equivalent generating unit that describes the average 1 Load 09 -0.45 -0.45
behaviour of all the generating units. This equivalent 2 Load 10 -0.45 -0.9
generating unit is called the COI.
3 Load 11 -0.45 -1.35
Firstly, we use the common system base to obtain
individual inertia constants as follows: 4 Load 07 -1.7 -3.05
5 Load 08 -2.7 -5.75
S 6 Load JUEL -3.4 -9.15
H i ,sys H i u n ,i
S (2)
base,sys 7 Load STCE -3.56 -12.71
8 Load FLQE -7.95 -20.66
Where Sbase,sys is the common power system base which is 9 Load STSY -6.25 -26.91
equals a pre-fault sum of all the island loads (PL0). By 10 Load STNO -7.55 -34.46
applying the methodology that is given in [15], the COI 11 Load MAST -10.3 -44.76
electrical frequency fCOI,pu and the inertia constant HCOI,pu
are given as follows: After the first step of load shedding is initiated, the loads
will wait for some time before they will measure the
n
f el ,i , pu u H i ,sys frequency again. Because of the calculations and circuit-
fCOI , pu i1 (3) breaker operation time, we face with the delay. Choosing
n
H i ,sys T is related to a system specific and depends on the
i1 preference between optimal load shedding and a better
n
H COI H i , sys (4) frequency profile. In this paper, we choose T around 10 in
i 1 which procedure can shed an optimal number of loads
without letting the frequency to decrease to a very low
PROPOSED ALGHORITHIM value even in worst case scenarios.
Loads are ranked based on their willingness to pay. A
lookup table is created and loads are shed according to it. MODELLING A REAL POWER SYSTEM
It is created by using the loads history and willingness to Analysing the performance of this is modelled in a real
pay. power system which is presented in Fiq. 1
Frequency is measured every half cycle and dfCOI/dt is
calculated. If dfCOI/dt is negative and lower than dfCOI,L/dt
(corresponding to the lowest load) according to the Table
1 we find N and shed loads. After shedding we measure
the frequency and obtain dfCOI/dt. Methodology will wait
for the frequency to go down below fCOI,L and for dfCOI/dt
to be negative for T half cycles to shed another load which
is located in the look up table.
To obtain a look up table we consider loads as fixed
amounts and find dfCOI/dt corresponding to a load by
simulating an islanded condition in which a real power
distributed among generators in two different manners. At [9] P.M. Anderson and M. Mirheydar, 1992, "An
the moment of islanding, it is distributed according to their adaptive method for setting underfrequency load
synchronizing power coefficient and later on according to shedding relays", IEEE Trans. Power Syst. vol. 7,
their inertia constants. The frequency of the COI is used in 647-655.
this method. The proposed technique does not require
communication between the components and real time
system data; rather, it uses loads histories to shed the loads
automatically with declining frequency. This method [10] S.J. Huang and C.C. Huang, 2000, "An adaptive load
provides accurate information about the system's total shedding method with time based design for isolated
deficit value and requires fewer load elimination power systems", Int. J. Elect. Power Energy Syst,
mentioned in [1]. The proposed underfrequency load vol.22, 51-58.
shedding can stabilize the frequency of the distribution
system with DGs when it is islanded by shedding an [11] D. Prasetijo, W.R. Lachs, and D. Sutanto, 1994, "A
optimal number of loads. In this situation with a minimum new load shedding scheme for limiting
control requirement, this distribution system can be underfrequency", IEEE Trans. Power Syst. vol. 9,
considered as a micro grid. 1371-1378.
[4] B. Delfino, S. Massucco, A. Morini, P. Scalera, and [16] H.You, V. Vittal, and Z.Yang, 2003, "Self-healing in
F. Silvestro, 2001, "Implementation and comparison power systems: An approach using islanding and rate
of different under frequency load sheding schemes", of frequency decline based load shedding", IEEE
Proc. Power Engineering Society Summer Meeting, Trans. Power Syst. vol. 18, 174-181.
vol.1, 307-312.
[17] M.S. Pasand and H. Seyedi, 2007, "New centralized
[5] P.G. Harrison, 1988, "Considerations when planning adaptive under frequency load shedding algorithms",
a load shedding programme", Brown Bovcri Rev, Proc. Conf. Power Engineering, 44-48.
no.10, 593-598.
[6] S.A. Nirenberg and D.A. McInnis, 1992, "Fast acting [18] P. Mahat, Z. Chen, and B. Bak-Jensen, 2009, "A
load shedding", IEEE Trans Power Syst. vol. 7, 873- hybrid islanding detection technique using average
877. rate of voltage change and real power shift", IEEE
Trans. Power Del. vol. 24, 764-771.
[7] M. Parniani and A. Nasri, 2006, "SCADA based
under frequency load shedding integrated with rate
of frequency decline", IEEE Power Eng. Soc.
General Meeting, 1-6.