Lontar Extension Coal Rev C

Fired Steam Power Plant For External Review


(1X315MW) Project Civil General Construction 31-Oct-2016

52 Silica fume 7 percent max


53 Determining Maximum Water-Cementitious Determine maximum water-cementitious materials
Material Ratio ratio on a cement mass basis
If fly ash is used, use the combined mass of cement
and pozzolan to determine the water-cementitious
materials ratio
54 Aggregates
55 Fine Aggregate Sand Equivalent Not less than 75 for an average of three samples
tested
56 Ratio of fine to total aggregates, based
on solid volumes (not weights), for
following coarse aggregate sizes
57 ASTM C33 Size Number 67 Minimum 0.35, Maximum 0.50
3/4 inch (19 mm) to No. 4 (4.75 mm)
sieve
58 ASTM C33 Size Number 57 Minimum 0.30, Maximum 0.46
1 inch (25 mm) to No. 4 (4.75 mm)
sieve
59 ASTM C33 Size Number 467 Minimum 0.25, Maximum 0.42
1-1/2 inch (37.5 mm) to No. 4 (4.75
mm) sieve
60 Maximum size of coarse aggregate for 1-1/2 inches (37.5 mm)
pumped concrete mixtures
61 Miscellaneous Requirements
62 Tolerance for total volumetric air content 1.5 percent of the specified value
of concrete after placement
63 Air-entraining admixture Omit from concrete for interior slabs to be trowel
finished
64 Limit on additional slump of pumped Amount of slump loss in the pumping system up to 1
concrete above specified maximum inch (25 mm) maximum increase
slump
65 Time to Initial Set 5-1/2 hours 1 hour after the water and cement are
added to the aggregates, for each concrete mixture
66 Polyolefin Fibers
2
67 Required for Application 0.905 g/ml specific gravity and 3.5kN/mm Youngs
Modulus shall be used for all important structures. Its
quantity per cubic concrete shall be based on the
manufacturers printed recommendation.
3
68 Dosage Rate 0.9 kg/m
69 Maximum Drying Shrinkage Values, based
on application and laboratory test
specimen size
70 Liquid-Containing Structures

189963.71.0402 Page 96 of 204