You are on page 1of 3

3UG4615-2CR20 Page 1

Product data sheet 3UG4615-2CR20

DIGITAL MONITORING RELAY FOR THREE-PHASE


LINE VOLTAGE REVERSIBLE PHASE SEQUENCE
PHASE FAILURE 3X 160 TO 690V AC 50 TO 60 HZ
UNDERVOLT. AND OVERVOLT. 160-690V
HYSTERESIS 1-20V 0-20S EACH FOR UMIN AND
UMAX 1 W FOR UMIN 1W FOR UMAX SPRING-
LOADED TYPE

General technical details:


Measurable voltage / for AC
initial value 160 V
final value 690 V
Type of voltage / for operating AC
Control supply voltage
at 50 Hz / for AC / rated value
minimum 160 V
maximum 690 V
at 60 Hz / for AC / rated value
minimum 160 V
maximum 690 V
Impulse voltage resistance / rated value 6 kV
Adjustable backslide delay time
initial value 0.1 s
final value 20 s
Number of NC contacts / for auxiliary contact 0
Number of NO contacts / for auxiliary contact 0
Number of change-over switches / for auxiliary contact 2

Date: subject to modifications


01/13/2008 Copyright Siemens AG 2008
3UG4615-2CR20 Page 2

Relative metering precision 5%


Precision of digital display +/-1 digit
Product function
Asymmetry recognition Yes
Phase disturbance recognition Yes
Phase sequence recognition Yes
Overvoltage recognition Yes
Undervoltage recognition Yes

Mechanical design:
Design of the overload protection no
Design of the electrical connection spring-loaded terminals
Design of the electrical connection / Jumper socket Yes
Width 22.5 mm
Height 94 mm
Depth 91 mm

Date: subject to modifications


01/13/2008 Copyright Siemens AG 2008
3UG4615-2CR20 Page 3

last change: 10/31/2006

Technical Assistance: Telephone: +49 (0) 911-895-5900 (8 - 17 CET)


Fax: +49 (0) 911-895-5907
E-Mail: technical-assistance@siemens.com
Internet: www.siemens.de/lowvoltage/technical-assistance

Date: subject to modifications


01/13/2008 Copyright Siemens AG 2008