C6097A
GAS PRESSURE SWITCHES
INSTRUCTION SHEET
INSTALLATION
1. Read these instructions carefully. Failure to follow 3. The installation has to be carried out by qualified
the instructions could damage the product or personel only.
cause a hazardous condition. 4. Carry out a thorough checkout when installation is
2. Check the ratings given in the instructions and on completed.
the product to make sure the product is suitable 5. Electrical installation must be in accordance with
for your application. local requirements.
c E=j68
D
H
K
61 69 74
G
J --tlF---,-------t--,--,,_
49,5
E
F
1----=---.::-- 69-------1
Flanged mounted models
C 1 - - - - 52 ------1
H
K
52
J --ttf---,-------t--,--,,_
- - - - - 69 - - - - - - - I
A Bracket mounting hole (3), M4 tapping, depth 5 mm G Differential pressure (Rp 1/8")
~}
B Cover screw
E Inlet positive pressure (Rp 1/4") M Mounting screw holes (2 x 4.5 mm) for flanged versions
EN1R-91729907R1-NE 2
Mounting and orientation
In vertical, or horizontal plane with the setting dial facing
upwards. Make sure that dirt or humidity does not get into the
NO } load sld,
connection open for ventilation (G in Figure. 1.).
A WARNING NC
3 voltage side
Turn off gas supply before installation.
CaM
Disconnect power supply to the pressure switch
before beginning the installation to prevent ~ earth connection
electrical shock and damage to the equipment.
Fig. 2. C6058 connection diagram
Do not remove the seal over the pressure inlets,
until ready to connect piping.
A WARNING
A WARNING
The adjustment and checkout has to be carried out
by qualified personnel only.
Switch off power supply before making electrical
connections. Terminals are accessible, no protection against
electrical shock.
Take care that the wiring is in accordance with local
regulations. Pressure set point adjustment
Use lead wire that can withstand 105 QC ambient. (tolerance 15 % over total scale)
The electrical ON/OFF operator is provided with a terminal NOTE: The knob readings are approximations of the actual
block for electrical connections. settings.
1. Remove the cover of the pressure switch.
Wiring
Follow the instructions supplied by the appliance 2. Turn the dial clockwise to increase or
manufacturer. Refer to Figure 2. and 3. Connection diagram counter-clockwise to decrease the pressure set point.
C6097A. 3. Replace the cover.
3 EN1R-91729907R1-NE
Accurate pressure set point adjustment Checkout
(stand alone only)
Checking cut-off pressure
(tolerance < 3% over total scale) After the installation is completed, continue with the following
1. Remove the screw from the test nipple inlet. procedures:
2. Connect the tube of the pressure measurement device
1. Slowly close manual main valve with the burner in
to the nipple (Fig. 1. F).
operation. Shut down should occur when the pressure
3. Remove the cover of the pressure switch. drops below the set point and the alarm (if connected)
4. Slowly release pressure of the main gas supply line until should be energized.
the desired value is reached.
5. Turn dial slowly until contact 1-3 opens and contact 2. Re open the manual main valve. The pressure should
2-3 closes. rise and exceed the set point value, the burner should
6. Replace the cover. start up and the alarm turn off after the reset button is
depressed.
7. Disconnect the pressure measurement device and
replace the screw.
Honeywell
Combustion Controts Center Europe Honeywell UGV S.r.l.
Honeywell BV Via Ferrero, 16
Phileas Foggstraat 7 10090 Cascine- Vica Rivoli (TO)
7821 AJ Turin, Italy
Emmen, The Netherlands Tel: +39 (11) 957 8311
Tel: +31 (0) 591695911 Fax: +39 (11) 957 8322
Fax: +31 (0) 591695200
EN1R-91729907R1-NE 4