REMARKS:
CC:
Signed:
Patrick Dougherty
Columbia University
Graduate School of Journalism
Brown Institute for Media Innovation
Columbia University
2950 Broadway
New York, NY 10027
Updated Checked
Rev Date TAC Job # Description by by
1 11/25/13 NC13N2951 Submittal FS AMP
2 1/2/14 NC13N2951 Revised to Resubmit YBS AMP
Columbia University
Graduate School of Journalism
Brown Institute for Media Innovation
Columbia University
2950 Broadway
New York, NY 10027
Controls Drawings
Communication Riser
Page 1
Page 0
Architect: LTL
2950 Broadway
Contractor: Giachetti
Engineer: Buro Happold
H-000 Communication Riser
11/25/2013
SE7300F5045B SE7300F5045B
1/2/2014
SE7300F5045B SE7300F5045B
VAV-M201A VAV-201AB
Date:
VAV-201B VAV-202 FCU-S1 FCU-S2 FCU-S3 FCU-S4
SUBMITTAL
Revised to Resubmit
Record Drawing
SE7300F5045B SE7300F5045B SE7300F5045B SE7300F5045B SE7300F5045B SE7300F5045B SE7300F5045B SE7300F5045B
# Change:
Revision:
FCU-N4 FCU-N3 FCU-N2 FCU-N1 FCU-E3 FCU-E2 FCU-E1 FCU-S5
1
2
3
4
5
Date: 11/22/2013
11/22/2013
200 Level
Buro Happold
Date:
Date:
Ethernet Tie into Existing BMS Network Bacnet MS-TP
Giachetti
AMP
Ethernet Tie into Existing Fire Alarm System
LTL
FS Designed by:
Software by:
Checked by:
AHU-1E Panel
Contractor:
Engineer:
Located in Level 100
Architect:
30X36X10
Communication Riser
New York, NY 10027
2950 Broadway
B3865-V B3865-V B3865-V B3865-V SE7300F5045B
bCX-CR-8-INF b3920-1E
b3920 VAV-201N VAV-201S VAV-201C VAV-M201C FCU-IT
100 Level
1/2/2014
1/2/2014
Last Printed
Last Saved
NC13N2951
Job Number
Note: Coordinate thermostat Legend:
Riser Submittal
Comm
placements with landlord and
1.vsd
Sheet Number
BACnet MS/TP
File Name
1
construction manager
OF
H-000
Rev
Ethernet
1
Columbia University-
Graduate School of Journalism
Brown Institute for Media Innovation
Columbia University
2950 Broadway
New York, NY 10027
AHU Flow
Title Page
Panel Layout
AHU Wiring 2
AHU Wiring 1
System Sequence
Drawing Index:
Contractor: Giachetti
Engineer: Buro Happold
H-001 Air Handling Unit
11/25/2013
Controller Designator Gray GRY GY a
1/2/2014
from Controller 4. All thermowells shall be filled with heat conductive compound that is provided.
UI# SaTmp
White WHT WH w
Date:
COM 00_00
5. Wiring Terminations designated as X or XX indicate information was unavailable at time Gold GLD GL d
SUBMITTAL
of submittal. Please inform Schneider Electric before making field terminations. Silver SLV SV s
Pink PNK PK p
6. Remote control devices, not in local panels, shall be accessible for adjustment and
Temperature
Temperature Temperature Temperature Temperature Temperature service - below 7' above fixed floor whenever possible or as shown on the provided
Sensor, Bulb
Sensor, Duct Probe Sensor, Immersion Sensor, Averaging Sensor, Outside Air Sensor, Room Construction prints. 1-Letter abbreviations used for color of stripe on
(Strap-On)
SaTmp HwSTmp MaTmp RmTmp DxSucTmp wire. (WH/o = White wire with orange stripe)
Revised to Resubmit
00_00 00_00 00_00 00_00 00_00 7. Only prints marked Construction are to be used during installation. If the prints are not
OaTmp
Record Drawing
UI# COM UI# COM UI# COM UI# COM UI# COM marked Construction, the installer will correct any discrepancies between prints used and
00_00
RD BK RD BK RD BK
UI# COM
RD BK RD BK
Construction at no cost to Schneider Electric.
# Change:
TS# TS# TS# TS# TS#
Revision:
RD BK
TS# 8. All new BAS controller panels shall have a dedicated 120Vac power source. This source
shall be located and marked in the electrical panel as well as on the control prints returned to
Schneider Electric for Record prints.
1
2
3
4
5
Hydronic Heating Hydronic Cooling 9. Installer responsible for maintaining existing safeties into new BAS control electrically or
Gas Heating Current Sensor Pressure Sensor Pressure Switch pnuematically connected.
Coil Coil
SaFanStat SaStP
Gas 00_00 00_00 10. See Division 23 09 15 00 for any additional information on installation standards.
Date: 11/22/2013
11/22/2013
NO COM UI# COM
Htg + - NC C
LO HI LO HI
NO COM PS1 PS1
CSR1
Wiring Legend
Buro Happold
Date:
Date:
Low Voltage (50 volts or less) control wiring for inputs and outputs shall be 18 AWG or larger rated for 600-volt service. Terminate any
Giachetti
HeatPump or Dual shields or drains for input/outputs at the controller only. See Section 4.2 for additional details.
DX Cooling Electric Heating Smoke Detector Transformer Filter
Pipe Coil
AMP
LTL
1 Stage Indicates need for conduit to be ran by installer. Distances noted on plans are approximate values.
FS
Elect FILTER
D
Designed by:
Software by:
Checked by:
+
_ SD2
Contractor:
Engineer:
X
Architect:
Se
Pri
Htg c
XFR1
Ethernet
Ethernet Wiring: Unless stated differently by the client or the Schneider Electric Site Supervisor, network cable shall meet or exceed all
2950 Broadway
Legend
MS/TP BACnet or I/Net Wiring: Wiring to be installed using 24 AWG 7/26 Bare Copper 2 conductor stranded, 7/32 drain wire, 12.5
MS/TP pF/ft @ 1 KHz nominal UL TYPE CMP/CL3P 24 AWG. Maximum length is 4000' or 110 controllers. End of Line resistor (120 1/4W)
CHILLE
R CHWP01 to be installed at both ends of network segments. All communication cabling to be installed in a daisy chain configuration, no Ts are
Boiler #1
Heat permitted. Shield on communication cable is to remain continuous and grounded only at a controller. Polarity of the wires must be
Exchanger observed. Splicing of communication cable is not permitted. Cable can be purchase through Schneider Electric using this part number:
WBAC-4-242P-OR-SP
LON or FFT-10 Wiring to be installed using Level IV network cable. Level IV network cable is 22 AWG 7/30 Bare Copper, 2 conductor
FTT-10
VFD Motor Starter 3-way Valve 2-way Valve Fan Damper stranded, with or without a 7/32 drain wire, 17 pF/ft, and impedance of 100 ohm (1-20MHz) nominal UL TYPE SUBJECT 444, CMP.
1/2/2014
1/2/2014
Last Printed
Last Saved
The same cable shall be used through out the project to avoid impedance issues. Maximum length is 4600' or 55 controllers without
use of repeater. Terminator to be installed at both ends of network segments. All LON/FFT-10 cabling to be installed in a daisy chain
See Valve Schedule D1 D1
configuration (not FTT-10A). This cable is not to run in the same conduit with power for more than 5'. Splicing of communication
NC13N2951
CV1 CV1 CV1
N.O. N.O. cable is not permitted. Cable can be purchase through Schneider Electric using this part number: WLON-3-221P-BL-BX
Job Number
VFD STARTER
A AB N.O. N.C.
File AHU-EF
B
Submittal Rev
Number
Name
7
1.vsd
L3 L2 L1 L3 L2 L1
OF
480 VAC 480 VAC
Sheet
H-001
1
Floor Plan Legend is independent, please refer to Legend on that Page
Electric. Their use or reproduction without prior consent of
Sequence of Operation
11/25/2013
maintain 45F plenum temperatures.
1/2/2014
cooling/heating coils, shall stop the fans when the cooling coil entering
Date:
15. Monitor differential pressures across filter and annunciate alarm when
temperature falls below 35F (adj.), for 3 minutes (adj. 0-15 minutes at time
SUBMITTAL
differentia pressure set point is exceeded.
delay relay in control panel). Chilled water valve shall close, heating valve shall
16. If the supply fan fails to operate an alarm shall be annunciated at the BMS and
open. Freeze stats shall automatically reset when temperature rises above trip
dampers shall be indexed to their normal off positions.
set point. If 3 (adj.) freeze stat shutdowns occur within 15 minutes (adj.), unit
17. The Fire Alarm System shall signal the BMS when a fire alarm is present.
shall be commended off until reset from BMS computer.
When the floor/area the fans serves is in alarm, the FAS shall shut down the
Revised to Resubmit
4. For fans greater than 2,000 cfm, provide a high discharge static pressure
fans and close all dampers. Upon fire alarm reset all fans shall sequentially start
Record Drawing
switch if dampers are located upstream of the fan and/or a low static pressure
and operate in the normal mode.
switch if dampers are located downstream of the fan to prevent mechanical
# Change:
18. Demand Ventilation controls (DCV):
Revision:
damage if a damper fails to open. The switch shall stop the fan when duct
Upon a rise in zone CO2 concentration above set-point, the minimum occupied
pressure exceeds design. The fan shall remain off until the pressure switch is
airflow set-point at the zone VAV terminal shall first be reset from the design
1
2
3
4
5
reset.
minimum up to a ventilation override maximum value, 700 ppm (adj).
5. The AHU shall be started by the BMS based upon a start time optimization
program, time of day schedule, or manual command. Upon a command to start, Upon continued call for ventilation (based on continued rise in critical zone CO2
all associated dampers shall open and prove open through damper mounted concentration with VAV terminal at ventilation override maximum setpoint,
Date: 11/22/2013
11/22/2013
limit switch then the supply and return fans shall start. The outdoor air damper then increase the AHU minimum outdoor air rate (damper position) to design
and exhaust air damper shall be closed. minimum.
6. The AHU supply fan shall start and slowly ramp up to speed control set point.
The supply fan variable speed drive shall be controlled to maintain the supply
Buro Happold
Date:
Date:
static pressure set point, as sensed at a point 2/3 downstream of the supply fan. Propeller Exhaust Fan (EF-1)
Giachetti
7. The set point temperature noted in the schedule sheet for unit operation. The 1. As the space pressure sensor increases above the set point of 0.1 / WG ( Adj)
discharge set point (adjustable) for the air handling unit is presently set at
AMP
compare to outdoor pressure, the exhaust fan shall turn on.
LTL
FS Designed by:
Software by:
Checked by:
54.1 F DB / 53.9 F WB
Contractor:
Engineer:
Architect:
8. Morning Warm-up: The system shall be indexed to morning warm-up mode if Condensate pump
the return air temperature is below 60F (adj.) during start-up. The heating coil 1. BMS Contractor shall furnish, install and wire DDC controls and connection to
System Sequence
9. Morning Cool-down: The system shall be indexed to morning cool-down mode level inside tank.
2950 Broadway
if the return air temperature is above (80F adj.) during start-up. The cooling 3. If the pump fails to operate an alarm shall be annunciated at the BMS. AHU-1E
coil valve shall be controlled to maintain discharge air set point 54F (adj.). and FCU-IT served by the condensate pump shall be shut down.
Then it shall be indexed to the occupied mode.
10. Occupied Mode: The supply fan shall run continuously. The interlinked outdoor
air damper, the return and exhaust air dampers shall move to the fixed positions.
11. Unoccupied Heating: During unoccupied periods if the space temperature falls
below the unoccupied setback set point (60F adj.) the AHU shall cycle on and
the heating coil valve shall be controlled to maintain the space temperature at
1/2/2014
1/2/2014
Last Printed
Last Saved
setpoint .
12. Unoccupied Cooling: During unoccupied periods if the space temperature rises
NC13N2951
above the unoccupied setup set point (80F adj.) the AHU shall cycle on and the
Job Number
cooling coil valve shall be controlled to maintain the space temperature at 80F
File AHU-EF
Submittal Rev
(adj).
Number
Name
7
1.vsd
OF
Sheet
H-001
2
Electric. Their use or reproduction without prior consent of
These drawings and designs are the property of Schneider
AHU FLOW DIAGRAM
EXDpr
AHU-#RATmp AHU-#RACO2
AHU-1E
AHU-1E AHU-1E
Space V12 GND
IN1 RET IN6 RET PWR
11/25/2013
1/2/2014
GND XFR
24H 1
4 DmpCmd
Date:
M M GRN WHT CO2 COM PWR
Exhaust Fan TS-D CO2
SUBMITTAL
EA N.C. N.C. RA
Revised to Resubmit
AHU-1E COM2
Record Drawing
EF-FailAlm IN3
xPUI4-1 RET
AHU-#RADpr
# Change:
EFSpd V15
Revision:
AHU-1E
AHU-1E GND VFD
N.O. GND V13
EF-#EmgStop -
M
by FAS Contractor -
1
2
3
4
5
RADpr
2 EFDPS R2 See Damper Schedule
L1 L2 L3
120 VAC
ETD500-6
OADpr
Date: 11/22/2013
11/22/2013
AHU-#OATmp FilterDPS FilterDPS AHU-#PHCTmp 1 SaFan SF-#LoTmp AHU-#CCTmp 3 SaFan SF-#DPSHi AHU-#SaTmp AHU-#StPrs Note: Location of static
AHU-1E
AHU-1E xPUI4-1 AHU-1E AHU-1E AHU-1E AHU-1E AHU-1E AHU-1E AHU-1E pressure to be 2/3 downstream
V14 GND
IN5 RET IN2 RET IN10 RET IN2 RET IN9 RET IN3 RET IN12 RET IN4 RET IN13 RET of the supply fan.
OA-AFMS
AHU-1E
GRN WHT M IN16 RET High
NO C
Low High
NO C
Low
GRN WHT M1 L1 GRN WHT
Supply Fan
N.C. COM GRN WHT + -
TS-D DPS1 DPS1 TS-Avg LoTmp TS-Avg DPS2 TS-D StP
Buro Happold
Date:
Date:
OA N.C. SA
Giachetti
PRE-FILTER FILTER
AMP
OADpr IN15 SF-#Sts
LTL
CSR3
FS
See Damper Schedule RET AHU-1E
AFS
HWS CHWS NO3 SF-#SS
Designed by:
Software by:
Checked by:
COM3 AHU-1E
Contractor:
Engineer:
Architect:
V16 SF-#Spd
GND AHU-1E
See Valve Schedule IN4 SFSpdFdbk
AB A AB A
HWR CHWR RET xPUI4-1
See Valve Schedule
2950 Broadway
AHU-1E
V11 GND V10 GND
AHU Flow
R1 LoTmp 1 SFDPS 3
DprCmd 4
Condensate
Pump
L3 L2 L1
Condensate Out 120 VAC
IN1 CondPmpSts
CSR4
RET XPUI4-1
RmTmp
AHU-1E STARTER AHU-1E
IN17 RET SPWR Device Qty Part Number Description Manufacturer
120 VAC ----------------------------------------------------------------------------------------------------------------------------------------------------
1/2/2014
1/2/2014
Last Printed
Last Saved
L3 L2 L1 Electrical
IN RET SPWR CO2 1 VER-CDE CO2 SENSOR DUCT Veris Industries
TS1 CSR4 1 VER-H608 CURRENT SWITCH N.O. SPLIT CORE Veris Industries
CSR1-3 3 VER-H904 VFD CURRENT SWITCH N.O. SPLIT Veris Industries
NC13N2951
DPS 1 KEL-AFS-222 .05-12IN DIFF PRESS SWITCH Cleveland Controls [AFS-222]
Job Number
DPS1 2 KEL-AFS-262 .05-2IN PRESS SWITCH Cleveland Controls [AFS-262]
DPS2 1 KEL-AFS-460 .4-12IN SPST SWITCH W/MAN RES Cleveland Controls [AFS-460]
File AHU-EF
Submittal Rev
DPS1_1 4 KEL-A-302-K STATIC PRESSURE TIP 1/4 BARB Kele [A-302-K]
Number
LoTmp 1 JON-A70HA-1 ELECTRIC TEMP CONTROL 4 WIRE Johnson Controls
Name
7
1.vsd
StP 1 KEL-M267-MR3-C DP XMTR 0-5IN WC LOW AIR Setra Sensing Solutions
TS1 1 TTS-SD-LCD-1 SMART SENSOR, LCD DISPLAY, 10K Schneider Electric [TTS-SD-LCD-1]
OF
Sheet
TS-Avg 2 ETA500-12 TEMP SENSOR AVERAGE 12' 10K T3 Schneider Electric [ETA500-12]
H-001
3
TS-D 3 ETD500-6 TEMP SENSOR DUCT WBOX 10KT3 6" Schneider Electric [ETD500-6]
AIR HANDLING UNIT 1E WIRING DETAIL 1
11/25/2013
2 COM2 77 X2
1/2/2014
SS:EF-#SS T2-6 Start/Stop
SERVICE NO2 76 R3-1
Date:
PORT NC3 75
3 COM3 74 X2
To: Next Controller SS:SF-#SS
SUBMITTAL
RS-485 NO3 73
13 R4 14 X1
4 + NC4 72
From: Previous Controller Condensate
Return Air + T1-1 5 - 4 COM4 71 X2 5 9 T2-11
R1:CondPSS Pump
Temperature - T1-2 6 SHLD NO4 70 T2-12
R4-1 Start/Stop
NC5 69
Revised to Resubmit
8 IN1 6 COM6 65 (NO)
Cooling Coil + T1-5 9 IN2 NO6 64
TS-Avg:AHU-#PHCTmp
Record Drawing
Temperature - T1-6 Off On NC7 63 X1 T2-7
10 RET IN1
7 COM7 62 FSD Cmd
TS-Avg:AHU-#CCTmp T2-8
IN2
11 IN3 NO7 61
Supply Air + T1-7
# Change:
IN3
12 IN4 NC8 60
Revision:
Temperature - T1-8 TS-D:AHU-#SaTmp IN4
8 COM8 59
IN5
13 RET NO8 58
TS-D:AHU-#OATmp IN6
14 IN5
Outside Air + T1-9
1
2
3
4
5
IN7
15 IN6 ANALOG
Temperature - T1-10 CO2:AHU-#RACO2 IN8 OUTPUTS
X2
16 RET I9 57
+ T1-11 17 IN7 9 V9 56 T2-13 B 1 Chilled Water
- T1-12 18 IN8 GND 55 X1 T2-14 R 2 Control Valve
Return Air CO2 CSR1:UH-Sts
T2-15 (NC)
24(+) T1-13 I10 54 W 3
24(-) T1-14 19 RET 10 V10 53
LoTmp:SF-#LoTmp CHWVlv:AHU-#CHWVlv
X2 X1 20 IN9 GND 52 X2
Date: 11/22/2013
11/22/2013
21 IN10 I11 51
B 1
DPS1:FilterDPS T2-16 Hot Water
Unit Heater + T1-15 Off On 11 V11 50
IN9 HWVlv:AHU-#HWVlv X1 T2-17 R 2 Control Valve
Temperature - T1-16 22 RET GND 49
DPS:EX-#DPSHi IN10 T2-18 W 3 (NO)
23 IN11 I12 48
IN11
24 IN12 12 V12 47
DPS:SF-#DPSHi IN12 Damper:EXDpr X2
Unit Heater Fan NO T1-17 GND 46
IN13 T2-19 B 1 Exhaust Air
Buro Happold
Status COM T1-18 25 RET I13 45
Date:
Date:
StP:AHU-#StPrs
26 IN13 IN14
13 V13 44 X1 T2-20 R 2 Damper
X2 IN15 Damper:AHU-#RADpr
27 IN14 GND 43 T2-21 W 3 (NC)
CSR1:EF-#Sts
Giachetti
IN16
NO T1-19 I14 42
Low Temp
COM T1-20 13 R5 14 X1 28 RET 14 V14 41 X2
CSR1:SF-#Sts Damper:OADpr
AMP
29 IN15 GND 40
B 1
LTL
T2-22 Return Air
FS
5 9 30 IN16 I15 39
AFMS:OA-AFMS X1 T2-23 R 2 Damper
R5-1 15 V15 38
Speed:EF-#Spd T2-24 W 3 (NO)
31 SPWR GND 37
Designed by:
X1
Software by:
Checked by:
A This Page
Contractor:
R6-1
R5-2 TS1:RmTmp 32 RET I16 36
X2
Engineer:
Architect:
33 IN17 16 V16 35
NO T1-21 Speed:SF-#Spd
T2-25 B 1 Outside Air
Dirty Filter Alarm SMART GND 34
COM T1-22 SENSOR X1 T2-26 R 2 Damper
T2-27 W 3 (NC)
Exhaust Fan NC T1-23 X2
2950 Broadway
AHU Wiring 1
High DPS COM T1-26 13 R7 14 X1 (No field wiring required.)
5 9
Located in AHU-1E Supply Fan VFD
R7-1
A This Page B This Page T2-30 Supply Fan
R7-2 T2-31 VFD Speed
1/2/2014
1/2/2014
Exhaust Fan NO T1-29
Last Printed
Last Saved
Status COM T1-30
NC13N2951
Status COM T1-32
Job Number
AHU-1E
File AHU-EF
Submittal Rev
+ T1-33 B(+) B(+) Device Qty Part Number Description Manufacturer
Outside Air - T1-34 B(-) IIM-1 B(-)
Number
----------------------------------------------------------------------------------------------------------------------------------------------------
Name
Flow Measure +24 T1-35 X1
7
1.vsd
Panel
-24 T1-36 X2
AHU-1E 1 b3920 b3920, 16 UI, 8 DO, 8AO, 1 Sma Schneider Electric [b3920]
OF
Sheet
R1-7 7 KEL-RH2B-ULAC24V RELAY W/LIGHT 24V IDEC [RH2B-ULAC24V]
H-001
4
+24 T1-37 R1-7_1 1 KEL-SH2B-05 DPDT RELAY SOCKET DIN RAIL MTD IDEC [SH2B-05]
Room Temp - T1-38
+ T1-39
AIR HANDLING UNIT 1E WIRING DETAIL 1
11/25/2013
1/2/2014
Date:
Schneider Electric
SUBMITTAL
UNIVERSAL
INPUTS
xPUI4
Supply Fan NO T1-40 1 RET
CSR2:CondPmpSts
Status COM T1-41 2 IN1
3 IN2
DPS1:FilterDPS Off On
Dirty Pre-Filter NO T1-42 IN1
Alarm COM T1-43 4 RET IN2
Failure:EF-FailAlm
5 IN3 IN3
NO T1-44
Revised to Resubmit
EA Fan Failure 6 IN4 IN4
COM T1-45 Speed:SFSpdFdbk
Record Drawing
SF Speed + T1-46
Feedback - T1-47
# Change:
Revision:
xPUI4-1
1
2
3
4
5
Schneider Electric
UNIVERSAL
INPUTS
xPUI4
NO T1-48 1 RET
Date: 11/22/2013
11/22/2013
SA Fan Failure Failure:SF-Fail
COM T1-49 2 IN1
3 IN2
Off On
T1-50 IN1
Spare
T1-51 4 RET IN2
5 IN3 IN3
T1-52
Spare 6 IN4 IN4
T1-53
Buro Happold
Date:
Date:
T1-54
Spare
T1-55
Giachetti
TRANSFORMER WIRING DETAIL
AMP
Typical of 1 Unit
LTL
FS
xPUI4-2 (AHU-1E)
Designed by:
Software by:
Checked by:
Contractor:
Transformer Details
Engineer:
Architect:
120vac, Plug, b3920 controller
24vac
and 175VA field transformer. X1
2950 Broadway
AHU Wiring 2
120N N N1
N
120H H
BACnet CNTRL 32N CB1
CB2 H1
Schneider Electric CB3
bCX1 CB4
ETHERNET UL Panel Details
INPUT
POWER Max Voltage: 120 vac / 60 Hz
SERVICE
G GND 24 VAC
PORT SSCR: 10 kA
XFR 24N N N/- Total FLA: 6.54 A
1/2/2014
1/2/2014
1 24H L L/+ 12-28 VDC RS-485
Last Printed
Last Saved
CB 1 = 8.00 A (MAIN) AHU-1E
SHLD S CB 2 = 5.00 A (PLUG) Device Qty Part Number Description Manufacturer
- -
CB 3 = 1.00 A (CONTROLLER) ----------------------------------------------------------------------------------------------------------------------------------------------------
From: Previous Controller
+ +
Panel
CB 4 = 2 A (120/24VAC)
NC13N2951
COMM To: Next Controller CB 5 = 8.00 A (24VAC TRANS) bCX1 1 BCX1-CR-32 BACnet CNTRL 32N Schneider Electric
Job Number
PORT1 XMR1 1 VER-X150CAA TRANSFORMR CTRL 120V/24V 150VA Veris Industries [X150CAA]
RS-232
File AHU-EF
Submittal Rev
RS-232
Number
AHU-1E-XP
Name
7
1.vsd
Device Qty Part Number Description Manufacturer
----------------------------------------------------------------------------------------------------------------------------------------------------
OF
Sheet
Panel
H-001
bCX1
5
xPUI4-1-2 2 xPUI4 XP EXP MODULE - 4 UI Schneider Electric
BCX1-CR-32
43.00 x 1.00
PANDUIT
27.00 x 1.00
27.00 x 1.00
25.00 x 1.00
T2
T1
UL Tag
1
1
50
40
36.20 x 1.00
PANDUIT
13.00 x 1.00
1" Free Space
ON
OFF
8A
CB- 5
b3920
bCX1
PANDUIT
PANDUIT
PANDUIT
xPUI4
xPUI4
PANDUIT
24V
120V
150 VA
Panel Layout
ON
1" Free Space
OFF
ON
OFF
ON
OFF
1" Free Space
ON
OFF
2A 1 A 5 A 8 A
CB- 4 CB- 3 CB- 2 CB- 1
36.00 x 1.00
PANDUIT
Space Space Space Space Space Space Space
1" Free 1" Free 1" Free 1" Free 1" Free 1" Free 1" Free
4.75 x 1.00
DIN1
TDR
10.25 x 1.25
IIM-1
PANDUIT
R7 R6 R5 R4 R3 R2 R1
Space Space Space Space Space Space Space
1" Free 1" Free 1" Free 1" Free 1" Free 1" Free 1" Free
43.00 x 1.00
CP1 PANDUIT
CP1
Panel
Device
AHU-1E
Qty Part Number
1 UNM-SCH303610RC
Description
Unity Manufacturing
11/25/2013
Electrical
1/2/2014
CO2 1 VER-CDE CO2 SENSOR DUCT Schneider Electric
Date:
CSR4 1 VER-H608 CURRENT SWITCH N.O. SPLIT CORE Schneider Electric
SUBMITTAL
CSR1-3 3 VER-H904 VFD CURRENT SWITCH N.O. SPLIT Schneider Electric
DPS 1 KEL-AFS-222 .05-12IN DIFF PRESS SWITCH Schneider Electric
DPS1 2 KEL-AFS-262 .05-2IN PRESS SWITCH Schneider Electric
DPS2 1 KEL-AFS-460 .4-12IN SPST SWITCH W/MAN RES Schneider Electric
DPS1_1 4 KEL-A-302-K STATIC PRESSURE TIP 1/4 BARB Schneider Electric
LoTmp 1 JON-A70HA-1 ELECTRIC TEMP CONTROL 4 WIRE Schneider Electric
Revised to Resubmit
StP 1 KEL-M267-MR3-C DP XMTR 0-5IN WC LOW AIR Schneider Electric
TS1 1 TTS-SD-LCD-1 SMART SENSOR, LCD DISPLAY, 10K Schneider Electric
Record Drawing
TS-Avg 2 ETA500-12 TEMP SENSOR AVERAGE 12' 10K T3 Schneider Electric
TS-D 3 ETD500-6 TEMP SENSOR DUCT WBOX 10KT3 6" Schneider Electric
# Change:
Revision:
Panel
AHU-1E 1 b3920 b3920, 16 UI, 8 DO, 8AO, 1 Sma Schneider Electric
1
2
3
4
5
bCX1 1 BCX1-CR-32 BACnet CNTRL 32N Schneider Electric
R1-7 7 KEL-RH2B-ULAC24V RELAY W/LIGHT 24V Schneider Electric
R1-7_1 1 KEL-SH2B-05 DPDT RELAY SOCKET DIN RAIL MTD Schneider Electric
XMR1 1 VER-X150CAA TRANSFORMR CTRL 120V/24V 150VA Schneider Electric
Date: 11/22/2013
11/22/2013
AHU-1E-XP
Device Qty Part Number Description Vendor
----------------------------------------------------------------------------------------------------------------------------------------------------
Panel
xPUI4-1-2 2 xPUI4 XP EXP MODULE - 4 UI Schneider Electric
Buro Happold
Date:
Date:
Giachetti
Default
AMP
Device Qty Part Number Description Vendor
LTL
FS
----------------------------------------------------------------------------------------------------------------------------------------------------
Designed by:
Software by:
Checked by:
Contractor:
CP1 1 UNM-SCH304810RC ENCL 30X48X10 RECS GRY CVR Schneider Electric
Engineer:
Architect:
Columbia University - Graduate
School of Journalism (BIMI)
1/2/2014
Last Printed
Last Saved
NC13N2951
Job Number
File AHU-EF
Submittal Rev
Number
Name
7
1.vsd
OF
Sheet
H-001
7
Columbia University-
Graduate School of Journalism
Brown Institute for Media Innovation
Columbia University
2950 Broadway
New York, NY 10027
Total BOM
Drawing Index:
Page 4
Page 3
Page 2
Page 0
Architect: LTL
2950 Broadway
Contractor: Giachetti
Engineer: Buro Happold
H-002 Variable Air Volume Units
11/25/2013
Controller Designator Gray GRY GY a
1/2/2014
from Controller 4. All thermowells shall be filled with heat conductive compound that is provided.
UI# SaTmp
White WHT WH w
Date:
COM 00_00
5. Wiring Terminations designated as X or XX indicate information was unavailable at time Gold GLD GL d
SUBMITTAL
of submittal. Please inform Schneider Electric before making field terminations. Silver SLV SV s
Pink PNK PK p
6. Remote control devices, not in local panels, shall be accessible for adjustment and
Temperature
Temperature Temperature Temperature Temperature Temperature service - below 7' above fixed floor whenever possible or as shown on the provided
Sensor, Bulb
Sensor, Duct Probe Sensor, Immersion Sensor, Averaging Sensor, Outside Air Sensor, Room Construction prints. 1-Letter abbreviations used for color of stripe on
(Strap-On)
SaTmp HwSTmp MaTmp RmTmp DxSucTmp wire. (WH/o = White wire with orange stripe)
Revised to Resubmit
00_00 00_00 00_00 00_00 00_00 7. Only prints marked Construction are to be used during installation. If the prints are not
OaTmp
Record Drawing
UI# COM UI# COM UI# COM UI# COM UI# COM marked Construction, the installer will correct any discrepancies between prints used and
00_00
RD BK RD BK RD BK
UI# COM
RD BK RD BK
Construction at no cost to Schneider Electric.
# Change:
TS# TS# TS# TS# TS#
Revision:
RD BK
TS# 8. All new BAS controller panels shall have a dedicated 120Vac power source. This source
shall be located and marked in the electrical panel as well as on the control prints returned to
Schneider Electric for Record prints.
1
2
3
4
5
Hydronic Heating Hydronic Cooling 9. Installer responsible for maintaining existing safeties into new BAS control electrically or
Gas Heating Current Sensor Pressure Sensor Pressure Switch pnuematically connected.
Coil Coil
SaFanStat SaStP
Gas 00_00 00_00 10. See Division 23 09 15 00 for any additional information on installation standards.
Date: 11/22/2013
11/22/2013
NO COM UI# COM
Htg + - NC C
LO HI LO HI
NO COM PS1 PS1
CSR1
Wiring Legend
Buro Happold
Date:
Date:
Low Voltage (50 volts or less) control wiring for inputs and outputs shall be 18 AWG or larger rated for 600-volt service. Terminate any
Giachetti
HeatPump or Dual shields or drains for input/outputs at the controller only. See Section 4.2 for additional details.
DX Cooling Electric Heating Smoke Detector Transformer Filter
Pipe Coil
AMP
LTL
1 Stage Indicates need for conduit to be ran by installer. Distances noted on plans are approximate values.
FS
Elect FILTER
D
Designed by:
Software by:
Checked by:
+
_ SD2
Contractor:
Engineer:
X
Architect:
Se
Pri
Htg c
XFR1
Ethernet
Ethernet Wiring: Unless stated differently by the client or the Schneider Electric Site Supervisor, network cable shall meet or exceed all
2950 Broadway
Legend
MS/TP BACnet or I/Net Wiring: Wiring to be installed using 24 AWG 7/26 Bare Copper 2 conductor stranded, 7/32 drain wire, 12.5
MS/TP pF/ft @ 1 KHz nominal UL TYPE CMP/CL3P 24 AWG. Maximum length is 4000' or 110 controllers. End of Line resistor (120 1/4W)
CHILLE
R CHWP01 to be installed at both ends of network segments. All communication cabling to be installed in a daisy chain configuration, no Ts are
Boiler #1
Heat permitted. Shield on communication cable is to remain continuous and grounded only at a controller. Polarity of the wires must be
Exchanger observed. Splicing of communication cable is not permitted. Cable can be purchase through Schneider Electric using this part number:
WBAC-4-242P-OR-SP
LON or FFT-10 Wiring to be installed using Level IV network cable. Level IV network cable is 22 AWG 7/30 Bare Copper, 2 conductor
FTT-10
VFD Motor Starter 3-way Valve 2-way Valve Fan Damper stranded, with or without a 7/32 drain wire, 17 pF/ft, and impedance of 100 ohm (1-20MHz) nominal UL TYPE SUBJECT 444, CMP.
1/2/2014
1/2/2014
Last Printed
Last Saved
The same cable shall be used through out the project to avoid impedance issues. Maximum length is 4600' or 55 controllers without
use of repeater. Terminator to be installed at both ends of network segments. All LON/FFT-10 cabling to be installed in a daisy chain
See Valve Schedule D1 D1
configuration (not FTT-10A). This cable is not to run in the same conduit with power for more than 5'. Splicing of communication
NC13N2951
CV1 CV1 CV1
N.O. N.O. cable is not permitted. Cable can be purchase through Schneider Electric using this part number: WLON-3-221P-BL-BX
Job Number
VFD STARTER
A AB N.O. N.C.
B
Submittal Rev
VAV
Number
File Name
4
1.vsd
L3 L2 L1 L3 L2 L1
OF
H-002
480 VAC 480 VAC
Sheet
1
Floor Plan Legend is independent, please refer to Legend on that Page
Electric. Their use or reproduction without prior consent of
These drawings and designs are the property of Schneider
VAV System Diagram
11/25/2013
1/2/2014
Date:
VAV-M201A
SUBMITTAL
VAV-M201B
VAV
AFS Box
b3865-V Built in Actuator on
Revised to Resubmit
(HIGH) (LOW) VAV Controller
Record Drawing
Air from AHU Supply Air to Room
# Change:
Revision:
AFS
1
2
3
4
5
By Box MFGR RmTmp
b3865-V
IN5 RET PWR
1/4" Tubing
IN RET SPWR
TS1
Date: 11/22/2013
11/22/2013
To VP Sensor on
VAV Box Sequence of Operations VAV Controller
1. BMS Contractor shall furnish all controls to air terminal device manufacturer
for factory installation and adjustment. Coordinate factory mounting and wiring
Buro Happold
Date:
Date:
of controller, actuator, and transformer with the VAV box manufacturer. The
Giachetti
BMS contractor shall be responsible for furnishing, installing, and wiring any
AMP
controls not furnished, installed, or wired by others that are required for an
LTL
FS
operational system.
Designed by:
Software by:
Checked by:
Contractor:
Engineer:
Architect:
2. Provide one local DDC controller for each VAV box.
3. The VAV box should be indexed off when the local Air Handling Unit that the
2950 Broadway
4. The VAV box should be indexed on when the Air Handling Unit that the VAV
box is serving is indexed on in the occupied mode. When the VAV box is
indexed on the damper shall modulate to maintain the set point of the zone
temperature.
5. The VAV box controller shall be set a min set point at 50% design value as per
schedule.
1/2/2014
1/2/2014
Last Printed
Last Saved
6. Thermostat: electronic type with temperature set-point display in Fahrenheit
and Celsius.
NC13N2951
Job Number
Submittal Rev
7. Provide sensor for ventilation air flow measurement and DCV option.
VAV
Number
VAV
File Name
4
1.vsd
Device Qty Part Number Description Manufacturer
----------------------------------------------------------------------------------------------------------------------------------------------------
OF
H-002
8. The VAV box shall annunciate an alarm to the BMS when the air flow is
Sheet
Electrical
2
TS1 8 TTS-SD-LCD-1 SMART SENSOR, LCD DISPLAY, 10K Schneider Electric
greater than 15% above design value or below the minimum airflow set point.
Electric. Their use or reproduction without prior consent of
These drawings and designs are the property of Schneider
VAV Controller I/O Diagram
11/25/2013
AFS:AFS
1/2/2014
IN1
IN2
IN3
IN4
(HIGH) + 18
From: From Previous
On - 17
Date:
1 IN1 Off SHLD 16
VAV Power Supply Panel Layout
SUBMITTAL
2 IN2
3 RET SERVICE
UNIVERSAL PORT
INPUTS
4 IN3 1'-0"
5 IN4
6 RET
Revised to Resubmit
NO T1-3 9 IN5 DIGITAL OUT5 14
OUTPUTS OUT4 13
Record Drawing
24H 10 24VAC OUT3 12
24 VAC
11 GND
From PSH40A40AB10 Panel
24N +
# Change:
Pri Sec
SEE DETAIL#1,2 on page 3
Revision:
XMR1 COM
DAMPER
GND COM 10"
- 4 1/2"
1
2
3
4
5
EN
CL
Date: 11/22/2013
11/22/2013
Buro Happold
Date:
Date:
1 PSH40A40A Transformer Wiring Detail 2 PSH40A40A Transformer Wiring Detail
Giachetti
PSH40A40AB10 Panel 1 PSH40A40AB10 Panel 2
AMP
LTL
(Located on Level 200)
FS
(Located on Level 100)
Designed by:
Software by:
Checked by:
Contractor:
Engineer:
Architect:
Columbia University - Graduate
120VAC 120VAC
(by others) (by others)
1/2/2014
1/2/2014
Last Printed
Last Saved
VAV
NC13N2951
Device Qty Part Number Description Manufacturer
Job Number
----------------------------------------------------------------------------------------------------------------------------------------------------
Electrical
Submittal Rev
ENCL 2 KEL-SC12106 12X10X6 SCREW COVER ENCLOSURE Kele
VAV
Number
XMR2 2 KEL-PSH40A40AB10 POWER SUPPLY Functional Devices [PSH40A40AB10]
File Name
4
1.vsd
XMR1 8 VER-X020ADA Transformer: 20 VA, 24 VAC, 1H Veris Industries
OF
H-002
Sheet
Other
3
b3865-V 8 b3865-V b3865, 4 UI, 1 Airflow, 1 IBS Schneider Electric
TS1
VAV
Other
ENCL
XMR1
XMR2
Device
b3865-V
Electrical
8
b3865-V
Qty Part Number
2 KEL-SC12106
8 VER-X020ADA
8 TTS-SD-LCD-1
2 KEL-PSH40A40AB10
Description
POWER SUPPLY
Total Bill of Materials
Schneider Electric
Schneider Electric
Schneider Electric
Schneider Electric
Total BOM
System Diagram
System Sequence
Drawing Index:
Page 6
Page 0
Architect: LTL
2950 Broadway
Contractor: Giachetti
H-003 Fan Coil Units
11/25/2013
Controller Designator Gray GRY GY a
1/2/2014
from Controller 4. All thermowells shall be filled with heat conductive compound that is provided.
UI# SaTmp
White WHT WH w
Date:
COM 00_00
5. Wiring Terminations designated as X or XX indicate information was unavailable at time Gold GLD GL d
SUBMITTAL
of submittal. Please inform Schneider Electric before making field terminations. Silver SLV SV s
Pink PNK PK p
6. Remote control devices, not in local panels, shall be accessible for adjustment and
Temperature
Temperature Temperature Temperature Temperature Temperature service - below 7' above fixed floor whenever possible or as shown on the provided
Sensor, Bulb
Sensor, Duct Probe Sensor, Immersion Sensor, Averaging Sensor, Outside Air Sensor, Room Construction prints. 1-Letter abbreviations used for color of stripe on
(Strap-On)
SaTmp HwSTmp MaTmp RmTmp DxSucTmp wire. (WH/o = White wire with orange stripe)
Revised to Resubmit
00_00 00_00 00_00 00_00 00_00 7. Only prints marked Construction are to be used during installation. If the prints are not
OaTmp
Record Drawing
UI# COM UI# COM UI# COM UI# COM UI# COM marked Construction, the installer will correct any discrepancies between prints used and
00_00
RD BK RD BK RD BK
UI# COM
RD BK RD BK
Construction at no cost to Schneider Electric.
# Change:
TS# TS# TS# TS# TS#
Revision:
RD BK
TS# 8. All new BAS controller panels shall have a dedicated 120Vac power source. This source
shall be located and marked in the electrical panel as well as on the control prints returned to
Schneider Electric for Record prints.
1
2
3
4
5
Hydronic Heating Hydronic Cooling 9. Installer responsible for maintaining existing safeties into new BAS control electrically or
Gas Heating Current Sensor Pressure Sensor Pressure Switch pnuematically connected.
Coil Coil
SaFanStat SaStP
Gas 00_00 00_00 10. See Division 23 09 15 00 for any additional information on installation standards.
Date: 11/22/2013
11/22/2013
NO COM UI# COM
Htg + - NC C
LO HI LO HI
NO COM PS1 PS1
CSR1
Wiring Legend
Buro Happold
Date:
Date:
Low Voltage (50 volts or less) control wiring for inputs and outputs shall be 18 AWG or larger rated for 600-volt service. Terminate any
Giachetti
HeatPump or Dual shields or drains for input/outputs at the controller only. See Section 4.2 for additional details.
DX Cooling Electric Heating Smoke Detector Transformer Filter
Pipe Coil
AMP
LTL
1 Stage Indicates need for conduit to be ran by installer. Distances noted on plans are approximate values.
FS
Elect FILTER
D
Designed by:
Software by:
Checked by:
+
_ SD2
Contractor:
Engineer:
X
Architect:
Se
Pri
Htg c
XFR1
Ethernet
Ethernet Wiring: Unless stated differently by the client or the Schneider Electric Site Supervisor, network cable shall meet or exceed all
2950 Broadway
Legend
MS/TP BACnet or I/Net Wiring: Wiring to be installed using 24 AWG 7/26 Bare Copper 2 conductor stranded, 7/32 drain wire, 12.5
MS/TP pF/ft @ 1 KHz nominal UL TYPE CMP/CL3P 24 AWG. Maximum length is 4000' or 110 controllers. End of Line resistor (120 1/4W)
CHILLE
R CHWP01 to be installed at both ends of network segments. All communication cabling to be installed in a daisy chain configuration, no Ts are
Boiler #1
Heat permitted. Shield on communication cable is to remain continuous and grounded only at a controller. Polarity of the wires must be
Exchanger observed. Splicing of communication cable is not permitted. Cable can be purchase through Schneider Electric using this part number:
WBAC-4-242P-OR-SP
LON or FFT-10 Wiring to be installed using Level IV network cable. Level IV network cable is 22 AWG 7/30 Bare Copper, 2 conductor
FTT-10
VFD Motor Starter 3-way Valve 2-way Valve Fan Damper stranded, with or without a 7/32 drain wire, 17 pF/ft, and impedance of 100 ohm (1-20MHz) nominal UL TYPE SUBJECT 444, CMP.
1/2/2014
1/2/2014
Last Printed
Last Saved
The same cable shall be used through out the project to avoid impedance issues. Maximum length is 4600' or 55 controllers without
use of repeater. Terminator to be installed at both ends of network segments. All LON/FFT-10 cabling to be installed in a daisy chain
See Valve Schedule D1 D1
configuration (not FTT-10A). This cable is not to run in the same conduit with power for more than 5'. Splicing of communication
NC13N2951
CV1 CV1 CV1
N.O. N.O. cable is not permitted. Cable can be purchase through Schneider Electric using this part number: WLON-3-221P-BL-BX
Job Number
VFD STARTER
A AB N.O. N.C.
B
Submittal Rev
FCU
Number
File Name
5
1.vsd
L3 L2 L1 L3 L2 L1
OF
H-003
480 VAC 480 VAC
Sheet
1
Floor Plan Legend is independent, please refer to Legend on that Page
Electric. Their use or reproduction without prior consent of
Sequence of Operation
1. BMS Contractor shall furnish, install and wire DDC controls and connection to
11/25/2013
1/2/2014
the BMS.
Date:
SUBMITTAL
2. A space temperature sensor shall control the FCUs heating valve, cooling
valve, and fan shall cycle on.
NOTE: According to the mechanical schedule, FCU-IT only has a cooling valve.
3. Furnish a leak detector in the drip pan under the FCU. Upon detection of water
Revised to Resubmit
the FCU shall shut down and an alarm shall be annunciated to the BMS.
Record Drawing
# Change:
4. If the supply fan fails to operate an alarm shall be annunciated at the BMS and
Revision:
dampers shall be indexed to their normal off positions.
1
2
3
4
5
Date: 11/22/2013
11/22/2013
Fan Coil Unit (FCU-N/S/E)
Buro Happold
Date:
Date:
1. BMS Contractor shall furnish, install and wire DDC controls and connection to
Giachetti
the BMS and local DDC controller.
AMP
LTL
FS
2. During occupied period, wall mounted FCU temperature sensors shall control
Designed by:
Software by:
Checked by:
the FCUs heating valve, or cooling valve, and fan shall remain on to maintain
Contractor:
Engineer:
Architect:
the setpoint.
Design room temperature: 70 deg F: winter & 75 deg F: summer adjustable
System Sequence
control the FCUs heating valve, or cooling valve, and fan shall cycle on to
2950 Broadway
maintain the setpoint.
Design room temperature: 60 deg F: winter & 80 deg F: summer adjustable
5. Furnish a leak detector in the drip pan under the FCU. Upon detection of water
the FCU shall shut down and an alarm shall be annunciated to the BMS.
1/2/2014
1/2/2014
Last Printed
Last Saved
6. If the supply fan fails to operate an alarm shall be annunciated at the BMS and
dampers shall be indexed to their normal off positions.
NC13N2951
Job Number
Submittal Rev
FCU
Number
File Name
5
1.vsd
OF
H-003
Sheet
2
FAN COIL UNIT (COOLING ONLY) FLOW DIAGRAM
11/25/2013
1/2/2014
RA SA
Date:
SUBMITTAL
CHWRCtrlVlv BI1 FanSts
CSR1
SE7300-1 SCOM SE7300-1
AO1 BO5
BO5 FanSS
STARTER R1
BO5 SE7300-1 SE7300F5045B
See Valve Schedule CtrlVlv SpTemp
L3 L2 L1 SE7300-1
CHWR 120 VAC
A AB + -
Revised to Resubmit
(NC)
Record Drawing
CHWS
+ -
LD TS1
SE7300-1
# Change:
Revision:
BI2 SCOM PWR
24N 1
24H XFMR
NO COM PWR
1
2
3
4
5
Leak
Drip Pan
Condensate
Pump
Condensate Out
Date: 11/22/2013
11/22/2013
Wiring to b3920 shown on AHU-1E Submittal page 4
Buro Happold
Date:
Date:
(3) FCU-E
Giachetti
(4) FCU-N
AMP
LTL
FS
(5) FCU-S
Designed by:
Software by:
Checked by:
Contractor:
Engineer:
Architect:
Columbia University - Graduate
RA SA
System Diagram
HWRCtrlVlv CHWRCtrlVlv BI1 FanSts + -
2950 Broadway
CSR1
SE7300-2 SE7300-2 SCOM SE7300-2
AO2 BO5 AO1 BO5
BO5 FanSS + -
STARTER R1
BO5 SE7300-2 TS1
See Valve Schedule CtrlVlv See Valve Schedule CtrlVlv
L3 L2 L1
HWR CHWR 120 VAC
A AB A AB
(NO) (NC)
HWS CHWS
1/2/2014
1/2/2014
Last Printed
Last Saved
SE7300-2 Device Qty Part Number Description Manufacturer
BI2 SCOM ----------------------------------------------------------------------------------------------------------------------------------------------------
24N 1 Electrical
24H XFMR CSR1 1 VER-H600 CURRENT SWITCH N.O. SPLIT CORE Veris Industries
NC13N2951
NO COM PWR Leak 1 LT-410 SPOT LEAK DETECTOR Kele
Job Number
Leak
Submittal Rev
Drip Pan FCU (Heating & Cooling)
FCU
Number
Device Qty Part Number Description Manufacturer
File Name
5
1.vsd
----------------------------------------------------------------------------------------------------------------------------------------------------
Electrical
OF
H-003
Sheet
CSR1 12 VER-H600 CURRENT SWITCH N.O. SPLIT CORE Veris Industries
3
Leak 12 LT-410 SPOT LEAK DETECTOR Kele
FCU CONTROLLER
11/25/2013
1/2/2014
Date:
SUBMITTAL
1 X2
XFR X1
X2 10-30 VAC/DC
Start/Stop:FanSS
WHT/YEL R1 WHT/BLU X1
Revised to Resubmit
WHT/BLK
Record Drawing
120 VAC
1 2 3 4 5 6 7 8 ORG YEL
To Starter
24V+
MFS
24V-
# Change:
BO5
BO5
HFS
LFS
Terminal blocks
Revision:
R1-1
Schneider
1
2
3
4
5
Electric
SE7300F5045B
BACNET FAN COIL CONTROLLER
SE7300-1
SE7300F5045B
+
From: Previous Device
Date: 11/22/2013
11/22/2013
-
REF
To: Next Device
SCOM
AO2
AO1
UI3
BI1
BI2
RS
9 10 11 12 13 14 15 16
X2
Buro Happold
Date:
Date:
1 B
Chilled Water
2 R X1
Giachetti
Control Valve
3 W CtrlVlv:CHWRCtrlVlv NO
Leak:LD
COM
AMP
CSR1:FanSts
LTL
24(+)
FS
NO 24(-)
COM
Designed by:
X1 X2
Software by:
Checked by:
Contractor:
Engineer:
Architect:
Columbia University - Graduate
1/2/2014
Last Printed
Transformer Details
Last Saved
24VAC
X1
24vac
NC13N2951
Panel # ___ COM
X2
Job Number
CB # ___ Pri
XMR2
Sec
Submittal Rev
Device Qty Part Number Description Manufacturer
FCU
Number
----------------------------------------------------------------------------------------------------------------------------------------------------
File Name
5
1.vsd
GND Electrical
120vac R1 1 VER-V100 RELAY ENC SPDT 10-30AC/DC, 120 Veris Industries [V100]
OF
120 N
H-003
(From FCU)
Sheet
120 H SE7300-1 1 SE7300F5045B BACNET FAN COIL CONTROLLER Schneider Electric [SE7300F5045B]
4
XMR2 1 VER-X050CEB TRANSFRMR CTRL MULTI/120V 50VA Veris Industries [X050CEB]
Electric. Their use or reproduction without prior consent of
FCU CONTROLLER
11/25/2013
1/2/2014
Date:
SUBMITTAL
1 X2
XFR X1
X2 10-30 VAC/DC
Start/Stop:FanSS
WHT/YEL R1 WHT/BLU X1
WHT/BLK
120 VAC
Revised to Resubmit
1 2 3 4 5 6 7 8 ORG YEL To Starter
Terminal blocks
Record Drawing
24V+
MFS
24V-
BO5
BO5
HFS
LFS
R1-1
# Change:
Revision:
Schneider
Electric
SE7300F5045B
1
2
3
4
5
BACNET FAN COIL CONTROLLER
SE7300-2
SE7300F5045B
+
From: Previous Device
-
REF
To: Next Device
Date: 11/22/2013
11/22/2013
SCOM
AO2
AO1
UI3
BI1
BI2
RS
9 10 11 12 13 14 15 16
X2
1 B
Hot Water
Control Valve 2 R X1
3 W
Buro Happold
CtrlVlv:HWRCtrlVlv
Date:
Date:
CtrlVlv:CHWRCtrlVlv NO
Leak:LD
X2 COM
1 B CSR1:FanSts
Giachetti
Chilled Water 24(+)
Control Valve
2 R X1 24(-)
3 W
AMP
LTL
X1 X2
FS
NO
Designed by:
COM
Software by:
Checked by:
Contractor:
Engineer:
Architect:
1/2/2014
Last Printed
Last Saved
Transformer Details
24VAC
X1
24vac
NC13N2951
Panel # ___ COM
X2
Job Number
CB # ___ Pri
XMR2
Sec
FCU (Heating & Cooling)
Submittal Rev
Device Qty Part Number Description Manufacturer
FCU
Number
----------------------------------------------------------------------------------------------------------------------------------------------------
File Name
5
1.vsd
GND Electrical
120vac R1 12 VER-V100 RELAY ENC SPDT 10-30AC/DC, 120 Veris Industries [V100]
OF
H-003
120 N
(From FCU)
Sheet
SE7300-2 12 SE7300F5045B BACNET FAN COIL CONTROLLER Schneider Electric [SE7300F5045B]
120 H
5
XMR2 12 VER-X050CEB TRANSFRMR CTRL MULTI/120V 50VA Veris Industries [X050CEB]
Electric. Their use or reproduction without prior consent of
Total Bill of Materials
Revised to Resubmit
Record Drawing
# Change:
Revision:
1
2
3
4
5
FCU (Cooling Only)
Device Qty Part Number Description Vendor
----------------------------------------------------------------------------------------------------------------------------------------------------
Electrical
CSR1 1 VER-H600 CURRENT SWITCH N.O. SPLIT CORE Schneider Electric
Leak 1 LT-410 SPOT LEAK DETECTOR Schneider Electric
R1 1 VER-V100 RELAY ENC SPDT 10-30AC/DC, 120 Schneider Electric
Date: 11/22/2013
11/22/2013
SE7300-1 1 SE7300F5045B BACNET FAN COIL CONTROLLER Schneider Electric
XMR2 1 VER-X050CEB TRANSFRMR CTRL MULTI/120V 50VA Schneider Electric
Buro Happold
Date:
Date:
Electrical
CSR1 12 VER-H600 CURRENT SWITCH N.O. SPLIT CORE Schneider Electric
Leak 12 LT-410 SPOT LEAK DETECTOR Schneider Electric
Giachetti
R1 12 VER-V100 RELAY ENC SPDT 10-30AC/DC, 120 Schneider Electric
SE7300-2 12 SE7300F5045B BACNET FAN COIL CONTROLLER Schneider Electric
AMP
XMR2 12 VER-X050CEB TRANSFRMR CTRL MULTI/120V 50VA Schneider Electric
LTL
FS Designed by:
Software by:
Checked by:
Contractor:
Engineer:
Architect:
Columbia University - Graduate
School of Journalism (BIMI)
Total BOM
1/2/2014
1/2/2014
Last Printed
Last Saved
NC13N2951
Job Number
Submittal Rev
FCU
Number
File Name
5
1.vsd
OF
H-003
Sheet
6
Columbia University-
Graduate School of Journalism
Brown Institute for Media Innovation
Columbia University
2950 Broadway
New York, NY 10027
System Diagram
Drawing Index:
Page 2
Page 1
Page 0
Architect: LTL
2950 Broadway
Contractor: Giachetti
Engineer: Buro Happold
H-004 Hot Water Unit Heater
11/25/2013
Controller Designator Gray GRY GY a
1/2/2014
from Controller 4. All thermowells shall be filled with heat conductive compound that is provided.
UI# SaTmp
White WHT WH w
Date:
COM 00_00
5. Wiring Terminations designated as X or XX indicate information was unavailable at time Gold GLD GL d
SUBMITTAL
of submittal. Please inform Schneider Electric before making field terminations. Silver SLV SV s
Pink PNK PK p
6. Remote control devices, not in local panels, shall be accessible for adjustment and
Temperature
Temperature Temperature Temperature Temperature Temperature service - below 7' above fixed floor whenever possible or as shown on the provided
Sensor, Bulb
Sensor, Duct Probe Sensor, Immersion Sensor, Averaging Sensor, Outside Air Sensor, Room Construction prints. 1-Letter abbreviations used for color of stripe on
(Strap-On)
SaTmp HwSTmp MaTmp RmTmp DxSucTmp wire. (WH/o = White wire with orange stripe)
Revised to Resubmit
00_00 00_00 00_00 00_00 00_00 7. Only prints marked Construction are to be used during installation. If the prints are not
OaTmp
Record Drawing
UI# COM UI# COM UI# COM UI# COM UI# COM marked Construction, the installer will correct any discrepancies between prints used and
00_00
RD BK RD BK RD BK
UI# COM
RD BK RD BK
Construction at no cost to Schneider Electric.
# Change:
TS# TS# TS# TS# TS#
Revision:
RD BK
TS# 8. All new BAS controller panels shall have a dedicated 120Vac power source. This source
shall be located and marked in the electrical panel as well as on the control prints returned to
Schneider Electric for Record prints.
1
2
3
4
5
Hydronic Heating Hydronic Cooling 9. Installer responsible for maintaining existing safeties into new BAS control electrically or
Gas Heating Current Sensor Pressure Sensor Pressure Switch pnuematically connected.
Coil Coil
SaFanStat SaStP
Gas 00_00 00_00 10. See Division 23 09 15 00 for any additional information on installation standards.
Date: 11/22/2013
11/22/2013
NO COM UI# COM
Htg + - NC C
LO HI LO HI
NO COM PS1 PS1
CSR1
Wiring Legend
Buro Happold
Date:
Date:
Low Voltage (50 volts or less) control wiring for inputs and outputs shall be 18 AWG or larger rated for 600-volt service. Terminate any
Giachetti
HeatPump or Dual shields or drains for input/outputs at the controller only. See Section 4.2 for additional details.
DX Cooling Electric Heating Smoke Detector Transformer Filter
Pipe Coil
AMP
LTL
1 Stage Indicates need for conduit to be ran by installer. Distances noted on plans are approximate values.
FS
Elect FILTER
D
Designed by:
Software by:
Checked by:
+
_ SD2
Contractor:
Engineer:
X
Architect:
Se
Pri
Htg c
XFR1
Ethernet
Ethernet Wiring: Unless stated differently by the client or the Schneider Electric Site Supervisor, network cable shall meet or exceed all
2950 Broadway
Legend
MS/TP BACnet or I/Net Wiring: Wiring to be installed using 24 AWG 7/26 Bare Copper 2 conductor stranded, 7/32 drain wire, 12.5
MS/TP pF/ft @ 1 KHz nominal UL TYPE CMP/CL3P 24 AWG. Maximum length is 4000' or 110 controllers. End of Line resistor (120 1/4W)
CHILLE
R CHWP01 to be installed at both ends of network segments. All communication cabling to be installed in a daisy chain configuration, no Ts are
Boiler #1
Heat permitted. Shield on communication cable is to remain continuous and grounded only at a controller. Polarity of the wires must be
Exchanger observed. Splicing of communication cable is not permitted. Cable can be purchase through Schneider Electric using this part number:
WBAC-4-242P-OR-SP
LON or FFT-10 Wiring to be installed using Level IV network cable. Level IV network cable is 22 AWG 7/30 Bare Copper, 2 conductor
FTT-10
VFD Motor Starter 3-way Valve 2-way Valve Fan Damper stranded, with or without a 7/32 drain wire, 17 pF/ft, and impedance of 100 ohm (1-20MHz) nominal UL TYPE SUBJECT 444, CMP.
1/2/2014
1/2/2014
Last Printed
Last Saved
The same cable shall be used through out the project to avoid impedance issues. Maximum length is 4600' or 55 controllers without
use of repeater. Terminator to be installed at both ends of network segments. All LON/FFT-10 cabling to be installed in a daisy chain
See Valve Schedule D1 D1
configuration (not FTT-10A). This cable is not to run in the same conduit with power for more than 5'. Splicing of communication
NC13N2951
CV1 CV1 CV1
N.O. N.O. cable is not permitted. Cable can be purchase through Schneider Electric using this part number: WLON-3-221P-BL-BX
Job Number
VFD STARTER
A AB N.O. N.C.
B
Submittal Rev
EUH
Number
File Name
2
1.vsd
L3 L2 L1 L3 L2 L1
OF
H-004
480 VAC 480 VAC
Sheet
1
Floor Plan Legend is independent, please refer to Legend on that Page
Electric. Their use or reproduction without prior consent of
These drawings and designs are the property of Schneider
UNIT HEATER FLOW DIAGRAM
11/25/2013
1/2/2014
RA SA
Date:
SUBMITTAL
IN7 FanSts
CSR1
RET AHU-1E
NO1 FanSS
STARTER R1
COM1 AHU-1E
HWS
L3 L2 L1
120 VAC
Revised to Resubmit
HWRCtrlVlv
AHU-1E
Record Drawing
V9 GND TTS-S-1
SpTemp
AHU-1E
# Change:
IN6 RET
Revision:
See Valve Schedule CtrlVlv
HWR
A AB
(NO) + -
1
2
3
4
5
SpTemp
Sequence Of Operations
Date: 11/22/2013
11/22/2013
Hot Water Unit Heater
Buro Happold
Date:
Date:
1. BMS Contractor shall furnish, install and wire DDC controls and connection to
the BMS.
Giachetti
AMP
LTL
FS
2. A space temperature sensor shall control the heating valve and fan shall cycle
on.
Designed by:
Software by:
Checked by:
Contractor:
Engineer:
Architect:
3. If the supply fan fails to operate an alarm shall be annunciated at the BMS.
System Diagram
2950 Broadway
NOTE: See AHU Submittal page 4 for actual AHU-1E Controller Wiring Diagram
UH Wiring Detail
NO1
FanSS COM1 X2
NO1 13 R1 14 X1
5 9 T2-1 To Starter
R1-1 T2-2
+ T1-7 RET Terminal blocks
SpTemp
- T1-8 IN7
1/2/2014
1/2/2014
Last Printed
Last Saved
IN8
NO T1-7 FanSts AHU-1E
COM T1-8
CONTROLLER Unit Heaters
NC13N2951
Device Qty Part Number Description Manufacturer
Job Number
----------------------------------------------------------------------------------------------------------------------------------------------------
Electrical
Submittal Rev
CSR1 1 VER-H600 CURRENT SWITCH N.O. SPLIT CORE Veris Industries
EUH
Number
SpTemp 1 TTS-S-1 TEMP SENSOR 4" ROOM 10K T3 Schneider Electric [TTS-S-1]
File Name
2
Com
1.vsd
COM5 T2-9 Hot Water Valve
HWRCtrlVlv NO5 Panel
OF
T2-10
H-004
X2 X1 Hot
Sheet
R1 1 KEL-RH1B-ULAC24V SPDT RELAY W/ LIGHT 24VAC IDEC [RH1B-ULAC24V]
2
R1_1 1 KEL-SH1B-05 SPDT RELAY SOCKET DIN RAIL MTD IDEC [SH1B-05]
Columbia University-
Graduate School of Journalism
Brown Institute for Media Innovation
Columbia University
2950 Broadway
New York, NY 10027
FSD Riser
System Sequence
Drawing Index:
Page 3
Page 2
Page 1
Page 0
Architect: LTL
2950 Broadway
Contractor: Giachetti
Engineer: Buro Happold
H-005 Fire/Smoke Dampers
11/25/2013
Controller Designator Gray GRY GY a
1/2/2014
from Controller 4. All thermowells shall be filled with heat conductive compound that is provided.
UI# SaTmp
White WHT WH w
Date:
COM 00_00
5. Wiring Terminations designated as X or XX indicate information was unavailable at time Gold GLD GL d
SUBMITTAL
of submittal. Please inform Schneider Electric before making field terminations. Silver SLV SV s
Pink PNK PK p
6. Remote control devices, not in local panels, shall be accessible for adjustment and
Temperature
Temperature Temperature Temperature Temperature Temperature service - below 7' above fixed floor whenever possible or as shown on the provided
Sensor, Bulb
Sensor, Duct Probe Sensor, Immersion Sensor, Averaging Sensor, Outside Air Sensor, Room Construction prints. 1-Letter abbreviations used for color of stripe on
(Strap-On)
SaTmp HwSTmp MaTmp RmTmp DxSucTmp wire. (WH/o = White wire with orange stripe)
Revised to Resubmit
00_00 00_00 00_00 00_00 00_00 7. Only prints marked Construction are to be used during installation. If the prints are not
OaTmp
Record Drawing
UI# COM UI# COM UI# COM UI# COM UI# COM marked Construction, the installer will correct any discrepancies between prints used and
00_00
RD BK RD BK RD BK
UI# COM
RD BK RD BK
Construction at no cost to Schneider Electric.
# Change:
TS# TS# TS# TS# TS#
Revision:
RD BK
TS# 8. All new BAS controller panels shall have a dedicated 120Vac power source. This source
shall be located and marked in the electrical panel as well as on the control prints returned to
Schneider Electric for Record prints.
1
2
3
4
5
Hydronic Heating Hydronic Cooling 9. Installer responsible for maintaining existing safeties into new BAS control electrically or
Gas Heating Current Sensor Pressure Sensor Pressure Switch pnuematically connected.
Coil Coil
SaFanStat SaStP
Gas 00_00 00_00 10. See Division 23 09 15 00 for any additional information on installation standards.
Date: 11/22/2013
11/22/2013
NO COM UI# COM
Htg + - NC C
LO HI LO HI
NO COM PS1 PS1
CSR1
Wiring Legend
Buro Happold
Date:
Date:
Low Voltage (50 volts or less) control wiring for inputs and outputs shall be 18 AWG or larger rated for 600-volt service. Terminate any
Giachetti
HeatPump or Dual shields or drains for input/outputs at the controller only. See Section 4.2 for additional details.
DX Cooling Electric Heating Smoke Detector Transformer Filter
Pipe Coil
AMP
LTL
1 Stage Indicates need for conduit to be ran by installer. Distances noted on plans are approximate values.
FS
Elect FILTER
D
Designed by:
Software by:
Checked by:
+
_ SD2
Contractor:
Engineer:
X
Architect:
Se
Pri
Htg c
XFR1
Ethernet
Ethernet Wiring: Unless stated differently by the client or the Schneider Electric Site Supervisor, network cable shall meet or exceed all
2950 Broadway
Legend
MS/TP BACnet or I/Net Wiring: Wiring to be installed using 24 AWG 7/26 Bare Copper 2 conductor stranded, 7/32 drain wire, 12.5
MS/TP pF/ft @ 1 KHz nominal UL TYPE CMP/CL3P 24 AWG. Maximum length is 4000' or 110 controllers. End of Line resistor (120 1/4W)
CHILLE
R CHWP01 to be installed at both ends of network segments. All communication cabling to be installed in a daisy chain configuration, no Ts are
Boiler #1
Heat permitted. Shield on communication cable is to remain continuous and grounded only at a controller. Polarity of the wires must be
Exchanger observed. Splicing of communication cable is not permitted. Cable can be purchase through Schneider Electric using this part number:
WBAC-4-242P-OR-SP
LON or FFT-10 Wiring to be installed using Level IV network cable. Level IV network cable is 22 AWG 7/30 Bare Copper, 2 conductor
FTT-10
VFD Motor Starter 3-way Valve 2-way Valve Fan Damper stranded, with or without a 7/32 drain wire, 17 pF/ft, and impedance of 100 ohm (1-20MHz) nominal UL TYPE SUBJECT 444, CMP.
1/2/2014
1/2/2014
Last Printed
Last Saved
The same cable shall be used through out the project to avoid impedance issues. Maximum length is 4600' or 55 controllers without
use of repeater. Terminator to be installed at both ends of network segments. All LON/FFT-10 cabling to be installed in a daisy chain
See Valve Schedule D1 D1
configuration (not FTT-10A). This cable is not to run in the same conduit with power for more than 5'. Splicing of communication
NC13N2951
CV1 CV1 CV1
N.O. N.O. cable is not permitted. Cable can be purchase through Schneider Electric using this part number: WLON-3-221P-BL-BX
Job Number
VFD STARTER
A AB N.O. N.C.
B
Submittal Rev
FSD
Number
File Name
5
1.vsd
L3 L2 L1 L3 L2 L1
OF
H-006
480 VAC 480 VAC
Sheet
1
Floor Plan Legend is independent, please refer to Legend on that Page
Electric. Their use or reproduction without prior consent of
Sequence of Operation
11/25/2013
3. Low temperature detector (freeze stat), mounted upstream of the
1/2/2014
maintain 45F plenum temperatures.
cooling/heating coils, shall stop the fans when the cooling coil entering
Date:
15. Monitor differential pressures across filter and annunciate alarm when
SUBMITTAL
temperature falls below 35F (adj.), for 3 minutes (adj. 0-15 minutes at time
differentia pressure set point is exceeded.
delay relay in control panel). Chilled water valve shall close, heating valve shall
16. If the supply fan fails to operate an alarm shall be annunciated at the BMS and
open. Freeze stats shall automatically reset when temperature rises above trip
dampers shall be indexed to their normal off positions.
set point. If 3 (adj.) freeze stat shutdowns occur within 15 minutes (adj.), unit
17. The Fire Alarm System shall signal the BMS when a fire alarm is present.
shall be commended off until reset from BMS computer.
When the floor/area the fans serves is in alarm, the FAS shall shut down the
Revised to Resubmit
4. For fans greater than 2,000 cfm, provide a high discharge static pressure
fans and close all dampers. Upon fire alarm reset all fans shall sequentially start
Record Drawing
switch if dampers are located upstream of the fan and/or a low static pressure
and operate in the normal mode.
switch if dampers are located downstream of the fan to prevent mechanical
# Change:
Revision:
18. Demand Ventilation controls (DCV):
damage if a damper fails to open. The switch shall stop the fan when duct
Upon a rise in zone CO2 concentration above set-point, the minimum occupied
pressure exceeds design. The fan shall remain off until the pressure switch is
1
2
3
4
5
airflow set-point at the zone VAV terminal shall first be reset from the design
reset.
minimum up to a ventilation override maximum value, 700 ppm (adj).
5. The AHU shall be started by the BMS based upon a start time optimization
program, time of day schedule, or manual command. Upon a command to start, Upon continued call for ventilation (based on continued rise in critical zone CO2
all associated dampers shall open and prove open through damper mounted concentration with VAV terminal at ventilation override maximum setpoint,
Date: 11/22/2013
11/22/2013
limit switch then the supply and return fans shall start. The outdoor air damper then increase the AHU minimum outdoor air rate (damper position) to design
and exhaust air damper shall be closed. minimum.
6. The AHU supply fan shall start and slowly ramp up to speed control set point.
The supply fan variable speed drive shall be controlled to maintain the supply
Buro Happold
Date:
Date:
static pressure set point, as sensed at a point 2/3 downstream of the supply fan. Propeller Exhaust Fan (EF-1)
Giachetti
7. The set point temperature noted in the schedule sheet for unit operation. The 1. As the space pressure sensor increases above the set point of 0.1 / WG ( Adj)
AMP
discharge set point (adjustable) for the air handling unit is presently set at
LTL
compare to outdoor pressure, the exhaust fan shall turn on.
FS Designed by:
Software by:
Checked by:
Contractor:
54.1 F DB / 53.9 F WB
Engineer:
Architect:
8. Morning Warm-up: The system shall be indexed to morning warm-up mode if Condensate pump
the return air temperature is below 60F (adj.) during start-up. The heating coil 1. BMS Contractor shall furnish, install and wire DDC controls and connection to
System Sequence
level inside tank.
2950 Broadway
9. Morning Cool-down: The system shall be indexed to morning cool-down mode
if the return air temperature is above (80F adj.) during start-up. The cooling 3. If the pump fails to operate an alarm shall be annunciated at the BMS. AHU-1E
coil valve shall be controlled to maintain discharge air set point 54F (adj.). and FCU-IT served by the condensate pump shall be shut down.
Then it shall be indexed to the occupied mode.
10. Occupied Mode: The supply fan shall run continuously. The interlinked outdoor
air damper, the return and exhaust air dampers shall move to the fixed positions.
11. Unoccupied Heating: During unoccupied periods if the space temperature falls
below the unoccupied setback set point (60F adj.) the AHU shall cycle on and
the heating coil valve shall be controlled to maintain the space temperature at
1/2/2014
1/2/2014
Last Printed
Last Saved
setpoint .
12. Unoccupied Cooling: During unoccupied periods if the space temperature rises
NC13N2951
above the unoccupied setup set point (80F adj.) the AHU shall cycle on and the
Job Number
cooling coil valve shall be controlled to maintain the space temperature at 80F
Submittal Rev
FSD
Number
(adj).
File Name
5
1.vsd
OF
H-006
Sheet
2
Level 100
Level 200
Network
Tie to BMS
FSD-100-1
BACNet
FSD-100-2
BACNet
FSD-100-3
FSD Riser
BACNet
FSD-200-1
BACNet
FSD-100-4
BACNet
FSD-200-2
BACNet
FSD-100-5
BACNet
FSD-200-3
BACNet
FSD-100-6
VALVE PRESSURE DROP (PSI) TO BE USED IN H2O CALCULATIONS: 5.0 STEAM INLET PRESSURE (PSIG) TO BE USED IN STEAM APPLICATIONS: 5.0
Page 1 of 2
Columbia University
Graduate School of Journalism
Brown Institute for Media Innovation
Columbia University
2950 Broadway
New York, NY 10027
Description
Static Pressure Sensors
The A-300-K Series sensors are used with pressure transmitters and
pressure switches to sense duct pressures. Two sensors are required
to monitor pressure across coils, filters, blowers, etc. A-301-K and
A-302-K have four radial sensing holes and 4" (10.2 cm) insertion
depth. The A-308-K should be used only where accuracy is not
critical. All mount in a 3/8" hole in the duct. If the interior of the duct is
not accessible, an optional A-345-K flange mounting kit may be used. 60681
Room Static Pressure or Total Pressure Sensor Kit RPS-W
The versatile Model 60681 Pressure Sensing Kit is used for
monitoring static pressure (aspiration) or total pressure (impact).
The kit includes a 7" (17.8 cm) universal sensing probe, adjustable
mounting flange, 1/4" adapter, and 3' (0.9 m) length of tubing (1/4" ID
x 3/8" OD). For total (impact) pressure applications, install the curved
tip opening facing into the air stream or away from the air stream for
vacuum applications.
RPS & SD-01
Total Pressure Sensor
The Model 21122 (4") and 21123 (8") sensors are used primarily for A-300 Series
proving air flow in ducts. The opening in the tip of the 4" (10.2 cm)
aluminum tube faces upstream and senses impact (total) pressure. APPLICATION
The "-112" models accept 1/8" to 1/4" ID flexible tubing.
PRESSURE
sensors have a 100 micron stainless steel breather vent.
Filter Kit 4 5
The Model A-605 Filter Kit includes an aluminum surface mounting
bracket and screws, two 5 ft lengths of 1/4" aluminum tubing, two
static pressure tips, and two plastic vent valves.
Surge Dampener
Surge Dampener Model SD-01 absorbs rapid pressure fluctuations
to provide steady pressure outputs. The dampener has two
independent channels - one for the low pressure tubing and one for 4. Negative pressure increases as the filter gets dirty.
the high pressure tubing. Surge dampeners are typically used with 5. Fan operation and true air flow: varying amounts of
outdoor pressure sensors, which are subject to wind gusts, and static pressure. Probes must be perpendicular to air flow.
isolation rooms, clean rooms, or operating rooms where opening or
closing doors creates sudden pressure changes.
ORDERING INFORMATION
19
MODEL DESCRIPTION
60681 Static or total pressure sensing kit
A-301-K Duct static pressure tip, 1/4" compression
A-302-K Duct static pressure tip, 1/4" barb
A-308-K Duct static pressure fitting, 1/4" barb
A-345-K Flange mounting kit (1 required for each A-301-K or A-302-K)
A-3145K A-301-K duct static pressure tip, 1/4" compression with A-345-K mounting flange
A-3245K A-302-K duct static pressure tip, 1/4" barb with A-345-K mounting flange
A-3845K A-308-K duct static pressure fitting, 1/4" barb with A-345-K mounting flange
21122 4" aluminum impact tube, 1/4" OD connection
21122-112 6" aluminum impact tube for 1/8" thru 1/4" ID flexible plastic tubing
21123 8" aluminum impact tube, 1/4" OD connection
21123-112 8" aluminum impact tube for 1/8" thru 1/4" ID flexible plastic tubing
A-306-K Outdoor air static pressure kit
A-605 Mounting kit for air filter application. Includes aluminum surface mounting brackets with screws, two 5 ft. lengths of 1/4"
aluminum tubing, two static pressure tips and two plastic vent valves.
RPS Stainless steel room pressure sensor, 1/4" barb
RPS-I Ivory plastic room pressure sensor, 1/4" barb
RPS-W White plastic room pressure sensor, 1/4" barb
SD-01 Surge dampener
B-137 1/4" barb adapter for #21122 and #21123 (standard pack-50)
January 2012 2012 Kele, Inc. All rights reserved. The Kele name and logo are registered trademarks of Kele, Inc. kele.com 888-397-5353 USA 001-901-382-6084 International
925
Controls Group 507 E. Michigan Street
P.O. Box 423, Milwaukee, WI 53202
Code No. LIT-1927140
a70s p;w 1927140 9thcc:7-25 Refrigeration Temperature Controls Rev:
07/18/97
A70 Series logo:
JCI
left ft:
refrig
Applications
M2 Typical applications include energizing an
indicator light after a low temperature cutout
M1
on a ventilating system.
A70GA-1
To Order
Description
Specify the code number from the following
The A70 Series temperature control The contacts are designed so that when the selection chart.
incorporates a vapor-charged sensing main contact opens, the auxiliary contact
element. The A70G, A70H, and A70K have a closes.
4-wire, 2-circuit contact block that contains
two isolated sets of contacts.
Selection Chart
Code Switch Action Range Diff F Bulb and Max Bulb Range
Number Main Contacts Auxiliary Contacts F (C) (C) Capillary Temp F (C) Adjuster
15 to 55 20 ft of 1/8 in.
A70GA-1C(a) 5 (2.8) 400 (204.4) Screwdriver slot
(-9.4 to 12.8) O.D. Tubing
3 to 30
35 to 80 (-16.1 to -1.1),
A70GA-2C 3/8 in. x 3 in. 6 ft Cap. 250 (121) Screwdriver slot
(1.7 to 26.7) factory set at 12
Open Low Close Low
(-11.1)
15 to 55 20 ft. of 1/8 in. O.D.
A70HA-1C(a) Manual reset 400 (204.4) Screwdriver slot
(-9.4 to 12.8) Tubing
35 to 80
A70HA-2C Manual reset 3/8 in. x 3 in. 6 ft cap. 250 (121) Screwdriver slot
(1.7 to 26.7)
100 to 170
A70KA-1C Open High Close High Manual reset 3/8 in. x 10 in. 6 ft cap. 240 (116) Screwdriver slot
(37.8 to 76.7)
(a) The low cutout stop is set and sealed at 35F (1.6C). The control responds only to the lowest temperature along any one ft. of the entire 20 ft. element or bellows
cup.
Electrical Ratings
Pole Number LINE-M2 (Main) LINE-M1 (Auxiliary)
Motor Ratings VAC 120 208 240 277 (a) (a) 120 208 240 277
480 600
AC Full Load Amp 16.0 9.2 8.0 5.0 4.8 6.0 3.4 3.0
AC Locked Rotor Amp 96.0 55.2 48.0 30.0 28.8 36.0 20.4 18.0
AC Non-Inductive Amp 16.0 9.2 8.0 7.2 6.0 6.0 6.0 6.0
Pilot Duty Both Poles 125 VA, 120 to 600 VAC and 57.5 VA, 120 to 300 VDC
(a) Not compressor motor loads.
The performance specifications are nominal and conform to acceptable industry standards. For applications at conditions beyond these specifications, consult the local Johnson
Controls office. Neither Johnson Controls, Inc. nor its subsidiaries or affiliates shall be liable for damages resulting from misapplication or misuse of its products.
1/1 07/03 Johnson Controls, Inc
NEW!
PRESSURE
PSI
Adjustable Differential Pressure Switches
AFS Series
Description
The AFS Series Adjustable Differential Pressure Switches
are general-purpose, airflow-proving switches designed for
HVAC and building automation applications. The AFS Series
can be used to sense positive, negative, or differential air
pressure. The diaphragm and calibration spring are housed in
a plated enclosure with a removable metal guard protecting
the set point screw and snap action switch terminals.
Electrical connections are made through a 7/8 diameter
opening in the metal guard that accepts a conduit connection.
Air sampling connections accept OD rigid or semi rigid tubing.
The Model AFS-460 features a manual reset button to close
the switch following actuation. For low current applications
use Model AFS-405 with gold contacts.
C US
Features
Adjustable set point
For static or differential pressure Application
15A switch rating Proving fan status
Manual reset (Model AFS-460) Monitoring filter for excess pressure drop FM
Gold contacts (Model AFS-405) Monitoring duct static pressure
C
APPROVED
US
Specifications
PRESSURE
Wiring
NO C A
C Lead
C Opens on a NC
rise in
NC differential
NC
pressure C B
Action on a rise in differential pressure Lag
Opens on a rise in differential pressure
NC
850 001-901-382-6084 International 888-397-5353 USA kele.com 2012 Kele, Inc. All rights reserved. The Kele name and logo are registered trademarks of Kele, Inc. January 2012
NEW!
PRESSURE
Adjustable Differential Pressure Switches PSI
AFS Series
DIMENSIONS
in 2.81
6.13
(15.57)
(cm) (7.14)
Low pressure inlet (B)
3.88 3.25 C NO NC
3.25 (8.23)
(9.86)
(8.23) 0.710
1.38
(3.50) (1.80)
1.63
1.94
(4.14)
(4.93)
OPERATION
Select a mounting location that is free from vibration. The switch Refer to the Dimensions drawing to identify the high pres-
must be mounted with the diaphragm in any vertical plane in sure inlet (A) and the low pressure inlet (B), and connect the
order to obtain the lowest specified operating setpoint. Avoid sample lines as follows:
mounting with the sample line connections in the up position.
Surface mount via the two 3/16" diameter holes in the integral Positive Pressure Only
mounting bracket. Connect the sample line to (A);
(B) remains open to the atmosphere.
The Model AFS-460-DSS has a lead switch (A) and a lag switch Negative Pressure Only
(B). The lead switch trips according to the setpoint knob and the Connect the sample line to (B);
lag switch trips after the lead switch. If dual-switch simultaneous (A) remains open to the atmosphere.
operation is required, order AFS-460-136 (120 VAC power) or Two Negative Samples
AFS-460-137 (24 VAC power). Connect the higher negative sample to (B);
Connect the lower negative sample to (A).
PRESSURE
Locate sampling probe a minimum of 1-1/2 duct diameters Two Positive Samples
downstream from the air source. Install the sampling probe as Connect the higher positive sample to (A);
close to the center of the airstream as possible. Connect the lower positive sample to (B).
One Positive and One Negative Sample
Connect the positive sample to (A);
Connect the negative sample to (B).
ORDERING INFORMATION
MODEL DESCRIPTION
AFS-145 Differential pressure switch 0.05" to 12" W.C. (12.5 to 2989 Pa), 1/8" NPTF
AFS-222 Differential pressure switch 0.05" to 12" W.C. (12.5 to 2989 Pa), 1/4" compression fittings
AFS-222-121 Differential pressure switch 0.05" to 12" W.C. (12.5 to 2989 Pa), 1/4" barbed fittings
AFS-262 Differential pressure switch 0.05" to 2" W.C. (12.5 to 498 Pa), 1/4" compression fittings
AFS-262-121 Differential pressure switch 0.05" to 2" W.C. (12.5 to 498 Pa), 1/4" barbed fittings 19
AFS-405 Differential pressure switch 0.05" to 12" W.C. (12.5 to 2989 Pa), gold contacts
AFS-460 Manual reset differential pressure switch, 0.4" to 12" W.C. (99.3 to 2989 Pa), SPST
AFS-460-136 Manual reset differential pressure switch, 0.4" to 12" W.C. (99.3 to 2989 Pa), 120 VAC, SPDT
AFS-460-137 Manual reset differential pressure switch, 0.4" to 12" W.C. (99.3 to 2989 Pa), 24 VAC, SPDT
AFS-460-DSS Manual reset differential pressure switch, 2" to 12" WC (498 to 2989 Pa), 2 SPST switches
January 2012 2012 Kele, Inc. All rights reserved. The Kele name and logo are registered trademarks of Kele, Inc. kele.com 888-397-5353 USA 001-901-382-6084 International
851
BACnet
b3865/866/885-V VAV
Controllers with Built-in Actuator
Native BACnet MS/TP communications The b3866-V model is identical to the b3865-V,
with the exception that it also offers damper
Support for 18 BACnet object types, including
position feedback and two analog outputs to
Trends, Schedules, Calenders, and Loops
control reheat valves, lighting ballasts, etc.
Low-cost VAV control in compact package
The b3885-V has a reduced I/O point count for
Built-in damper actuator simplifies smaller VAV applications.
hardware installation
All VAV models feature Flash memory, user
Universal inputs with Form A, Form K, and memory for programs, and a fast (32-bit)
analog outputs for flexible control options processor for faster can times, with plenty of
Non-volatile Flash memory for application additional memory available for data logging of
program and operating system storage your critical data.
Schneider Electric One High Street, North Andover, MA 01845 USA Telephone: +1 978 975 9600 Fax: +1 978 975 9674 www.schneider-electric.com/buildings
SDS-B3865/866/885-A4.BU.N.EN.2.2007.0.00.CC
03
The non-volatile Flash memory stores your operating pulsed control of lighting, heat, and fan units or24VAC ,
SENSOR
OUT4 13
9 IN 5 0.5A
system and application programs, so that in the event for bi-directional control of dampers
USE COPPER CONDUCTORS and ONLY valves; or OUT3 12
10 2 4VAC
INPUT: CLASS 2 POWER ONLY
of a power loss, your application is restored when configured into
11 one Form
24VAC ,K Tri-state
0.42A, 10VA, 50/60HZoutput and one
power is returned. In addition, the Flash memory Form A output. (Note: Any two consecutive Triac
allows for easy upgrades of your operating system via outputs can be configured as a Form K output.)
Outputs are (LOW)
rated for AC loads only. The b3866-V
software downloads, eliminating the need to swap out
memory chips. Each controller, except the b3885-V, controller also offers AIRtwoFLOW
INPUT (0-10V) analog outputs. 866-V
includes an on-board battery to safeguard your
(HIGH)
Connection Labels
Damper Actuator
The integrated damper actuator allows simple
865-V
(LOW)
AIR FLOW
direct mounting of the controller directly over the (HIGH)
INPUT
AIR FLOW
an easy method to tailor the controller to meet your INPUT
(HIGH)
AIR FLOW
change setpoints, balance VAV boxes, monitor INPUT
(HIGH)
occupancy status, and turn equipment on and off.
An enhanced version of the Smart Sensor is also
available with a four-digit custom LCD that provides 1 IN 1
COM 12
RS-485
the following icons: PM, %, , Setpoint, Cool, Heat, 2 IN 2
UNIVERSAL
INPUTS
PORT
COM 11
SHIELD 10
CFM, Fan, OA, and SP. 3 RET CAUTION
MORE THAN ONE DISCONNECT
SWITCH MAY BE REQUIRED
TO DE-ENERGIZE THIS EQUIPMENT
BEFORE SERVICING.
This equipment complies with part 15
of the FCC rules. Operation is subject
to the following two conditions. TRIAC REF 9
(1) This device may not cause harmful
interference.
(2) This device must accept any DIGITAL
interference received, including NOT USED 8
interference that may cause OUTPUTS
undesired operation.
24VAC , OUT4 7
0.5A
USE COPPER CONDUCTORS ONLY OUT3 6
4 2 4VAC
INPUT: CLASS 2 POWER ONLY
5 24VAC , 0.42A, 10VA, 50/60HZ
Schneider Electric One High Street, North Andover, MA 01845 USA Telephone: +1 978 975 9600 Fax: +1 978 975 9674 www.schneider-electric.com/buildings
SDS-B3865/866/885-A4.BU.N.EN.2.2007.0.00.CC
05
b3865/866/885-V Controller
Electrical User LEDs Universal Inputs
Power Status Indicator LEDs: Connections
24 VAC, +10%-15%, 50/60 Hz, CPU CPU Active Model b3865-V: Four inputs and
Class 2 Limited Power Green = Active two returns
Power Consumption Model b3866-V: Four inputs and
Less than 10 VA Airflow Input two returns
Overload Protection Range Model b3885-V: Two inputs and
Fused, MOV protected 0 to 1 W.C. (0-250 Pa) one return
Resolution Input Voltage Range
Mechanical 0.0013 W.C. (0.33Pa) @ 73F (23C) 0 to 5.115 VDC
Operation Environment Accuracy Input Impedance
32 to 122F (0-50C), 0.05 W.C. (12.50 Pa) @ 73F (23C) 10K ohm to 5.120 V
10 - 90% RH (non-condensing) Input Voltage Resolution
Dimensions Damper Shaft Mounting Screws 5.0 mV
7.75 W x 6.25 L x 2.5 H Torque Minimum Digital Resolution
(197 mm W x 159 mm L x 63 mm H) Varies according to shaft material 10 bits
Weight Torque Maximum Input Voltage Accuracy
2.50 lbs (1.04 kg) 30 inch-pounds (3.4 Nm) 15mV
Hex Screws Temperature Range
Battery 10-32 (with supplied hex wrench) -30 to 230F (-34 to 110C)
Replaceable, rechargeable battery. Damper Actuator Motor Temperature Accuracy
Provides 30 days typical accumulated Shaft Diameter 1 F from -10 to 150F
power failure backup of RAM memory. 1/2 (with a 3/8 adapter) ( 0.56C from -23 to +66C)
All data stored in Flash on power loss. 12.6 mm (with a 9.45 mm adapter) Counter Frequency
Shaft Torque 4 Hz @ 50% duty cycle
Communications 53 inch-pounds (5.989 Nm) Input Protection
RS-485 port for implementing Damper Speed 1000 V transients
BACnet MS/TP connection, including: 180 sec. @ 60 Hz and 216 sec @ 50 Hz: Input Filter
Three-position removable screw terminal for 90 adjustable end limits with two 16 Hz with one pole RC filter
Standard service port, four-position set screws Connector
shrouded connector Motor Removable, 5 mm screw terminal
LEDs: Type: 24 VAC synchronous
TD = Transmit Enable Motor Protection: Mechanical clutch
RD = Received Data Manual clutch override with a
Wired/Wireless Field Bus push-button release
RS-485 port for implementing Hardware position feedback
Wireless BACnet connection, including: (model b3866-V only)
Standard service port, four-position
shrouded connector
Schneider Electric One High Street, North Andover, MA 01845 USA Telephone: +1 978 975 9600 Fax: +1 978 975 9674 www.schneider-electric.com/buildings
SDS-B3865/866/885-A4.BU.N.EN.2.2007.0.00.CC
06
b3865/866/885-V Controller
Smart Sensor Interface Analog Outputs Agency Listings
Connections Connections FCC Rules and Regulations CFR 47,
Model b3865-V: One input, Model b3865-V: Not available Part 15, Class A, ICES-003,
SPWR, and return Model b3866-V: Two analog outputs AS/NZS 3548, European Union (EU)
Model b3866-V: One input, and one return Directive 2002/96/EC
SPWR, and return Model b3885-V: Not available
Model b3885-V: Not available Analog Output Channels Required Models
Digital Outputs Two, voltage only b3865-V
Connections Voltage Output Range BACnet 865-V VAV Controller
Model b3865-V: Three triac outputs 0 10 V b3866-V
and one reference Output Source Current BACnet 866-V VAV Controller
Model b3866-V: Three triac outputs 5 mV Maximum b3885-V
and one reference Voltage Output Load BACnet 885-V VAV Controller
Model b3885-V: Two triac outputs 2K ohm Minimum Impedance b3865-V-WL
and one reference Voltage Output Resolution Wireless BACnet 865-V VAV Controller
SPST Accuracy 50 mV b3866-V-WL
0.1 second for pulse width modulation Digital Resolution Wireless BACnet 866-V VAV Controller
Contact Ratings 8 bits b3885-V-WL
0.5 A Maximum, 24 VAC Output Voltage Accuracy Wireless BACnet 885-V VAV Controller
Connector 100 mV
Removable, 5mm screw terminal Connector
Removable, 5mm screw terminal
All brand names, trademarks and registered trademarks are the property of their respective owners. Information contained within this document is subject to change
without notice.
On October 1st, 2009, TAC became the Buildings Business of its parent company Schneider Electric. This document reflects the visual identity of Schneider Electric,
however there remains references to TAC as a corporate brand in the body copy. As each document is updated, the body copy will be changed to reflect appropriate
corporate brand changes.
Schneider Electric One High Street, North Andover, MA 01845 USA Telephone: +1 978 975 9600 Fax: +1 978 975 9674 www.schneider-electric.com/buildings
b3920 System
Controllers
Andover Continuum
b3920 System Controllers
Features
Native BACnet MS/TP Communications for As a native BACnet controller, the b3920 series can
Interoperability to Third-Party Systems communicate with other BACnet devices on the
Supports 18 BACnet Object Types including MS/TP network, in strict accordance with ANSI/
Trends, Schedules, Calendars, and Loops ASHRAE standard 135-2004, and are listed with the
Powerful, Flexible System Controller for the
BACnet Testing Labs (BTL) as BACnet Advanced
Most Demanding Applications
Application Controllers (B-AAC). By connecting to
Andovers Continuum b4920 device or bCX1, the
Expandable I/O Meets Additional Point b3920 and other MS/TP devices can share data
Count Needs from the wider Ethernet/IP network of controllers.
Non-Volatile Flash Memory Provides Utmost
Reliability Stores Both Application Program Increased Reliability with Flash Memory
and Operating System The b3920s non-volatile Flash memory stores your
Optional Local Display/Keypad Provides Easy
operating system and application programs, so that
Operator Interface
in the event of a power loss, your application will
be restored when power is returned. In addition,
Local, Extended Storage of Log Data the Flash memory allows for easy upgrades of
View and Modify Information with Optional your operating system via software downloads,
Smart Sensor Display eliminating the need to swap out proms.
BTL Listed B-AAC Controller with Local Trends
Schneider Electric One High Street, North Andover, MA 01845 USA Telephone: +1 978 975 9600 Fax: +1 978 975 9674 www.schneider-electric.com/buildings
SDS-B3920-A4.BU.N.EN.10.2005.0.00.CC
03
Andover Continuum
b3920 System Controllers
Features (continued)
temperature sensor.
1
!# 0/7%2
.
6!#
6!
(:
,
Outputs
The b3920 contains 16 outputs - eight Form C relay
outputs, each rated for 24 VAC/VDC, 3 amp, and
4
3%26)#%
0/24
2$
2%4
).
I/O Expansion
/&& /.
).
2%4
).
).
).
).
).
).
).
). /&& /.
3
).
).
2%4
).
2%4
).
3072
).
3-!24
3%.3/2
Schneider Electric One High Street, North Andover, MA 01845 USA Telephone: +1 978 975 9600 Fax: +1 978 975 9674 www.schneider-electric.com/buildings
SDS-B3920-A4.BU.N.EN.10.2005.0.00.CC
04
Andover Continuum
b3920 System Controllers
Features (continued)
).
Smart Sensor Interface ).
/&& /.
2%4
turn equipment on and off. An enhanced version
).
of the Smart Sensor is also available with a 4-digit
).
custom LCD that provides the following icons: PM,
%, , Setpoint, Cool, Heat, CFM, Fan, OA, and SP. 2%4
).
). /&& /.
2%4
).
).
2%4
).
).
2%4
).
).
3072
#05
2% 4
).
!.!,/'
/540543
3-!24 #522%.4 /54054
3%.3/2
6/,4!'% /54054
2%34!24
Schneider Electric One High Street, North Andover, MA 01845 USA Telephone: +1 978 975 9600 Fax: +1 978 975 9674 www.schneider-electric.com/buildings
SDS-B3920-A4.BU.N.EN.10.2005.0.00.CC
05
Andover Continuum
b3920 System Controllers
Specifications
Schneider Electric One High Street, North Andover, MA 01845 USA Telephone: +1 978 975 9600 Fax: +1 978 975 9674 www.schneider-electric.com/buildings
SDS-B3920-A4.BU.N.EN.10.2005.0.00.CC
06
Andover Continuum
b3920 System Controllers
Specifications (continued)
All brand names, trademarks and registered trademarks are the property of their respective owners. Information contained within this document is subject to change
without notice.
On October 1st, 2009, TAC became the Buildings Business of its parent company Schneider Electric. This document reflects the visual identity of Schneider Electric,
however there remains references to TAC as a corporate brand in the body copy. As each document is updated, the body copy will be changed to reflect appropriate
corporate brand changes.
Schneider Electric One High Street, North Andover, MA 01845 USA Telephone: +1 978 975 9600 Fax: +1 978 975 9674 www.schneider-electric.com/buildings
Schneider Electric One High Street, North Andover, MA 01845 USA Telephone: +1 978 975 9600 Fax: +1 978 975 9674 www.schneider-electric.com/buildings
SDS-BACNET-BCX1-A4.BU.N.EN.7.2008.0.00.CC
03
Programmable
The dynamic memory of the bCX1-CR can
be allocated for any combination of programs
and BACnet object (including Schedules,
Alarms, and Trends). Our powerful Plain English
programming language can directly reference
any BACnet object either locally or globally.
Our object-oriented Plain English, with intuitive
keywords, provides an easy method to tailor the
controller to meet your exact requirements. As
a programmable controller, the bCX1-CR can
locally support a wide range of BACnet objects,
including BACnet loops, trends, and schedules.
Plain English programs may be created to
program coordinated control strategies, giving
you the freedom to move data between third party
devices that do not have peer to peer functionality
provided in all Andover Continuum controllers. Power Drawing RS-485 RS-232
Communications Communications
Embedded Web Server Drawing Drawing
With the power of Plain English, standard HTML
web pages can be created and embedded into the
bCX1-CR to provide a simple-to-use, browser-based
interface for monitoring or changing data points.
The embedded web pages are fully customizable
to meet any special customer requirements.
Schneider Electric One High Street, North Andover, MA 01845 USA Telephone: +1 978 975 9600 Fax: +1 978 975 9674 www.schneider-electric.com/buildings
SDS-BACNET-BCX1-A4.BU.N.EN.7.2008.0.00.CC
04
All bCX1 controllers are compatible with SNMP Wireless BACnet Yes Yes
monitoring tools, which allow the controller to be MS/TP Node Options 64 0, 8, 32, 64, 127
interrogated for basic SNMP information. The CR Flash Memory Yes Yes
model features advanced SNMP alarm functionality xP Expansion I/O No 2+ Display
as an option (SA), providing alarm delivery for any
Plain English No Yes
device on the MS/TP network it manages.
XDriver Support No Yes
Email Support No Yes
XDriver Support
The BACnet bCX1 Controller/Router is available Web
with XDriver Support for 2nd generation Andover Basic Configuration Yes Yes
Continuum XDrivers to interface with third-party Embedded Web Server No Yes
devices. (Note: This feature is not available on the SNMP
Router Only version.)
SNMP Monitoring Yes Yes
SNMP Alarming No Optional
BACnet Device Profile Router Only B-BC
BTL Listed No
Schneider Electric One High Street, North Andover, MA 01845 USA Telephone: +1 978 975 9600 Fax: +1 978 975 9674 www.schneider-electric.com/buildings
SDS-BACNET-BCX1-A4.BU.N.EN.7.2008.0.00.CC
05
Schneider Electric One High Street, North Andover, MA 01845 USA Telephone: +1 978 975 9600 Fax: +1 978 975 9674 www.schneider-electric.com/buildings
SDS-BACNET-BCX1-A4.BU.N.EN.7.2008.0.00.CC
06
All brand names, trademarks and registered trademarks are the property of their respective owners. Information contained within this document is subject to change
without notice.
On October 1st, 2009, TAC became the Buildings Business of its parent company Schneider Electric. This document reflects the visual identity of Schneider Electric,
however there remains references to TAC as a corporate brand in the body copy. As each document is updated, the body copy will be changed to reflect appropriate
corporate brand changes.
Schneider Electric One High Street, North Andover, MA 01845 USA Telephone: +1 978 975 9600 Fax: +1 978 975 9674 www.schneider-electric.com/buildings
FEATURES
Microprocessor design increases accuracy and reduces installation time
DESCRIPTION
3Year Warranty
SPECIFICATIONS
Input Power 20 to 30VDC/24AC; 100mA Maximum
AIR QUALIT Y
EMC Conformance: Low voltage directive 2006/95/EC and EMC directive 2004/108/EC.
EMC Special Note: Connect this product to a DC distribution network or an AC/DC power adaptor with proper SURGE PROTECTION (EN 61000-6-1:2007 specification requirements).
* Measured at NTP
CALIBRATION
PUSHBUTTON
CO2-OUT
V+ GND
LED
Optional *
* Note: Connector blocks and headers for optional features are not included with non-option models.
DIMENSIONAL DRAWINGS
CWE Wall Mount CDE Duct Mount
6.7" 10.2"
(170 mm) (258 mm)
AIR QUALIT Y
4.8"
(122 mm) 3.1"
(78 mm)
2.4" 7.8"
(61 mm) (97 mm)
3.5" 1.2"
(89 mm) (30 mm)
Temperature Sensors
General Instructions
APPLICATION
FEATURES
#OPYRIGHT 3CHNEIDER %LECTRIC !LL 2IGHTS 2ESERVED &
INSTALLATION
ROOM TEMPERATURE SENSORS
This unit is suitable for either drywall mounting or junction box mounting. The room sensor is provided with screw terminal blocks for all connections. Re-
move the cover from the unit and mount the housing base to the wall using the (2) 6/32 x 1 machine screws. Replace the cover and tighten down, using
the (2) 1/16 Allen Screws located on the bottom of the enclosure.
WIRING DIAGRAMS
Diagram for ETR Sensors
Tenant Override Output to
Controller (Separ ate Input Only)
Tenant Override Output to
Setpoint Output to Controller Controller (Separ ate Input Only)
Short Sensor
Thermistor and Override
Output to Controller Separate Input
J3
Thermistor and Override J2
Output to Controller Membrane SW1
Gnd + - SE T O/R
Wire Access Hole
After Hours Normally-Open
1 2 3 4
Override Switch
Communication Jack
Override Options Jumper Settings (J3)
Terminals for RJ11 Communications Override Short Separ ate Input
Sensor (Dr y Contact Closur e )
Short Sensor Short Sensor
c Multi4 Rev 7 Separate Input Separate Input
Fi gure #1
On October 1st, 2009, TAC became the Buildings business of its parent company Schneider Electric. This document reflects the visual identity of Schneider Electric,
however there remains references to TAC as a corporate brand in the body copy. As each document is updated, the body copy will be changed to reflect appropriate
corporate brand changes.
General Instructions
FEATURES
Accurate, Reliable Type III Thermistor
Two 7-Segment LED Display or Four Digit Custom
LCD Display
6-Button Programmable Keypad
Built-In Service Port for Andover Lap-Top Service Tool
Powered Directly from Andover Controls
TCX 866 VAV Controller
ORDERING INFORMATION
F-27636
Room Controllers
SE7300 Series
C C
Filter Fan
status status
switch switch
SE73 45
Humidity Sensor and PIR Options: Communication Options:
Control: -50 = PIR ready but PIR -B = BACnet MS/TP
-0 = No humidity sensor cover not included -E = Echelon
2011 Schneider Electric. All rights reserved.
Compatibility:
Center Key Fuction: -C = Floating or on-off
-0 = Override, for commercial digital control outputs
applications -F = Analog 0-10 Vdc
-5 = C/F, for hotels control outputs
/ lodging applications
Schneider Electric 1354 Clifford Ave. Loves Park, IL 61111 1-888-444-1311 www.schneider-electric.com
F-27750 Sep 2011 bm
Current Switches:
Fixed Trip Point
H300
Split-Core & Solid-Core Go/No Go
Current Switches
APPLICATIONS
Monitoring status of electrical loads
Monitoring direct-drive units, exhaust fans, and other fixed loads
H600
Verifying lighting run times
FEATURES
H900
On/off status for direct-drive fans, pumps, and process motors 0.15 A H800
More reliable for status than relays across auxiliary contacts TURN-ON!
US Patent No. 7,193,428
Ideal for direct-drive units, unit vents, fan coil units, exhaust fans, and other
fixed loads
Great for lighting statusless expensive than 277V relays
Low 0.15A turn-on (H300 and H600)...ideal for small exhaust fans (not intended DESCRIPTION
5YearWarranty
impressive improvement in turn-on levels. The Hawkeye H300 and H600 now have
Split-core H300, H600, and H900 for fast retrofit installation the lowest turn-on current in the industry at a mere 150mA!
Mini solid-core H800 and micro split-core H300 fit in tight enclosures...saves
valuable panel space
100% solid-state, no moving parts to fail
Polarity insensitive output
5-year limited warranty
Maximize Reliability
Minimize Installed Cost
SPECIFICATIONS
Sensor Power (N.O. Models) Induced from monitored current
Insulation Class 600VAC RMS (UL), 300VAC RMS (CE)
Frequency Range 50/60 Hz
Temperature Range H800, H800NC, H300, H900: -15 to 60C (5 to 140F)
H600: -15 to 40C (5 to 104F) (to 200A); -15 to 60C (5 to 140F) (to 150A)
H800HV: -40 to 50C (-40 to 122F) (to 200A); -40 to 75C (-40 to 167F) (to 100A, & 0.25A output)
Humidity Range 10-90% RH, non-condensing
Sensor Power (N.C. Models) 5-30VDC, permanently connected
Off State Leakage (N.C. Models) 34A@5VDC, 200A@30VDC
On State Voltage Drop (N.C. Models) 1.9VDC (max.) @0.1A
Terminal Block Maximum Wire Size 14 AWG (16 AWG for H300)
Terminal Block Torque (nominal) 4 in-lbs (7 in-lbs for H300)
Agency Approvals UL 508 open device listing; CE:EN61010-1:2001-02, CAT III, deg. 2, basic insulation
0.3 0.6"
(16 mm) 0.7" 0.9"
(8 mm) 1.6 1.2" (23 mm)
(18 mm)
6 AWG max. (40 mm) 0.7" (31 mm)
2.1"
(54 mm) (18 mm)
2.8" *
0.5" 2.5" *
(71 mm)
1.5 (13 mm) (64 mm)
(38 mm)
0.18 (x2)
(5 mm)
0.6 1.7
(15 mm) 2.1" (43 mm)
1.8 (54 mm) 0.4 x 0.2
(46 mm) Slot (x2)
1.1" *
1.0" * (27 mm)
(26 mm)
0.4 x 0.2 2.3"
(10 mm x 5 mm) (58 mm)
Slot (2x) 2.9"
(74 mm)
3.5"
(89 mm)
H900
Removable Mounting Bracket
1.0
APPLICATION/WIRING DIAGRAM (25 mm) Bracket can be mounted
Unit Vent Heater Control 1.1 0.8
on either side for added
installation flexibility.
BUILDING AUTOMATION (26 mm) (21 mm)
CONTROLLER **3.1
POWER (79 mm)
SOURCE
CURRENT MONITORING
DI
Self-gripping
Iris
2.8
(70 mm)
DI
1.4*
= 0.3 (36 mm)
(8 mm)
2.5
(64 mm)
3.0
(76 mm)
MODEL AMPERAGE RANGE STATUS OUTPUT (max.) TRIP POINT HOUSING UL CE RoHS
H300 0.15 - 60A N.O. 1.0A@30VAC/DC 0.15A or less Split-core n n2 n
1
H600 0.15 - 200A N.O. 1.0A@30VAC/DC 0.15A or less Split-core n n n
1
H800 0.25 -200A N.O. 1.0A@30VAC/DC 0.25A or less Solid-core n n n
H800NC 0.5 - 200A N.C. 0.1A@30VDC 0.5A or less Solid-core n1 n
H800HV 0.75 - 200A N.O. 0.5A@250VAC/DC 0.75A or less Solid-core n3
H900 1.5 - 200A N.O. 1.0A@30VAC/DC 1.5A or less Split-core n n
1
Listed for use on 75C insulated conductors.
2
Product provides functional insulation only. ACCESSORIES
3
Listed for use on 90C insulated conductors. DIN Rail Clip Set (AH01, AH27)
DIN Rail (AV01) and DIN Stop Clip (AV02)
Self-gripping iris on the split-core housing for easy installation Hx08 Series and H701 current switches offer high performance, with a wide array
Status LEDs for easy setup and local indication (no LED on the H701) of amperage range options. These products can accurately detect belt loss, coupling
Bracket on H908 can be installed in three different configurations shear, or other mechanical failure on loads from 1/5 to 100HP.
1 Amp status output for increased application flexibility
All devices are 100% solid state and polarity insensitive, with a 5-year warranty
CURRENT MONITORING
Fan/pump Electrical
On failure Maximize Reliability
Calibrated Minimize Installed Cost
Trip
Point Off Off
Loss of belt/coupling shear
SPECIFICATIONS
Sensor Power Induced from monitored conductor
Insulation Class 600VAC RMS (UL), 300VAC RMS (CE)
Frequency Range 50/60 Hz
Temperature Range -15 to 60C (5 to 140F)
Humidity Range 10-90% RH, non-condensing
Hysteresis 10% (typical)
Terminal Block Maximum Wire Size 14 AWG (16 AWG for H308)
Terminal Block Torque (nominal) 4 in-lbs (7 in-lbs for H308)
UL 508 open device listing; CE: EN61010-1:2001-02, CAT III, deg. 2, basic insulation
Do not use the LED status indicators as evidence of applied voltage.
CURRENT MONITORING
(79 mm)
DI
9
Self-gripping
2.8" Iris
(68 mm) 2.8
(70 mm)
1.1" *
(27 mm) 1.4*
0.2 x 0.15
= 0.3 (36 mm) Fan or Pump
(8 mm)
slot (2x) 3.8"
(95 mm) 2.5
4.2" (64 mm)
(106 mm) 3.0
(76 mm) Motor
* Terminal block may extend up to 1/8 over the height dimensions shown.
MODEL AMPERAGE RANGE STATUS OUTPUT (max.) MIN. TRIP POINT HOUSING STATUS LED UL CE RoHS
2
H308 0.75 - 50A 0.75A or less Split-Core n n n n
1
H608 0.5 - 175A 0.5A or less Split-Core n n n n
DESCRIPTION
The Model M264 Differential Pressure Transmitter is a
low-air pressure transmitter able to sense differential pressure
in both negative and positive ranges. The Model M264
incorporates a tensioned stainless steel diaphragm to form
a variable capacitor that will produce variation in the output
signal. The Model M264's durable design will tolerate an
overpressure of 10 psig (68.95 kPa) and has an unconditional
three-year warranty.
FEATURES
4-20 mA output signal
Voltage output signal optional
10 psig (68.70 kPa) overpressure
Three-year unconditional warranty
1% accuracy
Reverse wiring protected
Stainless steel diaphragm APPLICATION
Ideal for air and non-conducting gases HVAC building automation
Variable air volume control
Environmental pollution control
Lab and fume hood control
Filter monitoring
Medical instrumentation
PRESSURE
Velocity pressure measurement
SPECIFICATIONS
Supply Voltage Position Effect (Unit is factory calibrated at 0g effect
Current Models 9 to 33 VDC with diaphragm vertical),
Voltage Models 9 to 30 VDC Range Zero offset (%FS/G)
Signal Output 4-20 mA (two-wire) Up to 0.5" WC 0.60
0-5 VDC (three-wire) Up to 1.0" WC 0.50
Maximum Output Up to 2.5" WC 0.22
Impedance (mA) 750 @ 24 VDC Up to 5.0" WC 0.14
Minimum Output Operating Temperature 0 to 175F (-18 to 79C)
Impedance (VDC) 5000 Storage Temperature -65 to 250F (-54 to 121C) 19
Accuracy 1% FS Enclosure Fire-retardant glass filled polyester
Non-linearity 0.96% FS (UL 94 V-0 approved)
Non-repeatability 0.1% FS Process Connection 3/16" OD barbed brass
Hysteresis 0.2% FS Dimensions 3.00"H x 5.51"W x 1.91"D
Compensated Temperature (14.00 x 7.62 x 4.85 cm)
Range 0 to 150F (-18 to 65C) Approvals CE
Thermal Effect Zero/Span shift 0.033F (0.018C) Weight 9 oz (255g)
Overpressure Upto 10 psig (68.95 kPa) range Warranty 3 years
dependant
DIMENSIONS
in 4.56 (11.59)
(cm)
Zero
Model M264
2.75 1.66
High
Low
(6.99) (4.22)
Span
WIRING
Power
Supply
9-30 VDC
4-20 mA
0-5 VDC
4-20 mA Output 0-5 VDC Output
ORDERING INFORMATION
PRESSURE
MODEL DESCRIPTION
M264 Differential pressure transmitter
XXX RANGE CODE (see Table 1 below)
C 4-20 mA output (stocked at Kele)
V 0-5 VDC output (call Kele for availability)
Example: M264-2R5WB-C Differential pressure transmitter
M264 - 2R5WB - C with a 4-20 mA output proportional to a range of
-2.5" to 2.5" W.C. (622 Pa)
8.625
8.250 4.500
c c c c c c
c c c c c
c c c c c c
c c c c c
c c c c c c
c c c c c RESET RESET
c c c c c c
c c c c c
c c c c c c
MADE IN USA
SPECIFICATIONS
OFF OFF
RESET RESET
4.500
Over Current Protection: Inherently Limited
RESET
NOTES
DESCRIPTION
IDEC general-purpose relays are available in the RH Series
blade-style relays and the RR Series pin-style relays and the
RJ Series compact relays.
SPECIFICATIONS
COIL RATINGS CONTACT RATINGS
RH SERIES RH SERIES (UL ratings)
RATED CURRENT (mA) 15% @ 20C INRUSH CURRENT RESISTIVE (A) INDUCTIVE (A) MOTOR LOAD (hp)
RATED
DIMENSIONS
in
1.07 (2.75)
1.07 (2.75)
1.07 (2.75)
1.07 (2.75)
(cm)
1.418 (3.6)
1.13 (2.38)
1.42 4
(3.64) 2
WIRING
1 1 4 1 2 4 1 2 3 4
Legend 5 5 8 5 6 8 5 6 7 8
3 4 5
NC 9 9 12 9 10 12 9 10 11 12
NO 13
(-)
14
(+)
13 (-) (+)14 13 (-) (+)14 13 (-) (+)14 4 3 6
2 1 2 3
3 6 4 8
5 4 6 4 5 6
1 5 1 8
3 9 7 7 9 7 8 9
2 7 A B RJ1S RJ2S
A B A B
(-) (+) 2 10
(-) (+)
(-) (+) (-) (+) (-) (+)
1 8 1 11
RR1BA RR2BA RR3B
RR2P RR3PA
ORDERING INFORMATION
20 AC240V
DC12V
240 VAC coil voltage
12 VDC coil voltage
AC120V
AC240V
120 VAC coil voltage
240 VAC coil voltage
DC24V 24 VDC coil voltage DC12V 12 VDC coil voltage
DC24V 24 VDC coil voltage
RH1B U AC24V
RR2P U AC24V
MODEL DESCRIPTION
RJ1S Relay, SPDT (use SJ1S-05B socket) Example: RR2PUAC24V DPDT relay 8 pin with 24VAC coil
RJ2S Relay, DPDT (use SJ2S-05B socket)
C No options
CL LED indicator
A24 24 VAC coil voltage
A120 120 VAC coil voltage
D24 24 VDC coil voltage
RJ1S C A24
RIBD2421C Enclosed Time Delay Relay 10 Amp SPDT with 24Vac/dc 120-277Vac Coil
Contact Ratings:
10 Amp Resistive @ 30 Vdc
10 Amp General Use @ 250 Vac
1/2 HP @ 125-250 Vac Wht/Brn Blu
470 VA Pilot Duty @ 120-240 Vac 120-277 Vac N/C
Input Current:
100 mA @ 24 Vac
30 mA @ 24 Vdc
Wht/Blu Yel
55 mA @ 277 Vac
c c c c c c
c c c c c
c c c c c c
c c c c c
c c c c c c
c c c c c
24 Vac/dc Comm
c c c c c c
c c c c c
c c c c c c
DELAY ON MAKE (N/O) APPLICATION FOR INTERVAL (N/C) APPLICATION FOR DELAY ON BREAK (N/C)
Note: Load Power + Coil Input
must use same voltage source
Time Delay
COIL COIL COIL
-OR-
N/C Power
COIL
Time Delay
N/O Power
COIL COIL LOAD
LOAD LOAD
N/C Power
COIL
LOAD
Andover Continuum TM
Schneider Electric One High Street, North Andover, MA 01845 USA Telephone: +1 978 975 9600 Fax: +1 978 975 9674 www.schneider-electric.com/buildings
SDS-XPEXPANSION-I/O-US.BU.N.EN.8.2007.0.00.CC
03
INPUTS INPUTS
xPAO4 xPDO4
Schneider Electric One High Street, North Andover, MA 01845 USA Telephone: +1 978 975 9600 Fax: +1 978 975 9674 www.schneider-electric.com/buildings
SDS-XPEXPANSION-I/O-US.BU.N.EN.8.2007.0.00.CC
04
Dimensional Drawings
xP Module
xP Display
Models
xP-Display
(includes 3 foot cable)
xP-Display-10
(includes 10 foot cable)
Power Consumption
70 mA
Display Properties
4 lines x 16 characters,
backlit
Enclosure Type
IP54 Rating
Installation
Modules can be connected to the bottom of the
controller with the built-in expansion port connector
or they may be connected remotely via a 3-foot (~1
m) or 10-foot (~3m) ribbon cable. A total of 10 feet
of cable may be used for all Expansion Modules.
Mounting and securing of the xP modules is provided
through four mounting holes in the base plate.
Schneider Electric One High Street, North Andover, MA 01845 USA Telephone: +1 978 975 9600 Fax: +1 978 975 9674 www.schneider-electric.com/buildings
SDS-XPEXPANSION-I/O-US.BU.N.EN.8.2007.0.00.CC
05
xP Expansion I/O
Electrical Communications Agency Listings
Power Communications Interface UL/CUL 916, FCC CFR 47 Part 15,
Up to two I/O module and an xP-Display may Through built-in Expansion Port ICES-003, EN55022, AS/NZS 3548,
be connected to a controller. All controllers on controller Class A, CE
provide a total of 180 mA of power, the bCX1
controller/router has 400 mA of power, for the Connections xPDI8 (Digital Inputs)
modules. Each modules power consumption Fixed Terminal Connectors Points
is listed below. Reference installation sheet for Reference specific module on previous 8 Digital Inputs
valid combinations. page for terminal point assignments Power Consumption
Input (top) 25 mA
Mechanical 6-pin shrouded connector Voltage
Operating Environment Output (bottom) 0-5 VDC, or contact closure
32120F (049C), 6-pin shrouded connector Input Impedance
1095% RH (non-condensing) User LEDs/Switches 10K ohm ref to +5VDC
Size Status Indicator LEDs Frequency
Module: 3.21 H x 7.10 W x 1.60 D CPU Module is Active 140Hz, 50% duty cycling, 3.57 ms
(82H x 180 W x 41 D) mm Switches pulse width min.
Display: 7.25 H x 5.00 W x 1.65 D RESET Overvoltage Protection
(184H x 127 W x 42 D) mm 24 VAC/DC +/- 1500 V transients
Weight General
Module: 0.48 lb (0.22 kg) xP Modules
Display: 1lb (0.45 kg) Consult the xP Module Installation
Enclosure Type Guide for the maximum number
Modules: UL Open class, IP 10. of inputs/outputs allowed on
Flammability rating of UL94-5V each controller.
Display: IP54
Cable Options
xP-Mod-Cable-3
3-foot (~1m) ribbon cable terminated
xP-Mod-Cable-10
10-foot (~3m) ribbon cable terminated
Schneider Electric One High Street, North Andover, MA 01845 USA Telephone: +1 978 975 9600 Fax: +1 978 975 9674 www.schneider-electric.com/buildings
SDS-XPEXPANSION-I/O-US.BU.N.EN.8.2007.0.00.CC
06
N1831
xP Expansion I/O
xPUI4/xPBA4/xPBD4 xPAO2/xPAO4/xPBA4 xPDO2/xPDO4/xPBD4
(Universal Inputs) (Analog Outputs) (Digital Outputs)
Points Points Points
4 Universal Inputs 2 Analog Outputs (xPAO2) 2 Digital Outputs (xPDO2)
Power Consumption 4 Analog Outputs (xPAO4, xPBA4) 4 Digital Outputs (xPDO4, xPBD4)
50 mA (xPUI4) Power Consumption Type
60 mA (xPBA4) 80 mA (xPAO2) 2 or 4 single pole single throw (SPST)
125 mA (xPBD4) 120 mA (xPAO4) Form C relays
Voltage 60 mA (xPBA4) Power Consumption
0-5.115 VDC Output Rating 60 mA (xPDO2)
Input Impedance 0-10 VDC 100 mA (xPDO4)
10K ohm ref to +5VDC 4-20mA per channel (xPAO2, xPAO4) 125 mA (xPBD4)
Frequency Output Resolution Output Rating
4Hz, 50% duty cycling, 0.1V for 0-10V Maximum 3A, 24 VAC/VDC,
125 ms pulse width min. (Inputs 1-3) 0.1mA for 4-20mA (xPAO2, xPAO4) +/- 1500 V transients (tested
140Hz, 50% duty cycling, 3.57 ms Overrides according to EN61000-4-4)
pulse width min. (Input 4) yes per output point. Software Output Accuracy
Overvoltage Protection feedback of the switch position is 0.1 sec for pulse width modulation
24 VAC/DC +/- 1500 V transients provided, for display and alarming Output Overrides
Potentiometer Each Output is equipped with a
yes per output point manual override switch. Software
feedback of the switch position is
provided, for display and alarming
All brand names, trademarks and registered trademarks are the property of their respective owners. Information contained within this document is subject to change
without notice.
On October 1st, 2009, TAC became the Buildings Business of its parent company Schneider Electric. This document reflects the visual identity of Schneider Electric, how-
ever there remains references to TAC as a corporate brand in the body copy. As each document is updated, the body copy will be changed to reflect appropriate corporate
brand changes.
Schneider Electric One High Street, North Andover, MA 01845 USA Telephone: +1 978 975 9600 Fax: +1 978 975 9674 www.schneider-electric.com/buildings
DESCRIPTION
The SH and SR Series of IDEC relay sockets are for use with
the IDEC RH / RR Series relays and RTE Series timers. The
SH and SR Series include both blade and pin style sockets
and are available for one, two, three and four pole relays.
The SH and SR sockets can be DIN rail or surface mounted.
The SJ Series of IDEC relay sockets are for use with the
SJ1S, SJ2S SH1B-05
IDEC RJ1S and RJ2S Series relays. They can be DIN rail or
surface mounted.
FEATURES
Use with IDEC RH / RR / RJ relays and RTE timers
Screw terminals with captive wire clamp
Surface or DIN rail mount
UL recognized, CSA certified and CE approved
SH2B-05 SH3B-05
DIMENSIONS
0.66
(1.7) 1.12 0.86 1.12
2.2 (5.6) 0.1 0.32 (2.2) (2.85)
(2.85)
1.9 (4.9) (0.2) (0.8) 0.32 0.7
1.4 (3.5) (0.8) (1.88)
8
4
5
8 5
2
1
7
2
4 1
3
14 13 14 13
2 Mounting
4
9
5
12 9 2 Mounting
Holes Holes
5
0.16 dia
3
1.12 1.25
1.25 1.12
(2.85) 1.65 (2.85) 1.40 (2.85)
0.32 (3.2) 0.7 (3.6)
0.32 (4.2) 0.7
(0.8) (1.88) (0.8) (1.88) 0.32 0.64
(0.8) (1.7)
8 6 5 8 7 6 5 5 4
4 2 1 4 3 2 1 6 3
20 ORDERING INFORMATION
MODEL DESCRIPTION
SH1B-05 Relay socket, SPDT blade type, DIN/surface mount
SH1B-05C SH1B-05QT20 SH2B-05 Relay socket, DPDT blade type, DIN/surface mount
SH2B-05C SH2B-05QT10 SH3B-05 Relay socket, 3PDT blade type, DIN/surface mount
SH4B-05 Relay socket, 4PDT blade type, DIN/surface mount
SH4B-05C SJ1S-05B Relay socket, SPDT blade type, DIN/surface mount
SJ2S-05B Relay socket, DPDT blade type, DIN/surface mount
SR2P-05 Relay socket, DPDT pin type, DIN/surface mount
SR2P-06 Relay socket, DPDT pin type, DIN/surface mount
SR3B-05 Relay socket, three-pole blade type, DIN/surface mount
SR3P-06 Relay socket, 3PDT pin type, DIN/surface mount
Andover Controls Wall Mount Temperature Sensor provides accurate, reliable measurement of F E A T U R E S
interior room temperature for use in an Andover Controls building automation system. The active Accurate, Reliable Type III Thermistor
sensing element is a highly stable, precision thermistor, accurate to within 0.36F. The sensor has an
Attractive, Ventilated Two-Piece
operating range of 40F to 100F (4.4C to 37.8C).
Housing
The thermistor is encapsulated with a low mass, high-conductivity thermal compound for good heat Fast Response to Temperature Changes
The sensor may be mounted directly on dry wall, or on any electrical outlet box with no adapters
required. The sensor is for interior use only, and is not suitable for use where condensation may
occur.
SPECIFICATIONS
Stability: Thermistor will not deviate from accuracy spec for minimum of 5 years
Maximum Distance to Sensor: 24 gauge wire: 490 ft. with less than 0.1F (-17.72C) error
22 gauge wire: 850 ft. with less than 0.1F (-17.72C) error
20 gauge wire: 1,200 ft. with less than 0.1F (-17.72C) error
18 gauge wire: 2,000 ft. with less than 0.1F (-17.72C) error
Color: Off-white
ORDERING INFORMATION
DIMENSIONAL DRAWING
1.05
(27)
3.50
(89)
4.50
(114)
Andover Controls Corporation Andover Controls Ltd. Andover Control GmbH Andover Control S.A. Andover Controls Andover Controls Mexico
World Headquarters Smisby Road Am Seerhein 8 Immeuble Dolomites 2 Corporation Insurgentes Sur 1722-501
300 Brickstone Square Ashby-de-la-Zouch D-78467 Konstanz, Germany 58, Rue Roger Salengro Unit 1201-02, Phase I, Col. Florida
Andover, Massachusetts 01810 Leicestershire LE65 2UG, Tel: 07531 99370 94126 Fontenay-Sous-Bois, Cheuk Nang Centre Mexico D.F. 01030 Mexico
USA England Fax: 07531 993710 Cedex, France 9 Hillwood Road, Tsim Sha Tsu Tel: 525 661 56 72
Tel: 978 470 0555 Tel: 01530 417733 Tel: 331 53 99 16 16 Kowloon, Hong Kong Fax: 525 661 54 15
ax: 978 470 0946 Fax: 01530 415436 ax: 331 53 99 16 15 Tel: 852 2739 5497
http://www.andovercontrols.com Fax: 852 2739 7350
DESCRIPTION FEATURES
Victory 100 and 200 Series 10A enclosed relays are pilot-duty relays in an easy- Sleek field enclosure reduces the need for panel space
to-use nipple mount enclosure. The V100/V200 Series provide quick relay mounting The nipple mount feature allows the Victory Series to be mounted to any
without a dedicated field enclosure, making them ideal for retrofit projects. Field- electrical enclosure
selectable high and low voltage coil inputs provide on-site versatility. Flexible tinned stranded wire...fits easily in tight spaces & provides secure
connections to wire nuts
APPLICATIONS UL508 Listed...designed and approved for field installation...makes electrical
inspection a snap
Command contactors
Run low voltage instead of line voltage...eliminate conduit in some applications
Control motors
Isolation
Device interlocking
TYPICAL COIL PERFORMANCE
Relay logic
Pull in Voltage AC DC
Sense voltages for alarm conditions
10-30V..................................... 8 9
120V........................................ 78
208-277V................................. 154
Drop Out Voltage AC DC
10-30V..................................... 2 3
120V........................................ 18
208-277V................................ 36
RELAYS
CONTACT RATINGS
Resistive.............. 10A@277VAC, 28VDC
Motor.................... 120VAC, 1/3HP N.O. & 1/6HP N.C.
240VAC, 1/3HP N.O. & 1/6HP N.C.
277VAC, 1/4HP N.O. & 1/8HP N.C.
Pilot Duty............. 277VAC, (1.7A), 480VA N.O.
Ballast.................. 277VAC, 1.7A
Tungsten............... 120VAC, TV3 N.O. TV2 N.C.
SPECIFICATIONS 5Year
Warranty
Gold Flash............. Yes
Operating Temperature:
V100, V100DC, V200 -34 to 60C (-29 to 140F)
V100D, V200D -40 to 55C (-40 to 131F)
Operating Humidity 10-90% RH non-condensing
Expected Relay Life Electrical (@ rated current) 100,000 cycles; Mechanical (unpowered) 10,000,000 cycles
Relay Status LED ON=energized
Wire Specifications:
Lead Length 14 (356 mm) min.
Gauge UL1015; Coil: 18 AWG; Contacts: 16 AWG
Insulation Class 600VAC RMS
UL 508 enclosed device listing
2.8" 1.6"
(71 mm) (41 mm)
CONTACTS
To Load
COIL
Wire
Nut
2.3" 2.5"
(59 mm) (64 mm)
RELAYS
3/4" NPT Nipple
br
or a
or a
ow
wht/brown
ow
wht/orange
ng
ng
n
208-277VAC
e
bla
wht/black
ck
ck
120VAC wht/red
120VAC
* YELLOW
*
Common Common
LOW White LOW
blu
blu
wht/blue grey/wht
e
10-30VAC/DC 10-30VAC/DC
COMM ORANGE
COMM
White
ye
ye
wht/yellow
llo
llo
wht/violet
w
ORDERING INFORMATION
MODEL RELAY COIL AMPERAGE RATING RELAY POWER LED UL
V100* SPDT 10-30VAC/DC, 120VAC n n
V100D 2x SPDT 10-30VAC/DC, 120VAC n n
V100DC SPDT 10-30VDC 10A n n
V200 SPDT 10-30VAC/DC, 208-277VAC n n
V200D 2x SPDT 10-30VAC/DC, 208-277VAC n n
Some devices are Plenum rated per UL 1995...see White Paper VWP01 at veris.com for details.
* Optional domestic version available.
HQ0001833.A 01121
X SERIES VERIS INDUSTRIES
DESCRIPTION APPLICATIONS
Veris X Series Control Transformers are a convenient source of control power for Controller power
HVAC control and building automation applications. A wide variety of UL-listed Switching relays and other digital I/O circuits
transformers are available with single and dual threaded hub mounting options.
Powering sensors
Multiple current limiting options are available, including a circuit breaker in some
models. Save ordering time and purchase order costs when buying other Veris
sensors by including transformers in your order. FEATURES
UL Listings for all models simplify panel building requirements
Threaded hub options maximize installation flexibility
One stop shopping...save time by ordering along with other Veris products
DIMENSIONAL DRAWING
L
W A
POWER SOURCES
H B
Threaded for
* See ordering table for dimensions. conduit nut
WIRE COLORS
STANDARD CENTER TAP
PRIMARY WIRES* SECONDARY WIRES SECONDARY WIRES
COMMON BLACK BLUE 24VAC BLUE 24VAC
SPECIFICATIONS
Frequency 50/60Hz
Operating Temperature -40 to 65C (-40 to 149F)
No Load Voltage 27-28VAC
Hub Style Fits 1/2" electrical k.o.
Wire UL 1015, 18 AWG*
Wire Length 8 inches
*X085AAA, X375DAC have 14AWG, Secondary wires
ORDERING INFORMATION
UL 5085 DIMENSIONS (inches)
MODEL VA PRIMARY VOLTAGE (VAC) SECONDARY CURRENT LIMITING METHOD CLASS MOUNTING SEPARATED UL CE L W H A B
VOLTAGE PRIMARY &
(VAC) SECONDARY WIRES
STANDARD
X020AAA 120 Inherent II, III 1HUB+FT n n 2.3 1.9 2.6 1.59 1.69
X020ACA 277 Inherent II, III 1HUB+FT n n 2.3 1.9 2.6 1.59 1.69
20
X020ADA 24 Inherent General 1HUB+FT n n 2.3 1.9 2.6 1.59 1.69
X020ADB 24 Inherent General 2HUB+FT n n n 2.3 1.9 2.6 1.59 1.69
X040AAA 120 Inherent II, III 1HUB+FT n n 2.7 2.2 2.9 1.98 1.81
24
X040AAB 120 Inherent II, III 2HUB+FT n n n 2.7 2.2 2.9 1.98 1.81
X040ACA 277 Inherent II, III 1HUB+FT n n 2.7 2.2 2.9 1.98 1.81
X040ADA 40 24 Inherent II, III 1HUB+FT n n 2.7 2.2 2.9 1.98 1.81
X040AMB 120/208/240/277 Fuse II, III 2HUB+FT n n n 2.7 2.2 2.9 1.98 1.81
X040BNA 120/208/240 Fuse II, III 1HUB+FT n n 2.7 2.2 2.9 1.98 1.81
X040BPC 24 12/24 Fuse II, III Foot n n n 2.7 2.2 2.9 1.98 1.81
X050BAA 120 Fuse II, III 1HUB+FT n n 2.8 2.2 2.9 2.06 1.81
X050BAB 120 Fuse II, III 2HUB+FT n n n 2.8 2.2 2.9 2.06 1.81
X050BCA 277 Fuse II, III 1HUB+FT n n 2.8 2.2 2.9 2.06 1.81
X050BCB 277 Fuse II, III 2HUB+FT n n n 2.8 2.2 2.9 2.06 1.81
X050BGB 208/240 24 Fuse II, III 2HUB+FT n n n 2.8 2.2 2.9 2.06 1.81
X050CAA 120 Circuit Breaker II, III 1HUB+FT n n 3.5 2.5 3.1 1.91 2.03
X050CBA 120/240/277/480 Circuit Breaker II, III 1HUB+FT n n 3.5 2.5 3.1 1.91 2.03
X050CBB 120/240/277/480 Circuit Breaker II, III 2HUB+FT n n n 3.5 2.5 3.1 1.91 2.03
X050CCA 277 Circuit Breaker II, III 1HUB+FT n n 3.5 2.5 3.1 1.91 2.03
X050CEB 50 208/240/277/480 Circuit Breaker General 2HUB+FT n n n 3.5 2.5 3.1 1.91 2.03
120
X050CEG 208/240/277/480 Circuit Breaker General Plate, 90 Sec Elbow n n n 3.5 4.0 4.0 3.38 3.38
X050CGG 208/240 Circuit Breaker II, III Plate, 90 Sec Elbow n n n 4.0 4.0 4.0 3.38 3.38
X050CHA 120/208/240/480 Circuit Breaker II, III 1HUB+FT n n 3.5 2.5 3.1 1.91 2.03
POWER SOURCES
X050CHB 120/208/240/480 Circuit Breaker II, III 2HUB+FT n n n 3.5 2.5 3.1 1.91 2.03
X050CNA 120/208/240 Circuit Breaker II, III 1HUB+FT n n 3.5 2.5 3.1 1.91 2.03
X050CNB 120/208/240 Circuit Breaker II, III 2HUB+FT n n n 3.5 2.5 3.1 1.91 2.03
X050COA 120/208/240/277/480 Circuit Breaker II, III 1HUB+FT n n 3.5 2.5 3.1 1.91 2.03
X050COB 120/208/240/277/480 Circuit Breaker II, III 2HUB+FT n n n 4.3 2.5 3.1 2.70 2.00
X050DLB 220 None II, III 2HUB+FT n n n 2.8 2.2 2.9 2.06 1.81
X075CAA 120 Circuit Breaker II, III 1HUB+FT n n 3.9 2.5 3.1 2.31 2.03
X075CAB 120 Circuit Breaker II, III 2HUB+FT n n n 3.9 2.5 3.1 2.31 2.03
X075CBA 120/240/277/480 24 Circuit Breaker II, III 1HUB+FT n n 3.9 2.5 3.1 2.31 2.03
75
X075CCA 277 Circuit Breaker II, III 1HUB+FT n n 3.9 2.5 3.1 2.31 2.03
X075CHA 120/208/240/480 Circuit Breaker II, III 1HUB+FT n n 3.9 2.5 3.1 2.31 2.03
X075CHD 120/208/240/480 Circuit Breaker II, III 1HUB+FT n n 3.9 2.5 3.1 2.31 2.03
X085AAA 85 120 Inherent General 1HUB+FT n n 3.2 3.8 3.2 2.2 3.14
X100CAA 120 Circuit Breaker II, III 1HUB+FT n n 4.1 2.5 3.1 2.51 2.03
X100CAB 120 Circuit Breaker II, III 2HUB+FT n n n 4.1 2.5 3.1 2.51 2.03
X100CBA 120/240/277/480 Circuit Breaker II, III 1HUB+FT n n 4.3 2.5 3.1 2.70 2.03
X100CBB 120/240/277/480 Circuit Breaker II, III 2HUB+FT n n n 4.3 2.5 3.1 2.70 2.03
99
X100CBE 120/208/277/480 Circuit Breaker II, III Plate n n 4.3 4.0 4.0 3.38 3.38
X100CHB 120/208/240/480 Circuit Breaker II, III 2HUB+FT n n n 4.3 2.5 3.1 2.70 2.03
X100CKB 480 120 Circuit Breaker General 2HUB+FT n n n 4.1 2.5 3.1 2.51 2.03
X100CLB 220 Circuit Breaker II, III 2HUB+FT n n n 4.1 2.5 3.1 2.51 2.03
X150CAA 150 120 Circuit Breaker General 1HUB+FT n n 3.5 3.8 3.2 2.08 3.26
X175BAB 120 Fuse General 2HUB+FT n n n 4.1 3.8 3.2 3.19 3.14
X175BLB 220 Fuse General Foot n n n 3.8 3.8 3.2 3.05 3.14
X175CAB 175 120 24 Circuit Breaker General 2HUB+FT n n n 4.1 3.8 3.2 3.19 3.14
X175CLB 220 Circuit Breaker General Foot n n n 3.8 3.8 3.2 3.05 3.14
X175DGC 208/240 None General Foot n n n 4.1 3.8 3.2 3.19 3.14
X240DAA 240 120 None General 1HUB+FT n n n 3.7 3.8 4.5 3.24 3.18
X375DAC 375 120 None General Foot n n n 4.3 3.8 4.5 3.83 3.18
CENTER TAP
X020APC 24 Inherent II, III Foot n n n 2.3 1.9 2.6 1.59 1.69
20
X020AQC 120/208/240 Inherent II, III Foot n n n 2.3 1.9 2.6 1.59 1.69
X040BPC 24 Fuse II, III Foot n n n 2.7 2.2 2.9 1.98 1.81
40 12/24
X040BQC 120/208/240 Fuse II, III Foot n n n 2.7 2.2 2.9 1.98 1.81
X050CIA 50 120 Circuit Breaker II, III 1HUB+FT n n n 2.8 2.2 2.9 2.06 1.81
X100CRC Circuit Breaker II, III 1HUB+FT n n n 4.3 2.5 3.1 2.70 2.03
100 120/240
X100CSC 16/32 Circuit Breaker II, III 1HUB+FT n n n 4.3 2.5 3.1 2.70 2.00
HQ0001823.B 04121
SURGE PROTECTION & POWER SOURCES
5YearWarranty
Control Transformers
X020AAA Veris X Series Control Transformers are a convenient Versatile UL Listed transformers...simplify
source of control power for HVAC control and building product selection and installation
automation applications. A wide variety of UL-listed UL Listings for all models simplify panel building
transformers are available with single and dual requirements
threaded hub mounting options. Multiple current Threaded hub options maximize installation
limiting options are available, including a circuit flexibility
breaker in some models. Save ordering time and One stop shopping...save time by ordering along
purchase order costs when buying other Veris sensors with other Veris products
by including transformers in your order.
1 Hub and Foot Mount
APPLICATIONS
Controller power
X050BAB
Switching relays and other digital I/O circuits
Powering sensors
DIMENSIONAL DRAWINGS
L * See ordering table
for dimensions.
2 Hub and Foot Mount W A
X100CBE
H B
WIRE COLORS
STANDARD CENTER TAP
Plate Mount PRIMARY WIRES* SECONDARY WIRES SECONDARY WIRES
COMMON BLACK BLUE 24VAC BLUE 24VAC
X075CBA
SPECIFICATIONS
Frequency 50/60 Hz
Operating Temperature -40 to 65C (-40 to 149F)
No Load Voltage 27 to 28VAC
Hub Style Fits 1/2" electrical k.o.
Wire UL 1015, 18 AWG*
1 Hub and Foot Mount with Separated Secondary Wires Wire Length 8 inches
*X085AAA, X375DAC have 14AWG, Secondary wires
ORDERING INFORMATION
DIMENSIONS (inches)
MODEL # MODEL # VA PRIMARY VOLTAGE SECONDARY CURRENT CLASS MOUNTING SEPARATED UL CE SPECIAL L W H A B
TAC VERIS (VAC)
WHITE VOLTAGE LIMITING PRIMARY & ORDER
(VAC) METHOD SECONDARY WIRES ONLY *
STANDARD
T-255-120 120 Inherent II, III 1HUB+FT n n 2.3 1.9 2.6 1.59 1.69
T-255-277 277 Inherent II, III 1HUB+FT n n 2.3 1.9 2.6 1.59 1.69
20
T-255-24 24 Inherent General 1HUB+FT n n 2.3 1.9 2.6 1.59 1.69
X020ADB 24 Inherent General 2HUB+FT n n n 2.3 1.9 2.6 1.59 1.69
X040AAA 120 Inherent II, III 1HUB+FT n n 2.7 2.2 2.9 1.98 1.81
X040AAB 120 Inherent II, III 2HUB+FT n n n 2.7 2.2 2.9 1.98 1.81
X040ACA 277 Inherent II, III 1HUB+FT n n n 2.7 2.2 2.9 1.98 1.81
40
X040ADA 24 Inherent II, III 1HUB+FT n n 2.7 2.2 2.9 1.98 1.81
X040AMB 120/208/240/277 Fuse II, III 2HUB+FT n n n n 2.7 2.2 2.9 1.98 1.81
X040BNA 120/208/240 24 Fuse II, III 1HUB+FT n n n 2.7 2.2 2.9 1.98 1.81
T-201-1 120 Fuse II, III 1HUB+FT n n 2.8 2.2 2.9 2.06 1.81
X050BAB 120 Fuse II, III 2HUB+FT n n n 2.8 2.2 2.9 2.06 1.81
T-240 277 Fuse II, III 1HUB+FT n n 2.8 2.2 2.9 2.06 1.81
X050BCB 277 Fuse II, III 2HUB+FT n n n 2.8 2.2 2.9 2.06 1.81
T-258 208/240 Fuse II, III 2HUB+FT n n n n 2.8 2.2 2.9 2.06 1.81
X050CAA 120 Circuit Breaker II, III 1HUB+FT n n 3.5 2.5 3.1 1.91 2.03
X050CBA 120/240/277/480 Circuit Breaker II, III 1HUB+FT n n 3.5 2.5 3.1 1.91 2.03
T-245 120/240/277/480 Circuit Breaker II, III 2HUB+FT n n n 3.5 2.5 3.1 1.91 2.03
X050CCA 277 Circuit Breaker II, III 1HUB+FT n n n 3.5 2.5 3.1 1.91 2.03
50
X050CEB 208/240/277/480 Circuit Breaker General 2HUB+FT n n n n 3.5 2.5 3.1 1.91 2.03
120
T-249 208/240/277/480 Circuit Breaker General Plate, 90 Sec n n n n 3.5 4.0 4.0 3.38 3.38
X050CGG 208/240 Circuit Breaker II, III Plate, 90 Sec n n n n 4.0 4.0 4.0 3.38 3.38
X050CHA 120/208/240/480 Circuit Breaker II, III 1HUB+FT n n n 3.5 2.5 3.1 1.91 2.03
X050CHB 120/208/240/480 Circuit Breaker II, III 2HUB+FT n n n n 3.5 2.5 3.1 1.91 2.03
X050CNA 120/208/240 Circuit Breaker II, III 1HUB+FT n n n 3.5 2.5 3.1 1.91 2.03
X050CNB 120/208/240 Circuit Breaker II, III 2HUB+FT n n n n 3.5 2.5 3.1 1.91 2.03
X050COA 120/208/240/277/480 Circuit Breaker II, III 1HUB+FT n n n 3.5 2.5 3.1 1.91 2.03
X050DLB 220 None II, III 2HUB+FT n n n n 2.8 2.2 2.9 2.06 1.81
T-207 120 Circuit Breaker II, III 1HUB+FT n n 3.9 2.5 3.1 2.31 2.03
X075CAB 120 Circuit Breaker II, III 2HUB+FT n n n 3.9 2.5 3.1 2.31 2.03
X075CBA 75 120/208/240/480 24 Circuit Breaker II, III 1HUB+FT n n n 3.9 2.5 3.1 2.31 2.03
X075CCA 277 Circuit Breaker II, III 1HUB+FT n n 3.9 2.5 3.1 2.31 2.03
X075CHA 120/208/240/480 Circuit Breaker II, III 1HUB+FT n n n 3.9 2.5 3.1 2.31 2.03
T-202 85 120 Inherent General 1HUB+FT n n 3.2 3.8 3.2 2.2 3.14
T-208 120 Circuit Breaker II, III 1HUB+FT n n 4.1 2.5 3.1 2.51 2.03
X100CAB 120 Circuit Breaker II, III 2HUB+FT n n n 4.1 2.5 3.1 2.51 2.03
X100CBA 120/240/277/480 Circuit Breaker II, III 1HUB+FT n n 4.3 2.5 3.1 2.70 2.03
X100CBB 120/240/277/480 Circuit Breaker II, III 2HUB+FT n n n 4.3 2.5 3.1 2.70 2.03
99
X100CBE 120/208/277/480 Circuit Breaker II, III Plate n n n 4.3 4.0 4.0 3.38 3.38
X100CHB 120/208/240/480 Circuit Breaker II, III 2HUB+FT n n n n 4.3 2.5 3.1 2.70 2.03
X100CKB 480 120 Circuit Breaker General 2HUB+FT n n n n 4.1 2.5 3.1 2.51 2.03
X100CLB 220 Circuit Breaker II, III 2HUB+FT n n n n 4.1 2.5 3.1 2.51 2.03
X150CAA 150 120 Circuit Breaker General 1HUB+FT n n 3.5 3.8 3.2 2.08 3.26
T-203 120 Fuse General 2HUB+FT n n n 4.1 3.8 3.2 3.19 3.14
X175CLB 175 220 24 Fuse General Foot n n n n 3.8 3.8 3.2 3.05 3.14
T-223 208/240 None General Foot n n n 4.1 3.8 3.2 3.19 3.14
T-204 240 120 None General 1HUB+FT n n n 3.7 3.8 4.5 3.24 3.18
T-205 375 120 None General Foot n n n 4.3 3.8 4.5 3.83 3.18
CENTER TAP
X020APC 24 Inherent II, III Foot n n n n 2.3 1.9 2.6 1.59 1.69
20
X020AQC 120/208/240 Inherent II, III Foot n n n n 2.3 1.9 2.6 1.59 1.69
X040BPC 24 Fuse II, III Foot n n n n 2.7 2.2 2.9 1.98 1.81
40 12/24
X040BQC 120/208/240 Fuse II, III Foot n n n n 2.7 2.2 2.9 1.98 1.81
X050CIA 50 120 Circuit Breaker II, III 1HUB+FT n n n n 2.8 2.2 2.9 2.06 1.81
X100CRC 100 120/240 Circuit Breaker II, III 1HUB+FT n n n n 4.3 2.5 3.1 2.70 2.03
* Special orders are not kept in stock, and may require some additional lead time. Call the factory for more details.
1/4 to1/2
min. min. 1/4 to 1/2
3-5/1 [6-12] 3/4
[80] 6 [20] [6-12]
min 3/4
[20]
min 3-5/16
[84]
ZDB-TF
min 3-5/16
[84]
ZDB-TF
139
Installation Instructions
Mechanical Installation
Mechanical Operation
The actuator is mounted directly to a damper shaft up to 1/2 in diameter by means
of its universal clamp. A crank arm and several mounting brackets are available for
applications where the actuator cannot be direct coupled to the damper shaft. min 3-5/16
[84]
The TF series actuators provide true spring return operation for reliable fail-safe
application and positive close-off on air tight dampers. The spring return system
provides consistent torque to the damper with, and without, power applied to the
actuator.
The TF series provides 95 of rotation and is provided with a graduated position
indicator showing 0 to 95.
The TF-S versions are provided with 1 built-in auxiliary switch. This SPDT switch
is provided for safety interfacing or signaling, for example, for fan start-up. The
switching function is adjustable between 0 and 95.
7. Mount the spring return actuator to the shaft. Tighten the universal clamp,
finger tight only.
8. Mount the anti-rotation strap at the base of the actuator. Do not tighten the
screws.
9. Remove the screw from one end of the mounting bracket and pivot it away from
the actuator.
10. Loosen the universal clamp and, making sure not to move the damper shaft,
rotate the actuator approximately 5 in the direction which would open the
damper.
11. Tighten the universal clamp to the shaft.
12. Rotate the actuator to apply pressure to the damper seals (b) and re-engage the
anti-rotation strap (c).
13. Tighten all fasteners.
140
Installation Instructions
Mechanical Installation
141
Installation Instructions
Mechanical Installation
Initialization of the TF24-SR (-S) US The TF actuators are provided with an adjustable stop to limit the rotation of the
actuator. This function works in conjunction with the universal clamp or the optional
When power is applied, the internal microprocessor recognizes that the actua- position indicator. The adjustable stop is needed when rotation of less than 95 is
tor is at its full fail-safe position and uses this position as the base for all of its required. The TF actuator can be indefinitely stalled, in any position, without harming
position calculations. This procedure takes approximately 15 seconds. During the actuator.
this time you will see no response at the actuator. The microprocessor will re-
tain the initialized zero during short power failures of up to 25 seconds. When
power is applied during this period, the actuator will return to normal operation
and proceed to the position corresponding to the input signal provided. For
power failures over 25 seconds, the actuator will be at its fail-safe position and
will go through the start up initialization again.
The TF, On/Off actuators are electronically protected against overload. The TF, 1. Loosen the end stop fastening screw using a #2 Phillips screwdriver.
On/Off actuator have an internal current limiter which maintains the current 2. Move the stop block so the bottom edge of the block lines up with the number
at a safe level which will not damage the actuator while providing adequate corresponding to the desired degrees of rotation. (example: 45 degrees of rotation
holding torque. = .5)
3. Lock the block in place with the fastening screw.
The TF24, modulating, actuators (TF24-SR (-S) US, TF24-3 US) are protected
4. Check the actuator for proper rotation.
against overload by digital technology located in the ASIC. The ASIC circuitry
constantly monitors the rotation of the brushless DC motor inside the actuator
and stops the pulsing to the motor when it senses a stall condition. The motor Using the IND-TF Position Indicator with Adjustable Stop
remains energized and produces full rated torque during stall conditions. The NOTE: preferred method if short shaft mounting is used.
actuator will try to move in the direction of the stall every 2 minutes, for a
period of 32 minutes. After this, the actuator will try again every 2 hours. 1. With the actuator in its fail-safe position, place the IND-TF Position Indicator so that
it points to the 0 degree position.
2. Loosen the end stop fastening screw using a #2 Phillips screwdriver.
3. Move the stop block so the bottom edge of the block lines up with the number
corresponding to the desired degrees of rotation (example: 45 degrees of rotation =
.5).
4. Lock the block in place with the fastening screw.
M40024 - 05/10 - Subject to change. Belimo Aircontrols (USA), Inc.
142
Installation Instructions
Mechanical Installation
Switch Rating
Voltage Resistive load Inductive load
250 VAC 3A 0.5 A
3.15"
[81]
1.59"
S 8
SH8 [40.5]
[19.5] [18]
0.77" 0.71"
KG6
G66
0.43"
[11]
0.43"
[11]
143
Installation Instructions
General Wiring
WARNING The wiring technician must be trained and experienced with electronic Wire Length for TF... Actuators
circuits. Disconnect power supply before attempting any wiring connections or
changes. Make all connections in accordance with wiring diagrams and follow all Keep power wire runs below the lengths listed in the table in Figure A. If more than
applicable local and national codes. Provide disconnect and overload protection as one actuator is powered from the same wire run, divide the allowable wire length by
required. Use copper, twisted pair, conductors only. If using electrical conduit, the the number of actuators to determine the maximum run to any single actuator.
attachment to the actuator must be made with flexible conduit. Example for TF24-SR US: 3 actuators, 16 Ga wire
550 Ft 3 Actuators = 183 Ft. Maximum wire run
Always read the controller manufacturer's installation literature carefully be-
fore making any connections. Follow all instructions in this literature. If you have TF24(-S) US / TF120(-S) US Maximum Wire Length
any questions, contact the controller manufacturer and/or Belimo. Wire Size Max. Feet. Wire Size Max. Feet
12 Ga 1300 Ft. 18 Ga 575 Ft.
14 Ga 1175 Ft. 20 Ga 300 Ft.
Transformers 16 Ga 900 Ft. 22 Ga 150 Ft.
The TF24 . . actuator requires a 24 VAC class 2 transformer and draws a maximum of
5 VA per actuator. The actuator enclosure cannot be opened in the field, there are no TF24-3(-S) US Maximum Wire Length
parts or components to be replaced or repaired. Wire Size Max. Feet. Wire Size Max. Feet
16 Ga 1125 Ft. 20 Ga 400 Ft.
EMC directive: 89/336/EEC
18 Ga 725 Ft. 22 Ga 200 Ft.
Software class A: Mode of operation type 1
Low voltage directive: 73/23/EEC
TF24-SR(-S) US Maximum Wire Length
CAUTION It is good practice to power electronic or digital controllers from a separate Wire Size Max. Feet. Wire Size Max. Feet
power transformer than that used for actuators or other end devices. The power 12 Ga 1800 Ft. 18 Ga 450 Ft.
supply design in our actuators and other end devices use half wave rectification. 14 Ga 1100 Ft. 20 Ga 275 Ft.
Some controllers use full wave rectification. When these two different types of 16 Ga 700 Ft. 22 Ga 125 Ft.
power supplies are connected to the same power transformer and the DC commons FIGURE A
are connected together, a short circuit is created across one of the diodes in the full
wave power supply, damaging the controller. Only use a single power transformer to
power the controller and actuator if you know the controller power supply uses half
Wire Type and Wire Installation Tips
wave rectification.
For most installations, 18 or 16 Ga. cable works well with the TF24 actuators.
Use code-approved wire nuts, terminal strips or solderless connectors where wires
Multiple Actuators, One Transformer are joined. It is good practice to run control wires unspliced from the actuator to
Multiple actuators may be powered from one transformer provided the following the controller. If splices are unavoidable, make sure the splice can be reached for
rules are followed: possible maintenance. Tape and/or wire-tie the splice to reduce the possibility of the
1. The TOTAL current draw of the actuators (VA rating) is less than or equal to the splice being inadvertently pulled apart.
rating of the transformer. The TF24 proportional actuators have a digital circuit that is designed to ignore
2. Polarity on the secondary of the transformer is strictly followed. This means that all most unwanted input signals (pickup). In some situations the pickup may be severe
No. 1 wires from all actuators are connected to the common leg on the transformer enough to cause erratic running of the actuator. For example, a large inductive load
and all No 2 wires from all actuators are connected to the hotleg. Mixing wire No. (high voltage AC wires, motors, etc.) running near the power or control wiring may
M40024 - 05/10 - Subject to change. Belimo Aircontrols (USA), Inc.
1 & 2 on one leg of the transformer will result in erratic operation or failure of the cause excessive pickup. To solve this problem, make one or more of the following
actuator and/or controls. changes:
1. Run the wire in metallic conduit.
2. Re-route the wiring away from the source of pickup.
Multiple Actuators, Multiple Transformers 3. Use shielded wire (Belden 8760 or equal). Ground the shield to an earth ground.
Multiple actuators positioned by the same control signal may be powered from Do not connect it to the actuator common.
multiple transformers provided the following rules are followed:
1. The transformers are properly sized. Brushless DC Motor Operation
2. All No. 1 wires from all actuators are tied together and tied to the negative leg of
the control signal. See wiring diagram. Belimo's brushless DC motor spins by reversing the poles of stationary electromag-
nets housed inside rotating permanent magnets. The electromagnetic poles are
switched by a microprocessor and a special ASIC (Application Specific Integrated Cir-
cuit) developed by Belimo. Unlike the conventional DC motor, there are no brushes to
wear or commutators to foul.
144
Startup and Checkout
Instructions For TF24-SR(-S) US
145
TFB24-SR(-S), TFX24-SR(-S)
Proportional, Spring Return, 24 V, for 2 to 10 VDC or 4 to 20 mA Control Signal
Application
For proportional modulation of dampers in HVAC systems. Actuator sizing should be
done in accordance with the damper manufacturers specifications.
The actuator is mounted directly to a damper shaft from 1/4 up to 1/2 in diameter
by means of its universal clamp, 1/2 shaft centered at delivery. A crank arm and
several mounting brackets are available for applications where the actuator cannot be
direct coupled to the damper shaft.
The actuator operates in response to a 2 to 10 VDC, or with the addition of a 500
resistor, a 4 to 20 mA control input from an electronic controller or positioner.
Operation
The TF series actuators provide true spring return operation for reliable fail-safe
application and positive close-off on air tight dampers. The spring return system
provides consistent torque to the damper with, and without, power applied to the
actuator.
The TF series provides 95 of rotation and is provided with a graduated position
indicator showing 0 to 95.
The TF uses a brushless DC motor which is controlled by an Application Specific
Technical Data TFB24-SR(-S), TFX24-SR(-S)
Integrated Circuit (ASIC) and a microprocessor. The microprocessor provides the
Power supply 24 VAC 20% 50/60 Hz intelligence to the ASIC to provide a constant rotation rate and to know the actuators
24 VDC 10% exact fail-safe position. The ASIC monitors and controls the brushless DC motors
Power consumption running 2 W rotation and provides a digital rotation sensing function to prevent damage to the
holding 1 W actuator in a stall condition. The actuator may be stalled anywhere in its normal
Transformer sizing 4 VA (class 2 power source) rotation without the need of mechanical end switches. Power consumption is reduced
Electrical connection in holding mode.
TFB... 3 ft, 18 GA plenum cable, 1/2 conduit connector
The TF-S version is provided with one built-in auxiliary switch. This SPDT switch is
-S models: two 3 ft, 18 gauge appliance cables
provided for safety interfacing or signaling, for example, for fan start-up. The switching
with 1/2" conduit connectors
function is adjustable between 0 and 95. The auxiliary switch in the TF-S is double
TFX 3 ft [1m], 10 ft [3m], or 16 ft [5m], 18 GA
insulated so an electrical ground in not necessary.
appliance or plenum cable, with or without 1/2
conduit connector
-S models: two 3 ft [1m], 10 ft [3m] or 16 ft
[5m] appliance cables with or without 1/2" SAFETY NOTE
conduit connectors Screw a conduit fitting into the actuators bushing. Jacket the actuators input and
Overload protection electronic throughout 0 to 95 rotation output wiring with suitable flexible conduit. Properly terminate the conduit in a
Operating range Y 2 to 10 VDC, 4 to 20mA suitable junction box.
D096
Torque 22 in-lbs [2.5 Nm]
0.68" [16.7]
2.40"
[61]
[5.2]
3.0"
0.2"
TFB24-SR-S, TFX24-SR-S
Auxiliary switch 1 x SPDT 3A (0.5A) @ 250 VAC, UL approved
adjustable 0 to 95 (double insulated)
800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA / CARIBBEAN
173
TFB24-SR(-S), TFX24-SR(-S)
Proportional, Spring Return, 24 V, for 2 to 10 VDC or 4 to 20 mA Control Signal
Accessories
W1228
24 VAC Transformer 6
Tool-06 8mm and 10 mm wrench
KH-TF Crank arm for up to 1/2 round shaft Blk (1) Common
Line
ZG-TF2 Crank arm adaptor kit for TF Volts 3
Red (2) + Hot
ZG-TF112 Mounting bracket, kit for TF
Wht (3) Y1 Input, 2 to 10V
ZS-100 Weather shield (metal) Control Signal ()
ZS-150 Weather shield (polycarbonate) 2 to 10 VDC (+)
NOTE: When using TFB24-SR (-S), TFX24-SR (-S) actuators, only use accessories listed on this page. Org (5) U Output, 2 to 10V
2 to 10 VDC ()
For actuator wiring information and diagrams, refer to Belimo wiring guide.
Feedback Signal (+)
2
Typical Specification
Spring return control damper actuators shall be direct coupled type which require
no crank arm and linkage and be capable of direct mounting to a shaft up to a 1/2 2 to 10 VDC control of TFX24-SR(-S)
diameter and center a 1/2 shaft. The actuator must provide proportional damper
control in response to a 2 to 10 VDC or, with the addition of a 500 resistor, a 4 to
20 mA control input from an electronic controller or positioner.The actuators must be
designed so that they may be used for either clockwise or counterclockwise fail-safe
operation. Actuators shall use a brushless DC motor controlled by a microprocessor
and be protected from overload at all angles of rotation. Run time shall be constant,
and independent of torque. If required, one SPDT auxiliary switch shall be provided
having the capability of being adjustable. Actuators with auxiliary switch must be
constructed to meet the requirements for Double Insulation so an electrical ground is
not required to meet agency listings. Actuators shall be cULus listed certified, have a Org (5) U Output, 2 to 10V
5 year warranty, and be manufactured under ISO 9001 International Quality Control
Standards. Actuators shall be as manufactured by Belimo.
Wiring Diagrams
W1222
2
Up to 4 actuators may be connected in parallel. With 4 actuators wired to
one 500 resistor, a +2% shift of control signal may be required. Power
consumption must be observed.
Actuators with plenum rated cable do not have numbers on wires; use
6 color codes instead.
For end position indication, interlock control, fan startup, etc., TFB24-SR-S,
7 TFX24-SR-S incorporates one built-in auxiliary switch: 1 x SPDT, 3A
(0.5A ) @250 VAC, UL Approved, adjustable 0 to 95. Auxiliary switch of TFB24-SR-S, TFX24-SR-S
WARNING
G Live Electrical Components!
During installation, testing, servicing and troubleshooting of this product, it may be
necessary to work with live electrical components. Have a qualified licensed electrician or other
individual who has been properly trained in handling live electrical components perform these
tasks. Failure to follow all electrical safety precautions when exposed to live electrical compo-
nents could result in death or serious injury.
174