You are on page 1of 76

FIRESTOP GUIDE 2016

SAVING LIVES THROUGH


INNOVATION AND EDUCATION.
Hilti. Outperform. Outlast.
Available nearby.

WITH YOU EVERY STEP


OF THE WAY.

At Hilti, our people and products are with you every step of the way. From design to
construction, we help make your team more productive every day with expert
technical advice, reliable products, prompt delivery, ongoing research and
development, and outstanding service.

Fire Protection Specialists offer restop consultation and training


Fire Protection Engineers works directly with architects and engineers
to provide technical assistance and on-site problem solving
Engineering Back-ofce provides solutions and Engineering Judgments
for unique and complex applications

Project References
Hilti restop systems are used continuously worldwide in various types of projects.
Please contact your local restop specialist or Hilti center for international or local
project references.
Engineering Judgement
Hilti has performed extensive testing in both through penetration and constructio
joint applications. However, dueto variations in construction through out the
phases of a project, it is not possible to test every application that may been
countered. For these situations, Hilti has developed a process for creating custom
drawings to accommodateparticular applications. Hilti custom drawings, or
Engineering Judgements, are developed through the careful and restricted
application of accepted engineering principles and re protection guidelines set
forth by the IFC (International Firestop Council). Please contact your local Hilti
restop specialist ifyou require an Engineering Judgement solution.
Sample Written Specications
Sample written specications for restop are available in accordance to various
international standards. It includes allrequired specication details on restop
expertly laid out forspeciers and designers. Please contact your local Hilti Firestop
specialist for a copy of restop sample specications according to BS standard,
ASTM standard, or to any otherinternational standards.
MSDS
Material Safety Data Sheets for all Hilti restop systems are available if required.
Please contact your local Hiltirepresentative for details.

Test reports and approvals


Test reports and approvals according to ASTM E814 UL1479, UL2079, EN 1366,
DIN 4102, or any other international standard, or local approvals are available upon
request. Please contactyour local Hilti Firestop specialis for further details.

Support
Firestop Design Center Support Call 800-HILTI (44584)
Hilti Online
www.hilti.ae E: ae.contactus@hilti.com

1
Hilti Firestop Systems

Contents

About Hilti Firestop . . . . . . . . . . 2


Hilti and the Environment . . . . . . . . . . 3
Problems and Hilti Solutions . . . . . . . . . 4-6
Firestop Application Review . . . . . . . . . 7-9
Firestop approvals & testings . . . . . . . . . 10
Additional Attributes . . . . . . . . . .11

Product Information and Installation Instructions

Firestop joint spray CFS-SP WB . . . . . . . .12-13


Flexible restop sealant CP 606 . . . . . . . .14-15
Elastomeric silicone sealant CP 601S . . . . . . . .16-17
High-performance intumescent restop sealant FS-ONE MAX . . . . . . . .18-19
Firestop foam CP 620 . . . . . . . .20-21
Firestop foam CP 660 . . . . . . . .22-23
Firestop mortar CP 636 . . . . . . . .24-25
Firestop mortar CP 637 . . . . . . . .26-27
Firestop coating CP 670 . . . . . . . .28-29
Firestop block CFS-BL . . . . . . . .30-31
Firestop plug CFS-PL . . . . . . . .32-33
Firestop speed sleeve CP 653 . . . . . . . .34-35
Drop-in device CFS-DID . . . . . . . .36-37
Cast-In Firestop Device CP-680 . . . . . . . .38-39
Firestop wrap strip CP 648-E (endless) . . . . . . . .40-41
Firestop wrap strip CP 648-S (single) . . . . . . . .42-43
Firestop collar CP 643 N . . . . . . . .44-45
Firestop collar CP 644 . . . . . . . .46-47
Firestop putty pad CP 617 . . . . . . . .48-49
Firestop cable coating CP 678 . . . . . . . .50-51
Firestop cable coating (ablative) CP 679 A . . . . . . . .52-53
Dispenser foam CF125-50 . . . . . . . . . .54
Filling foam CF-F 750 . . . . . . . . . .54
Insulating foam CF-I 750 . . . . . . . . . .54
Smoke and acoustic sealant CP 506 . . . . . . . . . .55

Accessories . . . . . . . . . .56
Estimating Tables . . . . . . . .57-61
Engineering Judgments . . . . . . . .62-65
Legislation . . . . . . . .66-70
Hilti Firestop
Save lives, protect assets
and improve building performance.

Hilti. Outperform. Outlast. 1


Dedicated to Life Safety

Visit the local website for more information on products and services.
2
Hilti Firestop Systems

Hilti and the Environment.


Hilti supplies the construction industry Green building is a globally visible In addition, there are environmental
worldwide with technologically trend to increase the resource
superior products, systems and structures and, in some cases, of
services. We help our customers to be the comfort and well-being for their relocating key services - such as
successful by identifying future needs occupants. Green building is the added car travel if a local school is
and developing innovative solutions
with outstanding added value. All with which buildings use resources - safety and sustainable development
Hilti products are designed for energy, water, and materials - while communities have a common interest
exceptionally high performance and reducing building impacts on human in making sure that there are as
long life. In early product development health and the environment during the
we use ecological guidelines to select buildings lifecycle, through better site cause as little damage as possible.
both recyclable materials to be used in management, design, construction,
their manufacture and environmentally operation, maintenance, and removal.
friendly packaging materials. Positive effects of green building are
related to:
As one of the worlds largest The sustainability of sites can be
manufacturers of power tools, high 8 - 9 % decrease in operating costs
performance consumables (including 7.5 % increase in building values air sealing products by supporting the
6.6 % improvement in return on following important characteristics
protection systems) and integrated investment of a building: movement capability,
services, Hilti recognises the value 3.5 % increase in occupancy
of designing buildings to meet green 3 % rent increase Movement capability allows the
building standards. A great number Healthier and more motivated tracing of building movement. Firestop
of Hilti products and services help to employees properties of Hilti products are tested
comply with green building standards to various worldwide standards to
Fire Safety & Green Building
around the globe such as BREEAM,
HQE, DGNB and LEED. during the building phase. Water
bad for the environment. As well tightness aids in avoiding jobsite
Green Building Overview
as combustion products such as damage due to water penetration,
The building sector is one of the major carbon dioxide and sulphur oxides,
contributors to increasing global
CO2 emissions. Green building is
one important means to meet the
challenge of climate change while also the risk of land contamination from

owners. that may contain heavy metals.

www.hilti.com
3
The designers Problem

3.6

2.6

Visit the local website for more information on products and services.
4
Hilti Solution

www.hilti.com
5
Firestop and Fire Protection Systems

Firestop Sealants, Sprays


Firestop joint spray CFS-SP WB Page 12 - 13
Flexible restop sealant CP 606 Page 14 - 15
Elastomeric silicone sealant CP 601S Page 16 - 17
High-performance intumescent restop sealant FS-ONE MAX Page 18 - 19

Firestop Foams
Firestop foam CP 620 Page 20 - 21
Firestop foam CP 660 Page 22 - 23

Firestop Coating Systems and Mortars

Firestop mortar CP 636 Page 24 - 25


Firestop mortar CP 637 Page 26 - 27
Firestop coating CP 670 Page 28 - 29

Firestop Block and Plug Systems

Firestop block CFS-BL Page 30 - 31


Firestop plug CFS-PL Page 32 - 33

Firestop Cast-In and Sleeve Devices

Firestop speed sleeve CP 653 Page 34 - 35


Drop-in device CFS-DID Page 36 - 37
Cast-In Firestop Device CP 680-P and CP 680-M Page 38 - 39

Firestop Collars and Wraps

Firestop wrap strip CP 648-E (endless) Page 40 - 41


Firestop wrap strip CP 648-S (single) Page 42 - 43
Firestop collar CP 643 N Page 44 - 45
Firestop collar CP 644 Page 46 - 47

Firestop Putties

Firestop putty pad CP 617 Page 48 - 49

Cable Protection

Firestop cable coating CP 678 Page 50 - 51


Firestop cable coating (ablative) CP 679 A Page 52 - 53

Visit the local website for more information on products and services.
6
Product Information

Firestop Systems Application Review Application

Insulated metal pipes

Multiple penetrations
Plastic/glass pipes

Cables/cable trays

Metal ducts
Metal pipes

Joints
Page Description Features

12
Firestop Joint Spray Sprayable or apply by brush Contains no halogens,
(CFS-SP WB) Paintable solvents or asbestos so it is
safe to use and wont harm
Quick and easy installation the environment
mastic for construction with the Titan 600 or 1100
Water based formulation so
joints where higher Sprayers
movement is expected spills and over-spray clean
Meets 500 cycle up quickly and easily

14 Flexible Acrylic based formula Fast and easy clean-up with


Firestop Sealant Can be painted water
(CP 606) Available in foil pack (580 ml)
appearance
Tested up to 33% movement
sealant for joint and with 500 cycles in Fast and easy dispensing
through penetration accordance to UL 2079 and
applications ASTM 1966

16 Elastomeric Firestop Silicone based formula Allows for movement and


Sealant 1/4" depth systems vibration
(CP 601S) Available in foil pack (600 ml) Cost effective solutions
A single component Meets 500 cycle Fast and easy dispensing

requirements in joint Smoke, fume and water
for joint and through applications (ASTM E 1966 resistant
penetration applications and UL 2079) Meets Class I W Rating
requirements
18 FS-ONE MAX UL Listings for various One product to specify,
High Performance penetrating items purchase or inspect for most
Intumescent Several 1/4" depth systems applications
Firestop Sealant Available in foil pack (600 ml) Low cost per penetration
A water-based Quick and simple installation
sealant, designed procedure
to expand when exposed
to heat

20 Fire Foam One stop application One solution for various


CP 620

sodfm,ev

4i5kirdwi
Brandsc

u9+ 12oeoo
hutzbes
iJdjwhri

loi4jtf-
uh. N

x-.vbvbv
oWE
chichtu

h, ireiv
ng
(CP 620) Virtually impervious to smoke applications

Fully cures in approximately


solution for common 1 minute reach applications
construction materials. Excellent mold resistance

No additional materials
Can also be used in required Meets Class I W Rating
conjunction with CP 648E requirements
Wrap Strip High yield

22 CP 660 BS approvals for various One product to specify,


High Performance penetrating items purchase or inspect for most
Expanding Sealant Suitable for openings up to applications

A water-based 300 x 300mm Low cost penetrations



Available in foil pack Quick and easy installation
sealant, designed to One side application procedure
expand when exposed Good for congested
to heat openings
24 CP 636 Good thermal insulating Suitable for wall applications
Firestop Mortar properties High yield
Fire resistant cement- Good adhesion to seal,
based mortar with thermal A cementitious mortar with concrete and masonry
insulating properties for

perlite Paintable
large openings

www.hilti.com
7
Product Information

Firestop Systems Application Review Application

Insulated metal pipes

Multiple penetrations
Plastic/glass pipes

Cables/cable trays

Metal ducts
Metal pipes

Joints
Page Description Features

26 Firestop Mortar Some applications require Economical and simple to


(CP 637) minimum 2-1/2" depth use
A dry powder, when Cleans up with water Fast and easy clean-up
mixed with water forms

a pourable, trowelable

be used in conjunction
with CP 648E Wrap Strip

28 CP 670 Lightweight design Easy to install; can be cut


Firestop Board with Variety of tested systems without power tools
Accessories Solutions for low and high
Ready to use Firestop penetrated openings

Board designed for large Solutions for congested
openings with cable trays areas
and multiple penetrations

30 Firestop Block Easy to install, reuse and


(CFS-BL) Easy to cut and shape repenetrate
An innovative and simple User friendly UL systems
around penetrating items
One-sided wall systems
designed to expand when available Reduces need for extra
exposed to heat labor, tools and parts
Non-curing
Easiest solution for large
openings with multiple
penetrations

32 Firestop Plug Soft Flexible Design Fast and cost effective


(CFS-PL) Versatile in use installation
A pre-sized, intumescent Non-curing Provides temporary or


openings and cable Reusable
penetrations

34 Speed Sleeve Fast installation Easy penetration and


(CP 653) Low L-ratings re-penetration
Re-penetrable cable Can be installed in wall and Withstands the rigors of
management device for usage and time

electrical and telecom
professionals

36 Firestop Drop-In Integrated moisture and


Device smoke seal inspectors
(CFS-DID) Quick and simple installation Solution for renovation/

construction
for a variety of
pipe materials and Buy American compliant
diameters

Visit the local website for more information on products and services.
8
Product Information

Firestop Systems Application Review Application

Insulated metal pipes

Multiple penetrations
Plastic/glass pipes

Cables/cable trays

Metal ducts
Metal pipes

Joints
Page Description Features

38 Cast-In Firestop Quick and simple installation Ready to use no


Device Integrated moisture and additional caulk required
(CP 680-P) smoke seal Easy to specify, install and
A one-step cast-in inspect

thicknesses from 2-1/2" Cost effective solution
variety of pipe materials (63 mm)
and diameters Innovative adapter for metal
deck applications
38 Cast-In Firestop Quick and simple installation Ready to use no
Device Integrated moisture and additional caulk required
(CP 680-M) smoke seal Easy to specify, install and
inspect

device for a wide variety thicknesses from 2-1/2" Cost effective solution
of non-combustible pipe (63 mm)
materials and diameters Innovative adapter for metal
deck applications
40 Firestop Wrap Strip May be continuously No need to measure
(CP 648E) wrapped each layer for multi-wrap
Flexible applications

Versatile Easy to use



and insulated pipe May be used inside the
penetrations annular space or outside of
nd
sch
utz
ma

oW
nsc

E
h. the substrate
8 Bra . N uze
64 riuh 7
CP wh 0288u2vh, ireiv
v iJdj bvb
fm,e p3i4 x-.v
sod 23aw jtf-
Z8Z irdwiloi4
4i5k 12oeoo
u9+

42 Firestop Wrap Strip Pre-measured no cutting Easy installation


(CP 648S) required User friendly
Integrated fastening tape Saves time and labor costs
No special tools required

pipe penetrations

44 Firestop Collar Ready-to-use out of package Simple and quick installation


(CP 643N) Adjustable mounting tabs Flexibility in positioning of
collar
device designed to Allows for correct installation

collapse plastic pipe in tight areas
penetrations when

Firestop Collar Ready-to-use out of package Simple and quick installation


46
(CP 644) Adjustable mounting tabs Flexibility in positioning of
collar
device designed to Allows for correct installation

collapse plastic pipe in tight areas
penetrations when

48 Firestop Putty Pad Pad sizes 6" x 7", 7" x 7" or Fits most common electrical
(CP 617, CP 617 L and 9" x 9" boxes (refer to UL listings)

CP 617 XL) 1 and 2 hour systems Only one pad to stock and
Tested for wood and steel install
A moldable putty sheet
studs Can be used for commercial
designed to help protect
and residential applications
electrical outlet boxes

www.hilti.com
9
Approvals and Testings

Firestop products Approvals and Testing

CPS - SP-WB
FM EN 1364-4 EN 1366-4
APPROVED

CP 606 FM EN 1366-3 EN 1366-4


APPROVED

CP 601S FM EN 1366-4
APPROVED

FS ONE MAX FM
APPROVED

CP 620 FM EN 1366-3
APPROVED

CP 660 EN 1366-3

CP 636 FM EN 1366-3
SPECIFICATION TESTED

CP 637 EN 1366-3

CP 670 FM EN 1366-3
SPECIFICATION TESTED

CFS -BL FM EN 1366-3


APPROVED

CFS -PL FM EN 1366-3


APPROVED

CP 653 FM EN 1366-3
APPROVED

CFS -DID FM
APPROVED

CFS -680 FM EN 1366-3


APPROVED

FM EN 1366-3
CP 648-E
APPROVED

CP 648-S FM EN 1366-3
APPROVED

FM EN 1366-3
CF 643 N
APPROVED

CF 644 FM EN 1366-3
APPROVED

CF 617 FM EN 1366-3
APPROVED

CF 678 FM IEC-60332
APPROVED

CF 679 A FM IEC-60332
APPROVED

Visit the local website for more information on products and services.
10
Additional Attributes

Protecting against more than just re.


Improving building performance tested and certied.
In addition to their superior behavior in passive fire protection, Hilti high-quality firestop systems enhance
the performance and quality factor of a building in many more areas. They meet the requirements in
building technology which continue to gain significance for designers and building owners.

Improving seismic performance


Hilti firestop products are tested for their performance in seismic events and help to
reduce the risk of post-earthquake impacts.

Avoiding the risk of mold and mildew


Hilti firestop products are fungus resistant, thus alleviating the effects of surface
moisture on the building.

Improving acoustics
Sound insulation is of great importance to the health and well-being of the occupants
of a building. Hilti firestop products are tested for this purpose and individually tailored
to the requirements of the installation and building structure.

Electrical resistance
Hilti has had the surface resistance and volume resistivity of fully cured and hardened
firestop products tested for high electrical resistance in order to ensure that the firestop
seal presents no hazards to the persons concerned.

Chemical Resistance
Hilti Firestop products have excellent resistance against chemicals. Chemical resistance
is very important when working in environment were accidental spillage or concern of
restops coming in contact of chemicals is expected.

Thermal Insulation
Hilti Firestop products are also tested and can act as thermal barrier between
compartments. Thermal Insulation is an important part when it comes to
areas/compartments with variable temperature.

Smoke and Gas Tightness


Hilti Firestop products are Smoke and Gas tight. The smoke and gas-tightness of
restop products is of decisive importance in the event of re as it may save lives.
The requirements to be complied with in terms of smoke and gas-tightness are laid
down in various laws and regulations.
Water resistance
Water resistance is an important ancillary element of firestop systems. Hilti firestop
systems are not merely tested and approved in accordance with international firestop
requirements, but have also been tested for their water-resistant properties according
to the valid national and international standards.

Explosion resistance
Many building materials, building elements and penetration seals are significantly less
endangered to static loads than to short-termed dynamic loads. Hilti Products were tested
against the more critical type of load, which is the quick impact load similar to a detonation
The tests to evaluate explosion resistant building components and building component
sealing were conducted according to prEN DIN 13123-1 and prEN DIN 13124-1.

Supporting green building standards


Hilti products meet stringent environmental requirements, thereby supporting
environmentally friendly building construction. Health, safety and environment profiles
are available with references to LEED and BREEAM standards.

www.hilti.com
11
Product Information

Firestop Joint Spray (CFS-SP WB)

Product description
Product features
maximum movement is required Sprayable or apply by brush or trowel

Areas of application Approval) (ASTM E 1966 and UL 2079)
Top-of-wall joints Quick and easy installation with the Titan 600 or 1100
Curtain wall/edge of slab Sprayers can help save you time and money
Expansion joints Contains no halogens, solvents or asbestos
For use with Water based formulation so spills and over-spray clean up
Concrete, masonry and gypsum wall assemblies quickly and easily
Paintable
Meets LEED requirements for indoor environmental quality
Examples credit 4.1 Low Emitting Materials, Sealants and Adhesives
Where a gypsum wall assembly meets the underside of a metal or and 4.2 Paints and Coatings
concrete deck

wall (concrete, glass, etc.) Technical Data* CFS-SP WB


Density Approx. 10.8 lb/gal (1.3 g/cm3)
Color Available in red, white and gray**
Application temperature 39F to 104F (4C to 40C)
Temperature resistance -40F to 176F (-40C to 80C)
Consistency Sprayable liquid
Chemical basis Acrylic-water-based-dispersion
Curing time Approx. 24 hours @ 73F,
50% humidity for 1/8" (3mm) depth
Average volume shrinkage 51.1%
(ASTM C1241)
Ph-value Approx. 8-9
Movement capability Up to 50%
Surface burning characteristics Flame spread: 15
(CAN/ULC-S102) Smoke development: 10

Shelf life1) 12 Months

LEED VOC 73 g/l

59
(ASTM E 90-99) (per tested construction type)
Tested in accordance with
UL 2079 ASTM E 1966 ASTM E 84 ASTM E 2837
UL 1479 ASTM E 814 ASTM E 2307
*At 73F (23C) and 50% relative humidity
**Gray color requires six (6) weeks lead time
Internationally Tested and approved

FM EN 1366-3 EN 1366-4
APPROVED

Visit the local website for more information on products and services.
12
Product Information

Ordering designation Volume per unit Sales pack Item number


quantity
CFS-SP WB red 19000 ml 1 pc 430815
CFS-SP WB white 19000 ml 1 pc 430816

Installation instructions for Firestop Joint Spray CFS-SP WB


Notice
Before handling, read Material Safety Data Sheet and 3. Application of Firestop Joint Spray: Apply Firestop 5. Identication: For maintenance reasons all Firestop
product label for safe usage and health information. Joint Spray to the required depth in order to obtain Joint Spray applications can be permanently marked
Instructions below are general guidelines always the desired rating. Make sure Firestop Joint Spray with an identication plate and fastened in a visible
refer to the applicable drawing in the UL Fire contacts all surfaces and overlaps beyond all position next to the seal.
Resistance Directory or Hilti Firestop Systems Guide surrounding surfaces (Refer to UL System). Titan
Sprayers have been successful in applying Firestop Not for use
for complete installation information
Joint Spray. Hilti recommends the use of the Titan In areas immersed in water
Opening 600 (for application temperatures above 50F) or On hot surfaces (above 176F) (80C)
1. Clean the opening. Surfaces to which Firestop Joint
Firestop Joint Spray may also be brushed on with a Storage
Spray will be applied should be cleaned of loose
paint brush. Contact Hilti Technical Support for more Store only in the original packaging at temperatures
debris, dirt, oil, wax and grease. The surface should
information. 39F to 77F (4C to 25C)
be moisture and frost free.
4. Curing time: Allow approx. 24 hours for typical Observe expiration date on package
Application of Firestop Joint Spray application thickness (@ 73F / 23C) 50% humidity
2. Mineral wool packing: Install the prescribed back for 1/8" depth for the Firestop Joint Spray to fully
lling material type and depth to obtain desired cure.
rating.

1. Clean opening 2. Pack in mineral wool 3. Spray or brush on 4. Allow Firestop Spray
compressed per UL Firestop Spray to cure (if required)
System

www.hilti.com
13
Product Information

Flexible Firestop Sealant (CP 606)

Product description
Product features
Silicone free
applications Halogen, asbestos and solvent free
Paintable
Areas of application Tested up to 33% movement with 500 cycles in accordance to
Sealing construction/expansion joints UL 2079 and ASTM 1966
Top-of-wall joints Smoke and fume resistant
Metal pipes Easy clean up with water
Cable bundles Single component systems available
HVAC penetrations Meets LEED requirements for indoor environmental quality
For use with credit 4.1 Low Emitting Materials, Sealants and Adhesives and
4.2 Paints and Coatings
Various base materials such as masonry, concrete, gypsum, etc.

Examples Technical Data* CP 606


Where a gypsum wall assembly meets the underside of a metal or Chemical basis Acrylic based restop sealant
concrete deck
Color Available in red, white and gray

Application temperature 40F to 104F (5C to 40C)


toxic fumes
Skin-forming time Approx. 15 min

Curing time Approx. 3 mm / 3 days


Average volume shrinkage 22.2%
(ASTM C1241)
Movement capability Approx. 10%
Temperature resistance 22F to 176F (30C to 80C)

Surface burning characteristics Flame Spread: 10


(ASTM E 84-96) Smoke Development: 0

Sound transmission classication 56


(ASTM E 90-99) (Relates to specic construction)

Shelf life1) 24 Months

LEED VOC 75 g/l

Base materials Concrete, Masonry,


Drywall, Steel

Tested in accordance with


UL 2079 ASTM E 814 ASTM E 1966
ASTM E 84 UL 1479 ASTM G21
*At 73F (23C) and 50% relative humidity

Internationally Tested and approved

FM EN 1366-3 EN 1366-4
APPROVED

Visit the local website for more information on products and services.
14
Product Information

Ordering designation Content per can/cartridge Volume per unit Sales pack Item number
quantity
CP 606 310ml white 310 ml 310 ml 1 pc 209625
CP 606 310ml INT grey 310 ml 310 ml 1 pc 209630
CP 606 580ml white 580 ml 580 ml 1 pc 209632
CP 606 5GAL white 19000 ml 19000 ml 1 pc 209637

Related Products

Dispensers CP 670 Collars CP 643, CP 644 Wraps CP 648-S, CP 648-E


page no 56 page no 28 page no 44-46 page no 40-42

Installation instructions for CP 606


Notice 4. Smooth restop sealant with a trowel before the skin forms.
Before handling, read Material Safety Data Sheet and product Once cured, CP 606 can only be removed mechanically.
label for safe usage and health information. 5. For maintenance reasons, a penetration seal can be permanently
Instructions below are general guidelines always refer to the marked with an identication plate and fastened in a visible
applicable drawing in the UL Fire for complete installation position next to the seal.
information
Not for use
The use of backing material is recommended to control the
On areas immersed in water
sealant depth and help ensure assembly seal is complete
Storage
Opening Store only in the original packaging in a location
1. Clean the opening. Surfaces to which CP 606 will be applied protected from moisture at a temperature of 40F to
should be cleaned of loose debris, dirt, oil, wax and grease. 77F (5C to 25C)
The surface should be moisture and frost free. Observe expiration date on package

Application of restop
2. Insert ll of mineral wool or backer rod (as required).
3. Apply restop over backer rod.
JOINT

Firestop
System

1. Clean opening 2. Insert backing 3. Apply CP 606 4. Smooth CP 606


material compressed plate (if required)
per UL System
DUCT

Firestop
System

1. Clean opening 2. Insert backing 3. Apply CP 606 4. Smooth CP 606


material plate (if required)

www.hilti.com
15
Product Information

Elastomeric Firestop Sealant (CP 601S)

Product description
Product features
Halogen and solvent free
applications Asbestos free
Simple to use and apply
Areas of application
Good adhesion without use of a primer
Sealing construction/expansion joints
Smoke, fume, water and UV resistant
Top-of-wall joints
Excellent movement capability, meets 500 cycle requirements
Metal pipes
(ASTM E 1966 and UL 2079)
Cable bundles
Meets Class I W-rating requirements
HVAC penetrations
Meets LEED requirements for indoor environmental quality
For use with credit 4.1 Low Emitting Materials, Sealants and Adhesives and
Various base materials such as masonry, concrete, metal, glass, etc. 4.2 Paints and Coatings

Examples
Where a gypsum wall assembly meets the underside of a metal or
Technical Data* CP 601S
concrete deck Chemical basis Neutral elastic silicone
Density Approx. 1.25 g/cm3
toxic fumes Color Available in White, Gray
Application temperature 40F to 104F (5C to 40C)
Skin-forming time Approx. 15 min.
Curing time Approx. 2 mm / 3 days
Volume shrinkage Approx. 0 5%
Movement capability Approx. 25%
Temperature resistance 40F to 320F (40C to 160C)
LEED VOC 3 g/l

Shelf life1) 12 Months

Surface burning characteristics Flame spread: 0


(ASTM E84-96) Smoke development: 30

(ASTM E 90-97)
Tested in accordance with
UL 2079 ASTM E 814 ASTM E 1966
ASTM C 920 UL 1479 ASTM E 84 ASTM G21
*At 73F (23C) and 50% relative humidity

Internationally Tested and approved

FM EN 1366-4
APPROVED

Visit the local website for more information on products and services.
16
Product Information

Ordering designation Content per can/cartridge Volume per unit Sales pack Item number
quantity
CP 601S 310ML white 310 ml 310 ml 1 pc 310633
CP 601S 310ML grey 310 ml 310 ml 1 pc 310635
CP 601S 310ML red 310 ml 310 ml 1 pc 314268
CP 601S 600ML grey 600 ml 600 ml 1 pc 312111

Related Products

Dispensers
page no 56

Installation instructions for CP 601S


Notice Not for use
Before handling, read Material Safety Data Sheet and 5. For maintenance reasons, a penetration seal can be In areas immersed in water
product label for safe usage and health information. permanently marked with an identication plate and Not to be painted
Instructions below are general guidelines always fastened in a visible position next to the seal.
refer to the applicable drawing in the UL Fire Storage
Chemical resistance Store only in the original packaging in a location
Resistance Directory or Hilti Firestop Systems Guide At room temperature the cured silicone sealant is
for complete installation information protected from moisture at a temperature of 40F to
resistant for a short time to diluted (15%) acids and 77F (5C to 25C)
Opening lyes/alkalis as well as most commercially available
Observe expiration date on package
1. Clean the opening. Surfaces to which CP 601S will cleaning agents and disinfectants (except those
be applied should be cleaned of loose debris, dirt, containing iodine)
oil, wax and grease. The surface should be moisture Concentrated acids and lyes/alkalis destroy silicone
and frost free. rubber over time.
Solvents and mineral oils cause cured silicone to
Application of restop
swell. Consequently, proper functioning of the
2. Insert ll of mineral wool (or backer as required).
sealant should be checked after exposure to a
3. Apply restop over backer. solvent or mineral oil. Please contact your local sales
4. Smooth restop sealant with a trowel before the skin representative or the nearest Hilti center if special
forms. Once cured, CP 601S can only be removed requirements for chemical resistance have to be met.
mechanically.
JOINT

Firestop
System

1. Clean opening 2. Insert backing 3. Apply CP 601S 4. Smooth CP 601S


material compressed plate (if required)
per UL System
DUCT

Firestop
System

1. Clean opening 2. Insert backing 3. Apply CP 601S 4. Smooth CP 601S


material plate (if required)

www.hilti.com
17
Product Information

High performance intumescent restop sealant FS-ONE MAX

Product description
Product features
helps protect combustible and non-combustible penetrations for Smoke, gas and water resistant after material has cured
up to 4 hours re rating Contains no halogen, solvents or asbestos
Advantages
One product for a variety of common through penetrations Water based, easy to clean
Cost-effective and easy-to-use solution
W-rated systems available Paintable
Ethylene glycol-free Single component systems available
Industry leading VOC results Meets LEED requirements for indoor environmental quality
credit 4.1 Low Emitting Materials, Sealants and Adhesives and
Areas of application 4.2 Paints and Coatings
Steel, copper and EMT pipes
Insulated steel and copper pipes
Cable bundles
Closed or vented plastic pipes
HVAC penetrations Technical Data* FS-ONE
Chemical basis Water-based intumescent acrylic
For use with dispersion
Color Red
Application temperature 40F to 104F (5C to 40C)
Skin forming time Approx. 20-30 min.
Examples
Curing time Approx. 4 mm / 3 days

Average volume shrinkage 24.1%


construction (ASTM C1241)
Movement capability Approx. 5%
construction
Expansion rate (unrestricted) Up to 3-5 times original volume
Intumescent activation Approx. 302 F (150 C)

Temperature resistance (cured) 40F to 212F (40C to 100C)

Shelf life 1) 18 Months

LEED VOC 9 g/l

Surface burning characteristics Flame Spread: 0


(ASTM E 84-96) Smoke Development: 5

(ASTM E 90-99)
Tested in accordance with
UL 1479 ASTM E 814 ASTM E 84 ASTM G21
*At 73F (23C) and 50% relative humidity

Internationally Tested and approved

FM
APPROVED

Visit the local website for more information on products and services.
18
Product Information

Ordering designation Content per can/cartridge Volume per unit Sales pack Item number
quantity
FS-ONE MAX 10.1OZ CART 300 ml 300 ml 1 pc 2101534
FS-ONE MAX 20.0OZ FOIL 592 ml 592 ml 1 pc 2101535
FS-ONE MAX 5GAL PAIL 19000 ml 19000 ml 1 pc 2101536

Related Products

Dispensers Collars CP 643, CP 644 Wraps CP 648-S, CP 648-E CFS-BL CFS-PL


page no 56 page no 44-46 page no 40-42 page no 30 page no 32

Installation instructions for FS-ONE MAX


Notice 3. Application of restop sealant: Apply FS-ONE to the Not for use
Before handling, read Material Safety Data Sheet required depth in order to obtain the desired re rating. High movement expansion joints
and product label for safe usage and health Make sure FS-ONE contacts all surfaces to provide Underwater
information. maximum adhesion. For application of FS-ONE use a
On materials where oil, plasticizers or solvents may
Instructions below are general guidelines always standard caulking gun, foil pack gun, bulk loader and
bleed i.e. impregnated wood, oil based seals, green
refer to the applicable drawing in the UL Fire bulk gun. With FS-ONE buckets, Graco type sealant
or partially vulcanized rubber
Resistance Directory or Hilti Firestop Systems Guide pumps may be used. (Contact pump manufacturer for
proper selection). In any penetration other than those specically
for complete installation information described in this manual or the test reports
Opening 4. Smoothing of restop sealant: To complete the
seal, tool immediately to give a smooth appearance. Storage
1. Clean the opening. Surfaces to which FS-ONE will Store only in the original packaging in a location
be applied should be cleaned of loose debris, dirt, Excess sealant, prior to curing, can be cleaned away
from adjacent surfaces and tools with water. protected from moisture at temperatures between
oil, moisture, frost and wax. Structures supporting 40F (5C) and 77F (25C)
penetrating items must be installed in compliance 5. Leave completed seal undisturbed for 48 hours.
Observe expiration date on the package
with local building and electrical standards. 6. For maintenance reasons, a penetration seal could
be permanently marked with an identication plate.
Application of restop sealant
In such a case, mark the identication plate and
2. Install the prescribed backlling material type and
fasten it in a visible position next to the seal.
depth to obtain the desired rating (if required). Leave
sufcient depth for applying FS-ONE.
CABLE

Firestop
System

1. Clean opening. 2. Pack mineral wool. 3. Apply FS-ONE. 4. Smooth 5. Leave completed 6.
(If required) FS-ONE. seal undisturbed for plate (if required).
48 hours.
PIPE

Firestop Firestop
System System

1. Clean opening. 2. Pack mineral wool. 3. Apply FS-ONE. 4. Smooth 5. Leave completed 6.
(If required) FS-ONE. seal undisturbed for plate (if required).
48 hours.

www.hilti.com
19
Product Information

Fire Foam (CP 620)

Product description
Product features
Up to 6 times expansion of can yield
Areas of application Repenetrable
Sealing small to medium size openings Cures within 60 seconds
Cables and cable trays
Non-combustible pipes Paintable
Combustible pipes when used in conjunction with Hilti Wrap Strips Virtually impervious to smoke
Where cables, steel, copper, cast iron or plastic pipes all pass Mold resistant
through the same opening
No additional materials required
Execllent water vapor resistance
Concrete, drywall and masonry Meets LEED requirements for indoor environmental quality
credit 4.1 Low Emitting Materials, Sealants and Adhesives and
Examples 4.2 Paints and Coatings
Multiple penetrations
Insulated metal pipes

Technical Data* CP 620


Chemical basis Two component polyurethane
Color Red
Fire foam yield Up to 110 in3 (1.8 litre)
Application temperature Substrate: 32F to 104F (0C to 40C)
Product: 50F to 104F (10C to 40C)
Curing time* Non-tacky after Approx. 35 seconds
Ready to cut after Approx. 1 minute
Thermal insulation (R-value) 2.83.0 per inch of thickness
Temperature resistance of cured foam 22F to 212F (30C to 100C)

Shelf life1) 9 Months

LEED VOC 1.3 g/l

(ASTM E90-97)
Expansion rate (unrestricted) Up to 1.5-2 times original volume
Intumescent activation Approx. 482 F (250 C)
Surface burning characteristics Flame spread: 0
(ASTM E84-01) Smoke development: 15
Tested in accordance with
UL 1479 ASTM E 814 ASTM E 84
ASTM G21 CAN/ULC-S115
*At 73F (23C) and 50% relative humidity

Internationally Tested and approved

FM EN 1366-3
APPROVED

Visit the local website for more information on products and services.
20
Product Information

Ordering designation Content per can/cartridge Package contents Sales pack Item number
quantity
CP 620 US 300 ml 1x Cartridge, 2x Mixer, 1x Extension tube 1 pc 338725
Kit DSC kit 300 ml 1000x Dispenser DSC, 1000x Case, 4000x Firestop foam CP 620 GB-D-F-NL 1 pc 339132

assy, 8000x Mixer, 4000x Extension tube

Related Products

Dispensers CFS-BL CFS-PL


page no 56 page no 30 page no 32

Installation instructions for CP 620


Notice When dispensed quickly, the consistency of the Pieces of cured excess CP 620 Fire Foam which have
Before handling, read Material Safety Data Sheet and Fire Foam is more liquid allowing it to ow better been cut off can be laid in the next opening and fresh
product label for safe usage and health information. between the cables. Note: The CP 620 Fire Foam CP 620 Fire Foam can be applied around these.
becomes warm for a short time after application.
Instructions below are general guidelines always Not for use
refer to the applicable drawing in the UL Fire 6. For maintenance reasons, the application can be Exposed to weather
Resistance Directory or Hilti Firestop Systems Guide permanently marked with an installation plate. Mark
Exposed to UV
for complete installation information the installation plate and fasten it in a visible position
Application
next to the seal. Storage
Store only in the original packaging in a dry place
1-4. Re-installing cables or pipes
at a temperature of 40F to 77F (5C to 25C).
Prepare dispenser and cartridges as shown below. Additional cables or pipes can be installed later
See technical data for application and substrate
The Fire Foam from the rst few strokes of the without difculty.
temperatures. Partly-used cartridges can be stored
dispenser should be discarded until the Fire Foam in Use a suitable tool to create an opening. Push the with mixer attached until they are required again.
the mixer has a consistent red color. cable or pipe through and then seal the remaining When re-using a partially used cartridge, simply
5. Apply the CP 620 Fire Foam in the opening. opening carefully with CP 620 Fire Foam. attach a new mixer and dispense accordingly.
Begin applying CP 620 Fire Foam at the back of Notes
the opening and work toward the front. Fill the The CP 620 Fire Foam can be cut back to no less
opening completely with CP 620 Fire Foam. than the minimum specied installation depth (see
When dispensed slowly, the Fire Foam can be applicable UL systems for depths).
easily built up.

Aus-
f hrungsschild

1. Hold the cartridge 2. Fit the mixer and 3. Release the 4. Insert the cartridge 5. Apply CP 620 Fire 6. Attach the
in the upright position screw in a clockwise dispenser and pull in the dispenser. Foam, building up a seal installation plate
and unscrew the cap. motion until secure. back the piston rod. by working from the (if required).
back towards the front.

www.hilti.com
21
Product Information

CP 660

Product description
An innovative expanding product offering firestopping solutions Product Features
for complex applications in small to medium sized openings.
Foam can be easily shaped during the curing process
Neat and tidy application
Applications:
Very quick and easy to install and provides a reliable restop
Permanent firestop seals in small and medium-sized openings seal with only one product
(optimum size range:100 x 100 mm to 300 x 300 mm) Maintenance and retrotting of cables is very easy
Cable trays,bunched and single cables Single-sided installation possible
Openings accommodating pipes and cables Smoketightness and restopping with one system
Paintable
Plastic pipes (can also be installed as a system in
conjunction with Hilti firestop jackets and firestop wrap)
Technical data CP 660
Metal pipes (uninsulated or with flammable or non-flammable
Chemical basis Two component polyurethane
insulation)
(National approvals must be observed.) Base materials Concrete, Masonry, Drywall

Approvals ETA-10/0109

Fire foam Yield 2.1 Litre


Repenetration Easy

Approx. tack-free time 5 min


(at 23 C / 50% rel. humidity)
Approx. curing time 1) 10 min

Application temperature range 10 - 35 C

Temperature resistance range -30 - 60 C

Expansion rate (unrestricted) Up to 2 times original volume

Intumescent activation Approx. 482 F (250 C)

LEED VOC 20 g/l

Shelf life 1) 9 Months

Storage and transportation 5 - 25 C


temperature range
Required dispenser HDM 330, HDE 500

Content per can / cartridge 325 ml

1) at 75F / 24C, 50% relative humidity

Internationally Tested and approved

EN 1366-3

Visit the local website for more information on products and services.
22
Product Information

Ordering designation Content per can/cartridge Package contents Sales pack Item number
quantity
CP 660 INT 325 ml 1x Firestop foam CP 660 Internat. 1 pc 203517

Related Products

Dispensers
page no 56

Installation instructions for CP 660


Notice 5. Discard the unevenly mixed initial quantity 9. Additional cables or pipes can be installed in the
Before handling, read Material Safety Data Sheet and
product label for safe usage and health information. The mixed components of the foam react and begin approved maximum number and size of cables or
to expand approx. 30 seconds after application (at pipes. The cable or pipe may be pushed directly
through the foam. Where necessary, use a suitable
Application of restop
including gaps between individual cables, etc. tool (screwdriver or drill bit, etc.) to make a hole in
1. Clean the opening to be sealed free from dust or the foam before pushing the cable or pipe through.
grease. 7. The foam can be shaped or smoothed by hand (if Seal any remaining caps carefully with CP 660
2. Slide the foil pack into the holder. necessary) after approx. 5 minutes (at 23C). Wear
protective gloves! After approx. 10 minutes (at 23C) Storage
3. Remove the cap. Screw the mixing nozzle all the way the foam becomes hard and it can then be cut. Store in a cool, dry, dark place at a temperature of
onto the foil pack and tighten it securely.
+5C to +25C / +41F to +77F.
4. Insert the holder containing the foil pack into the correctly sealed opening.
dispenser:

10min (@23C)

www.hilti.com
23
Product Information

Firestop mortar (suitable for walls) CP 636

Product description
A fire resistant, cement based mortar with thermal insulating Product features
properties for sealing small to large sized openings where further Suitable for wall applications
penetrations may be required. Providing integrity of up to 4 hours. Excellent pot life / working time
High yield
Areas of application Stiff (forms not always required)
Cables and cable trays Contains no asbestos, phenol, or halogen constituents.
Ductwork dampers Good adhesion to steel, concrete, and masonry
Metal pipes Simple application by trowel
paintable
Base materials
Concrete
Porous Concrete Technical data CP 636
Masonry
Fire rating Up to 4 hours
Base materials Concrete, Concrete
(porous block), Masonry
Chemical basis Concrete mortar with perlite
Application temperature range 5C - 40C
LEED VOC 1 g/l
Acoustics performance Up to 59dB
Air Leakage Rating 0.00047 m3/h (min)

Gypsum based no

Yield (20Kg Bag) 21.7 - 24.1 Litres depending


on mix ratio

Internationally Tested and approved

FM EN 1366-3
SPECIFICATION TESTED

Visit the local website for more information on products and services.
24
Product Information

Ordering designation Weight Sales pack Item number


quantity
CP 636 20KG 20 kg 1 pc 334897

Related Products

CP 606 Collars CP 643, CP 644 Wraps CP 648-S, CP 648-E CFS-BL


page no 14 page no 44-46 page no 40-42 page no 30

Mixers
page no 56

Installation instructions for CP 636


Notice 3. Application of restop mortar 5. Identication plate
Before handling, read Material Safety Data Sheet and Forms should be placed on one or both sides Some countries require the cable re seal to be
product label for safe usage and health information. of large openings. Openings in oors must have marked with a lasting identication plate. This
Instructions below are general guidelines forming on the underside. Ready-mixed mortar plate must be given the appropriate wording
should be applied with a trowel or pump and and then fastened next to the cable re seal in
Application
then compacted. Make sure that gaps, voids a clearly visible position.
1. Preparation of the opening
and remaining openings are completely closed
Clean and pre-moisten the opening sides.
and sealed. Smooth the surface like ordinary
Cables and cable trays must be dry and free
concrete.
from dust, oil or grease. Cables must be laid and
secured as stated in the respective standard.
4. Follow-up installation/reworking
2. Mixing the restop mortar CFS-BL restop bricks and CP 606 A
Mix CP 636 restop mortar in the mortar-to- intumescent mastic can be installed in the
water ratio of about 3:1 by volume. It is important re seal, while keeping in mind the maximum
that rst water then CP 636 is poured into the allowable size of the opening. Care must be
bucket. Thoroughly mix small quantities using a taken to completely close any gaps, voids or
remaining openings.
drilling machine and mixer. It is important that no
further binding agents or additives are used.

6
63
CP
Aus-
fhrungsschild

Clean opening, Mix CP 636 mortar Put mortar into Optional: add Fasten installation Re-installation:
moisten surfaces (by adding mortar place CFS-BL for plate in place lay cables and
to water) future cable changes (if required) close remaining
opening

www.hilti.com
25
Product Information

Firestop Mortar (CP 637)

Product description
Product features
Quick-setting forms can be removed in as little as 2 hours
Areas of application Superior working properties
Sealing medium size to large openings with non-combustible Can be used in horizontal or vertical applications
pipes or cable trays
Saves time

Versatile
pipes
Simple mixing
For use with Paintable
Concrete and masonry assemblies

Technical Data* CP 637


Examples Color Light red, Light Grey
Large openings containing multiple steel, conduit and EMT pipes Application temperature 40F to 110F (5C to 43C)
Large openings with single or multiple cable tray applications Form removal Approx. 2 hours
(depending on consistency)
Chemical Basis Gypsum Based Mortar
Density (dry) Approx. 40.6 pcf (650 kg/m3)
Expansion on setting (approx.) 0.08%
Compressive
strength 24 hrs. after casting After full cure
Pourable 508 psi (3.5 N/mm2) 725 psi (5.0 N/mm2)
Trowelable 870 psi (6.0 N/mm2) 1784 psi (12.3 N/mm2)

Shelf life1) 12 Months

LEED VOC 0 g/l

Surface burning characteristics Flame spread: 5


(ASTM E84-01) Smoke development: 0

Yield (20Kg Bag) 21.7 - 24.1 Litres depending


on mix ratio
Tested in accordance with
ASTM E 814 UL 1479 ASTM E 84 ASTM G21
*At 75F (25C) and 50% relative humidity

Internationally Tested and approved

EN 1366-3

Visit the local website for more information on products and services.
26
Product Information

Ordering designation Weight Sales pack Item number


quantity
CP 637 FS 13.6 kg 1 pc 340645
CP 637 FS GB 20 kg 1 pc 340785

Related Products

CP 606 Collars CP 643, CP 644 Wraps CP 648-S, CP 648-E CFS-BL


page no 14 page no 44-46 page no 40-42 page no 30

Mixers
page no 56

Installation instructions for CP 637


Notice 3. Application of restop mortar 5. Identication plate
Before handling, read Material Safety Data Sheet and Forms should be placed on one or both sides Some countries require the cable re seal to be
product label for safe usage and health information. of large openings. Openings in oors must have marked with a lasting identication plate. This
Instructions below are general guidelines forming on the underside. Ready-mixed mortar plate must be given the appropriate wording and
should be applied with a trowel or pump and then fastened next to the cable re seal in
Application
then compacted. Make sure that gaps, voids a clearly visible position.
1. Preparation of the opening
and remaining openings are completely closed
Clean and pre-moisten the opening sides. Mix ratio (recommended, mortar to water):
and sealed. Smooth the surface like ordinary
Cables and cable trays must be dry and free
concrete. Trowelable 30 lb (13.6 kg) : 2 U.S. gal (8 L)
from dust, oil or grease. Cables must be laid and
Pourable 30 lb (13.6 kg) : 2.5 U.S. gal (9.5 L)
secured as stated in the respective standard.
4. Follow-up installation/reworking
2. Mixing the restop mortar CFS-BL restop bricks and CP 606 A
intumescent mastic can be installed in the
It is important that rst water then CP 637 is re seal, while keeping in mind the maximum
poured into the bucket. Thoroughly mix small allowable size of the opening. Care must be
quantities using a drilling machine and mixer. taken to completely close any gaps, voids or
It is important that no further binding agents remaining openings.
or additives are used.

7
63
CP
Aus-
fhrungsschild

Clean opening, Mix CP 637 mortar Put mortar into Optional: add Fasten installation Re-installation:
moisten surfaces (by adding mortar place CFS-BL for plate in place lay cables and
to water) future cable changes (if required) close remaining
opening

www.hilti.com
27
Product Information

Firestop coated board system CP670

Product description
Hilti CP670 is an innovative system for fast, reliable and cost Product features
effective firestopping of wall and floor openings especially Pre-coated board
large ones. Odourless and solvent free
Areas of application Less prone to damage due to pliancy of the material and the
Extended approvals for large diameter cables, dampered resilient elastic coating
penetrations and double board usage Approved for a wide range of applications
Single cables, cable bundles, cable tray air ducts and pipes
Combustible and non combustible pipes
Large penetrations possible up to 5 meters high by any length

Base materials Technical data CP 670


Drywall, Masonry, Concrete Fire rating Up to 4 hours
Storage Base materials Concrete, Masonry, Drywall
Store only in the original packaging in a location protected Application temperature range 5C - 40C
from moisture and direct sunlight at a temperature of 5C
to 37C. Shelf life1) (Coating) 15 Months
Observe expiry date on packaging.
Shelf life (Board)
1) N/A

LEED VOC 38 g/l


Acoustics performance Up to 62dB
Density (coating) 1470 kg/m
Density (board) 160 kg/m
Coating Thickness 0.7mm dry (1.1mm wet)
Colour White

Approx. curing time2) 3 mm/day

Skin forming time 7 hours


(at 23C/50% r.H) (CP 670 Coating)
1)
at 77F/25C and 50% relative humidity; from date of manufacture
2)
at 75F/24C, 50% relative humidity

Internationally Tested and approved

FM EN 1366-3
SPECIFICATION TESTED

Visit the local website for more information on products and services.
28
Product Information

Ordering designation Weight Sales pack Item number


quantity
CP 670 17,5kg (coating) 17.5 kg 1 pc 286955
CP 670 1200x600x50 white (board) 16 pc 236673

Related Products

CP 606 Collars CP 643, CP 644 Wraps CP 648-S, CP 648-E


page no 14 page no 44-46 page no 40-42

Installation instructions for CP 670 coated board system


Notice Note
Before handling, read Material Safety Data Sheet and Firestop Sealant (refer to relevant reports for specic Instead of using a Hilti CP 670 Firestop board Hilti
product label for safe usage and health information. details). CP 670 Fire Safety Coating can be either sprayed or
Instructions below are general guidelines Insert the mineral wool panel ush with the opening painted on the jobsite prior or during installation,
edge. respectively in advance. To achieve the dry coating of
4. Pack any larger gaps with loose mineral wool. 0.7 mm, a wet lm thickness of ca. 1.1 mm is required.
Application of Coated Board Seal between cables with Hilti CP 606 Firestop Hilti CP 670 Fire Safety Coating can be used where
1. Clean the opening. Do not pre-moisten opening Sealant. cutting has caused exposed mineral wool to appear.
surfaces. Cables and cable supporting structures Fill gaps with Hilti CP 606 Firestop Sealant. In addition, the coating can be applied if mineral wool
must be dry andclean from dust, grease or oil, 5. Thoroughly stir Hilti CP 670 Fire Safety Coating is used to pack gaps.
and installed in compliance with local building and Apply Hilti CP 670 Fire Safety Coating to the cables
electrical standards. and cable trays on all surfaces over the required Storage
2 Cut the Hilti CP 670 Firestop board to size. In case of length. It can be applied using a brush, roller or Store only in the original packaging in a location
services cut out required space.Coat cut edges with airless spray gun (recommendation: a nozzle 0.029 protected from moisture and direct sunlight
Hilti CP 606 Firestop Sealant. diameter, spray angle 40). To achieve the dry
3. Coat the surface of the opening with Hilti CP 606 coating of 0.7 mm, a wet lm thickness of ca. 1.1
mm is required. Fasten installation plate (if required)

Clean the opening Coat mineral wool Coat cut edges Fit mineral wool Fill gaps with CP Fasten installation
panel with CP 670 with CP 606 panel 606 (if required)

www.hilti.com
29
Product Information

Firestop Block (CFS-BL)

Product description
Product features
medium to large size openings Integrated Grid-Tech increases Annular Space up to 12
Areas of application Suitable for re-penetration or new penetrations
Sealing single or multiple penetrations in small to large openings Economical to use with short installation times
Temporary or permanent sealing of cables and cable tray Easy installation no special tools required
penetrations
Temporary or permanent sealing of insulated and non-insulated One sided wall systems available
metallic pipes and combustible pipe penetrations
Halogen, asbestos and solvent free
For use with Operational immediately after installation
Walls UL tested up to max. opening 72 " x 36" (1.8m x 0.9m) Smoke resistant
Floors UL tested up to max. opening 72" x 36" (1.8m x 0.9m) Paintable
Concrete, porous concrete, masonry and gypsum wall assemblies
Wall assemblies rated up to 4 hours
Technical Data* CFS-BL
Floor assemblies rated up to 3 hours
Color Red
Examples Chemical basis Two component polyurethane
Application temperature 40 F to 104 F (5 C to 40 C)
installations are frequently used (ie: computer centers, hospitals, Temperature resistance 5 F to 140 F (-15 C to 60 C)
laboratories, etc.)
Intumescent activation Approx. 392 F (200 C)
New buildings in the construction phase and during renovation
Expansion ratio (unrestricted) Up to 1:3
Large openings containing multiple penetrations as found in
production bays, warehouses, hospitals etc. Surface burning characteristics Flame Spread Index: 10
(ASTM E 84-10b) Smoke Development Index: 15

Shelf life1) N/A

LEED VOC 5.4 g/l

STC Rating: 52
(ASTM E 90)
Tested in accordance with
UL 1479 ASTM E 814 ASTM E 84
*At 73F (23C) and 50% relative humidity

Internationally Tested and approved

FM EN 1366-3
APPROVED

Visit the local website for more information on products and services.
30
Product Information

Ordering designation Package contents Sales pack Item number


quantity
CFS-BL 1x Firestop block CFS-BL (200 x 130 x 50 mm) 1 pc 2030020

Related Products

FS-One Max CP 620


page no 18 page no 20

Installation instructions for Firestop Block CFS-BL


Notice 2b.If penetrations are located, build up Firestop Block Install the penetrant and re-lay the block in
Before handling, read Material Safety Data Sheet and CFS-BL, rmly seated, while cutting blocks with a compliance with the approval. Fill gaps and spaces
product label for safe usage and health information. knife to suit the placed penetrations. with FS-ONE Firestop Sealant (as required).
Instructions below are general guidelines always 3. Finish building up Firestop Blocks until entire Single cables can be run through joints between
refer to the applicable drawing in the UL Fire opening is lled. blocks or a hole can be drilled through a block using
Resistance Directory or Hilti Firestop Systems Guide 4. Completely ll cable spaces, gaps between blocks a sharpened piece of metal pipe or tubing.
for complete installation information and pipes, and joints with FS-ONE Firestop Sealant
Not for use
(as required).
Opening In wet rooms, outdoors or exposed to the weather
1. Clean the opening. Penetration and penetration 5. For maintenance reasons, a penetration seal could or UV radiation (can be done only after applying an
supporting structures must be installed in be permanently marked with an identication plate. additional silicone coating, i.e. CP 601S).
compliance with local building and electrical In such a case, mark the identication plate and
standards. fasten it in a visible position next to the seal. Storage
Store only in the original packaging in a location
Application of Firestop Blocks protected from moisture and direct sunlight
Re-installing cables or other penetrations
2a.If no penetrations are located, build up Firestop
Remove or cut the block from the seal.
Block CFS-BL, rmly seated, within opening.

1. Clean opening. 2a. Build up blocks 2b. Cut blocks to 3. Build up blocks 4. Fill gaps with
size for penetrations FS-ONE, CP 617
in place or CP 618 putty (as
required).

plate in place (If


required)

www.hilti.com
31
Product Information

Firestop Plug (CFS-PL)

Product description
Ready-to-use intumescent and reusable plug for small openings Product features
Fast and easy installation no special tools required, helps
Areas of application reduce installation time and costs
Immediately functional after installation
Temporary or permanent sealing of cables single or bundled Suitable for laying new cables later
cables Versatile in use (temporary or permanent protection)
Examples Smoke resistant
One-sided installation wall systems available
are frequently changed such as computer centers, hospitals and Halogen and solvent free
laboratories Paintable
New buildings in the construction phase and during renovation

Technical Data* CFS-PL


Density Approx. 0.27 g/cm3
Chemical basis Two component polyurethane
Color Red
Application temperature 40F to 104F (5C to 40C)
Temperature resistance 5F to 140F (-15C to 60C)
Intumescent activation Approx. 392F (200C)
Expansion ratio (unrestricted) Approx. 1:3
Shelf life 1) N/A
LEED VOC 4.9 g/l
Surface burning characteristics Flame Spread Index: 10
(ASTM E 84-10b) Smoke Development Index: 15
STC Rating: 55
(ASTM E 90)
Tested in accordance with
UL 1479 ASTM E 814 ASTM E 84 ASTM E 90 CAN/ULC S115
*At 73F (23C) and 50% relative humidity

Internationally Tested and approved

FM EN 1366-3
APPROVED

Visit the local website for more information on products and services.
32
Product Information

Ordering designation Package contents Sales pack Item number


quantity
CFS-PL 2 1x Firestop plug CFS-PL 2 10 pc 2030021
CFS-PL 4 1x Firestop plug CFS-PL 4 6 pc 2030022

Related Products

FS-One Max CP 620


page no 18 page no 20

Installation instructions for Firestop Plug CFS-PL


Notice 3b. Insert restop plug into sleeve. Optional: seal cables If single cables are installed, a hole can be drilled
Before handling, read Material Safety Data Sheet and by forcing CP 618 into interstices of cables. through the restop plug and a cable passed
product label for safe usage and health information. 4. For maintenance reasons, a penetration seal can be through.
Instructions below are general guidelines always permenantly marked with an identication plate and
Not for use
refer to the applicable drawing in the UL Fire fastened in a visible position next to the seal.
In wet rooms or outdoors exposed to the weather or
Resistance Directory or Hilti Firestop Systems Guide UV radiation
for complete installation information
Re-installing cables
Remove restop plug from opening
Storage
Opening Install the penetrant and re-install the restop plug in Store only in the original packaging in a location
1. Clean the opening. surfaces Firestop Plug CFS-PL compliance with the appropriate UL system. protected from moisture and direct sunlight
will be in contact with, should be cleaned of loose
debris, dirt, oil, moisture, frost and wax.

Application of restop plug


2. If there are no penetrations, install Firestop Plug
CFS-PL within opening and bead with Hilti CP 618
Putty Stick where restop plug interfaces with inside
of sleeve (when required).
3a. If there are penetrations, cut Firestop Plug CFS-PL
to t around cables.

Firestop
System

1. Clean opening 2. Blank opening: Install 3a. With cables: Cut plug to 3b. Install plug around 4. Fasten installation plate
plug and CP 618 Putty cables (optional: in place (if required)
Stick CP 618 Putty Stick
forced into interstices
of cables)

www.hilti.com
33
Product Information

Speed Sleeve (CP 653)

Product description
Re-penetrable cable management device for electrical and Product features
telecom professionals Fast installation
Areas of application Easy penetration and re-penetration
Cable and cable bundles Low L-ratings
Withstands the rigors of usage and time
For use with

Gypsum walls rated up to 4 hours

Examples
Electrical wiring Technical Data CP 653
Premise wiring 2" (50 mm) 4" (102 mm)
Low voltage and datacom OD (device only) 2.3" (60 mm) 4.3" (110 mm)
4.7" (120 mm) 6.7" (170 mm)
ID 1.7" (48 mm) 3.6" (92 mm)
Total length 12.4" (315 mm) 12.4" (315 mm)
1.5 lbs 2.6 lbs
Temperature resistance 22 F to 212 F (-6 C to 100 C)
Intumescent activation Approx. 320 F (160 C)
Expansion ratio (unrestricted) 1:40
Shelf life 1) N/A
LEED VOC 7.6 g/l

Metal Steel with zinc coating


Plastic ABS
Fabric
Tested in accordance with
UL 1479
ASTM E 814

Internationally Tested and approved

FM EN 1366-3
APPROVED

Visit the local website for more information on products and services.
34
Product Information

Ordering designation Outside diameter (ange) Core bit diameter Sales pack Item number
quantity
CP 653 2 BA 120 mm 63 mm 1 pc 2008603
CP 653 2 120 mm 63 mm 1 pc 236323
CP 653 4 BA 170 mm 113 mm 1 pc 2008604
CP 653 4 170 mm 113 mm 1 pc 236324

Related Products

CP 606 FS-One Max


page no 14 page no 18

Installation instructions for CP 653


Notice 4. Spin the ange clockwise onto the device. Repeat 6. To close the device:
Always refer to the MSDS before use and the UL Fire on other side of the wall. (a) On the same side of the wall, press the clip
Resistance Directory or Hilti Firestop Systems Guide for 5. To open the device: closures inward.
complete installation information.
(a) On one side of the wall, press the clip closures (b) Twist the device clockwise until nger-tight,
Instructions for use inward. allowing it to engage with a click.
1. Use hole saw to create the appropriate hole. (b) Twist the device counterclockwise and pull the For repenetration of cables, repeat steps 5 and 6.
2. Insert the sleeve. red housing outwards to eliminate the bunching of For installation options not presented here, consult
the smoke seal fabric. A yellow label will be visible to your local Hilti representative for other rated restop
3. Seal the gap with restop sealant to impede smoke
indicate that the device is open. systems.
and gas migration. Repeat on other side of the wall

4 7 10
CF
S-
S
AC
R

1 5 8 11

2 6

Open
Close

3 9 12
x x
Aus-
l d
hrungsschi

www.hilti.com
35
Product Information

Firestop Drop-In Device (CFS-DID)

Product description
Product features
diameters Integrated moisture and smoke seal
Helps reduce labor costs and increase productivity Simple, quick error free installation
Ready-to-use out of box
Internationally tested and approved by UL
Areas of application
For use in concrete, hollow core, and metal deck slab thicknesses
ranging from 2-1/2" to 12-1/2"

cored or sleeved holes Technical Data CFS-DID


Installation complete with several fastening options including gas Expansion temperature ~ 356 F (~ 180 C)
actuated fasteners, metal hit anchors, and kwik con screw anchor
Expansion rate 1:15 load expansion, load = 5g/cm3
systems
1:40 free expansion

Shelf life 1) N/A

LEED VOC 0.19 g/l

Temperature resistance -4 up to 190 F


(20 up to 88 C)
Storage temperature 23 up to 122 F
(-5 up to 50 C)
Tested in accordance with
ASTM E814 UL 1479

Internationally Tested and approved

FM
APPROVED

Visit the local website for more information on products and services.
36
Product Information

Ordering designation Sales pack Item number


quantity
CFS-DID 2 C 1 pc 2008097
CFS-DID 3 C 1 pc 2008098
CFS-DID 4 C 1 pc 2008099
CFS-DID 6 C 1 pc 2008250
CFS-DID 2 MD 1 pc 2008251
CFS-DID 3 MD 1 pc 2008252
CFS-DID 4 MD 1 pc 2008253

Related Products

Installation instructions for CFS-DID


Notice
Always refer to the MSDS before use and the UL Fire Resistance Directory or Hilti
Firestop Systems Guide for complete installation information.

www.hilti.com
37
Product Information

Cast-In Firestop Devices (CP 680-P and CP 680-M)

For use in
Product features
centers and laboratories Quick and simple installation
SpeedLine Alignment system promotes faster layout
QuickTurn System creates fast, simple vertical connections
Product description
Integrated moisture and smoke seal
and diameters Innovative adapter for metal deck applications
Helps reduce labor costs and increase productivity
Ready-to-use out of the package
Internationally tested and approved by UL and FM Technical Data CP 680-P and CP 680-M
Reduces the chance of project delays due to failed inspections ID Footprint Opening required thru metal deck
2" (50mm) 95mm x 114mm 89mm diameter
Installation and applications
3" (75mm) 120mm x 143mm 114mm diameter

4" (100mm) 162mm x 171mm 140mm diameter


or concrete over metal deck
CP 680-M: 6" (150mm) 228mm x 241mm 184mm diameter

- Insulated and non-insulated metal pipes Expansion temperature 392F (200C)


- EMT and electrical conduits Expansion rate 1:50 (unrestrained)
1:30 (Load expansion, Load = 20g/cm3)
- Cable bundles
- Multiple pipes Shelf life 1) N/A
CP 680-P: LEED VOC 1.4 g/l
Addresses all applications for CP 680-M as well as the following: Standard height 8" (200mm)
- Plastic pipes such as PVC, CPVC, ABS, ENT and FRPP Temperature resistance Maximum 212F (100C)
- Fresh and waste water pipes Color CP 680-P: red
CP 680-M: black
Not suited for Tested in accordance with
Areas with high condensation UL 1479 ASTM E 814 ASTM G21
Outdoor areas Internationally tested and approved
Wall applications

Internationally Tested and approved

FM EN 1366-3
APPROVED

Visit the local website for more information on products and services.
38
Product Information

Ordering designation Color Sales pack


Item number
quantity
CP 680-P 2" Cast-In Device for Combustible Penetrations Red 1 244244
CP 680-P 3" Cast-In Device for Combustible Penetrations Red 1 244245
CP 680-P 4" Cast-In Device for Combustible Penetrations Red 1 244246
CP 680-P 6" Cast-In Device for Combustible Penetrations Red 1 244247
CP 680-M 2" Cast-In Device for Metallic Penetrations Black 1 244248
CP 680-M 3" Cast-In Device for Metallic Penetrations Black 1 244249
CP 680-M 4" Cast-In Device for Metallic Penetrations Black 1 244250
CP 680-M 6" Cast-In Device for Metallic Penetrations Black 1 244251

Related Products

Installation instructions for CP 680 N


Notice 2. Assemble the metal-deck Adaptor. Remove the 5. Clean the pipe. The exible sealing membrane
Before handling, read Material Safety Data Sheet underside plastic protective cap. Fix the plastic ensures the water tightness of the device once the pipe
and product label for safe usage and health extension and the two metal plates on the CP 680 has been passed through. Very dirty pipes with remains
information. cast-in restop device. of mortar for example, may lead to a loss of the tight
Installation instructions for concrete slabs available seal by damaging this membrane. Very dirty pipes can
3. Fix the CP 680 cast-in restop device Position the CP also disturb expansion of the intumescent material and
680 at the right place ensuring that the plastic extension lead to delays in the closing action during re. Badly
Concrete oor with metal decking has been well positioned in the hole. Screw the two soiled pipes should, therefore, be cleaned.
For applications, use the correct size CP 680 metal plates on the metal deck with the device using 6. Install the pipe. Pipes can be installed from the top
Metal Deck Adapter for installed cast-in Hilti self drilling srews. Before pouring the concrete, or from the bottom. Remove the plastic protective
device and follow the illustrations. make sure the top cap is in place thereby preventing the caps and pass through the pipe breaking the white
ow of concrete into the cast-in device. membrane. If insulation is required pass the pipe
1. Create the opening in the metal-deck Use the correct through rst followed by the insulation. Installation is
size CP 680 Metal Deck Adaptor with the installed cast- 4. Pour the concrete slab to the required thickness nished and restop functional at this stage.
in device. Size the hole with the plastic extension, and
cut the metal deck.

Concrete oor Installation option


1 2 Follow the illustrations if CP 680 has to be cut to slab
1 2 thickness before installation, or when riser clamps are
used.

1 2

3 4
3 4

5 6

www.hilti.com
39
Product Information

Firestop Wrap Strip (CP 648-E)

h.
sc
an
tzm
hu
sc
nd E
Bra oW
48 . N uze
6 riuh 7
CP wh 288u2 , ireiv
dj
v iJ i4e 0 vbvbvh
fm,e p3 x-.
sod 23aw i4jtf-
Z 8 Z w ilo
kird oo
4i5 12oe
u9+

Product description
Product features
insulated pipe penetrations Highly Intumescent
Areas of application Long length avoids waste
Firestopping combustible pipe penetrations Can be continuously wrapped
Cost effective
Penetrations through concrete over metal deck Quick and easy closure without tools
Plastic and insulated penetrations using Ideal for very tight installations
PVC, CPVC, PPR, ABS, FRPP and PEX

For use with Technical Data* CP 648-E

Density Approx. 1.35 g/cm3

Dimensions (approximate) 3/16" (5mm) x 1" (25mm) x 33 ft (10m)


3/16" (5mm) x 1-3/4" (45mm) x 33 ft (10m)
Examples
Waste water pipes Color Black with foil backing
Fresh water pipes Temperature resistance 40F to 212F (40C to 100C)
Decking penetrations Intumescent activation Approx. 210C
Shelf life 1) N/A

LEED VOC 3.1 g/l

Height 5 mm

Expansion ratio (unrestricted) 1:19


Tested in accordance with
UL 1479 ASTM E 814 ASTM G21
*At 73F (23C) and 50% relative humidity

Internationally Tested and approved

FM EN 1366-3
APPROVED

Visit the local website for more information on products and services.
40
Product Information

Ordering designation Sales pack Item number


quantity
CP 648-E 1 x 33 1 pc 304308
CP 648-E 1,75 x 33 1 pc 304309

Related Products

CP 648 - ER CP 606 FS-One Max


page no 56 page no 14 page no 18

Installation instructions for CP 648-E


Notice Application of restop system Not for use
Before handling, read Material Safety Data Sheet and 2. Tightly wrap the required number of strips In highly corrosive surroundings
product label for safe usage and health information. continuously around the penetrant, and hold in place With unapproved retaining collars,
Instructions below are general guidelines always with tape. anchors/fasteners
refer to the applicable drawing in the UL Fire 3. Push the Hilti Wrap Strip into the opening until it is Outdoors
Resistance Directory or Hilti Firestop Systems Guide ush with the substrate surface unless otherwise
for complete installation information required by the UL system. It may be required by Storage
the UL system to clamp, wire or use a Hilti Retaining Store only in the original packaging in a
Collar to secure the wrap strip in place for some location protected from moisture at
Opening applications. temperatures between 23F and
1. Clean the plastic or insulated pipe penetration. 4. If the UL system requires a cold smoke seal, then 86F (5C and 30C).
Expansion of the intumescent material during a re apply the proper amount of Hilti FS-ONE sealant in
closes the plastic or insulated pipe penetration. Very the opening over the wrap strip.
dirty pipes (ie: with remains of mortar) may lead to
5. For maintenance reasons, a penetration seal can be
a delay in this closing action. Soiled plastic pipes
permanently marked with an identication plate and
or insulated pipe penetrations should, therefore, be
fastened in a visible position next to the seal.
cleaned in the area where the CP 648-E Firestop
Wrap Strip is to be installed.

Firestop
System

1. Clean penetration 2. Wrap strips around 3. Push Wrap Strips 4. Seal penetration against 5. Fasten installation plate
into hole smoke with FS-ONE (If required)
of times

www.hilti.com
41
Product Information

Firestop Wrap Strip (CP 648-S)

Product description
Product features
plastic and insulated pipe penetrations Highly intumescent
Areas of application Pre-measured no cutting required
Firestopping combustible pipe penetrations Integrated fastening tape
Cost effective
Penetrations through concrete over metal deck Quick and easy closure without tools
Suitable for the following plastic pipe materials: Ideal for very tight installations
PVC, CPVC, ABS, FRPP

For use with Technical Data* CP 648-S


Density Approx. 1.35 g/cm3
Dimension (approximate) 1.5": 3/16" x 1" x 6-3/4"
(thkns" x width" x length") 2": 3/16" x 1" x 8-1/4"
Examples 3": 3/16" x 1-3/4" x 11-1/2"
Waste water pipes 4": 3/8" x 1-3/4" x 15"
Fresh water pipes 6": 1/2" x 1-3/4" x 22-1/4"
Decking penetrations Color Black with foil backing
Shelf life 1) N/A
LEED VOC 3.1 g/l
Temperature resistance 4F to 212F (20C to 100C)
Intumescent activation Approx. 210C
Expansion ratio (unrestricted) 1:19
Tested in accordance with
UL 1479 ASTM E 814 ASTM G21
*At 73F (23C) and 50% relative humidity

Internationally Tested and approved

FM EN 1366-3
APPROVED

Visit the local website for more information on products and services.
42
Product Information

Ordering designation Dimensions (LxWxH) Sales pack Item number


quantity
CP 648-S-2 US 202 x 25 x 5 mm 10 pc 304304
CP 648-S-3 US 291 x 45 x 5 mm 10 pc 304305
CP 648-S-4 US 383 x 45 x 9 mm 10 pc 304306
CP 648-S-6 US 569 x 45 x 14 mm 6 pc 304307

Related Products

CP 606 FS-One Max


page no 14 page no 18

Installation instructions for CP 648-S


Notice 2. Install Wrap Strip. First check the annular space Not for use
Before handling, read Material Safety Data Sheet and to ensure compatibility with the appropriate UL In highly corrosive surroundings
product label for safe usage and health information. System. Use the CP 648-S Firestop Wrap Strip Outdoors
Instructions below are general guidelines always corresponding to the diameter of the pipe to be
installed. Wrap the CP 648-S strip around the pipe Storage
refer to the applicable drawing in the UL Fire
and fasten it tightly using the integrated adhesive Store only in the original packaging in a location
Resistance Directory or Hilti Firestop Systems Guide
strip. protected from moisture at temperatures between
for complete installation information
23F and 86F (5C and 30C).
Push the CP 648-S Firestop Wrap Strip into the
Installation
annular space in accordance with the UL listing.
1. Clean the plastic or insulated pipe penetration.
Expansion of the intumescent material during a re 3. Seal against smoke and gas. Seal the remaining gap
closes the plastic pipe. Very dirty pipes (ie: with with Hilti FS-ONE sealant.
remains of mortar) may lead to a delay in the closing 4. For maintenance reasons, a penetration seal can be
action. Soiled plastic or insulated pipes should, permanently marked with an identication plate and
therefore, be cleaned in the area where the fastened in a visible position next to the seal.
CP 648-S Firestop Wrap Strip is to be installed.

1. Clean penetration 2A. Wrap the CP 648-S 2B. Push the CP 648-S 3. Seal penetration against 4. Fasten installation plate
Wrap Strip around Wrap Strip along the pipe smoke with FS-ONE (If required)
the pipe and fasten it and into the annular space sealant.
tightly with the as indicated above.
adhesive strip.

www.hilti.com
43
Product Information

Firestop Collar (CP 643N)

Product description
Product features
Ready-to-use collar
No construction required
Areas of application
Fast installation time
Firestopping combustible pipes up to 6" diameter in penetrations
Adjustable mounting tabs
Suitable for the following pipe materials:
PVC, CPVC, ABS, PVDF, PP and FRPP

For use with


Technical Data CP 643N
Pipe Collar Collar No. of
outside outside Height hooks and
Types of installation Description dia (in.) dia. (in.) (in.) fasteners
Wall: two collars, one on each side CP 643-50/1.5"N 1.42.0 2.8 0.9 2
Floor: one collar on underside (bottom) CP 643-63/2"N 2.02.5 3.4 1.3 2

Example CP 643-90/3"N 2.63.6 4.9 1.7 3


Waste water pipes CP 643-110/4"N 3.64.5 6.0 1.9 3
Fresh water pipes CP 643-160/6"N 6.6 9.8 1.9 4
Temperature resistance -4F to 212F (20C to 100C)
Shelf life 1) N/A
LEED VOC 7.6 g/l
Intumescent activation Approx. 250C
Expansion ratio (unrestricted) Up to 1:17
Tested in accordance with
UL 1479 ASTM E 814 ASTM G21
1)
at 77F/25C and 50% relative humidity; from date of manufacture

Internationally Tested and approved

FM EN 1366-3
APPROVED

Visit the local website for more information on products and services.
44
Product Information

Ordering designation Outside diameter Pipe diameter - range Sales pack Item number
quantity
CP 643-50/1.5 N 67 mm 32 - 51 mm 1 pc 304325
CP 643-63/2 N 82 mm 52 - 64 mm 1 pc 304326
CP 643-90/3 N 116 mm 79 - 91 mm 1 pc 304328
CP 643-110/4 N 146 mm 92 - 115 mm 1 pc 304329
CP 643-125/5 N 166 mm 116 - 125 mm 1 pc 304330
CP 643-160/6 N 236 mm 126 - 170 mm 1 pc 304331

Related Products

CP 606 FS-One Max


page no 14 page no 18

Installation instructions for CP 643N


Notice 3. Close the CP 643N Firestop Collar. Place the c. To secure the CP 643N Firestop Collar, use Hilti
Before handling, read Material Safety Data Sheet and CP 643N Firestop Collar around the plastic pipe anchors/fasteners.
product label for safe usage and health information. and lock the closure by applying rm pressure until d. For maintenance reasons, a penetration can be
Instructions below are general guidelines always it latches. permanently marked with an identication plate and
refer to the applicable drawing in the UL Fire 4. Attach fastening hooks. The fastening hooks can fastened in a visible position next to the seal.
Resistance Directory or Hilti Firestop Systems Guide be attached to various points on the metal housing.
for complete installation information This allows the fastening points to be made to suit Not for use
the space available in each case. The hooks must With metal pipes
Opening be positioned as symmetrically as possible. The In highly corrosive surroundings
1. Clean the plastic pipes. Expansion of the required number of fastening hooks is indicated on With unapproved anchors/fasteners
intumescent material during a re acts to close the the packaging.
plastic pipe. Very dirty pipes (ie: with remains of Storage
mortar) may lead to a delay in this closing action. 5. Fastening the CP 643N Firestop Collar. Only when Store only in the original packaging in a location
Soiled plastic pipes should, therefore, be cleaned in fastened properly can CP 643N offer protection protected from moisture
the area where the CP 643N Firestop Collar is to be against re.
installed. a. Mark the fastening points.
b. Drill holes with a Hilti rotary hammer drill (i.e.
Application of restop system
TE 4-A18) or, depending on base material, fasten
2. Seal the opening if required. Gaps may be closed
using Hilti powder-actuated tool.
with FS-ONE. The approved methods vary and are
given in the specic UL system.

1. Clean plastic pipe. 2. Close remaining gap to 3. Close collar. 4. Attach fastening hooks. 5. Fasten collar and
provide smoke and gas
resistant seal. (if required).

www.hilti.com
45
Product Information

Firestop Collar (CP 644)

Product description
Product features
Ready-to-use collar
No construction required
Areas of application
Fast installation time
Sealing of penetrations for combustible pipes from 8" to 10" in
diameter Adjustable/moveable fastening tabs
Vented or closed pipe
PVC or CPVC pipe

For use with Technical Data CP 644


Concrete, masonry, and gypsum walls Pipe Collar Collar No. of
outside outside Height hooks and
Description dia (in.) dia. (in.) (in.) fasteners
Types of installation CP 644-200/8" 8.8 10.0 6.9 10
Wall: two collars, one on each side CP 644-250/10" 10.8 12.4 9.1 12
Floor: one collar on underside (bottom) Temperature resistance -4F to 212F (20C to 100C)
Examples Shelf life 1) N/A
Waste water pipes LEED VOC 7.6 g/l
Fresh water pipes Intumescent Activation Approx. 210C
Expansion ratio (unrestricted) Up to 1:17
Tested in accordance with
UL 1479 ASTM E 814 ASTM G21
1)
at 77F/25C and 50% relative humidity; from date of manufacture

Internationally Tested and approved

FM EN 1366-3
APPROVED

Visit the local website for more information on products and services.
46
Product Information

Ordering designation Outside diameter Pipe diameter - range Sales pack Item number
quantity
CP 644-50/1.5 67 mm 32 - 51 mm 1 pc 304332
CP 644-63/2 82 mm 52 - 64 mm 1 pc 304333
CP 644-75/2.5 102 mm 65 - 78 mm 1 pc 304334
CP 644-90/3 117 mm 79 - 91 mm 1 pc 304335
CP 644-110/4 146 mm 92 - 115 mm 1 pc 304336
CP 644-125/5 166 mm 116 - 125 mm 1 pc 304337
CP 644-180/7 228 mm 1 pc 304339
CP 644-160/6 236 mm 126 - 170 mm 1 pc 304338
CP 644-200/8 US 257 mm 1 pc 304341
CP 644-225/9 289 mm 1 pc 304342
CP 644-250/10 319 mm 1 pc 304343

Related Products

CP 606 FS-One Max


page no 14 page no 18

Installation instructions for CP 644


Notice 3. Close the CP 644 Firestop Collar. Place the CP 644 c. To secure the CP 644 Firestop Collar, use Hilti
Before handling, read Material Safety Data Sheet and Firestop Collar around the plastic pipe and lock the anchors/fasteners.
product label for safe usage and health information. closure by applying rm pressure until it latches. d. For maintenance reasons, a penetration can be
Instructions below are general guidelines always 4. Attach fastening hooks. The fastening hooks can permanently marked with an identication plate
refer to the applicable drawing in the UL Fire be attached to various points on the metal housing. and fastened in a visible position next to the seal.
Resistance Directory or Hilti Firestop Systems Guide This allows the fastening points to be made to suit
for complete installation information the space available in each case. Not for use
With metal pipes
The hooks must be positioned as symmetrically as
Opening In highly corrosive surroundings
possible. The required number of fastening hooks is
1. Clean the plastic pipes. Expansion of the
indicated on the packaging. With unapproved anchors/fasteners
intumescent material during a re acts to close the
plastic pipe. Very dirty pipes, (ie: with remains of Storage
mortar) may lead to a delay in this closing action. 5. Fastening the CP 644 Firestop Collar. Only when Store only in the original packaging in a location
Soiled plastic pipes should, therefore, be cleaned in fastened properly can CP 644 offer protection protected from moisture
the area where the CP 644 Firestop Collar is to be against re passing through.
installed. a. Mark the fastening points.
b. Drill holes with a Hilti rotary hammer drill
Application of restop system
(i.e. TE 4-A18) or, depending on base material,
2. Seal the opening. Gaps must be closed with FS-
fasten using Hilti powder-actuated tool.
ONE. The approved methods vary and are given in
the specic UL system.

1. Clean plastic pipe 2. Close remaining gap to 3. Close collar 4. Attach fastening hooks 5. Fasten collar and
provide smoke and gas
resistant seal required)

www.hilti.com
47
Product Information

Firestop Putty Pad (CP 617, CP 617L and CP 617XL)

Product description
Product features
boxes Applied by hand
Areas of application Fast installation
Protection of electrical outlet boxes

For use with


Gypsum wall assemblies with wood or metal studs Technical Data* CP 617
Dimensions (LxWxH) CP 617: 6" x 7" x 1/8" (15 x 18 x 0.3 cm)
Examples CP 617L: 7" x 7" x 1/8" (18 x 18 x 0.3 cm)
Where two outlets are within a single stud/cavity or within 24" CP 617XL: 9" x 9" x 1/8" (23 x 23 x 0.3 cm)
Consistency Moldable putty
Color Red
Application temperature 32F (0C) to 104F (40C)
Storage temperature 23F (-5C) to 104F (40C)
Temperature resistance range -20 - 60 C
Curing time Non-curing
Density 1.48 g/cm3
Intumescent activation Approx. 220F to 250F
(104C to 121C)
Shelf life 1) N/A
LEED VOC 4.35 g/l
Volatile solvents None
None
Surface burning characteristics Flame Spread: 15
(ASTM E 84-96) Smoke development: 10

(ASTM E 90-97)
Tested in accordance with
UL 263 ASTM E 84 ASTM G21
*At 73F (23C) and 50% relative humidity

Internationally Tested and approved

FM EN 1366-3
APPROVED

Visit the local website for more information on products and services.
48
Product Information

Ordering designation Dimensions (LxWxH) Package contents Sales pack Item number
quantity
CP 617 6x7 152 x 178 x 3 mm 1x Firestop putty pad CP 617 6x7 20 pc 309760
CP 617 L 7x7 178 x 178 x 3 mm 1x Firestop putty pad CP 617L 7x7 20 pc 333583
CP 617 XL 9x9 229 x 229 x 3 mm 1x Firestop putty pad CP 617XL 9x9 20 pc 373387

Related Products

Installation instructions for CP 617


Notice 2. CP 617 Firestop Putty Pads are to be installed to Not for use
Before handling, read Material Safety Data Sheet and completely cover the exterior surfaces of the outlet In areas exposed to water
product label for safe usage and health information. box (except for the side of the outlet box against the
Storage
Instructions below are general guidelines always
Store only in the original packaging in a location at
refer to the applicable listing (CLIV) in the UL Fire stud) and completely seal against the stud within the temperatures 40F (5C) to 104F (40C)
Resistance Directory or Hilti Firestop Systems Guide stud cavity.
for complete installation information
3. Reshape CP 617 to t around conduit or cables.
Application of restop putty 4. Press CP 617 to all sides of electrical box.
1. After ensuring box is cleaned of loose debris, dirt, 5. Remove other side of label.
oil, moisture, frost and wax, remove label from one
side of pad. For a 1 to 2 hour re rating, one
CP 617 pad is required. Exposed side of pad is
placed against box.

1. Remove label from one 2. Adhere CP 617 to 4. Press CP 617 to all 5. Remove other side
side of CP 617 outlet box around box sides of outlet box of label

www.hilti.com
49
Product Information

Firestop cable coating CP 678

Product description
Hilti CP 678 is a ready to use, water based, intumescent Product features
cable coating, which can be applied by brush or airless spray Water soluble, odourless and solvent free.
to prevent the propagation of res along internal electrical Rapid drying.
cables. Cables coated with CP 678 will exhibit increased Remains exible when dry.
protection in the event of a re. Also suitable for Intumescent.
protecting against spread of ame on timber panels. Free of bres, or as asbestos.
No derating effect on cables.
Main applications Compatible with the sheathing of electrical cables.
Power plants.
Telecommunication complexes.
Industrial plants. CP 678
Petrochemical plants.
Paper mills.
Factories and production facilities.
Chemical basis Vinyl Acetate

Approx. curing time2) 24 h

Intumescent. Yes

LEED VOC 60 g/l

Temperature resistance
30C to 80C
of cured coating
Application of second layer After 2 to 4 hours
Consistency can be applied by paint brush or sprayed

electric surface resistance per


1,1 x 109
DIN VDE 0472/05.85
Transport Temperature: +5C to +25C
Viscosity: approx. 50.000 mPas

at 77F/25C and 50% relative humidity; from


1)

date of manufacture
at 75F/24C, 50% relative humidity
2)

Internationally Tested and approved

FM IEC-60332
APPROVED

Visit the local website for more information on products and services.
50
Product Information

Ordering designation Package contents Sales pack Item number


quantity
CP 678 20KG 1x Firestop cable coating CP 678 kpl. 1 pc 334892

Consumption of CP 678 cable coating depends upon the application for which it is being used.
The following application rates apply for the different standards:

Test Standard Dry lm thickness Wet lm thickness Aprox. Requirement


IEC 60 332 -3 1 .0 mm coating 1. 4 mm coating 1 .8 kg/m (1. 4 liters/m )

Germanischer Lloyd 0 .5 mm coating 0.7 mm coating


0 .9 kg/m (0.7 liters/m )
(based on IEC 60332 -3 )

Factory Mutual Approval 1.6 mm 2.2 mm 2.86 kg/m (2.2 liters/m )

* Each 20 kilogram container of CP 678 contains approximately 15.4 liters.

Installation instructions for CP 678


Opening Each application will achieve a dry lm thickness of Do not
approx. 0.5 mm. To meet IEC 332 requirements, the dry Paint over the coating.
Clean the cables. The cables and cable supporting
lm thickness must be at least 0.5 mm. For Factory Use outside or in damp rooms.
structures must be dry and free from dust, grease or oil
Mutual requirements the dry lm thickness must reach Apply to uninsulated cables.
and installed in compliance with local building and
electrical standards. 1.6 mm. Safety precautions
Keep out of the reach of children.
Prepare the cable coating. Thoroughly mix the CP 678 Observe the safety data sheet.
coating. Any separated water in the container must also Coverage Wear suitable gloves and eye protection.
be mixed in. Do not add water. On a flat surface coverage will be approximately 650 gm Storage
per m2 (at 0.5 mm DFT) . Store only in the original packaging in a
Apply CP 678 cable coating to all areas of the cables and
On cable bundles and cable trays allow 1 to 1.5 kg per m2 location protected from moisture.
cable run over the required length. This can be done
(at 0.5 mm DFT) depending on volume of cables, method Observe expiry date on bucket.
using a paint brush, roller or airless spray gun with the
of application and wastage (ie. over spray). Store at temperatures between 5C and 37C.
recommended 0.029 nozzle and 40 spray angle.

1 2 3 4
1 =
5 - 40C
41 - 104F

5a 5b 5c 6
2-4h

5 40

7 8 9
24h* x = (2 - 1) / 2
FM: x = 1.6 mm (0.07")
2=
5a 5b 5c GL (IEC 60332-3):
x = 0.5 mm (0.02")
1x = ca. 0.5 mm

www.hilti.com
51
Product Information

Ablative restop cable coating CP 679A

Product description
CP 679A is a solvent and chlorine-free dispersion with flame Product Features
retarding pigments ablations coating compound. Asbestos Viscoelastic, remains elastic even in thick coats.
and halogen free. Impermeable to water.
CP 679A is an ablation product, which undergoes an Resistant to oil and petrol spills.
endothermic reaction when subjected to fire. This means that Weatherproof, virtually odourless and Environmental
evaporation of the water released by the heat has a crucial friendly.
effect on the spreading of the fire. Paintable

Fields of applications
CP 679A
CP 679A is a universal fire retardant coating used on cables
laid horizontally or vertically. It can be used both for indoor or
outdoor applications.
Offshore exploration, production & refining Chemical basis Acrylate
Oil & Gas Ablative Yes
Power Plants

Dust dry 3h

LEED VOC 60 g/l

Temperature resistance of -30C to +80C


cured coating
Thickness of layer One single layer can achieve 1 mm dry
coating thickness
approx. 1.7 kg/m amount of coating

Thickness of layer: wet dry 1,5 mm wet 1,0 mm dry


2,2 mm wet 1,6 mm dry

Application of 2nd layer after 24 hours. (23C/50% humidity)

can be applied by paint brush, roller or


Consistency sprayed
Transport temperature + 5C to +25C

* at 23C and 50% relative humidity

Internationally Tested and approved

FM IEC-60332
APPROVED

Visit the local website for more information on products and services.
52
Product Information

Ordering designation Sales pack Item number


quantity
CP 679 A 20KG 1 pc 372097

Consumption of CP 679A cable coating depends upon the application for which it is being
used. The following application rates applying for the different standards:

Test Standard Dry lm thickness Wet lm thickness Aprox. Requirement


IEC 60332-3 1.0 mm coating 1.5 mm coating Flat surface:
1.7 kg/m (1.3 liters/m )

Cable bundles and


cable trays :
2.0 - 3.5 kg/m (1.5
2.7 liters/m )
Factory Mutual Approval 1.6 mm 2.2 mm Flat surface:
2.5 kg/m (1.9 liters/m )

Cable bundles and


cable trays:
3.0 - 5.0 kg/m (2.3
3.8 liters/m )

Installation instructions for CP 679A


Opening Safety precautions
Clean the cables. The cables and cable supporting A single coat can achieve a dry lm thickness (DFT) of CP 679A has no toxic additives and therefore
structures must be dry and free from dust, grease or oil, approx. 1.0 mm (0.04 in.). Please note that a 1.0 mm only requires such measures as are to be
and installed in compliance (0.04 in.) DFT is required to meet ABS (American adopted when applying paints.
Remove splashes arising during application
with local building and electrical standards. Bureau of Shipping) and/or DNV (Det Norske Veritas)
Prepare the cable coating. Thoroughly mix the CP 679A rules. immediately with water.
Keep out of the reach of children.
coating. Any separated water in the container must also Coverage Observe the material safety data sheet.
be mixed in. Do not add water. CP 679A should be On bunched cables the coverage rate of CP 679A Wear suitable gloves and eye protection.
applied at its original viscosity. will be approximately 1.7 kg per m2 (at 1.0 mm DFT).
Apply CP 679A cable coating to all areas of the cables
Storage
and cable run over the required length. CP 679A can be Do not
Store only in the original packaging in a dry
applied with conventional brush, roller or with airless Dilute with water. location protected from moisture.
spraying equipment. It is advisable to use nozzle Apply to uninsulated cables. Observe expiry date on bucket.
openings 0.58 to 0.63 mm or 0.023 to 0.025 inch. Store at room temperature, free from frost.
CP 679A can also be applied in several thinner coats,
each of them being allowed to dry before recoating.

Clean cables Mix coating Apply coating

www.hilti.com
53
Product Information

Dispenser foam CF125-50


Technical data
Application temper- 5 - 30 C
ature range
Foam yield (up to) 50 l

Shelf life1) 15 Months

Colour Manila

at 77F/25C and 50% relative humidity; from


1)

Key applications and advantages date of manufacture


Insulating gaps around window frames,
cooling equipment and pipes, heating
pipes, baths, wood oors, air-condition-
ing equipment, air ducts
High yield
Stop-and-go controlled dispensing

Ordering designation Sales pack Item number


quantity
CF 125-50 750ML 1 pc 259628

Filling foam CF-F 750


Technical data
Application temper- 5 - 30 C
ature range
Foam yield (up to) 35 l

Shelf life1) 12 Months

Colour Manila

at 77F/25C and 50% relative humidity; from


1)

Key applications and advantages date of manufacture


Gaps and cracks
Drywall voids
Cavities around electrical ttings
Easy to use - nger dispensing
High adhesive strength

Ordering designation Sales pack Item number


quantity
CF-F 750 1 pc 369811

Insulating foam CF-I 750


Technical data
Application temper- 5 - 30 C
ature range
Foam yield (up to) 50 l

Shelf life1) 15 Months

Colour Manila

at 77F/25C and 50% relative humidity; from


1)

Key applications and advantages date of manufacture


Insulating window joints, attics, drywall
General-purpose construction foam
Filling - wall openings, pipe penetra-
tions, panels, risers, ducts and prefabri-
cated sections
Suitable for universal use
HFC-free

Ordering designation Sales pack Item number


quantity
CF-I 750 1 pc 369800

Visit the local website for more information on products and services.
54
Product Information

Smoke and Acoustic Sealant


(CP 506)

Applications
Sealing construction joints and through-penetration openings in

Advantages
Easy to dispense, apply and tool
Excellent airborne sound insulation properties
Low shrinkage after curing
Easy cleaning with water
Paintable

Tested/evaluated in accordance with:


ASTM E 90
ASTM C 834
ASTM E 84 Technical Data CP 506
ASTM C 919 Color white
Chemical basis acrylic
Storage and transport temperature 40F to 77F
range (5C to 25C)
Curing time approx. 3 mm / 3 days
(73F / 50% relative humidity)
Skin-forming time approx. 15 min
(73F / 50% relative humidity)
Application temperature range 40F to 104F
(5C to 40C)
Shelf life 24 months from date of manufacture
STC 63
(ASTM E 90) (per tested construction type)
Movement capability (ISO 11600) approx. 12.5%
Mold and mildew (ASTM G 21) mold resistant
Surface burning characteristics Flame spread: 10
(ASTM E 84-08) Smoke development: 10
Air leakage L-Rating at Ambient =
Less than 1 CFM / Lin Ft.
L-Rating at 400F =
Less than 1 CFM / Lin Ft.

Ordering designation Volume per unit Sales pack Item number


quantity
CP 506 580ml 580 ml 1 pc 412590

Installation instructions for CP 506


Notice Opening Not for use
Before handling, read Material Safety Data Sheet and 1. Clean the opening. Surfaces to which CP 506 will be In areas immersed in water
product label for safe usage and health information. applied should be cleaned of loose debris, dirt, oil,
wax, grease, and other contaminants. The surface Storage
Instructions below are general guidelines always
should be moisture and frost free. Store only in the original packaging in a location
refer to the product label, applicable product test
protected from moisture at a temperature of 40F to
reports and/or architect requirements
Application of sealant 77F (5C to 25C)
2. Apply sealant in opening at required depth Observe expiration date on package
3. Smooth sealant with a trowel before the skin
forms. Once cured, CP 506 can only be removed
mechanically

1. Clean opening 2. Apply CP 506 3. Tool CP 506

www.hilti.com
55
Accessories

Dispensers Dispensers

Ordering designation Package Contents Sales pack Item number


quantity
Dispenser CFS-DISP for 300ml cartridge 1x Dispenser CFS-DISP 1 pc 2005843
Dispenser CS 270-P1 for 600ml foil pack 1x Dispenser CS 270-P1 1 pc 24669
Foil Dispenser Replacement Nut - 1 pc 334548
Foil Dispenser Nozzles - 10 pc 220139
Dispenser DSC box for CP 620 1x Dispenser DSC 1 pc 338720
Dispenser DSC cas 1x Dispenser DSC, 1x Case 1 pc 339131
Extension tube CP 620-EXT 1x Extension tube 12 pc 338716
Mixer CP 620-M 1x Mixer 12 pc 338718

Foam dispenser CF-DS1

Ordering designation Sales pack Item number


quantity
Dispenser gun CF DS-1 1 pc 259768

Foam accessories CF

Ordering designation Package contents Sales pack Item number


quantity
Grip adapter CF-GA1 1x Adapter CF-GA1 12 pc 259765
Finger adapter CF-FA1 1x Finger adapter CF-FA1 12 pc 259766

Cleaner CFR 1/CF 100

Ordering designation Sales pack Item number


quantity
Cleaner CFR1 500ML 1 pc 24506

Construction chemicals accessories

Ordering designation Sales pack Item number


quantity
Mixing paddle stnls. 1 pc 24155

Retaining collar CP 648-ER


Key applications and advantages
For use with CP 648-E restop wrap
Holds CP 648-E restop wrap in place

Ordering designation Sales pack Item number


quantity
Retaining collar CP 648-ER 1.75 x 25 1 pc 283225

Visit the local website for more information on products and services.
56
Estimating Tables

Estimating Tables

CP 620 Expanding Fire Seal

Foam installation thickness:


Surface area of Diameter of Seal No. of CP 620 cartridges
Seal (mm x mm) mm Cable loading (as % of opening size) Unit Conversion Table
0% 10% 30% 60%
0.005 90 50 x 100 1 1 1 1 1 = 25.4 mm
0.01 120 100 x 100 1 1 1 1
0.015 140 100 x 150 2 2 1 1
1 ft = 304.8 mm
0.02 160 100 x 200 2 2 2 1 1sq in = 6.45 sq cm = 0.000645 sqm
0.025 180 100 x 250 3 2 2 1
0.03 200 100 x 300 3 3 2 1 1 in3 = 16.39 ml
0.04 220 200 x 200 4 3 3 2 1 oz. = 29.5 ml
0.045 240 200 x 225 4 4 3 2
0.05 250 200 x 250 5 4 3 2 1 gallon = 3.78 litre
0.06 280 200 x 300 5 5 4 2
0.07 300 200 x 350 6 6 4 3
0.08 320 200 x 400 7 6 5 3
0.09 340 300 x 300 8 7 6 3
0.1 350 300 x 330 8 8 6 4
0.12 400 300 x 400 10 9 7 4
0.16 - 400 x 400 13 12 10 6
0.20 - 400 x 500 17 15 12 7

CP 636 Firestop Mortar


c
20 kg bags yield 22.2 litres
a = opening depth in cm b
b = opening length in cm
c = opening width in cm
Blank opening
Number of bags required = a x b x c a
22,000

e.g. 100 mm thick floor with 1 meter x 1 meter opening:


Therefore number of bags required = 10 x 100 x 100
= 5 bags
22,000

Opening with 30% cross sectional area of services


Number of bags required = a x b x c x 0.7
22,000

Opening with 50% cross sectional area of services


Number of bags required = a x b x c x 0.5
22,000

Hilti CP 670 Ablative Firestop Coated Board System

Degree of Load
0% 10% 30% 60%
Opening Size (m2) L x w (mm)
CP 670 (kg) CP 670 (kg) CP 670 (kg) CP 670 (kg)
0.1 100x1000 0.30 0.28 0.22 0.12
0.5 500x1000 1.50 1.34 1.04
0.8 800x1000 2.40 2.18
1.0 1000x1000 3.00 2.70 2.10 1.20
1.5 1000x1500 4.48 4.00 3.20 1.80
2.0 1000x2000 5.00 4.20 2.40
2.4 1200x2000 7.20 5.00

Note

www.hilti.com
57
Estimating Tables

Estimating tables for through-penetrations

How to estimate amount of Firestop needed for pipe penetrations

Single pipe, circular opening Single pipe, rectangular opening For multiple pipes in an opening
Use the Estimation Chart (Table 3) found on 1. Calculate the area of the pipe. For Use the methods stated previously, but add
page 59. Find the pipe size across the top of schedule 40 steel pipe, use the Calculation all of the penetration areas (A p ) together
the table and match it with the hole diameter Chart For Pipe Areas (Table 1) found on before subtracting from the total area of the
found along the side of the chart. The value page 59. Find the pipe size that is used opening (A o).
from the table represents the volume of and note the Area located in the far right
column OR calculate the total cross-
sectional area of the penetration using the
following formula (note: all values should
be in units of inches):
AP = (rP2 ) x 3.14
AP = total area of penetrating pipe
rP = outside radius of
penetrating pipe = ________
diameter
2

2. Calculate the area of the opening (all


values in units of inches):
Ao = length x width
Ao = area of opening
Circular Opening: Ao = (rP2) x 3.14

3. Subtract the area of the penetrating pipe


from the area of the opening and multiply

o
- AP ) x FD

FD

penetration. For wall systems requiring

2.

Sample Problem

System C-AJ-1226 (1/4" depth FS-ONE)


Ao = 8" diameter 50.24 in2
AP = 6" diameter - 34.19 in2
________
16.05 in2 x 1/4" = 4.0 in3 of FS-ONE MAX
= 65.5ml of FS-ONE MAX

Visit the local website for more information on products and services.
58
Estimating Tables

Estimating tables for through-penetrations


TABLE 1 TABLE 2
Calculation chart for pipe areas General estimation table for CP 648-E
Nominal pipe size Pipe O.D. Area (sq. in.)
(Length of Wrap Strip required for different
pipe diameters)
1/2" 0.84 0.55
Length of CP 648-E Wrap Strips
1" 1.3 1.33 (3/16" thick) Required*
1-1/2" 1.9 2.83 (Number of layers of Wrap Strips) Unit Conversion Table
Nominal
2" 2.4 4.52 Pipe Size 1 2 3 4
1 = 25.4 mm
3" 3.5 9.62 1-1/2" 8" 16" 26" 37"
1 ft = 304.8 mm
4" 4.5 15.9 2" 9" 20" 31" 43"
1sq in = 6.45 sq cm = 0.000645 sqm
6" 6.6 34.19 3" 12" 27" 41" 58"
8"
1 in3 = 16.39 ml
8.6 58.06 4" - 30" 50" 70"
10" 10.8 91.56 6" - - 71" 97" 1 oz. = 29.5 ml
12" 12.75 127.61 8" - - - 122" 1 gallon = 3.78 litre
Pipe O.D. based on schedule 40 steel pipe and plastic 10" - - - 142"
pipe 12" - - - 167"
Estimations based upon Schedule 40 PVC Plastic Pipe.
* Estimated quantities are approximate. No allowance has
been made for waste.
TABLE 3
3

between the O.D. of a penetrating pipe and the I.D. of the opening through which it passes.
Actual pipe diameter (in.) (O.D.*)

Opening 0.84 1.05 1.3 1.9 2.4 3.5 4.5 5.6 6.6 8.6 10.8 12.8
diameter Nominal pipe size (I.D.)
1/2 3/4 1 1-1/2 2 3 4 5 6 8 10 12
1 0.12
1-1/2 0.60 0.46 0.22
2 1.30 1.14 0.90 0.16
2-1/2 2.18 2.02 1.78 1.04 0.20
3 3.26 3.10 2.86 2.12 1.28
3-1/2 4.54 4.38 4.14 3.40 2.54
4 6.00 5.84 5.62 4.86 4.02 1.48
5 9.54 9.38 9.14 8.40 7.56 5.00 1.86
6 13.86 13.70 13.46 12.72 11.86 9.32 6.18 1.82
7 18.96 18.80 18.56 17.82 16.98 14.42 11.28 6.92 2.14
8 24.84 24.68 24.46 23.70 22.86 20.32 17.18 12.82 8.02
9 31.52 31.36 31.12 30.38 29.54 26.98 23.84 19.48 14.70 2.76
10 38.98 38.82 38.58 37.84 36.98 34.44 31.30 26.94 22.16 10.22
12 56.24 56.08 55.86 55.10 54.26 51.72 48.58 44.22 39.42 27.50 10.74
14 76.66 76.50 76.26 75.52 74.66 72.12 68.98 64.62 59.84 47.90 31.14 13.12
16 100.20 100.10 99.82 99.06 98.22 95.68 92.54 88.18 83.38 71.46 54.70 36.68
Coverages are based on the outside diameter of schedule 40 steel pipe. * For insulated pipes, use the outside diameter of the insulation.
For 1/4" depth, divide above number by 2.
For 1" depth, multiply above number by 2.
For 5/8" depth, multiply above number by 1.25.
For 1-1/4" depth, multiply above number by 2.5.
For 3/4" depth, multiply above number by 1.50.

Estimate only. Assumes no waste.

TABLE 4

Approximate # of 10.1
FS ONE volume Oz.Tubes required Collar length
Pipe I.D. (in.) Pipe O.D. (in.) Collar I.D. (in.) required (cu. in.) required** (in.)
4 4.5 6.5 30.22 1.66 21.42
3 3.5 5.5 24.73 1.35 18.28
2 2.4 4.4 18.68 1.03 14.82
1.5 1.9 3.9 15.94 0.88 13.25
1 1.4 3.4 13.19 0.72 11.68
* Applies to Hilti listed systems using retaining colllars refer to system(s) for details. Volumes are approximate, and assumes no waste.
** Collar length assumes the ends overlap 1". Volume of FS-ONE calculated with retaining collar item no. 00283225s

www.hilti.com
59
Estimating Tables

Estimating tables for joints


TABLE 1
Top of wall joint estimation table for CP 601S, CP 606 and CP 506 (Fluted deck only deck ribs perpendicular to wall), table is based on a
1/2" joint and there would be no overspray with sealants.

Joint Width 1-1/2" 2" 3"


1.2 lineal feet/10.5 oz. tube 1.1 lineal feet/10.5 oz. tube 0.82 lineal feet/10.5 oz. tube
1/2" 2.2 lineal feet/600 ml foil pack 2.1 lineal feet/600 ml foil pack 1.5 lineal feet/600 ml foil pack
14.1 lineal feet/gallon 13.5 lineal feet/gallon 10.0 lineal feet/gallon
Estimations based upon 1/2" product depth on both sides of the wall. For 1/4" depth, multiply values by 2. Estimates may vary depending on deck type. All estimates are approximate, and

TABLE 2

to wall)

Joint Width 1-1/2" 2" 3"


1.9 lineal feet/10.5 oz. tube 2.1 lineal feet/10.5 oz. tube 1.9 lineal feet/10.5 oz. tube
1/2" 3.5 lineal feet/600 ml foil pack 4.0 lineal feet/600 ml foil pack 3.6 lineal feet/600 ml foil pack
23.2 lineal feet/gallon 26.1 lineal feet/gallon 23.6 lineal feet/gallon
Estimations based upon 5/8" product depth on both sides of the wall. For 1-1/4" depth, divide values by 2. Estimates may vary depending on deck type. All estimates are approximate, and
assume no waste.

TABLE 3

a 1/2" joint and there would be no overspray with sealants.


Lineal Feet/10.5 oz. Tube Lineal Feet/600 ml Foil Pack Lineal Feet/Gallon
Sealant Depth (in.) Sealant Depth (in.) Sealant Depth (in.)

Joint Width 1/4 1/2 5/8 1-1/4 1/4 1/2 5/8 1-1/4 1/4 1/2 5/8 1-1/4
1/4" 25.2 12.6 10.08 5.04 48.0 24.0 19.2 9.6 308 154 123 61
1/2" 12.6 6.3 5.04 2.52 24.0 12.0 9.6 4.8 154 77 61 30
3/4" 8.4 4.2 3.36 1.68 16.0 8.0 6.4 3.2 102 51 41 20
1" 6.3 3.15 2.52 1.26 12.0 6.0 4.8 2.4 76 38 30 15
1-1/4" 5.04 2.52 * * 9.6 4.8 * * 60 30 * *
1-1/2" 4.2 2.1 * * 8.0 4.0 * * 50 25 * *
2" 3.14 1.57 * * 6.0 3.0 * * 38 19 * *
2-1/2" 2.52 1.26 * * 4.8 2.4 * * 30 15 * *
3" 2.1 1.05 * * 4.0 2.0 * * 24 12 * *
3-1/2" 1.8 0.9 * * 3.5 1.7 * * 22 11 * *
6" 1.0 0.52 * * 2.0 1.0 * * 12 6 * *
7" 0.9 0.45 * * 1.7 0.87 * * 11 5.5 * *
8" 0.78 0.39 * * 1.5 0.76 * * 9.6 4.8 * *
For wall to wall and top of wall joints, values shown are for one side of the wall only. Divide values by 2 to estimate for both sides of wall. Estimates may vary depending on deck type.

TABLE 4

Joint Width 1-1/2" 2" 3"


1/4" 38.5 lineal feet/gallon 34.2 lineal feet/gallon 28.0 lineal feet/gallon
1/2" 34.2 lineal feet/gallon 30.8 lineal feet/gallon 25.6 lineal feet/gallon
3/4" 30.8 lineal feet/gallon 28.0 lineal feet/gallon 23.6 lineal feet/gallon
1" 28.0 lineal feet/gallon 25.6 lineal feet/gallon 22.0 lineal feet/gallon
1-1/2" 23.6 lineal feet/gallon 22.0 lineal feet/gallon 19.2 lineal feet/gallon
2" 20.5 lineal feet/gallon 19.3 lineal feet/gallon 17.1 lineal feet/gallon
2-1/2" 18.1 lineal feet/gallon 17.1 lineal feet/gallon 15.4 lineal feet/gallon
3" 16.2 lineal feet/gallon 15.4 lineal feet/gallon 14.0 lineal feet/gallon
3-1/2" 14.6 lineal feet/gallon 14.0 lineal feet/gallon 12.8 lineal feet/gallon
Estimations based upon 1/8" product depth with 1/2" overlap and installation on both sides of the wall. For 1/4" depth, divide values by 2.

may vary depending on deck type. All estimates are approximate, and assume no waste.

Visit the local website for more information on products and services.
60
Estimating Tables

Estimating tables for joints


TABLE 5
General joint estimation table for CFS-SP
WB Firestop Joint Spray, and Unit Conversion Table
wall, top of wall, curtain wall) 1 = 25.4 mm
1 ft = 304.8 mm
Joint Width plus Lineal Feet/
Joint Width overlap Gallon 1sq in = 6.45 sq cm = 0.000645 sqm

1/2" 1-1/2" 102 1 in3 = 16.39 ml


1 oz. = 29.5 ml
3/4" 1-3/4" 88
1 gallon = 3.78 litre
1" 2" 77
1-1/2" 2-1/2" 61
2" 3" 51
3" 4" 38
4" 5" 30
5" 6" 26
6" 7" 22
8" 9" 17
Estimations based upon 1/8" product depth, with 1/2"
overlap. For 1/4" depth, divide values by 2. For wall to
wall and top of wall joints, divide values by 2 to estimate
for both sides of wall.
All estimates are approximate and assume no waste.

www.hilti.com
61
Engineering
Judgment
Process

Engineering Judgment
Process
Hilti has performed extensive testing in both through-penetration and construction
joint applications. However, due to variations in construction throughout the phases
of a project, it is not possible to test every application that may be encountered.

For these situations, Hilti has developed a process for creating custom drawings
to accommodate particular applications. Hilti custom drawings, or Engineering
Judgments, are developed through the careful and restricted application of accepted
re protection engineering principles and guidelines set forth by the IFC. Test data of
like systems are analyzed and applied toward similar applications that do not exactly
meet the criteria of a current UL Listed System.

If the systems listed in this guide do not accommodate a particular application,


please photocopy, complete, and submit the appropriate form(s) to request an
Engineering Judgment on the following page. Once received, the requested
information will be evaluated and an Engineering Judgment will be created, if
possible.

Support
Firestop Design Center Support Call 800-HILTI (44584)
Hilti Online
www.hilti.ae E: ae.contactus@hilti.com

Hilti. Outperform. Outlast.


575
575

Visit the local website for more information on products and services.
62
Hilti. Outperform. Outlast.

Remarks

www.hilti.com
63
Legislation

The UL Fire resistance nomenclature directory

The Fire resistance Directory utilizes an alpha-numeric numbering system: Basic number
system = ALPHA-ALPHA-NUMERIC

Through Penetrations
The first letter represents The second letter(s) provide The four digit number EXAMPLE: CAJ1150
what is being penetrated: more information about the describes the penetrating
floor or wall: item(s):
C = FLOOR OR WALL PENETRATION
F = FLOOR A = CONCRETE FLOORS 5 INCHES 0000 0999 BLANK OPENINGS A = CONCRETE FLOORS 5 OR LESS
W = WALLS THICK OR LESS 1000 1999 METAL PIPE CONDUIT J = CONCRETE OR MANSONRY
B = CONCRETE FLOORS GREATERE OR TUBING WALLS 8 OR LESS
C = FLOORS OR WALLS (COMBINED)
THAN 5 INCHES THICK 2000 2999 NONMETALLIC PIPE
C = FRAMED FLOORS CONDUIT OR TUBING 1150 = METAL PIPE, CONDUIT OR
FLOOR/CEILING ASSEMBLIES TUBING
3000 3899 CABLES
D = STEEL DECK CONSTRUCTION 4000 4999 CABLE TRAYS
E THRU I = NOT USED AT THE 5000 5999 INSULATED PIPES
PRESENT TIME
6000 6999 MISCELLANEOUS
J = CONCRETE OR MANSONRY ELECTRICAL (BUSWAY)
WALLS 8 INCHES THICK
7000 7999 MISCELLANEOUS
K = CONCRETE WALLS GREATER MECHANICAL
THAN 8 INCHES THICK
8000 8999 MIXED PENETRATING
L = FRAMED WALLS - GYPSUM ITEMS
WALLBOARD ASSEMBLIES
9000 9999 RESERVED FOR
M = BULKHEADS FUTURE USE
N THRU Z = NOT USED AT THE
PRESENT TIME

Joint Systems
The first letters indentify the The third letter signifies the The four digit number EXAMPLE: HWD0042
type or joint: movement capabilities of the describes the nominal joint
joint system: width: HW = HEAD-OF-WALL
D = ALLOWS MOVEMENT
FF = FLOOR-TO-FLOOR S = NO MOVEMENT (STATIC) 0000 0999 LESS THAN OR (DYNAMIC)
WW = WALL-TO-WALL EQUAL TO 2
D = ALLOWS MOVEMENT (DYNAMIC)
FW = FLOOR-TO-WALL 1000 1999 GREATER THAN 2
AND LESS THAN OR 0042 = LESS THAN OR EQUAL TO 2
HW = HEAD-TO-WALL EQUAL TO 6
CG = WALL-TO WALL JOINTS 2000 2999 GREATER THAN 6
INTENDED AS CORNER AND LESS THAN OR
GUARDS EQUAL TO 12
BW = BOTTOM OF WALL 3000 3999 GREATER THAN 12
AND LESS THAN OR
EQUAL TO 24
4000 4999 GREATER THAN 24

Perimeter Fire Containment Systems


The first letters identify the The third letter signifies the The four digit number
perimeter fire containment movement capabilities of the describes the nominal joint
system: joint system: width:

CW = CURTAIN WALL S = NO MOVEMENT (STATIC) 0000 0999 LESS THAN OR


EQUAL TO 2
D = ALLOWS MOVEMENT (DYNAMIC)
1000 1999 GREATER THAN 2
AND LESS THAN OR
EQUAL TO 6
2000 2999 GREATER THAN 6
AND LESS THAN OR
EQUAL TO 12

Visit the local website for more information on products and services.
64
Legislation

Building regulations (United States of America)

Code References

Building Code Through Membrane Construction Joints Curtain Wall


(Year) Penetrations Penetrations

IBC (2000) 711.3.1.2 711.3.2 712.3 712.4


711.4.1.2 711.4.2 705.10
705.9 706.8
706.7 707.9
707.8 708.8
708.7 709.7
709.6 710.6
710.5

IBC (2003) 712.3.1.2 712.3.2 713.3 713.4


712.4.1.2 712.4.2 705.10
705.9 706.9
706.8 707.9
707.8 708.8
708.7 709.7
709.6 711.6
711.5

IBC (2006) 712.3.1.2 712.3.2 713.3 713.4


712.4.1.1.2 712.4.1.2 713.6
705.9 705.10
706.7 706.8
707.8 707.9
708.7 708.8
709.6 709.7
711.5 711.6

IBC (2009) 713.3.1.2 713.3.2 714.3 714.4


713.4.1.1.2 713.4.1.2 714.6
706.9 706.10
707.7 707.8
708.8 708.9
709.7 709.8
710.6 710.7
712.5 712.6

NFPA 101 (2000) 8.2.3.2.4.1 8.2.2.2


A.8.2.2.2
A.8.2.3.2.4.2 A.8.3.2
8.2.5.2 8.2.5.2
A.8.2.5.2 A.8.2.5.2
8.3.2
NFPA 101 (2006) 8.3.5.1 8.3.5.6 8.3.6.5
8.3.5.1.3 8.3.6.6
8.3.5.1.4
8.3.5.5.1

NFPA 70
National Electrical
Code 300-21

2006 International Building Code (IBC)


Penetrations (Sec. 712)

Fire resistance rated walls Hilti Interpretation


712.3.1.2

www.hilti.com
65
Accessories
Legislation

Hilti Interpretation
712.4.1.1.2

Fire Resistant Joint Systems (Sec.713)

713.1 Hilti Interpretation

713.3 Hilti Interpretation

713.4 Hilti Interpretation

E2307.

2000 NFPA Life Safety Code (NFPA 101)

Construction and Compartmentation (Sec. 8.2)

Section 8.2.2.2 Hilti Interpretation

Visit the local website for more information on products and services.
66
Legislation

Section A.8.2.2.2 Hilti Interpretation

Section 8.2.5.2 Hilti Interpretation

Section A.8.2.5.2 Hilti Interpretation


ASTM E814 Methods for Fire Tests of Through-Penetration
Fire Stops,

Methods for Fire Tests of Through-Penetration Fire Stops.

Section A.8.2.5.2 Exception No. 3 Hilti Interpretation

Section 8.3.2 Hilti Interpretation

Section A.8.3.2 Hilti Interpretation

Penetrations and Miscellaneous Openings in Fire Barriers (8.2.3.2.4)

Section 8.2.3.2.4.1 Hilti Interpretation

1.

2.

3.

www.hilti.com
67
Accessories
Legislation
Firestop code overview

Section A.8.2.3.2.4.27LUL[YH[PVUZ[OYV\NOYLIHYYPLYZI` Hilti Interpretation


JHISLZ^PYLZ[\ILZJVUK\P[Z]LU[ZHUKV[OLYWLUL[YH[PUN
;OYV\NOWLUL[YH[PVUZJHUIL[LZ[LKPUHJJVYKHUJL^P[O5-7(
P[LTZHZ^LSSHZPUZ\SH[PVUHUKJV]LYPUNZVUWLUL[YH[PUN
^OPJOPZHM\SSZJHSL^HSSVYVVY[LZ[YLX\PYPUNZWLJPTLU
P[LTZZOV\SKTLL[VULVM[OLMVSSV^PUNJYP[LYPH!
ZPaLZVM_M[_T7YHJ[PJHSS`ZWLHRPUN[OPZPZUL]LY
;OL`ZOV\SKIL[LZ[LKPUHJJVYKHUJL^P[O5-7( KVULK\L[V[OL]LY`OPNOJVZ[VM[OLSHYNL[LZ[ZWLJPTLUHUK
Standard Methods of Tests of Fire Endurance of Building YLX\PYLKM\YUHJL
Construction and Materials, HZWHY[VMHYH[LKHZZLTIS`
;OYV\NOWLUL[YH[PVUZJHUIL[LZ[LKPUHJJVYKHUJL^P[O
;OL`ZOV\SKILWYV[LJ[LKI`HUHWWYV]LK[OYV\NO (:;4,^OPJOPZ[OLZTHSSZJHSL[LZ[ZWLJPHSS`KL]LSVWLK
WLUL[YH[PVUZ`Z[LT[OH[OHZILLU[LZ[LKPUHJJVYKHUJL MVY[LZ[PUNVMWLUL[YH[PVUYLZ[VWWPUN;OLYLHYL[OV\ZHUKZ
with ASTM E814, Methods for Fire Tests of Through- VMZ`Z[LTZ[LZ[LK[V[OPZZ[HUKHYKHUKSPZ[LKPU[OL<3YL
Penetration Fire Stops. YLZPZ[HUJLKPYLJ[VY`HUKV[OLY[LZ[SHISPZ[PUNKPYLJ[VYPLZPLZ

2006 NFPA Life Safety Code (NFPA 101)

8.3.5.1 Firestop Systems and Devices Required.

7LUL[YH[PVUZMVYJHISLZJHISL[YH`ZJVUK\P[ZWPWLZ[\ILZ Hilti Interpretation


JVTI\Z[PVU]LU[ZHUKL_OH\Z[]LU[Z^PYLZHUKZPTPSHY
(U`WLUL[YH[PVUZ[OYV\NOYLYLZPZ[HUJLYH[LK^HSSZVVYZ
P[LTZ[VHJJVTTVKH[LLSLJ[YPJHSTLJOHUPJHSWS\TIPUNHUK
VYJLPSPUNZT\Z[ILWYV[LJ[LKI`HYLZ[VWZ`Z[LT[OH[OHZ
JVTT\UPJH[PVUZZ`Z[LTZ[OH[WHZZ[OYV\NOH^HSSVVYVY
ILLU[LZ[LK[V(:;4,VY<3 ^OPJOHYLLZZLU[PHSS`
VVYJLPSPUNHZZLTIS`JVUZ[Y\J[LKHZHYLIHYYPLYZOHSSIL
LX\P]HSLU[[LZ[WYV[VJVSZ
WYV[LJ[LKI`HYLZ[VWZ`Z[LTVYKL]PJL;OLYLZ[VWZ`Z[LT
VYKL]PJLZOHSSIL[LZ[LKPUHJJVYKHUJL^P[O(:;4, ;OLYLYH[PUN-VM[OLYLZ[VWZ`Z[LTMVYH^HSSZOHSSLX\HS
Standard Test Method for Fire Tests Through- Penetration [OLYH[PUNVM[OL^HSS5V;YH[PUNPZYLX\PYLK
Firestops, or UL 1479, Standard for Fire Tests of Through-
Penetration Firestops,H[HTPUPT\TWVZP[P]LWYLZZ\YL -VYWLUL[YH[PVUZ[OYV\NOHVVY[OLJOVZLUYLZ[VWZ`Z[LT
KPMMLYLU[PHSVMPU^H[LYJVS\TU54IL[^LLU[OL T\Z[OH]LH;YH[PUNHUKHU-YH[PUN[OH[HYLIV[OLX\HS[V
L_WVZLKHUK[OL\UL_WVZLKZ\YMHJLVM[OL[LZ[HZZLTIS` [OLYH[PUNVM[OLVVY/V^L]LYPM[OLVVYWLUL[YH[PVUPZ
JVUJLHSLK^P[OPUH^HSSVYPM[OLWLUL[YH[PUNP[LTPZSVJH[LK
8.3.5.1.3.-PYLZ[VWZ`Z[LTZHUKKL]PJLZZOHSSOH]LHU-YH[PUN Z\JO[OH[P[PZL_WLJ[LK[VUV[L]LYILPUJVU[HJ[^P[O
VMH[SLHZ[OV\YI\[UV[SLZZ[OHU[OLYLX\PYLKYLYLZPZ[P]L JVTI\Z[PISLTH[LYPHSZ[OLUVUS`[OL-YH[PUNPZYLX\PYLK
YH[PUNVM[OLYLIHYYPLYWLUL[YH[LK
0MHWPWPUNJOHUNLZMYVTWSHZ[PJ[VTL[HS[OH[[YHUZP[PVUT\Z[
8.3.5.1.47LUL[YH[PVUZPUYLYH[LKOVYPaVU[HSHZZLTISPLZZOHSS VJJ\YHTPUPT\TKPZ[HUJLVMPUJOLZ TTMYVT^OLYL
ILYLX\PYLK[VOH]LH;YH[PUNVMH[SLHZ[OV\YI\[UV[SLZZ [OLWPWLPZYLZ[VWWLKH[[OL^HSSVYVVY
[OHU[OLYH[PUNVM[OLOVYPaVU[HSHZZLTIS`HUKZOHSSUV[IL
YLX\PYLKMVY[OLMVSSV^PUN!
-SVVYWLUL[YH[PVUZJVU[HPULK^P[OPU[OLJH]P[`VMH^HSS
HZZLTIS`
7LUL[YH[PVUZ[OYV\NOVVYZVYVVYHZZLTISPLZ^OLYL
[OLWLUL[YH[PVUPZUV[PUKPYLJ[JVU[HJ[^P[OJVTI\Z[PISL
TH[LYPHS
8.3.5.5.1>OLYLWPWPUNWLUL[YH[LZHYLYLZPZ[HUJLYH[LK^HSS
VYVVYHZZLTIS`JVTI\Z[PISLWPWPUNZOHSSUV[JVUULJ[[V
UVUJVTI\Z[PISLWPWPUN^P[OPUPU TTVM[OLYLZ[VW
Z`Z[LTVYKL]PJL^P[OV\[KLTVUZ[YH[PVU[OH[[OL[YHUZP[PVU
^PSSUV[YLK\JL[OLYLYLZPZ[HUJLYH[PUNL_JLW[PU[OLJHZLVM
WYL]PV\ZS`HWWYV]LKPUZ[HSSH[PVUZ

8.3.5.6 Membrane Penetrations

8.3.5.6.14LTIYHULWLUL[YH[PVUZMVYJHISLZJHISL[YH`Z Hilti Interpretation


JVUK\P[ZWPWLZ[\ILZJVTI\Z[PVU]LU[ZHUKL_OH\Z[ (U`WLUL[YH[PVUZVM[OLTLTIYHULVULMHJLVMHYL
]LU[Z^PYLZHUKZPTPSHYP[LTZ[VHJJVTTVKH[LLSLJ[YPJHS YLZPZ[HUJLYH[LK^HSSVVYVYJLPSPUNZT\Z[ILWYV[LJ[LKI`
TLJOHUPJHSWS\TIPUNHUKJVTT\UPJH[PVUZZ`Z[LTZ[OH[ HYLZ[VWZ`Z[LT[OH[OHZILLU[LZ[LK[V(:;4,VY<3
WHZZ[OYV\NOHTLTIYHULVMH^HSSVVYVYVVYJLPSPUN 1479
HZZLTIS`JVUZ[Y\J[LKHZHYLIHYYPLYZOHSSILWYV[LJ[LKI` -V\YL_JLW[PVUZL_PZ[^OPJOHSSV^HTLTIYHULWLUL[YH[PVU
HYLZ[VWZ`Z[LTVYKL]PJLHUKZOHSSJVTWS`^P[O ^P[OV\[[OL\ZLVMHYLZ[VWZ`Z[LT[VWYV[LJ[P[0UIYPLM[OL
through 8.3.5.5.2. L_JLW[PVUZHYLMVY!
8.3.5.6.2;OLYLZ[VWZ`Z[LTVYKL]PJLZOHSSIL[LZ[LKPU *LPSPUNZ[OH[KVU[WYV]PKLHU`YLYLZPZ[HUJL
HJJVYKHUJL^P[O(:;4,Standard Test Method for Fire 4L[HSWPWLZHUKJVUK\P[ZL_JLW[HS\TPU\T[OH[HYLPU
Tests Through- Penetration Firestops, or UL 1479, Standard OVSLZ[OH[KVU[HKK\W[VTVYL[OHUM[T
for Fire Tests of Through-Penetration Firestops,H[HTPUPT\T WLYM[ TVMJLPSPUNHYLHHUK[OH[OH]LILLU
WVZP[P]LWYLZZ\YLKPMMLYLU[PHSVMPU^H[LYJVS\TU5 ZLHSLK^P[OHTH[LYPHSHJJLW[HISL[V[OL(\[OVYP[`/H]PUN
4IL[^LLU[OLL_WVZLKHUK[OL\UL_WVZLKZ\YMHJLVM[OL 1\YPZKPJ[PVU
[LZ[HZZLTIS`\USLZZVULVM[OLMVSSV^PUNHWWSPLZ!
9LJLZZLKLSLJ[YPJHSIV_LZ[OH[OH]LILLUZWLJPHSS`[LZ[LK
4LTIYHULWLUL[YH[PVUZ[OH[VMJLPSPUNZ[OH[HYLUV[HU HUKSPZ[LKMVY\ZLPU[OLYLYLZPZ[HUJLYH[LK^HSSVYVVY
PU[LNYHSWHY[VMHYLYLZPZ[HUJLYH[LKVVYJLPSPUNVYYVVM
-PYLZWYPURSLYOLHKWPWLWLUL[YH[PVUZ[OH[OH]LHTL[HS
JLPSPUNHZZLTIS`ZOHSSILWLYTP[[LK
LZJ\[JOLVUWSH[LH[[OLWVPU[VMTLTIYHULWLUL[YH[PVU
69

Visit the local website for more information on products and services.
68
Legislation

www.hilti.com
69
Accessories
Legislation

European Technical Approval (ETA).


European Technical Approval is harmonised test standard based on Independent
Testing based on EN Standards.

It symbolises that product is in conformity with essential requirements of the Construction


Product Directive (CPD) and the product has been subjected to appropriate conformity

Introduction
Hilti Firestop systems for penetration seals of pipes, cables and construction joints within re
rated walls and oors will be sold with a European Technical Approval (ETA) and therefore be
provided with a CE mark from January 2012. This will lead to more transparency, higher
quality and improved safety.

Difference between ETA and National Approvals


European Technical Approval National Approvals
All regulated properties related to the essential Only resistance to re is assessed. No full assessment of
requirements are assessed. Not only re. the product properties.
Assessment of durability and servicability. Not required.
3rd party control. No 3rd party control.
Must be accepted throughout Europe. Not accepted in other countries (only in case of mutual
agreement).

Advantages of ETA
Safety
More comparable results based on strict and demanding testing
Higher building performance through additional testing according to ofcial standards
More realistic results - products tested for essential performance criteria, not only re.
- Health and Environment
- Mechanical Resistance
- Movement
- Durability and Servicability

Transparency
Independent testing and certication according to specied test programme - easy product comparison
Harmonised tests throughout Europe
The Firestop Products are covered according to common guidelines (ETAG 026) which enables customers
to act according to a harmonised International Standard

Reliability and Quality


Higher quality of products - third party approval
Production quality control monitored by approved third party
CE marking for the Firestop Products to indicate ETA and third party approval with Certicate of Conformity.

Visit the local website for more information on products and services.
70
Estimating Tables

Hilti CFS-DM Firestop Documentation Manager

FOR PEACE OF MIND.


Its never been easier to plan and document every

Firestop Documentation Manager. This comprehensive


software application allows planners, building owners and

installations, as well as produce compliant installation

Documentation Manager.

Hilti restop documentation


compliant, simple and efcient.

and installers and demands considerable administrative work. In order to

project participants including the building owner, general contractor, as well as


supervisory authorities.

Hilti CFS-DM Firestop Documentation Manager this task becomes almost trivial

application.

documentation - all from one single software application.

www.hilti.com
71
Accessories

Simplicity itself.
Professional restop documentation
management in just 3 easy steps.

1 Prepare the project


The project is planned using the user-friendly application.

plans of the building integrated as necessary and all


necessary data set out.

2 Record the re seal

are recorded on the spot using a smartphone or tablet


computer. This data is transferred straight to the database

label carrying the corresponding QR code.

3 Create a report
After completion of the project, or in an intermediate step,
all data from the project is retrieved and a report then
produced automatically. Information about the project can
be supplemented at any time. The report can also be

in a list and subsequently processed. All reports created


are saved automatically.

Visit the local website for more information on products and services.
72
Estimating Tables

Firestop Documentation

To learn more about how CFS-DM can be


implemented in your facility, visit
www.hilti.ae/cfs-dm

Get started in 5 easy steps


Download the free app from iTunes or Google Play
Buy your full license online or call 800-Hilti (44584) for full enrollment.
Receive a welcome email with a username and password

Create a project and start documenting

The CFS-DM software program offers following package options:


Standard (#2093088) Basic (#2093086) Premium (#2093330)
Unlimited Users Unlimited Users Unlimited Users
Multiple reports Multiple reports Multiple reports
2D Plan Integration 2D Plan Integration 2D Plan Integration
Upload technical documents Upload technical documents Upload technical documents

Permanently save the documentation Permanently save the documentation Permanently save the documentation
for up to 500 penetrations for up to 5000 penetrations for up to 20,000 penetrations

Extension options
Barcodes and Stickers 10,000 penetrations
#2096831 Identication sticker small 500 per roll 20,000 penetrations
#2096832 Identication sticker small 2000 per roll 50,000 penetrations

System requirements
Hilti CFS-DM is a web-based application that can be
accessed through the internet using a standard browser
utilizing Microsoft Internet ExplorerTM, Google ChromeTM
and Mozilla FirefoxTM
The mobile application is available for devices running
Apple iOS 6 or higher (Apple iPhoneTM and iPadTM),
AndroidTM 2.3 or higher.

Hilti. Outperform. Outlast.


Hilti Emirates L.L.C | Dubai | UAE | Toll Free 800-Hilti (44584) | www.hilti.ae

www.hilti.com
73
www.hilti.com

You might also like