You are on page 1of 12

1838 IEEE Transactions on Power Delivery, Vol. 9,No.

4,October 1994

EMTP-Based Model for Grounding System Analysis


Frank E. Menter, Member, IEEE Leonid Grcev, Member, IEEE
Technical University of Aachen University of Skopje
Aachen, Germany*) Skopje, Republic of Macedonia

Abshzct - EMC and lightning protection analyses of Since in most cases EMC studies require the knowledge
large power systems require the knowledge of the dynamic of the systems performance over a wide frequency range,
behavior of extended grounding systems. They cannot be the presented methodology extends the range of validity of
regarded as equipotential planes, but must be treated as the well-known models for grounding systems towards
coupling paths for transient overvoltages. This
higher frequencies in the order of magnitude of some
contribution presents a model for linear earth conductors
based on the transmission line approach and outlines its megahertz An approach could be based on the three basic
integration in the transients program EMTP. Validation concepts developed thus far. These are:
of the presented model is achieved by comparison with - The NetworkApproach, which models an earth con-
field measurements and with a rigorous electromagnetic ductor as equivalent x-circuits made up of lumped R-L-C
model. Overvoltages and electrical fields throughout elements. The coupling of earth conductors can be taken
electrical power systems thus can be computed. into account by mutually coupled inductances. Among
others, Velazquez and Mukhedkar describe the procedure
KEYWORDS - Grounding Systems, Buried Conductors,
111 *
EMC, Lightning Protection, Computer Modellling,
Electromag netic Fields, EMTP
- The Transmission Line Approach was brought to
practical applicability by Sunde [2].The topology of the
network of interconnected linear ground conductors is
1. INTRODUCIION treated by the travelling wave technique pioneered by
Bergeron. Nowadays, Papalexopoulos and Meliopoulos are
Grounding systems serve two purposes: Firstly, their basing their work on this method (e.g., [3]).
task is to disperse fault currents into the earth, which can - The Electromagnetic Field Approach exhibits the
be evoked either by internal, unbalanced faults or by ex- most rigorous theoretical background of all three
ternal sources, such as lightning. Secondly, extended approaches. Strictly based on the theorems of electro-
grounding systems create a reference potential for all elec- magnetism and with the least neglects possible, the prob-
tric and electronic apparatus making up a large-scale lems are defined in terms of retarded potentials, and
system. Local inequalities of this reference potential and among the possible strategies for their solution, the
disturbances conducted across the grounding system method of moments proved to be most efficient. Dawalibi
reportedly are a source of malfunction and destruction of could translate the highly complex relationships into prac-
components in electrical connection with the grounding tical, engineering programs [4].
system. This contribution treats grounding systems from For a model valid in the envisaged frequency range, the
the point of view of the electromagnetic compatibility network approach was assumed not to be appropriate. In
(EMC) and thus regards a grounding system as a path of contrast, this contribution shall point out that the trans-
coupling between a source of interference, usually being an mission line approach is a suitable and practical choice for
impressed fault or lightning current, and a consequence, the determiqation of both the transient ground potential
typically a transient overvoltage or field stress, at the loca- rise and the electric fields in the vicinity of the grounding
tion of a disturbed object. system. An existing program based on the electromagnetic
field approach could validate this statement.
94 WM 135-4 PWRD A paper recommended and approved
by the IEEE Substations Committee of the IEEE Power A brief review of Sundes transmission line theory and
Engineering Society for presentation at the IEEE/PES the evaluation of the transmission line characteristics for
1994 Winter Meeting, New York, New York, January 30 - common earth electrodes introduces this paper, followed
February 3, 1994. Manuscript submitted July 29, 1993; by the description of an interface to the ATP version [SI of
made available for printing December 22, 1993.
the wide-spread Electromagnetic Transients Program
(EMTP) [6]. A post processor which computes electric
fields in the soil from the current distribution in the

*) At present with SIEMENS AG, TransportationSystems,


Erlangen, Germany

0885-8977/94/$04.000 1994 IEEE


1839
grounding system is sketched next, preceding the presen-
tation of field measurements and of comparisons with a
rigorous electromagnetic model. Finally, a lightning
protection study for a 123 kV substation underlines the 1
great advantage of not having just a stand-alone grounding
systems program, but a tool capable of analyzing specific
grounding systems in conjunction with the entire electrical
system.

H
I
.i. . .e. :. . :. .e

x = 0)) x = e
Fig. 1 . Horizontal earth electrode and transition t o an
equivalent transmission line segment

11. TRANSMISSION
LINE MODELFORBURIED CON-
DUCTORS

Fig. 1illustrates the transition from a linear earth elec-


trode to an equivalent transmission line with complex- -CO
Ph
valued, frequency dependent parameters G o ) and y (a), 0.01
which denote the characteristic impedance and propa-
gation function, respectively: 0.001

f-
Fig. 2. Surge impedance, attenuation and phase
velocity of a horizontal, bare copper wire ( 3 5 mm2)
The angular frequency, o = 27& uses f in Hz (j= f i ) . buried at a depth of 0 . 5 m
This form corresponds to any two-conductor transmission
line. Sunde derived equivalent expressions for a single -
l-(o)= J j w o .(OE +jOEO&,,E) 9 (5)
conductor in contact to the soil, with the current returning which would govern the transmission of impulses along the
through the earth. Both the longitudinal impedance per conductor if it were imbedded in a homogeneous soil with
unit length, z',
and the transversal admittance per unit these parameters. Plumey, Kouteymkoff et al. derived
length, x',
of a horizontal conductor consist of an internal analogous expressions for vertical ground rods [A,reading
term and an earth return term in the following manner [2]:

Here, denotes the internal impedance of a conductor Equation (2) together with (3) and (4) leads to a
of radius, a, buried at a depth, z, which is mainly governed complex-valued, transcendent equation for the propa-
by the skin effect, whereas stands for the insulation gation function
admittance of an eventual coating, through which the
conductor is in contact to the surrounding medium. The which is repeatedly solved for all frequencies under
latter is characterized by the earth's conductivity, uE, investigation by means of a standard IMSL routine [8,9].
relative permeability, and permittivity, b. All three
lead to a propagation function, Fig. 2 shows the resulting quantities as functions of fre-
quency for a variety of soil parameters oEand It is
1840

0 replacing the line by Thevenin equivalent circuits at both


terminals, consisting of the constant and real-valued
characteristic impedance and a current source for the
history OF the travelling waves with the travel time z
(Fig. 3, upper indedsign for forward travelling wave, lower
indedsign for backward travelling wave):
1
'"'(t) =-*v f-z)fik(f-z) (11)
1L zc $( 1
In the frequency domain, the transition to complex-
valued, frequency-dependent parameters necessary for
earth conductors is simply,
Ly'"
k
= H'(Zc-' 'zkf i k )
I 1
, (12)

Fig. 3 . Equivalent circuit for frequency-dependent


transmission line

common engineering practice to express the propagation


function in terms of transfer function, H=exp{-y-!}, or
attenuation per unit length, h', and phase velocity, cpb:

Z1 z2 P1 logo-
Only for lower frequencies, the properties of the ground Fig. 4-a. Marti's strategy o f approximation applied t o the
are exclusively determined by the conductivity of the earth. modulus o f the characteristic impedance
Above some tens of kilohertz, its dielectric nature has to
be taken into account.

111.USAGE OF EMTP FOR


GROUNDING SYSJXM A N a Y S I S

Once the characteristic impedance and the transfer


function of linear earth conductors are known, any kind of
extended grounding system can be modelled by a network
of transmission line segments, provided that inductive and
capacitive coupling between the different line segments
can be neglected, At first sight, it is not evident that this
assumption is permissible, but the purpose of this contri-
bution is to show that for the grounding systems analyzed Fig. 4-b. Occurrence o f numerical oscillations by Marti's
thus far, the resulting error is within acceptable limits. strategy i f applied t o the attenuation
From an engineering point of view, the gained versatility
and flexibility in modelling an actual earthing system
together with live parts of the installation compensates the
loss in accuracy.

A. Znteqace of the Ground Conductor Model to EMTP


Live and earthed parts of the electrical system are mod-
elled by the Electromagnetic Transients Program. EMTP
incorporates Bergeron's method for transmission lines, i. e.
Fig. 4 - c . Remedy by modified strategy ( c f . text)
1841

but since EMTP works in the time domain, the back trans- the longitudinal impedance, z, remains unchanged by
formation leads to two nested convolution integrals: ionization phenomena.
iFiSGH(f)= hs (f)* [3+{ z,(a)}* vk(f) f i&)] (13) The basic idea of incorporating an ionization model into
the simulation network is to concentrate that part of the
k 1 1
transversal admittance, AX(%/&), which exceeds the value
The numerical effort for the convolutions can be
disregarding the ionization, &, at the intersections of
reduced drastically if the technique of the so-called recur-
transmission line segments, which can be generated with-
sive convolution can be applied [lo]. For this purpose, it is
out the necessity of taking the soil ionization into account
necessary to approximate the characteristic impedance and
(Fig. 5).
the transfer function by rational functions, i. e. it is manda-
tory to identify their poles and zeroes. Martis original The implementation of the model makes use of the ob-
strategy ([ll], Fig. 4-a) of proceeding form lower to higher servation that the additional transverse admittance, AX(o,
frequencies in a log-log-chart and placing a pole or zero %/&), can be decomposed into
wherever an asymptotic approximation leaves a tolerance Ar (ai / ax,o) = K(ai /ax) A l l (o) ,
+
(17)
strip of width 2A is not adequate in the present case: In where AX1 is a specific fundamental function and K is a
contrast to its original field of application, observed multiplier, only depending on the leakage current. Both
frequency, characteristic impedance and attenuation cover functions can be determined by formal variations of o and
several orders of magnitude, and thus frequently cause %/& before the simulation run. At the beginning of the
numerical oscillations (Fig. 4-b). run, A I 1 is similarly approximated by its poles and zeroes,
A remedy could be found by the introduction of a rela- which are passed to EMTPs laplace xfomz module for the
tive error criterion for the tolerance strip and by the representation of arbitrary, frequency dependent imped-
possibility of placing closely adjacent pole/zero-pairs in ances. During the run, the additional transversal admit-
order to jump exactly on the target function ([12], Fig. tances are scaled by the multiplier K, whose locally valid
4-C) . actual argument, W&(x), is determined at each time step
from the difference of the longitudinal currents and the
B. Modelling the Soil Ionization with EMTP length, e, of the corresponding transmission line segment.
These run-time evaluations, the interpolation on the
If large current densities emanate from the conductor pointlist function K(%/&) and the scaling of all elements
into the soil, the critical field strength can be exceeded and A x is performed by the recently developed tool models
breakdowns occur. Then, the conductor will be of the ATP version of EMTP [14,15].
surrounded by a cylindrical corona-type discharge pattern, i(x) i(x + e)
which augments the available surface for the transition of
the current from the conductor to the earth. The break-
down strength, E,, of the soil is a function of its conduc-
tivity, measurements [13] lead to the empirical formula
Ec.it = 2 4 1 . 0 i ~ . ~ ~ ~ (14)
for E,,., in kV/m and the soil conductivity, c E , in
The distance from the center of the earth conductor at Fig. 5 . Leakage current controlled lumped elements
which the ionization of the soil ceases, may be regarded as t o model soil ionization
an effective radius. Ohms law governs the relationship
between current density at a distance, a, from the con-
ductor and field in the soil, Iv. COMPUTATIONOF THE ELECIWCFIELD
DISTRIBUTION

Considering the possibility to extend the application of


The combination of the two latter expression for a = a e f f the developed model to EMC studies, the electric field
and E =Ec,., yields vector is chosen as a key quantity. The main reason for this
is the well known fact that in the general case the voltage
between points along specitied path is not equal to the
for the effective radius, a e f f ,in m, and the leakage current potential difference, but is defined as a line integral of the
per unit length, a/&, in W m . The seemingly increased electric field vector along the path. In order to compute
circumference of the conductor will affect only the trans- the electric field distribution in the vicinity of the
versal admittance, X(%/&),whereas the by far most part grounding system, a post processor to EMTP has been
of the longitudinal current will stay within the conductor: developed. Since the grounding system is modelled as a
1842

network of arbitrarily connected or disconnected straight =p f =e


thin conductors, the electric field can be computed as a
superposition of the contributions of field-generating cur-
rents on all straight conductors, which are readily available
as EMTP results.
Usually, in order to avoid complications in the solution,
only the electric charge distribution in the grounding
system conductors is considered as a source of the electric 21 d 22 2
field. This is equivalent to consider only the leakage cur-
Fig. 6 . Computation o f the electric field distribution
rents from the conductors in the evaluation of the electric
field and the voltages [16]. In other words, this simpli- the near fields [19]. In this study, the influence of the inter-
fication is based on the neglect of the time-varying longi- face between the air and the earth is taken into account
tudinal current in the ground conductors as an additional approximately by the modified image theory 1161.
source of the electric field. But it has been shown [17l that By this way the electric field at a point in the earth due
such simplification can lead to extremely wrong results in
to the sinusoidal sources on the k-th segment is obtained
the computation of voltages. The procedure used here by superposition of the field of the original and image
takes into account both components of the electric field, sinusoidal sources both placed in the unbounded con-
due to the electric charges and longitudinal current distri- ducting medium. The exact expressions for the electric
bution in all the ground conductors. field in a local cylindrical co-ordinate system illustrated in
In this study, a frequency-domain approach is used, i.e. Fig. 6, due to the current distribution given in (18) on the
fields are computed from the steady-state current distribu- k-th segment at a near point are:
tion for f = 0 ...1 MHz. This yields the transfer function
for the electric field at prescribed observation points in the
vicinity of the grounding system. Such transfer functions
subsequently can be Fourier transformed to obtain the
time-domain response.
Grounding conductors are divided in a number of
smaller segments in the EMTP and the longitudinal
currents are determined only in the end or junction points
of the segments. The current in all other points can be
determined by interpolation. Among the many choices for
the interpolating function, one is exceptionally attractive
for OUT purposes: the so called piecewise sinusoidal
approximation of the current distribution I(t) that can be where TJ is the intrinsic impedance of the medium:
expressed by:
(21)

The various geometrical quantities are illustrated in


(18) Fig. 6. The references concerning the derivation of (20)
r is explained above (2,
- and Pk(e) are unit pulse functions can be found elsewhere 1191.
with the values A brief description of the steps involved in the deriva-
1, 4 - , g e s e ' , tion are included in the Appendix for completeness.
PkW =
0, elsewhere
Here, e denote points along the axis of the conductors, V.VERIFICATIONAND APPLICATION
pk is the first, C+k is the second end point and dk is the
length of the k-th segment. i-k and i + k are current A. Comparison with Field Measurements by EDF
phasors at the first and the second end point of the k-th
segment, respectively. The Direction des Etudes et Recherches of the
The main reason for the approximation of the current klectricitC de France granted an insight in their
with sinusoidal functions on the segments (18) is to exploit recordings of extensive field measurements performed in
their properties revealed by Schelkunoff [18]. The the mid-80's [20]. Impulse currents with front times down
sinusoidal line current source is probably the only finite to 0.2 ps have been fed into single- and multi-conductor
source with simple and exact closed form expressions for earthing arrangements as used industrially. The resulting
1843

More complex grounding arrangements have been


studied, too. Fig. 9 depicts the results in time domain of a
tower footing, consisting of a set of four ground rods and
30 two square loops (6m x 6m) in l m and 4 m depth,
i respectively. Except for a 2oons long period during the
20 wave front, the agreement between measurement and

V
V simulation is satisfactory.
t-6m
100 a=lOmmSt - 10
= 0.025 (Qm)-l:
-%E e 8
.:0 . . 0.5' . . . . '1 .
' ' ' ' '
1.5
. . . . '2 '. . .2.5' . p. . 130
' '

t-
Fig. 7 . Measured and calculated ground
potential rise of a ground rod
transient ground potential rise has been measured by
means of a 60m long ohmic divider, still having a
measuring bandwidth of 3 MHz. aE10mmSt
--10

Fig. 7 shows the oscillograms of voltage and current as UE= 0.025 @my1-
fqE = 8
recorded on a ground rod (steel, 20 mm in diameter, other
parameters in the figure). Included in the figure is the . 0.2
' " " . 0.4' . ' . 0.6
' .
-2
6.8 .b. -lo
simulation result of the voltage when a current according
Fig. 9. Measured and calculated ground
to the measured one is impressed in the corresponding potential rise of a tower footing
transmission line segment. The peak of the measured
voltage curve is always higher than the corresponding value
of the simulation, which can be explained by some B. Comparison with a Rigorous Electromagnetic Model
remaining inductive voltage drop during the wave front
As an example, a grid-type grounding system of 10 m x
along the divider added to the actual potential rise at the
10 m with 3 x 3 meshes has been studied. A sinusoidal cur-
clamp of the ground rod.
rent of l kA and variable frequency is fed into the slightly
The effective grounding impedance (Fig. 8) has been de- asymmetric arrangement at its center ((q) = (5 m;5 m)),
termined by a division of the Fast Fourier Transforms of the first regular mesh branch being reached at
measured voltage and current on a 10 m long horizontal ( ~ 8=)(5 m;6.67 m). The conductors have a diameter of
ground wire made of copper alloy. The corresponding lo", are assumed to be of ideal conductivity and are
simulation curve has been generated by EMTP's frequency buried at a depth of 0.5 m in a soil with oE = 0.01 (Qm)-l
scan option, requesting a repeated set of phasor solutions and E ~ =E1.
of the simulation network. The curves show good agree-
ment up to frequencies of 1MHz, the underestimation at Since the local distribution of longitudinal and leakage
higher frequencies may be explained by the above- currents within the grounding system is only an inter-
mentioned effect. mediate quantity in the computation of touch and step
voltages above the grounding system, a comparison of the
resulting electric fields at the earth's surface has been per-
formed. Firstly, the current distribution in the grounding
system according to the transmission line approach out-
measurements lined above has been taken as input to the post processor
Zff described in section IV. The resulting field distribution is
compared to a second, independent computation accord-
ing to the rigorous electromagnetic approach developed by
r L = WO m I
J
the second author [21]. The results are compared in
1 n=immCu
10 UE = 0.061 (am)-]
Fig. 10.
EqE=4
The transmission line model slightly overestimates the
results of the rigorous model, which is taken as a reference
here. But still the interesting phenomena are modelled
correctly, and the results are obtained within a fraction of
the computation time required for the rigorous approach.
1844

, I
.................... .............................. .................. ........ ........ ............. . . . . . . . . . ......................
............................ ........................ .........................

x- I-

Fig. 10. Field distribution above a mesh-type grounding system. Comparison for f = 1 MHz
o f the transmission line approach (left) and the rigorous electromagnetic approach (right)

C. Lightning Protection study for a 123 kvsubstation


This application example sketches the procedure and re-
sults of a lightning protection study for a 123kV sub-
station. The lightning is assumed to hit the third tower of
an overhead line (Fig. 11)and should have a crest value of
200 kA and an impulse shape as recommended in [22].The
EMTP data deck for the two-system, three-phase overhead
line as well as the representation of the switchyard (voltage
transformers, surge arresters, busbars and power trans-
former) has been made available by a CIGRk working
group [B]. It has been combined with a detailed descrip-
tion of the tower footings and the meshed grounding
system of the switchyard (70 m x 50 m) by means of the Fig. 1 1 . Lightning-struck overhead line
transmission line model. entering 123 kV substation

f- t-

........ y- ......................
n
I for I = 200kA:
- - - - - tower #1
- - - - lower #2
- - - . tower U3
----- tower U4
tower U5
...... ' .. .....' .........' ........
0 10 20 30 p40
t-
Fig. 12. Voltages and currents across insulators, and conductor potential at towers # 1 ...# 5 for phase A.
1845

U
U) tI-
rate .-

i
t 2o
10

-10
10 100 ccs
2- t-
Fig. 13. Currents injected in the earthing system and voltages across transformer and arrester terminals,

The employed time-dependent flashover model leads to ments by the EDF at Paris, France, and With wmputa-
the fact that, as a consequence of the lightning stroke to tional results produced by the second authors code based
tower #3, backflashovers occur at the towers #2, #4 and on a rigorous electromagnetic field approach. As an exam-
#5, whereas the flashover at tower #3 impresses a portion ple, some aspects of a lightning protection study for a
of the lightning current into the phase conductor (Fig. 12). 123 kV substation have been selected in order to underline
Within the substation (Fig. l3), an oscillating overvoltage the versatility and flexibility of the proposed method, capa-
of nearly 9 p.u. very probably will destroy the power trans- ble of modelling not only the grounding system itself, but
former windings. The metal oxide arrester (vmax=3.5 P.u.) also the electrical apparatus connected to it.
has been placed at too large a distance from the trans-
former to provide sufficient protection. Under such fault
conditions, currents are impressed at different locations WI. ACKNOWLEDGEMEhTS
into the grounding system, the major part of which through
the foundation of the gate to which the neutral conductor Financial support of the project had been granted by the
of the overhead line is connected. This situation results in Deutsche Forschungsgemeinschaft, Bonn, Germany, which
considerable local variations of the transient ground is gratefully appreciated. Messrs. Hew6 Rochereau of
potential rise, temporarily reaching 100 kV. Such potential EDF, Park, France and Vincent Vanderstockt of
differences within the grounding system are able to cause LABORELEC, Brussels, Belgium, amiably made available
EMC problems, if, for example, the shield of a measuring the measurement and substation data, respectively.
cable between voltage transformer and relaying room is The fist author wishes to express his gratitude to his aca-
grounded at both ends. Then, a rapidly varying current will demic teacher, Prof. Dr. Klaus Moller. Under his supervi-
flow on the cable shield and crosstalk will occur onto sion, the Ph.D. thesis could be realized upon which parts
secondary circuits. of the present contribution are based.

VI. CONCLUSION

Lightning protection and EMC analyses of power


WI.REFERENCES
electric systems paying special attention to the grounding
conditions require the knowledge of the dynamic proper- [l] R. Velazquez and D. Mukhedkar, Analyticalmodel-
ling of grounding electrodes transient behavior,
ties of ground conductors and extended earthing systems.
IEEE Trans. Power Apparatus and Systems, vol. 103,
For this purpose, a methodology has been developed
1984, pp. 1314-1322.
which is based on a transmission line approach for linear
ground conductors. Thus, it is the possible to integrate the [2] E. D. Sunde Earth conduction effects in transmission
grounding system as a network of such conductors into systems, and ed., New York: Dover Publications,
EMTP. The necessary interface algorithm has been out- 1968.
lined as well as a post processor capable of deriving elec- [3] A. D. Papalexopoulos and A. P. Meliopoulos,
trical fields in the vicinity of the grounding system. Valida- Frequency dependent characteristics of grounding
tion of the method developed by the first author could be systems,IEEE Trans. Power Delive?, vol. 2, October
achieved by means of comparisons with field measure- 1987, pp. 1073-1081.
F. Dawalibi and A. Selbi, "Electromagnetic Fields of Currents," IEEE 1992 Intemational Symposium on
Energized Conductors," IEEEIPES I992 Summer Electromagnetic Compatibility; Anaheim, CA,
Meeting Paper 92 SM 456-4 PWRD. pp. 393-400.
D. van Dommelen [ed.], Altemative Transients Pro- [18] S. A. Schelkunoff and H. T. Friis, Antennas, Theory
gram - Rule Book, Leuven EMTP Center, Catholic and Practice, New York Wiley, 1952, p. 401.
University of Leuven, Belgium; July 1987. [19] D. V. Otto and J. H. Richmond, "Rigorous Field Ex-
W. Long, D. Cotcher, D. Ruiu, P. Adam, S. Lee, and pressions for Piecewise-Sinusoidal Line Sources,"
R. Adapa, "EMTP - A powerful tool for analyzing IEEE Trans.Antennas and Propagation, Vol. 17, 1969,
power system transients," IEEE Trans. Computer p. 98.
Application in Power, July 1990, pp. 36-41. [20] H. Rochereau, "Comportement des prises de terre
J. P. Plumey, D. J. Robertou, J. M. Fontaine, and localistes parcourues par des coyants B front raide,"
P. Kouteynikoff, "ImpCdance haute frtquence d'une EDF Bulletin de la Direction des Etudes et Recherches,
antenne dtposCe dans un demi-espace conducteur," sQie B, no. 2,1988, pp. 13-22.
Pmc. Colloque sur la Compatibilitk dlectromagnktique, [21] L. Grcev and F. Dawalibi "An electromagnetic model
paper C.l, Trtgastel, France; January 1981. for transients in grounding systems," IEEE Trans.
IMSL, Inc., IMSL Reference manual, 8th ed.; Power Delivery, vol. 5,1990, pp. 1773-1781.
Houston, T X IMSL, 1980. 1221 CIGRE working group 33.01, Guide to procedures for
P. Wolfe, 'The secant method for simultaneous non- estimating the lightning pe?$ormance of transmission
linear equations," Communications of the ACM, vol. 2, lines, Guide no. 63, Paris: CIGRE, October 1991.
1959. [23] V. Vanderstockt, Application procedures for station
A. Semlyen and A. Dabuleanu, "Fast and accurate insulation CO,-ordination, IWD7 SC 33-92 (WGll),
switching transients calculations on transmission lines Park CIGRE, May 1992
with ground return using recursive convolutions," [24] J. H. Richmond, Computer Analysis of Three-Dimen-
IEEE Trans. Power Apparatus and Systems, vol. 94, sional wire Antennas, Technical Report 2708-4, Elec-
1975, pp. 561-571. troScience Laboratory, Ohio State University, 1969.
J. R. Marti, "Accurate modelling of frequency-
dependent transmission lines in electromagnetic
transient simulations," IEEE Trans. Power Apparatus APPENDIX
and Systems, vol. 101,1982, pp. 147-155.
F. Menter, "Accurate modelling of conductors imbed- The derivation in this Appendix is based on [18] and
ded in earth with frequency-dependent distributed [24]. Amcording to the fundamental analysis [NI, the z-
parameter lines," Proceedings of the 2lSt EMTP User component of the electric field vector of the line source
Group Meeting, paper 92.09, Kolymbari, Greece;
with arbitrary current distribution illustrated in Fig.6 is
Athens: National Technical University, June 1992. given by:
E. E. Oettle, "A new general estimation curve for pre-
dicting the impulse impedance of concentrated earth
electrodes," IEEEIPES 1987 winter Meeting Paper
87 W M 567-1PWRD. with
L. Dub6 and 1. Bonfanti, "MODELS, a new simula-
tion tool in EMTP," European Transactions on Eneqy
and Power (ETEP), vol. 2,1992, pp. 45-50.
F. Menter, Computation of electromagnetic transients
in extended grounding systems (in German), Ph.D.
thesis, Technical University of Aachen; Aachen: and integrating the first term in (Al) by parts twice and
Shaker 1993. substituting (A2)in (Al) we have:
T. Takashima, T. Nakae, and R. Ishibashi, "High Fre-
quency Characteristics of Impedances to Ground and
Field Distributions of Ground Electrodes," IEEE
Trans. Power Apparatus and Systems, Vol. 100, 1980,
pp. 1893-1900.
L. Grcev, "Computation of Transient Voltages near
Complex Groundina Svstems Caused bv Liehtnine
1847

If the current betweenz=zl andz=z2 is of form Dr. F- E Menter (M 93) was


bom in Essen, Germany, on August 14,
1963. He graduated from the Rheinisch-
Westfalische Technixhe Hochschule in
Aachen, Germany, and received the
Dip].-Ing. degree. His practical experi-
the bracketed expression in the integrand of (A3)vanishes. ences include various stays with Siemens
Hence: AG, Nixdorf Computers and the
Research Laboratory of Hitachi Cable,
=-
l(zl>e-t - (z2)e-ER2 Inc. As a scientific assistant at the
R2 Institute for Highvoltage Engineering at
Aachen University, he worked as a
project co-ordinator of two larger
projects, the first of which resulting in a
lightning protection scheme for DC driven urban railways and the second
where r(zl) and L(z2) denote the derivatives of the treating EMC problems of high voltage switchgears. In May 1993, he
current at the end points. The constants A and B can be received the doctoral Dr.-Ing. degree from the same University.
eliminated to express the current distribution in terms of Currently, he is with Siemens Transportation Systems at Erlangen,
the endpoint currents L(zl) and L(z2)as follows: Germany. In the Traction Power Supply Department, he is concerned
with grounding and EMC problems. Dr. Menter is a member of the IEEE
1
~ ( z=)-[ z ~ z2 - z ) + l ( z 2 sinhr(z - z1)]
~ ( sinhg( Power Engineering Society and the W E .
Slnhrdk
(A61
From (A6): Dr.h m i d Gnxv (M 84) was born in Skopje, Macedonia on April 28,
r
L ( Z l ) = -[SlhEdk l ( Z 2 ) - Z ( Z 1 ) COShcdk ]
1951. He received Dipl. Ing. degree from the University of Skopje, and
the MSc. and Ph.D. degrees from the University of Zagreb, Croatia, all
(A?
in Electrical Engineering, in 1978,1982 and 1986, respectively. From 1978
1 to 1988, he held a position with the Electric Power Company of Mace-
L ( z 2 )= -[l(z2
SlnhEdk
)mshcdk - l ( z l I] (A@ donia, Skopje, working in the Telecommunication and Information
Systems Departments. He worked on a number of projects involving
Equations (A5) to (A8) yield the z-component of the radio systems, PLC and electromagnetic compatibility related problems
electric field in (18). This expression excludes the field and specialized computer software development. He was a Head of the
contributions from the point charges at the endpoints of Information System Department from 1985. In 1988, he joined the
the line segments, since these charges disappear when two Faculty of Electrical Engineering at the University of Skopje, and is now
an Associate Professor of Electrical Engineering. His present research
segments are connected. Such charges are also neglected interests are in computational electromagnetics applied to grounding and
in case of a segment with no connected end point. It is interference.
assumed that the longitudinal current at the open endpoint Dr. Grcev is a member of IEEE PE, AP,M?T, EMC, MAG and E1
is zero. Since the point charges there are equal to -IJjco, Societies. He is also a member of the Applied Computational Electro-
they are also zero. It should be noted that this assumption magnetic Society.
only applies on the longitudinal current at the segments
open endpoint and not on the radial or leakage current.
The same procedure can be repeated for the p-com-
ponent of the electric field. This will yield

(A91
The p-component of the electric field in (18) follows
from (AS) and (A6) to (A8).
1848
DISCUSSION The actual current, on the other hand, was only about
30 A.
Abdul M. Mousa (B.C. Hydro, Vancouver, Canada. I wish to
congratulateDr. Menter and Dr. Grcev for an interestingpaper.
My comments pertain to soil ionization, a factor which is REFERENCES
significant in case of concentrated electrodes, especially where
soil resistivity is high. In this connection, it should be noted [25] A.M. Mousa, The Soil Ionization Gradient Associated
that Oettles work [13]has been superseded by Mousas recent with Discharge of High Currents into Concentrated
paper [25]. The main findings as they pertain to this paper are Electrodes,IEEE Paper No. 94 WM 078-6PWRD.
as follows: [26] E.E. Oettle, The Characteristics of Electrical
Breakdown and Ionization Processes in Soil,Trans.of
1. The mechanism of breakdown of the soil indicates that no the South African IEE, pp. 63-70,December 1988.
direct correlation exists between the ionizationgradientE,,,,
and the resistivity p (or the conductivity)of the soil. That Manuscript received February 22, 1994.
fact is proven by the scatter in the relation between K,,,
and p observed by Oettle [26]. Please see Fig. 14.

20 F.P. DAWALIBI, Safe Engineering Services &


2 15
technologies Itd., Montreal, Quebec, Canada,
v
10
H3M 1G4. The authors should be commended for an
+ excellent paper illustrating the use of transmission line
w s
theory and its integration with the EMTP transient
d o
program. There is an urgent need for technical
RESISTIVITY (nm ) contributions in the area of transient performance of
SAND 0 RED CLAY 0 BLACK CLAY + MIXTURE x
grounding systems in order to help refine the various
analytical methods in use and determine the domain of
Fig.14. Relation between the ionization gradient and their validity by comparing their computation results.
resistivity of the soil according to Oettle.
One major simplification of this transmission line
approach is the neglect of the inductive, capacitive
2. E,,,, is mainly govemed by the water content of the soil. and perhaps the conductive coupling between the
3. Due to inhomogeneity of the soil, K,,,varies from point to conductor segments of the ground network.
point along the electrode. The effective value of &,,is
According to the authors, this neglect does not lead to
not the average of the subject values, but is rather equal
to the minimum value encountered along the electrode. significant errors. This conclusion may not be valid at
4. For practical applications, the value of the ionization all frequencies and for a l l ground grid configurations.
gradient should be taken equal to 300 kV/m. Based on the Indeed our own investigations [ 1,2] have revealed
above, equations (14)and (16)should be replaced by: that coupling from aboveground conductors and loops
may affect results even at low frequencies. Is the
E,,, = 300 kV/m ...(14.1)
authors conclusion based on extensive simulations or
qff= (p/6007r)(ailax) ...(16.1) simply the result of a limited number of tests on
simple ground configurations?
where ( W a x ) is in kA/m, and p is in Qm.

5. With typical water content, the value of the relative


[l] F.P. Dawalibi, W.K. Daily, Measurements and
permittivity of the soil should be around 10 or even Computations of Electromagnetic Fields in Electric
higher. The values shown in Figs. 7 and 8 are reasonable. Power Substations, Paper No. 93 WM 220-0 PWRD
On the other hand the value 1 used in part B of Section V T-PWRD, Presented at IEEE PES 1993 Winter
is not realistic. Meeting in New York, New York.
6. It should be noted that soil ionization was not present in
the examples given in Figs. 7 and 9, because the
amplitudes of the currents were too small. In the case of [2] W. Xiong, F.P. Dawalibi, Transient Performance
Fig. 7 in which a 6 m long rod is located in a soil having of Substation Grounding Systems Subjected to
p = 40 !Jm , the minimum current needed to initiate Lightning and Similar Surge Currents, Paper No. 94
ionizationwould be as follows: WM 139-6 PWRD, Presented at IEEE PES 1994
Winter Meeting in New York, New York.
a) About 1.4 KA if eqn. (14.1)is used.
b) About 2.5 KA if eqn. (14)is used. Manuscript received February 22, 1994.
1849
DR. FRANK E. MENTER, PROF. DR. LEONID authors' conclusion for the accuracy of the results is
GRCEV: The authors thank Messrs. A. M. Mousa and based on comparisons with field measurements
F. P. Dawalibi for their kind words. We are especially performed by the EDF, Paris, France. An extensive set
gratefbl to Mr. Abdul M. Mousa for his discussion, of experiments had been performed in Les Renardibres
which enhanced the quality of our paper. His remarks in 1976-78 and in St-Brieuc in 1985. All experiments
on recent findings in the experimental analysis of had been repeated to cover any seasonal and weather
breakdown phenomena are appreciated. Since we did effects. Among the grounding arrangemets under study
not perform such analyses ourselves, we had to adopt were vertical ground rods, horizontal earth electrodes,
one model available though the literature. So, we chose hemispheres, grids, star- and serpentine-shaped
Oettle's model which lead to equations (14) and (16). electrodes and tower footings. Further reference on the
Since the model Mr. Mousa now proposes (eqns. measurements can be found in [20]. The comparison
(14. l), (16.1)) is even less complicated, its introduction has been performed in Paris in 1992/93 and has been
is feasible and we are delighted to incorporate his documented in [15]. However, it is true that the
suggestion into our procedures. investigated earthing structures do not include larger
grids; the validation for such structures has been
achieved by comparison with a separate program
Regarding the questions raised by Mr. Farid F.
developed by the second author, implementing a
Dawalibi, it should be noted that the aim of this paper
rigorous electrodynamic approach. Additional checks
was to demonstrate that the transmission line approach
and analyses of large structures with conductors above
for grounding system analysis integrated within the
ground may be subject of a future paper.
EMTP could lead to practically useful results. The

Manuscript received May 3, 1994.

You might also like