BILL OF QUANTITIES

(CP-01) GENERAL CONSTRUCTION & TRADE WORKS


(Electrical Works)

Project: MR VALENZUELA BUILDING 3


Location:
ELECTRICAL Maysan
WORKS Road Corner I, Miranda Street, Valenzuela City
Section No. MAIN WORKS
Bill No. ELECTRICAL WORKS

UNIT COST
TOTAL
No. DESCRIPTION UNIT QTY Labor & Other
Material Total AMOUNT
Cost

Furnish materials, labor, tools , equipment,


supervision
RACE WAYS
RCS/EMT conduit(s) should be NEMA
standard trade sizes,
UL
andapproved or equivalent
all incidentals required to
to complete
PANASONIC,
the works in ARROW,
ALLIED, WHEATLAND, KOREA STEEL
Pipe or approved equal
PVC conduit(s) should be MOLDEX
accordance with the given plans
and specifications
A. RISER AND FEEDER SYSTEM

Concrete Encasement and Concrete


1
Pedestal
a. Excavation m2
b. Formworks m2
c. Rebars kg
d. Concreting m2
e. Backfill and Compaction m2
f. Others (Pls. Specify)

2 Intermediate Metallic Conduit


a. IMC Conduit, 50 mm lm
b. IMC Conduit, 40 mm lm
c. IMC Conduit, 25 mm lm
d. IMC Conduit, 20 mm lm
e. IMC Conduit, 15 mm lm
f. Locknut & Bushing, 50 mm prs
g. Locknut & Bushing, 40 mm prs
h. Locknut & Bushing, 25 mm prs
i. Locknut & Bushing, 20 mm prs
j. Locknut & Bushing, 15 mm prs
k. Elbow, 50 mm pcs
l. Elbow, 40 mm pcs
m. Elbow, 25 mm pcs
n. Elbow, 20 mm pcs
o. Elbow, 15 mm pcs
p. Others (Pls. Specify)
FEEDER AREA
Pipe 32 mm IMC l
63 mm PVC Pipe L
65 mm PVC Pipe L
100 mm PVC Pipe L
Adaptor w/ L&B 100mm prs

3 Liquid Tight Flexible Metal Conduit


a. LFMC Conduit, 65mm lm
b. LFMC Conduit, 50 mm lm
c. Straight Connector, 65 mm pcs
d. Straight Connector, 50 mm pcs
e. Others (Pls. Specify)

4 Polyvinyl Chloride Conduit


a. PVC, 100 mm lght
b. PVC, 40 mm lght
c. PVC, 32 mm lght
d. PVC, 25 mm lght
e. PVC, 20 mm lght
f. End Bell, 100 mm pcs
g. Elbow, 100 mm pcs
h. Elbow, 40 mm pcs
i. Elbow, 32 mm pcs
j. Elbow, 25 mm pcs
k. Elbow, 20 mm pcs
l. Adaptor w/ Lockout, 40 mm prs
m. Adaptor w/ Lockout, 32 mm prs
n. Adaptor w/ Lockout, 25 mm prs
o. Adaptor w/ Lockout, 20 mm prs
p. Others (Pls. Specify)

B Common Areas (Ground Floor to Eight Floor)


1 Polyvinyl Chloride Conduit / Flexible Metallic Conduit
a. PVC, 20mm lght
b. Elbow, 20mm pcs
c. Adaptor w/ Locknut, 20mm prs
d. FMC, 15mm lm
e. Straight Connector, 15mm pcs
f. Others (Pls. Specify)
Ground Floor
1 Polyvinyl Chloride Conduit / Flexible Metallic Conduit
a. PVC, 20mm lght
b. Elbow, 20mm pcs
c. Adaptor w/ Locknut, 20mm prs
d. FMC, 15mm lm
e. Straight Connector, 15mm pcs
f. Others (Pls. Specify)

D Second to Eight Floor


1 Polyvinyl Chloride Conduit / Flexible Metallic Conduit
a. PVC, 20mm lght
b. Elbow, 20mm pcs
c. Adaptor w/ Locknut, 20mm prs
d. FMC, 15mm lm
e. Straight Connector, 15mm pcs
f. Others (Pls. Specify)

E Roof Deck
1 Polyvinyl Chloride Conduit / Flexible Metallic Conduit
a. PVC, 20mm lght
b. Elbow, 20mm pcs
c. Adaptor w/ Locknut, 20mm prs
d. FMC, 15mm lm
e. Straight Connector, 15mm pcs
f. Others (Pls. Specify)
Pipe 15mm IMC l
Pipe 32mm IMC l
Adaptor w/ LB 32 mm pairs

Sub-Total (Raceways)

WIRES AND CABLES

Conductors should be ICEA or PEC


standard and manufactured by PHELPS
DODGE, AMERICAN WIRE & CABLE,
PHILFLEX or approval equal

A Riser and Feeder System


a. THHN, 250mm2 lm
b. THHN, 200mm2 lm
c. THHN, 125mm 2
lm
d. THHN, 80mm2 lm
e. THHN, 60mm2 lm
f. THHN, 50mm2 lm
g. THHN, 30mm2 lm
h. THHN, 22mm2 lm
i. THHN, 14mm2 lm
j. THHN, 8.0mm2 lm
k. THHN, 5.5mm 2
lm
l. THHN, 3.5mm2 lm
Others (Pls. Specify)

Wire 38.0mm2 lm

m. 0.75 sq mm TF (#18AWG) Twisted Pair lm

,
n. 800A, 3f 4 Conductor with Integral Hou lm
Aluminum Busway, Including accessories and connectors
o. Others (Pls Specify)
Bus Duct Flatwise Elbow - 4x800 sets
Bus Duct Edgewise Elbow - 4x800 sets
Bus Duct Plug-In Tap Box - 4x800 AMP sets
Bus Duct Terminal Lugs - 4x800 AMP sets
Br: 2B-90T/AF, 1P
2 - Space
a.2 Digital Kwhr-meter Gutter
with 28- Digital Kwhr-meters with Pulse Concentrator

B Meter Center Panel 3 & 4 assy


b.1 Breaker Gutter
Main: 150AT/AF, 3P, 400/230V, 3 Phase, 2-Wires
+ G with ground & Neutral Bus, Lugs Only
Br : 14-90AT/AF, 1P
4 - Space
b.2 Digital Kwhr-meter Gutter
with 28- Digital Kwhr-meters with Pulse Concentrator

C Meter Center Panel 5 & 6 assy


c.1 Breaker Gutter
Main: 150AT/AF, 3P, 400/230V, 3 Phase, 2-Wires
+ G with ground & Neutral Bus, Lugs Only
Br : 14-90AT/AF, 1P
4 - Space
c.2 Digital Kwhr-meter Gutter
with 28- Digital Kwhr-meters with Pulse Concentrator

D Meter Center Panel 7 & 8 assy


d.1 Breaker Gutter
Main: 150AT/AF, 3P, 400/230V, 3 Phase, 2-Wires
+ G with ground & Neutral Bus, Lugs Only
Br : 14-90AT/AF, 1P
4 - Space
d.2 Digital Kwhr-meter Gutter
with 28- Digital Kwhr-meters with Pulse Concentrator
Others (Pls. Specify)
ECB 125 AT set

Sub-Total (Panelboard(s), ECB'(s), Meter Center(s)

LIGHTNING PROTECTION

Supply, Delivery and Installation of


Lightning Protection and Grounding
System, approved brand only, Including all
necessary hangers and supports.
Complete as described in specification.

1 Wires and Cables


a. Soft-drawn Bare Copper Wire, 100 mm2 lm
b. Others (Pls. Specify)

2 Raceways
a. PVC, 63 mm dia. lght
b. PVC, 32 mm dia. lght
c. End Bell, 63 mm dia. pcs
d. Elbow, 63 mm dia. pcs
e. Elbow, 32 mm dia. pcs
f. Adaptor w/ Locknut, 63mm prs
g. Adaptor w/ Locknut, 32mm prs
h. Others (Pls. Specify)

3 Equipment
a. Lightning Arrester complete with Lightning assy
Counter in watertight fiber glass pullbox,
stand alone mast withbrackets and down conductor
b. Grounding system consists of 3 - ground assy
connection and concrete ground pit with cover
c. Grounding Busbar pcs
d. 25mm dia x 3000mm long Ground Rod C pcs
e. Miscellaneous and Consumables lot

Sub-Total (Lightning Protection and Ground System)

LIGHTNING FIXTURES

A Common Areas (Ground Floor to Eight Floor)

a. Emergency lightning unit with 5w high set


output lamp for a minimum of 1.5 hours emergency operation.
Unit shall be for 230v, 60hz and complete with
maintenance-free pure lead batteries, fully automatic,
solid state charger, test switch and ac-on light.

b. Ceiling outlet lightning fixture as indicated set


100mm x 55mm (4" x 2 -1/8")

c. Surface mounted medium base keyless set


with 50w, 230v incandescent bulb

d. Surface mounted circular fluorescent light set


300mm dia. with 21w, T5 lamp and acrylic cover

e. Wall Mounted exit lightning fixture 1x8w T set


fluorescent lamp for a minimum of 2 hours
emergency operation. Unit shall be complete with
sealed nickel cadmium battery, letter shall be 150mm
white block style with green background. Fixture
shall be one sided.

f. Others (Pls. Specify)


Single Fluorescent Lamp sets
Exit Light

B. Ground Floor

a. Surface mounted medium base keyless set


with 50w, 230v incandescent bulb

b. Others (Pls. Specify)

C. Second to Eight Floor

a. Surface mounted medium base keyless set


with 50w, 230v incandescent bulb

b. Others (Pls. Specify)

D. Roof Deck

a. Surface mounted medium base keyless set


with 50w, 230v incandescent bulb

b. Emergency lightning unit with 5w high set


output lamp for a minimum of 1.5 hours emergency operation.
Unit shall be for 230v, 60hz and complete with
maintenance-free pure lead batteries, fully automatic,
solid state charger, test switch and ac-on light.

c. Wall mounted Light


d. Ceiling outlet lightning fixture as indicated set
100mm x 55mm (4" x 2 -1/8")

e. Others (Pls. Specify)


Surface mounted circular fluorescent light set
300mm dia. with 21w, T5 lamp and acrylic cover
Single FI. set
Sub-Total (Lightning Fixtures)

WIRING DEVICES

Supply, Delivery and Installation of Wiring


Devices approved brand only. Complete
as described in specification.

A. Common Areas (Ground Floor to Eight Floor)

a. Single wall Convenience outlet, 10A, 250\ set


slots, grounding type

b. Duplex wall Convenience outlet, 16A, 250\ set


slots, grounding type mounted above counter if
marked "C"

c. Single pole toggle switch 15A, 300V, 100 set


utility box or as noted

d. Three Way Switch 15A, 300V set

e. Three Gang Toggle Switch 15A, 300V set

f. Others (Pls. Specify)

B. Ground Floor

a. Single Wall Convenience Outlet, 10A, 250 set


Grounding type with Built-in-Earth Leakage Circuit Breaker with
current sensitivity rating of 15mA, ref GFCI

b. Single Wall Convenience Outlet for Wash set


parallel slots Grounding type, ref. WM

c. Single Wall Convenience Outlet for Room set


250V, Tamdem Slots, Grounding type, ref. WAC

d. Single Wall Convenience Outlet for set


Electrical 250V, Parallel Slots, Grounding type, ref. ST

e. Single Wall Convenience Outlet for set


Electrical 250V, Parallel Slots, Grounding type, ref. WH

f. Single Wall Convenience Outlet 16A, 250V set


Grounding type for Refrigerator and Range Hood, ref R & RH

g. Duplex Wall Convenience Outlet 16A, 250V set


Grounding Type mounted, ref C

h. One Gang Toggle Switch 15A, 300V set

i. Others (Pls. Specify)

C Second to Eight Floor

a. Single Wall Convenience Outlet, 10A, 250 set


Grounding type with Built-in-Earth Leakage Circuit Breaker with
current sensitivity rating of 15mA, ref GFCI

b. Single Wall Convenience Outlet for Wash set


parallel slots Grounding type, ref. WM

c. Single Wall Convenience Outlet for Room set


250V, Tamdem Slots, Grounding type, ref. WAC

d. Single Wall Convenience Outlet for set


Electrical 16A, 230V, Parallel Slots, Grounding type, ref. ST

e. Single Wall Convenience Outlet for set


Electrical 250V, Parallel Slots, Grounding type, ref. WH

f. Single Wall Convenience Outlet 16A, 250V set


Grounding type for Refrigerator and Range Hood, ref R & RH

g. Duplex Wall Convenience Outlet 16A, 250V set


Grounding Type mounted, ref C

h. One Gang Toggle Switch 15A, 300V set

i. Others (Pls. Specify)

D Roof Deck

a. Single Wall Convenience Outlet 10A, 250V set


Grounding Type mounted, ref C
b. One Gang Toggle Switch 15A, 300V set

c. Two Gang Toggle Switch 15A, 300V set

d. Three Way Switch, 15A, 300V set

e. Others (Pls. Specify)

Sub-Total (Wiring Devices)

BOXES
A. Common Areas (Ground Floor to Eight Floor)

a. Junction Box set


b. Square Box set
c. Utility Box set
d. Switch Box set
e. Pullboxes set

B. Ground Floor

a. Junction Box set


b. Square Box set
c. Utility Box set

C. Second to Eight Floor

a. Junction Box set


b. Square Box set
c. Utility Box set

D. Roof Deck

a. Junction Box set


b. Utility Box set
c. Pullboxes set
d. Others (Pls. Specify)
Square Box

Others (Pls Specify)


FEEDER AREA
Splice Box x 20cm x 20cm x 15cm set
Splice Box x 25cm x 25cm x 20cm set

Sub - Total (Boxes)


Miscellaneous and Consumables
a. Testing and Commissioning lot
b. Wiring Terminations / cable lugs lot
c. Electrical Tape, G.I. wire terminal lugs, ex lot
bolt, anchor bolt, nut and screw, welding rod, angle
bar, U-bolt, masonry and drill bits, cutting disk,
paint, gasoline, solvent cement etc.
Others (Pls. Specify)
MEGGER TESTING lot

Sub-Total (Miscellaneous and Consumables)

TOTAL (ELECTRICAL WORKS)