LMR PLUS Electric Fire Pump Controllers 1-1

Features
FD80 Reduced Voltage - Wye Delta (Star-Delta) Closed Transition July 2011

LMR
Power I/O Board Membrane Keypad
Transformers Door Mount
S Incoming line voltage is run directly to the I/O The membrane keypad is accessible from the
PLU board from the incoming lines. The I/O board front door of the controller.
will accept voltage inputs between 100 and
600V.

Customer Connection Terminals


Connection terminals for external customer
connections, are located at the top of the Power
I/O board.

Product Description
NEMA Rating
The FD80 LMR Plus Controllers use a method The standard membrane keypad is rated for
of connecting the pump motor windings into NEMA 2, 3R, 4, 4X and 12.
wye configuration to start, then switching to a
delta configuration to run. Alarm & Status LEDs
This reduces the starting current of the motor Output Relays A total of 20, ( 10 Status - 10 Alarm ) LEDs
significantly. Five, 8 Amp, 2 Form - C (DPDT) output relays provide indication on the membrane keypad.
Wye-Delta starting is the only method that has a are provided standard on each power I/O board.
starting torque efficiency of 100%. The FD80 They are designated for: Common Alarm, Status LEDs Alarm LEDs
can be programmed for either fully automatic or Phase Failure, Phase Reversal, Pump Run and Power On Phase Reversal
semi-automatic operations. Future #1. Each socket has an LED mounted on Pump Running Phase Failure
the I/O board which indicates each relays coil Local Start Fail To Start
The use of an embedded web page for status.
retrieving diagnostics and history reports, along Remote Start Undervoltage
Deluge Valve Overvoltage
with USB and Ethernet communication ports for Optional Output Relay Boards Emergency Start Low Room Temperature
downloading data, make the LMR Plus Series of There is provision to add up to eight additional Interlock On Locked Rotor Trip
controllers easy to troubleshoot and maintain. relay outputs, via optional relay output boards. Low Pressure Low Suction Pressure
As well, critical information can be easily Each board contains a maximum of 2 additional Auto Shutdown Enabled Source 2 Disconnected
accessed and used for report generation and relays. The Power I/O Board will accept a Programmable LED # 1 Programmable LED # 2
analysis, which aids in providing effective, maximum of 4 optional boards which mount in a
reliable fire protection. snap-on configuration. Silence Button
Each board provides an area for the user to A silence pushbutton on the membrane can be
Product Features label the terminal number and relay name. used to silence the buzzer. When an alarm
Logic Controller Board condition exists, the alarm buzzer will sound. If
Communication Drain Valve Solenoid the Silence Alarm button is pressed, the alarm
The controller can be ordered with the option to All LMR Plus electric controllers are equipped buzzer will turn off. If a subsequent alarm
display and output current values and status, on with a drain valve solenoid used for weekly test condition occurs after the silence button is
command, from various software protocols purposes. pressed, the buzzer will re-sound. Pressing the
through the appropriate port(s). Silence Alarm button again, will silence the
buzzer.
Embedded Web Page USB External Drive
The web page is a multifunction tool that allows General Motor Test Button
the user to view the controllers current status, When using an external USB Drive, the drive The motor test button on the membrane can be
data values, programmed set points and history. should conform to the following specifications: used to simulate an automatic start.
It is accessed using the optional ethernet port.
Min: 128mb Automatic Shutdown Enabled
Ethernet Port Max: 2 Gig FAT16 protocol When the Automatic Shutdown function is
An optional Ethernet port can be used for direct USB 1.0 or 2.0 enabled, a Green LED will indicate on the
connection to a computer for data transfer. controller membrane.

RS485 Serial Port NEMA 2 Enclosures Standards & Certification


An optional RS485 serial port can be provided All LMR controllers come standard with NEMA 2
for communication to various external software enclosures unless otherwise ordered. Available The LMR Plus Electric Fire Pump Controllers
programs. options include: NEMA 3R, 4, 4X, 12. meet or exceed the requirements of
Underwriters Laboratories, Underwriters
USB Port / USB Drive Emergency Start Operator Laboratories Canada, Factory Mutual, the
The logic controller board is equipped with a A mechanically operated Canadian Standards Association, New York City
USB port that can be used to transfer data to emergency start handle building code, CE mark and U.B.C / C.B.C.
and from a portable USB Drive device (memory activates the motor Seismic requirements, and are built to NFPA 20
stick). contactor independent of standards.
any electrical control
Buzzer circuits or pressure
A buzzer is mounted on the logic board which switch input.
will operate if Fail to Start, Hardware N. Y. C.
SEISMIC QUALIFIED
U.B.C and C.B.C

Malfunction or any Common Alarm condition APPROVED

exists. Must Be Installed Per Applicable Code


and Manufacturers Recommendations

For more information visit: www.chfire.com BR05805052K/G


LMR PLUS Electric Fire Pump Controllers 1-2
Features
FD80 Reduced Voltage - Wye Delta (Star-Delta) Closed Transition July 2011

Firmware Update Language


Product Features Firmware revisions are updated from an The language sub-menu allows the user to select
external USB drive. All previously programmed English, French, Spanish or Other languages to
Main Display settings will remain intact when updating is be viewed on the LCD Display. Several other
General completed. Should there be an update failure, languages can be uploaded into the controller.
The main display will show the current system the controller will automatically revert back to Contact the factory for details.
pressure, time and date, voltage and amps the previous version of firmware.
reading for all three phases, the system Regional
frequency and any custom messages, alarms Regional settings include the ability to program
or timers. Embedded Web Page the date by adjusting the Month, Day, Year and
General Day of Week. As well, the Current Time can be
The embedded web page is a multifunction tool adjusted on the 24 hour clock.
that will allow the user to view the current status
of the controller as well as display all current Pressure
readings, set points, A variety of pressure settings can be
and history. An external programmed in the pressure sub-menu. These
computer can be settings include disabling the pressure
connected via the transmitter; setting of the start point, stop point,
Programmed Set-Point optional Ethernet low pressure alarm, high pressure alarm, stop
The set-point display will show programmed port to access the mode, proof pressure switch (for foam units), low
pressure start point, pressure stop point and page. When suction shutdown (low foam shutdown), pressure
weekly test timer setting. connected, the deviation and hourly pressure recording. Refer to
controller set the LMR Plus operation manual IM05805020K
Statistics points can be for details.
The statistics display will allow the user to programmed
scroll through all of the measured statistics via the webpage. Timers
stored in memory. Refer to LMR Plus operation Timers in the LMR Plus that can be programmed
manual IM05805020K for specific details. include: Run Period Timer (RPT), RPT Start
Multiple Pages Mode, Acceleration Timer (AT), Weekly Test
Diagnostics There are 5 viewable pages that show the Main Timer, Fail to Start Timer (FST) and Sequential
The diagnostics display allows the user to Display, Statistics, Diagnostics, History and Start Timer (SST). Refer to the LMR Plus
Programmed Set Points. operation manual IM05805020K for details.
scroll through various diagnostic points to
assist with troubleshooting the system.
Pressure Points Alarm Set Points
The pressure reports recorded in memory can There are five settable alarm points that can be
Message History programmed by the user. They include: Phase
The user will be able to scroll through all of the be graphed and/or sorted based on date and
time. Rotation, Over Voltage (OV), Under Voltage
messages stored in the memory of the (UV), Over Frequency (OF) and Under
controller with the most recent message being Frequency (UF). Refer to the LMR Plus operation
displayed first. Programmed Set Points
All of the programmed set points and their manual IM05805020K for details.
current status can be viewed via the webpage.
PRINT Menu
Description Custom Inputs / Outputs
Custom Messages There is provision on the Power I/O Board to
All fault and alarm information is sent to the
Users can create custom messages on a accept up to 9 additional inputs and 9 additional
USB and optional printer on demand, as well as
computer and upload to the controller using a outputs. Each of the inputs can be labeled using
the status of each output. The LMR Plus will
USB Drive (memory stick). Up to 10 custom one of 11 pre-set input descriptions or assigned a
store up to 10K events which are time and date
messages of up to 100 characters each, will custom description that is programmed by the
stamped. All information can also be retrieved
continuously scroll across the fourth line of the user. The optional outputs can be programmed to
and displayed on the LCD display.
LCD display once triggered. indicate up to 25 output conditions. As well, two
Saving to USB Drive optional alarm LEDs can be programmed for up
The controller will save four separate text files, to 12 alarm conditions.
one CSV file and the embedded webpage to the All optional inputs, outputs and LEDs can be
USB external drive. The files, at maximum size, linked, as required.
can be saved multiple times on one 128MB Inputs can be programmed to energize the
USB drive. common alarm output, link to relays and optional
Files to be saved are: Status Report, LEDs and latch until reset by the user.
Trigger Points Outputs can be programmed for fail safe and
Diagnostics Report, Statistics Report,
The message can be programmed to appear at latch until reset by the user.
Configuration File and Last 10K Messages.
specific trigger points such as specific date and Optional inputs and outputs can be programmed
time, specific number of operations, specific with time delay functions.
Print Menu
number of hours run or at any individual alarm
The optional printer menu is accessed in order
point.
to select the desired print function. System Configuration Menu
All of the trigger points can be selected as
Functions include: Print Messages, Last XX The system configuration menu section is
And/Or values.
Messages, Date & Time, Status Report, password protected and contains settings such
Diagnostics Report and Statistics Report. Programming Menu as system voltage, frequency, CT ratio etc. Refer
General to Technical Bulletin PU05805035K/D
Custom Messages The LMR Plus programming menu is divided for details.
When this item is selected, custom messages into 8 different sub-menus. Each sub-menu
can be cleared from memory or downloaded contains information relative to its particular Main Menu Password
from the USB external drive. function. Following is a brief description of each A password can be programmed by the user to
sub-menu. protect access to the Main Menu. Refer to the
LMR Plus Operation Manual IM05805020K for
details.

For more information visit: www.chfire.com BR05805052K/G


Pump and Plumbing for Fire Pump Controllers

Pump and Plumbing March 2010

Pump and Plumbing LMR


PLU
S

MD05805005K/B For more information visit: www.chfire.com


LMR PLUS Electric Fire Pump Controllers
Main Display
Main Display - LMR Plus Fire Pump Controllers March 2010

Main Display LMR


PLU
S

POWER ON PHASE REVERSAL LMR


PLU
S
PUMP RUNNING PHASE FAILURE
LOCAL START FAIL TO START
REMOTE START UNDERVOLTAGE
DELUGE VALVE OVERVOLTAGE
EMERGENCY START LOW ROOM TEMPERATURE
SILENCE
INTERLOCK ON LOCKED ROTOR TRIP
ALARM
LOW PRESSURE LOW SUCTION PRESSURE
MOTOR AUTO SHUTDOWN ENABLED SOURCE 2 DISCONNECTED
TEST

DATA
PRINT

LAMP
TEST MENU

RESET
SAVE/EXIT

ACK.
99-5816-01

NOTES:
1. Refer to the LMR Plus technical manual for detail and setup
information, as well as programming and custom labelling for
Programmable LED # 1 and Programmable LED # 2.

N. Y. C.
APPROVED

NOTE: As of January 1, 2009 - All Limited Service Controllers will not carry FM Approval.
MD05805096K/C For more information visit: www.chfire.com
LMR PLUS Electric Fire Pump Controllers
Dimensions
FD80 Wye-Delta (Star Delta) Closed July 2011

Dimensions
Standard Enclosure - Type NEMA 2, 3R, 4, 4X, 12
LMR
PLU
S

34.57 [878] 28.36 [720]


12.50 [317] 16.00 [406]

3A13357H01 3A13357H01

64.00
[1626] START

STOP

74.00 62.00 [1575]


[1880]

1.75 [44]
5.25 [133]
2.63 [67]
12.00 [305]
6.00 [152]

10.50 [267] 5.00 [127]

PIPING ENTRANCE PIPING ENTRANCE


1 - START PUSHBUTTON 1/4" NPT - FEMALE 1/2" NPT - FEMALE
2 - STOP PUSHBUTTON
6
3 - MAIN POWER SWITCH
4 - MSH (EMERGENCY START HANDLE)
5 - MAIN LMR PLUS DISPLAY
6 - RECOMMENDED CABLE ACCESS (BOTTOM ONLY)
8.42
1.19 [30] 4.24 [108]
[214]

2.09 [53]
19.28 [490] 1.22 [31]
Dimensions in inches and [millimeters]. 3.32 [84]

Motor Hp Line Voltage Withstand Rating Approx. Weight


Standard Intermediate High Lbs. (Kg)
5 - 40 200 - 208V 100,000 150,000 200,000 375
(170)
5 - 50 220 - 240V
5 - 75 380 - 415V *
5 - 100 440 - 480V
5 - 100 550 - 600V 25,000 100,000
* Coils Available: 380V-50Hz, 380V-60Hz, 415V-50Hz, 415V-60Hz

SEISMIC QUALIFIED
NOTES:
U.B.C and C.B.C 1. All enclosures finished in FirePump red.
N. Y. C. 2. Cable Entrance bottom only.
APPROVED 3. Standard Enclosure type NEMA 2.
Must Be Installed Per Applicable Code
and Manufacturers Recommendations

MD05805091K/C For more information visit: www.chfire.com


LMR PLUS Electric Fire Pump Controllers
Electrical Wiring Schematic
FD80 Wye Delta (Star-Delta) Closed May 2011

Electrical Wiring Schematic


LMR
PLU
S

DELUGE VALVE (REMOVE JUMPER IF USED)

LOW ROOM TEMPERATURE


REMOTE START

INTERLOCK ON
LOW SUCTION
PUMP START

INPUT #1
INPUT #2
INPUT #3
INPUT #4
INPUT #5
INPUT #6
INPUT #7
INPUT #8
INPUT #9
CUSTOMER INPUTS

OPTION RELAY #1 OPTION RELAY #5


(2 SETS FORM-C) (2 SETS FORM-C)

OPTION RELAY #2 OPTION RELAY #6


(2 SETS FORM-C) (2 SETS FORM-C)

OPTION RELAY #3 OPTION RELAY #7


(2 SETS FORM-C) (2 SETS FORM-C)

OPTION RELAY #4 OPTION RELAY #8


(2 SETS FORM-C) (2 SETS FORM-C)

INTERNAL CONNECTIONS
COMMON ALARM
(NORMALLY ENERGIZED)

COMMON ALARM
(NORMALLY ENERGIZED)

PHASE FAILURE
(NORMALLY ENERGIZED)
ALARM CONTACTS

PHASE FAILURE
(NORMALLY ENERGIZED)

PHASE REVERSAL

PHASE REVERSAL

FUTURE #1

FUTURE #1

PUMP RUN

PUMP RUN

N. Y. C.
APPROVED

ES05805098K/D For more information visit: www.chfire.com


LMR PLUS Electric Fire Pump Controllers
Field Connections
FD80 Wye Delta (Star-Delta) Closed September 2013

Field Connections
LMR
PLU
S
Line Terminals (Incoming Cables)
Line Terminals on Main Isolation Switch (Incoming Cables)
LINE VOLTAGE Qty. & Cable Sizes Service Entrance GND. LUG
200 - 208 220 - 240 *380 - 415 440 - 480 550 - 600 Qty. & Cable Sizes
Max HP 25 30 40 60 75 (1)#14-1/0 PER (CU/AL) (1)#14-2/0 (CU/AL)
40 50 75 100 100 (1)#4-4/0 PER (CU) (1)#4-350MCM (CU/AL)
75 75 150 200 200 (1)#3-350MCM PER (CU/AL) (1)#4-350MCM (CU/AL)
100 125 200 250 300 (2)3/0-250MCM PER (CU/AL) (2)1/0-750MCM (CU/AL)
150 200 300 400 400 (2)250-350MCM PER (CU/AL) (2)1/0-750MCM (CU/AL)
200 - 350 450 550 (2)#1-500MCM PER (CU/AL) (2)1/0-750MCM (CU/AL)
250 300 500 600 700 (3)3/0-400MCM PER (CU/AL) (2)1/0-750MCM (CU/AL)
* Coils available: 380V-50Hz, 380V-60Hz, 415V-50Hz, 415V-60Hz.
Load Terminals (To Motor)
Load Terminals (To Motor)
Line Voltage Qty and Cable Sizes
200-208 220-240 380-415 440-480 550-600 Single Run Double Run
Max HP 15 20 30 40 50 (1) #14 - #8 PER (CU/AL) -
40 50 75 100 100 (1) #14 - #1 PER (CU/AL) -
75 100 150 200 150 (1) #8 - 3/0 PER (CU/AL) -
150 150 250 300 300 (2) #2 - 250MCM PER (CU/AL) (2) 1/0 - 250MCM PER (CU/AL)
250 300 500 600 700 (2) 1/0 - 500MCM PER (CU/AL) (2) 1/0 - 500MCM PER (CU/AL)

For ambient temperatures above 30C (86F), the temperature rating of motor conductors is recommended to be a minimum of 90C (194F)
For Proper Cable Size Refer to National Electrical Code NFPA-70

External Inputs Alarm / Relay Outputs Typical Controller Connection


COMMON ALARM
(NORMALLY ENERGIZED)

COMMON ALARM
(NORMALLY ENERGIZED)

PHASE FAILURE
(NORMALLY ENERGIZED)
ALARM CONTACTS

PHASE FAILURE
(NORMALLY ENERGIZED)

PHASE REVERSAL

PHASE REVERSAL

FUTURE #1
NOTE:
1. MOTOR CONNECTIONS VARY, PLEASE
REFER TO SPECIFIC MOTOR CONNECTION
FUTURE #1 DIAGRAM.
2. PLEASE OBSERVE PROPER PHASE
ROTATION, A,B,C-L1,L2,L3 AS CONTROLLER
IS PHASE SENSITIVE.
PUMP RUN 3. CABLE SIZE TO BE 125% OF FULL LOAD
CURRENT. REFER TO WIRE SIZE TABLE IN
NFPA 70.
PUMP RUN

N. Y. C.
APPROVED

ES05805099K/E For more information visit: www.chfire.com


LMR PLUS Electric Fire Pump Controllers
Electric Motor Connections
FD70 Wye Delta (Star-Delta) Open / FD80 Wye Delta (Star-Delta) Closed
FT70 Wye Delta (Star-Delta) Open / FT80 Wye Delta (Star-Delta) Closed

March 2010

Electric Motor Connections


LMR
PLU
S

W ye-D elta Low er N am eplate V oltage

N O TE :
1. M O TO R C O N N E C TIO N S V A R Y P LE A S E R E FE R TO S P E C IFIC
M O T O R M A N U F A C TU R E R 'S C O N N E C TIO N D IA G R A M .
2. FO R S IN G LE V O LTA G E 12 LE A D M O TO R S
U S E LO W E R V O LTA G E C O N N E C TIO N D IA G R A M

W ye-D elta H igher N am eplate V oltage

N O TE :
1. M O TO R C O N N E C TIO N S V A R Y P LE A S E R E FE R TO S P E C IFIC
M O T O R M A N U F A C TU R E R 'S C O N N E C TIO N D IA G R A M .
2. FO R S IN G LE V O LTA G E 12 LE A D M O TO R S
U S E LO W E R V O LTA G E C O N N E C TIO N D IA G R A M

N. Y. C.
APPROVED

ES05805100K/B For more information visit: www.chfire.com


Electric Fire Pump Controllers & Transfer Switches
Part Number / Options Selection Guide
FD / FT & FDF / FTF (Foam) - Electric Fire Pump Controllers March 2014

Part Number / Options Selection Guide LMR


PL
US
Electric Fire Pump Controllers & Transfer Switches

FD / FDF
FT / FTF

Model
FD / FDF = Stand Alone Controller
FT / FTF = Controller c/w Transfer Switch Options
A - Built-in Alarm System
Starting Type B - Alarm Bell
20 = Limited Service C1 - Extra Contacts "Pump Run" (Two Form-C)
30 = Across the Line C2 - Extra Contacts "AC Power Failure" (Two Form-C)
40 = Part Winding C3 - Extra Contacts "Phase Rev." (Two Form-C)
50 = Primary Resistor C4 - Remote Contacts (2 Form C) Low Reservoir
60 = Autotransformer C5 - Remote Contacts (2 Form C) High Reservoir
70 = Wye Delta (Star-Delta) Open COM - Communications Option
80 = Wye Delta (Star-Delta) Closed CX - Extra Contacts (Two Form-C; Specify Function)
90 = Soft Start E1 - NEMA 3R - Raintight Enclosure
E2 - NEMA 4 - Watertight Enclosure
E3 - NEMA 12 - Industrial Dust Tight Enclosure
E5 - NEMA 4X - 304 Stainless Steel Enclosure
Horsepower E8 - Tropicalization
5 20 50 125 300 500 700 E9 - NEMA 4X - Painted Steel
7.5 25 60 150 350 550 E10 - NEMA 4X - 316 Stainless Steel Enclosure
10 30 75 200 400 600 EX - Export Crating
15 40 100 250 450 650 F2 - Floor Stand - 2 Inch Height**
* Higher Horsepowers not available on all H - High Withstand Rating (refer to tables)
models. Consult Factory for pricing. I - Intermediate Withstand Rating (refer to tables)
LX - Extra Light (Specify Description)
P5 - Proof Pressure Switch - ALCO 15-290 PSI
P7 - Low Suction Pressure Switch
Voltage P8 - Low Suction Shutdown (Requires P7)
A = 208V - 60HZ Language P10 - Pressure Transducer - Sea Water Rated
B = 240V - 60HZ L1 = English P13 - Externally Mounted Pressure Transducer**
C = 380V - 50HZ L2 = French R1 - Space Heater (120 / 220V)
D = 480V - 60HZ L4 = Italian R2 - Space Heater c/w Thermostat
E = 600V - 60HZ L5 = Spanish R3 - Space Heater c/w Humidistat
F = 415V - 50HZ L6 = Portuguese R4 - Low Pump Room Temperature Switch
H = 380V - 60HZ L7 = Chinese R5 - Space Heater (Externally powered - 120V)
J = 400V - 50HZ L8 = Polish USB- Externally Mounted USB Port
K = 400V - 60HZ L9 = Dutch X1 - Printer
G2 = 240V 60 HZ L11 = Turkish X2 - 4 Inch Chart Recorder ( 10 - 300 psi fresh water)
Single Phase* ** Not available for NEMA 4 or NEMA 4X units.
* Only available on Limited Service Controllers

SEISMIC QUALIFIED
U.B.C and C.B.C
N. Y. C.
APPROVED
Must Be Installed Per Applicable Code
and Manufacturers Recommendations

PA05805031K For more information visit: www.chfire.com


Fire Pump Controllers 1-1
Features

LMR Plus Electric Fire Pump Controllers

Typical Specifications 6. Microprocessor Control


A. The controller shall come complete with a 4 line by
1. Approvals 40 character LCD display mounted on a panel open-
A. The Fire Pump Controller shall meet the require- ing in the front door. The LCD display shall indicate
ments of the latest edition of NFPA 20 and shall be the following:
listed by [Underwriters Laboratories (UL)]and ap- 1. Main screen displaying system pressure, three-
proved by [Factory Mutual Research (FM)] [Cana- phase voltage and amperage readings, system
dian Standards Association (CSA)] [New York De- frequency, date, and time.
partment of Buildings (NYSB)] and carry the CE 2. Set point review screen displaying the pro-
marking for fire pump service. grammed pressure start and stop points, and
2. Starting Type weekly test time.
A. The controller shall be of the combined manual and 3. Controller statistics screen, including:
automatic type designed for [Full Voltage Starting] a. Powered Time
[Part Winding Starting] [Primary Resistor Starting] b. Motor Run Time
[Autotransformer Starting] [Wye-Delta (Star-Delta) c. Number of Calls to Start
Open Transition Starting] [Wye-Delta (Star-Delta) d. Number of Starts
Closed Transition Starting] [Solid State Soft Start e. Last Motor Start Time
Starting] f. Last Motor Run Time
3. Ratings g. Last Low Pressure Start
A. The Controller shall have a withstand rating of h. Minimum System Voltage
100,000 RMS symmetrical amperes @ [208V] [240V] i. Maximum System Voltage
[380V] [400V] [415V] [480V] [25,000 @ 600VAC]. j. Minimum System Frequency
4. Construction k. Maximum System Frequency
A. The controller shall include a motor rated combina- l. Minimum System Pressure
tion isolating switch and circuit breaker, mechanically m. Maximum System Pressure
interlocked and operated with a single externally n. Last System Startup
mounted handle. o. Last Phase Failure
B. The isolating switch shall be rated to disconnect the p. Last Phase Reversal
motor load. q. Last Locked Rotor Trip
C. The isolating switch/circuit breaker combination shall r. Maximum Run Current
be mechanically interlocked such that the enclosure s. Last Locked Rotor Current
door cannot be opened when the handle is in the on 4. Controller diagnostics screen, including:
position except by a tool operated defeater mechan- a. Date & Time
ism. b. Firmware Version
D. The controller manufacturer shall manufacture the c. Shop Order Number
contactor, isolating switch, circuit breaker, pushbut- d. Customer Order Number
tons, and enclosures. Brand-labeled components e. Transformer Output Voltage
will not be accepted. f. Current Transformer Outputs
5. Enclosure g. Pressure Transducer Calibrated Settings
A. The controller shall be housed in a NEMA Type 2 h. Input Status
(IEC IP11) drip-proof, powder baked finish, frees- i. Output Status
tanding enclosure. 5. Display last messages screen that will display
B. Optional Enclosures: up to 10,000 alarms/messages stored in the
1. NEMA 3R (IEC IP14) rain-tight enclosure. controllers' memory.
2. NEMA 4 (IEC IP66) watertight enclosure. 6. Display up to ten (10) custom messages of up to
3. NEMA 4X (IEC IP66) watertight 304 stainless 100 characters each, which will continually scroll
steel enclosure. across the fourth line of the display.
4. NEMA 4X (IEC IP66) watertight 316 stainless 7. Remaining time left on active timers.
steel enclosure. B. The controller shall be supplied with ten (10) green
5. NEMA 4X (IEC IP66) watertight corrosion resis- status LEDs for the following:
tant enclosure. 1. Power On
6. NEMA 12 (IEC IP52) dust-tight enclosure. 2. Pump Running
3. Local Start
4. Remote Start
5. Deluge Valve
6. Emergency Start

July 2011 For more information visit: www.chfire.com PS05805008K/E


Fire Pump Controllers 1-2
Features

LMR Plus Electric Fire Pump Controllers

7. Interlock On
8. Low Pressure 7. Programming Menu
9. Auto Shutdown Enabled A. The programming menu shall have the ability to ena-
10. Programmable LED #1 ble an entry password.
C. The controller shall be supplied with ten (10) red B. The programming menu shall be limited to two (2) le-
alarm LEDs to indicate the following: vels of password protection.
1. Phase Reversal C. The controller shall have three (3) languages as a
2. Phase Failure standard, English, French, and Spanish, with the
3. Fail to Start ability to add a fourth language.
4. Undervoltage D. The programming menu shall be grouped into 6 main
5. Overvoltage menu headings as follows:
6. Low Room Temperature 1. Regional Settings
7. Locked Rotor Trip 2. Pressure Settings
8. Low Suction Pressure 3. Timer Values
9. Source 2 Disconnected 4. Alarm Set points
10. Programmable LED #2 5. Input/Output Menu
D. The microprocessor logic board shall be available 6. System Configuration (password protected)
with: 8. Pressure Sensor
1. A USB port for transference of message history, A. A solid-state 4-20mA pressure sensor shall be pro-
controller status, diagnostics, and statistics and vided. The pressure Start and Stop points shall be
the ability to update firmware. adjustable in increments of one (1) PSI. A low pres-
2. An optional Ethernet port for direct connection to sure pre-alarm, indicated with a flashing green LED,
a computer for data transfer. shall denote a potential pump starting condition and
3. An optional RS485 Serial port for communica- will remain lit once the pump has started to indicate
tion to various external software programs. the starting cause.
E. The controller shall be available with an embedded 9. Custom Inputs/Outputs
web page to allow viewing of the controllers' current A. The controller shall come standard with nine (9) fu-
status, data values, programmed set points, and his- ture inputs, two (2) future LED indicators, and one (1)
tory. future output, with the ability to add up to another 8
F. A Fail-to-Start alarm shall occur if the motor control- outputs via optional relay boards.
ler sees less than 20% of the motor full load amps af- B. The user shall be able to program the future in-
ter an adjustable time delay of 1-90 seconds. puts/outputs through the main programming menu.
G. Locked rotor protection shall be provided. After a trip C. The inputs shall be selectable based on the following
condition and restoration of power, the LCD display criteria:
shall indicate LOCKED ROTOR TRIP. 1. User selected message or thirteen (13) prede-
H. A sequential start timer and weekly test timer shall termined messages.
be provided as standard. 2. Energize the common alarm relay when the in-
I. A restart time delay of two (2) seconds shall be pro- put is received.
vided to allow the residual voltage of the motor to 3. Link to a future relay and/or LED indicator.
decay prior to re-starting the motor. In the event that 4. Alarm latched until reset.
the pump motor continues to run after a request to 5. Normally open or closed input.
stop, then the controller must display a fail to stop 6. On-delay timer.
message to indicate this condition. D. The LED indicators shall be selectable based on the
J. Overvoltage (5-20%) and undervoltage (5-30%) following criteria:
sensing and alarming shall be provided as standard. 1. Indication based on a minimum of twelve (12)
K. The controller shall be supplied with interlock and predetermined alarms or a custom input.
shutdown circuits as standard. A flashing green LED E. The future relays shall be selectable based on the
shall indicate an interlock on condition. following criteria:
L. Where shutdown of the pump(s) due to low suction 1. Output based on a minimum of twenty-seven
pressure is required, it shall be accomplished without (27) predetermined alarms, controller status or a
the addition of a separate panel or enclosure. The custom input.
LCD display shall indicate low suction shutdown. 2. Latched until reset.
Resetting of the condition shall be automatic or ma- 3. Energized under normal conditions.
nual as selected by the user. 4. On or off delay timer on the output.
M. Means shall be provided to test the operation of all
LEDs to ensure their functionality.

July 2011 For more information visit: www.chfire.com PS05805008K/E


Fire Pump Controllers 1-3
Features

LMR Plus Electric Fire Pump Controllers

10. Alarm Relays


A. All relays shall be of the plug-in type. An LED on the
relay panel shall indicate the energized state of the
relay. All relay contacts shall be rated @ 8A,
277VAC/30VDC. Two (2) sets of Form-C contacts
shall be provided for each of the following:
1. Phase Reversal
2. Phase Failure
3. Common Alarm
4. Future #1
5. Pump Run.
B. The Common Alarm and Phase Failure relays shall
be energized under normal conditions.
11. Audible Alarm Buzzer
An audible alarm buzzer, capable of being heard
while the motor is operating, shall operate if Fail to
Start, Hardware Malfunction or any Common Alarm
condition exists.
12. Manufacturer
A. The controller shall be of the LMR Plus type as man-
ufactured by Eaton Corporation.

July 2011 For more information visit: www.chfire.com PS05805008K/E