Gas-insulated medium voltage switchgear

PowerIT
Power IT
ZX0. The common features

The compact multitalent


SF6 gas-insulated
Metal-enclosed and gas-tight
Each compartment is a hermetically
sealed pressure system
... 24 kV
630 A, 1250 A and 25 kA for
circuit-breaker
630 A and 25 kA for switch-disconnector

Design Advantages
Maximum safety
Wall mounting installation
Encapsulation completely protected
Single busbar version
against access to hazardous parts
Laser welded stainless steel enclosures
High voltage section totally independent of
Modular design environmental influences
Units coupled by plug-in busbar No effect on dielectric strength and there-
connectors without SF6 gas work fore independent of site altitude
Access to cables from front When HV fuses are used, the
atmospheric correction factor must
Outer cone cable plug system be taken into account
up to 1250 A
Minimum space requirement
Minimum switchgear dimensions due to
SF6 insulation
Building area and volume savings
Economy
Switching devices Maximum availability for the operator
Vacuum circuit-breaker with Maximum system service life independent
series 3-position switch of the environment
3-position switch-disconnector Maintenance free high voltage section
with and without fuses
Minimized life cycle costs

2
Circuit breaker VD4 X
Horizontal arrangement of circuit-breaker
poles
Operating mechanism outside the gas
compartment
Poles and mechanism connected via
gas-tight bushing
Additional earthing function in combination
with 3-position switch

3-position switch
3-position switch with three functions
Connecting, isolating and earthing
Disconnected position at centre
Limit positions: Disconnector ON or
earthing switch ON
De-energized preparation for every
connection: switching by circuit-breaker
only
Limited active switching components in
the gas compartment
Operating mechanism outside the gas
compartment
Position detection by sensors or
auxiliary switches
Advantages of earthing by circuit-breaker Mechanical position indicators
Circuit-breaker of higher quality than an
earthing switch
Highest number of switching cycles onto
short-circuits
No contamination of SF6 by switching
operations

3
The ZX0 variants at a glance

I. The independent model


in block design
ZX0 for all users without auxiliary voltage
Manual operating mechanism on the circuit-breaker,
3-position switch-disconnector, switch-disconnector
and combination of switch-disconnector with fuses
... 24 kV
... 630 A
... 25 kA

II. The comfortable model in block design


ZX0 for all users
Electrical operation of circuit-breaker,
3-position switch and switch-disconnector
With combined protection and control unit
REF542 plus
... 24 kV
... 1250 A
... 25 kA

III. The conventional model


with individual panel partitioning
ZX0 for specific demands
Manual operation of all switching devices locally, with
optional remote control
Any protection device as required
Transverse installation possible
... 24 kV
... 1250 A
... 25 kA

4
The independent model

Details
Manual operating mechanism
630 A
Operation without auxiliary voltage
CT powered tripping, (e.g. SEG WIP relay)
Pressure gauge
Current transformer on outer cone
Mechanical interlocking
Auxiliary switches for position indication on request
Mechanical position indicators
Suitable for ambient temperatures from -25C to 40C
For service in utility, switching and unit substations

5
The comfortable model

Details
Electrical operation
630 A and 1250 A Digital protection and control equipment
Block design 1250 A Protection, control and operation with
multifunction protection and switchbay
With auxiliary voltage supply
control unit REF542 plus
Position detection with sensors from overcurrent protection to distance
Emergency manual operation protection
protection against maloperation by
Monitoring of each gas compartment programmable logic with optional
by density sensors connection to automation system
Current transformer or Rogowski coil freely programmable LEDs in con-
on outer cone junction with status-dependent plain
text messages on REF542 plus

6
The conventional model

Details
Individual panel partitioning for circuit-breaker panels
630 A and 1250 A
Transverse installation
Panel width 600 mm
Manual operation in combination with mechanical
position indicators
Mechanical auxiliary switches for position indication
Separation of mechanical operating area and
Protection removable secondary systems bay
Manufacturer-independent protection Remote control optional
devices with option for a connection to
substation automation systems Plug-in voltage transformers on the busbar
Disconnectable voltage transformers on the cable side
Switch-disconnector panels with and without fuses
built as individual end panels for station transformers

7
ZX0.
As different as switchgear designs
may be, the conditions for their operation
are all the same.

Delivery
Complete panels
Factory tested
With SF6 at rated filling pressure
Suitable for handling by crane
or fork lift truck

Installation
Easy and fast installation
Erection on foundation
frame or raised false floor
Simple connection of panels
or blocks via plug-in
connections, without any
work on the gas systems
Cable termination compartments
with plug-in technology

Commissioning
By trained skilled personnel
Direct access to the conductors via the
cable plug is available for current and
voltage tests on site without gas work
A maintenance earth can be established at
the cable plug for inspection and servicing
Experience
Servicing and maintenance ABB Calor Emag Mittelspannung GmbH
No refill required under normal condition has over 35 years of experience with gas-
due to sealed pressure system insulated switchgear.
Gas compartments are maintenance free ZX panels have been in operation
under normal conditions successfully and reliably around the
world since 1995.
Inspection predominantly comprises visual
inspection and functional testing

8
ZX0. Performance features at a glance.
Rated voltage kV 12 17.5 24
Maximum operating voltage kV 12 17.5 24
Rated power frequency withstand voltage kV 28 1) 38 1) 50 1)
Rated lightning impulse withstand voltage kV 75 95 125
All voltages apply to an insulating gas pressure,
absolute, at 20 C, of: kPa 2) 120 120 120
Rated frequency Hz 50/60 50/60 50/60
Rated current for busbars A ...1250 ...1250 ...1250
Rated current for tee-off with CB A ...1250 ...1250 ...1250
Rated current for tee-off with SD A ...630 ...630 ...630
Rated peak short circuit current kA ...63 ...63 ...63
Rated short time current 3 s kA ...25 ...25 ...25
Rated short circuit breaking current
of the circuit-breaker kA ...25 ...25 ...25
Rated short circuit making current
of the circuit-breaker kA 63 63 63
of the 3-position switch-disconnector kA 63 63 63
Rated operating sequence of the CB O - 0.3 s - CO - 3 min - CO 3)
Total opening time of the CB ms ca. 60 ca. 60 ca. 60
Closing time of the CB ms ca. 60 ca. 60 ca. 60
4) 4)
Insulating gas SF6 SF6 SF6 4)
Design pressure, absolute, 20 C kPa 160 160 160
Rated filling pressure, absolute, 20 C kPa 130 130 130
Minimum operating pressure, absolute, 20 C kPa 120 120 120
Rated data:
Charging motor VA (W) 150 150 150
Closing coil VA (W) 250 250 250
Opening coil VA (W) 250 250 250
Auxiliary voltage V 60, 110, 220 DC 5)
Degree of protection (IEC 60529, DIN VDE 0470):
High voltage live parts IP 65 IP 65 IP 65
Low voltage bay IP 3X, 4X 6) IP 3X, 4X 6) IP 3X, 4X 6)
Ambient temperature:
Maximum value C + 40 + 40 + 40
Maximum value of 24 hour mean C + 35 + 35 + 35
Minimum value C - 5 7) - 5 7) - 5 7)
Altitude for erection above sea level 8) m ... 1000 ... 1000 ... 1000
Dimensions:
Height mm 21009)/1650 10) 21009)/1650 10) 21009)/1650 10)
Depth mm 85011)/1000 11) 12) 85011)/1000 11) 12) 85011)/1000 11) 12)
Width mm 400/600 12) 400/600 12) 400/600 12)

1)
Higher values to international standards on request 7)
25 C on request
2) 8)
100 kPa = 1 bar Higher altitude on request
3) 9)
Other sequences on request For all panels in a system with circuit-breaker panels
4) 10)
Insulating gas: sulphur hexafluoride For systems without circuit-breaker panels
5)
Other auxiliary voltages on request 11)
100 mm distance to wall
6) 12)
Depending on panel type, higher values on request For feeder currents > 800 A and for individually partitioned panels

9
ZX0. Block design variants
Feeder panels are always to the panels of a further block by
connected by outer cone cable plug-in busbar connectors.
plugs of angle or tee design. The connected blocks form a
Metering, earthing and riser panels system. System extensions can
round off the range. also be performed with a minimum
Each gas-tight block comprises up of work and without any work on
to six panels. These are connected the gas systems.

ZX0

ZX0 ZX0

10
ZX0.
Designed to meet the users needs.
Circuit-breaker
Switch-disconnector with fuses
Switch-disconnector

ZX0 ZX0

ZX0

11
ZX0 block design

From a block with up to 6 units ...

... through the smallest


extendable block ...

... to the individual end panel.


12
ZX0 block design

1 1

11 13
2 2
12
10 3 3
11

9 4 10 4

5 9 5
8
8
6 6
7
7

Circuit-breaker panel 630 A Circuit-breaker panel 1250 A


1 Bay control and protection 6 Ring-type current trans- 1 Bay control and protection 6 Ring-type current transformer
unit REF542 plus former unit REF542 plus 7 Voltage transformer
2 Measuring sockets for ca- 7 Pressure relief plate 2 Measuring sockets for 8 VT disconnecting device
pacitive voltage indicator capacitive voltage indicator 9 Pressure relief plate
8 External cone
system system 10 External cone
9 Vacuum circuit-breaker
3 3-position switch mecha- 3 3-position switch 11 Vacuum circuit-breaker
nism 10 3-position switch mechanism 12 3-position switch
4 Circuit-breaker mechanism 11 Busbars 4 Circuit-breaker mechanism 13 Busbars
5 Cable plug SF6 5 Cable plug SF6

7
1 11 1
6 10
2
2
3
9
4
3 8
5
5
7
4
6

Switch-disconnector panel Switch-disconnector panel with fuses


1 Measuring sockets for ca- 4 Pressure relief plate 1 Measuring sockets for 7 Pressure relief plate
pacitive voltage indicator 5 External cone capacitive voltage 8 Cable earthing switch
system 6 3-position switch-discon- indicator system
9 Fuse container
2 3-position switch-discon- nector 2 3-position switch-discon-
10 3-position switch-discon-
nector mechanism 7 Busbars nector mechanism
nector
3 Cable plug SF6 3 Metallic cover plate
11 Busbars
4 Orifice for strike pin
5 Cable plug
6 External cone SF6

13
ZX0. Panel partitioning

ZX0. Individual panels


Metal-enclosed individual panels manual operating mechanisms.
which fulfil the requirements for There is an additional option of
transverse installation, i.e. remote control, enabling the ZX0
exchange of one panel between systems to fulfil all the require-
without dismantling of more ments of utilities and industry.
panels. They represent the best Their technical parameters provide
compromise possible between for the economical implementation
economy and metalclad individual all conceivable applications.
panels. In the standard version,
the switching devices have

Alternatives of voltage
measurements

14
14 1

13 2
12
3
11
4 Circuit-breaker panel
10
1 Removable secondary 7 Ring-type current transformer
9 5
systems bay 8 External cone
2 Mechanical operating area 9 Pressure relief plate
8 6 10 Vacuum circuit-breaker
3 Measuring sockets for
capacitive voltage indicator 11 3-position switch
7
system 12 Busbar
4 3-position switch 13 Plug-in socket for voltage
mechanism transformer
5 Circuit-breaker mechanism 14 Plug-in voltage transformer
6 Cable plug SF6

15
Leaflet no. DECMS 2313 03 E Printed in Germany (03.03-2000-PPI)

ABB Calor Emag Mittelspannung GmbH Note:


We reserve the right to make technical changes or modify the contents of this
Oberhausener Strasse 33 Petzower Strasse 8 document without prior notice. With regard to purchase orders, the agreed
particulars shall prevail.
40472 Ratingen 14542 Werder (Havel) OT Glindow ABB does not accept any responsibility whatsoever for potential errors
DEUTSCHLAND DEUTSCHLAND or possible lack of information in this document.
We reserve all rights in this document and in the subject matter and illustrations
Phone: +49(0)21 02/12-12 30, Fax: +49(0)21 02/12-19 16 contained therein. Any reproduction in whole or in parts is forbidden without
E-mail: powertech@de.abb.com ABBs prior written consent.
Copyright 2003 ABB