TRANSFORMADOR Y AUTOTRANSFORMADOR MONOFSICA

Catota acata Bryan Alonso


EI
Quito, Ecuador
bryan_bc150hotmail.com

Chaln Martnez Esteban Eduardo


EI
Quito, Ecuador
esteban_chalan@hotmail.com

AbstractThis document details how the connections were made 2.-Tabular los datos obtenidos durante la prctica.
to take data in a transformer in phase reducer and elevator, in
addition in an autotransformer in phase reducer and elevator, for Tabla2. Valores de Continuidad
this we must have knowledge on how to make these connections
to obtain this data the same as are taken with a multimeter with Parmetro Valor (V)
amperimetric tweezers measuring their output and input Vf 20.3
voltages, also their output and input currents realizing it with
four loads for both the transformer and the autotransformer in Vs 40.1
its two previously named phases.

I. INTRODUCTION (HEADING 1) Para Transformador


Al momento de comenzar la respectiva prctica primero
obtuvimos conocimientos sobre la debidas y correctas
conexiones que debemos realizar para tener un transformador Tabla3. Valores fase reductor (vaco)
y un autotransformador en sus fases reductor y elevador , como
en la prctica anterior ya obtuvimos conocimientos sobre como Parmetro Valor
energizar la mesa de trabajo donde estamos trabajando se nos 126.8
facilitara esta parte ; despus con la utilizacin de un Vf [v]
autotransformador y resistencias que se encuentran en el
laboratorito conectadas adecuadamente y ya con el Vs 63 [v]
conocimiento de cmo funciona un transformador realizamos Ie 0.1 [A]
la toma de datos correspondientes.
Is 0.2 [A]
II. CUESTIONARIO

1.- Presentar los datos de placa de los transformadores


utilizados. Tabla4. Valores de cargas en fase reductor
Tabla1. Datos de placa
Carga 1
Transformadores Datos de placa Parmetro Valor
Ve 102.5[v]
Transformador Voltaje de 110 Vs 60.6[v]
Ie 0.4[A]
VA de 18.2
Is 0.8[A]
Carga 2
Transformador M1 Np1:Ns1=1:1 Ve 102[v]
Np1:Ns2=1:1 Vs 58.5[v]
Np2:Ns1=1:1
Np2:Ns2=1:1 Ie 0.8[A]
Vn=127 V Is 1.4[A]
Transformador de 0 a 100 V
Variable
Escuela Politcnica Nacional
Facultad de Ingeniera Mecnica
GR21
Carga3 Para Autotransformador

Ve 101.3[v]
Vs 55.4[v] Tabla7. Valores fase reductor (vaco)

Ie 1.1[A] Parmetro Valor


Is 2[A] Vf 127 [v]
Carga4 Vs 83.7[v]
Ve 101.1[v] Ie 3.1[A]
Vs 52.2[v] Is 0.1 [A]
Ie 1.4[A]
Is 2.6[A]
Tabla8. Valores de carga en fase reductor

Carga 1
Tabla5. Valores fase elevador (vaco)
Parmetro Valor
Parmetro Valor Ve 127[v]
Vf 63.7 [v] Vs 1.2[v]
Vs 126 [v] Ie 3.1[A]
Ie 0.2 [A] Is 0.1[A]
Is 0.1 [A] Carga 2
Ve 126.8[v]
Vs 0.6[v]
Tabla6. Valores de cargas en fase elevador
Ie 3.2[A]
Carga 1 Is 3.1[A]
Parmetro Valor Carga 3
Ve 62.5[v] Ve 126.4[v]
Vs 101.6[v] Vs 0.4[v]
Ie 3[A] Ie 3.1[A]
Is 1.3[A] Is 0.1[A]
Carga 2 Carga 4
Ve 62[v] Ve 126.4[v]
Vs 77[v] Vs 0.3[v]
Ie 4.5[A] Ie 3.2[A]
Is 1.9[A] Is 0[A]
Carga 3
Ve 62.1[v]
Vs 59.9[v] Tabla9. Valores fase elevador (vaco)

Ie 5.2[A] Parmetro Valor


Is 2.2[A] Vf 126.9 [v]
Carga 4 Vs 2[v]
Ve 62.2[v] Ie 0.1[A]
Vs 48.5[v] Is 0.2 [A]
Ie 5.5[A]
Is 2.4[A]
Escuela Politcnica Nacional
Facultad de Ingeniera Mecnica
GR21
Tabla10. Valores de Carga en fase elevador Vvaco Vcarga
=
Vcarga
Carga 1
Parmetro Valor 63 60.6
=
60.6
Ve 127.2[v]
Vs 0.8[v] = 0.0396
Ie 0.1[A]
Is 0.2[A] -Carga Elevador
Carga 2
Ve 127.1 [v] Potencia de entrada y salida:
Vs 0.4[v]
Ie 0.1[A] =
Is 0.2[A] = 62.53
= 187.5
Carga 3
Ve 127.2[v] =101.6x1.3
= 132.08
Vs 0.6[v]
Ie 0.1[A]
Rendimiento:
Is 0.2[A]
Carga 4
Pout
Ve 127.2[v] =
Pin
Vs 0.5[v]
132.08
Ie 0.1[A] = x 100%
187.5
Is 0.2[A]
=0.70445

3.-Para cada paso de carga, calcular la potencia de entrada,


Regulacin de voltaje:
de salida y la regulacin de voltaje.

Transformador Vvaco Vcarga


=
Vcarga
-Carga Reductor
126 101.6
Potencia de entrada y salida: =
101.6
= = 0.2401
= 102.50.4
= 41
Tabla11. Valores para diferentes cargas en el transformador
=60.6x0.8
= 48.5 Transformador Reductor

Rendimiento:
Potencia Potencia
Regulacion De
Carga De De Rendimento
Pout Entrada Salida
Voltaje
=
Pin
12,6 99,36908517 0
48.5 Vacio 12,68
= x 100%
41 41 48,48 118,2439024 0,03960396
Carga 1
=1.182 % Carga 2 81,6 81,27 99,59558824 0,085271318

Carga 3 111,43 110,8 99,43462263 0,137184116


Regulacin de voltaje:
Carga 4 141,54 135,72 95,88808817 0,206896552
Escuela Politcnica Nacional
Facultad de Ingeniera Mecnica
GR21
Tabla12. Valores para diferentes cargas en el transformador Figura 3 Regulacin de voltaje

Transformador elevador
Transformador Elevador
Potencia
Potencia Regulacion De
Potencia De Salida
Carga De Rendimento
De Salida Voltaje
Entrada 200
Vacio 12,74 12,6 98,9010989 0
150
Carga 1 187,5 132,08 70,44266667 0,24015748
52,43727599 100 Potencia De
Carga 2 279 146,3 0,636363636
Salida
Carga 3 322,92 131,78 40,80886907 1,103505843 50
Carga 4 342,1 116,4 34,02513885 1,597938144 0
4.-Con los resultados obtenidos en el punto 2 graficar la 0 2 4 6
potencia de salida, rendimiento y regulacin de voltaje en Figura 4. Potencia de salida
funcin de los pasos de carga ( utilice una escala
adecuada)Compare los resultados y justifique sus
diferencias. Rendimento
Transformador Reductor 120
100
Potencia De Salida 80
60
5 Rendimento
40
4
20
3 0
Potencia De
2 0 2 4 6
Salida
1 Figura 5. Rendimiento
0
0 50 100 150 Regulacion De Voltaje
Figura 1. Potencia de salida 2

150
Rendimento 1.5

1 Regulacion De
Voltaje
100 0.5

0
Rendimento 0 2 4 6
50
Figura 6. Regulacin de voltaje

0 5.-Para cada paso de carga, calcular las potencias de


0 1 2 3 4 5 entrada y salida, el rendimiento y la regulacin de voltaje del
Figura 2. Rendimiento transformador con los valores obtenidos en los numerales 5
y 6 del procedimiento.
Regulacion De Voltaje Autotransformador
5 -Carga Reductor
4 Potencia de entrada y salida:
3
Regulacion De =
2 Voltaje = 1273.1
1 = 393.7
0
=1.2x0.1
0 0.1 0.2 0.3
= 0.12
Escuela Politcnica Nacional
Facultad de Ingeniera Mecnica
GR21
Rendimiento:
Autotransformador elevador
Pout
= Potencia
Pin Carga De
Potencia
Rendimento
Regulacion
De Salida De Voltaje
0.12
Entrada
= x 100%
393.7 Vacio 121,44 12,6 10,37549407 0

=3.04x10^-4% Carga 1 453,6 1,82 0,401234568 89


Carga 2 457,56 1,92 0,419617099 104
Regulacin de voltaje: Carga 3 497,25 2,09 0,420311714 113,5455

Vvaco Vcarga Carga 4 511,2 2 0,391236307 125


=
Vcarga
6.-Con los resultados obtenidos en el punto 4 graficar la
83.7 1.2 potencia de salida, rendimiento y regulacin de voltaje en
= funcin de la carga (utilice una escala adecuada).Compare
1.2 los resultados y justifique sus diferencias.
= 68.75
Autotransformador reductor
-Carga Elevador
Potencia de entrada y salida: Potencia De Salida
= 10
= 127.20.1 8
= 12.72
6
Potencia De
=0.8x0.2 4
Salida
= 0.16 2
Rendimiento: 0
-2 0 2 4 6
Pout
= Figura 7. Potencia de salida
Pin

=
0.16
12.72
x 100% Rendimento
2.5
=0.0125%
Regulacin de voltaje: 2
1.5
Vvaco Vcarga
= 1 Rendimento
Vcarga
0.5
2 0.8
= 0
0.8
-0.5 0 2 4 6
= 1.5 Figura 8. Rendimiento
Autotransformador reductor
Regulacion De Voltaje
Potencia
Potencia Regulacion 300
Carga De Rendimento
De Salida De Voltaje
Entrada 250
Vacio 393,7 8,37 2,125984252 0 200
Carga 1 393,7 0,12 0,030480061 68,75
150 Regulacion De
100 Voltaje
Carga 2 405,76 1,86 0,458399054 138,5
50
Carga 3 391,84 0,04 0,010208248 208,25
0
Carga 4 404,48 0 0 278 0 2 4 6
Figura 9. Regulacin de voltaje
Escuela Politcnica Nacional
Facultad de Ingeniera Mecnica
GR21
en el caso de transformadores reductores, elevadores y en los
respectivos autotransformadores.

8.- Seale las aplicaciones del transformador u


Autotransformador elevador autotransformador.

Las aplicaciones de los autotransformadores son utilizados


para la conexin de dos diferentes sistemas de transmisin de
Potencia De Salida tensiones. Son utilizados como transformadores elevadores en
15 centrales para alimentar dos diferentes sistemas de transporte.
Presenta perdidas menores que un transformador normal,
tambin tiene un menor tamao y peso que permite el
10 transporte de potencias superiores.
Potencia De Los transformadores monofsicos son utilizados para
5 Salida disminuir las perdidas mediante la aplicacin del efecto Joule
esto en las subestaciones de transporte de energa elctrica.
Tambin se encuentra mltiples aplicaciones para los
0 transformadores elevadores y reductores en el mismo
0 2 4 6 transporte de energa.
Figura 10. Potencia de salida
Son utilizados tambin como una proteccin a sobrecargas,
con esto nos permite enviar un valor constante a los circuitos
que intenta eliminar los picos que ingresan al circuito
Rendimento manteniendo una valor regular.
12
10 III. CONCLUSIONES
8
6 (Catota Bryan)
Rendimento
4
2 1.- Existe un rendimiento mayor en los trasformadores que en
0 los autotransformadores segn los datos obtenidos de esta
-2 0 2 4 6 prctica.

Figura 11. Rendimiento


2.- En el transformador reductor encontramos un rendimiento
Regulacion De Voltaje constante y elevado que garantiza pocas perdidas de energa.
Tambin encontramos que tanto en el transformador elevador y
150 el reductor la diminucin o aumento de voltaje se complementa
con el aumento y disminucin de la corriente respectivamente.
100
Regulacion De 3.- Tenemos que el nmero de vueltas en el primario respecto
50 Voltaje al secundario es inversamente proporcional a la corriente del
primario respecto a la corriente del secundario.
0
0 2 4 6 (Chaln Esteban)
Figura 12. Regulacin de voltaje
1.- Con la realizacin de la presente practica se pudo realizar
diferentes clculos como la potencia de salida, entrada el
7.-Comparar el rendimiento del transformador monofsico
rendimiento y la regulacin de voltaje los cuales permitieron
con el del autotransformador para el caso de carga mxima, entender de mejor manera basndonos en los resultados sobre
cuando funcionan como levadores y reductores. cmo funciona un transformador y autotransformador.
Al comparar el transformador monofsico y el 2.- Al momento de conectar el transformador en fase reductor y
autotransformador tenemos que el transformador monofsico elevador se puede observar que hay una gran diferencia en lo
es mucho mas eficiente con un rendimiento mucho mayor que que se refiere a sus datos numricos debido a que al momento
varia entre el 90% y el 100%, mientras los valores de de cambiar de reductor a elevador estamos invirtiendo su factor
rendimiento para los auto transformadores nos dan valores de conversin.
muy pequenos de rendimiento. Este mismo caso se repite tanto 3.-Las diferentes conexiones que se realizaron permitieron
tener un mejor enfoque de cmo funciona un transformador y
Escuela Politcnica Nacional
Facultad de Ingeniera Mecnica
GR21
un autotransformador ya que n cada uno se utilizo resistencias 1.- Realizar correctamente las diferentes conexiones en el
para obtener sus valores de voltaje y corriente de entrada y autotransformador antes de energizar el mismo revisar y
salida, adems se realizo una conexin en cortocircuito que verificar las conexiones.
permitieron determinar algunos parmetros en el transformador
y autotransformador.. 2.-Tener un conocimiento claro el funcionamiento de las
diferentes conexiones en el autotransformador, adems de que
debemos utilizar cables que tengan una conexin segura.
IV. RECOMENDACIONES 3.- Si al momento de tomar los diferentes datos obtenidos en la
prctica observamos resultados que no concuerdan con la teora
uno d los posibles fallos es que un fusible se haya quemado por
lo que antes de ser utilizado el autotransformador debemos
(Catota Bryan) revisar los mismo con la utilizacin del multmetro con pinza
amperimtrica.
1.-Revisar previamente el funcionamiento de los
transformadores monofsicos.
V. REFERENCIAS
2.- Realizar unas buenas conexiones de las mquinas para
evitar cortocircuitos o sobrecargas [1] P. San Miguel, Electrotecnia Electricidad Electrnica, Instalaciones
Elctricas y automticas.
[2] J.Stephen Chapman, Mquinas Elctricas, Introduccin a los
Principios de Mquinas, (3ra Ed.), McGraw-Hill,2000,pp8-29.
3.- Comprobar los valores nominales de cada equipo para [3] Trujillo, D.(2009). Diagnstico y actualizacin del tablero de control y mesas de
evitar sobrecargarlos y que se produzca una falla de los trabajo del laboratorio de mquinas elctricas de la Escuela Politcnica Nacional.
mismos. [Tesis de Ingeniera Elctrica]. Recuperado de
http://bibdigital.epn.edu.ec/handle/15000/1598

(Chaln Esteban)
Escuela Politcnica Nacional
Facultad de Ingeniera Mecnica
GR21

You might also like