Primary Fuses
Introduction
and power fuses. These devices are found on nearly
The wide variety of fuse links offered by the A.B. all systems and their coordination must be treated
Chance Company is instrumental in reducing the in a manner similar to that which will be discussed
many problems facing todays coordination engineers. for fuse links.
Besides the increasingly popular ANSI K and T fuse
links, there is available a series of precision engi-
neered fuse links designed especially for transformer
The Fuse Link as a Protective Device
protection.
The fuse link may be considered as the electrical weak
The up to date design and construction plus rigid
element in the distribution system. This so-called
quality control of Chance fuse links assures the
weak element is purposely introduced into the system
coordination engineer of dependable electrical and
to prevent any damage to the lines and equipment
mechanical fuse link operation. In nearly all cases
which make up the distribution network. Whenever
regardless of the application or coordination problem
an overload or fault current passes through a section
there is a Chance fuse link to fill the need.
of line or a piece of equipment the fuse link which is
the weakest element electrically must melt in time to
open the circuit and prevent damage to the line or
Scope equipment. The relationship of the magnitude current
To more clearly understand why Chance fuse links passing through the link to the time required for the
are the answer to your every day fusing problems let link to melt is referred to as the minimum melting time
us take a closer look at what is expected of a fuse link current characteristic of the fuse link, Figure 1. The
as a protective device. The following discussion of fuse relationship of the magnitude of the current passing
link application and coordination will be limited to through the link to the time required for the link to
fuse links only. However, in actual practice the util- melt and the arc to be extinguished is referred to as
ity engineer must take into consideration substation the total clearing time-current characteristics of the
breakers and relay settings, reclosers, sectionalizers, fuse link, Figure 1.
www.hubbellpowersystems.com
210 N. Allen Centralia, Mo 65240 Phone: 573-682-5521 Fax: 573-682-8714 E-mail: hpsliterature@hps.hubbell.com
Figure 2
MECHANICAL APPLICATION OF 5 KVA 7.2 kV 25 KVA 7.2 kV
TRANSFORMER TRANSFORMER
FUSE LINKS IN CUTOUTS
The first step in the application of fuse links is to
determine the type of cutout in which the fuse link 6 AMP K OR 12 AMP K OR
0.7 AMP 3.5 AMP 2400
is to be used, and thereby establish the fuse link AMPS 80 AMP K
SLOFAST SLOFAST
construction required. For example, most open type S.C. OR
and enclosed type cutouts are designed to use the 40 AMP T
20 inch minimum length universal type fuse links. 2000 amps s.c. SECTIONALIZING
Most 18 and 23 kV cutouts and even some 15 kV 10 AMP K OR OR PROTECTED
6 AMP K OR
cutouts require fuse links longer than the 20 inch 2.1 AMP FUSE
14 AMP
length. Open link type cutouts require an open link SLOFAST SLOFAST
type fuse link specifically designed for the purpose.
Special cutouts may impose additional mechanical
requirements on the fuse links. Because of the adapt- 15 KVA 7.2 kV 10 KVA 7.2 kV
ability of the fuse links offered by the A. B. Chance TRANSFORMER TRANSFORMER
Company these requirements can be met in nearly all
Figure 3
cases regardless of the cutout in use. Where problems
exist on mechanical applications not readily solved Transformer Fusing
consult your Chance representative.
Using the information given in Figure 3, let us de-
termine the fuse link required for each transformer.
ELECTRICAL APPLICATION FUSE LINKS Assume the utility has standardized on the ANSI type
K fuse links for reasons of economy and supply. The
The following factors are pertinent to the proper ap-
5 KVA 7.2 kV transformer has a full load current
plication of fuse links on a distribution system:
rating of approximately 0.7 amperes. Any 1 ampere
1. Safe loading characteristics of equipment to be fuse link will carry the full load current of this trans-
protected. former without melting. However, consideration must
2. In the case of transformer fuses, the degree of be given to the time current characteristics of the 1
overcurrent protection to be provided. ampere fuse link compared with the overload capac-
ity of this transformer. The ANSI overcurrent curve
3. Load current at the point of application.
for this distribution transformer is shown in Figure
4. The fault current available at various locations on
the system.
1 6
5. Time current characteristics of fuse links to be AMP AMP
K K
used on the system.
6. The type of protection to be provided by the fuse
link.
A typical lateral of a distribution system is shown in ANSI/IEEE OVERCURRENT
CURVE FOR A 5 KVA 7.2 KV
Figure 3. The information given in Figure 3 covers DISTRIBUTION TRANSFORMER
most of the factors listed above. Providing that no
secondary fuses are used, the fuse links located at
TIME IN SECONDS
of the transformer but a large portion of this capac-
6 12 20 ity is sacrificed. Also, protection is lost against low
AMP AMP AMP
K K K overcurrents of long duration.
It can be seen from the preceding discussion that
the conventional type K fuse link leaves much to
be desired in the way of transformer protection. Let
us consider the steps possible to provide more ideal
transformer protection where such protection is con-
sidered essential. There have been for many years fuse
links available with dual time current characteris-
TIME IN SECONDS
the 25 KVA transformer. The use of this 12 ampere ANSI CURVE AND SLOFAST TOTAL CLEARING CURVE
K fuse link utilizes some of the overcurrent capacity Figure 6
Coordination of Sectionalizing Fuses SUB STA-
TION
In selecting a fuse link for use at a sectionalizing
point, we must give consideration to coordination,
25 KVA 7.2 KV
that is the cooperation of one fuse link with another TRANSFORMER
to limit outages to the smallest possible section of the 80 AMP T
distribution system. PROTECTED
FUSE
When coordination is being considered, the section-
3.5 AMP
alizing fuse link shown in Figure 3 is referred to as SLOFAST
the protected fuse, whereas the fuse links located 2400 AMPS. S.C
at the transformers are referred to as protecting
fuses. These two terms, protected and protecting 40 AMP T
are used to indicate that one fuse link, the protect- 14 AMP PROTECTING
SLOFAST FUSE
ing, operates and clears the circuit before the other,
the protected, is damaged. In order to provide the
necessary coordination between these fuse links we
must refer to the fuse link time current characteristic 100 KVA 7.2 KV
curves. Using these curves, we first determine the TRANSFORMER
maximum total time required by the protecting fuse
Figure 7
link to clear the maximum short circuit fault current
which is available at the point of its application. The link will, therefore, meet the necessary coordination
proper protected fuse must carry the full load current requirements.
and have a minimum melting time greater than the Where two sectionalizing fuses are in series the one
maximum total clearing time of the protecting fuse farthest from the power source becomes the protecting
at the maximum fault current available at the pro- link and the one nearest the power source becomes
tecting fuse. To provide protection against operating the protected link. In this application the proper pro-
variables, 75% of the minimum melting time of the tected link has to be selected in the same manner as
protected fuse link is often used. Naturally, in deter- in the application where a transformer fuse protects
mining the coordination of the sectionalizing fuse link a sectionalizing fuse. As an example, there are two
with transformer fuse links the largest transformer sectionalizing fuses shown in series in Figure 7. In
fuse link in the section should be considered since it the consideration to select the proper fuse link for the
will place the strictest coordination requirements on point nearest the power source this fuse link becomes
the sectionalizing fuse link. the protected link. It has already been determined that
In Figure 3 it is necessary to determine the sectional- a 40 ampere type T link is required for what has now
izing fuse link required to coordinate with the largest become the protecting link. By reference to the time
fuse link in the branch which in this case is the 3.5 current characteristic curves and the use of the 75%
ampere SloFast fuse link used to protect the 25 KVA operating variable factor it can be determined that the
transformer. The total clearing time curve of the 3.5 protected link should be an 80 ampere type T.
ampere SloFast fuse link indicates that the maximum
time required by this fuse link to clear a 2400 ampere Use of Time Current Characteristic Curves
fault is .0134 seconds. The proper sectionalizing fuse
link, therefore, must be capable of carrying 2400 and Coordination Tables
amperes for .0134 seconds without being damaged. Since time current characteristic curves are usually
The ANSI type T fuse links have been selected for our printed on transparent paper, it is possible to overlay
sectionalizing fuse because of their slow time current the total clearing time characteristic curve with the
characteristics. The minimum melting time curves minimum melting time characteristic curve or vice
of the type T fuse links indicate that the minimum versa. The minimum melting curve can be shifted
melting time of a 40 ampere T link at 2400 amperes downward by 25% with respect to the total clearing
is .0185 Sec. As previously stated, to allow for oper- time curve. This shift, since the curves are printed on
ating variables, 75% of this minimum melting time log-log paper, automatically provides for 75% of the
is used, or .0139 seconds. The 40 ampere T fuse minimum melting time to be used in coordination.
Solder junction
Heater coil Fuse wire
Heat absorber
Strain wire
TABLE 1
COORDINATION CHART
for
CHANCE TYPE K (FAST) ANSI FUSE LINKS
6 170 320 490 620 840 1000 1300 1600 2250 2650 3450 5800 9400
8 190 400 620 840 1000 1300 1600 2250 2650 3450 5800 9400
10 250 480 840 1000 1300 1600 2250 2650 3450 5800 9400
12 310 700 1000 1300 1600 2250 2650 3450 5800 9400
15 440 750 1300 1600 2250 2650 3450 5800 9400
20 480 1000 1600 2250 2650 3450 5800 9400
Above Coordination Chart based on maximum total clearing time of the protecting link and the minimum melting time of the protected
link.
TABLE 2
COORDINATION CHART
for
CHANCE TYPE T (SLOW) ANSI FUSE LINKS
6 340 690 920 1150 1500 1900 2490 3000 3900 4800 6200 9500 15000
8 400 850 1150 1500 1900 2490 3000 3900 4800 6200 9500 15000
10 480 990 1500 1900 2490 3000 3900 4800 6200 9500 15000
12 550 1190 1900 2490 3000 3900 4800 6200 9500 15000
15 670 1500 2490 3000 3900 4800 6200 9500 15000
20 890 2000 3000 3900 4800 6200 9500 15000
TABLE 3
COORDINATION CHART
for
CHANCE MS FUSE LINKS
Protected Type MS Fuse Link Ampere Rating
Protecting Type
MS Fuse Link 3 5 7 10 15 20 25 30 40 50 65 80 100 125 150 200
Ampere Rating
Maximum Currents (R.M.S. Amperes) For Safe Co-ordination
3 640 980 1300 1630 2100 2600 3250 4200 5300 6200 8400 10000 10000 10000
5 980 1300 1630 2100 2600 3250 4200 5300 6200 8400 10000 10000 10000
7 850 1600 2100 2600 3250 4200 5300 6200 8400 10000 10000 10000
10 780 1650 2600 3250 4200 5300 6200 8400 10000 10000 10000
15 1000 1900 3250 4200 5300 6200 8400 10000 10000 10000
20 1200 2250 4000 5300 6200 8400 10000 10000 10000
200
Above Coordination Chart based on maximum total clearing time of the protecting link and the minimum melting time of the protected
link.
TABLE 4
COORDINATION CHART
for
CHANCE TYPE SLOFAST FUSE LINKS
Protected Type SloFast Fuse Link Ampere Rating
Protecting Type
SloFast Fuse Link .2 .3 .4 .6 .7 1.0 1.3 1.4 1.6 2.1 3.1 3.5 4.2 5.2 6.3 7.0 7.8 10.4
Ampere Rating Maximum Currents (R.M.S. Amperes) For Safe Co-ordination
.2 35 52 62 65 112 135 143 175 230 325 340 440 530 620 660 820 1060
.3 87 112 120 160 225 325 340 440 530 620 660 820 1060
.4 75 100 110 150 215 325 340 440 530 620 660 820 1060
.6 67 95 104 145 211 325 340 440 530 620 660 820 1060
.7 60 90 100 140 208 325 340 440 530 620 660 820 1060
1.0 90 168 295 315 440 530 620 660 820 1060
1.3 145 275 300 415 530 620 660 820 1060
1.4 130 265 285 405 530 620 660 820 1060
1.6 230 250 380 500 620 660 820 1060
7.0 650
7.8
10.4
Above Coordination Chart based on maximum total clearing time of the protecting link and the minimum melting time of the protected
link.
TABLE 5
COORDINATION CHART
for
CHANCE TYPE SLOFAST AND TYPE K (FAST) ANSI FUSE LINKS
Protected Type K Ampere Rating
Protecting Type
SloFast Fuse Link 3 6 8 10 12 15 20 25 30 40 50 65 80 100 140 200
Ampere Rating
Maximum Currents (R.M.S. Amperes) For Safe Co-ordination
.2 78 165 220 295 370 490 620 840 1000 1300 1600 2250 2650 3450 5800 9400
.3 140 210 295 370 490 620 840 1000 1300 1600 2250 2650 3450 5800 9400
.4 125 195 295 370 490 620 840 1000 1300 1600 2250 2650 3450 5800 9400
.6 190 285 370 490 620 840 1000 1300 1600 2250 2650 3450 5800 9400
.7 190 285 370 490 620 840 1000 1300 1600 2250 2650 3450 5800 9400
1.0 240 350 490 620 840 1000 1300 1600 2250 2650 3450 5800 9400
1.3 320 490 620 840 1000 1300 1600 2250 2650 3450 5800 9400
1.4 320 490 620 840 1000 1300 1600 2250 2650 3450 5800 9400
1.6 440 620 840 1000 1300 1600 2250 2650 3450 5800 9400
2.1 550 840 1000 1300 1600 2250 2650 3450 5800 9400
3.1 700 950 1300 1600 2250 2650 3450 5800 9400
3.5 700 950 1300 1600 2250 2650 3450 5800 9400
Above Coordination Chart based on maximum total clearing time of the protecting link and the minimum melting time of the protected
link.
TABLE 6
COORDINATION CHART
for
CHANCE TYPE SLOFAST AND TYPE T (SLOW) ANSI FUSE LINKS
Protecting Type Protected Type T Fuse Link Ampere Rating
SloFast Fuse Link 3 6 8 10 12 15 20 25 30 40 50 65 80 100 140 200
Ampere Rating
Maximum Currents (R.M.S. Amperes) For Safe Co-ordination
.2 83 285 385 510 690 920 1150 1500 1900 2490 3000 3900 4800 6200 9500 15000
.3 285 385 510 690 920 1150 1500 1900 2490 3000 3900 4800 6200 9500 15000
.4 285 385 510 690 920 1150 1500 1900 2490 3000 3900 4800 6200 9500 15000
.6 275 385 510 690 920 1150 1500 1900 2490 3000 3900 4800 6200 9500 15000
.7 275 385 510 690 920 1150 1500 1900 2490 3000 3900 4800 6200 9500 15000
1.0 370 510 690 920 1150 1500 1900 2490 3000 3900 4800 6200 9500 15000
1.3 510 690 920 1150 1500 1900 2490 3000 3900 4800 6200 9500 15000
1.4 510 690 920 1150 1500 1900 2490 3000 3900 4800 6200 9500 15000
1.6 690 920 1150 1500 1900 2490 3000 3900 4800 6200 9500 15000
2.1 920 1150 1500 1900 2490 3000 3900 4800 6200 9500 15000
3.1 1150 1500 1900 2490 3000 3900 4800 6200 9500 15000
3.5 1150 1500 1900 2490 3000 3900 4800 6200 9500 15000
4.2 1500 1900 2490 3000 3900 4800 6200 9500 15000
5.2 1900 2490 3000 3900 4800 6200 9500 15000
6.3 1800 2490 3000 3900 4800 6200 9500 15000
Above Coordination Chart based on maximum total clearing time of the protecting link and the minimum melting time of the protected
link.
TABLE 7
COORDINATION CHART
for
CHANCE TYPE SLOFAST AND TYPE MS FUSE LINKS
Protected Type MS Fuse Link Ampere Rating
Protecting Type
SloFast Fuse Link 3 5 7 10 15 20 25 30 40 50 65 80 100 125 150 200
Ampere Rating
Maximum Currents (R.M.S. Amperes) For Safe Co-ordination
.2 300 410 650 980 1300 1630 2100 2600 3250 4200 5300 6200 8400 10000 10000 10000
.3 300 410 650 980 1300 1630 2100 2600 3250 4200 5300 6200 8400 10000 10000 10000
.4 300 410 650 980 1300 1630 2100 2600 3250 4200 5300 6200 8400 10000 10000 10000
.6 300 410 650 980 1300 1630 2100 2600 3250 4200 5300 6200 8400 10000 10000 10000
.7 300 410 650 980 1300 1630 2100 2600 3250 4200 5300 6200 8400 10000 10000 10000
1.0 400 650 980 1300 1630 2100 2600 3250 4200 5300 6200 8400 10000 10000 10000
1.3 650 980 1300 1630 2100 2600 3250 4200 5300 6200 8400 10000 10000 10000
1.4 650 980 1300 1630 2100 2600 3250 4200 5300 6200 8400 10000 10000 10000
1.6 650 980 1300 1630 2100 2600 3250 4200 5300 6200 8400 10000 10000 10000
2.1 980 1300 1630 2100 2600 3250 4200 5300 6200 8400 10000 10000 10000
3.1 1300 1630 2100 2600 3250 4200 5300 6200 8400 10000 10000 10000
3.5 1300 1630 2100 2600 3250 4200 5300 6200 8400 10000 10000 10000
4.2 1630 2100 2600 3250 4200 5300 6200 8400 10000 10000 10000
5.2 1500 2100 2600 3250 4200 5300 6200 8400 10000 10000 10000
6.3 2600 3250 4200 5300 6200 8400 10000 10000 10000
7.0 2600 3250 4200 5300 6200 8400 10000 10000 10000
7.8 3250 4200 5300 6200 8400 10000 10000 10000
10.4 3000 4200 5300 6200 8400 10000 10000 10000
Above Coordination Chart based on maximum total clearing time of the protecting link and the minimum melting time
of the protected link.
TABLE 8
ELECTRICAL AND MECHANICAL INTERCHANGEABILITY TABLE
for
EQUIVALENT FUSE LINKS
Chance Type MSA Fuse Links Kearney Type KS and KS-U Fuse Links
Ampere Rating Catalog Number Ampere Rating Catalog Number
10
CONVERSION TO ANSI FUSE LINKS
Advantages of Conversion
Through the joint efforts of users and manufacturers, the ANSI Standards for Distribution Fuse Links were established
to provide the levels of performance and utility necessary to meet modern protective practices and operating conditions.
They serve the two-fold purpose of providing guidance to the manufacturer and assurance to the user that specific elec-
trical requirements are met.
These joint standards, along with existing ANSI standards, set forth characteristics that will allow and provide for the
electrical, as well as mechanical, interchangeability of fuse links. Conversion to ANSI standard fuse links therefore permits
multiple sources of supply for fuse links.
The ANSI standards are prepared so as to still permit the utility engineer to select fuse links using his individual judgment
based on the details of manufacture, use with related equipment and other application factors.
Two Speed Ratios Available
The joint ANSI standards have established two types of fuse links, designated Type K and Type T. The Type K link
commonly called fast has speed ratios of the melting time-current characteristics varying from 6 for the 6-ampere rating
to 8.1 for the 200 ampere rating. Type T (slow) fuse links have speed ratios of the melting time-current characteristic
varying from 10 for the 6-ampere rating to 13 for the 200 ampere rating.
The type of link selected, K or T, is based largely on the time-current characteristics of the fuse link presently used, if
such characteristics meet present day coordination requirements. The more closely the time-current characteristics meet
those of the present fuse links, the easier the conversion.
TIME IN SECONDS
TIME IN SECONDS
Representative minimum and maximum time cur- Representative minimum and maximum curves for
rent characteristic curves for ANSI Type K (fast) ANSI Type T (slow) fuse links.
fuse links.
Converting to EEE-NEMA Links buttonhead, removable buttonhead and/or open link styles
that you would use on your system.
After the type of link, K or T is selected, the following
steps are suggested as a guide to implementing a conver- Construction details such as construction of the fuse ele-
sion program. ment, auxiliary tubes and fuse link cable size and coating
should also be considered along with the quality and per-
1. Select the supplier Considerations in determining formance of the fuse links produced.
which manufacturer or manufacturers from whom you
would purchase fuse links include availability of stocks, In Chance type K fuse links, elements are made of silver
reputation of company service rendered by salesman, and, copper or silver alloy and Type T fuse links are made with
of course, the quality and consistency of performance of a tin fuse element.
the fuse links produced. The purpose of the auxiliary tube is to assist the cutout in
Samples of links should be obtained from all potential the clearing of low fault currents and to protect the fuse
suppliers and should include all physical types solid element from physical damage.
11
TABULATION OF
MINIMUM CLEARING VALUES
TYPE K 10 AMP FUSE LINK
Manufacturer
To actually prepare the composite curve for each size link, For Overload For Short Circuit Pro-
Protection of tection**
the minimum figure at each current rating should be select- Transformers*
ed and plotted for the minimum melting composite curve.
Ampere Rating Ampere Rating Ampere Rating
When plotting the total clearing time curve, the maximum
figure should be selected at each current rating. K or T K T
The composite curves thus obtained will provide a band
3 3 10 6
within which the fuse links of all the selected suppliers 5 12 8
6
will operate. 7 8 20 10 or 12
10 10 25 or 30 15
TABULATION OF 15 15 40 20 or 25
MINIMUM MELTING CURRENT VALUES 20 20 50 25 or 30
25 25 65 30 or 40
TYPE K 10 AMP FUSE LINK 30 80 40
30
Manufacturer
40 40 80 or 100 50
Time Period CHANCE A B C
50 50 100 or 140 65 or 80
in Seconds Current in Amperes 65 65 140 80 or 100
300 19.5 19.5 19.5 20.0 80 80 140 or 200 100
100 20.0 20.0 20.0 21.0 100 100 140 or 200 100 or 140
10 25.0 23.0 24.5 26.0 125 100 or 140 200 140
1 42.5 43.0 43.0 45.0 150 140 200
.1 129.0 130.0 129.0 130.0 200 140 or 200
Figure 6