TECHNICAL DATA
for
LIST OF CONTENT:
TESTS METHODS FOR ALL CABLE COMPONENTS IN THE RFOU, RFXU, BFOU AND BFXU CABLES..........25
INSTALLATION RECOMMENDATIONS............................................................................................................................26
Maximum operating
Conductor temperature : 85OC
Fixed installation for power, control and lighting in safe IEC:60092-3 -Design guidelines
areas, general purposes. IEC:60332-3/A -Flame retardance
IEC:60754-1,2 -Halogen-free properties
IEC:61034-1,2 - Low smoke properties
IEEE:45/383 - Flame retardance
CONSTRUCTION
CODE LETTER
Conductor Tinned, annealed, stranded copper. (1)
Insulation R EP-rubber. (2)
Bedding F Flame retardant halogen-free thermoset compound. (3)
No armour X No armour
Impregnated glass-tape and rubberrized nylontape (4)
Outer sheath U Flame retardant halogen-free thermoset compound. (5)
ELECTRICAL DATA
No. of cores x Conductor resistance Reactance Impedance Continous Short circuit
cross section [/km] at 85 current rating [Ampere]
[/km] [/km] C Ampere
[mm2] at 20 C at 85 C at 60 Hz at 60 Hz at 25 C 1 sec 0,3 sec
INSTALLATION DATA
TYPE Overall Diameter Minimum bending radius Maximum pulling
During Fixed tension
[mm2] [mm] installation installed [N]
(mm) (mm)
Maximum operating
Conductor temperature : 85OC
Fixed installation for power, control and lighting in both EX- IEC:60092-3 - Design guidelines
and safe areas, general purposes. IEC:60332-3/A - Flame retardance
IEC:60754-1,2 - Halogen-free properties
IEC:61034-1,2 - Low smoke properties
IEEE:45/383 - Flame retardance
CONSTRUCTION
CODE LETTER
Conductor Tinned, annealed, stranded copper. (1)
ELECTRICAL DATA
No. of cores x Conductor resistance Reactance Impedance Continous Short circuit
cross section [/km] at 85 current rating [Ampere]
[/km] [/km] C Ampere
[mm2] at 20 C at 85 C at 60 Hz at 60 Hz at 25 C 1 sec 0,3 sec
INSTALLATION DATA
TYPE Overall Diameter Minimum bending radius Maximum pulling
During Fixed tension
[mm2] [mm] installation installed [N]
(mm) (mm)
Maximum operating
Conductor temperature : 85OC
Fixed installation for power,control and lighting in both EX- IEC:60092-3 - Design guidelines
and safe areas, emergency and critical systems. IEC:60332-3/A - Flame retardance
IEC:60754-1,2 - Halogen-free properties
IEC:61034-1,2 - Lowskome properties
IEC:60331 - Fire resistance
IEEE:45/383 - Flame retardance
CONSTRUCTION
CODE LETTER
Conductor Tinned, annealed, stranded copper. (1)
Colour Black.
ELECTRICAL DATA
No. of cores x Conductor resistance Reactance Impedance Continous Short circuit
cross section [/km] current rating [Ampere]
[/km] [/km] at 85 C Ampere
[mm2] at 20 C at 85 C at 60 Hz at 60 Hz at 25 C 1 sec 0,3 sec
Maximum operating
conductor temperature : 85OC
Operating voltage Uo/U : 600V
Insulated conductor for earthing and bonding services. IEC:60092-3 - Design guidelines
IEC:60332-1 - Flame retardance
IEC:60332-3/A - Flame retardance
IEC:60754-1,2 - Halogen-free properties
IEC:61034-1,2 - Low smoke properties
IEEE: 45/383 - Flame retardance
CONSTRUCTION
CODE LETTER
Conductor Tinned, annealed, stranded copper. (1)
Rubberized nylon-tape (2)
Unsheathed X
ELECTRICAL DATA
INSTALLATION DATA
TYPE Overall Diameter Minimum bending radius Maximum pulling
During Fixed tension
[mm2] [mm] installation installed [N]
(mm) (mm)
Maximum operating
1
2 4 pair 0,75 1,1 0,8 1,2 14,51,0 0,25 1,4 19,01,0 535 175
4 1 pair 1,0 1,3 0,8 1,1 9,00,8 0,20 1,1 12,51,0 235 72
6 4 pair 1,0 1,3 0,8 1,2 16,01,0 0,25 1,5 20,51,5 625 220
8 1 pair 1,5 1,6 0,8 1,1 9,50,8 0,20 1,2 13,01,0 275 95
12 2 pair 1,5 1,6 0,8 1,2 15,01,0 0,25 1,4 19,01,0 545 190
14 4 pair 1,5 1,6 0,8 1,3 17,51,0 0,25 1,5 22,01,5 750 296
16 12 pair 1,5 1,6 0,8 1,5 28,01,5 0,30 1,9 33,02,0 1710 720
18 24 pair 1,5 1,6 0,8 1,7 38,52,0 0,40 2,3 44,52,5 3190 1390
10 1 pair 2,5 2,0 0,8 1,1 10,51,0 0,20 1,2 14,01,0 330 120
20 1 triple 1,5 1,6 0,8 1,1 10,51,0 0,20 1,2 14,01,0 310 110
22 2 triple 1,5 1,6 0,8 1,2 16,51,0 0,25 1,5 20,51,5 640 230
24 7 triple 1,5 1,6 0,8 1,4 23,01,5 0,30 1,8 28,01,5 1365 580
26 12 triple 1,5 1,6 0,8 1,5 31,02,0 0,30 2,0 36,02,0 2130 910
The coverage density of the braided armour are minimum 90% in acc. with IEC 60092-3
1 4 pair 0,75 1,1 0,8 1,2 14,51,0 0,25 1,4 19,01,0 535 175
3 1 pair 1,0 1,3 0,8 1,1 9,00,8 0,20 1,1 12,51,0 235 72
5 4 pair 1,0 1,3 0,8 1,2 16,01,0 0,25 1,5 20,51,5 625 220
7 1 pair 1,5 1,6 0,8 1,1 9,50,8 0,20 1,2 13,01,0 275 95
11 2 pair 1,5 1,6 0,8 1,2 15,01,0 0,25 1,4 19,01,0 545 190
13 4 pair 1,5 1,6 0,8 1,3 17,51,0 0,25 1,5 22,01,5 750 296
15 12 pair 1,5 1,6 0,8 1,5 28,01,5 0,30 1,9 33,02,0 1710 720
17 24 pair 1,5 1,6 0,8 1,7 38,52,0 0,40 2,3 44,52,5 3190 1390
9 1 pair 2,5 2,0 0,8 1,1 10,51,0 0,20 1,2 14,01,0 330 120
19 1 triple 1,5 1,6 0,8 1,1 10,51,0 0,20 1,2 14,01,0 310 110
21 2 triple 1,5 1,6 0,8 1,2 16,51,0 0,25 1,5 20,51,5 640 230
23 7 triple 1,5 1,6 0,8 1,4 23,01,5 0,30 1,8 28,01,5 1365 580
25 12 triple 1,5 1,6 0,8 1,5 31,02,0 0,30 2,0 36,02,0 2130 910
The coverage density of the braided armour are minimum 90% in acc. with IEC 60092-3
SDDR code:
Draka Offshore Cables G06
Doc. title: Technical Data Book Power and Instrumentation Page 16 of 33
Doc. no.: Cables Rev. 00
ELECTRICAL CHARACTERISTICS
Type Capacitance approx. Inductance approx. Resistance at 20C max. L/R ratio
nF/km mH/km Ohm/km H/ohm
INSTALLATION DATA
TYPE Overall Diameter Minimum bending radius Maximum pulling
During Fixed tension
[mm2] [mm] installation installed [N]
(mm) (mm)
Halogen-free
Maximum operating
conductor temperature : 85OC
Operating voltage : 250V
Application Standards applied
The coverage density of the braided armour are minimum 90% in acc. with IEC 60092-3
The coverage density of the braided armour are minimum 90% in acc. with IEC 60092-3
ELECTRICAL CHARACTERISTICS
Type Capacitance approx. Inductance approx. Resistance at 20C max. L/R ratio
nF/km mH/km Ohm/km H/ohm
INSTALLATION DATA
TYPE Overall Diameter Minimum bending radius Maximum pulling
During Fixed tension
[mm2] [mm] installation installed [N]
(mm) (mm)
Cable properties
Tensile strength (IEC 60794-1-2E1) Temperature window
Max tensile load during installation 1500 N Operation -30C to +60C
Max tensile load during operation 500 N Installation -10C to +60C
Storage -40C to +70C
Crush (IEC 60794-1-2E3) 3000 N/10cm Fire and smoke classifications
Impact (IEC 60794-1-2E4) 20 impacts, 5J IEC 60331-25(750C, 3 hours) <1 dB excess loss
Torsion (IEC 60794-1-2E7) 1 turn/1m Upgraded IEC 60331-25(1000C, 3 hours) <1.5 dB excess loss
Cable bending BP-236
Minimum bending diameter 250 mm IEC 61034
Cable bend (IEC 60794-1-2E11) <0.1dB/ 5 turn IEC 60332-3 cat. A and C
IEC 60754-1
IEC 60754-2
SDDR code:
Draka Offshore Cables G06
Doc. title: Technical Data Book Power and Instrumentation Page 21 of 33
Doc. no.: Cables Rev. 00
Optical fibres
Fibre type 62.5/125
FDDI
Core diameter 62.5 3.0 m
Mode field diameter
Cladding diameter 125 2.0 m
Primary coating 250 m
diameter (nominal)
Attenuation
850 nm 3.2 dB/km
1300 nm 0.9 dB/km
1310 nm
1550 nm
Bandwidth
850 nm >200 MHzkm
1300 nm >500 MHzkm
Dispersion
1285-1330 nm
1550 nm
Numerical aperture 0.275 0.015
Minimum permanent
bending diameter 50 mm
SDDR code:
Draka Offshore Cables G06
Doc. title: Technical Data Book Power and Instrumentation Page 22 of 33
Doc. no.: Cables Rev. 00
Application:
Bostrig MHV-15(LS)BS single conductor 15,000 volt shielded cables are suitable for use in commercial
marine applications, MODUs and platforms where flame retardant cables having excellent physical and
electrical properties are required. These cables have excellent resistance to oils, abrasion, petrochemical
fluids, moisture and sunlight.
Conductor:
Soft annealed tinned copper. Stranding shown in the data table in pdf file embedded below.
Conductor Shield:
Semi-comnducting tape with extruded thermosetting semi-conducting EPR.
Insultation:
Extruded thermosetting EPR, 90C-Type E. Thicknesses shown in the data table in the pdf file embedded
below.
Insulation Shield:
Extruded thermosetting semi-conducting XLPO.
Armor:
Braided Bronze.
Tests:
Meets applicable test requirements in IEC 60502, IEC 60092-354, IEEE 45-1998 & 1993 (draft), ICEA S-68-
516, UL 1072, J-120 and flame test in IEC 332-2, cat A, A/F.
Rating:
Listed by a Nationally Recognized Testing Laboratory, (NRTL) in conformance to IEC 60502, IEC 60092-
354, UL 1072 and ICEA S-68-516. Cable meets the performance requirements of IEEE 45-1998 % 1993
(draft). Type approved by DNV, ABS and LRS.
Application:
Bostrig MHV3-15(LS)BS single conductor 15,000 volt shielded cables are suitable for use in commercial
marine applications, MODUs and platforms where flame retardant cables having excellent physical and
electrical properties are required. These cables have excellent resistance to oils, abrasion, petrochemical
fluids, moisture and sunlight.
Cables are also available with either a fully insulated grounding conductor or an un-insulated grounding
conductor evenly distributed in the interstices of the cable.
Conductor:
Soft annealed tinned copper. Stranding shown in the data table in pdf file embedded below.
Conductor Shield:
Semi-comnducting tape with extruded thermosetting semi-conducting EPR.
Insultation:
Extruded thermosetting EPR, 90C-Type E. Thicknesses shown in the data table in the pdf file embedded
below.
Insulation Shield:
Extruded thermosetting semi-conducting XLPO.
Armor:
Braided Bronze.
Tests:
Meets applicable test requirements in IEC 60502, IEC 60092-354, IEEE 45-1998 & 1993 (draft), ICEA S-68-
516, UL 1072, J-128 and flame test in IEC 332-2, cat A, A/F.
Rating:
Listed by a Nationally Recognized Testing Laboratory, (NRTL) in conformance to IEC 60502, IEC 60092-
354, UL 1072 and ICEA S-68-516. Cable meets the performance requirements of IEEE 45-1998 % 1993
(draft). Type approved by DNV, ABS and LRS.
Notes
INSTALLATION RECOMMENDATIONS
Minimum cable bending radius, RFXU,RFOU, BFXU and BFOU, 250V and 0,6/1kV cables.
The internal radius of cable bends which are not subjected to movements by expansion, is not to be less than:
Installations temperature, RFXU,RFOU, BFXU and BFOU, 250V and 0,6/1kV cables..
Storage conditions, RFXU,RFOU, BFXU and BFOU, 250V and 0,6/1kV cables..
Extended storage conditions on the site can be estimated to at least two years. The cable-ends always have to be
sealed to stop ingress of moisture.
Note: One turn of the cable have to be scrapped if the cable end not have been sealed.
The internal radius of cable bends which are not subjected to movements by expansion, is not to be less than:
6 times the external diameter of cable for unarmoured and sheathed cables
Extended storage conditions on the site can be estimated to at least two years. The cable-ends always have to be
sealed to stop ingress of moisture.
Note: One turn of the cable have to be scrapped if the cable end not have been sealed.
SDDR code:
Draka Offshore Cables G06
Doc. title: Technical Data Book Power and Instrumentation Page 27 of 33
Doc. no.: Cables Rev. 00
Flanges, 2-ply
(spruce)
Center
hole
Barrel
Bolts for
reinforcing
Material : spruce
Sealed
cable end
Lagging
Hoop-iron
2. 2 or 3 hoop-irons are applied over the lagging to ensure the tightness to the drum.
3. The sealed inner cableend is coming out through the flange, which makes it possible to test
the cable on the drum.
4. The drum may be lifted by forklift truck, or through the center hole.
SDDR code:
Draka Offshore Cables G06
Doc. title: Technical Data Book Power and Instrumentation Page 29 of 33
Doc. no.: Cables Rev. 00
2. The cable drums are marked in accordance with instructions given in the Purchase Order
documents.
3. Both cable ends are free, (the inner end comes out through the drum flange) and the cable can thus be tested
while still on drum.
UNPACKING PROCEDURE
1. Remove the hoop-irons, they are not nailed to the lagging.
The drums must be stored in the upright position, small drums may be stored in two layers, use stoppers at the end
of the bottom row. The drums may be sent by rail, ship or air.
During shipment the drums are prevented from starting rolling by placing (wooden) stoppers underneath by the
flanges, like this:
SDDR code:
Draka Offshore Cables G06
Doc. title: Technical Data Book Power and Instrumentation Page 30 of 33
Doc. no.: Cables Rev. 00
Tightening
Due to changing weather conditions or transport,
wooden drums may slightly shrink or loosen
which necessitates retightening of the flange
nuts.
Rolling of drums
To prevent cable "crawl", drums must be rolled in
the same direction as the cable has been laid up
on the drum from the factory. This is especially
when the wooden lagging has been removed.
Care must be taken when drums are rolled
against each other, specially when cardboard
protection is used, or if wooden lagging has been
removed.
Lifting
When using wires or ropes for lifting,
they must be parallell to the flanges
to prevent inward pressure. (Use
spreader.)
When using a fork lift truck the forks
must be applied across the flanges and
have sufficient reach.
Drums must be lowered gently, not
dropped.
SDDR code:
Draka Offshore Cables G06
Doc. title: Technical Data Book Power and Instrumentation Page 31 of 33
Doc. no.: Cables Rev. 00
Stacking
Drums MUST be stacked or stored
STANDING on the flanges, not lying flat. Wood
chocks should be placed onder the flanges to
prevent accidental rolling. When stacking it is
essential to have the flanges meet, particulaly
with heavy drums. When cardboard protection is
used, stacking should be avoided.
Temperature
Handling and spooling of cables must only take
place within the specified temperature range (as
specified in contracts, sales documents, manuals
etc.) The cable needs time to adjust to changes
in temperature. It is estimated that a full cable
drum needs about 24 hours to adjust to a
temperature change of 20C.
SDDR code:
Draka Offshore Cables G06
Doc. title: Technical Data Book Power and Instrumentation Page 32 of 33
Doc. no.: Cables Rev. 00
Direction of spooling
The cable must be drawn off the drum AGAINST
the direction the cable has been laid up on the
drum.
Cutting
When cut, the exposed cable ends must be
taped or otherwise sealed off to keep out
moisture.
Transport - road/rail
The drums must be secured by suitable wooden
wedges pressed under the flanges and nailed to
the floor.
SDDR code:
Draka Offshore Cables G06
Doc. title: Technical Data Book Power and Instrumentation Page 33 of 33
Doc. no.: Cables Rev. 00
CODE DESIGNATION
This code designation covers the norwegian cables RFXU, RFOU, BFXU, BFOU and QFCI and it does not
cover the Bostrig MHV cables.