Owner: MUNDRA SOLAR PV LIMITED.

MUNDRA,KUTCH

CONSULTANT : SEMAC CONSULTANTS PVT. LTD.

CONTRACTOR: SFS FIRE & SECURITY PVT. LTD

SHEKHA Digitally signed by


SHEKHAR AGARWAL

R
DN: cn=SHEKHAR
AGARWAL, o=ADANI,
ou=AHMEDABAD,

CAT-INFORMATION AGARW email=shekhar.agarw


al@adani.com, c=IN

AL
Date: 2016.07.27
14:32:38 +05'30'

MSPVL DOC.NO. : 5281-E-EMC-FDS-DE-L-V-008 Revision: 02


PROJECT DOC. TITLE : Load list

CONTRACTOR DOC. NO.: SFS-553-P-FFS-E-08 Revision: 02

APPROVAL STATUS : FOR FRESH SUBMISSION

Revised as per comments dated


02 26.07.2016 MK MK MS
on 27.06.2016
Revised as per comments dated
01 21.06.2016 MK MK MS
on 03.06.2016
00 24.05.2016 MK MK MS SUBMISSION FOR APPROVAL
INITIALS SIGN INITIALS SIGN INITIALS SIGN DETAILS OF REVISION
REV DATE
PREPARED CHECKED APPROVED
FROM:SFSFIRE&SECURITYPVT.LTD.
TO:MUDRASOLARPVLIMITED(MUNDRA,KUTCH)
SUBJECT:SUPPLY&ETCOFCOMPLETEFIREFIGHTINGSYSTEM
SFSDOC.NO:SFS553PFFSE09
MSPVLDOC.NO:5281EEMCFDSDELV009
DOC.TITLE:Loadlist
COMPLIANCEREPORT
Sr.No MSPVL'SComments SFS'Compliance
Rev.0 Rev.1Dated21.06.2016 Rev.2Dated26.07.2016

1 PleasementionedtheConnectedLoad. WehavementionedthesameinrevisedElectricalLoadList.

Refertoapproveddatasheetno.5281EEMCFDSDMDV001:
Datasheet&G.A.ofPumpsetsSr.No.12forWorkingloadatDuty
Point&Sr.No.16.4forWorkingloadat150%rated;Weconfirmthat
theMotorratingselectedisadequateandinlinewithTACGuidelines.

Inviewofaboveclarificationsandasperconfirmationreceivedfrom
motorMotormanufacturer,

Formainpumpmotors:Connectedloadi.e.198KWofeachmotoris
approx.20%higherthanthemaximumWorkingloadi.e.162.3KW
PleasementionWorkingLoadofeachmotorinseparate
2 whichisrequirementat150%dutypointofpumpset.
column
ForJockeypumpmotors:Connectedloadi.e.22KWofeachmotoris
approx.70%higherthanthemaximumWorkingloadi.e.12.01KW
whichisrequirementatdutypointofpumpset.

Pl.notethattheapplicationofJockeyPumpistomaintainleakages/
pressurisationpurpose;WorkingLoadat150%dutypointofpumpsetis
notapplicableinlinewithTACGuidelines.

Acordingly,thedesireddetailismentionedinrevisedElectricalLoadList.


3 PleasementionPFofeachmotorinseparatecolumn WehavementionedthesameinrevisedElectricalLoadList.

Weconfirmthatasallthemotorsarebeingusedforfirefighting
4 Pleaserechecktheoperationmodeofrespectivemotors.
pacakge,theyareincontinuousmodeofoperation.

PleaseshowtotalConnected&WorkingLoadforFW
5 WehavementionedthesameinrevisedElectricalLoadList.
PumpHouseinseparaterow.
Rev.0
1 WillbefedfromNormalpowerSupplyonly. Loadlistisrevisedaccordingly.
Itmaypleasebenotedthat,PowersupplyforexitsignisnotinSFS
2 PleaseaddloaddetailsofExitSignLamp
scope.Hence,thiscommentisnotapplicable.
PROJECT : 1.2 GW SOLAR PV CELL & MODULE MANUFACTURING UNIT AT MUNDRA,GUJARAT
PACKAGE : SUPPLY & ETC OF COMPLETE FIRE FIGHTING SYSTEM CLIENT'S Doc. No : 5281-E-EMC-FDS-DE-L-V-008
CLIENT : MUDRA SOLAR PV LIMITED ( MUNDRA, KUTCH) SFS's Doc. No.: SFS-553-P-FFS-E-08
VENDOR : SFS FIRE & SECURITY PVT. LTD. Date & Rev. No. : 26.07.2016 REV.02

ELECTRICAL LOAD LIST


Connected load Working load RPM Normal / No of
S. No. Tag No. Description Supply type PF Feeder type Working / Standby Operation Controlled from Location Remarks
(KW / Amp / KVA ) (KW / Amp / KVA ) (Nom.) Emergency Feeder
A Fire Water Pump House

Electric Motor driven Hydrant Motor Fire Water Pump


1 H-M-01 198 KW 162.83 KW 415V- 3Ph-50 Hz 1485 0.88 Normal 1 Working Continuous MCC
cum sprinkler Pump - 1 (Uni-directional) House

Electric Motor driven Hydrant Motor Fire Water Pump


2 H-M-02 198 KW 162.83 KW 415V- 3Ph-50 Hz 1485 0.88 Normal 1 Working Continuous MCC
cum sprinkler Pump - 2 (Uni-directional) House

Electric Motor driven Jockey Motor Fire Water Pump


3 JP-M-01 22 KW 12.01 KW 415V- 3Ph-50 Hz 2925 0.89 Normal 1 Working Continuous MCC
Pump - 1 (Uni-directional) House

Electric Motor driven Jockey Motor Fire Water Pump


4 JP-M-02 22 KW 12.01 KW 415V- 3Ph-50 Hz 2925 0.89 Normal 1 Standby Continuous MCC
Pump - 2 (Uni-directional) House
Diesel Engine Cum Battery
Fire Water Pump
5 BCH-01 Charger Panel for Diesel Driven 25 Amp - 230V- 1Ph-50 Hz - Normal SFU 1 Working Continuous DECP
House
Hydrant cum sprinkler Pump
B Fire Alarm System

1 MFAP Master Fire Alarm Panel 5 Amp - 230V- 1Ph-50 Hz - Normal SFU -- Working Continuous MFAP Second floor

Mini UPS - 1 KVA Rating for PC


2 UPS 1 KVA - 230V- 1Ph-50 Hz - Normal SFU -- Working Continuous MFAP Second floor
Based Monitoring station

3 FAP - 1 Fire Alarm Panel 1 5 Amp - 230V- 1Ph-50 Hz - Normal SFU -- Working Continuous FAP - 1 Ground floor
4 FAP - 2 Fire Alarm Panel 2 5 Amp - 230V- 1Ph-50 Hz - Normal SFU -- Working Continuous FAP - 2 First floor
5 FAP - 3 Fire Alarm Panel 3 5 Amp - 230V- 1Ph-50 Hz - Normal SFU -- Working Continuous FAP - 3 First floor

6 FAP - 4 Fire Alarm Panel 4 5 Amp - 230V- 1Ph-50 Hz - Normal SFU -- Working Continuous FAP - 4 Seconf floor

7 FAP - 5 Fire Alarm Panel 5 5 Amp - 230V- 1Ph-50 Hz - Normal SFU -- Working Continuous FAP - 5 Seconf floor
8 FAP - 6 Fire Alarm Panel 6 5 Amp - 230V- 1Ph-50 Hz - Normal SFU -- Working Continuous FAP - 6 Plenium area
9 REP - 1 Repeater Panel - 1 5 Amp - 230V- 1Ph-50 Hz - Normal SFU -- Working Continuous REP - 1 Fire Station

NOTE - POWER SUPPLY FOR MCC PANEL SHALL BE PROVIDED BY M/S MSPVL.

Legends :
S. No. Serial Number
Tag No. Unique Tag Number of the Equipment
Description Description of the Equipment
Rating Rating in kW or Amps
kW / VA Unit of 'Rating' i.e., KW or VA
Supply type Voltage, Phases & Frequency
PF Power Factor
Normal / Emergency Normal Supply or Emergency Supply
Feeder type Motor feeder or Heater feeder or SFU
Working / Standby Normally working or standby
Operation Continuous or Intermittent operation
Controlled from Controlled from MCC or Local Panel
Location Location of the Eqipment
Remarks Any other relevant information