2-component Primer in the Renitherm Fire Protective System.

Product Description: Technical Data Renitherm EP 61


Renitherm Primer EP 61 is a two-pack primer coat
Composition Renitherm Primer EP 61:
based on epoxy resin with zincphosphate, with the Epoxy resin, solvent containing
following properties: Hardener EP 61:
High mechanical strength, with Aminadduct
excellent adhesion properties. Mass density (Mixed) 1.4 g/cm3
Application on steel, hot-dip Solids content (Mixed) 180 g/m2 at 60 m
galvanized steel, aluminium. dry film thickness
Applicable at standard film thickness. 100 m WFT is approx. 50 m
DFT
Practical approx. 290 g/m2 at 60 m
Application Areas:
Renitherm Primer EP 61 provides a mechanical, Heat resistance dry
c. +120 deg. C. continuous
chemical and water resistant coating, applied at
c. +150 deg. C. short term
standard film thickness to exposed galvanised steel
surfaces, and other non-ferrous metals. humid/liquid
Renitherm Primer EP 61 is recommended for use Details of resistance are avail-
able on request
as an adhesion-promoting primer on galvanized steel,
for Renitherm Fire Protection Systems for Steel. Shelf life 12 months in cool and dry
storage conditions, in original
unopened containers.
Packaging and Colours:
Packaging: 24 kg. Base component, 4 kg. Hardener
Colours: sand (RAL 1002), redbrown,
other shades available on request
Finish: matt
Application Instructions: Brushing/Rolling: 02 % Thinner R 400
Surface Compatible primers should be used. Air assisted spraying: 5 10 % Thinner R 400
preparation/ Surfaces must be clean, dry and free Airless spraying 02 % Thinner R 400
steel: from dirt, grease, oil and salts. (Nozzle >0,38 mm)
Areas of breakdown should be manu-
ally cleaned and repaired. Pot life:
Min. 8 hours at +20 C.
Galvanised Remove any contamination. Surfaces
Steel and should be dry and free from dirt, oil Drying/curing (20 C):
other non and grease. In situations of frequent Dust-free after approx. 30 minutes Tack-free
ferrous metals: condensation or where salt formation 23 hours, after 5 hours overcoatable
is likely the surface should be
prepared by sweep blasting. Nominal recommended dry lm thickness:
Prolonged contact with water is to 40 m (corresponds to 90 m wet fi lm thickness)
be avoided.
Theoretical covering capacity:
Stainless Steel/ Sweep blast to give an average profi le 8.3 m2/kg at 40 microns dry fi lm thickness.
Aluminium: of 50 microns.
Theoretical consumption:
Brushing/Rolling: 0.12 kg/m2 at 40 microns dry fi lm thickness.
To achieve a regular fi nish with a MIO top coat, The practical consumption depends on the surface
apply in one direction only with the brush or roller. confi guration, and the application method.
To avoid a striping pattern, spray application is
necessary. Overcoatable:
With itself and two-pack systems based on EP and
Application and drying temperature: AY-PUR and Renitherm intumescent Fire Protection
min. +10 deg. C. (Surface and ambiance). Systems for Steel.

Relative humidity:
Max. 80 % (application temperature should be at least
3 deg. C. above the dew point).

Product mixing: AUDAX fully complies with the


Stir base component thoroughly then add the hardener requirements of EN ISO 9001
standard. This certifi cation is
at the specifi ed mixing ratio. Stir fully using a powered
one more proof for Renitherms
mixer. quality, reliability and safety.

Mixing ratio by weight:


Base: Hardener 100 : 20 (5 : 1)

Preparation of coating material:


According to the specifi c requirements, thinner
should be added as follows:

RM PRO
HE
TE
RENIT

CTS

AUDAX-Keck GmbH
Weiherstrae 10 75365 Calw
G
GR

E Fon 07051 1625-0 info@audax.de


IN

EN D
B UIL www.audax.de