Professional Documents
Culture Documents
AbstractConcentric neutral cables are commonly used in and concentric wires serving as the neutral conductor. Three
medium-voltage power distribution systems. Presently, the cable concentric neutral cables form a three-phase, multigrounded
ampacity calculation methods can take into account only the underground distribution feeder. Unfortunately, the published
fundamental frequency current and the harmonic currents in
the phase conductors. In reality, the cable neutral can carry cable derating methods shown in [1][7] cannot be applied to
fundamental frequency and harmonic currents (induced and such cases, as the concentric neutral cable cannot be treated as a
unbalanced), leading to a further increase of cable temperature. single-core cable with a metallic sheath due to its different op-
In view of the increased harmonics and load imbalance in power erating arrangements. In a multigrounded underground feeder,
distribution systems and the need to determine their impact on the loads are connected between the (concentric) neutral and the
concentric neutral cables, this paper presents a method to estimate
the ampacity of concentric neutral cables, especially for multi- phase conductors. This makes the neutral carry (unbalanced or
grounded neutral systems. The proposed cable derating factor zero sequence) load current, in addition to the induced current.
can be used to determine the increase in cable loading caused by On the other hand, the sheath of a cable is not connected to the
unbalanced load and harmonics. A chart is also presented as a sim- load. As a result, the metallic sheath carries only the induced
plied method for cable ampacity and cable loading estimation, current. In addition, the unbalanced loads may induce more
for which only the total harmonic distortion and zero-sequence
current ratio of the phase current are needed. current to the neutral in comparison with the balanced load
case. Therefore, the unbalanced load currents and the induced
Index TermsCable ampacity and concentric neutral cable, har-
currents (at the fundamental and harmonic frequencies) must
monics, power quality (PQ).
be considered together to derive a derating method for the
concentric neutral cables. To the authors' best knowledge,
I. INTRODUCTION little research has been published in the subject area. In view
of the widespread adoption of harmonic-producing loads in
power systems, it has become timely and important to research
0885-8977 2014 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission.
See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
1972 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 31, NO. 5, OCTOBER 2016
where is the permissible temperature rise above the am- A. Proposed Derating Factor for Concentric Neutral Cable
bient temperature; is the cable ampacity (fundamental
current in the phase conductor); is the ac resistance The structure of a single conductor cable with metallic sheath
of the phase conductor at the fundamental frequency; is the is similar to that of the concentric neutral cable except the con-
ratio of loss in the metallic sheath to the loss in the phase con- centric neutral is connected to the load and carries load current.
ductor; are the thermal resistances between the Therefore, in (1), replacing power losses on the sheath with the
phase conductor (sheath) and the surrounding medium; power losses on concentric neutral, (3) must hold true.
is the temperature increase caused by the dielectric loss, solar
radiation, and so on. The rst and second items in (1) are ac- (3)
tually the temperature increases caused by power losses on the
phase conductor and the sheath, respectively. In fact, in this where and are the power losses on the phase con-
equation considers the derating impact of the metallic sheath on ductor and concentric neutral conductor, respectively.
the cable ampacity. Since is the temperature rise caused by the dielectric
Although (1) can include the cable sheath, it cannot be di- loss which is determined by voltage, solar radiation, and so on,
rectly used for concentric neutral cables. A concentric neutral it is reasonable to assume is independent of load. In addi-
cable has loads connected between the phase conductor and the tion, since the phase conductor is located in the center of cable,
concentric neutral whereas the sheath does not have loads con- the thermal resistance between the phase conductor and the sur-
nected to it. In addition, the equation has not included the effect rounding medium is bigger than that between the sheath
of harmonic currents. and the surrounding medium . It is also acceptable to as-
Separately, [1] and [2] proposed a method to consider the ef- sume for conservative estimation, which is pre-
fect of harmonic currents on single-core, nonconcentric neutral ferred when dealing with loading issues.
cables. An index called harmonic derating factor was As a result, the maximum permissible power losses of
established as follows: concentric neutral cable can be obtained by
(2)
(4)
(11)
where
Fig. 1. Typical distribution feeder.
.
In the above equation
approximately equal to the power loss on concentric neu-
tral when the loads are three-phase balanced and harmonic
free. Therefore
(12) (15)
B. Applications of
From (13), we have
Before explaining the methods to determine the additional
power loss, it is useful to discuss the potential applications of
. has three applications: (17)
1) Select cable size. The new derating factor can be used at the Since , and in practice, (18) can be
system design stage to consider the effects of harmonics easily proved mathematically.
and load imbalance on cable-size selection. 3) Estimate the equivalent cable loading level. The equivalent
2) Quantify the increase in cable loading caused by load im- loading level can be calculated by (19) to esti-
balance and harmonics. The inverse of represents mate the actual loading level
the total cable loading normalized to the fundamental fre-
quency current loading. Therefore, the increase of normal- (18)
ized cable loading , called loading increase here-
inafter, can be obtained as follows: where is the cable ampacity provided by the manu-
facturer. is the fundamental loading level. The
(13) equivalent loading level is very helpful for utilities to per-
form estimates of the online load condition since
The impacts of load imbalance and harmonics on the (1) can be measured directly. In order to prevent the cable
loading increase can be estimated separately by (14) and from overheating, the maximum permissible
(16). is 1.0 p.u. and the higher values imply an overloading
The loading increase caused by fundamental load imbal- situation.
ance only can be estimated by (15)
III. DETERMINATION OF THE NEUTRAL CURRENT
(14) Fig. 1 illustrates a typical distribution feeder using multi-
grounded concentric neutral cable. is the equivalent system
where is the equivalent unbalanced fundamental impedance. and in this gure represent the grounding
current in concentric neutral. The power loss on neutral resistances of the substation and neutral, respectively. In most
caused by the fundamental current is con- practices, is much smaller than . Since some of the
tributed by induced current and partially triplex harmonics and unbalanced load current will return
unbalanced current return . is through the ground resistance and the amount of return current
1974 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 31, NO. 5, OCTOBER 2016
Fig. 3. Equivalent circuit of the MGN system for neutral current calculation.
is location dependent, the neutral current at each feeder span is Since all neutrals are bonded at two ends of a span, the fol-
different as well. lowing equation holds true:
The goal of the neutral current estimation is to determine the
highest neutral current among all locations, based on known (25)
three-phase currents (magnitudes and phase angles), the feeder
Solving (19)(25) for yields
impedance parameters, and the cable conguration data.
It is worth noting that [3] and [4] presented methods to es-
timate the cable sheath current. The method assumes that the
sheath is solidly grounded to remote earth (i.e., 0). This
assumption signicantly simplies the problem, but it can be
too conservative, that is, it can overestimate the sheath current. (26)
Such a conservative approach cannot be applied to the case of Equation (26) reveals that the concentric neutral current de-
the concentric neutral cable. This is because the unbalanced cur-
termined not only the inductive coupling, but also the unbal-
rent will ow into the ground instead of into the cable neutral if
anced load current. So far, the remaining problem is how to de-
0, which will result in an underestimate of the current in
termine the total neutral current .
cable neutral.
B. Determination of Total Neutral Current
A. Derivation of Neutral Current of Concentric Neutral Cable
Assume each neutral span has the same length and each neu-
The cable system can be installed either in trefoil or in par- tral grounding resistance is equal. The equivalent circuit
allel, and the cables can be placed either in a touching formation for a multigrounded neutral (MGN) system can be illustrated in
or separately. The trefoil and one-cable-diameter separation in- Fig. 3. In the gure, indicates the unbalanced load cur-
stallation has been considered in the following analysis.
rent, that is, three times that of zero-sequence current, injected
A detailed circuit for a span of cable neutral is shown in Fig. 2.
In the gure, , , and are induced into node .
voltages from the other conductors (both phase and neutral) in For the cascade circuit, one can obtain the total equivalent
the cable system. is the self-impedance of each neutral con- impedance of the three concentric neutral based on
ductor while is the total neutral current, which is the phasor Fig. 2 for the th span
summation of three neutral currents in three neutral conductors
(19)
(27)
The voltage drops , , and on the neutral where is one-third of the summation of the three
span for each neutral conductor can be expressed as phase load currents corresponding to span
(20)
(21)
(22) By establishing the node and loop equations, the equation in
matrix form shown in (22) can be obtained
Since the three cables are identical and trefoil installed, the
mutual impedances between the phase and neutral in the same (28)
cable (denoted as ), the mutual impedances between
the phase and neutral in different cable (denoted as ), where as shown in the equation at the bottom of the next page.
and the mutual impedances between the neutrals of different Let , and we have
cable (denoted as ) are equal, respectively. Therefore,
the induced current on phase can be expressed by (29)
(30)
(31)
It can be seen that is determined only by the param- In summary, the steps in determining the neutral current of
eters of power line and ground resistances, that is, , each phase are as follows.
, , and and the rst load location . Equation 1) Measure the three-phase currents experienced by a cable
(31) suggests that for a given concentric neutral cable system where the cable is already in operation. For the planned
with evenly distributed loads, the total neutral current of span cable installation, the three-phase currents are calculated
can be obtained by multiplying the summation of three-phase using distribution power-ow programs.
currents by , and the unavailable neutral current can 2) Calculate zero-sequence harmonic currents from the
be obtained by (26). aforementioned results.
Sensitivity studies have been performed to investigate the 3) Estimate the neutral current of each cable by using (31).
variation of the with the above factors. The results With the calculated neutral current, the proposed new der-
are presented in the Appendix. The main conclusions are drawn ating factor can be obtained by (11). More indices can
as follows. also be calculated to estimate the impact of harmonics and
The unbalanced current return ratio is among 0.9 unbalanced loads on the ampacity of concentric neutral cable
0.98 for the typical system of which the parameters are shown systems.
in Table I. The range of does not have a signi- More complicated calculations for the neutral current, as-
cant change with the substation and neutral grounding resis- suming the three-phase cables are in parallel installation, using
tances and the separation distance of cables. It will be slightly the aforementioned process but considering the actual mutual
higher in harmonics. The highest value of occurs impedances, are also done. The results show that the different
when the loads are intensively located at the end of the feeder. installations do not impact the neutral current signicantly.
For a conservative estimation, it is reasonable to assume that
and and are in phase. Thus, the IV. EXAMPLE CABLE DERATING RESULTS
neutral current can be obtained through
In order to demonstrate the impact of harmonics and unbal-
anced load on the concentric neutral cable ampacity, case studies
using actual eld data have been conducted. Those case studies
are based on measurements taken from 15 actual feeders, which
(32) supply residential and industrial loads. In the following case
1976 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 31, NO. 5, OCTOBER 2016
TABLE II
NORMALIZED AC RESISTANCES OF PHASE AND NEUTRAL CONDUCTORS
A. Impact of Load Imbalance and THD on the Loading Fig. 5. Averaged spectrum for zero sequence harmonic current of each
case.
Increase
In order to know the impacts of various unbalanced and THD
loads, the relationships between the load imbalance rate and the
corresponding loading increase and between the THDs of loads
and the corresponding loading increase of the 15 cases have
been investigated.
The results for various feeders are sorted by load imbalance
rate and THD and presented in Fig. 6. The left gure
in Fig. 6 presents the impact of load imbalance on the loading
increase, and the right one presents the impact of THD on the
loading increase. The total loading increase sorted by and
THD is also shown in the gure for comparison.
In this measured load imbalance and phase-current Fig. 6. Comparison of loading increase for different THD and .
range, the following conclusions can be drawn.
The load imbalance has a slightly signicant impact on
the loading increase in comparison with the harmonics,
especially in the low THD range.
Higher THD leads to closer contributions caused by har-
monics and load imbalance.
The above conclusions imply that if it's necessary to consider
the impact of harmonics, the load imbalance has to be consid-
ered in estimating the level of loading.
Fig. 10. Ratios for different load distributions. Fig. 11. Ratios for different load distributions with different cable separation
distances.
Jing Yong (M08) received the B.Sc., M.Sc., and Ph.D. degrees in electrical Wilsun Xu (M90SM95F05) received the Ph.D. degree from the University
engineering from Chongqing University, Chongqing, China, in 1985, 1988, and of British Columbia, Vancouver, BC, Canada in 1989.
2007, respectively. He was an Engineer with BC Hydro, Burnaby, BC, Canada, from 1990 to
Currently, she is a Professor at Chongqing University and a Visiting Professor 1996. Currently, he is a Professor and an NSERC/iCORE Industrial Research
at the University of Alberta, Edmonton, AB, Canada. Her research interests are Chair at the University of Alberta, Edmonton, AB, Canada. His research inter-
the analysis of power distribution systems and power quality. ests are power quality and harmonics.