You are on page 1of 56

Actuator controls

AUMA MATIC
AM 01.1/ AM 02.1
AMExB 01.1/ AMExC 01.1
Profibus DP

ISO 9001
ISO 14001
Certificate Registration No.
12 100 4269
12 104 4269
Operation instructions
Actuator controls AUMA MATIC AM/ AMExB/ AMExC
Profibus DP Operation instructions

Scope of these instructions These instructions are valid for multi-turn actuators of type ranges
SA(R) 07.1 SA(R) 16.1 and SA(R)ExC 07.1 SA(R)ExC 16.1 and for
part-turn actuators of type ranges
SG(R) 05.1 SG(R) 12.1 and SGExC 05.1 SGExC 12.1
with the controls AUMA MATIC AM 01.1/ AM 02.1
or AMExB 01.1 and AMExC 01.1 and Profibus DP interface.

Table of contents Page


1. Safety instructions 4
1.1 Range of application 4
1.2 Commissioning (electrical connection) 4
1.3 Maintenance 4
1.4 Warnings and notes 4
2. Short description 4
3. Transport and storage 5
4. General information about Profibus DP 5
4.1 Basic characteristics 5
4.2 Basic functions of Profibus DP 6
4.3 Transfer mode 6
4.4 Bus access 6
4.5 Communication 6
4.6 Functionality 6
4.7 Protection functions 6
4.8 Device types 6
5. Technical data 7
6. Design AUMA MATIC Profibus DP 10
7. Electrical connection 11
7.1 Power supply (standard) 11
7.2 Bus connection (standard) 12
7.3 Fitting the cover 13
7.4 Remote position transmitter 14
7.5 AUMA MATIC on wall bracket 14
7.6 Test run 14
7.7 Mains and bus connection for Ex-version with plug/ socket connector/ terminal board (KP) 15
7.8 Mains and bus connection for Ex-version with plug-in terminal connection (KES) 17
7.9 Redundant bus connection 18
7.10 Bus cables 19
7.11 Setting the Profibus DP address 20
8. Commissioning with controls 21
8.1 Introduction 21
8.2 Programming 21
8.3 Configuration of the Profibus DP interface of the AUMA MATIC 21
8.4 Communication start-up 22
8.5 Description of AUMA user parameters 22
9. Process representation input 29
9.1 Process representation input (default process representation) 30
10. Process representation output 34
10.1 Description of the output data 34

2
Actuator controls AUMA MATIC AM/ AMExB/ AMExC
Operation instructions Profibus DP

Page
11. Description of actuator functions 36
11.1 Operation commands for OPEN/ CLOSE operation 36
11.2 Positioner 37
11.3 Stepping mode 38
12. Failure function 38
13. Description Profibus DP interface 39
13.1 Assignment of the customer inputs of the Profibus DP interface (option) 40
13.2 Assignment Profibus DP connection 41
13.3 Assignment positioner connections 41
13.4 Checking/ setting the switches on the logic board 42
14. Troubleshooting and corrective actions 43
14.1 Optical signals during operation 43
14.2 Actuator can not be controlled via Profibus DP 45
14.3 Position feedback does not function 48
14.4 Actuator is not switched off by the limit switch in direction CLOSE 48
14.5 Actuator stops immediately after start 48
14.6 Measuring the Profibus signals using an oscilloscope 48
15. Appendix A standard wiring diagram 49
15.1 Legend for standard wiring diagram 50
15.2 Additional information to the wiring diagram legend 50
16. Appendix B Proposed external wiring diagram 51
17. Appendix C GSD file 54
18. Appendix D Literature references 54
19. Appendix E Connecting the cable shield for the AUMA MATIC AMExB/ AMExC 01.1 54
Index 55
Addresses of AUMA offices and representatives 56

3
Actuator controls AUMA MATIC AM/ AMExB/ AMExC
Profibus DP Operation instructions

1. Safety instructions
1.1 Range of application AUMA actuators are designed for the operation of industrial valves, e.g.
globe valves, gate valves, butterfly valves and ball valves.
For other applications, please consult us. The manufacturer is not liable for
any possible damage resulting from use in other than the designated appli-
cations. Such risk lies entirely with the user. Observance of these operation
instructions is considered as part of the controls designated use.

1.2 Commissioning During electrical operation, certain parts inevitably carry lethal voltages.
(electrical connection) Work on the electrical system or equipment must only be carried out by a
skilled electrician himself or by specially instructed personnel under the
control and supervision of such an electrician and in accordance with the
applicable electrical engineering rules.

1.3 Maintenance The maintenance instructions must be strictly observed, otherwise a safe
operation of the multi-turn actuator/ the controls is no longer guaranteed.

1.4 Warnings and notes Non-observance of the warnings and notes may lead to serious injuries or
damage. Qualified personnel must be thoroughly familiar with all warnings
and notes in these operation instructions.
Correct transport, proper storage, mounting, and installation, as well as
careful commissioning are essential to ensure a trouble-free and safe
operation.
The following references draw special attention to safety-relevant proce-
dures in these operation instructions. Each is marked by the appropriate
pictograph.

This pictograph means: Note!


Note marks activities or procedures which have major influence on the
correct operation. Non-observance of these notes may lead to consequen-
tial damage.

This pictograph means: Electrostatically endangered parts!


If this pictograph is attached to a printed circuit board, it contains parts
which may be damaged or destroyed by electrostatic discharges. If the
boards need to be touched during setting, measurement, or for exchange, it
must be assured that immediately before a discharge through contact with
an earthed metallic surface (e.g. the housing) has taken place.

This pictograph means: Warning!


Warning marks activities or procedures which, if not carried out correctly,
can affect the safety of persons or material.

2. Short description AUMA actuators have a modular design. Motor and gearing are mounted in
a common housing.
The actuators are driven by an electric motor and controlled via the elec-
tronic controls AUMA MATIC Profibus DP. The electronic controls are
included in the scope of delivery.

4
Actuator controls AUMA MATIC AM/ AMExB/ AMExC
Operation instructions Profibus DP

3. Transport and storage .. Transport to place of installation in sturdy packing.

..
Do not attach ropes or hooks to the handwheel for the purpose of lifting by
hoist.
Store in well-ventilated, dry room.

..
Protect against floor dampness by storage on a shelf or on a wooden
pallet.
Cover to protect against dust and dirt.
Apply suitable corrosion protection agent to bright surfaces.

4. General information about Profibus DP


For the exchange of information among automation systems and between
automation systems and the connected decentral field devices, serial field-
buses are mainly used today as the communication system. Thousands of
applications have proved impressively that cost savings of up to 40 % in
wiring, commissioning, and maintenance are achieved by using fieldbus
technology. While in the past the fieldbuses used were often manufacturer
specific and incompatible with other bus systems, the systems employed
today are almost exclusively open and standardized. This means that the
user does not depend on individual suppliers and can choose the best
product at the most competitive price.
Profibus DP is the leading open fieldbus system in Europe, which is also
used successfully throughout the world. The application range includes
automation in the areas of manufacturing, processing and building. Profibus
DP is an international, open fieldbus which has been standardized in the
fieldbus standard EN 50 170. This standardization ensures that the invest-
ments of manufacturers and users are protected to the best possible degree
and the independence of the manufacturer is guaranteed.
These operation instructions cannot provide a general introduction into
Profibus DP. For more information, please refer to the literature references in
appendix D.
4.1 Basic characteristics Profibus DP defines the technical and functional features of a serial fieldbus
system allowing the interconnection of distributed, digital automation
devices. Profibus DP distinguishes between master and slave devices.
Profibus DP is designed for fast data transmission on the field level. Here,
central control devices, such as a PLC or PC, communicate via a fast serial
connection with peripheral field devices such as input/ output devices,
valves, and actuators.
The interchange of data among the field devices is realised on a cyclic
basis. The respectively necessary communication functions are established
by the Profibus DP basic functions according to EN 50 170.

Master devices control the data traffic on the bus. A master is allowed to
send messages without an external request. Masters are also called active
devices in the Profibus protocol.

Slave devices such as AUMA Profibus DP actuators are peripheral devices.


Typical slave devices are input/ output devices, valves, actuators and
measuring transmitters. They do not have bus access, i.e. they may only
acknowledge received messages or, at the request of a master, transmit
messages to that master. Slaves are also called passive devices.

5
Actuator controls AUMA MATIC AM/ AMExB/ AMExC
Profibus DP Operation instructions

4.2 Basic functions of Profibus DP


The master reads the input information from the slaves cyclically and writes
the output information cyclically to the slaves. In addition to this
cyclic data transfer of the process representation, Profibus DP also provides
powerful functions for diagnostics and commissioning purposes. The data
traffic is monitored through the monitoring functions on the master and slave
side.

4.3 Transfer mode .. RS-485 twisted pair cable or fibre optic cable.
AUMA actuators support baud rates up to 1.5 MBits/s

.
..
4.4 Bus access Token-passing between the masters and polling between master and
slave.
Mono-master or multi-master systems are possible.
Master and slave devices: max. 126 devices connected to one bus

.
.
4.5 Communication Peer-to-peer (process data exchange [DATA EX]) or Multicast (control
commands to all slaves).
Cyclic master-slave process data exchange (DATA EX) or acyclic
master-master data transfer. Cyclic master-slave process data exchange
(DATA EX) or acyclic master-master data transfer.

.
..
4.6 Functionality Cyclic process data exchange (DATA EX) between DP master and DP
slaves.

.
Dynamic activation or de-activation of individual DP slaves.
Checking the configuration of the DP slaves
Synchronisation of inputs and/ or outputs.

..
..
4.7 Protection functions All messages are transmitted with Hamming Distance HD=4.
Watchdog timer at DP slaves.
Access protection for the inputs/ outputs of the DP slaves

.
Process data exchange (DATA EX) monitoring with configurable timer
interval at the master.
Adjustable failure behaviour.

..
.
4.8 Device types DP master class 2 (DPM2), e.g. programming/ configuration tools.
DP master class 1 (DPM1), e.g. central controllers such as PLC, PC.
DP slave, e.g. AUMA Profibus DP devices. Devices with binary or
analogue inputs/ outputs, actuators, valves.

6
Actuator controls AUMA MATIC AM/ AMExB/ AMExC
Operation instructions Profibus DP

5. Technical data
Table 1: Profibus DP interface for actuator controls AM/ AMExB/ AMExC
Features and functions
Power supply Standard voltages:
3-phase AC 1-phase AC 1)
voltages/ frequencies voltages/ frequencies
Volt 220 230 240 380 400 415 440 460 480 500 Volt 110,115,120 220,230,240
Hz 50 50 50 50 50 50 60 60 60 50 Hz 50/60 50/60
Special voltages:
3-phase AC 1-phase AC 1)
voltages/ frequencies voltages/ frequencies
Volts 525 575 660 690 208
Hz 50 50 50 50 60
External supply of the electronics 24 V DC + 20 % / 15 %,
(option) Current consumption: Basic version approx. 200 mA, with options up to 500 mA
Switchgear Standard: Reversing contactors2) (mechanically and electrically interlocked)
for motor power up to 1.5 kW
Options: Reversing contactors2) (mechanically and electrically interlocked)
for motor power up to 7.5 kW
Thyristor unit3) (recommended for modulating actuators)
for motor power up to 1.5 kW, 500 V AC with internal fuses
for motor power up to 5.5 kW, 500 V AC, external fuses required
Control and output signals via Profibus DP interface
Profibus DP interface with Profibus DP interface with 4 free 24 V DC inputs and 2 free 0/4 20 mA inputs. Signal
additional inputs (option) transmission via fieldbus interface.
Local controls Standard: Selector switch LOCAL OFF REMOTE (lockable in all three positions)
Push buttons OPEN STOP CLOSE
3 indication lights:
End position CLOSED (yellow), collective fault signal (red),
End position open (green)
Option: Protection cover, lockable
Functions Standard Switch-off mode adjustable
Limit or torque seating for end position CLOSED
Overload protection against excessive torque over the whole travel
Phase failure monitoring with automatic phase correction
Push-to-run operation or self-retaining in LOCAL
Positioner4):
Nominal position value via Profibus DP interface
Adjustable behaviour on loss of signal
Adjustable sensitivity (dead band) and pause time
Motor protection evaluation Standard: For AM: Monitoring of the motor temperature in combination with
thermoswitches in the actuator motor
For AMExB/ AMExC: Monitoring of the motor temperature with PTC tripping
device in combination with PTC thermistors in the actuator motor
Options: Additional thermal overload relay in the controls in combination with
thermoswitches within the actuator
PTC tripping device in combination with PTC thermistors in the actuator motor
Electrical connection Standard: For AM: AUMA plug/ socket connector with screw type connection
For AMExB/ AMExC: Ex-plug/ socket connector with terminal board
For further options and threads for cable entries, please refer to separate
technical data sheets
Special threads, other than standard mentioned above, possible
Control plug gold plated3) (sockets and pins)
Parking frame for wall mounting of the disconnected plug
Protection cover for plug compartment (when plug is removed)
Overvoltage protection3) (option) Protection of the actuator and controls electronics against overvoltages on the fieldbus
cables of up to 4 kV
Wiring diagram (basic version) MSP 1B1-00-1-F18E1 KMS TP102/001

1) AC current only with AM 01.1/ AM 02.1 and AMExC 01.1 in combination with actuator SGExC
2) The lifetime guaranteed by the manufacturer amounts to min. 2 million cycles. If a higher number of switching cycles is to be expected, thyristor units with
virtually unlimited lifetime should be used
3) Only in combination with AM 01.1 and AM 02.1
4) Requires position transmitter (potentiometer or RWG) in actuator

7
Actuator controls AUMA MATIC AM/ AMExB/ AMExC
Profibus DP Operation instructions

Settings/ programming of the Profibus DP interface


Setting of the baud rate Automatic baud rate recognition
Setting of the Profibus DP The Profibus DP address is set via rotary switches
address
Commands and signals of the Profibus DP interface
Process representation output OPEN, STOP, CLOSED
(command signals) Nominal position value
4)

Process representation input End position OPEN, CLOSE


(feedback signals) Actual position value 4)
Selector switch in position LOCAL/ REMOTE
Running indication4) (directional)
Torque switch OPEN, CLOSED
Limit switch OPEN, CLOSED
Manual operation by handwheel 4) or via local controls
Process representation input Motor protection tripped
(fault signals) Torque switch tripped in mid-travel
One phase missing
Behaviour on loss of The behaviour of the actuator is programmable:
communication running to end position OPEN or CLOSED
running to any intermediate position4)
General data Profibus DP
Communication protocol Profibus DP according to EN 50 170-2 or DIN 19 245
Network topology Linear (BUS) structure. When using repeaters, tree structures can also be realised. Coupling
and uncoupling of devices during operation without affecting other devices is possible.
Transmission medium Twisted, shielded copper cable according to EN 50 170
Profibus DP interface EIA-485 (RS485)
Transmission speed/
cable length Max. cable length (segment Possible cable length with repea-
Baud rate (kbit/s)
length) without repeater ter (total network cable length)
9.6 1,200 m approx. 10 km
19.2 1,200 m approx. 10 km
45.45 1,200 m approx. 10 km
93.75 1,200 m approx. 10 km
187.5 1,000 m approx. 10 km
500 400 m approx. 4 km
1,500 200 m approx. 2 km

Device types DP master class 1, e.g. central controllers such as PLC, PC, ...
DP master class 2, e.g. programming/ configuration tools
DP slave, e.g. devices with digital and/ or analog inputs/ outputs such as actuators, sensors
Number of devices 32 devices without repeater, with repeater expandable to 126
Bus access Token-passing between the masters and polling for slaves.
Mono-master or multi-master systems are possible.
Supported Profibus DP functions Cyclic data exchange, sync mode, freeze mode, fail-safe mode
Service conditions
Enclosure protection according Standard: IP 67 (when mounted)
to EN 60 529 Options: IP 685)
DS3) Terminal compartment additionally sealed against interior
(double sealed)
Corrosion protection Standard: KN Suitable for installation in industrial units, in water or power plants
with a low pollutant concentration
Options: KS Suitable for installation in occasionally or permanently aggressive
atmosphere with a moderate pollutant concentration
(e.g. wastewater treatment plants, chemical industry)
KX Suitable for installation in extremely aggressive atmosphere with high
humidity and high pollutant concentration
KX-G Same as KX, however aluminium-free version (outer parts)

3) Only in combination with AM 01.1 and AM 02.1


4) Requires position transmitter (potentiometer or RWG) in actuator
5) For version in enclosure protection IP 68, higher corrosion protection KS or KX is strongly recommended

8
Actuator controls AUMA MATIC AM/ AMExB/ AMExC
Operation instructions Profibus DP

Finish coating Standard: Two-component iron-mica combination


Option: Special primer/ special finish coat (customers choice)
Colour Standard: Silver-grey (DB 701, similar to RAL 9007)
Option: Other colours than standard colour are possible on request
Ambient temperature AM 01.1/ AM 02.1:
Standard: 25 C to + 70 C
Options: 40 C to + 70 C, low temperature version
50 C to + 70 C, extreme low temperature version incl. heating system
60 C to + 70 C, extreme low temperature version incl. heating system
AMExB/ AMExC:
Standard: 20 C to + 40 C
Options: 40 C to + 40 C, low temperature version
50 C to + 40 C, extreme low temperature version incl. heating system
Vibration resistance6) 1 g, from 10 Hz to 200 Hz
according to IEC 60 068-2-6 (Only actuator with controls. Not valid in combination with gearboxes)
Gewicht approx. 7 kg (with AUMA plug/ socket connector)
approx. 12 kg (including Ex-plug/ socket connector with terminal board)
Accessories
Wall bracket7) AUMA MATIC mounted separately from the actuator, including plug/ socket connector.
Connecting cables on request.
Recommended for high ambient temperatures, difficult access, or in case of heavy
vibrations during service.
Other information
EU Directives Electromagnetic Compatibility (EMC): (89/336/EEC)
Low Voltage Directive: (73/23/EEC)
Machinery Directive: (98/37/EC)
Reference documents Product description Actuator controls AUMA MATIC
Dimension sheets Multi-turn actuators/ part-turn actuators
with integral controls AUMA MATIC

6) Resistant to vibrations during start-up or for failures of the plant. However, a fatigue strength may not be derived from this
7) Cable length between actuator and AUMA MATIC max. 100 m. Not suitable for version with potentiometer in the actuator. Instead of the potentiometer, an RWG
has to be used in the actuator

9
Actuator controls AUMA MATIC AM/ AMExB/ AMExC
Profibus DP Operation instructions

6. Design AUMA MATIC Profibus DP


The AUMA MATIC Profibus DP by AUMA represents the ideal controls for
connecting multi-turn actuators of the SA range and part-turn actuators of
the SG range to Profibus DP.

Figure A: AUMA MATIC Profibus DP


Profibus DP interface

Logic board

Local controls

Profibus DP
connection board

Electrical connection with


AUMA plug/ socket connector

Power supply unit

Switchgear
Selector switch
Signal and control board

Plug/ socket connector


to the actuator

The integral controls AUMA MATIC Profibus DP consist of the following

.
modules:

.
Profibus DP interface. The interface links the Profibus DP data with the
internal electronics.
The logic board links the signals of the actuator with the local controls and

.
the Profibus DP interface and controls the reversing contactors or the
thyristors.
Local controls with selector switch, push buttons, and indication lights.
The selector switch is used to select the control devices for local control
LOCAL 0 REMOTE for remote control.

.
The push buttons (OPEN) Stop (CLOSE) are used for the
electric operation of the actuator on site.

.
Plug/ socket connectors for easy mounting of the AUMA MATIC Profibus
DP on the actuators.
Signal and control board with primary fuses, relays for conversion of the

..
local control commands into electrical signals, and indication lights as an
option.
Switchgear: Reversing contactors or thyristors for motor controls.
Profibus DP connection board with terminals for the Profibus DP cable and
the termination resistor for bus termination.

Actuators which have already been installed can be retrofitted for Profibus
DP by exchanging the controls AUMA MATIC for controls AUMA MATIC
Profibus DP.

10
Actuator controls AUMA MATIC AM/ AMExB/ AMExC
Operation instructions Profibus DP

7. Electrical connection . Work on the electrical system or equipment must only be


carried out by a skilled electrician himself or by specially
instructed personnel under the control and supervision of
such an electrician and in accordance with the applicable

. electrical engineering rules.


Installation regulations for Profibus DP must be observed
for the wiring.
(For literature references, please refer to appendix D)

Make sure to respect electromagnetic compatibility (EMC) when installing cables:

.
Signal and bus cables are susceptible to interference. Electric power cables,
in particular motor cables, are interference sources.

.
Lay cables being susceptible to interference or sources of interference at
the highest possible distance from each other.

.
The interference immunity of signal and bus cables increases if the cables
are laid close to the ground potential.

.
If possible, avoid laying long cables and make sure that they are installed
in areas being subject to low interference.
Avoid long parallel paths with cables being either susceptible to interfe-
rence or interference sources.

7.1 Power supply (standard) For explosion-proof version (type designation: AMExB/ AMExC), please

.
refer to page 15 or page 17.
Figure B-1: Connection

..
Check whether type of current, supply voltage, and frequency comply with
50.0 motor data (refer to name plate at motor).
Loosen bolts (50.01) (figure B-1) and remove connection housing.

.
50.01 Loosen screws (51.01) and remove socket carrier (51.0) from plug cover
(50.0).
Insert cable glands suitable for connecting cables.

..
(The enclosure protection stated on the name plate is only ensured if suit-
51.0
able cable glands are used).
Seal cable entries which are not used with suitable plugs.
Connect cables according to order-related wiring diagram.
51.01 The wiring diagram applicable to the actuator is attached to the handw-
heel in a weather-proof bag, together with the operation instructions. In
case the wiring diagram is not available, it can be obtained from AUMA
(state commission no., refer to name plate) or downloaded directly from
Figure B-2: Parking frame (accessory) the Internet (www.auma.com).

A special parking frame (figure B-2) for protection against touching the bare
contacts and against environmental influences, in case the electrical
connection has been removed, is available.

Parking frame

Table 2: Technical data AUMA plug/ socket connector for bus connection
Technical data Motor power connections1) Protective earth Control terminals
No. of contacts max. 6 (3 are used) 1 (leading contact) 50 pins / sockets
Marking U1, V1, W1, U2, V2, W2 according to VDE 1 to 50
Connecting voltage max. 750 V 250 V
Nominal current max. 25 A 16 A
Type of customer connection Screws Screw for ring lug Screws
Cross section max. 6 mm2 6 mm2 2.5 mm2
Material: Pin/ socket carrier Polyamide Polyamide Polyamide
Contacts Brass (Ms) Brass (Ms) Brass, tin plated or gold plated (option)
1)Suitable for copper wires. For aluminium wires, please contact AUMA

11
Actuator controls AUMA MATIC AM/ AMExB/ AMExC
Profibus DP Operation instructions

7.2 Bus connection (standard) For explosion-proof version (type designation: AMExB/ AMExC), please
refer to page 15 or page 17.
For version with FO (fibre optics), please refer to separate operation instruc-

.
tions AUMA MATIC AM 01.1/ AM 02.1 FO connection.

Connect bus cable. Refer to figures C-1 and C2.

The termination resistors for channel 1 and channel 2 (options) are switched
in via switches (S1) and (S2). Both switches are supplied in position OFF.
Only switch on the termination resistors (position ON) if the actuator is the
final device in the Profibus segment.

Only switch on the termination resistors (position ON) if the


actuator is the final device within the Profibus DP segment.

Table 3: Switch positions of S1 and S2

ON Bus termination channel 1 ON


S1
OFF Bus termination channel 1 OFF
ON Bus termination channel 2 ON (option)
S2
OFF Bus termination channel 2 OFF (option)

Figure C-1: Connection board (standard)

S1 S2
Bus termination Bus termination
channel 1 channel 2
(option)

Connection Connection
channel 1 channel 2
(redundant)

Screening Screening

Figure C-2: Connection (standard)

X1

5V P/B N/A P/B N/A GND

B A B A
from previous / to next
Profibus DP device
channel 1

12
Actuator controls AUMA MATIC AM/ AMExB/ AMExC
Operation instructions Profibus DP

Figure C-3: Connection board (for overvoltage protection)

x1 x2

Figure C-4: Connection for overvoltage protection

X1

1 2 3 4

from previous/ to next


Profibus DP device
channel 1

Table 4: Assignment of Profibus cable


AUMA SUB-D 9 plug pin
Profibus
labelling at the (for other Colour
cable
connection Profibus devices)
A N/A 8 green
B P/B 3 red

.
7.3 Fitting the cover After connection:

..
Insert the socket carrier (51.0) into the plug cover (50.0) and fasten it with
screws (51.01).

..
Clean sealing faces at the plug cover and the housing.
Check whether O-ring is in good condition.

.
Apply a thin film of non-acidic grease (e.g. Vaseline) to the sealing faces.
Replace plug cover (50.0) and fasten bolts (50.01) evenly crosswise.
Fasten cable glands with the specified torque to ensure the required
enclosure protection.

13
Actuator controls AUMA MATIC AM/ AMExB/ AMExC
Profibus DP Operation instructions

7.4 Remote position transmitter For the connection of remote position transmitters (potentiometer, RWG)
screened cables must be used.

.
7.5 AUMA MATIC on wall bracket The AUMA MATIC can also be mounted separately from the actuator on a
wall bracket.
Figure C-5: AM on wall bracket For the connection of actuator and AUMA MATIC on wall bracket, use suit-

.
able flexible and screened connecting cables.
(Preconfectioned cables can be obtained from AUMA on request)

.
Permissible cable distance between actuator and AUMA MATIC amounts
to a max. of 100 m.

.
Versions with potentiometer in the actuator are not suitable. Instead of the
potentiometer, an RWG has to be used in the actuator.
Connect the wires in correct phase sequence.
Check direction of rotation before switching on.

Connecting cable to actuator

7.6 Test run Perform test run. Please refer to the operation instructions pertaining to the
actuator (multi-turn actuator SA(R) ... / part-turn actuator SG ...).
Check limit and torque switching:
Check limit and torque switching, electronic position transmitter RWG or
potentiometer (option) and re-set where appropriate.
The settings are described in the operation instructions pertaining to the
actuator (multi-turn actuator SA(R) ... part-turn actuator SG ... ).

For actuators with feedback signal (RWG, potentiometer), a reference


operation has to be performed after having changed the setting.

.
Perform reference operation:
Run actuator electrically (via the push buttons OPEN and CLOSE of the

.
local controls) once to the end position OPEN and once to the end posi-
tion CLOSED.
If no reference operation is performed after changing the limit switching,
the feedback signal via the bus is not correct. The bus signals the missing
reference operation as warning (see page 32).

14
Actuator controls AUMA MATIC AM/ AMExB/ AMExC
Operation instructions Profibus DP

7.7 Mains and bus connection for Ex-version with plug/ socket connector/ terminal board (KP)

When working in potentially explosive areas, observe the


European Standards EN 60079-14 Electrical installations in
hazardous areas and EN 60079-17 Inspection and mainten-
ance of electrical installations in hazardous areas.

Figure D-1: Connection For the Ex-plug/ socket connector (figure D-1), the electrical mains connec-
tion is made after removing the plug cover (50.0) at the EEx e terminals of
50.0 the terminal board (51.0). The flameproof compartment (type of protection

.
EEx d) remains hereby closed.
50.01

.
Check whether type of current, supply voltage, and frequency correspond
to motor data (refer to name plate at motor).
Loosen bolts (50.01) (figure D-1) and remove plug cover.

51.0 . Insert cable glands with EEx e approval and of size suit-
able for connecting cables. For the recommended cable
glands refer to appendix E, page 54.
(The enclosure protection stated on the name plate is only

Figure D-2: Disconnection from the mains


.. ensured if suitable cable glands are used).
Seal cable entries which are not used with suitable plugs.
Maximum 2 wires with the same cross section may be con-

.
nected to one terminal.
50.0
Remove cable sheathing in a length of 120 140 mm.

.
Strip wires: Controls max. 8 mm, motor max. 12 mm.
For stranded wires use end-sleeves according to DIN 46228.
51.0 Connect bus cable. Refer to figures (D-4 or D-5).
The termination resistor for channel 1 is connected through linking the

.
terminals 1 4 and 3 2 (standard). Only connect the termination resistor
51.02
if the actuator is the final device in the Profibus segment.
Connect screen largely to the cable glands. For the recommended cable
glands refer to appendix E, page 54.

If the actuator must be taken from the valve, e.g. for service purposes, it can be
separated from the mains without having to remove the wiring (figure D-2). For
this purpose, the screws (51.02) are removed and the plug/ socket connector is
pulled off. Plug cover (50.0) and terminal board (51.0) remain together.

Figure D-3: Parking frame (accessory)


Flameproof enclosure! Before opening, ensure that no
explosive gas and no voltage is present.

A special parking frame (figure D-3) for protection against touching the bare
contacts and against environmental influences is available.

Parking frame

15
Actuator controls AUMA MATIC AM/ AMExB/ AMExC
Profibus DP Operation instructions

Figure D-4: Bus connection for channel 1 (standard)

Another bus device follows the actuator

from previous to next


Profibus DP device Profibus DP device
channel 1 channel 1
Actuator is final bus device

Table 5: Technical data Ex plug/socket connector with terminal board for explosion-proof actuators
Technical data Motor power connections1) Protective earth Control terminals
No. of contacts max. 3 1 (leading contact) 38 pins/ sockets
Marking U1, V1, W1 1 to 24, 31 to 50
Connecting voltage max. 550 V 250 V
Nominal current max. 25 A 10 A
Type of customer connection Screws Screws Screws
Cross section max. 6 mm2 6 mm2 1.5 mm2
Material: Pin/ socket carrier Araldite/ Polyamide Araldite/ Polyamide Araldite/ Polyamide
Contacts Brass (Ms) Brass (Ms) Brass (Ms) tin-plated
1) Suitable for copper wires. For aluminium wires, please contact AUMA.

16
Actuator controls AUMA MATIC AM/ AMExB/ AMExC
Operation instructions Profibus DP

7.8 Mains and bus connection for Ex-version with plug-in terminal connection (KES)

When working in potentially explosive areas, observe the


European Standards EN 60079-14 Electrical installations in
hazardous areas and EN 60079-17 Inspection and mainten-
ance of electrical installations in hazardous areas.

The bus connection is realised via terminals (figure E-1) The terminal
compartment is designed for explosion protection EEx e (increased
Figure E-1: Plug-in terminal connection safety). The controls AUMA MATIC (type of protection EEx d) remain closed.

.
.
Loosen bolts (1) (figure E-1) and remove terminal cover.

Terminal
Insert cable glands with EEx e approval and of size suit-
cover able for connecting cables. For the recommended cable
glands refer to appendix E, page 54.
(The enclosure protection stated on the name plate is only

Terminals
. ensured if suitable cable glands are used).
Seal cable entries which are not used with suitable plugs.

Cross sections for connection:


Control cables: max. 2.5 mm
Motor connection: max. 10 mm,

.
Suitable bus cables, see page 19.

Terminal Connect bus cable to channel 1 according to configuration of the termi-


board nals (figure E-2).

.
The termination resistor for channel 1 is connected through linking the
terminals 1 2 and 3 4.
Only connect the termination resistors if the actuator is the final device in
the Profibus segment.
Figure E-2: Terminal configuration for Ex connection (KES)

Another bus device


follows the actuator

Previous Next
Profibus DP device Profibus DP device

Actuator is final
bus device

Previous
Profibus DP device

17
Actuator controls AUMA MATIC AM/ AMExB/ AMExC
Profibus DP Operation instructions

7.9 Redundant bus connection AUMA Profibus DP devices can be connected with a second (redundant)
Profibus cable. If the bus on channel 1 fails,
e. g. through cable break, the slave automatically switches to channel 2.

This cable redundancy may only be applied after previous


integration test using the desired process control system!

. For versions with AUMA plug/ socket connector (subclause 7.2):

.
Connect redundant bus cable to channel 2in the same way as channel 1
(refer to connection diagram figure C-2).
For Ex-version with plug/ socket connector / terminal board (KP)
(subclause 7.7):
Connect cable B to terminal 6, cable A to terminal 7.

.
The termination resistor for channel 2 is connected through linking the
terminals 5 6 and 7 8.
For Ex-version with plug-in terminal connection KES)
(subclause 7.8):
Connect cable B to terminal 6, cable A to terminal 7 (figure E-2).
The termination resistor for channel 2 is connected through linking the
terminals 5 6 and 7 8.

The setting of the redundant bus connection is realised via the parameters
4 and 5 (see page 23).

18
Actuator controls AUMA MATIC AM/ AMExB/ AMExC
Operation instructions Profibus DP

7.10 Bus cables Only cables according to standard DIN 19245 or EN 50170-2, cable type A,
may be used for Profibus DP wiring.

A maximum of up to 32 Profibus devices may be connected in one segment.


If more devices are to be connected to one Profibus network, several
segments must be connected with repeaters.
The bus cable must be laid at a distance of at least 20 cm from other cables.
It should be laid in a separate, conductive and earthed cable trunking.
It must be ensured that there are no potential differences between the indivi-
dual devices on the Profibus (perform a potential compensation).

Table 6

Transmission rate in kBit/s


93.75 187,5 500 1500
Maximum segment length in m
1200 1000 400 200

Cable specification cable type A for Profibus DP

Characteristic impedance: 135 to 165 Ohm, at a frequency


of 3 to 20 Mhz.
Cable capacity: < 30 pF per meter
Core diameter > 0.64 mm
Core cross section: > 0.34 mm, corresponds to AWG 22
Loop resistance: < 110 Ohm per km
Screening: Copper shielding braid or shielding braid and
shielding foil

Figure F: Example: Profibus with one segment

Controls (master) Bus termination


switched on

2-wire cable

Profibus DP board Bus termination


switched on
Connection
board

AUMA MATIC
Profibus DP

19
Actuator controls AUMA MATIC AM/ AMExB/ AMExC
Profibus DP Operation instructions

7.11 Setting the Profibus DP address

.
The bus address is set on the Profibus DP interface board.

Loosen screws and remove cover (figure G-1)


Figure G-1
Screws

Profibus DP
interface board

. Set the required bus address using rotary switches S2 and S3


(figure G-2). (Factory setting: slave address 2)

Switch (S2) for setting the units digit.


Switch (S3) for setting the tens digit.

Example: The address 65 is set as follows:


(S2) to position 5 = (5 * 1 = 5)
(S2) to position 6 = (6 * 10 = 60)

Figure G-2: Profibus DP interface board

Rotary switch S3
Rotary switch S2

20
Actuator controls AUMA MATIC AM/ AMExB/ AMExC
Operation instructions Profibus DP

8. Commissioning with controls


8.1 Introduction When commissioning a Profibus DP network, the devices on the Profibus DP
must be parameterized and configured with the programming software of the
controls (Profibus configurator).
The programming software first reads the GSD file (General Station Data) of
the individual actuators. The GSD file contains information about the proper-
ties of the device which are needed by the master. The GSD file can be
downloaded from the Internet website www.auma.com.
Afterwards, the user can configure and program the instrument at the
Profibus DP for the programming software of the process control system.
This information is then stored in the controls (DP master) and sent to the
actuators (DP slaves) each time communication is started.
The control is executed via the process representation input and output
bytes.
If a configuration with consistent data is chosen, special functional elements
for the control of the Profibus DP slaves must be used with some PLCs.
8.2 Programming The parameterization is partly determined in the Profibus standard, e.g. a bit
for switching bus monitoring on and off (watchdog).
The AUMA Profibus DP control can additionally receive up to 100 bytes of
user parameters, in which AUMA specific parameters can be set. The
AUMA specific parameters are divided into 50 parameters with 2 bytes each
per parameter. The parameters can be changed via the programming soft-
ware of the controls. New programming software supports the setting of the
parameters via text and a menu selection. When using older software, the
values of the parameters must be entered using hexadecimal numbers.
The meaning of the individual AUMA specific parameters is explained in
subclause 8.5.
8.3 Configuration of the Profibus DP interface of the AUMA MATIC
During configuration, selection is made of how many input and output bytes
for each device are reserved in the controls memory. Additionally it is deter-
mined if the data is processed consistently or non-consistently.

Only the number of bytes determined in the configuration is


transferred between DP master and DP slave.

The following configurations are possible with AUMA Profibus DP actuators:


Table 7:
Number of input bytes Number of output bytes
1 1
2 1
2 2
4 4
6 1
6 2
6 4
8 4
12 4
16 8

All these configurations (except 1 In, 1 Out) can be selected as consistent or


non-consistent

The number of input bytes states how many of the maximum 16 bytes the
DP slave sends to the DP master.
The number of output bytes states how many of the maximum 8 bytes the
DP master sends to the DP slave.

21
Actuator controls AUMA MATIC AM/ AMExB/ AMExC
Profibus DP Operation instructions

If, for example, the configuration with 8 bytes input is selected, only the first
8 bytes are sent from the DP slave to the DP master. In this case, the
master does not have access to bytes 9 to 12.
This way, the DP master saves memory space since it only has to reserve 8
input bytes for the actuator.
The data of the AUMA actuators should be consistently processed by the
DP master. This ensures that the value of a 2 byte variable (position trans-
mitter, analogue customer input) does not change after the reading out of
the first byte and, thus, does not distort the value.
If a master does not offer the possibility to use consistent configurations by
means of the process control system, a non-consistent configuration can be
chosen. The values for the position transmitter and the analogue customer
inputs can then be transferred in 1 byte format (parameter 2 = 0).
8.4 Communication start-up When the DP master is switched on, it first sends a parameter and configu-
ration telegram to each DP slave. If parameters and configuration are
correct, the DP slave enters the Data Exchange mode to exchange
process data between the controls and the slave. Then, the DP master can
control the DP slave and read its current state via the process representa-
tion.
If communication is interrupted (e.g. due to switching off the slave or the
breaking of the Profibus cable), it is automatically resumed by the DP
master, once the origin of the fault has been eliminated.

8.5 Description of AUMA user parameters

The AUMA specific parameter are set by means of the GSD file.
Parameter 1 Position transmitter [Stellungsgeber]
Default value (standard setting): 1
0: The actuator is not equipped with a position transmitter.
1: Actuator is equipped with a potentiometer without RWG.
2: Actuator is equipped with an RWG 0 20 mA.
For this position transmitter, the signal interruption monitoring is not acti-
vated.
3: Actuator is equipped with an RWG 4 20 mA.
For this position transmitter, the signal interruption monitoring is activated.

Parameter 2 Measured data coding position transmitter


[Messwertkodierung Stellungsgeber]
Default value: 0
0: 0 to 100 percent, resolution amounts to 1 %
The position transmitter value is indicated in process representation input
in byte 4. Byte 3 is fixed to the value 0.
The setpoint is realised via byte 4 of process representation output.
Byte 3 must be set to 0.
1: 0 to 1000 per mil, resolution amounts to 0.1 %
The position transmitter value is read using bytes 3 and 4 of process
representation input.
The setpoint is realised via bytes 3 (high byte) and 4 (low byte) of process
representation output.

Parameter 3 "Reversing prevention in ms" [Reversiersperre in ms]


Parameter for setting the pause time in between a change of direction.
If necessary, adjust the value to the mechanics to prevent destruction
caused by excessively fast changes of direction.

Default value: 200


lowest value:100 (0.1s)
maximum value: 1000 (1 s)

22
Actuator controls AUMA MATIC AM/ AMExB/ AMExC
Operation instructions Profibus DP

Parameter 4 Redundancy [Redundanz]


Default value: 0
0: no cable redundancy (only the first channel is used for communication).
1: cable redundancy switched on (first and second channel cabled)
The watchdog must be activated, otherwise the
parameter record is rejected by the DP slave.

Parameter 5 Time for channel changing in 0.1 s


[Zeit fr Kanalwechsel in 0,1 s]
Indicates the time after which the channel is changed if no process data
exchange (DATA EX) takes place (no Data Exchange or DP-Fail-Safe
state).
This parameter is only effective if the cable redundancy (parameter 4) is
switched on.

Default value: 50
lowest value: 50 (5 s)
maximum value: 6000 (10 min)
Parameter 6 Failure behaviour [Sicherheitsverhalten]
Failure operation on failure of connection (no status Data_Exchange or DP
fail-safe).
The parameters set in the most recent connection also apply to the failure
behaviour after an interruption in the voltage supply. If the parameter is set
to the values 1 or 2, the watchdog must be activated, otherwise the para-
meter record is rejected by the DP slave.

Default value: 0
0: Failure behaviour switched off (parameters 7, 8, 9 are insignificant)
1: Simple failure behaviour switched on.
A failure operation will only be started if a connection to the master
(process data exchange [DATA EX]) has already been available.
2: Extended failure behaviour switched on.

If extended failure behaviour is switched on, a failure opera-


tion can be initiated immediately after the actuator has been
switched on.

Parameter 7 Delay time for failure operation 0.1s


[AusloesZeitSicherheitsfahrt 0,1 s]
Delay time for failure operation in 0.1 s.
Indicates the down time of process data exchange after which a failure
operation will be started. If the exchange is restored during this time, no
failure operation will be performed.

Default value: 30
lowest value: 0 (actuator reacts immediately)
maximum value: 12,000 (actuator reacts after 20 minutes)
Parameter 8 Failure operation [Sicherheitsfahrt]
Default value: 0
0: Actuator remains in its position (STOP).
1: Actuator runs CLOSE.
2: Actuator runs OPEN.
3: Actuator runs to failure position (refer to parameter 9).

If no position transmitter is installed (Parameter 1 = 0), value 3 is not


permitted. In this case, the parameter record is rejected.

23
Actuator controls AUMA MATIC AM/ AMExB/ AMExC
Profibus DP Operation instructions

Parameter 9 Failure position in per mil


[Sicherheitsposition in Promille]
Actuator runs to the pre-set failure position.
This parameter is only effective if parameter 8 (failure operation) is set to
value 3, and if parameter 6 (failure behaviour) is not 0.

Default value: 0
lowest value: 0 (end position CLOSED)
maximum value: 1000 (end position OPEN)

Parameter 10 Output speed failure operation percentage


[Drehzahl Sicherheitsfahrt Proz]
Running speed applied to approach failure position.
Only effective in combination with variable speed AUMA actuators, type AS,
ASR.
Only effective if parameter 8 (failure operation) and parameter 6 (failure
behaviour) are not set to 0.

Default value: 100


lowest value: 0 (minimum output speed)
maximum value: 100 (maximum output speed)

For detailed descriptions of parameters 11 to 14, please refer to


subclause 11.2
Parameter 11 Dead time positioner in 0.1 s
[Totzeit Stellungsregler in 0,1 s]
Indicates the dead time which has to be maintained between two motor
starts. In case the Profibus DP Master issues a command before that time,
the AUMA MATIC delays the actuator reaction until dead time has expired.

The controls must ensure that the maximum number of


motor starts of the actuator is not exceeded.

Default value: 0
minimum value: 0 (actuator reacts immediately)
maximum value: 600 (actuator delays reaction by 1 minute max.)
Parameter 12 Overrun direction OPEN in per mil
[Nachlauf Richtg AUF in Promille]
The motor is switched off as soon as the distance between the actuator
position and the nominal position reaches this value. This is only valid for
operations in direction OPEN. This parameter must be smaller than the
value in parameter 14 (max. error in per mil).

Default value: 5
minimum value: 0 (no overrun in direction OPEN)
maximum value: 100 (10 % overrun in direction OPEN)
Parameter 13 Overrun direction CLOSE in per mil
[Nachlauf Richtg ZU in Promille]
The motor is switched off as soon as the distance between the actuator
position and the nominal position reaches this value. This is only valid for
operations in direction CLOSE.
This parameter must be smaller than the value in parameter 14
(max. error in per mil).

Default value: 5
minimum value: 0 (no overrun in direction CLOSE)
maximum value: 100 (10 % overrun in direction CLOSE)

24
Actuator controls AUMA MATIC AM/ AMExB/ AMExC
Operation instructions Profibus DP

Parameter 14 Max. error in per mil


[max. Regelabweichung in Promille]
The actuator will only be restarted if the distance between the nominal posi-
tion and the actual position is higher than this value.
Corresponds to the outer dead band.
This parameter must be higher than the values of parameter 12 (overrun in
direction OPEN) and parameter 13 (overrun in direction CLOSE).

The parameter must be set sufficiently high to ensure a


stable function of the positioner. If the value is set too low,
the actuator moves continuously around the nominal value
which will result in reducing the life time of the actuator.

Default value: 10
minimum value: 1 (0.1 % error).
maximum value: 100 (10 % error).
Parameter 15 "Proportional operation active" [Proportionalfahrt aktiv]
Soft start/ soft stop is only possible together with variable speed actuators
(type AS, ASR). This parameter has no influence on non-variable speed
actuators.

Default value: 0
0: no soft start/ soft stop (proportional operation)
1: soft start/ soft stop (proportional operation)

Parameter 15 19 reserved for variable output speed


actuators of types AS, ASR with motor controls AUMA
VARIOMATIC.

Parameter 16 Proportional range Stop in per mil


[ProportBereich Stop in Promille]
Proportional range of the nominal position in per mil (soft stop).
If the difference between nominal and actual actuator position is smaller
than this value, the running speed will decrease proportionally to the diffe-
rence in nominal/ actual position. This allows the nominal position to be
gently reached. Only effective if parameter 15 (proportional operation
active) and parameter 1 (position transmitter) are not set to 0.

Default value: 100


minimum value: 0 (soft stop ineffective)
maximum value: 1000 (soft stop over the whole travel)
Parameter 17 Stop speed in percent [Stopgeschwindigeit in Prozent]
Default value: 0
minimum value: 0 (actuator moves to nominal position with min. speed)
maximum value:100 (actuator moves to nominal position with max speed).

Running speed with which the nominal position will be approached.


Only effective if parameter 15 (proportional operation active) and parameter
1 (position transmitter) are not set to 0.
Parameter 18 "Proportional range start in per mil" [ProportBereich
Start in Promille]
Proportional range of the start position in per mil (soft start)
If the difference between start position and actual actuator position is
smaller than this value the running speed will increase proportionally to the
difference in nominal/ actual position. This causes the actuator to gently
leave the start position. Only effective if parameter 15 (proportional opera-
tion active) and parameter 1 (position transmitter) are not set to 0.

Default value: 40
minimum value: 0 (soft start ineffective)
maximum value: 1000 (soft start over the whole travel)

25
Actuator controls AUMA MATIC AM/ AMExB/ AMExC
Profibus DP Operation instructions

Parameter 19 Starting speed in percent


[Startgeschwindigkeit in Prozent]
Running speed used to leave the start position.
Only effective if parameter 15 (proportional operation active) and parameter
1 (position transmitter) are not set to 0.

Default value: 50
minimum value: 0 (minimum starting speed)
maximum value: 100 (maximum starting speed)
Parameter 20 Start analogue 2 in 0.1 mA [Anfang Analog 2 in 0,1 mA]
Current value at which the measuring range of analogue 2 input (option)
begins.
This value must be smaller than the value in parameter 21
(end analogue 2 in 0.1 mA). If a sensor with a 4..20 mA signal is connected
to analogue 2, the value must be set to 40.

Default value: 0
minimum value: 0 (value for sensor with 0-20 mA output)
maximum value: 150
Parameter 21 End analogue 2 in 0.1 mA [Ende Analog 2 in 0,1 mA]
Current value at which the measuring range of analogue 2 input (option)
ends.
This value must be higher than the value in parameter 20
(start analogue 2 in 0.1 mA).

Default value: 200


minimum value: 50
maximum value: 200 (value for sensor with 0 20 mA or 4 20 mA output)
Parameter 22 "Coding analogue 2" [Kodierung Analog 2]
Default value: 0
0: 0 to 100 percent
1: 0 to 1000 per mil
2: 0 to 1023 (raw value of analogue-digital converter, not standardised)
Parameter 23 Start analogue 3/4 in 0.1 mA [Anfang Analog 3/4 in 0,1 mA]
Default value: 0
minimum value: 0 (value for sensor with 0 20 mA output)
maximum value: 150

Current value at which the measuring range of analogue 3/4 input begins.
This value must be smaller than the value in parameter 24
(end analogue 3/4).
If a sensor with a 4..20 mA signal is connected to analogue 3/4, the value
must be set to 40.
Parameter 24 End analogue 3/4 in 0.1 mA [Ende Analog 3/4 in 0.1 mA]
Default value: 200
minimum value: 50
maximum value: 200 (value for sensor with 0 20 mA or 4 20 mA output)

Current value at which the measuring range of analogue 3/4 input ends.
This value must exceed the value in parameter 23
(start analogue 3/4).
Parameter 25 Coding analogue 3/4 [Kodierung analog 3/4]
Default value: 0
0: 0 to 100 percent
1: 0 to 1000 per mil
2: 0 to 1023 (raw value of analogue-digital converter, not standardised)

26
Actuator controls AUMA MATIC AM/ AMExB/ AMExC
Operation instructions Profibus DP

The stepping mode increases the number of starts of the


actuator. It must be ensured that the maximum number of
starts will equally not be exceeded when operating in step-
ping mode.

Parameter 26 "Stepping direction OPEN active"


[Takt Richtung AUF aktiv]
This parameter is only effective if parameter 1 (position transmitter)
is not 0. Otherwise the parameter record will be rejected.

Default value: 0
0: Stepping mode in direction OPEN switched off
1: Stepping mode in direction OPEN switched on
Parameter 27 Stepping operating time OPEN in 0.1 s
[Takt Fahrzeit AUF in 0,1 s]
Stepping operating time direction OPEN in 0.1 s
This parameter is only effective if parameter 26 (stepping direction OPEN
active) is not 0.

Default value: 10
minimum value: 1 (actuator runs 0.1 s per stepping period)
maximum value: 36,000 (actuator runs 1 hour per stepping period)
Parameter 28 Stepping pause time OPEN in 0.1 s
[Takt Pausenzeit AUF in 0,1 s]
Stepping pause time direction OPEN in 0.1 s
This parameter is only effective if parameter 26 (stepping direction OPEN
active) is not 0.

Default value: 50
minimum value: 1 (actuator stationary 0.1 s per stepping period)
maximum value: 36,000 (actuator stationary 1 hour per stepping period)
Parameter 29 Stepping start OPEN in per mil
[Takt Anfang AUF in Promille]
Start of stepping distance in direction OPEN. Indication of position in per mil
This value must be smaller than the value in parameter 30 (stepping end
OPEN in per mil). Otherwise, the parameter record will be rejected. This
parameter is only effective if parameter 26 (stepping direction OPEN active)
is not 0.

Default value: 0
minimum value: 0 (stepping mode in direction OPEN begins at 0,
end position CLOSED)
maximum value: 999
Parameter 30 Stepping end OPEN in per mil [Takt Ende AUF in Promille]
End of stepping distance in direction OPEN. Indication of position in per mil
This value must be higher than the value in parameter 29 (stepping start OPEN
in per mil). Otherwise, the parameter record will be rejected. This parameter is
only effective if parameter 26 (stepping direction OPEN active) is not 0.

Default value: 1000


minimum value: 1
maximum value: 1000 (Stepping mode in direction OPEN ends at position
1000, end position OPEN)
Parameter 31 Stepping direction CLOSE active
[Takt Richtung ZU aktiv]
This parameter is only effective if parameter 1 (position transmitter) is not 0.
Otherwise, the parameter record will be rejected.

Default value: 0
0: Stepping mode in direction CLOSE switched off
1: Stepping mode in direction CLOSE switched on

27
Actuator controls AUMA MATIC AM/ AMExB/ AMExC
Profibus DP Operation instructions

Parameter 32 Stepping operating time CLOSE in 0.1 s


[Takt Fahrzeit ZU in 0,1 s]
Operating time for stepping mode in direction CLOSE. Indication in 0.1
seconds. This parameter is only effective if parameter 31 (stepping direction
CLOSE active) is not 0.

Default value: 10
minimum value: 1 (actuator runs 0.1 s per stepping period)
maximum value: 36000 (actuator runs 1 hour per stepping period)
Parameter 33 Stepping pause time CLOSE in 0.1 s
[Takt Pausenzeit ZU in 0,1 s]
Pause time for stepping mode in direction CLOSE. Indication in 0.1 seconds
This parameter is only effective if parameter 31 (stepping direction CLOSE
active) is not 0. Otherwise, the parameter record will be rejected.

Default value: 50
minimum value: 1 (actuator stationary 0.1 s per stepping period)
maximum value: 36,000 (actuator stationary 1 hour per stepping period)
Parameter 34 Stepping start CLOSE in per mil
[Takt Anfang ZU in Promille]
Default value: 1000
minimum value: 1
maximum value: 1000 (Stepping mode in direction CLOSE starts at
position 1000, end position OPEN)

Start of stepping distance in direction CLOSE.


Indication of position in per mil.
This value must be higher than the value in parameter 35 (stepping end
CLOSE in per mil). Otherwise, the parameter record will be rejected.
This parameter is only effective if parameter 31 (stepping direction CLOSE
active) is not 0.
Parameter 35 Stepping end CLOSE in per mil
[Takt Ende ZU in Promille]
End of stepping distance in direction CLOSE. Indication of position in per
mil.
This value must be higher than the value in parameter 34 (stepping start
CLOSE in per mil). This parameter is only effective if parameter 31 (stepping
direction CLOSE active) is not 0. Otherwise, the total parameter record will
be rejected.

Default value: 0
minimum value: 0 (stepping mode in direction CLOSE ends at position 0,
end position CLOSED)
maximum value: 999
Parameters 36 to 50 are spare parameters [Reserveparameter]
They are reserved for extensions.

Default value: 0
Value range: 0 to 65535

28
Actuator controls AUMA MATIC AM/ AMExB/ AMExC
Operation instructions Profibus DP

9. Process representation Via the process representation input, the master (controls) can read the
input state of the slave (actuator).
Grey bits are collective signals. They contain the results of a disjunction (OR
operation) of other information.

Byte1: Logical signals Byte 2: Actuator signals Byte 3: E2 Actual position Byte 4: E2 Actual position

Remote sw. position


CLOSED position
Setpoint reached
Running CLOSE

Local sw. position


Running OPEN

OPEN position
Warning ind.

Thermal fault
LSO (WOEL)
TSO (DOEL)

Mains failure
LSC (WSR)
TSC (DSR)
Fault ind.

--

Actual position (high byte) Actual position (low byte)


(position transmitter) (position transmitter)

Bit Bit Bit Bit Bit Bit Bit Bit Bit Bit Bit Bit Bit Bit Bit Bit
7 6 5 4 3 2 1 0 7 6 5 4 3 2 1 0

Byte 5: Fault signals Byte 6: Warning signals Byte 7: Physical operation Byte 8: Options
No reference operation

Loss of transm. signal

Rev.prev./ dead time


Start stepping mode
Failure 24 V supply
Torque fault CLOSE

Proport. operation
Selector not remote

Potentiometer fault
Torque fault OPEN

Operation pause
Remote CLOSE
Channel 2 active
Wrong command

Remote OPEN
Local CLOSE

Analog 3/4 loss


Hardware fault

Local OPEN

Analog 2 loss
Thermal fault
Mains failure

Dig. input 3
Dig. input 2
Dig. input 1
Dig. input 0
Clear state

--
--
--

--

--
Bit Bit Bit Bit Bit Bit Bit Bit Bit Bit Bit Bit Bit Bit Bit Bit Bit Bit Bit Bit Bit Bit Bit Bit Bit Bit Bit Bit Bit Bit Bit Bit
7 6 5 4 3 2 1 0 7 6 5 4 3 2 1 0 7 6 5 4 3 2 1 0 7 6 5 4 3 2 1 0

Byte 9: 1st analog input Byte 10: 1st analog input Byte 11: 2 analog input
nd
Byte12: 2nd analog input

High byte Low byte High byte Low byte


1st customer analog input 1st customer analog input nd
2 customer analog input
nd
2 customer analog input
(wiring diagram design. analog 2) (wiring diagram design. analog 2) (wiring diagram design. analog 3/4) (wiring diagram design. analog 3/4)

Byte13 Byte14 Byte15 Byte16

Spare Spare Spare Spare

To ensure that the actuator gives a correct end position


signal after power failure in end position CLOSED/ OPEN, we
recommend to evaluate the information LSC (WSR)/ LSO
(WOEL) (bit 5/4 in byte 2) for the end position signal
CLOSED/ OPEN.

29
Actuator controls AUMA MATIC AM/ AMExB/ AMExC
Profibus DP Operation instructions

9.1 Process representation input (default process representation)

Byte 1: Logical signals Bit Designation Value Description


Important signals from the ac- OPEN 1 Limit switch in direction OPEN operated.
tuator concerning errors, war- position
nings, operations: 0 Limit seating
in end positi- 0 other
on OPEN
CLOSED 1 Limit switch in direction CLOSE operated
position
Limit seating
in end positi- 0 other
on CLOSED
1 CLOSED po- Torque switch and limit switch in direction CLOSE
1
sition operated.
Torque sea-
ting in end
position 0 other
CLOSED
The setpoint is within max. error variable (outer dead
Setpoint 1 band). Signal occurs only if Profibus DP master has
2 set the Setpoint reached bit.
reached
0 other
1
3 (reserved for extensions)
0
Operation command (OPEN or SETPOINT) from Pro-
fibus DP in direction OPEN is executed. For operati-
Running 1 on in stepping mode, this signal is also active during
4 an off-time, the dead time, and the reversing preventi-
OPEN
on.
0 No operation is carried out via Profibus DP.
Operation command (CLOSE or SETPOINT) from
Profibus DP in direction CLOSE is executed. For ope-
Running 1 ration in stepping mode, this signal is also active du-
5 ring an off-time, the dead time, and the reversing pre-
CLOSE
vention.
0 No operation is carried out via Profibus DP.
One or several warnings have occurred.
1 Collective signal: Contains the result of a disjunction
(OR operation) of all bits of the byte Warning sig-
6 Warning ind. nals (page 33).
No warnings are active (all bits of the warnings can-
0
celled).
One or several faults have occurred so that the ac-
tuator can no longer be controlled via Profibus DP (at
least one bit set in fault byte).
1
Collective signal: Contains the result of a disjunction
7 Fault ind. (OR operation) of all bits of the byte Fault signals
(page 31 contd)
No faults are active (all bits are cancelled in fault
0
byte).

30
Actuator controls AUMA MATIC AM/ AMExB/ AMExC
Operation instructions Profibus DP

Byte 2: Actuator signals Bit Designation Value Description


Basic signals originating from
1 A thermal fault (motor protection) has occurred.
the logic 0 Thermal fault
0 No thermal fault has occurred.
1 A mains failure has occurred, e.g. phase error.
1 Mains failure
0 No mains failure has occurred.
Remote sw. 1 Selector switch in position REMOTE.
2
position 0 Selector switch not in position REMOTE.
Local sw. 1 Selector switch in position LOCAL.
3
position 0 Selector switch not in position LOCAL.
1 Limit switch OPEN left operated.
4 LSO (WOEL)
0 Limit switch OPEN left not operated.
1 Limit switch CLOSE right operated.
5 LSC (WSR)
0 Limit switch CLOSE right not operated.
1 Torque switch OPEN left operated (storing).
6 TSO (DOEL)
0 Torque switch OPEN left not operated.
1 Torque switch CLOSE right operated (storing).
7 TSC (DSR)
0 Torque switch CLOSE right not operated.

Byte 3: E2 Actual position (high byte) (position transmitter)


Byte 4: E2 Actual position (low byte) (position transmitter)

Bytes 3 and 4 are used to transmit the actual actuator position (requires
position transmitter within actuator). The actual position can be transmitted
either as a value between 0 100 (percent) or 0 1000 (per mil). For 0
100 (per cent), the consistency does not have to be regarded in the trans-
mission and only the low byte must be regarded. The change-over between
0 100 and 0 1000 is realised via a parameter in the GSD file (default
setting: transmission in 0 100 format).

Byte 5: Fault signals Bit Designation Value Description


The actuator is not ready for Indicates the fact that several operation commands
remote operation. As soon as were received simultaneously via Profibus DP (e.g. Re-
one of these signals is set, mote OPEN and Remote CLOSE simultaneously or Re-
Wrong com- 1
bit 7 of byte 1 will also be set) 0 mote CLOSE/ Remote OPEN and Remote SETPOINT
mand (nominal) simultaneously) or that the max. value for a
nominal position has been exceeded (setpoint > 1000).
0 Operation commands correct
Selector not 1 Selector switch: position LOCAL or OFF
1
remote 0 Selector switch: position REMOTE
Motor protection has tripped; remedy: resetting local
1 controls via selector switch position RESET after the
2 Thermal fault motor has cooled off.
0 other
1 Loss of one phase or incorrect phase sequence.
3 Mains failure
0 other
Torque fault OPEN occurred (only torque or torque be-
Torque fault 1 fore limit, according to type of seating); remedy: reset-
4 ting using counter command
CLOSE
0 other
Torque fault CLOSED occurred (only torque or torque
Torque fault 1 before limit, according to type of seating); remedy: re-
5 setting using counter command
OPEN
0 other

31
Actuator controls AUMA MATIC AM/ AMExB/ AMExC
Profibus DP Operation instructions

Bit Designation Value Description


1 Indicates that a telegram Global Control Clear was
sent via the Profibus DP (the bit can only be deleted
6 Clear state
0 with a telegram Global Control Operate). In this state,
the actuator can not be operated from REMOTE.
1
7 not assigned (reserved for extensions)
0

Byte 6: Warning signals Bit Designation Value Description


Warning signals serve only in- 1 Failure 24 V supply voltage.
Failure 24 V
formation purposes and do 0
supply 0 other
not interrupt or cancel an ope-
ration (as opposed to faults). Channel 2 1 Actuator uses channel 2 for communication.
As soon as one of these sig- 1
active 0 other
nals is set, bit 6 of byte 1 will
Signal interrupted at position transmitter RWG: For re-
be set simultaneously. Loss of 1 cognition purpose, parameter 1 must be set to value 3
2 transm. (RWG 4 20 mA).
signal
0 other
Potentiometer fault: in end position CLOSED a value
Potentio- 1 is measured being higher than the one in end position
3 OPEN.
meter fault
0 other
Hardware fault: If this bit is set, the Profibus board
Hardware 1
4 must be checked/ replaced.
fault
0 other
No reference operation: The values of the position
transmitter cannot be used as long as the reference
No reference 1 operation (end position OPEN, en position
5 CLOSED) has not been performed. A nominal ope-
operation
ration is not possible.
0 other
1
6 Not assigned (reserved for extensions)
0
1
7 Not assigned (reserved for extensions)
0

Byte 7: Physical operation Bit Designation Value Description


Reversing prevention/ dead time warning: The actuator
does not start as long as reversing prevention or dead
Rev.prev./ 1 time is still active. The bit is set if a run command is
0 available which cannot be executed immediately. The
dead time
bit is cancelled as soon as the actuator starts.
0 other
Proportional section reached (soft start or soft stop) ac-
tive. Only possible together with adjustable output
Proport. 1
1 speed actuators of the type ranges AS, ASR with
operation AUMA VARIOMATIC Profibus DP.
0 other
Operation 1 Operation pause
2
pause 0 other
Indicates that the actuator is within the stepping range
during active stepping mode. Conditions: position trans-
Start step- 1
3 mitter is provided, stepping mode is active, remote ope-
ping mode ration is being performed.
0 other

32
Actuator controls AUMA MATIC AM/ AMExB/ AMExC
Operation instructions Profibus DP

Remote operation via Profibus in direction OPEN (re-


mote operation bit for logic board set and movement of
Remote 1
4 potentiometer detected). Signalling of this bit requires a
OPEN position transmitter.
0 other
Remote operation via Profibus in direction CLOSE (re-
mote operation bit for logic board set and movement of
Remote 1
5 potentiometer detected). Signalling of this bit requires a
CLOSE position transmitter.
0 other
Actuator runs locally in direction OPEN (local controls
1 or handwheel).
6 Local OPEN Signalling of this bit requires a position transmitter.
0 other
Actuator runs locally in direction CLOSE (local controls
Local 1 or handwheel). Signalling of this bit requires a position
7 transmitter.
CLOSE
0 other

Byte 8: Options Bit Designation Value Description


Digital inputs and loss of
signal at analogue inputs 1 Digital input no. 1 = 1 (switch closed)
0 Dig. input 0
0 Digital input no. 1 = 0 (switch open)
1 Digital input no. 2 = 1 (switch closed)
1 Dig. input 1
0 Digital input no. 2 = 0 (switch open)
1 Digital input no. 3 = 1 (switch closed)
2 Dig. input 2
0 Digital input no. 3 = 0 (switch open)
1 Digital input no. 4 = 1 (switch closed)
3 Dig input 3
0 Digital input no. 4 = 0 (switch open)
1
4 not assigned (reserved for extensions)
0
Signal interrupted at analogue input 2 (first free analo-
Analog 2 1 gue input) i.e. the measured value is more than 0.2 mA
5 lower than the set minimum value.
loss
0 no signal interruption analogue input 2 detected
Signal interrupted at analogue input 3/4 (second free
Analog 3/4 1 analogue input) i.e. the measured value is more than
6 0.2 mA lower than the set minimum value.
loss
0 no signal interruption analogue input 3/4 detected
1
7 not assigned (reserved for extensions)
0

Byte 9: High byte first analogue customer input (wiring diagram designation analogue 2)
Byte 10: Low byte first analogue customer input (wiring diagram designation analogue 2)
The data content of bytes 9 and 10 depends on parameter 22; with the
default value (0 100 percent), only the low byte is used.

Byte 11: High byte second analogue customer input (wiring diagram designation analogue 3/4)
Byte 12: Low byte second analogue customer input (wiring diagram designation analogue 3/4)
The data content of bytes 11 and 12 depends on parameter 25; with the
default value (0 100 percent), only the low byte is used.

Byte 13 to 16: reserved for extensions

33
Actuator controls AUMA MATIC AM/ AMExB/ AMExC
Profibus DP Operation instructions

10. Process representation output


Via the process representation output, the master (controls) can control the
slave (actuator).

Byte 1: Command Byte 2: E3 Output speed Byte 3: E1 Setpoint Byte 4: E1 Setpoint


Remote SETPOINT

Remote CLOSE
Remote OPEN

Speed Setpoint position high byte Setpoint position low byte

Bit Bit Bit Bit Bit Bit Bit Bit


7 6 5 4 3 2 1 0

Byte 5 Byte 6 Byte 7 Byte 8

Spare Spare Spare Spare

In order to perform remote operations, the selector switch of


local controls must be set to Remote control.

Only one operation bit may be set at byte 1.


If several operation bits are set at the same time, the actuator stops and
signals the fault Wrong command.

10.1 Description of the output data

Byte 1: Commands Bit Designation Value Description


Bits 0 2 are used to transmit 1 Running OPEN
Remote
operation commands to ac- 0
OPEN 0 Not running OPEN
tuator. Only one of these bits
may be set at any given time. Remote 1 Running CLOSE
1
If Remote SETPOINT is set, CLOSED 0 Not running CLOSE
the value of the nominal positi- Running to setpoint
on (byte 3 and byte 4) is used. Remote 1 Can only be set if a position transmitter e.g. potentio-
Bits 3 7 are reserved for futu- 2 meter/ RWG (options) is available.
SETPOINT
re extensions and must re- 0 Not running to setpoint.
main set to 0.
1
3 -- Not assigned (reserved for extensions)
0
1
4 -- Not assigned (reserved for extensions)
0
1
5 -- Not assigned (reserved for extensions)
0
1
6 -- Not assigned (reserved for extensions)
0
1
7 -- Not assigned (reserved for extensions)
0

34
Actuator controls AUMA MATIC AM/ AMExB/ AMExC
Operation instructions Profibus DP

Byte 2: E3 Output speed: This byte is only effective in combination with variable output speed actua-
tors type AS and ASR.

Value range: 0..100:


Minimum output speed: 0 (actuator runs with min. set output speed)
Maximum output speed: 100 (actuator runs with max. set output speed)

Byte 3: E1 Setpoint (high byte)


Byte 4: E1 Setpoint (low byte)

The setpoint can be transmit- Byte 3: High Byte of setpoint position 0...1000
ted either as a value between
0 100 (percent) or 0 1000 Condition Value
(per mil). For the Parameter 2 (measured data
0 100 scaling, the consisten- This byte must be set to 0.
coding position transmitter) = 0
cy does not have to be consi-
dered in the transmission and Parameter 2 (measured data This byte indicates the low byte of the
coding position transmitter) = 1 setpoint (0...1000 per mil).
only the low byte must be eva-
luated. The change-over bet-
ween 0 100 and 0 1000 is
realised via a parameter in the Byte 4: Low Byte of setpoint position 0...100 or position 0...1000
GSD file via parameter 2
Measured data coding positi- Condition Value
on transmitter. According to Parameter 2 (measured data
this programming, different Setpoint position 0...100
coding position transmitter) = 0
maximum values apply. When Parameter 2 (measured data This byte indicates the low byte of the
these limits are exceeded, the coding position transmitter) = 1 setpoint (0...1000 per mil).
actuator stops and signals the
fault Wrong command.

Bytes 5 to 8: reserved for extensions, must be set to 0.

35
Actuator controls AUMA MATIC AM/ AMExB/ AMExC
Profibus DP Operation instructions

11. Description of actuator functions


11.1 Operation commands for OPEN/ CLOSE operation
Operation commands are determined by the operation command bits and
the nominal value (setpoint) of the Profibus process representation output.
Only one command bit may be set at any given time. If several command
bits are set, no operation is performed and the fault signal Wrong command
is given.
To avoid placing too much strain on the mechanics the actuator is equipped
with a (programmable) delay when changing direction (reversing preven-
tion).

The following operation command bits are required for OPEN/ CLOSE
operation:
Remote OPEN
Remote CLOSE

Remote operation OPEN/ STOP


Remote OPEN = 1 The actuator runs in direction OPEN.
Remote OPEN = 0 The actuator stops.
The actuator is switched off automatically if the end position OPEN (limit
switch LSO [WOEL] is reached.
Occurring faults (thermal failure, phase failure, torque failure) stop the
operation.

Remote operation CLOSE/ STOP


Remote CLOSED = 1 The actuator runs to position CLOSED.
Remote CLOSED = 0 The actuator stops.
The actuator is switched off automatically if the end position CLOSED is
reached (limit switch LSC [WSR] for limit seating or LSC [WSR] and TSC
[DSR] for torque seating). Occurring faults (thermal failure, phase failure,
torque failure) stop the operation.

Remote operation to setpoint position/ STOP

The positioner can only function if the actuator is equipped with a position
transmitter, e.g. potentiometer/ RWG (option).

Remote SETPOINT = 1 The actuator moves to the set nominal value.


Remote SETPOINT = 0 The actuator stops.
The setpoint must be indicated in % or in (depending on the AUMA user
parameter 2 Measured data coding position transmitter within the GSD
file).
Occurring faults (thermal failure, phase failure, torque failure) stop the
operation via the positioner.

With a setpoint of 0 % (0 ), the actuator runs to the end position CLOSED.


With a setpoint of 100 % (1000 ) the actuator runs to the end position
OPEN. In case the setpoint is more than 100 % (1000 ) , no operation is
performed and the fault signal Wrong command is given.

36
Actuator controls AUMA MATIC AM/ AMExB/ AMExC
Operation instructions Profibus DP

11.2 Positioner The positioner is activated via the bit Remote SETPOINT.
The positioner is a three-position-controller. Via the SETPOINT position in
the process representation input, the nominal value of the position is trans-
mitted cyclically to the actuator as nominal variable (cycle time = bus cycle
time DP). The positioner integrated in the actuator controls AUMA MATIC
provides the position signal for controlling the motor depending on the
nominal and actual position value. The feedback signal (actual value of
actuator position) is produced internally within the actuator.

The position transmitter compares the nominal value of the position set in
the controls to the locally measured actual value of the position. If the diffe-
rence between nominal value and actual value is higher than the max. error
(parameter 14), the positioner drives the motor, depending on the error,
either in direction OPEN or direction CLOSE.
Figure H: Modulating duty: nominal operation to 50 %

OPEN 100 %

51 %

50,5 %

Max.
Setpoint 50 % error
Overrun Setpoint reached =1%

49,5 %

49 %
Motor is switched off

CLOSED 0%
t

Overrun (inner dead band) The inner dead band determines the switching-off point of the actuator.
The tripping point in both directions can be set via the parameters 12 and
13 (page 24), so that the actuator stops as close as possible to the nominal
value.

Max. error (outer dead band)


The outer dead band determines the switching-on point of the actuator.
If the actual position or a change of the nominal value is higher than the max.
permissible error set with parameter 14 (page 25), the motor is started.

The parameter must be set sufficiently high to ensure a


stable function of the positioner. If the value is set too low,
the number of starts is likely to be increased Thus, the end
of the lifetime of the actuator and valve will be reached
sooner.

Dead time The dead time prevents the operation to a new nominal position within a
pre-determined time. The time can be between 0 and 1 minute and is set in
parameter 11.

The controls must ensure that the maximum number of


motor starts of the actuator is not exceeded. This can be
achieved by setting the parameter 11 to a sufficiently high
value.

For further information on the positioner, please refer to the operation


instructions pertaining to the actuator (multi-turn actuator SA(R).../ part-turn
actuator SG... with AUMA MATIC AM...).

37
Actuator controls AUMA MATIC AM/ AMExB/ AMExC
Profibus DP Operation instructions

11.3 Stepping mode Stepping mode requires a position transmitter (option).


The stepping mode lengthens the operating time for part of or for the whole
travel.

Setting operation and pause times


The operation and pause times (stepping times) in opening or closing direc-
tion are set with the parameters 27 to 33. An individual operation and pause
time can be set for each direction.

Indication of operation in stepping mode


The states of the operation in stepping mode are indicated by the bits 2 and
3 in byte 7 of the process representation output.

12. Failure function The failure function allows the start of failure operations in case of special
events, e.g. when the communication between the actuator and the master
is interrupted. This function is set with the parameters 6 to 10.

The failure function can only be set off when the watchdog function is acti-
vated within the master.

If the actuator is in the failure function, the set failure position is approached
via a failure operation.
If the actuator is then moved to another position (e.g. by manual operation),
it will try to perform the set failure action while the selector switch is in posi-
tion REMOTE.

To prevent a new approach to the failure position during


manual operation, the selector switch (local controls) must
be switched to position LOCAL or OFF before operating
the handwheel.

..
The following events can trigger the failure function:

The connection to the master is interrupted.


The master enters the Clear state and sends:

either a) global control telegrams with the content Clear.


or b) data telegrams with the length 0 (DP fail safe mode).

As soon as the cause for triggering the failure mode is eliminated (connec-
tion restored, master in Operate state), the operation commands from the
master can be executed again.

38
Actuator controls AUMA MATIC AM/ AMExB/ AMExC
Operation instructions Profibus DP

13. Description Profibus DP interface


Figure J: Profibus DP interface board
S1.2

Rotary switch S3
Rotary switch S2

S4

S1.1
X8 PROFIBUS X11 AI X10 AI

Table 8: Standard setting of Profibus DP interface board


S1.1 S1.2 S2 S3
V mA
AI 3 0 2
(with Potentiometer) (with RWG)

S1.1 When using the external analogue input X11 AI 3/4, the switch S1.1 must be
in position AI 3.
S1.2 Switch for setting the position feedback via position transmitter potentiome-
ters/ RWG (option).
S1.2 = V: If the actuator is equipped with a potentiometer without RWG, this
switch must be in position V.
S1.2 = mA: Switch may only be in this position if an RWG is installed in the
actuator.
If the actuator is equipped with an RWG (0- 20 mA or 4 20 mA), this
switch must be in position mA.

S2/S3 Rotary switches for Profibus address setting.


These two switches are used to set the address of the actuator within the
Profibus DP network. Only addresses from 0 to 125 may be allocated.

S2 Rotary switch for setting the unit digit.


S3 Rotary switch for setting the tens digit.

S4 Switch for setting the end position seating in end position CLOSED.
(In end position OPEN, switching off is always via limit seating)
This switch is used to inform the Profibus DP board about the type of
seating is to be used to operate the actuator in end position CLOSED (limit
seating or torque seating). The end position seating is set in the factory
according to the details given in the order.

The setting of the end position seating in end position


CLOSED must be the same on the Profibus DP board (switch
S4) and on the logic board (switch S1-2, figure J, page 42).

S4 = LIMIT: If the switch is in position LIMIT (left, no dot visible), the


actuator is in limit seating for end position CLOSED.

S4 = TORQUE: If the switch is in position TORQUE (right, dot visible), the


actuator is in torque seating for end position CLOSED.

39
Actuator controls AUMA MATIC AM/ AMExB/ AMExC
Profibus DP Operation instructions

13.1 Assignment of the customer inputs of the Profibus DP interface (option)

X7 spare This plug provides pins for 4 digital customer inputs.


Table 9: Digital inputs (galvanically isolated)

Pin Description
1 R1: digital input 1
2 R2: digital input 2
3 R3: digital input 3
4 R4: digital input 4
5 + 24 V
6 + 24 V

These signals are freely available inputs, which the micro-controller trans-
mits into the process representation input (byte 8, bits 0 3). The inputs are
galvanically isolated and internally connected to 0 V via pull-down resistors.
In an unconnected state, a logical zero is transmitted. To set an input to

.
logical one, 24 V DC must be applied (pins 5 or 6).

Proposed external wiring diagrams (appendix B of the


operation instructions) for these signals must be obser-

. ved.
The bounce time of the connected switches should not be
more than 1 ms.

X12 First analogue customer input (analogue 2).


An external 0/4- 20mA sensor for transmitting the measured values via the
Profibus can be connected to this input.
Table 10: Analogue inputs at plug X12 AI 2
Pin Description
1 AN 2: analogue signal 0 20 mA
2 GND (system ground)

X11 Second analogue customer input (analogue 3/4)


A 0/4-20mA sensor for transmitting the measured values via the Profibus
can be connected to this input.
Table 11: analogue inputs at plug X11 AI 3/4
Pin Description
1 + 24 V
2 GND (system ground)
3 GND (system ground)
4 AN 3+: analogue signal 0 20 mA (plus)
5 AN 4: analogue signal 0 20 mA (minus)
6 GND (system ground)

If the switch S1.1 is on the left side in position AI 3, the pin 5 (AN 4) is
connected to GND. Input AN 3 can be used in the same way as AN 2.
If the switch is on the right side in position AI 3-AI 4, a differential measure-

..
ment between AN 3 and AN 4 can be performed.

Potential-free differential measurement is not possible.

.. There is always a GND connection.


Proposed external wiring diagrams (appendix B) observed.
The inputs AN2, AN3, and AN4 do not have galvanic isola-
tion via opto-isolator. The maximum load of the 24 V
through the sensors must not exceed 40 mA.

40
Actuator controls AUMA MATIC AM/ AMExB/ AMExC
Operation instructions Profibus DP

13.2 Assignment Profibus DP connection

X8 PROFIBUS The bus signals and the galvanically isolated voltage supply for the bus
termination, as well as the bus termination resistors located on the Profibus
DP board are connected on this plug.
Table 12: Plug assignment X8

Pin Description
1 Channel 1: B cable bus termination
2 Channel 1: A cable bus termination
3 Channel 2: A cable Profibus (redundant channel)
4 Channel 2: A cable Profibus (redundant channel)
5 GND float (Profibus ground)
6 + 5 V float (Profibus + 5 V)

13.3 Assignment positioner connections

X10 AI 1 The signals required for the position transmitter potentiometer/ potentio-
meter with RWG are connected on this plug.
Table 13: Plug assignment X10 AI 1
Pin Description
1 + 5 V for potentiometer
2 AN 1: analogue signal from position transmitter
3 GND (system ground)
4 + 24V for RWG

41
Actuator controls AUMA MATIC AM/ AMExB/ AMExC
Profibus DP Operation instructions

13.4 Checking/ setting the switches on the logic board

The settings on the logic board are already made in the factory, according to
the order details.
The logic board is located below the Profibus DP board.

Figure K : Logic board


S3-2:
Switching-off in end position OPEN.
Switch position has no influence.
When controlling via Profibus DP,
switching-off is always realised by
limit seating in end position OPEN

S3-2

S2-2

Position1:
S1-2
Switching-off by limit seating in end
position CLOSED

Position 2:
Switching-off by torque seating in
end position CLOSED

The setting of the end position seating in end position


CLOSED must be the same on the Profibus DP board (switch
S4, figure H, page 39) and on the logic board (switch S1-2).

Table 14

DIP switch S2-2 Programming


(ON = pressed)
Direction CLOSE Direction OPEN
Self-retaining REMOTE
Self-retaining REMOTE
may not be used

Push-to-run operation REMOTE

Self-retaining LOCAL

Push-to-run operation LOCAL

Blinker transmitter must Blinker transmitter


be deactivated! deactivated
Blinker transmitter (option)

Torque error: torque switch trip- included not included


ping (in mid-travel) contained in
collective fault signal (insignificant
for fieldbus interface)

42
Actuator controls AUMA MATIC AM/ AMExB/ AMExC
Operation instructions Profibus DP

14. Troubleshooting and corrective actions

14.1 Optical signals during operation

Figure L: Profibus DP interface board


V1 V2 V3 V4 S1.2 S1.1 V8 V7 V6 V5

LED SYSTEM OK (V1) This LED shows the correct voltage supply to the Profibus DP board.
Is continuously illuminated: Voltage supply connected to Profibus interface.
Is blinking: No Eprom used or Eprom defective.
Is not illuminated: No voltage at the DP interface.

LED (V2) This LED indicates a run command in direction OPEN.


Is continuously illuminated: Run command in direction OPEN is executed.
Is not illuminated: No run command in direction OPEN active.

LED (V3) This LED indicates a run command in direction CLOSE.


Is continuously illuminated: Run command in direction CLOSE is being
executed.
Is not illuminated: No run command in direction CLOSE active.

LED LocErr (V5) This LED indicates local faults in the actuator.
A fault with higher blinking frequency prevails over a fault with lower blinking
frequency.

Blinking once: TH fault (Thermal fault) actuator has stopped,


motor overheating (motor protection).

Blinking 2 times: STE fault (electrical fault)


phase failure

Blinking 3 times: TSO (DOEL) fault (torque switch opening left)


Unexpected torque in direction OPEN.

Blinking 4 times: TSC (DSR) fault (torque switch closing right)


Unexpected torque in direction CLOSE.

Blinking 5 times: Supply voltage failure (24V)


Supply voltage of Profibus DP board
is higher than 30 V or smaller than 18 V.

Blinking 6 times: Slave is in CLEAR state

43
Actuator controls AUMA MATIC AM/ AMExB/ AMExC
Profibus DP Operation instructions

LED Data Ex (V8) When LED is illuminated, the Profibus DP board has entered the Data
Exchange state. Only in this state, the actuator can be controlled by the DP
master and the state of actuator can be read.

LED State (V7) Is illuminated or not illuminated: Profibus DP board is not operational
Blinking once: Program on the Profibus DP board is being
executed.
Blinking twice: Actuator is in failure mode.

Regular blinking of the LED during operation indicates correct operation of


the DP board.

LED BusErr (V6) This LED shows bus related faults.


A fault with higher blinking frequency prevails over a fault with lower
blinking frequency, continuous illumination covers all blinking signals.

Is continuously illuminated: setting of invalid address (higher than 125).


Blinking once: No baud rate on bus.
Blinking twice: Incorrect parameter data.
Blinking 3 times: Incorrect configuration data.

44
Actuator controls AUMA MATIC AM/ AMExB/ AMExC
Operation instructions Profibus DP

14.2 Actuator can not be controlled via Profibus DP

Actuator cannot be controlled


via Profibus DP

LED SYSTEM OK (V1) ?

continuously
illuminated is blinking is not illuminated

Profibus DP board Profibus DP board not


defective supplied with voltage

Yes EPROM No Yes Operation No


installed on via local controls
board? possible?

Exchange Install Exchange Check voltage supply


Profibus DP Profibus DP Profibus DP of AUMA MATIC
board Eprom board Check fuses

Voltage supply of
Profibus DP
board correct

45
Actuator controls AUMA MATIC AM/ AMExB/ AMExC
Profibus DP Operation instructions

Voltage supply of
Profibus DP
board correct

Yes LED DataEx No


illuminated
(V8)?

Profibus DP Profibus DP slave not


communication in Data Exchange mode
correct

LED Bus Err (V6) ?

blinking blinking blinking continuously not


once twice three times illuminated illuminated

Incorrect parameter Incorrect Master only functions


No baud rate Address on slave
data. Correct configuration data. on level 2. Does not
found set > 125
parameter in master Correct configuration try to program or
in master configure

- Check master
Check Profibus DP
- Check wiring
master
- Check bus connection

46
Actuator controls AUMA MATIC AM/ AMExB/ AMExC
Operation instructions Profibus DP

Profibus DP
communication
correct

blinking once LED blinking twice


State (V7)
?

Slave is in
failure mode 1)

LED LocErr (V5) ?

blinking blinking blinking blinking blinking blinking


is not
once twice three times four times five times six times
illuminated

STE-fault: TSO fault: TSC fault: Voltage Slave is in


Thermo fault:
power failure/ Torque in Torque in under 18V or CLEAR state
Motor overheating
overcurrent direction OPEN direction CLOSE over 30V

Let motor cool Check mains Eliminate cause Eliminate cause Check supply Check all other programmed
off. Eliminate connection of torque fault of torque fault voltage. Poss. slaves at the Profibus.
cause of .exchange power If necessary, switch off Auto-
overheating supply unit clear function in master.

Profibus DP
board does not
signal any fault

Yes Operation No
via local controls
possible?

LED Check
Yes or No logic board
illuminated? motor controls
motor

Check Profibus DP No operation


board command issued
Check logic board by master

Check programming
of controls

1) see setting of AUMA user parameters 6, 7, 8, 9, and 10

47
Actuator controls AUMA MATIC AM/ AMExB/ AMExC
Profibus DP Operation instructions

.
14.3 Position feedback does not function
Check, whether the voltage at plug (X10 AI1) on the Profibus DP board,
pin 3 (-) and pin 2 (+) rises linearly when operating to OPEN position and
falls linearly when operating to CLOSED position.
The value for position CLOSED should be within the range 0 to 2 V. The
value for position OPEN should be within the range 3 to 5 V. The voltage
difference between CLOSED and OPEN should be more than 3V.

14.4 Actuator is not switched off by the limit switch in direction CLOSE

.
The actuator is set to torque seating.
Set actuator to limit seating:

.
Set switch S4 (see figure H, page 39) on the Profibus DP board to
position LIMIT.
Set switch S1-2 on the logic board (see page 42) to position 1.

.
14.5 Actuator stops immediately after start
Set switch S2-2 (blinker transmitter) on the logic board to position ON.

14.6 Measuring the Profibus signals using an oscilloscope

On the Profibus board, the signal from Profibus channel 1 on plug


(X8 Profibus, refer to page 41) pin 1 (P/B) and pin 2 (N/A) can be checked
using a digital oscilloscope.
The off-load voltage between pin 1 (+) and pin 2 (-) must be positive and
within the range of 0.8 V and 1.4 V.

Example for correct Profibus signal:

Example for incorrect Profibus Signal


(Bus only terminated on one side):

48
Actuator controls AUMA MATIC AM/ AMExB/ AMExC
Operation instructions Profibus DP

15. Appendix A Standard wiring diagram Legend page 50


Original wiring diagram and legend are delivered together with the actuator.

49
Actuator controls AUMA MATIC AM/ AMExB/ AMExC
Profibus DP Operation instructions

15.1 Legend for standard wiring diagram

S1 TSC Torque switch, closing, clockwise rotation


TSO
S2 Torque switch, opening, counterclockwise rotation
(DOEL)
LSC
S3 Limit switch, closing, clockwise rotation
(WSR)
LSO
S4 Limit switch, opening, counterclockwise rotation
(WOEL)
R2 Potentiometer
F1 Th Thermoswitch (motor protection)
R1 H Heater
A 1.8 Profibus DP board
A2 Logic board
A8 Power supply board
A 13 Bus connection board
A 20 Signal and control board
F 1, F 2 Primary fuses for power supply unit
F 3, F 4 Secondary fuses
H1 Indication light end position CLOSED
H2 Indication light end position OPEN
H3 Indication light FAULT
K 1, K 2 Reversing contactors
K 3, K4 Control relays for reversing contactors
S 11 Selector switch LOCAL OFF REMOTE
S 12.1 Push button OPEN
S 12.2 Push button STOP
S 12.3 Push button CLOSE

15.2 Additional information to the wiring diagram legend

Information B:
Local controls
Information F:
Power supply board
Information H:
Profibus DP board

50
Actuator controls AUMA MATIC AM/ AMExB/ AMExC
Operation instructions Profibus DP

16. Appendix B Proposed external wiring diagram


Digital and analogue inputs are optional.

The two customer analogue connections (AI 3/4 and AI 2) as well as the
four digital customer inputs (Dig 1 ...4) are only provided (wired) by the
factory if explicitly mentioned on the order.
The 5th digit of the MSP number (refer to name plate) indicates if analogue
connections are available.
If the 5th digit is assigned to 0, no external connections are available.
If the 5th digit is assigned to L, the connections are provided.

Connection of external sensors, 2-wire technology

51
Actuator controls AUMA MATIC AM/ AMExB/ AMExC
Profibus DP Operation instructions

Connection of external sensors, 3-wire technology

52
Actuator controls AUMA MATIC AM/ AMExB/ AMExC
Operation instructions Profibus DP

Connection of external sensors, 4-wire technology

53
Actuator controls AUMA MATIC AM/ AMExB/ AMExC
Profibus DP Operation instructions

17. Appendix C GSD file GSD [Gertestammdatei] stands for device master file. GSD is the so-called
device data sheet for Profibus devices. The GSD file, supplied by AUMA,
contains a description of the Profibus DP interface. The descriptions and
characteristics contained within the GSD file facilitate easy configuration of
the actuator controls.

The GSD file can be downloaded from Internet


www.auma.com

18. Appendix D Literature references


1. As an introduction into Profibus DP:
Manfred Popp: Profibus DP, Grundlagen, Tips und Tricks fr Anwender.
Hthig Verlag, ISBN 3-7785-2676-6

2. Guidelines for the electrician:


Aufbaurichtlinien Profibus DP/FMS Order No. 2.111
Available from:
Profibus Nutzerorganisation Haid-und Neu-Str. 7
D-76131 Karlsruhe
Phone +49-721 / 96 58 590
Fax +49-721 / 96 58 589
Http:/ www.profibus.com

19. Appendix E Connecting the cable shield for the AUMA MATIC AMExB/ AMExC 01.1
The shield of the fieldbus cable should be largely connected with the
respective threads.

Recommended threads e.g. WAZU-EMV/EX supplied by Hugro


(refer to www.hugro-gmbh.de).

54
Actuator controls AUMA MATIC AM/ AMExB/ AMExC
Operation instructions Profibus DP

Index
A N
Actuator functions 36 Name plate 15 Parking frame 15
AUMA plug/ socket connector 10 Part-turn actuators 10
O
Phase failure 36
B Operating time 38
Plug/ socket connector 10,15 - 16
Basic functions 6 Output speed E3 35
Position transmitter 36
Basic signals 31 Overrun 24,37
Positioner 36 - 37
Blinker transmitter 42 Overvoltage protection 13
Power supply 11
Bus access 6
P Process representation 29,34
Bus cable 18 - 19
Parameter Programming 21
Bus connection 18
Coding 26 Protective functions 6
C Coding analogue 3/4 26 Push-to-run operation 42
Cable capacity 19 Dead time positioner 24 R
Cable type 19 Delay time for
Redundancy 23
Characteristic impedance 19 failure operation 23
Remote operation 34
Collective fault signal 42 End analogue 26
Remote position transmitter RWG 14
Commissioning 21 End analogue 3/4 in 0.1 mA 26
Reversing contactors 10
Communication 6 Failure behaviour 23
RWG 36
Connection board 10,12 Failure operation 23
Controls 10 Failure position 24 S
Core cross section (bus cable) 19 Max. error 25 Safety instructions 4
Core diameter (bus cable) 19 Measured data code 22 Screening (bus cable) 19
Corrosion protection 5 Output speed Selector switch 10
failure operation 24 Self-retaining 42
D
Overrun direction CLOSE 24 Setpoint 22
Dead band 30,37
Overrun direction OPEN 24 Signals 30,43
Dead time 30,37
Position transmitter 22 Soft start 25
Device types 6
Proportional operation active 25 Soft stop 25
E Proportional range Start 25 Stepping mode 27,38
Electrical connection 4,11 Proportional range Stop 25 Storage 5
End position seating 39 Redundancy 23 Switching off 39,42
Error 30,43 Reversing prevention 22 Switching-off point 37
Error variable 30 Start analogue 26
T
Start analogue 3/4 in 0.1 mA 26
F Technical data 7 - 9,16
Starting speed 26
Failure function 38 Termination resistors 10,12
Stepping 27
Fault signals 31 Thyristors 10
Stepping direction
Functionality 6 Torque switching 14
CLOSE active 27
Transfer mode 6
G Stepping end CLOSE
Transport 5
GSD file 54 in per mil 28
Trouble shooting and
Stepping end OPEN in per mil27
H corrective actions 43
Stepping operating time
Handwheel 38 CLOSE in 0.1 s 28 U
I Stepping operating time User parameter 22
Indication lights 10 OPEN in 0.1 s 27
W
Stepping pause time CLOSE
L in 0.1 s 28 Wall bracket 14
Limit seating 30 Stepping pause time OPEN Warning signals 32
Literature 54 in 0.1 s 27 Warnings 4,30
Local controls 10 Stepping start CLOSE Wiring diagram 49
Loop resistance 19 in per mil 28
M Stepping start OPEN
Maintenance 4 in per mil 27
Measuring the Profibus signals 48 Stop speed 25
Motor connection 17 Time for channel changing 23
Motor protection 31

Informationen also available Wiring diagram, GSD file, test records and further actuator information can
on the Internet: be downloaded directly from the Internet by entering the order no. or Com.
No. (see name plate).
Our website: http://www.auma.com

55
INDUSTRA Suplibarca
Europe AUMA (Schweiz) AG
CH-8965 Berikon PT-2710-297 Sintra VE- Maracaibo Estado, Zulia
AUMA Riester GmbH & Co. KG Tel +41 566 400945 Tel +351 2 1910 95 00 Tel +58 261 7 555 667
Factory Mllheim Fax +41 566 400948 Fax +351 2 1910 95 99 Fax +58 261 7 532 259
RettichP.ch@auma.com jpalhares@tyco-valves.com suplibarca@intercable.net.ve
DE-79373 Mllheim
Tel +49 7631 809 - 0 AUMA Servopohony spol. s.r.o. MEGA Endstri Kontrol Sistemieri Tic. Ltd. Sti.
Fax +49 7631 809 - 250 CZ-10200 Praha 10 TR-06460 vecler Ankara Asia
riester@auma.com Tel +420 272 700056 Tel +90 312 472 62 70 AUMA (INDIA) PRIVATE LIMITED
www.auma.com Fax +420 272 704125 Fax +90 312 472 62 74 IN-560 058 Bangalore
Factory Ostfildern-Nellingen auma-s@auma.cz megaendustri@megaendustri.com.tr Tel +91 80 2839 4655
DE-73747 Ostfildern OY AUMATOR AB Fax +91 80 2839 2809
Tel +49 711 34803 - 0 FI-02270 Espoo
Africa info@auma.co.in
Fax +49 711 34803 - 34 Tel +35 895 84022 AUMA South Africa (Pty) Ltd. www.auma.co.in
riester@wof.auma.com Fax +35 895 8402300 ZA-1560 Springs AUMA JAPAN Co., Ltd.
Service Centre Cologne auma@aumator.fi Tel +27 11 3632880 JP-210-0848 Kawasaki-ku, Kawasa-
DE-50858 Kln AUMA France Fax +27 11 8185248 ki-shi Kanagawa
Tel +49 2234 20379 - 00 FR-95157 Taverny Cdex aumasa@mweb.co.za Tel +81 44 329 1061
Fax +49 2234 20379 - 99 Tel +33 1 39327272 www.auma.co.za Fax +81 44 366 2472
Service@sck.auma.com Fax +33 1 39321755 A.T.E.C. mailbox@auma.co.jp
Service Centre Magdeburg stephanie.vatin@auma.fr EG- Cairo AUMA ACTUATORS (Singapore) Pte Ltd.
DE-39167 Niederndodeleben www.auma.fr Tel +20 2 3599680 - 3590861 SG-569551 Singapore
Tel +49 39204 759 - 0 AUMA ACTUATORS Ltd. Fax +20 2 3586621 Tel +65 6 4818750
Fax +49 39204 759 - 19 GB- Clevedon North Somerset BS21 6QH atec@intouch.com Fax +65 6 4818269
Service@scm.auma.com Tel +44 1275 871141 sales@auma.com.sg
Service Centre Bavaria Fax +44 1275 875492
America www.auma.com.sg
DE-85748 Garching-Hochbrck mail@auma.co.uk AUMA ACTUATORS INC. AUMA Middle East Rep. Office
Tel +49 89 329885 - 0 AUMA ITALIANA S.r.l. US-PA 15317 Canonsburg AE- Dubai
Fax +49 89 329885 - 18 IT-20023 Cerro Maggiore Milano Tel +1 724-743-AUMA (2862) Tel +971 4 3682720
Riester@scb.auma.com Tel +39 0331-51351 Fax +1 724-743-4711 Fax +971 4 3682721
Fax +39 0331-517606 mailbox@auma-usa.com auma@emirates.net.ae
North Office, Ship building sector
info@auma.it www.auma-usa.com PERFECT CONTROLS Ltd.
DE-21079 Hamburg
Tel +49 40 791 40285 www.auma.it AUMA Chile Respresentative Office HK- Tsuen Wan, Kowloon
Fax +49 40 791 40286 AUMA BENELUX B.V. CL- La Reina Santiago de Chile Tel +852 2493 7726
Stephan.Dierks@auma.com NL-2314 XT Leiden Tel +56 2 8214108 Fax +852 2416 3763
Tel +31 71 581 40 40 Fax +56 2 2778478 joeip@perfectcontrols.com.hk
North Office, Industry
Fax +31 71 581 40 49 aumachile@adsl.tie.cl DW Controls Co., Ltd.
DE-29664 Walsrode
Tel +49 5167 504 office@benelux.auma.com LOOP S. A. KR-153-803 Seoul Korea
Fax +49 5167 565 AUMA Polska AR-C1140ABP Buenos Aires Tel +82 2 2113 1100
Erwin.Handwerker@auma.com PL-41-310 Dabrowa Grnicza Tel +54 11 4307 2141 Fax +82 2 2113 1088/1089
Tel +48 32 26156 68 Fax +54 11 4307 8612 sichoi@actuatorbank.com
East Office
Fax +48 32 26148 23 contacto@loopsa.com.ar www.actuatorbank.com
DE-39167 Niederndodeleben
Tel +49 39204 75980 R.Ludzien@auma.com.pl Asvotec Termoindustrial Ltda. AL-ARFAJ Eng. Company W. L. L.
Fax +49 39204 75989 www.auma.com.pl BR-13190-000 Monte Mor/ SP. KW-22004 Salmiyah
Claus.Zander@auma.com AUMA Priwody OOO Tel +55 19 3879 8735 Tel +965 4817448
RU-141400 Moscow region Fax +55 19 3879 8738 Fax +965 4817442
West Office
Tel +7 095 221 64 28 atuador.auma@asvotec.com.br arfaj@qualitynet.net
DE-45549 Sprockhvel
Tel +49 2339 9212 - 0 Fax +7 095 221 64 38 TROY-ONTOR Inc. BEHZAD Trading Enterprises
Fax +49 2339 9212 - 15 aumarussia@auma.ru CA-L4N 5E9 Barrie Ontario QA- Doha
Karlheinz.Spoede@auma.com www.auma.ru Tel +1 705 721-8246 Tel +974 4433 236
ERICHS ARMATUR AB Fax +1 705 721-5851 Fax +974 4433 237
SoutheWest Office
SE-20039 Malm troy-ontor@troy-ontor.ca behzad@qatar.net.qa
DE-69488 Birkenau
Tel +49 6201 373149 Tel +46 40 311550 MAN Ferrostaal de Colombia Ltda. Sunny Valves and Intertrade Corp. Ltd.
Fax +49 6201 373150 Fax +46 40 945515 CO- Bogot D.C. TH-10120 Yannawa Bangkok
Dieter.Wagner@auma.com info@erichsarmatur.se Tel +57 1 4 011 300 Tel +66 2 2400656
www.erichsarmatur.se Fax +57 1 4 131 806 Fax +66 2 2401095
Wrttemberg Office
GRNBECH & SNNER A/S dorian.hernandez@manferrostaal.com sunnyvalves@inet.co.th
DE-73747 Ostfildern
Tel +49 711 34803 80 DK-2450 Kbenhavn SV www.manferrostaal.com Top Advance Enterprises Ltd.
Fax +49 711 34803 81 Tel +45 33 26 63 00 PROCONTIC Procesos y Control Automtico TW- Jhonghe City Taipei Hsien (235)
Siegfried.Koegler@wof.auma.com Fax +45 33 26 63 21 EC- Quito Tel +886 2 2225 1718
GS@g-s.dk Tel +593 2 292 0431 Fax +886 2 8228 1975
Baden Office
www.g-s.dk Fax +593 2 292 2343 support@auma-taiwan.com.tw
DE-76764 Rheinzabern www.auma-taiwan.com.tw
Tel +49 7272 76 07 - 23 IBEROPLAN S.A. info@procontic.com.ec
Fax +49 7272 76 07 - 24 ES-28027 Madrid IESS DE MEXICO S. A. de C. V. AUMA Beijing Representative Office
Wolfgang.Schulz@auma.com Tel +34 91 3717130 MX-C.P. 02900 Mexico D.F. CN-100029 Beijing
Fax +34 91 7427126 Tel +52 55 55 561 701 Tel +86 10 8225 3933
Power plant sector
iberoplan@iberoplan.com Fax +52 55 53 563 337 Fax +86 10 8225 2496
DE-79373 Mllheim mailbox@auma-china.com
Tel +49 7631 809 192 D. G. Bellos & Co. O.E. informes@iess.com.mx
GR-13671 Acharnai Athens Multi-Valve Latin America S. A. www.auma-china.com
Fax +49 7631 809 294
Tel +30 210 2409485 PE- San Isidro Lima 27
Klaus.Wilhelm@auma.com
Fax +30 210 2409486 Tel +511 222 1313 Australia
Bro Bavaria
info@dgbellos.gr Fax +511 222 1880 BARRON GJM Pty. Ltd.
DE-93356 Teugn/Niederbayern
Tel +49 9405 9410 24 SIGURD SRUM A. S. multivalve@terra.com.pe AU-NSW 1570 Artarmon
Fax +49 9405 9410 25 NO-1301 Sandvika PASSCO Inc. Tel +61 294361088
Mathias.Jochum@auma.com Tel +47 67572600 PR-00936-4153 San Juan Fax +61 294393413
Fax +47 67572610 Tel +18 09 78 77 20 87 85 info@barron.com.au
AUMA Armaturenantriebe GmbH www.barron.com.au
post@sigurd-sorum.no Fax +18 09 78 77 31 72 77
AT-2512 Tribuswinkel
Tel +43 2252 82540 Passco@prtc.net
Fax +43 2252 8254050 2005-04-11
office@auma.at

AUMA Riester GmbH & Co. KG AUMA Riester GmbH & Co. KG
ISO 9001
P. O. Box 1362 P. O. Box 1151 ISO 14001
D - 79373 Mllheim D - 73747 Ostfildern
Certificate Registration No.
Tel +49 (0)7631/809-0 Tel +49 (0)711 / 34803 0 12 100 4269
Fax +49 (0)7631/809 250 Fax +49 (0)711 / 34803 34 12 104 4269
riester@auma.com riester@wof.auma.com
www.auma.com www.auma.com

For detailed information about AUMA products, please refer to the Internet:
www.auma.com Y000.421/003/en/1.05

You might also like