Estimation of Air Volume Flowing Past Doors when Doors are Closed
i) Design criteria based on MS1472
ii) Leakage Area Calculation
Based on 50 Pa pressure differential and interpolation of data from Table 3 and 4
(MS1472)
Qc 0.35
F 2.66
n 30
Qd (CMS) 0.03 (assume lift shaft vent size = 0.16 sqr.m)
Qd (CMH) 111.95
Number of Lift(s) 1
Total Air Leakage through Closed Lift Landing Doors 3359 (D)
Table 6 (MS1472)
Value of F (vent size)
No. of Pressurised lobbies opening into the lift shaft (=n)
0.1sqr.m 0.16sqr.m
1 0.86 0.94
2 1.28 1.6
3 1.46 1.99
4 1.54 2.22
5 1.58 2.35
6 1.61 2.44
7 1.62 2.49
8 1.63 2.53
9 1.64 2.56
10 1.645 2.58
12 1.65 2.6
14 1.655 2.62
16 1.66 2.63
Above 16 1.66 2.66
The air flow of fans The air flow of fans Pressurrisation Shaft
Lift Lobby selected (CMH) selected (CFM) Dimension (W x D)
1 29863 17578 1950X650