 0.14 0.3 1.14 200 200
26 FCU-S3 HWR FcuS3HwrVlv 1 1st Fl. South Faade BEL-B207 TFRB24-SR 2-10 VDC N 2 Way Straight 1/2" 3/4" Fails Normally Open Screwed 0.32 0.14 0.3 1.14 200 200
27 FCU-S4 HWR FcuS4HwrVlv 1 1st Fl. South Faade BEL-B207 TFRB24-SR 2-10 VDC N 2 Way Straight 1/2" 3/4" Fails Normally Open Screwed 0.32 0.14 0.3 1.14 200 200
28 FCU-S5 HWR FcuS5HwrVlv 1 1st Fl. South Faade BEL-B207 TFRB24-SR 2-10 VDC N 2 Way Straight 1/2" 3/4" Fails Normally Open Screwed 0.32 0.14 0.3 1.14 200 200

Page 1 of 2
Columbia University
Graduate School of Journalism
Brown Institute for Media Innovation
Columbia University
2950 Broadway
New York, NY 10027

Product Data Sheets

Schneider Electric Phone +1 201-348-9240


210 Meadowlands Parkway Fax +1 201-348-9530
Secaucus, NJ 07094 Web www.schneider-electic.com
NEW!
PRESSURE
Air Pressure Sensors, Surge Dampeners PSI
A300 Series, RPS, SD-01, 21121, 60681

Description
Static Pressure Sensors
The A-300-K Series sensors are used with pressure transmitters and
pressure switches to sense duct pressures. Two sensors are required
to monitor pressure across coils, filters, blowers, etc. A-301-K and
A-302-K have four radial sensing holes and 4" (10.2 cm) insertion
depth. The A-308-K should be used only where accuracy is not
critical. All mount in a 3/8" hole in the duct. If the interior of the duct is
not accessible, an optional A-345-K flange mounting kit may be used. 60681
Room Static Pressure or Total Pressure Sensor Kit RPS-W
The versatile Model 60681 Pressure Sensing Kit is used for
monitoring static pressure (aspiration) or total pressure (impact).
The kit includes a 7" (17.8 cm) universal sensing probe, adjustable
mounting flange, 1/4" adapter, and 3' (0.9 m) length of tubing (1/4" ID
x 3/8" OD). For total (impact) pressure applications, install the curved
tip opening facing into the air stream or away from the air stream for
vacuum applications.
RPS & SD-01
Total Pressure Sensor
The Model 21122 (4") and 21123 (8") sensors are used primarily for A-300 Series
proving air flow in ducts. The opening in the tip of the 4" (10.2 cm)
aluminum tube faces upstream and senses impact (total) pressure. APPLICATION
The "-112" models accept 1/8" to 1/4" ID flexible tubing.

Outdoor Static Pressure Sensor 1 2 3


The A-306-K Outdoor Static Pressure Sensor provides an outdoor
pressure signal for reference in building pressurization applications.
The A-306-K includes the sensor, 50' (15.24m) of vinyl tubing,
mounting bracket, and hardware.

Room Static Pressure Sensor


The Model RPS is a stainless steel, wall-mounted room static
pressure sensor. It mounts directly to the wall or to a standard 1. Positive static pressure increases as the filter gets dirty.
electrical box. The Model RPS-W is a white plastic, wall-mounted 2. Differential across filter changes as filter gets dirty.
room static pressure sensor, and the Model RPS-I is ivory. The RPS 3. Flow is reduced as filter gets dirty.

PRESSURE
sensors have a 100 micron stainless steel breather vent.

Filter Kit 4 5
The Model A-605 Filter Kit includes an aluminum surface mounting
bracket and screws, two 5 ft lengths of 1/4" aluminum tubing, two
static pressure tips, and two plastic vent valves.

Surge Dampener
Surge Dampener Model SD-01 absorbs rapid pressure fluctuations
to provide steady pressure outputs. The dampener has two
independent channels - one for the low pressure tubing and one for 4. Negative pressure increases as the filter gets dirty.
the high pressure tubing. Surge dampeners are typically used with 5. Fan operation and true air flow: varying amounts of
outdoor pressure sensors, which are subject to wind gusts, and static pressure. Probes must be perpendicular to air flow.
isolation rooms, clean rooms, or operating rooms where opening or
closing doors creates sudden pressure changes.

ORDERING INFORMATION
19
MODEL DESCRIPTION
60681 Static or total pressure sensing kit
A-301-K Duct static pressure tip, 1/4" compression
A-302-K Duct static pressure tip, 1/4" barb
A-308-K Duct static pressure fitting, 1/4" barb
A-345-K Flange mounting kit (1 required for each A-301-K or A-302-K)
A-3145K A-301-K duct static pressure tip, 1/4" compression with A-345-K mounting flange
A-3245K A-302-K duct static pressure tip, 1/4" barb with A-345-K mounting flange
A-3845K A-308-K duct static pressure fitting, 1/4" barb with A-345-K mounting flange
21122 4" aluminum impact tube, 1/4" OD connection
21122-112 6" aluminum impact tube for 1/8" thru 1/4" ID flexible plastic tubing
21123 8" aluminum impact tube, 1/4" OD connection
21123-112 8" aluminum impact tube for 1/8" thru 1/4" ID flexible plastic tubing
A-306-K Outdoor air static pressure kit
A-605 Mounting kit for air filter application. Includes aluminum surface mounting brackets with screws, two 5 ft. lengths of 1/4"
aluminum tubing, two static pressure tips and two plastic vent valves.
RPS Stainless steel room pressure sensor, 1/4" barb
RPS-I Ivory plastic room pressure sensor, 1/4" barb
RPS-W White plastic room pressure sensor, 1/4" barb
SD-01 Surge dampener
B-137 1/4" barb adapter for #21122 and #21123 (standard pack-50)

January 2012 2012 Kele, Inc. All rights reserved. The Kele name and logo are registered trademarks of Kele, Inc. kele.com 888-397-5353 USA 001-901-382-6084 International
925
Controls Group 507 E. Michigan Street
P.O. Box 423, Milwaukee, WI 53202
Code No. LIT-1927140
a70s p;w 1927140 9thcc:7-25 Refrigeration Temperature Controls Rev:
07/18/97
A70 Series logo:
JCI
left ft:
refrig

Four-Wire, Two-Circuit Temperature Control right ft:


standard
Sect# = 0
seQ# = 1

a70s.eps a70ga1c.tif Features


A70 Series long-life, snap-acting contacts
automatic or manual reset models
L ine 2

Applications
M2 Typical applications include energizing an
indicator light after a low temperature cutout
M1
on a ventilating system.

L ine 1 Replacement Covers


Action on Increase Code Number Description
on Temperature
CVR17A-620R Automatic reset
CVR17A-621R Manual reset

A70GA-1
To Order
Description
Specify the code number from the following
The A70 Series temperature control The contacts are designed so that when the selection chart.
incorporates a vapor-charged sensing main contact opens, the auxiliary contact
element. The A70G, A70H, and A70K have a closes.
4-wire, 2-circuit contact block that contains
two isolated sets of contacts.

Selection Chart
Code Switch Action Range Diff F Bulb and Max Bulb Range
Number Main Contacts Auxiliary Contacts F (C) (C) Capillary Temp F (C) Adjuster
15 to 55 20 ft of 1/8 in.
A70GA-1C(a) 5 (2.8) 400 (204.4) Screwdriver slot
(-9.4 to 12.8) O.D. Tubing
3 to 30
35 to 80 (-16.1 to -1.1),
A70GA-2C 3/8 in. x 3 in. 6 ft Cap. 250 (121) Screwdriver slot
(1.7 to 26.7) factory set at 12
Open Low Close Low
(-11.1)
15 to 55 20 ft. of 1/8 in. O.D.
A70HA-1C(a) Manual reset 400 (204.4) Screwdriver slot
(-9.4 to 12.8) Tubing
35 to 80
A70HA-2C Manual reset 3/8 in. x 3 in. 6 ft cap. 250 (121) Screwdriver slot
(1.7 to 26.7)
100 to 170
A70KA-1C Open High Close High Manual reset 3/8 in. x 10 in. 6 ft cap. 240 (116) Screwdriver slot
(37.8 to 76.7)
(a) The low cutout stop is set and sealed at 35F (1.6C). The control responds only to the lowest temperature along any one ft. of the entire 20 ft. element or bellows
cup.

Electrical Ratings
Pole Number LINE-M2 (Main) LINE-M1 (Auxiliary)
Motor Ratings VAC 120 208 240 277 (a) (a) 120 208 240 277
480 600
AC Full Load Amp 16.0 9.2 8.0 5.0 4.8 6.0 3.4 3.0
AC Locked Rotor Amp 96.0 55.2 48.0 30.0 28.8 36.0 20.4 18.0
AC Non-Inductive Amp 16.0 9.2 8.0 7.2 6.0 6.0 6.0 6.0
Pilot Duty Both Poles 125 VA, 120 to 600 VAC and 57.5 VA, 120 to 300 VDC
(a) Not compressor motor loads.

The performance specifications are nominal and conform to acceptable industry standards. For applications at conditions beyond these specifications, consult the local Johnson
Controls office. Neither Johnson Controls, Inc. nor its subsidiaries or affiliates shall be liable for damages resulting from misapplication or misuse of its products.
1/1 07/03 Johnson Controls, Inc
NEW!
PRESSURE
PSI
Adjustable Differential Pressure Switches
AFS Series

Description
The AFS Series Adjustable Differential Pressure Switches
are general-purpose, airflow-proving switches designed for
HVAC and building automation applications. The AFS Series
can be used to sense positive, negative, or differential air
pressure. The diaphragm and calibration spring are housed in
a plated enclosure with a removable metal guard protecting
the set point screw and snap action switch terminals.
Electrical connections are made through a 7/8 diameter
opening in the metal guard that accepts a conduit connection.
Air sampling connections accept OD rigid or semi rigid tubing.
The Model AFS-460 features a manual reset button to close
the switch following actuation. For low current applications
use Model AFS-405 with gold contacts.

C US
Features
Adjustable set point
For static or differential pressure Application
15A switch rating Proving fan status
Manual reset (Model AFS-460) Monitoring filter for excess pressure drop FM
Gold contacts (Model AFS-405) Monitoring duct static pressure
C
APPROVED
US

UR, CSA, FM approved Proving air flow


Two-year warranty Monitoring damper status

Specifications
PRESSURE

Contact Rating Measurement Range


AFS-145, 222, 262, 405 15A non-inductive, 277 VAC, 60 Hz AFS-145, 222, 405 0.05" to 12.0" W.C. (12.5 to 2989 Pa)
24 VAC @ 2.4A AFS-262 0.05" to 2.0" W.C. (12.5 to 498 Pa)
AFS-460, 460-DSS 15A @ 125-277 VAC 1/4 HP @ 125 AFS-460 0.4" to 12.0" W.C. (99.3 to 2989 Pa)
VAC 1/2 HP @ 250 VAC 1/2A @ AFS-460-DSS 2.0" to 12.0" W.C. (498 to 2989 Pa)
125 VDC Life Expectancy AFS-145, 222, 262, 405: 100,000
Contact Type cycles minimum @ 0.5 psig (3.5 kPa)
AFS-145, 222, 262, 405 maximum pressure each cycle and
AFS-136, 460-137 SPDT at maximum electrical load AFS-460:
AFS-460 SPST N.C. 6000 cycles
AFS-460-DSS 2-SPST N.C. Operating Temperature -40 to 180F (-40 to 82C)
Switch Differential Process Connection
AFS-145, 222, 262, 405 Progressive, increasing from AFS-145 1/8" NPTF)
19 approximately 0.02" W.C. (5.0 Pa) @ All Others Ferrule and nut compression for
minimum set point to approximately 1/4" OD tubing
0.8" W.C. (199 Pa) @ maximum set Approvals CE, UR, cCSAus, RoHS, FM
point Weight 1.2 lb (0.54 kg)
AFS-460, 460-DSS None, manual reset Warranty 2 years
Overpressure 0.5 psig (3.5 kPa)

Wiring

NO C A
C Lead
C Opens on a NC
rise in
NC differential
NC
pressure C B
Action on a rise in differential pressure Lag
Opens on a rise in differential pressure
NC

850 001-901-382-6084 International 888-397-5353 USA kele.com 2012 Kele, Inc. All rights reserved. The Kele name and logo are registered trademarks of Kele, Inc. January 2012
NEW!
PRESSURE
Adjustable Differential Pressure Switches PSI
AFS Series

DIMENSIONS
in 2.81
6.13
(15.57)
(cm) (7.14)
Low pressure inlet (B)

3.88 3.25 C NO NC
3.25 (8.23)
(9.86)
(8.23) 0.710
1.38
(3.50) (1.80)
1.63
1.94
(4.14)
(4.93)

High pressure inlet (A)


0.44 0.78
Two mounting holes
(1.12) (1.98)
3/16 fastener required

OPERATION
Select a mounting location that is free from vibration. The switch Refer to the Dimensions drawing to identify the high pres-
must be mounted with the diaphragm in any vertical plane in sure inlet (A) and the low pressure inlet (B), and connect the
order to obtain the lowest specified operating setpoint. Avoid sample lines as follows:
mounting with the sample line connections in the up position.
Surface mount via the two 3/16" diameter holes in the integral Positive Pressure Only
mounting bracket. Connect the sample line to (A);
(B) remains open to the atmosphere.
The Model AFS-460-DSS has a lead switch (A) and a lag switch Negative Pressure Only
(B). The lead switch trips according to the setpoint knob and the Connect the sample line to (B);
lag switch trips after the lead switch. If dual-switch simultaneous (A) remains open to the atmosphere.
operation is required, order AFS-460-136 (120 VAC power) or Two Negative Samples
AFS-460-137 (24 VAC power). Connect the higher negative sample to (B);
Connect the lower negative sample to (A).

PRESSURE
Locate sampling probe a minimum of 1-1/2 duct diameters Two Positive Samples
downstream from the air source. Install the sampling probe as Connect the higher positive sample to (A);
close to the center of the airstream as possible. Connect the lower positive sample to (B).
One Positive and One Negative Sample
Connect the positive sample to (A);
Connect the negative sample to (B).

ORDERING INFORMATION

MODEL DESCRIPTION
AFS-145 Differential pressure switch 0.05" to 12" W.C. (12.5 to 2989 Pa), 1/8" NPTF
AFS-222 Differential pressure switch 0.05" to 12" W.C. (12.5 to 2989 Pa), 1/4" compression fittings
AFS-222-121 Differential pressure switch 0.05" to 12" W.C. (12.5 to 2989 Pa), 1/4" barbed fittings
AFS-262 Differential pressure switch 0.05" to 2" W.C. (12.5 to 498 Pa), 1/4" compression fittings
AFS-262-121 Differential pressure switch 0.05" to 2" W.C. (12.5 to 498 Pa), 1/4" barbed fittings 19
AFS-405 Differential pressure switch 0.05" to 12" W.C. (12.5 to 2989 Pa), gold contacts
AFS-460 Manual reset differential pressure switch, 0.4" to 12" W.C. (99.3 to 2989 Pa), SPST
AFS-460-136 Manual reset differential pressure switch, 0.4" to 12" W.C. (99.3 to 2989 Pa), 120 VAC, SPDT
AFS-460-137 Manual reset differential pressure switch, 0.4" to 12" W.C. (99.3 to 2989 Pa), 24 VAC, SPDT
AFS-460-DSS Manual reset differential pressure switch, 2" to 12" WC (498 to 2989 Pa), 2 SPST switches

RELATED PRODUCTS PAGE


21122 6" aluminum impact tube, 1/4" OD connection 925
21122-112 6" aluminum impact tube for 1/8" thru 1/4" ID flexible plastic tubing 925
60681 Static or total pressure sensing kit 925
A-301-K Duct static pressure tip, 1/4" compression 925
A-302-K Duct static pressure tip, 1/4" barb 925
A-308-K Duct static pressure fitting, 1/4" barb 925
A-345-K Flange mounting kit (1 required for each A-301-K or A-302-K) 925
T-101 1/4" OD black poly tubing, 1 coil, 250 ft (76 m) 759

January 2012 2012 Kele, Inc. All rights reserved. The Kele name and logo are registered trademarks of Kele, Inc. kele.com 888-397-5353 USA 001-901-382-6084 International
851
BACnet
b3865/866/885-V VAV
Controllers with Built-in Actuator

The Andover ContinuumTM b3865-V, b3866-V and b3885-V are


native BACnet controllers that communicate on an RS-485 field
bus as Master devices using the MS/TP BACnet protocol.
02

BACnet b3865/866/885-V VAV Controllers


with Built-in Actuator
Features

The controllers are highly intelligent,


low-cost VAV box controllers that come
equipped with a built-in actuator to
streamline hardware installation and save
commissioning time. Universal inputs, an
airow sensor, Form A triac-based outputs,
and an integrated damper actuator
make these controllers perfect for VAV
applications. The b3865/866-V models
feature a room sensor input, which supports
our Andover Continuum Smart Sensor, or
any standard room temperature sensor.

The b3865-V is the base model with four universal


inputs, an airflow sensor, three Form A triac-based
PRODUCT AT A GLANCE outputs, and an integrated damper actuator.

Native BACnet MS/TP communications The b3866-V model is identical to the b3865-V,
with the exception that it also offers damper
Support for 18 BACnet object types, including
position feedback and two analog outputs to
Trends, Schedules, Calenders, and Loops
control reheat valves, lighting ballasts, etc.
Low-cost VAV control in compact package
The b3885-V has a reduced I/O point count for
Built-in damper actuator simplifies smaller VAV applications.
hardware installation
All VAV models feature Flash memory, user
Universal inputs with Form A, Form K, and memory for programs, and a fast (32-bit)
analog outputs for flexible control options processor for faster can times, with plenty of
Non-volatile Flash memory for application additional memory available for data logging of
program and operating system storage your critical data.

Easy on-line software updates

Local extended storage of log data b3865-V b3866-V b3885-V

On-board airflow sensor Universal Inputs 4 4 2


Airow Sensor Yes Yes Yes
Optional Andover Continuum Smart
Sensor Display Smart Sensor Input Yes Yes Yes
Form A Triac Outputs 3 3 2
Complies with B-AAC BACnet profile
Analog Outputs - 2 -
Support for Wireless BACnet Field
Integrated Yes Yes Yes
Bus communications Actuator
Service Port Yes Yes Yes
Wireless Option Yes Yes Yes

Schneider Electric One High Street, North Andover, MA 01845 USA Telephone: +1 978 975 9600 Fax: +1 978 975 9674 www.schneider-electric.com/buildings

SDS-B3865/866/885-A4.BU.N.EN.2.2007.0.00.CC
03

BACnet b3865/866/885-V VAV Controllers


with Built-in Actuator
Features (continued)

As native BACnet controllers, the b3865/866/885-V Dimension Drawing


models can communicate with other BACnet
devices on the MS/TP network, in strict accordance
with ANSI/ASHRAE standard 135-2004. By
connecting to the Andover Continuum bCX1, the
controllers, or other MS/TP devices can share and
gather data from the wider Ethernet/IP network
of controllers. Among those Ethernet controllers
can be Andover Continuum controllers (BACnet or
Andover Continuum Infinet) or third party BACnet
IP devices. All Andover devices, both BACnet and
Andover Continuum Infinet, are fully compatible with
the Andover Continuum CyberStation front-end
software, a fully native BACnet Operator Workstation
(B-OWS) application.

A Highly Intelligent Controller


Andover Continuum field controllers are highly
intelligent and the VAV models are no exception.
TAC designs the Andover Continuum field controllers
to handle schedules, alarms and trends locally so
there is no reliance on any supervisory controllers.
Since each controller is programmable and can
operate independently, the Andover Continuum
is highly reliable. Furthermore, each controller is
peer-to-peer and can share data with any Andover from being lost if power is removed.
Continuum or third party BACnet controller.
Inputs
Optional Wireless BACnet The inputs consists of two or four full-range
The b3865/866/885-V BACnet controllers can Universal inputs that accept voltage (0-5VDC),
also communicate using a wireless mesh BACnet digital (on/off), counter signals (up to 4Hz), or
865-V
(LOW)

network. Simply plug Andover Continuum Wireless temperature signals,AIR plus


FLOWan on-board air flow
INPUT
Adapters into the service ports of the BACnet sensor. The (HIGH)
b3865/866-V models also offer an
controllers with wireless compatible firmware to additional input to support the Andover Continuum
create a wireless mesh network that sends and Smart Sensor, or any standardCAUTION room temperature
COM 18
receives BACnet messages. Because the native sensor. 1 IN 1 MORE THAN ONE DISCONNECT
SWITCH MAY BE REQUIRED RS-485
TO DE-ENERGIZE THIS EQUIPMENT COM 17
2 IN 2 PORT
BACnet communications are used wirelessly, the BEFORE SERVICING.
SHIELD 16
bCX1 connects the entire wireless BACnet network Outputs 3 RET UNIVERSAL
INPUTS
to the wired BACnet networks in your system, The b3865/866-V 4
IN 3
controllers contain three Form
This equipment complies with part 15
5 IN 4
regardless of manufacturer. A Triac-based outputs. The to theb3885-V controller
of the FCC rules. Operation is subject
following two conditions.
(1) This device may not cause harmful
6 RET interference.
contains two Form A Triac-based outputs.
(2) This device must accept any
interference received, including
interference that may cause
These TRIAC REF 15
7 SPWR
outputs can be usedSMART separately for on/off or
undesired operation.
Increased Reliability with Flash Memory 8 RET
DIGITAL
OUTPUTS
OUT5 14

The non-volatile Flash memory stores your operating pulsed control of lighting, heat, and fan units or24VAC ,
SENSOR
OUT4 13
9 IN 5 0.5A
system and application programs, so that in the event for bi-directional control of dampers
USE COPPER CONDUCTORS and ONLY valves; or OUT3 12
10 2 4VAC
INPUT: CLASS 2 POWER ONLY
of a power loss, your application is restored when configured into
11 one Form
24VAC ,K Tri-state
0.42A, 10VA, 50/60HZoutput and one
power is returned. In addition, the Flash memory Form A output. (Note: Any two consecutive Triac
allows for easy upgrades of your operating system via outputs can be configured as a Form K output.)
Outputs are (LOW)
rated for AC loads only. The b3866-V
software downloads, eliminating the need to swap out
memory chips. Each controller, except the b3885-V, controller also offers AIRtwoFLOW
INPUT (0-10V) analog outputs. 866-V
includes an on-board battery to safeguard your
(HIGH)

runtime data protecting all point data and log data


CAUTION COM 21
1 IN 1 MORE THAN ONE DISCONNECT
SWITCH MAY BE REQUIRED RS-485
TO DE-ENERGIZE THIS EQUIPMENT COM 20
Schneider Electric One High Street, North Andover, MA 01845 USA 2 +1
Telephone: IN 2 978 975 9600 PORT
BEFOREFax: +1 978 975 9674
SERVICING. www.schneider-electric.com/buildings
SHIELD 19
3 RET UNIVERSAL
SDS-B3865/866/885-A4.BU.N.EN.2.2007.0.00.CC A07 18
4 IN 3 INPUTS
ANALOG
This equipment complies with part 15 OUTPUTS RET 17
5 IN 4 of the FCC rules. Operation is subject
to the following two conditions. 0-10 VDC
04

BACnet b3865/866/885-V VAV Controllers


with Built-in Actuator
Features (continued)

Connection Labels
Damper Actuator
The integrated damper actuator allows simple
865-V
(LOW)

AIR FLOW
direct mounting of the controller directly over the (HIGH)
INPUT

existing damper shaft. This eliminates the need


for separate mounting, wiring, and positioning of CAUTION COM 18
the damper motor. Also, the actuator has a built-in 1 IN 1 MORE THAN ONE DISCONNECT
SWITCH MAY BE REQUIRED RS-485
TO DE-ENERGIZE THIS EQUIPMENT COM 17
clutch button to temporarily disengage the direct- 2 IN 2
BEFORE SERVICING.
PORT
SHIELD 16
drive gears during commissioning. The controller 3 RET UNIVERSAL
4 INPUTS
actuator may be preset for a limited range of IN 3
This equipment complies with part 15
5 IN 4 of the FCC rules. Operation is subject
motion using the mechanical stops provided. to the following two conditions.
(1) This device may not cause harmful
6 RET interference.
(2) This device must accept any
interference received, including
interference that may cause TRIAC REF 15
7 SPWR undesired operation.
Software Capabilities 8 RET
SMART
DIGITAL
OUTPUTS
OUT5 14
SENSOR
The dynamic memory of the b3865/866/885-V 9 IN 5
24VAC , OUT4 13
0.5A
controllers can be allocated for any combination 10 2 4VAC
USE COPPER CONDUCTORS ONLY OUT3 12
INPUT: CLASS 2 POWER ONLY
of programs, scheduling, alarming, and data 11 24VAC , 0.42A, 10VA, 50/60HZ

logging using the powerful Andover Plain English


programming language. Our object-oriented Plain
English language with intuitive keywords provides
866-V
(LOW)

AIR FLOW
an easy method to tailor the controller to meet your INPUT
(HIGH)

exact requirements. Programs are entered into the


controller using Andover Continuum CyberStation.
CAUTION
Programs are then stored and executed by the 1 IN 1 MORE THAN ONE DISCONNECT
SWITCH MAY BE REQUIRED
COM 21
RS-485
COM 20
controller. Programming multiple b3865/866/885-V 2 IN 2 TO DE-ENERGIZE THIS EQUIPMENT
BEFORE SERVICING.
PORT
SHIELD 19
controllers is inherently easy with Plain English. 3 RET UNIVERSAL
INPUTS A07 18
A complete copy of one controllers programs can 4 IN 3 ANALOG
This equipment complies with part 15 OUTPUTS RET 17
5 IN 4
be loaded directly into other controllers without of the FCC rules. Operation is subject
to the following two conditions.
(1) This device may not cause harmful
0-10 VDC
AO6 16
6 RET interference.
changing any point names or programs. (2) This device must accept any
interference received, including
interference that may cause TRIAC REF 15
7 SPWR undesired operation.
DIGITAL
SMART OUT5 14
8 RET OUTPUTS
Smart Sensor Interface 9 IN 5
SENSOR 24VAC , OUT4 13
0.5A
The b3865/866-V controllers provide a built-in 10 2 4VAC
USE COPPER CONDUCTORS ONLY OUT3 12
INPUT: CLASS 2 POWER ONLY
connection for an Andover Continuum Smart 11 24VAC , 0.42A, 10VA, 50/60HZ

Sensor. The Smart Sensor provides a two-character


LED display and a six-button programmable
keypad that enables operators and occupants to
885-V
(LOW)

AIR FLOW
change setpoints, balance VAV boxes, monitor INPUT
(HIGH)
occupancy status, and turn equipment on and off.
An enhanced version of the Smart Sensor is also
available with a four-digit custom LCD that provides 1 IN 1
COM 12
RS-485
the following icons: PM, %, , Setpoint, Cool, Heat, 2 IN 2
UNIVERSAL
INPUTS
PORT
COM 11

SHIELD 10
CFM, Fan, OA, and SP. 3 RET CAUTION
MORE THAN ONE DISCONNECT
SWITCH MAY BE REQUIRED
TO DE-ENERGIZE THIS EQUIPMENT
BEFORE SERVICING.
This equipment complies with part 15
of the FCC rules. Operation is subject
to the following two conditions. TRIAC REF 9
(1) This device may not cause harmful
interference.
(2) This device must accept any DIGITAL
interference received, including NOT USED 8
interference that may cause OUTPUTS
undesired operation.
24VAC , OUT4 7
0.5A
USE COPPER CONDUCTORS ONLY OUT3 6
4 2 4VAC
INPUT: CLASS 2 POWER ONLY
5 24VAC , 0.42A, 10VA, 50/60HZ

Schneider Electric One High Street, North Andover, MA 01845 USA Telephone: +1 978 975 9600 Fax: +1 978 975 9674 www.schneider-electric.com/buildings

SDS-B3865/866/885-A4.BU.N.EN.2.2007.0.00.CC
05

BACnet b3865/866/885-V VAV Controllers


with Built-in Actuator
Specifications

b3865/866/885-V Controller
Electrical User LEDs Universal Inputs
Power Status Indicator LEDs: Connections
24 VAC, +10%-15%, 50/60 Hz, CPU CPU Active Model b3865-V: Four inputs and
Class 2 Limited Power Green = Active two returns
Power Consumption Model b3866-V: Four inputs and
Less than 10 VA Airflow Input two returns
Overload Protection Range Model b3885-V: Two inputs and
Fused, MOV protected 0 to 1 W.C. (0-250 Pa) one return
Resolution Input Voltage Range
Mechanical 0.0013 W.C. (0.33Pa) @ 73F (23C) 0 to 5.115 VDC
Operation Environment Accuracy Input Impedance
32 to 122F (0-50C), 0.05 W.C. (12.50 Pa) @ 73F (23C) 10K ohm to 5.120 V
10 - 90% RH (non-condensing) Input Voltage Resolution
Dimensions Damper Shaft Mounting Screws 5.0 mV
7.75 W x 6.25 L x 2.5 H Torque Minimum Digital Resolution
(197 mm W x 159 mm L x 63 mm H) Varies according to shaft material 10 bits
Weight Torque Maximum Input Voltage Accuracy
2.50 lbs (1.04 kg) 30 inch-pounds (3.4 Nm) 15mV
Hex Screws Temperature Range
Battery 10-32 (with supplied hex wrench) -30 to 230F (-34 to 110C)
Replaceable, rechargeable battery. Damper Actuator Motor Temperature Accuracy
Provides 30 days typical accumulated Shaft Diameter 1 F from -10 to 150F
power failure backup of RAM memory. 1/2 (with a 3/8 adapter) ( 0.56C from -23 to +66C)
All data stored in Flash on power loss. 12.6 mm (with a 9.45 mm adapter) Counter Frequency
Shaft Torque 4 Hz @ 50% duty cycle
Communications 53 inch-pounds (5.989 Nm) Input Protection
RS-485 port for implementing Damper Speed 1000 V transients
BACnet MS/TP connection, including: 180 sec. @ 60 Hz and 216 sec @ 50 Hz: Input Filter
Three-position removable screw terminal for 90 adjustable end limits with two 16 Hz with one pole RC filter
Standard service port, four-position set screws Connector
shrouded connector Motor Removable, 5 mm screw terminal
LEDs: Type: 24 VAC synchronous
TD = Transmit Enable Motor Protection: Mechanical clutch
RD = Received Data Manual clutch override with a
Wired/Wireless Field Bus push-button release
RS-485 port for implementing Hardware position feedback
Wireless BACnet connection, including: (model b3866-V only)
Standard service port, four-position
shrouded connector

Schneider Electric One High Street, North Andover, MA 01845 USA Telephone: +1 978 975 9600 Fax: +1 978 975 9674 www.schneider-electric.com/buildings

SDS-B3865/866/885-A4.BU.N.EN.2.2007.0.00.CC
06

BACnet b3865/866/885-V VAV Controllers


with Built-in Actuator
Specifications (continued)

b3865/866/885-V Controller
Smart Sensor Interface Analog Outputs Agency Listings
Connections Connections FCC Rules and Regulations CFR 47,
Model b3865-V: One input, Model b3865-V: Not available Part 15, Class A, ICES-003,
SPWR, and return Model b3866-V: Two analog outputs AS/NZS 3548, European Union (EU)
Model b3866-V: One input, and one return Directive 2002/96/EC
SPWR, and return Model b3885-V: Not available
Model b3885-V: Not available Analog Output Channels Required Models
Digital Outputs Two, voltage only b3865-V
Connections Voltage Output Range BACnet 865-V VAV Controller
Model b3865-V: Three triac outputs 0 10 V b3866-V
and one reference Output Source Current BACnet 866-V VAV Controller
Model b3866-V: Three triac outputs 5 mV Maximum b3885-V
and one reference Voltage Output Load BACnet 885-V VAV Controller
Model b3885-V: Two triac outputs 2K ohm Minimum Impedance b3865-V-WL
and one reference Voltage Output Resolution Wireless BACnet 865-V VAV Controller
SPST Accuracy 50 mV b3866-V-WL
0.1 second for pulse width modulation Digital Resolution Wireless BACnet 866-V VAV Controller
Contact Ratings 8 bits b3885-V-WL
0.5 A Maximum, 24 VAC Output Voltage Accuracy Wireless BACnet 885-V VAV Controller
Connector 100 mV
Removable, 5mm screw terminal Connector
Removable, 5mm screw terminal

2007-2009 Schneider Electric. All rights reserved.

All brand names, trademarks and registered trademarks are the property of their respective owners. Information contained within this document is subject to change
without notice.
On October 1st, 2009, TAC became the Buildings Business of its parent company Schneider Electric. This document reflects the visual identity of Schneider Electric,
however there remains references to TAC as a corporate brand in the body copy. As each document is updated, the body copy will be changed to reflect appropriate
corporate brand changes.
Schneider Electric One High Street, North Andover, MA 01845 USA Telephone: +1 978 975 9600 Fax: +1 978 975 9674 www.schneider-electric.com/buildings

SDS-B3865/866/885-A4.BU.N.EN.2.2007.0.00.CC February 2007 pdw


Andover Continuum TM

b3920 System
Controllers

The Andover ContinuumTM b3920 series controllers are native


BACnet controllers that communicate on an RS-485 field bus as
Master devices using the MS/TP BACnet protocol.
02

Andover Continuum
b3920 System Controllers
Features

The b3920, which is designed for control of


large Air Handling Units, chillers, boilers, and
other mechanical plant equipment, features
plenty of dynamic memory for application
programs as well as for expanded local data
logging of critical data. The b3920 also
features a fast 32-bit processor, universal
inputs, override switches on all outputs,
two-piece removable connectors, and an
optional 4-line display with keypad. The
b3920, similar to other Andover Continuum
BACnet controllers, has an additional room
sensor input, which supports Andovers
Smart Sensor, or any standard room
Product AT A GLANCE temperature sensor.

Native BACnet MS/TP Communications for As a native BACnet controller, the b3920 series can
Interoperability to Third-Party Systems communicate with other BACnet devices on the
Supports 18 BACnet Object Types including MS/TP network, in strict accordance with ANSI/
Trends, Schedules, Calendars, and Loops ASHRAE standard 135-2004, and are listed with the
Powerful, Flexible System Controller for the
BACnet Testing Labs (BTL) as BACnet Advanced
Most Demanding Applications
Application Controllers (B-AAC). By connecting to
Andovers Continuum b4920 device or bCX1, the
Expandable I/O Meets Additional Point b3920 and other MS/TP devices can share data
Count Needs from the wider Ethernet/IP network of controllers.
Non-Volatile Flash Memory Provides Utmost
Reliability Stores Both Application Program Increased Reliability with Flash Memory
and Operating System The b3920s non-volatile Flash memory stores your
Optional Local Display/Keypad Provides Easy
operating system and application programs, so that
Operator Interface
in the event of a power loss, your application will
be restored when power is returned. In addition,
Local, Extended Storage of Log Data the Flash memory allows for easy upgrades of
View and Modify Information with Optional your operating system via software downloads,
Smart Sensor Display eliminating the need to swap out proms.
BTL Listed B-AAC Controller with Local Trends

Schneider Electric One High Street, North Andover, MA 01845 USA Telephone: +1 978 975 9600 Fax: +1 978 975 9674 www.schneider-electric.com/buildings

SDS-B3920-A4.BU.N.EN.10.2005.0.00.CC
03

Andover Continuum
b3920 System Controllers
Features (continued)

Inputs Dimensional Drawings


The input configuration on the b3920 series
consists of sixteen full range, 12-bit Universal inputs

that accept voltage (0-10VDC), digital (on/off), 
counter signals (up to 4Hz), temperature signals, or  
supervised alarm circuits for security applications.  
The b3920 offers an additional input to support
the Andover Smart Sensor or any standard room 

temperature sensor.
1
!# 0/7%2
 .   6!#
6!
 (:
 ,

Outputs
The b3920 contains 16 outputs - eight Form C relay
outputs, each rated for 24 VAC/VDC, 3 amp, and
4
3%26)#%
0/24
2$

eight analog outputs (0-10V, 4-20mA). Both the relay 2


23 

4$

 3(,$

and analog outputs have manual override switches,


with software feedback of the switch position.
 5.)6%23!,
).0543


 2%4

 ). 

I/O Expansion
/&& /.
 ). 

 2%4


 ). 

 ).  

The b3920 contains an I/O expansion port for



 2%4 



 ). 

 ). 

the addition of up to two Andover xP expansion


 2%4


 ). 

 ). 

modules directly on the bottom of the controller.  2%4

 ). 

 ).  /&& /.

The xP family of modules includes the DI-8, D0-2,


 2%4

3

 ).  

 ).  

 2%4 

D0-4, UI-4, AO-2, and AO-4. In addition, the I/O bus



 ).  

 ). 

 2%4

supports the xP Local Display Module, which allows


 ). 

 ). 

 3072

the user to view and change point values. The Local


#05
 2% 4

 ). 

3-!24
3%.3/2

Display Module is also available factory-mounted


2%34!24

directly onto the b3920.




Schneider Electric One High Street, North Andover, MA 01845 USA Telephone: +1 978 975 9600 Fax: +1 978 975 9674 www.schneider-electric.com/buildings

SDS-B3920-A4.BU.N.EN.10.2005.0.00.CC
04

Andover Continuum
b3920 System Controllers
Features (continued)

Software Capabilities Dimensional Drawings


The dynamic memory of the b3920 can be allocated
for any combination of programs, scheduling,  /540543

alarming, and data logging using the powerful !# 0/7%2


 .
Andover Plain English programming language. Our   6!#
6!
 (:
object-oriented Plain English language with intuitive  ,

keywords provides an easy method to tailor


the controller to meet your exact requirements. 1 Power Drawing
Programs are entered into the b3920 using the
23 
Andover Continuum CyberStationTM. Programs are 
then stored and executed by the b3920 controllers.

 3(,$
Programming multiple b3920 controllers is
inherently easy with Plain English. A complete copy 2 Communications
of one b3920s programs can be loaded directly Drawing
into other b3920s without changing any point 5.)6%23!,
).0543
names or programs.
 2%4

 ). 
Smart Sensor Interface  ). 
/&& /.

The b3920 provides a built-in connection for  2%4




Andover Continuum Smart Sensor. The Smart  ). 


Sensor provides a 2-character LED display and  ).  

a 6-button programmable keypad that enables  2%4 

operators and occupants to change setpoints,  ). 

balance VAV boxes, monitor occupancy status, and  ). 

 2%4
turn equipment on and off. An enhanced version
 ). 
of the Smart Sensor is also available with a 4-digit
 ). 
custom LCD that provides the following icons: PM,
%, , Setpoint, Cool, Heat, CFM, Fan, OA, and SP.  2%4

 ). 

 ).  /&& /.
 2%4

 ).  

 ).  

 2%4 

 ).  

 ). 

 2%4
 ). 

 ). 

 3072
#05
 2% 4

 ). 
!.!,/'
/540543
3-!24 #522%.4/54054
3%.3/2
6/,4!'%/54054
2%34!24

3 Inputs/Smart Sensor 4 Outputs Drawing


Drawing

Schneider Electric One High Street, North Andover, MA 01845 USA Telephone: +1 978 975 9600 Fax: +1 978 975 9674 www.schneider-electric.com/buildings

SDS-B3920-A4.BU.N.EN.10.2005.0.00.CC
05

Andover Continuum
b3920 System Controllers
Specifications

b3920 System Controllers


Electrical Bus Length Digital Outputs
Power 4,000 ft. (1,220m) standard; 8 single pole single throw (SPST) Form C
115/230 VAC, +10% -15%, 50/60 Hz BACnet repeater allows extension relays (Any two consecutive Form C outputs
Power Consumption to longer distances. can be configured as one Form K Tri-state)
45 VA Bus Media Output Rating
Overload Protection Twisted, shielded pair, Maximum 3A, 24VAC/VDC, 1500V
Fused with 3 amp fuse. MOV protected low capacitance cable transients (Tested according to EN61000-4-4)
Real-Time Clock BACnet Device Profile Output Accuracy
Battery-backed real-time clock B-AAC, BACnet Advanced 0.1 sec. for pulse width modulation
Application Controller
Mechanical BTL Listed Analog Outputs
Operating Environment B-AAC with Local Trends 8 analog outputs
32120F (049C), Output Rating
1095% RH (non-condensing) Inputs 0-10V (5mA maximum, 2K ohm
Size 16 Universal inputs: Voltage (0-10 VDC); minimum impedance), or 4-20mA
13.00 H x 10.66 W x 2.72 D Temperature -30F to 230F per channel. Fuse-protected.
(330.2H x 270.8 W x 69.0 D) mm (-34C to 110C), Digital (on/off), 1000V transients
Weight Counter (up to 4Hz at 50% duty cycle, (Tested according to EN61000-4-4)
3.5 lbs. (1.58 kg) 125 ms min. pulse width). Supervised Alarm Output Resolution
Enclosure Type (single or double resistor). Current input 0.1V for 0-10V; 0.1mA for 4-20mA
UL Open class, IP 10. (0 - 20 mA) using external 500 ohm resistor Output Overrides
Flammability rating of UL94-5V 1 Smart Sensor Temperature Input Each output is equipped with a manual
Mounting (32F to 105F) (0C to 41C) override switch. Software feedback of the
Panel mount Input Voltage Range switch position is provided, for display
0-10 volts DC and alarming
Battery Backup Input Impedance Expansion Bus
Replaceable, non-rechargeable, 30.1K ohm to 10V or 5M ohm Interfaces to optional xP I/O
lithium battery. Provides 5 years typical with pull-up resistor disabled Expansion Modules
accumulated power failure backup of Input Protection
RAM memory 24 VAC or 24 VDC temporarily on
any single channel, 1000V transients
Communications (Tested according to EN61000-4-4)
Communications Interface Input Resolution
RS-485 BACnet, MS/TP 2.5 mV
127 devices maximum Input Accuracy
Communications Speed 7.5mV (0.25C from -23C to +54C) or
9600, 19.2K, 38.4K, 76.8K baud (0.46F from -10F to +130F)

Schneider Electric One High Street, North Andover, MA 01845 USA Telephone: +1 978 975 9600 Fax: +1 978 975 9674 www.schneider-electric.com/buildings

SDS-B3920-A4.BU.N.EN.10.2005.0.00.CC
06

Andover Continuum
b3920 System Controllers
Specifications (continued)

b3920 System Controllers


Connections User LEDs/Switches General
Power Status Indicator LEDs Memory
3-position fixed screw terminal connector CPU CPU Active 1MB SRAM, 2MB FLASH
Inputs TD Transmit Data Processor
Removable two-piece terminal strip RD Receive Data Motorola 32-bit Coldfire
Outputs Output Output Status
Removable two-piece terminal strip (per output) Agency Listings
Smart Sensor EXPANSION UL/CUL 916, FCC CFR 47 Part 15,
Removable two-piece terminal strip PORT PWR Power Status ICES-003, EN55022, AS/NZS 3548,
Communications OVERRIDE Override Status Class A, CE
Removable two-piece terminal strip Switches
Expansion Port RESET Options
6-position shrouded connector Input Pull-up Resistor Switch (per input) UL864, Smoke Control System Equipment,
Service Port Individual Output Override Switches UUKL (b3920-S)
4-position shrouded connector

2005-2009 Schneider Electric. All rights reserved.

All brand names, trademarks and registered trademarks are the property of their respective owners. Information contained within this document is subject to change
without notice.
On October 1st, 2009, TAC became the Buildings Business of its parent company Schneider Electric. This document reflects the visual identity of Schneider Electric,
however there remains references to TAC as a corporate brand in the body copy. As each document is updated, the body copy will be changed to reflect appropriate
corporate brand changes.
Schneider Electric One High Street, North Andover, MA 01845 USA Telephone: +1 978 975 9600 Fax: +1 978 975 9674 www.schneider-electric.com/buildings

SDS-B3920-A4.BU.N.EN.10.2005.0.00.CC October 2005 pdw


BACnet
bCX1 Controller/
Router Series

The Andover ContinuumTM bCX1 Series is a series of Native BACnet


routers and controller/routers which heads up the BACnet family
of Andover Continuum controllers. These controllers reside at
the network level and route BACnet messages between BACnet/
IP, BACnet over Ethernet and MS/TP networks and can serve as
a BACnet Broadcast Management Device (BBMD) allowing for
routing of messages between IP networks.
02

BACnet bCX1 Controller/Router Series


Features

There are two basic bCX1 models: the


bCX1-R (Router Only) and the bCX1-CR
(Controller/Router). The bCX1-R model
provides all the functionality to route
messages between BACnet networks and
the bCX1-CR is a full-function BACnet
Building Controller (B-BC). The bCX1-CR
performs the routing functions of the
bCX1-R with the additional power of a
programmable controller with expansion
I/O capabilities.
PRODUCT AT A GLANCE All BCX1 Models (BCX1-R and BCX1-CR):
Native BACnet
B-BC BACnet Building Controller available As Native BACnet controllers developed in strict
in Router-only and Router/Controller combo accordance with the ASHRAE 135-2004 BACnet
models standard, the bCX1 can communicate directly with
other third partyBACnet/IP and BACnet MS/TP
Supports 18 BACnet object types including
devices as well as all Andover Continuum BACnet
Trends, Schedules, Calendars, and Loops
devices. The bCX1 also supports BACnet over
Native BACnet/IP and MS/TP communications Ethernet, allowing devices that communicate with
for interoperability to third-party systems the earlier versions of the BACnet Specification to
10/100 Ethernet port also communicate withBACnet/IP devices.

BACnet Broadcast Message Device


Easy Configuration
(BBMD) support
The bCX1 is designed with ease-of-installation
Expandable for local I/O and display using in mind. All configuration settings are done via
xP Expansion Modules a standard web browser set the IP address,
Advanced Flash Memory provides utmost and save to Flash. All connections to the bCX1
reliability stores application program, series controller are accomplished with removable
operating system, and run-time data connectors for easy installation, providing the ability
to pre-wire panels and service the unit simply.
Flash memory allows easy online software
LEDs provide troubleshooting information and
updates
communication activity for all ports.
Support for custom Embedded Web Server

Support for 2nd Generation Andover BBMD Support


Continuum XDrivers All bCX1 Series devices can be configured to
function as BACnet Broadcast Management
BTL Listed B-AAC Controller with local Trends
Devices, or BBMDs. It is the BBMDs job to pass
BACnet broadcasts across IP/Routers to other IP
segments. As a result of having a BBMDs in place,
BACnet devicesare able to fully communicate via
the Internet.

Schneider Electric One High Street, North Andover, MA 01845 USA Telephone: +1 978 975 9600 Fax: +1 978 975 9674 www.schneider-electric.com/buildings

SDS-BACNET-BCX1-A4.BU.N.EN.7.2008.0.00.CC
03

BACnet bCX1 Controller/Router Series


Features (continued)

Advanced Flash Memory Management Dimensional Drawings


The bCX1 Series uses non-volatile Flash memory
to store the operating system and application
programs. When a power loss in sensed, an
on-board battery maintains all logs, trends, and
other run-time data. When power is restored, both
application and run-time data are restored. Memory
backup or restore settings are configurable.
The Flash-based operating system simplifies
feature upgrades.

Controller/Router Combo Models (BCX1-CR)


BTL Listed BACnet Building Controller (B-BC)
The bCX1-CR is listed with the BACnet Testing
Laboratories (BTL) as a BACnet Building Controller
or B-BC, with interoperability BACnet Data Sharing,
Alarm and Event Management, Scheduling,
Trending, and Device Management.

Programmable
The dynamic memory of the bCX1-CR can
be allocated for any combination of programs
and BACnet object (including Schedules,
Alarms, and Trends). Our powerful Plain English
programming language can directly reference
any BACnet object either locally or globally.
Our object-oriented Plain English, with intuitive
keywords, provides an easy method to tailor the
controller to meet your exact requirements. As
a programmable controller, the bCX1-CR can
locally support a wide range of BACnet objects,
including BACnet loops, trends, and schedules.
Plain English programs may be created to
program coordinated control strategies, giving
you the freedom to move data between third party
devices that do not have peer to peer functionality
provided in all Andover Continuum controllers. Power Drawing RS-485 RS-232
Communications Communications
Embedded Web Server Drawing Drawing
With the power of Plain English, standard HTML
web pages can be created and embedded into the
bCX1-CR to provide a simple-to-use, browser-based
interface for monitoring or changing data points.
The embedded web pages are fully customizable
to meet any special customer requirements.

Schneider Electric One High Street, North Andover, MA 01845 USA Telephone: +1 978 975 9600 Fax: +1 978 975 9674 www.schneider-electric.com/buildings

SDS-BACNET-BCX1-A4.BU.N.EN.7.2008.0.00.CC
04

BACnet bCX1 Controller/Router Series


Features (continued)

Expansion I/O Features & Models bCX1-R bCX1-CR

The bCX1-CR contains an I/O expansion port for the Ports 3 3


addition of up to two xP expansion modules directly Ethernet 10/100 10/100
on the bottom of the controller. The xP family of Comm 1 Modem Modem, XDriver, Raw Port
modules includes the xPDI8, xPDO2, xPDO4, Comm 2 MS/TP MS/TP, Wireless BACnet,
xPAO2, xPAO4, xPUI4 as well as the xPBD4 and XDriver, Raw Port
xPBA4 expansion modules, which can only be used Routing
with the bCX1. In addition, the I/O bus supports the BBMD Yes Yes
xP Local Display Module, which allows the user to
BACnet/IP Yes Yes
view and change point values.
BACnet over Ethernet Yes Yes

SNMP Alarming Support MS/TP Yes Yes

All bCX1 controllers are compatible with SNMP Wireless BACnet Yes Yes
monitoring tools, which allow the controller to be MS/TP Node Options 64 0, 8, 32, 64, 127
interrogated for basic SNMP information. The CR Flash Memory Yes Yes
model features advanced SNMP alarm functionality xP Expansion I/O No 2+ Display
as an option (SA), providing alarm delivery for any
Plain English No Yes
device on the MS/TP network it manages.
XDriver Support No Yes
Email Support No Yes
XDriver Support
The BACnet bCX1 Controller/Router is available Web

with XDriver Support for 2nd generation Andover Basic Configuration Yes Yes
Continuum XDrivers to interface with third-party Embedded Web Server No Yes
devices. (Note: This feature is not available on the SNMP
Router Only version.)
SNMP Monitoring Yes Yes
SNMP Alarming No Optional
BACnet Device Profile Router Only B-BC
BTL Listed No

Schneider Electric One High Street, North Andover, MA 01845 USA Telephone: +1 978 975 9600 Fax: +1 978 975 9674 www.schneider-electric.com/buildings

SDS-BACNET-BCX1-A4.BU.N.EN.7.2008.0.00.CC
05

BACnet bCX1 Controller/Router Series


Specifications

bCX1 Controller/Router Series


Electrical Communications Connections
Power Communications Interface, Power
24VAC, +10% -15%, 50/60 Hz BACnet/IP: 3-position removable screw
12-28 VDC auto-sensing 10/100 BaseT* terminal connector
Power Consumption Communications Interface, Communications
40 VA, 25W BACnet MS/TP: Ethernet RJ-45
Overload Protection RS-485, 127 devices max Comm1: 9-pin D-Sub - female-DTE
Fused with 3 amp fuse. MOV protected Communications Interface, Comm2: RS-485 BACnet MS/TP:
Real-Time Clock Wireless BACnet: Removable 3-position
Battery-backed real-time clock RS-485, 32 devices screw terminal connector
Communications Speed, RS-485 Wireless BACnet:
Mechanical BACnet MS/TP 4-position shrouded
Operating Environment 9600, 19.2K, 38.4k, 76.8k baud connector (Service Port)
32120F (049C), RS-485 Bus Length (if RS-485 port is not used):
1095% RH (non-condensing) 4,000 ft. (1,220m) standard; RJ-45 8-pin (only 3 of the 8 pins
Size BACnet repeater allows extension are supported - RXD, TXD, GND)
Module: 5.47 H x 8.39 W x 2.43 D to longer distances. Expansion Port
(139H x 213 W x 62 D) mm RS-485 Bus Media 6-position shrouded connector
Weight Twisted, shieldedpair,
Module: 1.12 lb (0.508 kg) low capacitance cable User LEDs/Switches
Enclosure Type *Note: Auto-sensing cable polarity Status Indicator LEDs
UL Open class, IP 20. BACnet Device Profile CPU CPU Active
Flammability rating of UL94-5VB B-BC, BACnet Building Controller Green = BACnet
Mounting BTL Listed COMM1:
Panel mount B-BC TD-232 Transmit Data-RS-232
WSPCert Listed RD-232 Receive Data-RS-232
Battery B-BC DCD-232 Data Carrier Detect
Battery Backup RTS-232 Request to Send
Replaceable, rechargeable battery. ETHERNET Link/Act
Provides 30 days typical accumulated 10/100 Mbps
power failure backup of RAM memory. COMM2:
All data stored in Flash on power loss. TD-485 Transmit Data-RS-485
RD-485 Receive Data-RS-485
EXPANSION
PORT PWR Power Status
Switches
CPU RESET
IP ADDRESS RESET

Schneider Electric One High Street, North Andover, MA 01845 USA Telephone: +1 978 975 9600 Fax: +1 978 975 9674 www.schneider-electric.com/buildings

SDS-BACNET-BCX1-A4.BU.N.EN.7.2008.0.00.CC
06

BACnet bCX1 Controller/Router Series


Specifications (continued)

bCX1 Controller/Router Series


General Models Options
Memory BACnet Router -SA SNMP Alarming Option
32MB SDRAM, 16MB FLASH BCX1-R-64 -X1 XDriver Option (Ethernet & Comm1)
Processor BACnet Router, 64 Node MS/TP Support -X2 XDriver Option (Ethernet & Comm2
Motorola 32-bit Coldfire, 66 MHz BACnet Controller/Routers -X12 XDriver Option (Ethernet, Comm1 &
Network Setup BCX1-CR-0 Comm2)
Via embedded web interface Controller/Router, 0 Node Support -S Smoke Control Option
Note: bCX1 REQUIRES CyberStation BCX1-CR-8
software v1.7 version (or later): Controller/Router, 8 Node Support
v1.82 (or later) is required for BCX1-CR-32
XDriver support. Controller/Router, 32 Node Support
BCX1-CR-64
Agency Listings Controller/Router, 64 Node Support
UL/CUL 916, UL 864 9th Edition, FCC CFR BCX1-CR-127
47 Part 15, ICES-003, EN55022, AS/NZS Controller/Router, 127 Node Support
3548, Class A, VCCI, EN61000-6-1, CE

2008-2009 Schneider Electric. All rights reserved.

All brand names, trademarks and registered trademarks are the property of their respective owners. Information contained within this document is subject to change
without notice.
On October 1st, 2009, TAC became the Buildings Business of its parent company Schneider Electric. This document reflects the visual identity of Schneider Electric,
however there remains references to TAC as a corporate brand in the body copy. As each document is updated, the body copy will be changed to reflect appropriate
corporate brand changes.
Schneider Electric One High Street, North Andover, MA 01845 USA Telephone: +1 978 975 9600 Fax: +1 978 975 9674 www.schneider-electric.com/buildings

SDS-BACNET-BCX1-A4.BU.N.EN.7.2008.0.00.CC July 2008 pdw


Economy Duct and Wall
CO2 Sensors
Field-Selectable 4-20mA/0-10VDC Output
APPLICATIONS
Controlling ventilation in response to occupancy CDE
Facilitating compliance with ASHRAE 62.1 standard for air quality
Office buildings, conference rooms, schools, retail stores, etc.
CWE

FEATURES
Microprocessor design increases accuracy and reduces installation time
DESCRIPTION
3Year Warranty

Non-dispersive infrared technology repeatable to 20 ppm 1% of


The CDE/CWE are non-dispersive infrared (NDIR) analyzers designed for measuring
measured value environmental CO2 concentration in ventilation systems and indoor living spaces.
Innovative self-calibration algorithm...easy to maintain
Their measurement range of 0-2000ppm makes them compliant with ASHRAE and
other standards for ventilation control
5-year calibration interval (recommended)
Low ambient sensitivity The CWE/CDE Series provides a user-selectable 4-20mA or 0-10VDC output for
Alarm relay with setpoint for direct ventilation control versatility. Microprocessor-based digital electronics and a unique self-calibration
Output 4-20mA/0-10V for flexible control system interface algorithm improves long-term stability and accuracy.
3-year factory warranty from date of purchase

SPECIFICATIONS
Input Power 20 to 30VDC/24AC; 100mA Maximum
AIR QUALIT Y

Analog Output 4-20mA, (clipped and capped)/0-10VDC (selectable)


Operating Temperature Range 0 to 50C (32 to 122F)
Housing Material High impact ABS plastic
Sensor Type Non-dispersive infrared, diffusion sampling
Measurement Range 0-2000 ppm
Accuracy 30 ppm 2% of measured value*
Repeatability 20 ppm 1% of measured value
Response Time <60 seconds for 90% step change

EMC Conformance: Low voltage directive 2006/95/EC and EMC directive 2004/108/EC.
EMC Special Note: Connect this product to a DC distribution network or an AC/DC power adaptor with proper SURGE PROTECTION (EN 61000-6-1:2007 specification requirements).
* Measured at NTP

800.354.8556 +1 503.598.4564 www.veris.com 2010 Veris Industries


07101
APPLICATION/WIRING DIAGRAMS
CWE Wall Mount CDE Duct Mount

CALIBRATION
PUSHBUTTON
CO2-OUT
V+ GND

LED

Power (+24) N/A


CO2 OUT RTD
COMMON
RTD
CONDUIT ADAPTER

1/2 NPT MALE/FEMALE

Optional *
* Note: Connector blocks and headers for optional features are not included with non-option models.

DIMENSIONAL DRAWINGS
CWE Wall Mount CDE Duct Mount

6.7" 10.2"
(170 mm) (258 mm)

AIR QUALIT Y
4.8"
(122 mm) 3.1"
(78 mm)

2.4" 7.8"
(61 mm) (97 mm)

3.5" 1.2"
(89 mm) (30 mm)

ORDERING INFORMATION all models


Duct Mount Wall Mount
Sensor Type
CDE (No Options) CWE
SB = 100R Platinum, RTD
SC = 1k Platinum, RTD
SD = 10k T2, RTD, Thermistor Example:
SE = 2.2k, Thermistor
SF = 3k, Thermistor CWE SH
SG = 10k CPC, Thermistor
SH = 10k T3, Thermistor
SJ = 10k Dale, Thermistor
SK = 10k w/11k shunt, Thermistor
SM = 20k NTC, Thermistor
SN = 1800 ohm, Thermistor
SR = 10k US, Thermistor
SS = 10k 3A221, Thermistor
ST = 100k, Thermistor ACCESSORIES
SU = 20k D Thermistor Calibration kits and gases (AA01, AA26, AA27, AA28, AA29)
Handheld air quality testers (1010, 1008, 770)

800.354.8556 +1 503.598.4564 www.veris.com 2010 Veris Industries


07101
ET Series

Temperature Sensors

General Instructions
APPLICATION

Thermistors offer high accuracy and interchange-


ability over a wide temperature range. The ET
series can be used in the following applications:
Space
Duct
Immersion
Averaging
Strap-On
Bead/Bullet
Outdoor Air

FEATURES

Offer high accuracy and interchangeability


over a wide temperature range.
Non-polarity sensitive
ET Series Photo
SPECIFICATIONS
For TAC Vista, I/NET, Continuum, and 1000 Ohm Platinum 1000 Ohm BALCO
I/A
Output 1.8K Ohms @ 77 F (25 C) Vista 1K Ohms @ 32F (0C) 1000 Ohms @ 70F (21C)
10K Ohms @ 77 F (25 C) I/Net
10K Ohms @ 77 F (25 C) Continuum
10K Ohms @ 77 F (25 C) with 11K
Ohms shunt resistor I/A
Temperature Range -40 to 302 F (-40 to 150 C) -58 to 392F (-50 to 200C) -40 to 240F (-40 to 116C)
-50 to 275F (-45.5 to 134.8C)
Interchangeability +/- 0.2 C (0 to 70 C)
Dissipation Constant 3 mW / C
Stability
Accuracy +/- 0.2 C (0 to 70 C) +/- 0.06% @ 32F (0C) Single Point +/- 0.1%
+/- 1.0 Ohm @ 70F (Averaging)

Operating Humidity 0 to 90% RH non-condensing

0RINTEDINTHE53! #OPYRIGHT3CHNEIDER%LECTRIC!LL2IGHTS2ESERVED&  


DIMENSIONS

#OPYRIGHT3CHNEIDER%LECTRIC!LL2IGHTS2ESERVED&  
INSTALLATION
ROOM TEMPERATURE SENSORS
This unit is suitable for either drywall mounting or junction box mounting. The room sensor is provided with screw terminal blocks for all connections. Re-
move the cover from the unit and mount the housing base to the wall using the (2) 6/32 x 1 machine screws. Replace the cover and tighten down, using
the (2) 1/16 Allen Screws located on the bottom of the enclosure.

DUCT AND DUCT AVERAGING SENSORS


Duct temperature sensors - drill a 3/8 hole in the duct and insert the probe through the hole until the foam pad is tight to the duct. Now insert (2) screws
through the mounting holes in ange and tighten them until the unit is held rmly to the duct. Duct Averaging sensors - Drill a 3/8 hole in the duct and
insert the averaging element through the hole until the foam pad is tight to the duct. Now insert the (2) screws through the holes in the mounting ange
and tighten until the unit is held rmly to the duct. The sensor should then be strung in a criss-cross pattern throughout the duct using the mounting clips
provided, in a pattern that covers the greatest surface area of the duct, to insure that there is no stratication. When bending the copper tubing, be careful
that you use a gradual bend and that you DO Not kink the copper tubing.

IMMERSION TEMPERATURE SENSORS


The TAC Fluid Immersion-type sensors are provided with a 2 , 4, or 6 insertion length, 304 series stainless steel thermowell. The thermowell has a
1/2 NPT external or process thread and a 1/2 NPT internal or instrument thread. Heat transfer compound may be used but it is not necessary.

STRAP-ON TEMPERATURE SENSORS


The TAC Strap-On sensors, are provided in a NEMA 1 rated junction box with an adjustable 2 to 5 pipe clamp. The unit should be mounted on the bottom
side of the pipe to ensure proper heat transfer and a true temperature reading. Heat transfer compound and insulating the sensor will help the overall ac-
curacy of the sensor. By ordering extra straps, and fastening them together, it is possible to make them t larger pipes.

OUTSIDE AIR TEMPERATURE SENSORS


The TAC Outdoor Air temperature sensors are provided in a weatherproof enclosure. An optional weatherproof Aluminum Bell Box or NEMA 4X Polycarbon-
ate enclosure is also available upon request for an additional charge. All of the mounting hardware is provided with the sensor. Be sure to mount the sensor
out of direct sunlight, with the sensor probe pointing downward.

STAINLESS PLATE TEMPERATURE SENSORS


The TAC Stainless Plate temperature sensors are mounted on the back of a 1 Gang stainless steel plate. The foam pad will insulate the sensor from any drafts
in the wall. (2) 6/32 x 1 machine screws are provided for junction box mounting. Be sure that the sensor is not mounted on an outside wall, due to the
extreme temperature changes from either drafts or heat transfer.

WIRING DIAGRAMS
Diagram for ETR Sensors
Tenant Override Output to
Controller (Separ ate Input Only)
Tenant Override Output to
Setpoint Output to Controller Controller (Separ ate Input Only)

Setpoint Output to Controlle


r

Short Sensor
Thermistor and Override
Output to Controller Separate Input
J3
Thermistor and Override J2
Output to Controller Membrane SW1
Gnd + - SE T O/R
Wire Access Hole
After Hours Normally-Open
1 2 3 4
Override Switch
Communication Jack
Override Options Jumper Settings (J3)
Terminals for RJ11 Communications Override Short Separ ate Input
Sensor (Dr y Contact Closur e )
Short Sensor Short Sensor
c Multi4 Rev 7 Separate Input Separate Input
Fi gure #1

Diagram for ET Sensors Except ETR

Sensor Output to Controller Sensor Output t


Controller
C SE NS OR 2
S1
Sensor
2W - +

&  #OPYRIGHT3CHNEIDER%LECTRIC!LL2IGHTS2ESERVED 


ORDERING INFORMATION
Temperature Sensor TAC Vista I/NET Continuum I/A 1000 Ohm 1000 Ohm
Description Platinum BALCO
Room ETR100 ETR200 ETR500 ETR800 - -
Room with Setpoint ETR101 ETR201 ETR501 ETR801 - -
Room with Override Pushbutton ETR102 ETR202 ETR502 ETR802 - -
Room with Setpoint and Override Pushbutton ETR103 ETR203 ETR503 ETR803 - -
Wallplate (Stainless Steel) ETP100 ETP200 ETP500 ETP800
4 Duct (Galvanized Steel Enclosure) ETD100-4 ETD200-4 ETD500-4 ETD800-4 ETDPK0-4 ETDBK0-4
6 Duct Galvanized Steel Enclosure) ETD100-6 ETD200-6 ETD500-6 ETD800-6 ETDPK0-6 ETDBK0-6
8 Duct (Galvanized Steel Enclosure) ETD100-8 ETD200-8 ETD500-8 ETD800-8 ETDPK0-8 ETDBK0-8
12 Duct (Galvanized Steel Enclosure) ETD100-12 ETD200-12 ETD500-12 ETD800-12 ETDPK0-12 ETDBK0-12
4 Duct without Enclosure ETD100-NE-4 ETD200-NE-4 ETD500-NE-4 ETD800-NE-4 ETDPK0-NE-4 ETDBK0-NE-4
6 Duct without Enclosure ETD100-NE-6 ETD200-NE-6 ETD500-NE-6 ETD800-NE-6 ETDPK0-NE-6 ETDBK0-NE-6
8 Duct without Enclosure ETD100-NE-8 ETD200-NE-8 ETD500-NE-8 ETD800-NE-8 ETDPK0-NE-8 ETDBK0-NE-8
12 Duct without Enclosure ETD100-NE-12 ETD200-NE-12 ETD500-NE-12 ETD800-NE-12 ETDPK0-NE-12 ETDBK0-NE-12
2 Immersion (Galvanized Steel Enclosure) ETI100-2 ETI200-2 ETI500-2 ETI800-2 ETIPK0-2 ETIBK0-2
4 Immersion (Galvanized Steel Enclosure) ETI100-4 ETI200-4 ETI500-4 ETI800-4 ETIPK0-4 ETIBK0-4
6 Immersion (Galvanized Steel Enclosure) ETI100-6 ETI200-6 ETI500-6 ETI800-6 ETIPK0-6 ETIBK0-6
8 Averaging (Flexible Copper) ETA100-8 ETA200-8 ETA500-8 ETA800-8 - -
12 Averaging (Flexible Copper) ETA100-12 ETA200-12 ETA500-12 ETA800-12 ETAPK0-12 ETABK0-12
24 Averaging (Flexible Copper) ETA100-24 ETA200-24 ETA500-24 ETA800-24 ETAPK0-24 ETABK0-24
Outside Air ETO100 ETO200 ETO500 ETO800 - -
Strap On ETS100 ETS200 ETS500 ETS800 - -
Bead / Bullet ETB100 ETB200 ETB500 ETB800 - -

Miscellaneous Options Code Well Type Part Number


LCD Display (for room units only) -LCD 2 Stainless Steel Well ETI-WELL-2S
LED Indicator -LED 4 Stainless Steel Well ETI-WELL-4S
(for room units with override only) 6 Stainless Steel Well ETI-WELL-6S
Thermometer Indicator (for room units only) -TI
RS232 Communication Jack -RS232
(for use with I/NET systems only)
Four-Pin RJ11 Communication Jack -RJ4
(for use with TAC Vista and Continuum sys-
tems only)

On October 1st, 2009, TAC became the Buildings business of its parent company Schneider Electric. This document reflects the visual identity of Schneider Electric,
however there remains references to TAC as a corporate brand in the body copy. As each document is updated, the body copy will be changed to reflect appropriate
corporate brand changes.

Copyright 2010, Schneider Electric Schneider Electric


All brand names, trademarks and registered 1354 Clifford Avenue
trademarks are the property of their respective P.O. Box 2940
owners. Information contained within this Loves Park, IL 61132-2940
document is subject to change without notice. www.schneider-electric.com/buildings
F-27
Infinity
Smart Sensor LED/LCD
Display Temperature Sensors

General Instructions

Smart Sensor LED/LCD


Display Temperature Sensors
Andover Controls Smart Sensor combines an attractive display with
a room temperature sensor to provide users with a cost effective
way to view or modify VAV box operation. It is designed for use
with the Andover Controls TCX 866 VAV controller and can also
accomplish many local control and monitoring tasks.
The standard Smart Sensor provides a two character LED display
and a 6 button programmable keypad that enables operators and
occupants to change setpoints, monitor occupancy status and turn
equipment on and off. An enhanced version of the Smart Sensor is
also available with a 4-digit custom LCD that provides the follow-
ing icons: PM, %, , Setpoint, Cool, Heat, CFM, Fan, OA, and SP.
The function keys can be custom programmed to perform a wide
variety of functions, including switching a specific zone to occu-
pied mode, signaling an alarm condition, adjusting the amount of
override time, arming or disarming a security system, and enforcing
password security. Programming the display and function keys is
done with Andover Controls Plain English programming lan-
guage.
The Smart Sensor comes in a well-ventilated plastic enclosure.
The active sensing element is a highly stable, precision thermistor,
accurate to within 0.36F. The sensor has an operating range of
32F to 105F (0C to 40C). Both versions of the Smart Sensor Smart Sensor LED/LCD
provide a connection for the Andover Controls Infinity Lap-Top
Service Tool.
Display Temperature Sensors

FEATURES
Accurate, Reliable Type III Thermistor
Two 7-Segment LED Display or Four Digit Custom
LCD Display
6-Button Programmable Keypad
Built-In Service Port for Andover Lap-Top Service Tool
Powered Directly from Andover Controls
TCX 866 VAV Controller

Printed in the U.S.A Copyright 2009. All Right Reserved. F-27636


SPECIFICATIONS

Sensing Element Type III Thermistor, 10,000 ohms @ 77F (25C)


Range 32F to 105F (0C to 40C)
Accuracy Thermistor 0.36F ( 0.2C)
Stability Thermistor will not deviate from accuracy spec for minimum of 5 years
Wire Specifications 18, 20, 22 or 24 gauge, 3 conductor, unshielded wire
An additional single pair twisted shielded is required for Lap-Top Service Tool connection
Maximum Distance to Sensor 18 gauge wire: 1,200 ft. with less than 0.18F (-17.67C) error
20 gauge wire: 790 ft. with less than 0.18F (-17.67C) error
22 gauge wire: 500 ft. with less than 0.18F (-17.67C) error
24 gauge wire: 300 ft. with less than 0.18F (-17.67C) error
Dimensions 4.50H x 3.50 W x 0.813D (11.5 cm H x 8.9 cm W x 2.0 cm D)
Color Off-white
Power One Smart Sensor is powered directly from Andover Controls TCX 866

ORDERING INFORMATION

Copyright 2009 TAC TAC


All brand names, trademarks 1354 Clifford Ave
and registered trademarks are P.O. Box 2940
the property of their respective Loves Park, IL 61132-2940
owners. Information contained
within this documentation is www.tac.com
subject to change without
notice. All rights reserved.

F-27636
Room Controllers

SE7300 Series

When compared to traditional building automation


controllers, the SE7300 series provides unmatched
return on investment to building owners while
maximizing profits for system integrators.

Smart energy management has never been easier


Product Highlights:
than with the SE7300 series fan coil controllers. Open protocol allows for easy integration into
Designed for new construction and retrofit projects, most network systems
the controllers dramatically decrease total installed Network Ready models can be retrofit with
costs by reducing installation, configuration and optional communication modules
commissioning time. The SE7300 series provides One simple wall mounted device to install, wire
the advanced features and monitoring functions and commission
required by modern building automation systems Intuitive thermostat like interface
without the use of software and commissioning Application specific controllers can be configured
tools. to meet most applications
The SE7300 fan coil controllers have been No special software required for configuration
specifically designed to provide exceptional Fully embedded local configuration utility
temperature control of multi-speed fan coil units Advanced occupancy and monitoring functions
with either on-off, floating or 0 to 10 Vdc valves. through factory or field installed PIR cover
Also available are advanced models with built-in Hospitality and commercial models available with
relative humidity (RH) sensing and dehumidification market specific HMI
strategies. Extended configurable fan sequences with
automatic fan mode
Open protocol design provides network
compatibility to BACnet MS/TP, Echelon Lontalk
and Wireless Zigbee network systems. Our Network
Ready stand-alone versions can be upgraded with
optional communication modules which enable
the controllers to be integrated into most building
automation systems as budgets allow or as the
building requirements change.

All models can be customized with PIR motion


sensor functionality via an optional PIR accessory
cover. The cover can be installed in the field or
ordered as a factory installed option. This provides
advanced occupancy routines and automatic energy
savings during occupied periods without sacrificing
occupant comfort.
2
Room Controllers SE7300 Series

Cooling coil 3-speed fan Heating coil Electric heater


C H
Return air

C C

Filter Fan
status status
switch switch

Open communication protocols


Optional wireless Zigbee communication

Typical fan coil application


(SE7300 series)

Market Specific HMI Tailors Product to Application

Commercial Application Hotel and Lodging Application

SE7300 Series Fan Coil Unit Controllers Matrix


Please refer to the following matrix when ordering controllers:

SE73 45
Humidity Sensor and PIR Options: Communication Options:
Control: -50 = PIR ready but PIR -B = BACnet MS/TP
-0 = No humidity sensor cover not included -E = Echelon
2011 Schneider Electric. All rights reserved.

-5 = Internal humidity -55 = Factory assembled -W = Zigbee wireless


sensor with PIR cover - = Network Ready

Compatibility:
Center Key Fuction: -C = Floating or on-off
-0 = Override, for commercial digital control outputs
applications -F = Analog 0-10 Vdc
-5 = C/F, for hotels control outputs
/ lodging applications

Schneider Electric 1354 Clifford Ave. Loves Park, IL 61111 1-888-444-1311 www.schneider-electric.com
F-27750 Sep 2011 bm
Current Switches:
Fixed Trip Point
H300
Split-Core & Solid-Core Go/No Go
Current Switches
APPLICATIONS
Monitoring status of electrical loads
Monitoring direct-drive units, exhaust fans, and other fixed loads
H600
Verifying lighting run times

FEATURES
H900
On/off status for direct-drive fans, pumps, and process motors 0.15 A H800
More reliable for status than relays across auxiliary contacts TURN-ON!
US Patent No. 7,193,428
Ideal for direct-drive units, unit vents, fan coil units, exhaust fans, and other
fixed loads
Great for lighting statusless expensive than 277V relays
Low 0.15A turn-on (H300 and H600)...ideal for small exhaust fans (not intended DESCRIPTION
5YearWarranty

to detect belt loss)


Hawkeye x00 go/no go current switches provide a cost-effective solution for
Removable mounting bracket provides installation flexibility
monitoring status on unit vents, exhaust fans, recirculation pumps, and other fixed
Bracket on H900 can be installed in three different configurations...installer loads where belt loss is not a concern.
convenience
Veris has applied new technology to the H300, H600, and H800 models to achieve
Monitor status of fans, pumps, motors & other electrical loads
CURRENT MONITORING

impressive improvement in turn-on levels. The Hawkeye H300 and H600 now have
Split-core H300, H600, and H900 for fast retrofit installation the lowest turn-on current in the industry at a mere 150mA!
Mini solid-core H800 and micro split-core H300 fit in tight enclosures...saves
valuable panel space
100% solid-state, no moving parts to fail
Polarity insensitive output
5-year limited warranty

Maximize Reliability
Minimize Installed Cost

SPECIFICATIONS
Sensor Power (N.O. Models) Induced from monitored current
Insulation Class 600VAC RMS (UL), 300VAC RMS (CE)
Frequency Range 50/60 Hz
Temperature Range H800, H800NC, H300, H900: -15 to 60C (5 to 140F)
H600: -15 to 40C (5 to 104F) (to 200A); -15 to 60C (5 to 140F) (to 150A)
H800HV: -40 to 50C (-40 to 122F) (to 200A); -40 to 75C (-40 to 167F) (to 100A, & 0.25A output)
Humidity Range 10-90% RH, non-condensing
Sensor Power (N.C. Models) 5-30VDC, permanently connected
Off State Leakage (N.C. Models) 34A@5VDC, 200A@30VDC
On State Voltage Drop (N.C. Models) 1.9VDC (max.) @0.1A
Terminal Block Maximum Wire Size 14 AWG (16 AWG for H300)
Terminal Block Torque (nominal) 4 in-lbs (7 in-lbs for H300)
Agency Approvals UL 508 open device listing; CE:EN61010-1:2001-02, CAT III, deg. 2, basic insulation

Do not use the LED status indicators as evidence of applied voltage.

800.354.8556 +1 503.598.4564 www.veris.com 2010 Veris Industries


07101
DIMENSIONAL DRAWINGS
H300 H600 H800, H800HV, H800NC
Removable Mounting Bracket Removable Mounting Bracket
Removable/Adjustable Mounting Bracket

0.3 0.6"
(16 mm) 0.7" 0.9"
(8 mm) 1.6 1.2" (23 mm)
(18 mm)
6 AWG max. (40 mm) 0.7" (31 mm)
2.1"
(54 mm) (18 mm)
2.8" *
0.5" 2.5" *
(71 mm)
1.5 (13 mm) (64 mm)
(38 mm)
0.18 (x2)
(5 mm)
0.6 1.7
(15 mm) 2.1" (43 mm)
1.8 (54 mm) 0.4 x 0.2
(46 mm) Slot (x2)
1.1" *
1.0" * (27 mm)
(26 mm)
0.4 x 0.2 2.3"
(10 mm x 5 mm) (58 mm)
Slot (2x) 2.9"
(74 mm)
3.5"
(89 mm)

H900
Removable Mounting Bracket

1.0
APPLICATION/WIRING DIAGRAM (25 mm) Bracket can be mounted
Unit Vent Heater Control 1.1 0.8
on either side for added
installation flexibility.
BUILDING AUTOMATION (26 mm) (21 mm)
CONTROLLER **3.1
POWER (79 mm)
SOURCE

CURRENT MONITORING
DI
Self-gripping
Iris
2.8
(70 mm)
DI
1.4*
= 0.3 (36 mm)
(8 mm)
2.5
(64 mm)
3.0
(76 mm)

* Terminal block may extend up to 1/8 over the height


dimensions shown.
POWER
SOURCE

UNIT VENT HEATER

ORDERING INFORMATION RoHS


Compliant

MODEL AMPERAGE RANGE STATUS OUTPUT (max.) TRIP POINT HOUSING UL CE RoHS
H300 0.15 - 60A N.O. 1.0A@30VAC/DC 0.15A or less Split-core n n2 n
1
H600 0.15 - 200A N.O. 1.0A@30VAC/DC 0.15A or less Split-core n n n
1
H800 0.25 -200A N.O. 1.0A@30VAC/DC 0.25A or less Solid-core n n n
H800NC 0.5 - 200A N.C. 0.1A@30VDC 0.5A or less Solid-core n1 n
H800HV 0.75 - 200A N.O. 0.5A@250VAC/DC 0.75A or less Solid-core n3
H900 1.5 - 200A N.O. 1.0A@30VAC/DC 1.5A or less Split-core n n
1
Listed for use on 75C insulated conductors.
2
Product provides functional insulation only. ACCESSORIES
3
Listed for use on 90C insulated conductors. DIN Rail Clip Set (AH01, AH27)
DIN Rail (AV01) and DIN Stop Clip (AV02)

800.354.8556 +1 503.598.4564 www.veris.com 2010 Veris Industries


07101
Current Switches: Adjustable
Trip Point, Standard Output
H608 H908
Detect Belt Loss, Coupling Shear,
And Mechanical Failure
APPLICATIONS
Detecting belt loss, coupling shear, and mechanical failure
Verifying lighting circuit and other electrical service run times H608
Monitoring status of industrial process equipment
Monitoring status of critical motors (compressor, fuel, etc.) H708

FEATURES H808 H308


High performance devices in split- and solid-core housings
Minimum trip point as low as 0.5A (H608)...eliminates the need for multiple
wraps of the conductor through the sensor even on loads as small as 1/5HP
Small size...fits easily inside small enclosures DESCRIPTION
5YearWarranty

Self-gripping iris on the split-core housing for easy installation Hx08 Series and H701 current switches offer high performance, with a wide array
Status LEDs for easy setup and local indication (no LED on the H701) of amperage range options. These products can accurately detect belt loss, coupling
Bracket on H908 can be installed in three different configurations shear, or other mechanical failure on loads from 1/5 to 100HP.
1 Amp status output for increased application flexibility
All devices are 100% solid state and polarity insensitive, with a 5-year warranty
CURRENT MONITORING

Fan/pump Electrical
On failure Maximize Reliability
Calibrated Minimize Installed Cost
Trip
Point Off Off
Loss of belt/coupling shear

Now you can easily detect when drive belts slip,


break, or pump couplings shear. In fact, a typical
HVAC motor that loses its load has a reduction of
current draw of up to 50%. That's why our sensors
are the industry standard for status.

SPECIFICATIONS
Sensor Power Induced from monitored conductor
Insulation Class 600VAC RMS (UL), 300VAC RMS (CE)
Frequency Range 50/60 Hz
Temperature Range -15 to 60C (5 to 140F)
Humidity Range 10-90% RH, non-condensing
Hysteresis 10% (typical)
Terminal Block Maximum Wire Size 14 AWG (16 AWG for H308)
Terminal Block Torque (nominal) 4 in-lbs (7 in-lbs for H308)

UL 508 open device listing; CE: EN61010-1:2001-02, CAT III, deg. 2, basic insulation
Do not use the LED status indicators as evidence of applied voltage.

800.354.8556 +1 503.598.4564 www.veris.com 2010 Veris Industries


07101
DIMENSIONAL DRAWINGS
H308 H608 H808
Removable Mounting Bracket Removable/Adjustable Mounting Bracket
Removable Mounting Bracket
0.6" 0.9"
0.3 (16 mm) 0.7"
(8 mm) 1.2" (18 mm) (23 mm)
1.6
6 AWG max. 0.7" (31 mm)
(40 mm) 2.1"
(54 mm) (18 mm) 2.8" *
0.5" 2.5" * (71 mm)
(13 mm) (64 mm)
1.5
(38 mm)
0.18 (x2)
(5 mm)
0.6 1.7
(15 mm) 2.1" (43 mm)
(54 mm) 0.4 x 0.2
1.8 Slot (x2)
(46 mm) 1.1" *
(27 mm)
1.0" *
(26 mm)
0.4 x 0.2 2.3"
(10 mm x 5 mm) (58 mm)
Slot (2x) 2.9"
(74 mm)
3.5"
(89 mm)

H708/701 H908 APPLICATION/WIRING DIAGRAM


Removable/Adjustable Mounting Bracket Monitoring Fan /Pump Motors for
Removable Mounting Bracket
Positive Proof of Flow
0.9"
(23 mm) 1.0
0.7" Dia (25 mm) Bracket can be mounted
(19 mm) on either side for added CONTACTOR
1.1 0.8
3.0" ** (26 mm)
installation flexibility. CONTROLLER
(75 mm) (21 mm)
**3.1

CURRENT MONITORING
(79 mm)
DI
9

Self-gripping
2.8" Iris
(68 mm) 2.8
(70 mm)
1.1" *
(27 mm) 1.4*
0.2 x 0.15
= 0.3 (36 mm) Fan or Pump
(8 mm)
slot (2x) 3.8"
(95 mm) 2.5
4.2" (64 mm)
(106 mm) 3.0
(76 mm) Motor

* Terminal block may extend up to 1/8 over the height dimensions shown.

ORDERING INFORMATION RoHS


Compliant

MODEL AMPERAGE RANGE STATUS OUTPUT (max.) MIN. TRIP POINT HOUSING STATUS LED UL CE RoHS
2
H308 0.75 - 50A 0.75A or less Split-Core n n n n
1
H608 0.5 - 175A 0.5A or less Split-Core n n n n

H701 1 - 135A 1.0A or less Solid-Core n n


N.O. 1.0A@30VAC/DC
H708 1 - 135A 1.0A or less Solid-Core n n n

H808 0.75 - 50A 0.75A or less Solid-Core n n n n

H908 2.5 - 135A 2.5A or less Split-Core n n n n

For high voltage outputs, see page 26. 1


Listed for use on 75C insulated conductors.
2
Product provides functional insulation only.
ACCESSORIES
DIN Rail Clip Set (AH01, AH27)
DIN Rail (AV01) and DIN Stop Clip (AV02)

800.354.8556 +1 503.598.4564 www.veris.com 2010 Veris Industries


07101
PRESSURE
DIFFERENTIAL PRESSURE TRANSMITTER PSI
M264 SERIES

DESCRIPTION
The Model M264 Differential Pressure Transmitter is a
low-air pressure transmitter able to sense differential pressure
in both negative and positive ranges. The Model M264
incorporates a tensioned stainless steel diaphragm to form
a variable capacitor that will produce variation in the output
signal. The Model M264's durable design will tolerate an
overpressure of 10 psig (68.95 kPa) and has an unconditional
three-year warranty.

FEATURES
4-20 mA output signal
Voltage output signal optional
10 psig (68.70 kPa) overpressure
Three-year unconditional warranty
1% accuracy
Reverse wiring protected
Stainless steel diaphragm APPLICATION
Ideal for air and non-conducting gases HVAC building automation
Variable air volume control
Environmental pollution control
Lab and fume hood control
Filter monitoring
Medical instrumentation

PRESSURE
Velocity pressure measurement

SPECIFICATIONS
Supply Voltage Position Effect (Unit is factory calibrated at 0g effect
Current Models 9 to 33 VDC with diaphragm vertical),
Voltage Models 9 to 30 VDC Range Zero offset (%FS/G)
Signal Output 4-20 mA (two-wire) Up to 0.5" WC 0.60
0-5 VDC (three-wire) Up to 1.0" WC 0.50
Maximum Output Up to 2.5" WC 0.22
Impedance (mA) 750 @ 24 VDC Up to 5.0" WC 0.14
Minimum Output Operating Temperature 0 to 175F (-18 to 79C)
Impedance (VDC) 5000 Storage Temperature -65 to 250F (-54 to 121C) 19
Accuracy 1% FS Enclosure Fire-retardant glass filled polyester
Non-linearity 0.96% FS (UL 94 V-0 approved)
Non-repeatability 0.1% FS Process Connection 3/16" OD barbed brass
Hysteresis 0.2% FS Dimensions 3.00"H x 5.51"W x 1.91"D
Compensated Temperature (14.00 x 7.62 x 4.85 cm)
Range 0 to 150F (-18 to 65C) Approvals CE
Thermal Effect Zero/Span shift 0.033F (0.018C) Weight 9 oz (255g)
Overpressure Upto 10 psig (68.95 kPa) range Warranty 3 years
dependant

January 2012 kele.com 888-397-5353 USA 001-901-382-6084 International


2012 Kele, Inc. All rights reserved. The Kele name and logo are registered trademarks of Kele, Inc.
873
PRESSURE
PSI
DIFFERENTIAL PRESSURE TRANSMITTER
M264 SERIES

DIMENSIONS
in 4.56 (11.59)
(cm)

Zero

Model M264
2.75 1.66

High
Low
(6.99) (4.22)
Span

5.06 (12.86) 2.38 (6.03)

WIRING
Power
Supply
9-30 VDC

COM EXC OUT


Power
Supply High Low
Low High 9-30 VDC

4-20 mA

0-5 VDC
4-20 mA Output 0-5 VDC Output

ORDERING INFORMATION
PRESSURE

MODEL DESCRIPTION
M264 Differential pressure transmitter
XXX RANGE CODE (see Table 1 below)
C 4-20 mA output (stocked at Kele)
V 0-5 VDC output (call Kele for availability)
Example: M264-2R5WB-C Differential pressure transmitter
M264 - 2R5WB - C with a 4-20 mA output proportional to a range of
-2.5" to 2.5" W.C. (622 Pa)

TABLE 1. SPECIFYING RANGE


RANGE PRESSURE RANGE RANGE BIDIRECTIONAL PRESSURE RANGE
CODE "W.C. Pa CODE "W.C. Pa
0R1WD 0-0.10 0-24.9 0R1WB 0.1 24.9
0-0.25 0-62.2 0.25 62.2
19 R25WD
0R5WD 0-0.50 0-124
R25WB
0R5WB 0.5 124
001WD 0-1.00 0-249 001WB 1.0 249
2R5WD 0-2.50 0-622 2R5WB 2.5 622
005WD 0-5.00 0-1244 005WB 5.0 1244
010WD 0-10.0 0-2488 010WB 10.0 2488
025WD 0-25.0 0-6221 025WB 25.0 6221
050WD 0-50.0 0-12441
100WD 0-100.0 0-24883

RELATED PRODUCTS PAGE


264-A1 Conduit housing for M264 874
A-301-K Duct static pressure tip, 1/4" compression 925
A-302-K Duct static pressure tip, 1/4" barb 925
A-308-K Duct static pressure fitting, 1/4" barb 925
A-345-K Flange mounting kit (1 required for each A-301-K or A-302-K) 925
RPS Stainless steel room pressure sensor, 1/4" barb 925
RPS-I Ivory plastic room pressure sensor, 1/4" barb 925
RPS-W White plastic room pressure sensor, 1/4" barb 925
SD-01 Surge dampener 925
T-101 1/4" OD black poly tubing, 1 coil, 250 ft (76 m) 759

001-901-382-6084 International 888-397-5353 USA kele.com January 2012


874 2012 Kele, Inc. All rights reserved. The Kele name and logo are registered trademarks of Kele, Inc.
Functional Devices, Inc. Office 765.883.5538
Functional RIB
310 South Union Street Sales 800.888.5538
Devices, Inc. Russiaville, IN 46979
www.FunctionalDevices.com
Fax
Email
765.883.7505
sales@functionaldevices.com

PSH40A40A SERIES | Enclosed Dual 40 VA Power Supplies, 120 to 24 Vac

120 Vac Convenience Outlet*


CLASS II 24 Vac 24 Vac
ON/OFF ON/OFF

8.625
8.250 4.500
c c c c c c
c c c c c
c c c c c c
c c c c c
c c c c c c
c c c c c RESET RESET
c c c c c c
c c c c c
c c c c c c

MADE IN USA
SPECIFICATIONS
OFF OFF

RESET RESET

LED Indicator 4.250


RESET

Transformer: Two 40 VA Split-Bobbin OFF


OFF OFF

4.500
Over Current Protection: Inherently Limited
RESET

Input Wires: B10 Models Only OFF

Input Power Wires


Com 24 Vac Com 24 Vac
BLK: 120 Vac
WHT: Neutral 120 Vac Convenience Outlet*
GRN: Ground 8.250
10 Amp Main Breaker/Switch
All Other Models
Primary Wires Outlet Wires *Move internal jumper to HOT position if you
BLK: 120 Vac BLK: 120 Vac wish outlets to always be hot otherwise outlets
WHT: Common WHT: Neutral will be switched by main breaker.
GRN: Ground

Output Wires: B10 Models Only W Models Only


Auxiliary Output Transformer Output PSH40A40A SERIES SELECTION GUIDE
BLU: 120 Vac WHT/YEL: 24 Vac
WHT/BLU: Common 120 VAC AUX OUTPUT MAIN BREAKER ON
MODEL # OUTLETS WIRE INPUT POWER SECONDARY CONFIGURATION
PSH40A40A External Terminal Strip
Frequency: 50/60 Hz
24 Vac ON/OFF: On / Off Switch
PSH40A40AN External Terminal Strip
Main Breaker ON/OFF: Switch / Breaker (10 Amp) PSH40A40ANW Internal Wires
(Kills power to entire unit: Outlets, Aux. PSH40A40AW Internal Wires
Output, and Transformer)*
Total Combined Output 9A PSH40A40AB10 10 Amp Switch / Breaker External Terminal Strip
Approvals: Class II UL Listed, UL916, C-UL, CE PSH40A40ANB10 10 Amp Switch / Breaker External Terminal Strip
Dimensions: 4.500 x 8.625 x 4.500 PSH40A40ANWB10 10 Amp Switch / Breaker Internal Wires
Weight: 5.400 lbs.
PSH40A40AWB10 10 Amp Switch / Breaker Internal Wires

NOTES

CONDENSE WORK SPACE AND WIRING (POWER SUPPLIES)


The PSC, PSH, and PSB Series Power Supplies allow you to save large amounts of time, space, and wiring throughout your panel.

BEFORE AFTER POWER SUPPLIES


There is a lot of extra wiring in this enclosure By using one of Functional Devices' Power Any B10 models in the PSC,
which not only takes up space but also increases Supplies you will greatly reduce installation
the difficulty and time associated with installation. time, as well as save space in your enclosure. PSH, or PSB Power Supply
CONDUIT CONDUIT
Series
Power Supplies are pre-wired
ENCLOSURE ENCLOSURE 24Vac Switch/Breaker
SWITCH
H
N 120Vac from
G 10A Switch &
H CB to remainder 24Vac 24Vac
FUSE N of panel Indicator
G
24 POWER SUPPLY
Vac MAIN POWER
10A Switch/CB & Indicator Light
To remainder
SUB-PANEL of panel SUB-PANEL
RELAYS & CONTACTORS
IDEC GENERAL-PURPOSE RELAYS
RH, RJ, RR SERIES

DESCRIPTION
IDEC general-purpose relays are available in the RH Series
blade-style relays and the RR Series pin-style relays and the
RJ Series compact relays.

The RH Series features a 10A switching capacity. They


are available in SPDT, DPDT, 3PDT, and 4PDT contact
configurations, driven by AC or DC coils, and they have blade
terminals for socket mounting.The RR Series has a 10A
contact rating.
RH, RJ, RR Series
The RR Series relays are available in SPDT, DPDT, and
3PDT configurations driven by AC or DC coils, and they have
pin or blade terminals for socket mounting. FEATURES
Blade style, pin style, and compact models
The RJ Series is compact to reduce space requirements.
Indicator light and/or check button available
They are available in a 12A SPDT version and an 8A DPDT
Surface or DIN rail mount
version. They are driven by AC or DC coils and have blade
terminals for socket mounting.
UL recognized, CSA certified

SPECIFICATIONS
COIL RATINGS CONTACT RATINGS
RH SERIES RH SERIES (UL ratings)
RATED CURRENT (mA) 15% @ 20C INRUSH CURRENT RESISTIVE (A) INDUCTIVE (A) MOTOR LOAD (hp)
RATED

RELAYS & CONTACTORS


60 Hz 50 Hz (mA) VOLTAGE cos = 0.3
VOLTAGE SPDT DPDT 3PDT 4PDT SPDT DPDT 3PDT 4PDT SPDT DPDT 3PDT
SPDT DPDT 3PDT 4PDT SPDT DPDT 3PDT 4PDT SPDT DPDT 3PDT 4PDT
240 AC 10 10 7.5 7 7 * 5 1/3 1/3 1/3
12 75 100 140 165 86 118 165 196 120 170 260 310
120 AC 10 10 10 10 7.5 7.5 1/6 1/6 1/6
24 37 50 70 83 42 59.7 81 98 56 85 130 165
AC 120 30 DC 10 10 10 7 7
7.5 11 14.2 16.5 8.6 12.9 16.4 19.5 12 16 26 33 28 DC 10 10 10 10 7.5 7.5
240 3.2 5.5 7.1 8.3 3.7 6.5 8.2 9.8 7 8 12 16
* Note: 6.5A, 20A Total
SPDT DPDT 3PDT 4PDT SPDT DPDT 3PDT 4PDT
12 64 75 120 125
DC
24 32 36.9 60 62

RR Series RR SERIES (UL ratings)


Rated Rated Current (mA) 15% @ 20C INRUSH CURRENT VOLTAGE RESITIVE (A) INDUCTIVE (A) MOTOR LOAD (hp)
cos = 0.3
Voltage 60 Hz 50 Hz (mA)
240 AC 10 7 1/3
12 210 245 365
120 AC 10 7.5 1/4
24 105 121 182
30 DC 10 7
AC 120 20.5 24 35
240 10.5 12.1 18
12 120
DC 24 60 RJ1S RJ2S
CONTACT
Resistive Load
RJ Series (Maximum)
N.O. 12A @ 250 VAC/30 VDC 8A @ 250 VAC/30 VDC
N.C. 12A @ 250 VAC; 6A @ 30 VDC 8A @ 250 VAC; 4A @ 30 VDC
Coil Sensitivity Nominal Voltage Nominal Current Coil Resistance Inductive Load N.O. 7.5A @ 250 VAC; 6A @ 30 VDC 4A @ 250 VAC; 4A @ 30 VDC
1080
DC Coil

AC Coil (60 Hz)


24V
24V
25.7 mA
41.1 mA 243
(Maximum) N.C. 7.5A @ 250 VAC; 3A @ 30 VDC 4A @ 250 VAC; 2A @ 30 VDC
20
120V 8.1 mA 5270

Maximum continuous applied voltage Operate time


RH, RR 110% of rated voltage RH, RR 25 ms maximum
RJ 140% of rated voltage RJ 15 ms maximum
Pull-in voltage Release time
RH, RR, RJ/AC 80% of rated voltage RH, RR 25 ms maximum
RJ, RJ/DC 70% of rated voltage RJ 10 ms maximum
Drop-out voltage Min load
AC 30% or more of rated voltage RH 24 VDC/30 mA, 5 VDC/100 mA
DC 10% or more of rated voltage RR 24 VDC/10 mA, 5 VDC/20 mA
Contact material RJ 5 VDC/100 mA
RH Silver cadmium oxide Operating temp -22 to 158F (-30 to 70C)
RR Silver Agency approvals UL-recognized component,
RJ Silver nickel alloy (RH, RR): File #E66043,
Contact resistance (RJ): File #E55996
RH 50 m maximum CSA certified, File #LR35144;
RR 30 m maximum CE certified (not RR blade style)
RJ 50 m maximum Warranty 1 year

January 2012 kele.com 888-397-5353 USA 001-901-382-6084 International


2012 Kele, Inc. All rights reserved. The Kele name and logo are registered trademarks of Kele, Inc.
931
RELAYS & CONTACTORS
IDEC GENERAL-PURPOSE RELAYS
RH, RJ, RR SERIES

DIMENSIONS

in

1.07 (2.75)

1.07 (2.75)

1.07 (2.75)
1.07 (2.75)
(cm)

0.55 (1.39) 0.82 (2.1) 1.22 (3.1) 1.60 (4.1)


RH1B RH2B RH3B RH4B
1.39 (3.56) or less RH Series Relays (blade)
0.2 (0.5)
3
1.418 (3.6)

1.418 (3.6)

1.13 (2.38)
1.42 4

(3.64) 2

1.42 (3.6) 1.87 (4.8) or less 1.42 (3.64) 1 5


1.14 (2.9)

2.19 (5.55) RR2P RR3PA RR1BA, RR2BA, RR3B


1.06 (2.7) 0.5 (1.27)
RR Series Relays (pin) RR Series Power Relays (blade) RJ Series Relays (blade)

WIRING
1 1 4 1 2 4 1 2 3 4
Legend 5 5 8 5 6 8 5 6 7 8
3 4 5
NC 9 9 12 9 10 12 9 10 11 12

NO 13
(-)
14
(+)
13 (-) (+)14 13 (-) (+)14 13 (-) (+)14 4 3 6

RH1B RH2B RH3B RH4B 2 2 7


4 5 6
5 7
Bottom View 1 3
RELAYS & CONTACTORS

2 1 2 3
3 6 4 8
5 4 6 4 5 6
1 5 1 8
3 9 7 7 9 7 8 9
2 7 A B RJ1S RJ2S
A B A B
(-) (+) 2 10
(-) (+)
(-) (+) (-) (+) (-) (+)
1 8 1 11
RR1BA RR2BA RR3B
RR2P RR3PA

ORDERING INFORMATION

MODEL DESCRIPTION MODEL DESCRIPTION


RH1B Relay, SPDT, blade (use SH1B-05 socket) RR2P Relay, DPDT, 8 pin (use SR2P-05 or SR2P-06)
RH2B Relay, DPDT, blade (use SH2B-05 socket) RR3PA Relay, 3PDT, 11 pin (use SR3P-06 socket)
RH3B Relay, 3PDT, blade (use SH3B-05 socket) RR1BA Relay, SPDT, 11 blade (use SR3B-05 socket)
RH4B Relay, 4PDT, blade (use SH4B-05 socket) RR2BA Relay, DPDT, 11 blade (use SR3B-05 socket)
U Standard relay RR3B Relay, 3PDT, 11 blade (use SR3B-05 socket)
UL Indicator light U Standard relay
ULC Indicator light and check button UL Indicator light
AC12V 12 VAC coil voltage ULC Indicator light and check button
AC24V 24 VAC coil voltage AC12V 12 VAC coil voltage
AC120V 120 VAC coil voltage AC24V 24 VAC coil voltage

20 AC240V
DC12V
240 VAC coil voltage
12 VDC coil voltage
AC120V
AC240V
120 VAC coil voltage
240 VAC coil voltage
DC24V 24 VDC coil voltage DC12V 12 VDC coil voltage
DC24V 24 VDC coil voltage
RH1B U AC24V
RR2P U AC24V
MODEL DESCRIPTION
RJ1S Relay, SPDT (use SJ1S-05B socket) Example: RR2PUAC24V DPDT relay 8 pin with 24VAC coil
RJ2S Relay, DPDT (use SJ2S-05B socket)
C No options
CL LED indicator
A24 24 VAC coil voltage
A120 120 VAC coil voltage
D24 24 VDC coil voltage

RJ1S C A24

RELATED PRODUCTS PAGE


DINRSTL, DINRALU DIN rail 229

001-901-382-6084 International 888-397-5353 USA kele.com January 2012


932 2012 Kele, Inc. All rights reserved. The Kele name and logo are registered trademarks of Kele, Inc.
Functional 310 South Union Street Sales: (800) 888-5538 www.functionaldevices.com
Devices, Inc. RIB
Russiaville, IN 46979 Fax: (765) 883-7505 sales@functionaldevices.com

RIBD2421C Enclosed Time Delay Relay 10 Amp SPDT with 24Vac/dc 120-277Vac Coil
Contact Ratings:
10 Amp Resistive @ 30 Vdc
10 Amp General Use @ 250 Vac
1/2 HP @ 125-250 Vac Wht/Brn Blu
470 VA Pilot Duty @ 120-240 Vac 120-277 Vac N/C
Input Current:
100 mA @ 24 Vac
30 mA @ 24 Vdc
Wht/Blu Yel
55 mA @ 277 Vac
c c c c c c
c c c c c
c c c c c c
c c c c c
c c c c c c
c c c c c
24 Vac/dc Comm
c c c c c c
c c c c c
c c c c c c

Coil Voltage Input:


MADE IN USA 24 Vac/dc ; 120-277 Vac ; 50-60 Hz
Drop Out = 3 Vac / 3.8 Vdc
Pull In = 20 Vac / 20 Vdc Wht/Yel Org
Functional Devices, Inc. A600D 2006
Comm N/O
Notes:
# Relays & Contact Type: One (1) SPDT Continuous Duty Coil Order with terminals for coil voltage
Expected Relay Life: 10 million cycles minimum mechanical input by using model number RIBTD2421C
Operating Temperature: -30 to 140 F
Operate Time: 6mS after time delay
Relay Status: RED LED On = Activated
Time Delay Status: PINK LED FLASHING = Timing Range Selection
Timing Mode: Delay On Make (N/O)
Timing Range: 6 seconds - 20 minutes 1 2 3 4
Timing Adjustment: 4 position DIP switch for range selec-
tion and single turn potentiometer for Timing Adjustment
timing adjustment within range Close Only 1 Switch
Timing Tolerance: Switches 1& 2 = +10% C
Switches 3 & 4 = +5% B D
Timing Repeatability: +1%
A E
Temperature Timing Variance: +1%

Voltage Timing Variance: +1%

Recycle Time: 750ms Maximum


Dimensions: 4.00 x 4.00 x 1.80
with .50 NPT nipple TIMING CHART
Wires: 16, 600V Rated SWITCH CLOSE POTENTIOMETER SETTING
Approvals: UL Listed, UL916, UL864, C-UL RANGES DIP SWITCH A B C D E
California State Fire Marshal, CE 6s-20s 1 6s 9s 13s 16s 20s
Housing Rating: Plenum, NEMA 1 22s-1min15s 2 22s 36s 50s 1min4s 1min15s
Gold Flash: No 1min30s-5min 3 1min30s 2min10s 3min20s 4min16s 5min
Override Switch: No 6min-20min 4 6min 9min 13min20s 17min20s 20min

DELAY ON MAKE (N/O) APPLICATION FOR INTERVAL (N/C) APPLICATION FOR DELAY ON BREAK (N/C)
Note: Load Power + Coil Input
must use same voltage source

Time Delay
COIL COIL COIL

Time Delay LOAD


LOAD LOAD Time Delay

-OR-

N/C Power
COIL
Time Delay
N/O Power
COIL COIL LOAD
LOAD LOAD

N/C Power

COIL
LOAD
Andover Continuum TM

xP Expansion I/O Family

The Andover Continuum xP Expansion I/O Family provides a


convenient and cost-effective means to add additional inputs,
outputs, or a local display to the Andover Continuum InfinetTM II
and BACnetTM family of distributed controllers.
02

Andover Continuum xP Expansion I/O Family


Features

Up to two modules plus a local display


can be powered directly from any of
the following controllers in the Andover
Continuum Infinet II (i2) or BACnet (b3)
families: i2/b3 920, i2/b3 810, i2/b3 814, i2/
b3 850, i2/b3 851, or i2/b3 853.

The bCX1 Controller/Router models can also


be used to connect xP Expansion Modules (and
Display) and are the only controllers that support the
xPBA4 and xPBD4 module types. No external power
supply is required to power the Module(s). Consult
the xP Modules and Local Display Modules User
Guide for valid configurations.

xPDI8 The xPDI8 module allows the addition


of 8 Digital Inputs in a small enclosure.

Product AT A GLANCE xPUI4 The xPUI4 module allows the addition


of 4 Universal Inputs. Each can be configured
independently based on your needs for Digital,
Powerful, Flexible System Allows for Simple
Temperature, Motion Sensor, or Pulse Counter
Addition of a Few I/O Points
Inputs, etc., providing built-in flexibility for your
Individual Overrides of All Digital Outputs different application requirements.
Universal Inputs Provide the Most Flexibility, xPAO2/xPAO4 Both the xPAO2 (2 Analog
Including a Single High Speed Counter Input Outputs) and the xPAO4 (4 Analog Outputs)
Individual Overrides and Potentiometers for allow the addition of Analog Outputs. Each
All Analog Outputs output has individual manual override switches to
select Manual, Off, or Auto for program control.
Full Function Manual Overrides Provide
When in Manual mode, each output also has a
Status Feedback
potentiometer to allow control of the override point.
4-Line, 16-character Display with Keypad
xPDO2/xPDO4 Both the xPDO2 (2 Digital
Provides Simple and Convenient Operator
Outputs) and the xPDO4 (4 Digital Outputs) allow
Interface
the addition of Digital Outputs. Each output has
Locally Mounted or Remote Mount of individual manual override switches to select On,
Modules and Display Off, or Auto for program control.
Module Power Supplied by the Controller,
xPBA4/xPBD4 Both the xPBA4 and the xPBD4
Reducing Installation Time and Cost
combine the functions of two xP Expansion
modules. Similar to the xPUI4, both allow the
addition of 4 Universal Inputs. The xPBA4 allows
the addition of 4 Analog Outputs (like the xPAO4),
and the xPBD4 allows for the addition of 4 Digital
Outputs (like the xPDO4). (Note: The xPBA4 and
xPBD4 Expansion Modules can only be connected
to the bCX1 Controller/Routers and ACX Series
Access Controllers.)

Schneider Electric One High Street, North Andover, MA 01845 USA Telephone: +1 978 975 9600 Fax: +1 978 975 9674 www.schneider-electric.com/buildings

SDS-XPEXPANSION-I/O-US.BU.N.EN.8.2007.0.00.CC
03

Andover Continuum xP Expansion I/O Family


Features (continued)

Expansion I/O Family


xPDI8 xPUI4

INPUTS INPUTS

xPAO4 xPDO4

OUTPUTS xPAO2 OUTPUTS xPDO2


OUTPUTS OUTPUTS

Similar to xPAO4; Similar to xPDO4;


however only the first however only the first
2 outputs are populated. 2 outputs are populated.

Local Display Programming


The local display with keypad (xP Display) allows for Programming with the Expansion Modules points
the addition of a fully programmable local display are treated in the same manner as the built-in I/O
module that can be mounted within 10 feet (3 points on the controller. Once the points have been
meters) of the controller. Connected via a ribbon configured, they are available for graphics, Plain
cable, the xP Display easily allows the Operator EnglishTM programming, or for displaying data on
Interface to be mounted on the door of an enclosure the display.
or on a wall below or next to the controller.

Schneider Electric One High Street, North Andover, MA 01845 USA Telephone: +1 978 975 9600 Fax: +1 978 975 9674 www.schneider-electric.com/buildings

SDS-XPEXPANSION-I/O-US.BU.N.EN.8.2007.0.00.CC
04

Andover Continuum xP Expansion I/O Family


Features (continued)

Expansion I/O Family


xPBA4 xPBD4

INPUTS OUTPUTS INPUTS OUTPUTS

Dimensional Drawings

xP Module
xP Display

Models
xP-Display
(includes 3 foot cable)
xP-Display-10
(includes 10 foot cable)
Power Consumption
70 mA
Display Properties
4 lines x 16 characters,
backlit
Enclosure Type
IP54 Rating

Installation
Modules can be connected to the bottom of the
controller with the built-in expansion port connector
or they may be connected remotely via a 3-foot (~1
m) or 10-foot (~3m) ribbon cable. A total of 10 feet
of cable may be used for all Expansion Modules.
Mounting and securing of the xP modules is provided
through four mounting holes in the base plate.

Schneider Electric One High Street, North Andover, MA 01845 USA Telephone: +1 978 975 9600 Fax: +1 978 975 9674 www.schneider-electric.com/buildings

SDS-XPEXPANSION-I/O-US.BU.N.EN.8.2007.0.00.CC
05

Andover Continuum xP Expansion I/O Family


Specifications

xP Expansion I/O
Electrical Communications Agency Listings
Power Communications Interface UL/CUL 916, FCC CFR 47 Part 15,
Up to two I/O module and an xP-Display may Through built-in Expansion Port ICES-003, EN55022, AS/NZS 3548,
be connected to a controller. All controllers on controller Class A, CE
provide a total of 180 mA of power, the bCX1
controller/router has 400 mA of power, for the Connections xPDI8 (Digital Inputs)
modules. Each modules power consumption Fixed Terminal Connectors Points
is listed below. Reference installation sheet for Reference specific module on previous 8 Digital Inputs
valid combinations. page for terminal point assignments Power Consumption
Input (top) 25 mA
Mechanical 6-pin shrouded connector Voltage
Operating Environment Output (bottom) 0-5 VDC, or contact closure
32120F (049C), 6-pin shrouded connector Input Impedance
1095% RH (non-condensing) User LEDs/Switches 10K ohm ref to +5VDC
Size Status Indicator LEDs Frequency
Module: 3.21 H x 7.10 W x 1.60 D CPU Module is Active 140Hz, 50% duty cycling, 3.57 ms
(82H x 180 W x 41 D) mm Switches pulse width min.
Display: 7.25 H x 5.00 W x 1.65 D RESET Overvoltage Protection
(184H x 127 W x 42 D) mm 24 VAC/DC +/- 1500 V transients
Weight General
Module: 0.48 lb (0.22 kg) xP Modules
Display: 1lb (0.45 kg) Consult the xP Module Installation
Enclosure Type Guide for the maximum number
Modules: UL Open class, IP 10. of inputs/outputs allowed on
Flammability rating of UL94-5V each controller.
Display: IP54
Cable Options
xP-Mod-Cable-3
3-foot (~1m) ribbon cable terminated
xP-Mod-Cable-10
10-foot (~3m) ribbon cable terminated

Schneider Electric One High Street, North Andover, MA 01845 USA Telephone: +1 978 975 9600 Fax: +1 978 975 9674 www.schneider-electric.com/buildings

SDS-XPEXPANSION-I/O-US.BU.N.EN.8.2007.0.00.CC
06

Andover Continuum xP Expansion I/O Family


Specifications (continued)

N1831

xP Expansion I/O
xPUI4/xPBA4/xPBD4 xPAO2/xPAO4/xPBA4 xPDO2/xPDO4/xPBD4
(Universal Inputs) (Analog Outputs) (Digital Outputs)
Points Points Points
4 Universal Inputs 2 Analog Outputs (xPAO2) 2 Digital Outputs (xPDO2)
Power Consumption 4 Analog Outputs (xPAO4, xPBA4) 4 Digital Outputs (xPDO4, xPBD4)
50 mA (xPUI4) Power Consumption Type
60 mA (xPBA4) 80 mA (xPAO2) 2 or 4 single pole single throw (SPST)
125 mA (xPBD4) 120 mA (xPAO4) Form C relays
Voltage 60 mA (xPBA4) Power Consumption
0-5.115 VDC Output Rating 60 mA (xPDO2)
Input Impedance 0-10 VDC 100 mA (xPDO4)
10K ohm ref to +5VDC 4-20mA per channel (xPAO2, xPAO4) 125 mA (xPBD4)
Frequency Output Resolution Output Rating
4Hz, 50% duty cycling, 0.1V for 0-10V Maximum 3A, 24 VAC/VDC,
125 ms pulse width min. (Inputs 1-3) 0.1mA for 4-20mA (xPAO2, xPAO4) +/- 1500 V transients (tested
140Hz, 50% duty cycling, 3.57 ms Overrides according to EN61000-4-4)
pulse width min. (Input 4) yes per output point. Software Output Accuracy
Overvoltage Protection feedback of the switch position is 0.1 sec for pulse width modulation
24 VAC/DC +/- 1500 V transients provided, for display and alarming Output Overrides
Potentiometer Each Output is equipped with a
yes per output point manual override switch. Software
feedback of the switch position is
provided, for display and alarming

2007-2009 Schneider Electric. All rights reserved.

All brand names, trademarks and registered trademarks are the property of their respective owners. Information contained within this document is subject to change
without notice.
On October 1st, 2009, TAC became the Buildings Business of its parent company Schneider Electric. This document reflects the visual identity of Schneider Electric, how-
ever there remains references to TAC as a corporate brand in the body copy. As each document is updated, the body copy will be changed to reflect appropriate corporate
brand changes.
Schneider Electric One High Street, North Andover, MA 01845 USA Telephone: +1 978 975 9600 Fax: +1 978 975 9674 www.schneider-electric.com/buildings

SDS-XPEXPANSION-I/O-US.BU.N.EN.8.2007.0.00.CC August 2007 pdw


RELAYS & CONTACTORS
IDEC RELAY SOCKETS
SH, SJ, SR SERIES

DESCRIPTION
The SH and SR Series of IDEC relay sockets are for use with
the IDEC RH / RR Series relays and RTE Series timers. The
SH and SR Series include both blade and pin style sockets
and are available for one, two, three and four pole relays.
The SH and SR sockets can be DIN rail or surface mounted.
The SJ Series of IDEC relay sockets are for use with the
SJ1S, SJ2S SH1B-05
IDEC RJ1S and RJ2S Series relays. They can be DIN rail or
surface mounted.

FEATURES
Use with IDEC RH / RR / RJ relays and RTE timers
Screw terminals with captive wire clamp
Surface or DIN rail mount
UL recognized, CSA certified and CE approved
SH2B-05 SH3B-05

SH4B-05 SR2P-05 SR2P-06 SR3P-06 SR3B-05

RELAYS & CONTACTORS


SPECIFICATIONS
Rated Rated Hold Down Clip or
Model Socket Type Wire Size Weight Approvals
Voltage Current SpringWire Size

UL recognized File #E62437,


SJ1S-05B Blade, DIN rail or surface mount 250V 12A Lever: SJ9Z-C1 (provided) Two 14 AWG 0.06 lb (0.03 kg)
CSA certified File #LR84913, CE

UL recognized File #E62437,


SJ2S-05B Blade, DIN rail or surface mount 250V 8A Lever: SJ9Z-C1 (provided) Two 14 AWG 0.07 lb (0.034 kg)
CSA certified File #LR84913, CE

Spring: SYS-02F1; UL recognized File #E62437,


SH1B-05 Blade, DIN rail or surface mount 250V 10A Two 12 AWG 0.06 lb (0.03 kg)
Clip: SFA-101, SFA-202 CSA certified File #LR35144e, CE

Spring: SY4S-02F1; UL recognized File #E62437,


SH2B-05 Blade, DIN rail or surface mount 300V 10A Two 12 AWG 0.10 lb (0.05 kg)
Clip: SFA-101, SFA-202 CSA certified File #LR35144e, CE 20
Spring: SH3B05F1; UL recognized File #E62437,
SH3B-05 Blade, DIN rail or surface mount 300V 10A Two 12 AWG 0.13 lb (0.06 kg)
Clip: SFA-101, SFA-202 CSA certified File #LR35144e, CE

Spring: SH4B-02F1; UL recognized File #E62437,


SH4B-05 Blade, DIN rail or surface mount 300V 10A Two 12 AWG 0.16 lb (0.07 kg)
Clip: SFA-101, SFA-202 CSA certified File #LR35144e, CE

Spring: SR2B-02F1 (RR2P only); UL recognized File #E62437,


SR2P-05 8-Pin DIN rail or surface mount 300V 10A Two 12 AWG 0.10 lb (0.05 kg)
Clip: SFA-203 (RTE-P1 only) CSA certified File #LR35144e, CE

Spring: SR2B-02F1 (RR2P only); UL recognized File #E62437,


SR2P-06 8-Pin, DIN rail or surface mount 300V 10A Two 12 AWG 0.10 lb (0.05 kg)
Clip: SFA-202 (RTE-P1 only) CSA certified File #LR35144e, CE

Spring: SR3B-02F1 (RR only); UL recognized File #E62437,


SR3P-06 11-Pin, DIN rail or surface mount 300V 10A Two 12 AWG 0.13 lb (0.06 kg)
Clip: SFA-202 (RTE-P2 only) CSA certified File #LR35144e, CE

Spring: SR3B-02F1 (RR3PA only); UL recognized File #E62437,


SR3B-05 Blade, DIN rail or surface mount 300V 10A Two 12 AWG 0.14 lb (0.06 kg)
Clip: SFA-202 (RTE-P2 only) CSA certified File #LR35144e, CE

January 2012 kele.com 888-397-5353 USA 001-901-382-6084 International


2012 Kele, Inc. All rights reserved. The Kele name and logo are registered trademarks of Kele, Inc.
933
RELAYS & CONTACTORS
IDEC RELAY SOCKETS
SH, SJ, SR SERIES

DIMENSIONS
0.66
(1.7) 1.12 0.86 1.12
2.2 (5.6) 0.1 0.32 (2.2) (2.85)
(2.85)
1.9 (4.9) (0.2) (0.8) 0.32 0.7
1.4 (3.5) (0.8) (1.88)

8
4
5
8 5

2
1

7
2
4 1
3

2.62 0.16 DIN


(6.7) dia. 1.83 Rail
2.62 0.16 1.83 DIN
2.8 (0.42) (4.8) (6.7) dia. (4.8) Rail
(7.1) (0.42)

14 13 14 13
2 Mounting
4

9
5
12 9 2 Mounting
Holes Holes
5

0.16 dia
3

0.63 0.57 1.03 0.57 0.16 dia


SJ1S, (0.42) 0.10 (0.42)
0.10 (1.6) (1.5) (2.6) (1.5)
0.6 1.2 (2.9) (0.25) 1.03
(1.6)
SJ2S 0.2 (0.4) SJ1S SJ2S (0.25) 0.78 0.98 1.17 0.98 (2.6)
(2.0) 0.63 (3.0) (2.5)
(2.5) (1.6)

SJ1S, SJ2S SH1B-05 SH2B-05

1.12 1.25
1.25 1.12
(2.85) 1.65 (2.85) 1.40 (2.85)
0.32 (3.2) 0.7 (3.6)
0.32 (4.2) 0.7
(0.8) (1.88) (0.8) (1.88) 0.32 0.64
(0.8) (1.7)
8 6 5 8 7 6 5 5 4
4 2 1 4 3 2 1 6 3

2.62 0.16 DIN 2.03 1.28 0.9 DIN


(6.7) dia. 1.83 Rail 2.62 1.83 DIN (5.2) (3.3) (2.5) Rail
(0.42) (4.8) (6.7) (4.8) Rail
0.16
0.16 dia. 7 2
14 13 dia. (0.42)
(0.42) 14 13 8 1
12 10 9 2 Mounting Holes
2 Mounting 12 11 10 9 0.78 0.16 dia. (0.42)
1.42 Holes 1.14 (2.0)
(3.6) 0.57
0.16 dia 1.81 2 Mounting Holes 0.12 (2.9) 1.12
0.10 (1.5) (4.6) 0.57 0.16 dia (0.42) (0.25)
(0.25) 1.56 1.42 (0.42) 0.10 (1.5) (2.85)
(4.0)
0.98 (3.6) (.25) 1.97 1.81
1.14
(2.5) (5.0) 0.98 (2.9)
(2.5) (4.6)
RELAYS & CONTACTORS

SH3B-05 SH4B-05 SR2P-05


1.41
1.0 1.0 0.31 (3.6) 1.12
1.56 (2.55) (2.55) (0.8)
(4.0) M3.5 (2.85)
2.3 0.7
0.32 0.7 (5.9) 0.32 Terminal
(0.8) (1.8) (1.8) Screw 6 5 4
(0.8)
6 5 4 3 8 7 6 5 4 3 2 1

2.34 0.16 1.05 DIN 0.16 DIN


2.34 0.16 0.97 DIN 2.9 (0.42) 2.2
(6.0) dia. (2.5) (6.0) dia. (2.5) Rail (7.6) Rail
Rail (0.42) (5.6)
(0.42)
B A
9 10 11 1 2 3 9 8 7
7 8 1 2
2 Mounting Holes 2 Mounting
2 Mounting Holes 1.3 0.16 dia. (0.42) 1.45 (3.7) Holes
1.3 0.16 dia. (0.42) 0.12 0.57
(0.25) (3.3) 0.86 .07 1.45 0.16 dia.
0.04 (3.3) 0.86 (2.2) 1.3 1.69 (4.3) (1.5) (0.42)
(0.25) (0.2) (3.7)
(2.2) (3.3) 0.98
1.3 (2.5)
(3.3)

SR2P-06 SR3P-06 SR3B-05

20 ORDERING INFORMATION
MODEL DESCRIPTION
SH1B-05 Relay socket, SPDT blade type, DIN/surface mount
SH1B-05C SH1B-05QT20 SH2B-05 Relay socket, DPDT blade type, DIN/surface mount
SH2B-05C SH2B-05QT10 SH3B-05 Relay socket, 3PDT blade type, DIN/surface mount
SH4B-05 Relay socket, 4PDT blade type, DIN/surface mount
SH4B-05C SJ1S-05B Relay socket, SPDT blade type, DIN/surface mount
SJ2S-05B Relay socket, DPDT blade type, DIN/surface mount
SR2P-05 Relay socket, DPDT pin type, DIN/surface mount
SR2P-06 Relay socket, DPDT pin type, DIN/surface mount
SR3B-05 Relay socket, three-pole blade type, DIN/surface mount
SR3P-06 Relay socket, 3PDT pin type, DIN/surface mount

001-901-382-6084 International 888-397-5353 USA kele.com January 2012


934 2012 Kele, Inc. All rights reserved. The Kele name and logo are registered trademarks of Kele, Inc.
Infinity
Wall Mount Temperature Sensor

Andover Controls Wall Mount Temperature Sensor provides accurate, reliable measurement of F E A T U R E S

interior room temperature for use in an Andover Controls building automation system. The active Accurate, Reliable Type III Thermistor
sensing element is a highly stable, precision thermistor, accurate to within 0.36F. The sensor has an
Attractive, Ventilated Two-Piece
operating range of 40F to 100F (4.4C to 37.8C).
Housing

The thermistor is encapsulated with a low mass, high-conductivity thermal compound for good heat Fast Response to Temperature Changes

transfer characteristics. It is housed in an attractive, well-ventilated plastic enclosure. The unique


Easy Installation and Service
two-piece enclosure design permits changeout of the thermistor material, which is located in the
cover, without removal of the baseplate. The cover is securely snapped into the backplate.

The sensor may be mounted directly on dry wall, or on any electrical outlet box with no adapters
required. The sensor is for interior use only, and is not suitable for use where condensation may

occur.
SPECIFICATIONS

Sensing Element: Type III Thermistor, 10,000 ohms @ 77F (25C)

Range: 40F to 100F (4.4C to 37.8C)

Accuracy: 0.36F ( 0.2C)

Stability: Thermistor will not deviate from accuracy spec for minimum of 5 years

Wiring Connections: Wiring leads, 2 Yellow, Interchangeable

Wire Specifications: 18, 20, 22 or 24 gauge, 2 conductor, unshielded

Maximum Distance to Sensor: 24 gauge wire: 490 ft. with less than 0.1F (-17.72C) error
22 gauge wire: 850 ft. with less than 0.1F (-17.72C) error
20 gauge wire: 1,200 ft. with less than 0.1F (-17.72C) error
18 gauge wire: 2,000 ft. with less than 0.1F (-17.72C) error

Dimensions: 4.50"H x 3.50" W x 0.813"D (11.5 cm H x 8.9 cm W x 2.0 cm D)

Color: Off-white

ORDERING INFORMATION

WallMount Room Sensor, ACC Logo: TTS-S-1


WallMount Room Sensor, Blank Cover, No Logo: TTS-S-B-1

DIMENSIONAL DRAWING

1.05
(27)

3.50
(89)

4.50
(114)

Andover Controls Corporation Andover Controls Ltd. Andover Control GmbH Andover Control S.A. Andover Controls Andover Controls Mexico
World Headquarters Smisby Road Am Seerhein 8 Immeuble Dolomites 2 Corporation Insurgentes Sur 1722-501
300 Brickstone Square Ashby-de-la-Zouch D-78467 Konstanz, Germany 58, Rue Roger Salengro Unit 1201-02, Phase I, Col. Florida
Andover, Massachusetts 01810 Leicestershire LE65 2UG, Tel: 07531 99370 94126 Fontenay-Sous-Bois, Cheuk Nang Centre Mexico D.F. 01030 Mexico
USA England Fax: 07531 993710 Cedex, France 9 Hillwood Road, Tsim Sha Tsu Tel: 525 661 56 72
Tel: 978 470 0555 Tel: 01530 417733 Tel: 331 53 99 16 16 Kowloon, Hong Kong Fax: 525 661 54 15
ax: 978 470 0946 Fax: 01530 415436 ax: 331 53 99 16 15 Tel: 852 2739 5497
http://www.andovercontrols.com Fax: 852 2739 7350

Copyright 1998, Andover Controls Corporation. U.S. Patent # 4591967


Data subject to change without notice. All brand names, trademarks, and registered trademarks are the property of their respective holders.
#DS-WallMount-B
VICTORY 100 & 200 SERIES VERIS INDUSTRIES

Enclosed Victory Relays:


10A SPDT

Great For External


Mount Applications V100 V200D

DESCRIPTION FEATURES
Victory 100 and 200 Series 10A enclosed relays are pilot-duty relays in an easy- Sleek field enclosure reduces the need for panel space
to-use nipple mount enclosure. The V100/V200 Series provide quick relay mounting The nipple mount feature allows the Victory Series to be mounted to any
without a dedicated field enclosure, making them ideal for retrofit projects. Field- electrical enclosure
selectable high and low voltage coil inputs provide on-site versatility. Flexible tinned stranded wire...fits easily in tight spaces & provides secure
connections to wire nuts
APPLICATIONS UL508 Listed...designed and approved for field installation...makes electrical
inspection a snap
Command contactors
Run low voltage instead of line voltage...eliminate conduit in some applications
Control motors
Isolation
Device interlocking

TYPICAL COIL PERFORMANCE
Relay logic
Pull in Voltage AC DC
Sense voltages for alarm conditions
10-30V..................................... 8 9
120V........................................ 78
208-277V................................. 154
Drop Out Voltage AC DC
10-30V..................................... 2 3
120V........................................ 18
208-277V................................ 36
RELAYS

Voltage Coil Current


AC DC
10V.......................................... 25mA 14mA
12V.......................................... 25mA 14mA
24V.......................................... 31mA 16mA
30V.......................................... 39mA 18mA
120V........................................ 22mA -
208V........................................ 19mA
277V........................................ 25mA

CONTACT RATINGS
Resistive.............. 10A@277VAC, 28VDC
Motor.................... 120VAC, 1/3HP N.O. & 1/6HP N.C.
240VAC, 1/3HP N.O. & 1/6HP N.C.
277VAC, 1/4HP N.O. & 1/8HP N.C.
Pilot Duty............. 277VAC, (1.7A), 480VA N.O.
Ballast.................. 277VAC, 1.7A
Tungsten............... 120VAC, TV3 N.O. TV2 N.C.
SPECIFICATIONS 5Year
Warranty
Gold Flash............. Yes

Operating Temperature:
V100, V100DC, V200 -34 to 60C (-29 to 140F)
V100D, V200D -40 to 55C (-40 to 131F)
Operating Humidity 10-90% RH non-condensing
Expected Relay Life Electrical (@ rated current) 100,000 cycles; Mechanical (unpowered) 10,000,000 cycles
Relay Status LED ON=energized
Wire Specifications:
Lead Length 14 (356 mm) min.
Gauge UL1015; Coil: 18 AWG; Contacts: 16 AWG
Insulation Class 600VAC RMS
UL 508 enclosed device listing

800.354.8556 +1 503.598.4564 www.veris.com HQ0001833.A 01121


800.354.8556 +1 503.598.4564 www.veris.com

APPLICATION/WIRING EXAMPLES DIMENSIONAL DRAWINGS


Nipple mount directly to a panel V100/V100DC/V200
2.9"
(74 mm)
To Load CO
N TAC
TS

2.8" 1.6"
(71 mm) (41 mm)

COIL 1.7" 1.8"


(43 mm) (46 mm)
To Controls

1/2" NPT Nipple

Nipple mount to any 2x or 4x electrical box V100D/V200D


4.0"
(103 mm)

CONTACTS
To Load
COIL

Wire
Nut

To Controls 3.8" 2.0"


(97 mm) (52 mm)

2.3" 2.5"
(59 mm) (64 mm)

RELAYS
3/4" NPT Nipple

WIRE COLOR CODES


Primary Relay 2 on V100D and V200D only
CONTROL SYSTEM INPUT CONTACT OUTPUT CONTROL SYSTEM INPUT CONTACT OUTPUT
HI White HI
br

br

or a

or a
ow

wht/brown
ow

wht/orange
ng

ng
n

208-277VAC
e

or N.C. 208-277VAC or N.C.


HI White HI
bla

bla

wht/black
ck

ck

120VAC wht/red
120VAC
* YELLOW
*
Common Common
LOW White LOW
blu

blu

wht/blue grey/wht
e

10-30VAC/DC 10-30VAC/DC
COMM ORANGE
COMM
White
ye

ye

wht/yellow
llo

llo

wht/violet
w

Common N.O. Common N.O.


*Isolation600VAC *Isolation600VAC

ORDERING INFORMATION
MODEL RELAY COIL AMPERAGE RATING RELAY POWER LED UL
V100* SPDT 10-30VAC/DC, 120VAC n n
V100D 2x SPDT 10-30VAC/DC, 120VAC n n
V100DC SPDT 10-30VDC 10A n n
V200 SPDT 10-30VAC/DC, 208-277VAC n n
V200D 2x SPDT 10-30VAC/DC, 208-277VAC n n

Some devices are Plenum rated per UL 1995...see White Paper VWP01 at veris.com for details.
* Optional domestic version available.

HQ0001833.A 01121
X SERIES VERIS INDUSTRIES

Control Transformers 1 Hub and Foot


with Separate
Secondary Wires

2 Hub and Foot Foot Mount


Mount Plate Mount

DESCRIPTION APPLICATIONS
Veris X Series Control Transformers are a convenient source of control power for Controller power
HVAC control and building automation applications. A wide variety of UL-listed Switching relays and other digital I/O circuits
transformers are available with single and dual threaded hub mounting options.
Powering sensors
Multiple current limiting options are available, including a circuit breaker in some
models. Save ordering time and purchase order costs when buying other Veris
sensors by including transformers in your order. FEATURES
UL Listings for all models simplify panel building requirements
Threaded hub options maximize installation flexibility
One stop shopping...save time by ordering along with other Veris products

DIMENSIONAL DRAWING
L
W A
POWER SOURCES

H B

Threaded for
* See ordering table for dimensions. conduit nut

WIRE COLORS
STANDARD CENTER TAP
PRIMARY WIRES* SECONDARY WIRES SECONDARY WIRES
COMMON BLACK BLUE 24VAC BLUE 24VAC

120VAC WHITE BROWN 12VAC


BROWN 24VAC
208VAC RED Blk/Wht 0VAC
OR
240VAC ORANGE
WHITE 120VAC
277VAC YELLOW

480VAC GREY Blk/Wht 120VAC

*Primary of 24V isolation transformers= Red/Red

SPECIFICATIONS
Frequency 50/60Hz
Operating Temperature -40 to 65C (-40 to 149F)
No Load Voltage 27-28VAC
Hub Style Fits 1/2" electrical k.o.
Wire UL 1015, 18 AWG*
Wire Length 8 inches
*X085AAA, X375DAC have 14AWG, Secondary wires

800.354.8556 +1 503.598.4564 www.veris.com HQ0001823.B 04121


800.354.8556 +1 503.598.4564 www.veris.com

ORDERING INFORMATION
UL 5085 DIMENSIONS (inches)
MODEL VA PRIMARY VOLTAGE (VAC) SECONDARY CURRENT LIMITING METHOD CLASS MOUNTING SEPARATED UL CE L W H A B
VOLTAGE PRIMARY &
(VAC) SECONDARY WIRES
STANDARD
X020AAA 120 Inherent II, III 1HUB+FT n n 2.3 1.9 2.6 1.59 1.69
X020ACA 277 Inherent II, III 1HUB+FT n n 2.3 1.9 2.6 1.59 1.69
20
X020ADA 24 Inherent General 1HUB+FT n n 2.3 1.9 2.6 1.59 1.69
X020ADB 24 Inherent General 2HUB+FT n n n 2.3 1.9 2.6 1.59 1.69
X040AAA 120 Inherent II, III 1HUB+FT n n 2.7 2.2 2.9 1.98 1.81
24
X040AAB 120 Inherent II, III 2HUB+FT n n n 2.7 2.2 2.9 1.98 1.81
X040ACA 277 Inherent II, III 1HUB+FT n n 2.7 2.2 2.9 1.98 1.81
X040ADA 40 24 Inherent II, III 1HUB+FT n n 2.7 2.2 2.9 1.98 1.81
X040AMB 120/208/240/277 Fuse II, III 2HUB+FT n n n 2.7 2.2 2.9 1.98 1.81
X040BNA 120/208/240 Fuse II, III 1HUB+FT n n 2.7 2.2 2.9 1.98 1.81
X040BPC 24 12/24 Fuse II, III Foot n n n 2.7 2.2 2.9 1.98 1.81
X050BAA 120 Fuse II, III 1HUB+FT n n 2.8 2.2 2.9 2.06 1.81
X050BAB 120 Fuse II, III 2HUB+FT n n n 2.8 2.2 2.9 2.06 1.81
X050BCA 277 Fuse II, III 1HUB+FT n n 2.8 2.2 2.9 2.06 1.81
X050BCB 277 Fuse II, III 2HUB+FT n n n 2.8 2.2 2.9 2.06 1.81
X050BGB 208/240 24 Fuse II, III 2HUB+FT n n n 2.8 2.2 2.9 2.06 1.81
X050CAA 120 Circuit Breaker II, III 1HUB+FT n n 3.5 2.5 3.1 1.91 2.03
X050CBA 120/240/277/480 Circuit Breaker II, III 1HUB+FT n n 3.5 2.5 3.1 1.91 2.03
X050CBB 120/240/277/480 Circuit Breaker II, III 2HUB+FT n n n 3.5 2.5 3.1 1.91 2.03
X050CCA 277 Circuit Breaker II, III 1HUB+FT n n 3.5 2.5 3.1 1.91 2.03
X050CEB 50 208/240/277/480 Circuit Breaker General 2HUB+FT n n n 3.5 2.5 3.1 1.91 2.03
120
X050CEG 208/240/277/480 Circuit Breaker General Plate, 90 Sec Elbow n n n 3.5 4.0 4.0 3.38 3.38
X050CGG 208/240 Circuit Breaker II, III Plate, 90 Sec Elbow n n n 4.0 4.0 4.0 3.38 3.38
X050CHA 120/208/240/480 Circuit Breaker II, III 1HUB+FT n n 3.5 2.5 3.1 1.91 2.03

POWER SOURCES
X050CHB 120/208/240/480 Circuit Breaker II, III 2HUB+FT n n n 3.5 2.5 3.1 1.91 2.03
X050CNA 120/208/240 Circuit Breaker II, III 1HUB+FT n n 3.5 2.5 3.1 1.91 2.03
X050CNB 120/208/240 Circuit Breaker II, III 2HUB+FT n n n 3.5 2.5 3.1 1.91 2.03
X050COA 120/208/240/277/480 Circuit Breaker II, III 1HUB+FT n n 3.5 2.5 3.1 1.91 2.03
X050COB 120/208/240/277/480 Circuit Breaker II, III 2HUB+FT n n n 4.3 2.5 3.1 2.70 2.00
X050DLB 220 None II, III 2HUB+FT n n n 2.8 2.2 2.9 2.06 1.81
X075CAA 120 Circuit Breaker II, III 1HUB+FT n n 3.9 2.5 3.1 2.31 2.03
X075CAB 120 Circuit Breaker II, III 2HUB+FT n n n 3.9 2.5 3.1 2.31 2.03
X075CBA 120/240/277/480 24 Circuit Breaker II, III 1HUB+FT n n 3.9 2.5 3.1 2.31 2.03
75
X075CCA 277 Circuit Breaker II, III 1HUB+FT n n 3.9 2.5 3.1 2.31 2.03
X075CHA 120/208/240/480 Circuit Breaker II, III 1HUB+FT n n 3.9 2.5 3.1 2.31 2.03
X075CHD 120/208/240/480 Circuit Breaker II, III 1HUB+FT n n 3.9 2.5 3.1 2.31 2.03
X085AAA 85 120 Inherent General 1HUB+FT n n 3.2 3.8 3.2 2.2 3.14
X100CAA 120 Circuit Breaker II, III 1HUB+FT n n 4.1 2.5 3.1 2.51 2.03
X100CAB 120 Circuit Breaker II, III 2HUB+FT n n n 4.1 2.5 3.1 2.51 2.03
X100CBA 120/240/277/480 Circuit Breaker II, III 1HUB+FT n n 4.3 2.5 3.1 2.70 2.03
X100CBB 120/240/277/480 Circuit Breaker II, III 2HUB+FT n n n 4.3 2.5 3.1 2.70 2.03
99
X100CBE 120/208/277/480 Circuit Breaker II, III Plate n n 4.3 4.0 4.0 3.38 3.38
X100CHB 120/208/240/480 Circuit Breaker II, III 2HUB+FT n n n 4.3 2.5 3.1 2.70 2.03
X100CKB 480 120 Circuit Breaker General 2HUB+FT n n n 4.1 2.5 3.1 2.51 2.03
X100CLB 220 Circuit Breaker II, III 2HUB+FT n n n 4.1 2.5 3.1 2.51 2.03
X150CAA 150 120 Circuit Breaker General 1HUB+FT n n 3.5 3.8 3.2 2.08 3.26
X175BAB 120 Fuse General 2HUB+FT n n n 4.1 3.8 3.2 3.19 3.14
X175BLB 220 Fuse General Foot n n n 3.8 3.8 3.2 3.05 3.14
X175CAB 175 120 24 Circuit Breaker General 2HUB+FT n n n 4.1 3.8 3.2 3.19 3.14
X175CLB 220 Circuit Breaker General Foot n n n 3.8 3.8 3.2 3.05 3.14
X175DGC 208/240 None General Foot n n n 4.1 3.8 3.2 3.19 3.14
X240DAA 240 120 None General 1HUB+FT n n n 3.7 3.8 4.5 3.24 3.18
X375DAC 375 120 None General Foot n n n 4.3 3.8 4.5 3.83 3.18
CENTER TAP
X020APC 24 Inherent II, III Foot n n n 2.3 1.9 2.6 1.59 1.69
20
X020AQC 120/208/240 Inherent II, III Foot n n n 2.3 1.9 2.6 1.59 1.69
X040BPC 24 Fuse II, III Foot n n n 2.7 2.2 2.9 1.98 1.81
40 12/24
X040BQC 120/208/240 Fuse II, III Foot n n n 2.7 2.2 2.9 1.98 1.81
X050CIA 50 120 Circuit Breaker II, III 1HUB+FT n n n 2.8 2.2 2.9 2.06 1.81
X100CRC Circuit Breaker II, III 1HUB+FT n n n 4.3 2.5 3.1 2.70 2.03
100 120/240
X100CSC 16/32 Circuit Breaker II, III 1HUB+FT n n n 4.3 2.5 3.1 2.70 2.00

HQ0001823.B 04121
SURGE PROTECTION & POWER SOURCES

5YearWarranty
Control Transformers
X020AAA Veris X Series Control Transformers are a convenient Versatile UL Listed transformers...simplify
source of control power for HVAC control and building product selection and installation
automation applications. A wide variety of UL-listed UL Listings for all models simplify panel building
transformers are available with single and dual requirements
threaded hub mounting options. Multiple current Threaded hub options maximize installation
limiting options are available, including a circuit flexibility
breaker in some models. Save ordering time and One stop shopping...save time by ordering along
purchase order costs when buying other Veris sensors with other Veris products
by including transformers in your order.
1 Hub and Foot Mount
APPLICATIONS
Controller power
X050BAB
Switching relays and other digital I/O circuits
Powering sensors

DIMENSIONAL DRAWINGS
L * See ordering table
for dimensions.
2 Hub and Foot Mount W A

X100CBE
H B

WIRE COLORS
STANDARD CENTER TAP
Plate Mount PRIMARY WIRES* SECONDARY WIRES SECONDARY WIRES
COMMON BLACK BLUE 24VAC BLUE 24VAC

X375DAC 120VAC WHITE BROWN 12VAC


BROWN 24VAC
208VAC RED Blk/Wht 0VAC
OR
240VAC ORANGE
WHITE 120VAC
277VAC YELLOW

480VAC GREY Blk/Wht 120VAC

Foot Mount *Primary of 24V isolation transformers= Red/Red

X075CBA

SPECIFICATIONS
Frequency 50/60 Hz
Operating Temperature -40 to 65C (-40 to 149F)
No Load Voltage 27 to 28VAC
Hub Style Fits 1/2" electrical k.o.
Wire UL 1015, 18 AWG*
1 Hub and Foot Mount with Separated Secondary Wires Wire Length 8 inches
*X085AAA, X375DAC have 14AWG, Secondary wires

1 800.354.8556 503.598.4564 www.veris.com 2008 Veris Industries


SURGE PROTECTION & POWER SOURCES

ORDERING INFORMATION
DIMENSIONS (inches)
MODEL # MODEL # VA PRIMARY VOLTAGE SECONDARY CURRENT CLASS MOUNTING SEPARATED UL CE SPECIAL L W H A B
TAC VERIS (VAC)
WHITE VOLTAGE LIMITING PRIMARY & ORDER
(VAC) METHOD SECONDARY WIRES ONLY *
STANDARD
T-255-120 120 Inherent II, III 1HUB+FT n n 2.3 1.9 2.6 1.59 1.69
T-255-277 277 Inherent II, III 1HUB+FT n n 2.3 1.9 2.6 1.59 1.69
20
T-255-24 24 Inherent General 1HUB+FT n n 2.3 1.9 2.6 1.59 1.69
X020ADB 24 Inherent General 2HUB+FT n n n 2.3 1.9 2.6 1.59 1.69
X040AAA 120 Inherent II, III 1HUB+FT n n 2.7 2.2 2.9 1.98 1.81
X040AAB 120 Inherent II, III 2HUB+FT n n n 2.7 2.2 2.9 1.98 1.81
X040ACA 277 Inherent II, III 1HUB+FT n n n 2.7 2.2 2.9 1.98 1.81
40
X040ADA 24 Inherent II, III 1HUB+FT n n 2.7 2.2 2.9 1.98 1.81
X040AMB 120/208/240/277 Fuse II, III 2HUB+FT n n n n 2.7 2.2 2.9 1.98 1.81
X040BNA 120/208/240 24 Fuse II, III 1HUB+FT n n n 2.7 2.2 2.9 1.98 1.81
T-201-1 120 Fuse II, III 1HUB+FT n n 2.8 2.2 2.9 2.06 1.81
X050BAB 120 Fuse II, III 2HUB+FT n n n 2.8 2.2 2.9 2.06 1.81
T-240 277 Fuse II, III 1HUB+FT n n 2.8 2.2 2.9 2.06 1.81
X050BCB 277 Fuse II, III 2HUB+FT n n n 2.8 2.2 2.9 2.06 1.81
T-258 208/240 Fuse II, III 2HUB+FT n n n n 2.8 2.2 2.9 2.06 1.81
X050CAA 120 Circuit Breaker II, III 1HUB+FT n n 3.5 2.5 3.1 1.91 2.03
X050CBA 120/240/277/480 Circuit Breaker II, III 1HUB+FT n n 3.5 2.5 3.1 1.91 2.03
T-245 120/240/277/480 Circuit Breaker II, III 2HUB+FT n n n 3.5 2.5 3.1 1.91 2.03
X050CCA 277 Circuit Breaker II, III 1HUB+FT n n n 3.5 2.5 3.1 1.91 2.03
50
X050CEB 208/240/277/480 Circuit Breaker General 2HUB+FT n n n n 3.5 2.5 3.1 1.91 2.03
120
T-249 208/240/277/480 Circuit Breaker General Plate, 90 Sec n n n n 3.5 4.0 4.0 3.38 3.38
X050CGG 208/240 Circuit Breaker II, III Plate, 90 Sec n n n n 4.0 4.0 4.0 3.38 3.38
X050CHA 120/208/240/480 Circuit Breaker II, III 1HUB+FT n n n 3.5 2.5 3.1 1.91 2.03
X050CHB 120/208/240/480 Circuit Breaker II, III 2HUB+FT n n n n 3.5 2.5 3.1 1.91 2.03
X050CNA 120/208/240 Circuit Breaker II, III 1HUB+FT n n n 3.5 2.5 3.1 1.91 2.03
X050CNB 120/208/240 Circuit Breaker II, III 2HUB+FT n n n n 3.5 2.5 3.1 1.91 2.03
X050COA 120/208/240/277/480 Circuit Breaker II, III 1HUB+FT n n n 3.5 2.5 3.1 1.91 2.03
X050DLB 220 None II, III 2HUB+FT n n n n 2.8 2.2 2.9 2.06 1.81
T-207 120 Circuit Breaker II, III 1HUB+FT n n 3.9 2.5 3.1 2.31 2.03
X075CAB 120 Circuit Breaker II, III 2HUB+FT n n n 3.9 2.5 3.1 2.31 2.03
X075CBA 75 120/208/240/480 24 Circuit Breaker II, III 1HUB+FT n n n 3.9 2.5 3.1 2.31 2.03
X075CCA 277 Circuit Breaker II, III 1HUB+FT n n 3.9 2.5 3.1 2.31 2.03
X075CHA 120/208/240/480 Circuit Breaker II, III 1HUB+FT n n n 3.9 2.5 3.1 2.31 2.03
T-202 85 120 Inherent General 1HUB+FT n n 3.2 3.8 3.2 2.2 3.14
T-208 120 Circuit Breaker II, III 1HUB+FT n n 4.1 2.5 3.1 2.51 2.03
X100CAB 120 Circuit Breaker II, III 2HUB+FT n n n 4.1 2.5 3.1 2.51 2.03
X100CBA 120/240/277/480 Circuit Breaker II, III 1HUB+FT n n 4.3 2.5 3.1 2.70 2.03
X100CBB 120/240/277/480 Circuit Breaker II, III 2HUB+FT n n n 4.3 2.5 3.1 2.70 2.03
99
X100CBE 120/208/277/480 Circuit Breaker II, III Plate n n n 4.3 4.0 4.0 3.38 3.38
X100CHB 120/208/240/480 Circuit Breaker II, III 2HUB+FT n n n n 4.3 2.5 3.1 2.70 2.03
X100CKB 480 120 Circuit Breaker General 2HUB+FT n n n n 4.1 2.5 3.1 2.51 2.03
X100CLB 220 Circuit Breaker II, III 2HUB+FT n n n n 4.1 2.5 3.1 2.51 2.03
X150CAA 150 120 Circuit Breaker General 1HUB+FT n n 3.5 3.8 3.2 2.08 3.26
T-203 120 Fuse General 2HUB+FT n n n 4.1 3.8 3.2 3.19 3.14
X175CLB 175 220 24 Fuse General Foot n n n n 3.8 3.8 3.2 3.05 3.14
T-223 208/240 None General Foot n n n 4.1 3.8 3.2 3.19 3.14
T-204 240 120 None General 1HUB+FT n n n 3.7 3.8 4.5 3.24 3.18
T-205 375 120 None General Foot n n n 4.3 3.8 4.5 3.83 3.18
CENTER TAP
X020APC 24 Inherent II, III Foot n n n n 2.3 1.9 2.6 1.59 1.69
20
X020AQC 120/208/240 Inherent II, III Foot n n n n 2.3 1.9 2.6 1.59 1.69
X040BPC 24 Fuse II, III Foot n n n n 2.7 2.2 2.9 1.98 1.81
40 12/24
X040BQC 120/208/240 Fuse II, III Foot n n n n 2.7 2.2 2.9 1.98 1.81
X050CIA 50 120 Circuit Breaker II, III 1HUB+FT n n n n 2.8 2.2 2.9 2.06 1.81
X100CRC 100 120/240 Circuit Breaker II, III 1HUB+FT n n n n 4.3 2.5 3.1 2.70 2.03

* Special orders are not kept in stock, and may require some additional lead time. Call the factory for more details.

800.354.8556 503.598.4564 www.veris.com 2008 Veris Industries 2


Installation Instructions
Quick-Mount Visual Instructions for Mechanical Installation

Quick-Mount Visual Instructions Preliminary Steps


1. Rotate the damper to its failsafe position. If the shaft rotates counterclockwise, 1. Belimo actuators should be mounted indoors in dry, relatively clean environment
mount the CCW side of the actuator out. If it rotates clockwise, mount the free from corrosive fumes. If the actuator is to be mounted outdoors, a protective
actuator with the CW side out. enclosure must be used to shield the actuator. (See Mechanical Accessories Sec-
2. If the universal clamp is not on the correct side of the actuator, move it to the tion)
correct side. 2. For new construction work, order dampers with extended shafts. Instruct the
3. Slide the actuator onto the shaft and tighten the nuts on the V-bolt with an 8mm installing contractor to allow space for mounting and service of the Belimo actua-
wrench to 6-8 ft-lb of torque. tor on the shaft.
4. Slide the anti-rotation strap under the actuator so that it engages the slot at the 3. For standard mounting, the damper shaft must extend at least 3 1/2" from the
base of the actuator. Secure the strap to the duct work with #8 self-tapping duct. If the shaft extends less than 3 1/2", the actuator may be mounted in its
screws. short shaft configuration.
NOTE: Read the Standard Mounting instructions, on page 92, for more detailed
information.

Dimensions (Inches [mm])


Standard
Mounting Mounting

1/4 to1/2
min. min. 1/4 to 1/2
3-5/1 [6-12] 3/4
[80] 6 [20] [6-12]

min 3/4
[20]

min 3-5/16
[84]

ZDB-TF

M40024 - 05/10 - Subject to change. Belimo Aircontrols (USA), Inc.


min 3/4
[20]

min 3-5/16
[84]

ZDB-TF

800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA

139
Installation Instructions
Mechanical Installation

Mechanical Operation
The actuator is mounted directly to a damper shaft up to 1/2 in diameter by means
of its universal clamp. A crank arm and several mounting brackets are available for
applications where the actuator cannot be direct coupled to the damper shaft. min 3-5/16
[84]
The TF series actuators provide true spring return operation for reliable fail-safe
application and positive close-off on air tight dampers. The spring return system
provides consistent torque to the damper with, and without, power applied to the
actuator.
The TF series provides 95 of rotation and is provided with a graduated position
indicator showing 0 to 95.
The TF-S versions are provided with 1 built-in auxiliary switch. This SPDT switch
is provided for safety interfacing or signaling, for example, for fan start-up. The
switching function is adjustable between 0 and 95.

Standard Mounting / Airtight Damper Procedure


1. See Figure B. Manually move the damper to the fail-safe position (a) (usually
closed). If the shaft rotated counterclockwise ( )), this is a CCW installation.
If the shaft rotated clockwise ( )), this is a CW installation. In a Left Hand
installation, the actuator side marked CW faces out, while in a CW installation,
the side marked CCW faces out. All other steps are identical.
2. The actuator is usually shipped with the universal clamp mounted to the CW
side of the actuator. To test for adequate shaft length, slide the actuator over the
shaft with the side marked CW (or the CCW side if this is the side with the
clamp). If the shaft extends at least 1/8 through the clamp, mount the actuator
as follows. If not, go to the Short Shaft Installation section.
3. If the clamp is not on the correct side as determined in step #1, re-mount the
clamp as follows. If it is on the correct side, proceed to step #5. Look at the
universal clamp. If you are mounting the actuator with the CCW side out,
position the clamp so that the pointer section of the tab is pointing to 0 (see
Fig. C) and the spline pattern of the clamp mates with spline of the actuator.
Remount the stroke limiter to this side then slip the clamp over the spline. (Use
the same procedure if the CW side is out.)
4. See Remounting the Stroke Limiter after the section Short Shaft Mounting with
IND-TF Position Indicator.
5. Lock the clamp to the actuator using the retaining clip.
6. Verify that the damper is still in its full fail-safe position. (a)
M40024 - 05/10 - Subject to change. Belimo Aircontrols (USA), Inc.

7. Mount the spring return actuator to the shaft. Tighten the universal clamp,
finger tight only.
8. Mount the anti-rotation strap at the base of the actuator. Do not tighten the
screws.
9. Remove the screw from one end of the mounting bracket and pivot it away from
the actuator.
10. Loosen the universal clamp and, making sure not to move the damper shaft,
rotate the actuator approximately 5 in the direction which would open the
damper.
11. Tighten the universal clamp to the shaft.
12. Rotate the actuator to apply pressure to the damper seals (b) and re-engage the
anti-rotation strap (c).
13. Tighten all fasteners.

FIGURE B Standard Mounting (Dimensions in Inches [mm])

FIGURE C Universal Clamp

800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA

140
Installation Instructions
Mechanical Installation

Short Shaft Mounting with


min 3/4
IND-TF Position Indicator / Airtight Damper Procedure [20]
If the shaft extends at least 3/4 from the duct, follow these steps:
1. (See Figure D) Move damper blades to the fail-safe position (a).
2. Determine the best orientation for the universal clamp on the back of the
actuator. The best location would be where you have the easiest access to the V
bolt nuts on the clamp. ZDB-TF
3. Engage the clamp to the actuator as close as possible to the determined
location.
4. Lock the clamp to the actuator using the retainer clip.
5. Mount the spring return actuator to the shaft. Tighten the universal clamp,
finger tight only.
6. Mount the anti-rotation strap at the base of the actuator. Do not tighten the
screws.
7. Remove the screw from one end of the mounting bracket and pivot it away from
the actuator.
8. Loosen the universal clamp and, making sure not to move the damper shaft,
rotate the actuator approximately 5 in the direction which would open the
damper.
9. Verify that the damper is still in its full fail-safe position.
10. Tighten the universal clamp to the shaft.
11. Rotate the actuator to apply pressure to the damper seals (b) and re-engage the
anti-rotation strap (c).
12. Tighten all fasteners.
13. Use IND-TF accessory if position indication is needed.

Remounting the Stroke Limiter


1. Remove the stroke limiter by
inserting a small screwdriver, like
the one shown, and gently prying
upward. This procedure takes very
little force. See Figure 1.
2. While holding the back eye-let,
unscrew the end-stop so that eye-
let separates from the end-stop.
3. Flip the limiter over, so the teeth
point the other direction. Replace
the eye-let and end-stop.

M40024 - 05/10 - Subject to change. Belimo Aircontrols (USA), Inc.


4. Flip the actuator over to the
opposite side (this reverses the
spring return direction of the
actuator). Replace the stroke limiter
assembly by inserting the first two
teeth as shown in the orange circle. FIGURE 1
Then press the stroke limiter into
place by pushing downward on thee
adjustable stop.
5. Replace clamp and retaining clip.

FIGURE D Standard Mounting (Dimensions in Inches [mm])

800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA

141
Installation Instructions
Mechanical Installation

Operational Information for TF Actuators Mechanical Angle of Rotation Limiting

Initialization of the TF24-SR (-S) US The TF actuators are provided with an adjustable stop to limit the rotation of the
actuator. This function works in conjunction with the universal clamp or the optional
When power is applied, the internal microprocessor recognizes that the actua- position indicator. The adjustable stop is needed when rotation of less than 95 is
tor is at its full fail-safe position and uses this position as the base for all of its required. The TF actuator can be indefinitely stalled, in any position, without harming
position calculations. This procedure takes approximately 15 seconds. During the actuator.
this time you will see no response at the actuator. The microprocessor will re-
tain the initialized zero during short power failures of up to 25 seconds. When
power is applied during this period, the actuator will return to normal operation
and proceed to the position corresponding to the input signal provided. For
power failures over 25 seconds, the actuator will be at its fail-safe position and
will go through the start up initialization again.

Motor position detection TF24-SR (-S) US 37...100%


Belimo brushless DC motors eliminate the need for potentiometers for posi-
tioning. Inside the motor are three Hall Effect sensors. These sensors detect
the spinning rotor and send pulses to the microprocessor which counts the
pulses and calculates the position to within 1/3 of a revolution of the motor.

Overload protection Using the Universal Clamp

The TF, On/Off actuators are electronically protected against overload. The TF, 1. Loosen the end stop fastening screw using a #2 Phillips screwdriver.
On/Off actuator have an internal current limiter which maintains the current 2. Move the stop block so the bottom edge of the block lines up with the number
at a safe level which will not damage the actuator while providing adequate corresponding to the desired degrees of rotation. (example: 45 degrees of rotation
holding torque. = .5)
3. Lock the block in place with the fastening screw.
The TF24, modulating, actuators (TF24-SR (-S) US, TF24-3 US) are protected
4. Check the actuator for proper rotation.
against overload by digital technology located in the ASIC. The ASIC circuitry
constantly monitors the rotation of the brushless DC motor inside the actuator
and stops the pulsing to the motor when it senses a stall condition. The motor Using the IND-TF Position Indicator with Adjustable Stop
remains energized and produces full rated torque during stall conditions. The NOTE: preferred method if short shaft mounting is used.
actuator will try to move in the direction of the stall every 2 minutes, for a
period of 32 minutes. After this, the actuator will try again every 2 hours. 1. With the actuator in its fail-safe position, place the IND-TF Position Indicator so that
it points to the 0 degree position.
2. Loosen the end stop fastening screw using a #2 Phillips screwdriver.
3. Move the stop block so the bottom edge of the block lines up with the number
corresponding to the desired degrees of rotation (example: 45 degrees of rotation =
.5).
4. Lock the block in place with the fastening screw.
M40024 - 05/10 - Subject to change. Belimo Aircontrols (USA), Inc.

5. Check the actuator for proper rotation.

Direction of Rotation Switch


TF24-3 (-S) US and TF24-SR (-S) US actuators have a direction of rotation switch on
the cover labeled CW-CCW. Switch position indicates start point. For the TF24-SR,
with the switch in position CW, the actuator rotates clockwise with a decrease in
voltage or current. With the switch in position CCW, the actuator rotates counter-
clockwise with a decrease in voltage or current.
The TF24-3 (-S) US and TF24-SR (-S) US actuators rotate clockwise when the switch
is in the CW position and power is applied to wire #3. When power is applied to
wire #4 the actuator rotates counter clockwise.
Rotating the direction of rotation switch to CCW reverses the control logic.
During checkout, the switch position can be temporarily reversed and the actuator
will reverse its direction. This allows the technician a fast and easy way to check the
actuator operation without having to switch wires or change settings on the control-
ler. When the check-out is complete, make sure the switch is placed back to
its original position.

800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA

142
Installation Instructions
Mechanical Installation

Auxiliary Switches Control Accuracy and Stability


The -S model actuators are equipped with an adjustable auxiliary switch used to
indicate damper position or to interface additional controls or equipment. Switching TF24-SR US actuators have built-in
positions can be set over the full 0 to 95 rotation simply by setting a switch on the
actuator. brushless DC motors which provide
1. Set desired switch position. better accuracy and longer service life.
S2
(Example 60%)
0 S1 The TF24-SR US actuators are designed with a unique non-symmetrical dead-
2. As the actuator rotates, the switch .2 band. The actuator follows an increasing or decreasing control signal with a
indicator moves from .6 (60%) toward
0 (0%).
.4 S3 160 mV resolution. If the signal changes in the opposite direction, the actuator
will not respond until the control signal changes by 200 mV. This allows these
.6 actuators to track even the slightest deviation very accurately, yet allowing
S2 the actuator to wait for a much larger change in control signal due to control
S1 signal instability.
1 .8
S3

Switch Rating
Voltage Resistive load Inductive load
250 VAC 3A 0.5 A

M40024 - 05/10 - Subject to change. Belimo Aircontrols (USA), Inc.


Non-Direct Mounting Methods

ZG-TF2 Crank arm Adaptor


p Kit Dimensions (Inches [mm])
KG6
TF_install

3.15"
[81]
1.59"
S 8
SH8 [40.5]
[19.5] [18]
0.77" 0.71"

KG6
G66

0.43"
[11]

0.43"
[11]

800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA

143
Installation Instructions
General Wiring

WARNING The wiring technician must be trained and experienced with electronic Wire Length for TF... Actuators
circuits. Disconnect power supply before attempting any wiring connections or
changes. Make all connections in accordance with wiring diagrams and follow all Keep power wire runs below the lengths listed in the table in Figure A. If more than
applicable local and national codes. Provide disconnect and overload protection as one actuator is powered from the same wire run, divide the allowable wire length by
required. Use copper, twisted pair, conductors only. If using electrical conduit, the the number of actuators to determine the maximum run to any single actuator.
attachment to the actuator must be made with flexible conduit. Example for TF24-SR US: 3 actuators, 16 Ga wire
550 Ft 3 Actuators = 183 Ft. Maximum wire run
Always read the controller manufacturer's installation literature carefully be-
fore making any connections. Follow all instructions in this literature. If you have TF24(-S) US / TF120(-S) US Maximum Wire Length
any questions, contact the controller manufacturer and/or Belimo. Wire Size Max. Feet. Wire Size Max. Feet
12 Ga 1300 Ft. 18 Ga 575 Ft.
14 Ga 1175 Ft. 20 Ga 300 Ft.
Transformers 16 Ga 900 Ft. 22 Ga 150 Ft.
The TF24 . . actuator requires a 24 VAC class 2 transformer and draws a maximum of
5 VA per actuator. The actuator enclosure cannot be opened in the field, there are no TF24-3(-S) US Maximum Wire Length
parts or components to be replaced or repaired. Wire Size Max. Feet. Wire Size Max. Feet
16 Ga 1125 Ft. 20 Ga 400 Ft.
EMC directive: 89/336/EEC
18 Ga 725 Ft. 22 Ga 200 Ft.
Software class A: Mode of operation type 1
Low voltage directive: 73/23/EEC
TF24-SR(-S) US Maximum Wire Length
CAUTION It is good practice to power electronic or digital controllers from a separate Wire Size Max. Feet. Wire Size Max. Feet
power transformer than that used for actuators or other end devices. The power 12 Ga 1800 Ft. 18 Ga 450 Ft.
supply design in our actuators and other end devices use half wave rectification. 14 Ga 1100 Ft. 20 Ga 275 Ft.
Some controllers use full wave rectification. When these two different types of 16 Ga 700 Ft. 22 Ga 125 Ft.
power supplies are connected to the same power transformer and the DC commons FIGURE A
are connected together, a short circuit is created across one of the diodes in the full
wave power supply, damaging the controller. Only use a single power transformer to
power the controller and actuator if you know the controller power supply uses half
Wire Type and Wire Installation Tips
wave rectification.
For most installations, 18 or 16 Ga. cable works well with the TF24 actuators.
Use code-approved wire nuts, terminal strips or solderless connectors where wires
Multiple Actuators, One Transformer are joined. It is good practice to run control wires unspliced from the actuator to
Multiple actuators may be powered from one transformer provided the following the controller. If splices are unavoidable, make sure the splice can be reached for
rules are followed: possible maintenance. Tape and/or wire-tie the splice to reduce the possibility of the
1. The TOTAL current draw of the actuators (VA rating) is less than or equal to the splice being inadvertently pulled apart.
rating of the transformer. The TF24 proportional actuators have a digital circuit that is designed to ignore
2. Polarity on the secondary of the transformer is strictly followed. This means that all most unwanted input signals (pickup). In some situations the pickup may be severe
No. 1 wires from all actuators are connected to the common leg on the transformer enough to cause erratic running of the actuator. For example, a large inductive load
and all No 2 wires from all actuators are connected to the hotleg. Mixing wire No. (high voltage AC wires, motors, etc.) running near the power or control wiring may
M40024 - 05/10 - Subject to change. Belimo Aircontrols (USA), Inc.

1 & 2 on one leg of the transformer will result in erratic operation or failure of the cause excessive pickup. To solve this problem, make one or more of the following
actuator and/or controls. changes:
1. Run the wire in metallic conduit.
2. Re-route the wiring away from the source of pickup.
Multiple Actuators, Multiple Transformers 3. Use shielded wire (Belden 8760 or equal). Ground the shield to an earth ground.
Multiple actuators positioned by the same control signal may be powered from Do not connect it to the actuator common.
multiple transformers provided the following rules are followed:
1. The transformers are properly sized. Brushless DC Motor Operation
2. All No. 1 wires from all actuators are tied together and tied to the negative leg of
the control signal. See wiring diagram. Belimo's brushless DC motor spins by reversing the poles of stationary electromag-
nets housed inside rotating permanent magnets. The electromagnetic poles are
switched by a microprocessor and a special ASIC (Application Specific Integrated Cir-
cuit) developed by Belimo. Unlike the conventional DC motor, there are no brushes to
wear or commutators to foul.

800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA

144
Startup and Checkout
Instructions For TF24-SR(-S) US

TF24-SR(-S) US Electrical Check-Out Procedure


Does Not Give
Gives Expected Response
STEP Procedure Expected Response Expected Response
Go To Step
Go To Step
1. Remove power to reset actuator. Actuator will move to its Control Actuator operates properly Step 8. No response at all Step 2.
Re-apply power. Signal position. Operation is reversed Step 3.
Apply control signal to actuator. Does not drive toward "Control Signal
Position" Step 4.
2. Check power wiring. Correct any prob- Power supply rating should be the total Power wiring corrected, actuator Power wiring corrected, actuator still
lems. See Note 1. power requirement of the actuator(s). begins to drive Step 1. does not drive Step 4.
Minimum voltage of 19.2 VAC or 21.6
VDC.
3. Turn reversing switch to the correct Actuator will move to its Control Actuator operates properly Step 8. Does not drive toward Control Signal
position. Make sure the switch is Signal position. Position Step 4.
turned all the way left or right.
4. Make sure the control signal positive Drives to Control Signal position. Actuator operates properly Step 8. Step 5.
(+) is connected to Wire No 3 and con-
trol signal negative (-) is connected to
wire No. 1. Most control problems are
caused by reversing these two wires.
Verify that the reversing switch is all
the way CCW or CW.
5. Check input signal with a digital volt Input voltage or current should be 1% Controller output (actuator input) is cor- Reprogram, adjust repair or replace
meter (DVM). Make sure the input is of what controller's adjustment or pro- rect. Input Polarity Correct controller as needed Step 1.
within the range of the actuator. For gramming indicate. Step 6.
TF24-SR US this is 2 to 10 VDC or 4 to
20 mA. Note: The input signal must
be above the 2 VDC or 4 mA to have
the actuator move.
6. Loosen the nuts on the V-bolt and Damper will go from fully closed to Damper moves Find cause of damper jam and repair.
move the damper by hand from fully fully open. properly Step 7. Move damper back to the fully closed
closed to fully open. position and tighten the nuts
Step 1.
7. Check damper torque requirement. Torque requirement is actuators mini- Defective Actuator. Recalculate actuator requirement and
mum torque. Replace Actuator - See Note 2. correct installation.
8. Actuator works properly. Test

M40024 - 05/10 - Subject to change. Belimo Aircontrols (USA), Inc.


controller by following controller manu-
facturer's instructions.

NOTE 1 Check that the transformer(s) are sized properly.


If a common transformer is used, make sure that polarity is observed on the secondary. This means connect all No. 1 wires to one leg of the transformer and all No.
2 wires to the other leg of the transformer.
If multiple transformers are used with one control signal, make sure all No. 1 wires are tied together and tied to control signal negative (-).
Controllers and actuators must have separate 24 VAC/VDC power sources.
NOTE 2 If failure occurs within 5 years from original installation date, notify Belimo and give details of the application.

800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA

145
TFB24-SR(-S), TFX24-SR(-S)
Proportional, Spring Return, 24 V, for 2 to 10 VDC or 4 to 20 mA Control Signal

Torque min. 22 in-lbs, for control of air dampers

Application
For proportional modulation of dampers in HVAC systems. Actuator sizing should be
done in accordance with the damper manufacturers specifications.
The actuator is mounted directly to a damper shaft from 1/4 up to 1/2 in diameter
by means of its universal clamp, 1/2 shaft centered at delivery. A crank arm and
several mounting brackets are available for applications where the actuator cannot be
direct coupled to the damper shaft.
The actuator operates in response to a 2 to 10 VDC, or with the addition of a 500
resistor, a 4 to 20 mA control input from an electronic controller or positioner.

Operation
The TF series actuators provide true spring return operation for reliable fail-safe
application and positive close-off on air tight dampers. The spring return system
provides consistent torque to the damper with, and without, power applied to the
actuator.
The TF series provides 95 of rotation and is provided with a graduated position
indicator showing 0 to 95.
The TF uses a brushless DC motor which is controlled by an Application Specific
Technical Data TFB24-SR(-S), TFX24-SR(-S)
Integrated Circuit (ASIC) and a microprocessor. The microprocessor provides the
Power supply 24 VAC 20% 50/60 Hz intelligence to the ASIC to provide a constant rotation rate and to know the actuators
24 VDC 10% exact fail-safe position. The ASIC monitors and controls the brushless DC motors
Power consumption running 2 W rotation and provides a digital rotation sensing function to prevent damage to the
holding 1 W actuator in a stall condition. The actuator may be stalled anywhere in its normal
Transformer sizing 4 VA (class 2 power source) rotation without the need of mechanical end switches. Power consumption is reduced
Electrical connection in holding mode.
TFB... 3 ft, 18 GA plenum cable, 1/2 conduit connector
The TF-S version is provided with one built-in auxiliary switch. This SPDT switch is
-S models: two 3 ft, 18 gauge appliance cables
provided for safety interfacing or signaling, for example, for fan start-up. The switching
with 1/2" conduit connectors
function is adjustable between 0 and 95. The auxiliary switch in the TF-S is double
TFX 3 ft [1m], 10 ft [3m], or 16 ft [5m], 18 GA
insulated so an electrical ground in not necessary.
appliance or plenum cable, with or without 1/2
conduit connector
-S models: two 3 ft [1m], 10 ft [3m] or 16 ft
[5m] appliance cables with or without 1/2" SAFETY NOTE
conduit connectors Screw a conduit fitting into the actuators bushing. Jacket the actuators input and
Overload protection electronic throughout 0 to 95 rotation output wiring with suitable flexible conduit. Properly terminate the conduit in a
Operating range Y 2 to 10 VDC, 4 to 20mA suitable junction box.

N40103 - 09/11 - Subject to change. Belimo Aircontrols (USA), Inc.


Input impedance 100 k (0.1 mA), 500
Feedback output U 2 to 10 VDC, 0.5 mA max
Angle of rotation max 95, adjust. with mechanical stop Dimensions (Inches [mm])

D096
Torque 22 in-lbs [2.5 Nm]
0.68" [16.7]

Direction of rotation spring reversible with cw/ccw mounting


motor reversible with built-in switch
Position indication visual indicator, 0 to 95
(0 spring return position)
[83.72]
3.30"

2.40"
[61]

Running time motor 95 sec constant, independent of load


spring < 25 sec @-4F to 122F [-20C to 50C]
< 60 sec @-22F [-30C]
Humidity 5 to 95% RH non-condensing
Ambient temperature -22F to 122F [-30C to 50C] 6.28"
Storage temperature -40F to 176F [-40C to 80C] [159.5]

Housing NEMA type 2 / IP42, UL enclosure type 2 Standard:


1/4" to 1/2"
Housing material UL94-5VA
Agency listings cULus acc. to UL60730-1A/-2-14, CAN/CSA 1/4" to 5/16"
[76.2]

[5.2]
3.0"

0.2"

E60730-1:02, CE acc. to 2004/108/EC (and


2006/95/EC for -S versions)
Noise level (max) running < 35 db (A)
spring return 62 dB (A)
0.77" [19.5] 0.43" [11]
Servicing maintenance free 4.5"
[114]
Quality standard ISO 9001
Weight 1.4 lbs (0.6 kg), 1.5 lbs (0.7 kg) with switch
Rated Impulse Voltage 800V, Type of action 1.AA (1.AA.B for -S version), Control Pollution Degree 3.

TFB24-SR-S, TFX24-SR-S
Auxiliary switch 1 x SPDT 3A (0.5A) @ 250 VAC, UL approved
adjustable 0 to 95 (double insulated)
800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA / CARIBBEAN

173
TFB24-SR(-S), TFX24-SR(-S)
Proportional, Spring Return, 24 V, for 2 to 10 VDC or 4 to 20 mA Control Signal

Accessories

W1228
24 VAC Transformer 6
Tool-06 8mm and 10 mm wrench
KH-TF Crank arm for up to 1/2 round shaft Blk (1) Common
Line
ZG-TF2 Crank arm adaptor kit for TF Volts 3
Red (2) + Hot
ZG-TF112 Mounting bracket, kit for TF
Wht (3) Y1 Input, 2 to 10V
ZS-100 Weather shield (metal) Control Signal ()
ZS-150 Weather shield (polycarbonate) 2 to 10 VDC (+)
NOTE: When using TFB24-SR (-S), TFX24-SR (-S) actuators, only use accessories listed on this page. Org (5) U Output, 2 to 10V
2 to 10 VDC ()
For actuator wiring information and diagrams, refer to Belimo wiring guide.
Feedback Signal (+)

2
Typical Specification
Spring return control damper actuators shall be direct coupled type which require
no crank arm and linkage and be capable of direct mounting to a shaft up to a 1/2 2 to 10 VDC control of TFX24-SR(-S)
diameter and center a 1/2 shaft. The actuator must provide proportional damper
control in response to a 2 to 10 VDC or, with the addition of a 500 resistor, a 4 to
20 mA control input from an electronic controller or positioner.The actuators must be
designed so that they may be used for either clockwise or counterclockwise fail-safe
operation. Actuators shall use a brushless DC motor controlled by a microprocessor
and be protected from overload at all angles of rotation. Run time shall be constant,
and independent of torque. If required, one SPDT auxiliary switch shall be provided
having the capability of being adjustable. Actuators with auxiliary switch must be
constructed to meet the requirements for Double Insulation so an electrical ground is
not required to meet agency listings. Actuators shall be cULus listed certified, have a Org (5) U Output, 2 to 10V
5 year warranty, and be manufactured under ISO 9001 International Quality Control
Standards. Actuators shall be as manufactured by Belimo.

Wiring Diagrams

4 to 20 mA control of TFB24-SR(-S), TFX24-SR(-S)


CAUTION Equipment Damage!

W1222
2
Up to 4 actuators may be connected in parallel. With 4 actuators wired to
one 500 resistor, a +2% shift of control signal may be required. Power
consumption must be observed.

3 Actuator may also be powered by 24 VDC.

5 Only connect common to neg. () leg of control circuits.



N40103 - 09/11 - Subject to change. Belimo Aircontrols (USA), Inc.

Actuators with plenum rated cable do not have numbers on wires; use
6 color codes instead.
For end position indication, interlock control, fan startup, etc., TFB24-SR-S,
7 TFX24-SR-S incorporates one built-in auxiliary switch: 1 x SPDT, 3A
(0.5A ) @250 VAC, UL Approved, adjustable 0 to 95. Auxiliary switch of TFB24-SR-S, TFX24-SR-S

Meets cULus requirements without the need of an electrical ground


connection.
The ZG-R01 500 resistor converts the 4 to 20 mA control signal to
2 to 10 VDC.

WARNING
G Live Electrical Components!
During installation, testing, servicing and troubleshooting of this product, it may be
necessary to work with live electrical components. Have a qualified licensed electrician or other
individual who has been properly trained in handling live electrical components perform these
tasks. Failure to follow all electrical safety precautions when exposed to live electrical compo-
nents could result in death or serious injury.

800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA / CARIBBEAN