The ECOLINE series has now been extended to all models and the optimisation package has been developed further for
universal use with different refrigerants at the same time extending the operating ranges.
The refrigerants include: R134a, R404A, R407A, R407C, R407F, R507A, R22, R290 and R1270.
The compressors are already designed for operation with "Low-GWP" HFO refrigerants and HFO-/HFC blends.
The coefficient of performance (COP) of the new ECOLINE models has been improved by an average of 6% up to a maximum
of 12% compared with preceding series.
This is not achieved with a single component, but by optimising the valve plates, reducing flow losses and discharge gas
pulsation as well as specially adapted highly efficient motors with broad band characteristics.
Each ECOLINE is compatible with its predecessor compressor.
These predecessor compressors can be substituted without the need for modifying the system.
Whereas many of the major internal components have been redesigned, the outer shape has remained virtually unchanged:
the same outer dimensions, unchanged mounting points, valve and sensor positions, connections for oil and gas equalisation,
as well as for oil level regulators.
Motor version 2 covers the classic refrigeration applications medium and low temperature refrigeration with one single
product. In many cases it can thus replace a predecessor compressor with motor version 1.
For supermarket applications with R134a, a version with specially adapted motor is available for the ECOLINE models CE4,
BE5 and BE6 motor version 3 in addition to motor version 2.
Motor version 3 has been specially designed for the pressure levels of R134a and focuses on applications in the medium
temperature refrigeration range in modern systems.
For compressors with motor version 3, the standard motor can be operated with a frequency inverter up to 70 Hz (for mains
voltage 400V/3/50Hz).
Rating Conditions: 50Hz , 20 Deg Return Gas, no Sub-Cooling. Shaded areas require additional cooling &/or return vapour limitations.
Rating Conditions: 50Hz , 20 Deg Return Gas, no Sub-Cooling. Shaded areas require additional cooling &/or return vapour limitations.
Note: All 4 cylinder models supplied with one cylinder head prepared for capacity control (standard feature)
AIREFRIG AUSTRALIA PTY LTD ALL PRICES ARE EXCLUSIVE OF GST
RECOMMENDED LIST PRICES SUBJECT TO CHANGE WITHOUT NOTICE
A.B.N. 95 008 761 573 EFFECTIVE MARCH 2014 252
BITZER ECOLINE COMPRESSORS
R134A (Motor Options 1 & 2) Semi Hermetic Compressors contd
Capacities R134A
Refrigeration Capacity Watts Consumption Power (Kw)
Comp
Airefrig & Condensing Temperature C
Part Number Motor Evaporating Temperature C
Version
+15 +10 +5 0 -5 -10 -15 -20
4FES-5Y W 11910 9730 7850 6250 4890 3740 2790 2000
- Service Valves Comp 60.0
- Crankcase Heater Series P 3.83 3.55 3.25 2.93 2.60 2.26 1.92 1.60
- Protection Module CE3
- Oil Sight Glass
W 9620 7820 6270 4950 3820 2860 2070 1410
- POE Oil
70.0
Motor P 4.15 3.79 3.41 3.01 2.62 2.22 1.83 1.47
- DOL Start
- Mount Kit Type W 7340 5930 4720 3660 2760 2000 1360
- Integrated varicool opt. 1 80.0
- Terminal Box IP65 P 4.35 3.91 3.45 2.99 2.53 2.08 1.65
4EES-4Y W 17030 14000 11410 9190 7320 5730 4410
- Service Valves Comp 40.0
- Crankcase Heater Series P 3.52 3.36 3.16 2.93 2.67 2.40 2.12
- Protection Module CE3
- Oil Sight Glass
W 14760 12110 9830 7890 6240 4850 3690
- POE Oil
50.0
Motor P 4.18 3.90 3.59 3.26 2.91 2.56 2.22
- DOL Start
- Mount Kit Type W 12500 10230 8280 6610 5190 3980 2980
- Integrated varicool opt. 2 60.0
- Terminal Box IP65 P 4.75 4.35 3.93 3.51 3.08 2.67 2.27
4EES-6Y W 15130 12500 10230 8280 6610 5190 3980 2980
- Service Valves Comp 60.0
- Crankcase Heater Series P 5.02 4.67 4.30 3.90 3.50 3.09 2.69 2.31
- Protection Module CE3
- Oil Sight Glass
W 12450 10270 8380 6750 5340 4150 3130 2280
- POE Oil
70.0
Motor P 5.57 5.11 4.63 4.15 3.66 3.19 2.73 2.30
- DOL Start
- Mount Kit Type W 9760 8040 6540 5230 4100 3130 2300
- Integrated varicool opt. 1 80.0
- Terminal Box IP65 P 6.02 5.45 4.88 4.31 3.75 3.21 2.70
4DES-5Y W 20500 16690 13470 10750 8460 6550 4980
- Service Valves Comp 40.0
- Crankcase Heater Series P 4.16 3.96 3.71 3.42 3.11 2.77 2.43
- Protection Module CE3
- Oil Sight Glass
W 17650 14360 11550 9180 7180 5510 4130
- POE Oil
50.0
Motor P 4.88 4.54 4.17 3.77 3.35 2.93 2.51
- DOL Start
- Mount Kit Type W 14830 12030 9630 7600 5890 4450 3270
- Integrated varicool opt. 2 60.0
- Terminal Box IP65 P 5.47 5.00 4.50 4.00 3.49 2.99 2.51
4DES-7Y W 18090 14830 12030 9640 7610 5890 4460 3280
- Service Valves Comp 60.0
- Crankcase Heater Series P 5.79 5.38 4.94 4.47 3.98 3.49 3.01 2.54
- Protection Module CE3
- Oil Sight Glass
W 14720 12040 9730 7740 6050 4610 3410 2420
- POE Oil
70.0
Motor P 6.34 5.80 5.24 4.66 4.08 3.51 2.96 2.43
- DOL Start
- Mount Kit Type W 11350 9250 7420 5850 4490 3340 2370
- Integrated varicool opt. 1 80.0
- Terminal Box IP65 P 6.72 6.07 5.40 4.72 4.05 3.40 2.78
4CES-6Y W 25050 20450 16560 13260 10490 8170 6250
- Service Valves Comp 40.0
- Crankcase Heater Series P 5.05 4.82 4.54 4.20 3.83 3.44 3.04
- Protection Module CE3
- Oil Sight Glass
W 21700 17690 14290 11400 8970 6950 5270
- POE Oil
50.0
Motor P 5.94 5.55 5.12 4.65 4.16 3.67 3.19
- DOL Start
- Mount Kit Type W 18320 14920 12010 9540 7450 5710 4260
- Integrated varicool opt. 2 60.0
- Terminal Box IP65 P 6.69 6.14 5.57 4.98 4.38 3.80 3.24
4CES-9Y W 22300 18320 14920 12010 9540 7450 5710 4260
- Service Valves Comp 60.0
- Crankcase Heater Series P 7.20 6.69 6.14 5.57 4.98 4.38 3.80 3.24
- Protection Module CE3
- Oil Sight Glass
W 18240 14980 12160 9750 7680 5930 4470 3250
70.0
- POE Oil
Motor P 7.95 7.29 6.59 5.88 5.18 4.49 3.82 3.19
- DOL Start
- Mount Kit Type W 14170 11620 9390 7470 5820 4410 3220
- Integrated varicool opt. 1 80.0
- Terminal Box IP65 P 8.53 7.71 6.88 6.05 5.24 4.45 3.71
Rating Conditions: 50Hz , 20 Deg Return Gas, no Sub-Cooling. Shaded areas require additional cooling &/or return vapour limitations.
Note: All 4 cylinder models supplied with one cylinder head prepared for capacity control (standard feature)
Rating Conditions: 50Hz , 20 Deg Return Gas, no Sub-Cooling. Shaded areas require additional cooling &/or return vapour limitations.
Note: All 4 cylinder models supplied with one cylinder head prepared for capacity control (standard feature)
Rating Conditions: 50Hz , 20 Deg Return Gas, no Sub-Cooling. Shaded areas require additional cooling &/or return vapour limitations.
Note: All 4 & 6 cylinder models supplied with one cylinder head prepared for capacity control (standard feature)
Rating Conditions: 50Hz , 20 Deg Return Gas, no Sub-Cooling. Shaded areas require additional cooling &/or return vapour limitations.
Note: All 6 cylinder models supplied with one cylinder head prepared for capacity control (8 cylinder models 2x heads prepared)
Capacities R134A
Refrigeration Capacity Watts Refrigeration Capacity Watts
Consumption Power (Kw) Consumption Power (Kw)
Airefrig Condensing Temperature C Airefrig Condensing Temperature C
Part Number Part Number
Evaporating Temperature C Evaporating Temperature C
0 -5 -10 -15 -20 0 -5 -10 -15 -20
W 20400 16310 12850 9950 7550 4GE-20Y W 50500 41050 32900 26000 20200
4VES-6Y 30.0 30.0
- Service Valves
- Service Valves P 4.03 3.83 3.52 3.15 2.73 - Crankcase Heater P 10.31 9.70 8.97 8.15 7.27
- Crankcase Heater
- Protection Module
- Protection Module W 17720 14090 11020 8440 6290 - Oil Sight Glass
W 44850 36350 29100 22900 17720
- Oil Sight Glass 40.0 - POE Oil
40.0
- POE Oil P 4.68 4.29 3.85 3.38 2.90 P 12.14 11.19 10.15 9.05 7.92
- Mount Kit
- Mount Kit
- Part Wind Start W 15000 11850 9160 6880 4960 - Oil Press Switch W 38700 31200 24800 19400 14870
- Terminal Box IP65 50.0 - Part Wind Start 50.0
P 5.17 4.64 4.08 3.53 3.01 - Terminal Box IP65 P 13.69 12.42 11.09 9.73 8.38
W 24500 19660 15550 12100 9230 4FE-25Y W 60000 48550 38900 30800 24000
4TES-8Y 30.0 30.0
- Service Valves
- Service Valves P 4.83 4.59 4.24 3.82 3.34 - Crankcase Heater P 12.71 11.93 11.01 9.99 8.92
- Crankcase Heater
- Protection Module
- Protection Module W 21400 17080 13420 10340 7760 - Oil Sight Glass
W 53300 43100 34450 27200 21100
- Oil Sight Glass 40.0 - POE Oil
40.0
- POE Oil P 5.64 5.19 4.68 4.13 3.56 P 14.91 13.67 12.34 10.96 9.59
- Mount Kit
- Mount Kit
- Part Wind Start W 18210 14450 11240 8510 6210 - Oil Press Switch W 46500 37550 29900 23500 18130
- Terminal Box IP65 50.0 - Part Wind Start 50.0
P 6.27 5.65 5.00 4.35 3.72 - Terminal Box IP65 P 16.79 15.13 13.43 11.72 10.08
W 28300 22600 17750 13710 10360 6JE-22Y W 55500 44700 35600 27900 21500
4PES-10Y 30.0 30.0
- Service Valves
- Service Valves P 5.49 5.20 4.79 4.31 3.77 - Crankcase Heater P 10.87 10.39 9.70 8.86 7.90
- Crankcase Heater
- Protection Module
- Protection Module W 24500 19450 15170 11570 8570 - Oil Sight Glass
W 48820 39200 31000 24050 18280
- Oil Sight Glass 40.0 - POE Oil
40.0
- POE Oil P 6.34 5.82 5.23 4.59 3.94 P 12.88 11.93 10.84 9.63 8.37
- Mount Kit
- Mount Kit
- Part Wind Start W 20700 16280 12530 9360 6700 - Oil Press Switch W 42100 33500 26250 20150 15050
- Terminal Box IP65 50.0 - Part Wind Start 50.0
P 6.98 6.26 5.50 4.73 3.96 - Terminal Box IP65 P 14.51 13.13 11.65 10.11 8.58
W 33250 26600 21000 16330 12430 W 64500 52000 41500 32650 25250
4NES-12Y 30.0 6HE-25Y 30.0
- Service Valves P 6.48 6.14 5.68 5.14 4.55 - Service Valves P 12.91 12.25 11.40 10.39 9.28
- Crankcase Heater - Crankcase Heater
- Protection Module W 28950 23100 18100 13910 10420 - Protection Module W 56800 45700 36300 28350 21700
- Oil Sight Glass 40.0 - Oil Sight Glass 40.0
- POE Oil P 7.52 6.93 6.26 5.53 4.78 - POE Oil P 15.30 14.13 12.81 11.40 9.93
- Mount Kit - Mount Kit
- Part Wind Start W 24600 19470 15110 11410 8290 - Oil Press Switch W 49050 39300 31000 24000 18130
- Terminal Box IP65 50.0 - Terminal Box IP65 50.0
P 8.35 7.53 6.64 5.74 4.85 P 17.27 15.61 13.87 12.08 10.29
4JE-13Y W 37300 30200 24100 18920 14560 6GE-30Y W 74900 60700 48700 38600 30150
- Service Valves 30.0 - Service Valves 30.0
- Crankcase Heater P 7.36 7.01 6.54 5.98 5.36 - Crankcase Heater P 15.21 14.37 13.37 12.23 11.01
- Protection Module - Protection Module
- Oil Sight Glass
W 32800 26400 21000 16370 12470 - Oil Sight Glass
W 66300 53700 43000 33950 26400
- POE Oil
40.0 - POE Oil
40.0
P 8.66 8.06 7.36 6.60 5.81 P 18.07 16.70 15.20 13.62 11.99
- Mount Kit - Mount Kit
- Oil Press Switch W 28350 22750 17950 13880 10430 - Oil Press Switch W 57600 46600 37200 29250 22600
- Part Wind Start 50.0 - Part Wind Start 50.0
- Terminal Box IP65 P 9.82 8.97 8.05 7.09 6.13 - Terminal Box IP65 P 20.47 18.61 16.67 14.69 12.71
4HE-15Y W 43800 35450 28350 22300 17220 6FE-40Y W 88800 71800 57500 45450 35400
- Service Valves 30.0 - Service Valves 30.0
- Crankcase Heater P 8.68 8.21 7.63 6.95 6.23 - Crankcase Heater P 18.27 17.27 16.08 14.73 13.27
- Protection Module - Protection Module
- Oil Sight Glass
W 38550 31100 24750 19390 14870 - Oil Sight Glass
W 78400 63300 50600 39800 30800
- POE Oil
40.0 - POE Oil
40.0
P 10.22 9.46 8.61 7.71 6.78 P 21.50 19.88 18.12 16.25 14.32
- Mount Kit - Mount Kit
- Oil Press Switch W 33300 26800 21250 16530 12570 - Oil Press Switch W 67900 54700 43500 34050 26100
- Part Wind Start 50.0 - Part Wind Start 50.0
- Terminal Box IP65 P 11.56 10.52 9.42 8.29 7.18 - Terminal Box IP65 P 24.13 21.97 19.69 17.36 15.02
Rating Conditions: 50Hz , 20 Deg Return Gas, no Sub-Cooling.
Note: All 4 cylinder models supplied with one cylinder head prepared for capacity control (standard feature)
Rating Conditions: 50Hz , 20 Deg Return Gas, no Sub-Cooling. Shaded areas require additional cooling &/or return vapour limitations.
Note: All 4 cylinder models supplied with one cylinder head prepared for capacity control (standard feature)
Rating Conditions: 50Hz , 20 Deg Return Gas, no Sub-Cooling. Shaded areas require additional cooling &/or return vapour limitations.
Note: All 4 cylinder models supplied with one cylinder head prepared for capacity control (standard feature)
Rating Conditions: 50Hz , 20 Deg Return Gas, no Sub-Cooling. Shaded areas require additional cooling &/or return vapour limitations.
Note: All 4 cylinder models supplied with one cylinder head prepared for capacity control (standard feature)
Rating Conditions: 50Hz , 20 Deg Return Gas, no Sub-Cooling. Shaded areas require additional cooling &/or return vapour limitations.
Note: All 4 cylinder models supplied with one cylinder head prepared for capacity control (standard feature)
Rating Conditions: 50Hz , 20 Deg Return Gas, no Sub-Cooling. Shaded areas require additional cooling &/or return vapour limitations.
Note: All 4 cylinder models supplied with one cylinder head prepared for capacity control (standard feature)
Rating Conditions: 50Hz , 20 Deg Return Gas, no Sub-Cooling. Shaded areas require additional cooling &/or return vapour limitations.
Note: All 4 & 6 cylinder models supplied with one cylinder head prepared for capacity control (standard feature)
W 174500 146400 122000 100800 82500 66700 53200 41650 31900 23700
6FE-50Y 30
- Service Valves Comp P 33.41 32.59 31.3 29.63 27.63 25.38 22.93 20.37 17.74 15.14
- Crankcase Heater Series
- Protection Module BE6 W 148500 124600 103800 85700 69900 56300 44600 34600 26100 18880
- Oil Sight Glass
- POE Oil
40
- Mount Kit
Motor P 39.56 37.8 35.65 33.16 30.41 27.46 24.38 21.23 18.08 15
- Oil Press Switch Type
- Part Wind Start 1 W 121700 102200 85100 70100 57100 45700 35850 27400 20150 13970
- Terminal Box IP65 50
P 44.8 42.15 39.16 35.9 32.43 28.82 25.13 21.42 17.77 14.24
Power Supply:
- Motor connections: (DOL) Direct on line
- Voltage: 380-420Y/3/50 (compressor data based on 400volt)
Accessories
Airefrig List Price
Description
Part Number Excl GST
34701901 Motor protection device SE-B1 (replacement for INT69VS7-11 part # 34701301) $486.32
34702303 Discharge Gas temperature control device (sensor) $514.99
34302101 Additional cooling fan to suit 2 cylinder (CE1 series compressors) $1,293.28
34302112 Additional cooling fan to suit 2 cylinder (CE2 series compressors) $1,064.22
34302119 Additional cooling fan to suit 4 cylinder (CE3 series compressors) $1,064.22
34760001 Solenoid Valve assembly for capacity control (includes valve, coil & gasket) $537.15
34330902 Solenoid coil (ONLY) suit capacity control solenoid valve (240v 50Hz) P.O.A.
Power Supply:
- Motor connections: (PWS) Part Winding Start winding partition 50% / 50%
(select motor contactors @ approx 60% of the maximum operating current)
- Voltage: 380-420YY/3/50 (compressor data based on 400volt)
Accessories
Airefrig List Price
Description
Part Number Excl GST
34733403 OLC-K1 Electronic oil monitoring control (suit CE4 series) $484.76
34701901 Motor protection device SE-B1 (replacement for INT69VS7-11 part # 34701301) $486.32
34302113 Additional cooling fan to suit CE4 series (4VES 4NES compressors) $886.84
34760001 Solenoid Valve assembly for capacity control 4VES-4NES (includes valve, coil & gasket) $537.15
34330902 Solenoid coil (ONLY) suit capacity control solenoid valve (240v 50Hz) P.O.A.
Comp A B C D D1 E F G H J K L
Compressor Model
Series mm mm mm mm mm mm mm mm mm mm mm mm
2KES05Y 343 220 273 208 65 162 148 37 242 247 32 232
2JES07Y 343 220 273 208 65 162 148 37 242 247 32 232
2HES1Y 343 220 273 208 65 162 148 37 242 247 32 232
2HES2Y CE1 343 220 273 208 65 162 148 37 242 247 32 232
2GES2Y 343 220 273 208 65 162 148 37 242 247 32 232
2FES2Y 343 220 273 208 65 162 148 37 242 247 32 232
2FES3Y 343 220 273 208 65 162 148 37 242 247 32 232
Note: legend for connections on last page of Bitzer compressor information.
Comp A B C D D1 E F G H J K L
Compressor Model
Series mm mm mm mm mm mm mm mm mm mm mm mm
2EES2Y 398 259 307 223 85 198 167 42 266 275 37 262
2EES3Y 398 259 307 223 85 198 167 42 266 275 37 262
2DES2Y 398 259 307 223 85 198 167 42 266 275 37 262
CE2
2DES3Y 398 259 307 223 85 198 167 42 266 275 37 262
2CES3Y 398 259 307 223 85 198 167 42 266 275 37 262
2CES4Y 398 259 307 223 85 198 167 42 266 275 37 262
Note: legend for connections on last page of Bitzer compressor information.
AIREFRIG AUSTRALIA PTY LTD ALL PRICES ARE EXCLUSIVE OF GST
RECOMMENDED LIST PRICES SUBJECT TO CHANGE WITHOUT NOTICE
A.B.N. 95 008 761 573 EFFECTIVE MARCH 2014 269
BITZER COMPRESSORS
Dimensional Details
Comp A B C D D1 E F G H J K L
Compressor Model
Series mm mm mm mm mm mm mm mm mm mm mm mm
4FES3Y 432 309 347 293 75 198 221 42 313 361 37 306
4FES5Y 432 309 347 293 75 198 221 42 313 361 37 306
4EES4Y 432 309 352 293 75 198 221 56 316 361 37 306
4EES6Y 432 309 352 293 75 198 221 56 316 361 37 306
CE3
4DES5Y 432 309 352 293 75 198 221 56 316 361 42 310
4DES7Y 457 309 352 293 101 198 246 56 316 386 42 310
4CES6Y 457 309 352 293 101 198 246 56 316 386 42 310
4CES9Y 457 309 352 293 101 198 246 56 316 386 42 310
Comp A B C D D1 E F G H J K L
Compressor Model
Series mm mm mm mm mm mm mm mm mm mm mm mm
4VES6Y 633 303 385 367 140 256 44 61 161 558 42 338
4VES7Y 633 303 385 367 140 256 44 61 161 558 42 338
4VES10Y 633 303 385 367 140 256 44 61 161 558 42 338
4TES8Y 633 303 385 367 140 256 44 64 161 557 56 342
4TES9Y 633 303 385 367 140 256 44 64 161 557 56 342
4TES12Y 633 303 385 367 140 256 44 64 161 557 56 342
CE4
4PES10Y 633 303 385 367 140 256 44 64 161 557 56 342
4PES12Y 633 303 385 367 140 256 44 64 161 557 56 342
4PES15Y 658 303 385 367 162 256 48 110 173 582 56 342
4NES12Y 633 303 385 367 140 256 44 64 161 557 56 342
4NES14Y 633 303 385 367 140 256 44 64 161 557 56 342
4NES20Y 658 303 385 367 162 256 48 110 173 582 56 342
Note: legend for connections on last page of Bitzer compressor information.
Comp A B C D D1 E F G H J K L
Compressor Model
Series mm mm mm mm mm mm mm mm mm mm mm mm
4JE13Y 688 456 452 381 151 305 66 110 361 501 56 362
4JE15Y 688 456 452 381 151 305 66 110 361 501 56 362
4JE22Y 688 456 452 381 151 305 66 110 361 501 56 362
4HE15Y 688 456 452 381 151 305 66 110 361 501 56 362
4HE18Y 688 456 452 381 151 305 66 110 361 501 56 362
4HE25Y 737 456 452 381 200 305 87 127 377 549 56 362
BE5
4GE20Y 706 456 452 381 169 305 76 127 377 519 56 362
4GE23Y 706 456 452 381 169 305 76 127 377 519 56 362
4GE30Y 737 456 452 381 200 305 87 127 377 549 56 362
4FE25Y 737 456 452 381 200 305 87 127 377 549 56 362
4FE28Y 737 456 452 381 200 305 87 127 377 549 56 362
4FE35Y 737 456 452 381 200 305 87 127 377 549 56 362
Note: legend for connections on last page of Bitzer compressor information.
Comp A B C D D1 E F G H J K L
Compressor Model
Series mm mm mm mm mm mm mm mm mm mm mm mm
6JE22Y 766 503 447 381 211 305 76 127 377 740 64 271
6JE25Y 766 503 447 381 211 305 76 127 377 740 64 271
6JE33Y 797 503 447 381 242 305 87 127 377 771 64 271
6HE25Y 766 503 447 381 211 305 76 127 377 740 64 271
6HE28Y BE6 766 503 447 381 211 305 76 127 377 740 64 271
6HE35Y 797 503 447 381 242 305 87 127 377 771 64 271
6GE30Y 766 503 447 381 211 305 76 127 377 740 64 271
6GE34Y 766 503 447 381 211 305 76 127 377 740 64 271
6GE40Y 797 503 447 381 242 305 87 127 377 771 64 271
Note: legend for connections on last page of Bitzer compressor information.
Comp A B C D D1 E F G H J K L
Compressor Model
Series mm mm mm mm mm mm mm mm mm mm mm mm
6FE40Y 790 503 447 381 242 305 87 127 377 729 111 381
6FE44Y BE6 790 503 447 381 242 305 87 127 377 729 111 381
6FE50Y 790 503 447 381 242 305 87 127 377 729 111 381
Note: legend for connections are listed below.
6 Oil drain
10 Crankcase heater