1 1.

REFFERENCE DATA
2 Requisition No. N/A Equipment Quantity
3 1 Cable Wire Refer to
4 Specification No. 2
5 3
6 Code & Standard IEC 60502-2 Single Line Diagram:
11 2. ENVIRONMENT
12 Ambient Temp: Max 37.8 C Unusual Condition:
13 Min 17.2 C Salt-Laden Atmospheric
14 Relative Humidity: 56-93 % Humid Tropical Corrosive
15 Dust
16 Seismic Zone: 2 Area Classification:
17 General
18 Altitude: Less than 100 m Indoor
19 Outdoor
20 Class Div Group
21 Class Zone Group
22 Non Hazard
23 3. ELECTRICAL DATA
24 Voltage: 20 kV
25 Frequency: 50 Hz
26 No. of Phases: 3 Phase 3 Wire
27 4. CABLE TYPE
28 Type: NA2XSEFGbY
29 Conductor Material: Aluminium
30 Insulation: XLPE
31 Outer Sheat: PVC
32 Screen Material: Copper Tape Screen
33 Armoured Construction: Steel Flat Wire Armor
34 Phase Colour: R (Black)
35 S (Red)
36 T (Blue)
37 5. SPECIFIC REQUIREMENT
38 Specification : IEC 60502-2
39 Cable Type : NA2XSEFGbY
40 Conductor Material : Aluminium (Al)
41 Cable Size : 35 50 70 95 120 150 240 300 mm2
42 Number of Core per Cable : 3 3 3 3 3 3 3 3 CORES
43 Rated System Voltage : 12/20 Kv
44 Frequency: : 50 Hz
45 Conductor Max. AC Resistance at 90 C : 1.113 0.822 0.568 0.411 0.323 0.265 0.162 0.13 OHM/Km
46 Overall Diameter Approx : 56.5 59 63 67 70 73.5 83 88 mm
47 Cable Net Weight Approx : 3882 4212 4832 5434 6013 6622 8431 9509 Kg/Km
48 Standard Length per Reel : VTA VTA VTA VTA m
49 Minimum Bending Radius : VTA VTA VTA VTA mm
50 Capacitance : VTA VTA VTA VTA uF/km
51 Inductance : VTA VTA VTA VTA mH/km
52 Current Carrying Capacity at 30 C :
53 - In Air : 147 175 218 263 302 339 453 515 A
54 - In Ground : 135 159 194 232 263 293 383 430 A
55 Short Circuit Current at 1 Sec. : VTA VTA VTA VTA VTA VTA VTA VTA kA
56 6. CONSTRUCTION
57
58
59
60
61
62
63
64
65
66
67
68
69
70
71
72
1 1. REFFERENCE DATA
2 Requisition No. N/A Equipment Quantity
3 1 Cable Wire Refer to
4 Specification No. 2
5 3
6 Code & Standard IEC 60502-2 Single Line Diagram:
11 2. ENVIRONMENT
12 Ambient Temp: Max 37.8 C Unusual Condition:
13 Min 17.2 C Salt-Laden Atmospheric
14 Relative Humidity: 56-93 % Humid Tropical Corrosive
15 Dust
16 Seismic Zone: 2 Area Classification:
17 General
18 Altitude: Less than 100 m Indoor
19 Outdoor
20 Class Div Group
21 Class Zone Group
22 Non Hazard
23 3. ELECTRICAL DATA
24 Voltage: 20 kV
25 Frequency: 50 Hz
26 No. of Phases: 1 Phase 1 Wire
27 4. CABLE TYPE
28 Type: N2XSY
29 Conductor Material: Copper
30 Insulation: XLPE
31 Outer Sheat: PVC
32 Screen Material: Copper Tape Screen
33 Armoured Construction: Steel Flat Wire Armor
34 Phase Colour: N/A
35
36
37 5. SPECIFIC REQUIREMENT
38 Specification : IEC 60502-2
39 Cable Type : N2XSY
40 Conductor Material : Aluminium (Al)
41 Cable Size : 35 50 70 95 120 150 240 300 mm2
42 Number of Core per Cable : 1 1 1 1 1 1 1 1 CORES
43 Rated System Voltage : 12/20 Kv
44 Frequency: : 50 Hz
45 Conductor Max. AC Resistance at 90 C : 0.668 0.494 0.342 0.247 0.196 0.159 0.098 0.079 OHM/Km
46 Overall Diameter Approx : 24.5 25.5 27.5 29 30.5 32 36.5 38.5 mm
47 Cable Net Weight Approx : 884 984 1236 1518 1786 2078 3004 3595 Kg/Km
48 Standard Length per Reel : VTA VTA VTA VTA m
49 Minimum Bending Radius : VTA VTA VTA VTA mm
50 Capacitance : VTA VTA VTA VTA uF/km
51 Inductance : VTA VTA VTA VTA mH/km
52 Current Carrying Capacity at 30 C :
53 - In Air : 200 238 297 361 416 474 641 735 A
54 - In Ground : 182 214 262 314 357 401 524 590 A
55 Short Circuit Current at 1 Sec. : VTA VTA VTA VTA VTA VTA VTA VTA kA
56 6. CONSTRUCTION
57
58
59
60
61
62
63
64
65
66
67
68
69
70
71
72
1 1. REFFERENCE DATA
2 Requisition No. N/A Equipment Quantity
3 1 LV Cables Refer to
4 Specification No. 2
5 3
6 Code & Standard IEC 60502-2 Single Line Diagram:
11 2. ENVIRONMENT
12 Ambient Temp: Max 37.8 C Unusual Condition:
13 Min 17.2 C Salt-Laden Atmospheric
14 Relative Humidity: 56-93 % Humid Tropical Corrosive
15 Dust
16 Seismic Zone: 2 Area Classification:
17 General
18 Altitude: Less than 100 m Indoor
19 Outdoor
20 Class Div Group
21 Class Zone Group
22 Non Hazard
23 3. ELECTRICAL DATA
24 Voltage: 0.6/1 kV
25 Frequency: 50 Hz
26 No. of Phases: 3 Phase 4 Wire
27 4. CABLE TYPE
28 Type: NYFGbY
29 Conductor Material: Copper
30 Insulation: PVC
31 Armor: Steel Flat Wire Armor
32 Sheath: PVC
33 Phase Colour: R (Black)
34 S (Red)
35 T (Blue)
36 N (Yellow Strip Green)
37 5. SPECIFIC REQUIREMENT
38 Specification : IEC 60502-1
39 Cable Type : NYFGbY
40 Conductor Material : Copper (Cu)
41 Cable Size : 4 6 10 16 25 35 50 300 mm2
42 Number of Core per Cable : 4 4 4 4 4 4 4 4 CORES
43 Rated System Voltage : 0.6 / 1 KV
44 Frequency: : 50 Hz
45 Conductor Max. AC Resistance at 90 C : 5.516 3.685 2.19 1.376 0.87 0.627 0.464 0.075 OHM/Km
46 Overall Diameter Approx : 19 20.5 23 25.5 29 32 37.5 74.5 mm
47 Cable Net Weight Approx : 775 912 1174 520 2053 2584 3173 14773 Kg/Km
48 Standard Length per Reel : VTA VTA VTA VTA m
49 Minimum Bending Radius : VTA VTA VTA VTA mm
50 Capacitance : VTA VTA VTA VTA uF/km
51 Inductance : VTA VTA VTA VTA mH/km
52 Current Carrying Capacity at 30 C :
53 - In Air : 41 52 71 94 126 154 177 559 A
54 - In Ground : 48 59 79 101 131 157 176 481 A
55 Short Circuit Current at 1 Sec. : VTA VTA VTA VTA VTA VTA VTA VTA kA
56 6. CONSTRUCTION
57
58
59
60
61
62
63
64
65
66
67
68
69
70
71
72
1 1. REFFERENCE DATA
2 Requisition No. N/A Equipment Quantity
3 1 LV Cables Refer to
4 Specification No. 2
5 3
6 Code & Standard IEC 60502-2 Single Line Diagram:
11 2. ENVIRONMENT
12 Ambient Temp: Max 37.8 C Unusual Condition:
13 Min 17.2 C Salt-Laden Atmospheric
14 Relative Humidity: 56-93 % Humid Tropical Corrosive
15 Dust
16 Seismic Zone: 2 Area Classification:
17 General
18 Altitude: Less than 100 m Indoor
19 Outdoor
20 Class Div Group
21 Class Zone Group
22 Non Hazard
23 3. ELECTRICAL DATA
24 Voltage: 0.8/1 kV
25 Frequency: 50 Hz
26 No. of Phases: 1 Phase 1 Wire
27 4. CABLE TYPE
28 Type: NYY
29 Conductor Material: Copper
30 Insulation: PVC
31 Sheath: PVC
32 Phase Colour: N/A
33
34
35
36
37 5. SPECIFIC REQUIREMENT
38 Specification : IEC 60502-1
39 Cable Type : NYY
40 Conductor Material : Copper (Cu)
41 Cable Size : 50 70 95 120 150 185 240 300 mm2
42 Number of Core per Cable : 1 1 1 1 1 1 1 1 CORES
43 Rated System Voltage : 0.6 / 1 KV
44 Frequency: : 50 Hz
45 Conductor Max. AC Resistance at 90 C : 0.464 0.321 0.232 0.184 0.15 0.121 0.093 0.075 OHM/Km
46 Overall Diameter Approx : 15 16.7 19.1 21 23 25.5 29 32 mm
47 Cable Net Weight Approx : 600 807 1079 1316 1604 2020 2636 3219 Kg/Km
48 Standard Length per Reel : VTA VTA VTA VTA m
49 Minimum Bending Radius : VTA VTA VTA VTA mm
50 Capacitance : VTA VTA VTA VTA uF/km
51 Inductance : VTA VTA VTA VTA mH/km
52 Current Carrying Capacity at 30 C :
53 - In Air : 172 218 270 315 362 420 503 580 A
54 - In Ground : 180 221 264 300 336 379 439 494 A
55 Short Circuit Current at 1 Sec. : VTA VTA VTA VTA VTA VTA VTA VTA kA