Fault Level At 33 Base(100)÷(Xs+St)=
11 side 321.85
12 Total Fault Current At
33KV Side
5.63KA
Alternative-2
Sr. No. Description Voltage Amps MVA Qty. Remarks
220KV
1 System Voltage
8.737KA 3329.1 PU Rectance=Base
2 Fault Level MVA MVA÷Fualt MVA
PU Reactance of Considering 100MVA Xs=100÷3329.1
System (Xs) Base
3 0.003
4 N0. of the transformer 2
5 Rating of each trans. 220/33KV 42/280A 50 MVA
% Impedance.of 11.82% cosidering 90% i.e. 10.638%
6 each trafo.
Fault rating of each 1.233/ 470MVA PU Rectance=Base
7 transfo. 220/33 Kv 8.22KA MVA÷Fualt MVA
Xs=100÷470
PU Reactance of Considering 100MVA
Each Trafo. Base
8 0.212
PU Reactance of Considering 100MVA
Each Trafo. Base
8 0.212
Total PU Reactance PU Rectance=Base
9 of Trafo (Xt) 0.10638 MVA÷Fualt MVA
Total PU Impedance 0.13638 Xs=100÷(2x470)
10 ( Xs+Xt)
Fault Level At 33 Base(100)÷(Xs+St)=
11 side 733.24 Fault Current=Base
12 Fault Current At 33 MVA÷Total PU
KV Side
12.83KA Impdance
Alternative-3
Sr. No. Description Voltage Amps MVA Qty. Remarks
220KV
1 System Voltage
8.737KA 3329.1 PU Rectance=Base
2 Fault Level MVA MVA÷Fualt MVA
PU Reactance of Considering 100MVA Xs=100÷3329.1
3 System (Xs) Base 0.003
4 N0. of the transformer 2
5 Rating of each trans. 220/33KV 183.7/1224 70 MVA
% Impedance.of 12.52% cosidering 90% i.e. 11.268% PU Rectance=Base
6 each trafo. MVA÷Fualt MVA
Fault rating of each 1.63/ 621.22 MVA Xs=100÷621.22
7 transfo. 220/33 Kv 10.868KA