You are on page 1of 4

ELECTRICAL LOAD SUMMARY FOR MSB-V2

ITEM GENERAL
AC WH COOKER LIGHTS POWER OTHERS
1 DB-GF 3.00 3.00 4.00 17.00 9.00 0.00
2 DB-FF 3.00 6.00 0.00 18.10 6.30 0.00
3 LIFT 0.00 0.00 0.00 0.00 15.00
4 ACCU 25.00 0.00 0.00 0.00 0.00
5 BOOSTER PUMP 0.00 0.00 0.00 0.00 2.50
6 TRANSFER PUMP 0.00 0.00 0.00 0.00 2.50
7 ACCU (FUTURE) 25.00 0.00 0.00 0.00 0.00
TOTAL 56.00 9.00 4.00 50.40 20.00
TOTAL CONNECTED LOAD IN KW
MAXIMUM DEMAND LOAD IN KW

TOTAL ELECTRICAL LOAD SUMMARY


ITEM
AC WH COOKER GENERAL OTHERS

EXISTING MSB-V 1 44.00 26.00 8.00 115.00 101.00


(EXISTING KM METER 48315)
NO LOAD MODIFICATION

MODIFIED MSB-V 2
(EXISTING KM METER 49095) 56.00 9.00 4.00 50.40 20.00

TOTAL 100.00 35.00 12.00 165.40 121.00


TOTAL CONNECTED LOAD IN KW
MAXIMUM DEMAND LOAD IN KW
ELECTRICAL LOAD SUMMARY FOR MSB-V1
ITEM GENERAL
TOTAL AC WH COOKER LIGHTS
36.00 DB-GF1 16.00 4.00 4.00 20.00
33.40 DB-GF2 10.00 6.00 0.00 18.00
15.00 DB-FF1 8.00 6.00 4.00 6.00
25.00 DB-FF2 6.00 4.00 0.00 5.00
2.50 BOOSTER PUMP 0.00 0.00 0.00 0.00
2.50 TRANSFER PUMP 0.00 0.00 0.00 0.00
25.00 DB-K 4.00 6.00 0.00 4.00
139.40 DB-EX 0.00 0.00 0.00 12.00
139.40 TOTAL 44.00 26.00 8.00 115.00
112.68 TOTAL CONNECTED LOAD IN K
MAXIMUM DEMAND LOAD IN K

TOTAL

294.00

139.40

433.40
433.40
331.98
MARY FOR MSB-V1
GENERAL
POWER OTHERS TOTAL
14.00 8.00 66.00
10.00 9.00 53.00
8.00 15.00 47.00
8.00 6.00 29.00
6.00 6.00
10.00 10.00
5.00 25.00 44.00
5.00 22.00 39.00
115.00 101.00 294.00
TOTAL CONNECTED LOAD IN KW 294.00
AXIMUM DEMAND LOAD IN KW 219.3
TO PROPOSED VILLA

TO
EXISTING VILLA

You might also like