You are on page 1of 3

2/22/2016 Exampleof315psito420mAConversion|InstrumentationTools

INSTRUMENTATION TOOLS

Example of 3-15 psi to 4-20mA Conversion


Formulas September23,2015

A currenttopressure transducer is used to convert a 420 mA electronic


signal into a 315 PSI pneumatic signal.This particular transducer is
configured for reverse action instead of direct, meaning that its pressure
outputat4mAshouldbe15PSIanditspressureoutputat20mAshouldbe
3 PSI. Calculate the necessary current signal value to produce an output
pressureof12.7PSI.

Wearesolvingthisproblemusingstandard420mAconversionFormula.
Clickhereforformula

Reverseactinginstrumentsarestilllinear,andthereforestillfollowthe
slopeinterceptlineformulay=mx+b,albeitwithanegativeslope:

http://instrumentationtools.com/exampleof315psito420maconversion/ 1/3
2/22/2016 Exampleof315psito420mAConversion|InstrumentationTools

Calculatingandsubstitutingtheslope(m)valueforthisequation,usingthefull
riseoverrunofthelinearfunction.Notehowtheriseisactuallyafallfrom
20milliampsdownto4milliamps,yieldinganegativevalueform:

http://instrumentationtools.com/exampleof315psito420maconversion/ 2/3
2/22/2016 Exampleof315psito420mAConversion|InstrumentationTools

Therefore,acurrentsignalof7.07mAisnecessarytodrivetheoutputofthis
reverseactingI/Ptransducertoapressureof12.7PSI.

AlsoSee:InstrumentationonlineTools

InstrumentationSearchterms:

howtoconvertpsito420mAsignal
i/p420maoutput315psiformula
psitomilliamps
rumus420mAke315psi

POSTED BY S BHARADWAJ REDDY