You are on page 1of 1

General information

Burner description

Burner description Packaging Boiler room ventilation


NC4, NC6 and NC9 fuel oil burners are The burner with its cover is supplied in a The required volume of new air is 1.2m3/
forced-draught burners, which operate package weighing about 10 kg which kWh produced by the burner.
with an all or nothing firing rate. contains:
These burners can be adapted to - the assembly accessories kit, Operating specifications
different types of boiler. They are - the document folder containing:
available with an adjustable head - the operating instructions, Ambient temperature:
length. Details of the recommended - the wiring diagram, - during use: - 5 - 40C
burner for any given boiler are available - the guarantee certificate. - during storage: - 20 - 70C
on request. They use domestic fuel oil
with a density of 0.84 at a temperature of Space requirements and dimensions Max. electrical power consumed: 244W
10C and with a heating capacity (Hi) of Ensure there is a gap of at least 0.60 m (230V - 50Hz)
11.86 kWh/kg. each side of the burner to allow for
These burners conform to the IP 21 maintenance operations.
protection level.

NC4 NC6 NC9

A Min 270 270 297

Max 310 310 357

B Min 70 70 70

Max 120 120 138

C 80 80 90

D Min 21 21 15

Max 71 71 83

NC4 R101A NC4 H101A, NC6 H/R101A NC9 H101A


daPa mbar daPa mbar daPa mbar
12 1,2
12 1,2 12 1,2
10 1 10 1
10 1
8 0,8 8 0,8 8 0,8

6 0,6 6 0,6 6 0,6

4 0,4 4 0,4 4 0,4

2 0,2 2 0,2 2 0,2

0 0 0 0 0 0
18 40 20 40 45 95
15 25 35 45 15 25 35 45 55 65 kW 40 50 60 70 80 90 100 kW

Main components
Burner Cell Conical flow Flame Nozzle Preheated
power nozzle Safety unit: TCH1xx
turbulator kg/h kW US gal/h line Pump and fan motor:
single-phase 230V, 50Hz, 2800 min-1
NC 4 R101A 63/16-4 1.5 - 3.4 18 - 40 0.5 to 0.85 FPHB5 85-110W, 4F/400V capacitor
slots Electronic igniter:
NC 4 H101A 63/16-4 1.7 -3.4 20 - 40 0.5 to 0.85 no
EBI 5
slots Blower turbine:
MZ 770S NC4/6: 133x42;
NC 6 R101A 63/16-6 3.4 - 4.6 40 - 55 1 to 1.2 FPHB5 NC9: 133x62
lg. 44 mm slots Air flap control: manual
Fuel oil pump with solenoid valve:
NC 6 H101A 63/16-6 3.4 - 4.6 40 - 55 1 to 1.2 no
slots AS47D
Blast tube:
NC 9 H101A 75/20-6 3.8 - 8 45 - 95 1.25 to 1.75 no NC4/6: 63/80x177
slots NC9: 75/90x192
12/2008 - Art. Nr. 4200 1013 9300A 31