19 c* 2.5 sq
1 mm 1.8 0.9 3.6 5 18 0.3 18.6 1.555 21.71 1.4 24.51
19 c* 2.5 sq
mm 1.8 0.9 3.6 5 18 0.3 18.6 1.645 21.89 1.4 24.69
12C
2 *2.5sqmm 1.8 0.9 3.6 4.16 14.976 0.3 15.576 1.555 18.686 1.4 21.486
12C
*2.5sqmm 1.8 0.9 3.6 4.16 14.976 0.3 15.576 1.645 18.866 1.4 21.666
10C *
3 2.5sqmm 1.8 0.9 3.6 4 14.4 0.3 15 1.555 18.11 1.4 20.91
10C *
2.5sqmm 1.8 0.9 3.6 4 14.4 0.3 15 1.645 18.29 1.4 21.09
7C *
4 2.5sqmm 1.8 0.9 3.6 3 10.8 0.3 11.4 1.36 14.12 1.24 16.6
7C *
2.5sqmm 1.8 0.9 3.6 3 10.8 0.3 11.4 1.44 14.28 1.24 16.76
4C *
5 2.5sqmm 1.8 0.9 3.6 2.42 8.712 0.3 9.312 1.36 12.032 1.24 14.512
4C *
2.5sqmm 1.8 0.9 3.6 2.42 8.712 0.3 9.312 1.44 12.192 1.24 14.672
2C *
6 2.5sqmm 1.8 0.9 3.6 2 7.2 0.3 7.8 1.36 10.52 1.24 13
2C *
2.5sqmm 1.8 0.9 3.6 2 7.2 0.3 7.8 1.44 10.68 1.24 13.16
8 3.6 1 5.6 2.42 13.552 0.3 14.152 1.555 17.262 1.56 20.382
4C * 10sqmm 3.6 1 5.6 2.42 13.552 0.3 14.152 1.645 17.442 1.56 20.562
4.5 1 6.5 2.42 15.73 0.4 16.53 1.555 19.64 1.72 23.08
9 4C * 16sqmm 4.5 1 6.5 2.42 15.73 0.4 16.53 1.645 19.82 1.72 23.26
LT XLPE single core
1C * 120
10 sqmm 12.4 1.5 15.4
3.5 core XLPE cable.
3.5C *
11 300sqmm
Diameter calculations for Cable
Thickness Thickness
Core dia of Core dia of of of Dia with Thickness Dia with Thickness
Sr. Cable phase Nuetral insulation insulation K factor & of Inner innersheat Dia of Dia with of outer Overall
No size conductor conductor Total Dia Of phase Of Nuetral Insulation sheath h armoured armoured sheath diameter
3.5 c*
300 sq
mm 19.5 13.8 43.7415 1.8 1.4 50.1415 0.6 51.3415 1.4 54.1415 2.36 58.8615
3.5 c*
300 sq
mm 19.5 13.8 43.7415 1.8 1.4 50.1415 0.6 51.3415 1.4 54.1415 2.36 58.8615
1
3.5 c*
300 sq
mm 19.5 13.8 43.7415 1.8 1.4 50.1415 0.6 51.3415 0.72 52.7815 2.2 57.1815
3.5 c*
300 sq
mm 19.5 13.8 43.7415 1.8 1.4 50.1415 0.6 51.3415 0.88 53.1015 2.2 57.5015
3.5 c*
240 sq
mm 17.5 9.4 37.4495 1.7 1.1 43.0495 0.5 44.0495 1.4 46.8495 2.04 50.9295
3.5 c*
240 sq
mm 17.5 9.4 37.4495 1.7 1.1 43.0495 0.5 44.0495 1.4 46.8495 2.04 50.9295
2
3.5 c*
240 sq
mm 17.5 9.4 37.4495 1.7 1.1 43.0495 0.5 44.0495 0.72 45.4895 2.04 49.5695
3.5 c*
240 sq
mm 17.5 9.4 37.4495 1.7 1.1 43.0495 0.5 44.0495 0.88 45.8095 2.04 49.8895
3.5 c*
185 sq
mm 15.3 11 34.4245 1.6 1.1 39.8245 0.5 40.8245 1.4 43.6245 2.04 47.7045
3.5 c*
185 sq
mm 15.3 11 34.4245 1.6 1.1 39.8245 0.5 40.8245 1.4 43.6245 2.04 47.7045
3
3.5 c*
185 sq
mm 15.3 11 34.4245 1.6 1.1 39.8245 0.5 40.8245 0.72 42.2645 1.88 46.0245
3.5 c*
185 sq
mm 15.3 11 34.4245 1.6 1.1 39.8245 0.5 40.8245 0.88 42.5845 1.88 46.3445
3.5 c*
120 sq
mm 12.4 9.4 28.193 1.2 1.1 32.793 0.4 33.593 0.8 35.193 1.72 38.633
3.5 c*
120 sq
mm 12.4 9.4 28.193 1.2 1.1 32.793 0.4 33.593 0.8 35.193 1.72 38.633
4
3.5 c*
120 sq
mm 12.4 9.4 28.193 1.2 1.1 32.793 0.4 33.593 0.72 35.033 1.72 38.473
3.5 c*
120 sq
mm 12.4 9.4 28.193 1.2 1.1 32.793 0.4 33.593 0.88 35.353 1.72 38.793
3.5 c*
095 sq
mm 12.4 9.4 28.193 1.1 1 32.393 0.4 33.193 0.8 34.793 1.72 38.233
3.5 c*
095 sq
mm 12.4 9.4 28.193 1.1 1 32.393 0.4 33.193 0.8 34.793 1.72 38.233
5
5
3.5 c*
095 sq
mm 12.4 9.4 28.193 1.1 1 32.393 0.4 33.193 0.72 34.633 1.56 37.753
3.5 c*
095 sq
mm 12.4 9.4 28.193 1.1 1 32.393 0.4 33.193 0.88 34.953 1.56 38.073
3.5 c*
070 sq
mm 9.4 6.7 21.1145 1.1 0.9 25.1145 0.4 25.9145 0.8 27.5145 1.72 30.9545
3.5 c*
070 sq
mm 9.4 6.7 21.1145 1.1 0.9 25.1145 0.4 25.9145 0.8 27.5145 1.72 30.9545
6
3.5 c*
070 sq
mm 9.4 6.7 21.1145 1.1 0.9 25.1145 0.4 25.9145 0.72 27.3545 1.56 30.4745
3.5 c*
070 sq
mm 9.4 6.7 21.1145 1.1 0.9 25.1145 0.4 25.9145 0.88 27.6745 1.56 30.7945
3.5 c*
050 sq
mm 8 5.6 17.908 1 0.9 21.708 0.3 22.308 0.8 23.908 1.56 27.028
3.5 c*
050 sq
mm 8 5.6 17.908 1 0.9 21.708 0.3 22.308 0.8 23.908 1.56 27.028
7
3.5 c*
050 sq
mm 8 5.6 17.908 1 0.9 21.708 0.3 22.308 0.72 23.748 1.4 26.548
3.5 c*
050 sq
mm 8 5.6 17.908 1 0.9 21.708 0.3 22.308 0.88 24.068 1.4 26.868
Diameter calculations for Cable