You are on page 1of 31

IS 1893 (Part 4) : 2015

analysis unless a more definite value is to be taken as minimum for strength design of structures
available for use in such condition (see IS 456, only. However, for structures with interconnected equipment
at one or more levels, where displacement is a governing
IS 800 and IS 1343). parameter, use of site specific spectra shall be the governing
criteria.
6.3 Increase in Permissible Stresses
7.2 For all other projects, where site-specific studies
6.3.1 Increase in Permissible Stresses in Materials
are not carried out, the standard (this code) specific
When earthquake forces are considered along with spectra multiplied with zone factor as per 7.3.2 shall
other normal design forces, the permissible stresses in be considered as design spectra.
material, in the working stress method of design, may NOTES
be increased by one-third. However, for steels having 1 Zone factors are given in Annex A.
a definite yield stress, the stress shall be limited to the 2 Standard specific spectra is given in Annex B.
yield stress, for steels without a definite yield point,
the stress shall be limited to 80 percent of the ultimate 7.3 Design Horizontal Seismic Coefficient
strength or 0.2 percent proof stress, whichever is
smaller; and that in pre-stressed concrete members, the The horizontal seismic coefficient Ah shall be obtained
tensile stress in the extreme fibers of the concrete may using the period T, described as under.
be permitted so as not to exceed two-thirds of the 7.3.1 When using site specific spectra for DBE, the
modulus of rupture of concrete. seismic coefficient shall be calculated from the
6.3.2 Increase in Allowable Pressures in Soils expression:

When earthquake forces are included, the allowable Sa I


bearing pressure in soils shall be increased as per Ah =
g R
Table 1, depending upon type of foundation of the
structure and the type of soil. Sa
where = spectral acceleration coefficient
In soil deposits consisting of submerged loose sands g
and soils falling under classification SP with standard corresponding to time period T of the structure.
penetration N values less than 15 in seismic zones III,
IV, V and less than 10 in seismic zone II, the vibration [For evaluation of Time Period T of the structure
caused by earthquake may cause liquefaction or (see 9.3, 14.1 and 14.2) as applicable].
excessive total and differential settlements. For specific
7.3.2 When using standard specific spectra for DBE,
sites, study should be conducted to determine its
the seismic co-efficient shall be calculated as under:
liquefaction potential on need basis. Specialist
literature may be referred for liquefaction potential. Z Sa I
Such sites should preferably be avoided while locating Ah =
2 g R
new settlements or important projects. Otherwise, this
aspect of the problem needs to be investigated and where
appropriate methods of compaction or stabilization
Z = Zone factor corresponding to each zone is
adopted to achieve suitable N values as indicated in
as given in Table 13 (Zone factors for some
Note 3 of Table 1. Alternatively, deep pile foundation
important towns are also listed in Annex D).
may be provided and taken to depths well into the layer,
which is not likely to liquefy. Marine clays and other Sa/g = Spectral acceleration coefficient value for
sensitive clays are also known to liquefy due to collapse rock and soil sites corresponding to period
of soil structure and will need special treatment of structure T as shown in Fig. 1. These
according to site condition. values are for 5 percent damping normalized
to zero period acceleration equal to unity
Specialist literature may be referred for liquefaction (ZPA =1).Values for other damping are
potential, pile lateral and tensile resistance. obtained by multiplying factors as given in
7 DESIGN SPECTRUM Table 14 (see Annex A).
I = Importance factors (see Table 3 and Table 9).
7.1 For all-important projects, and all industries
dealing with highly hazardous/toxic chemicals, R = Response reduction factors (see Table 4
evaluation of site-specific spectra for DBE and MCE and 10).
is recommended. Such DBE site-specific spectra shall NOTE Ratio (I/R) shall in no case be more than 1.0.
be considered as design spectra. T = Time period of the structure (see 9.3 and
NOTE Standard specific design spectra as per 7.3.2, is 14).

IS 1893 (Part 4) : 2015

In the limit state design of reinforced and pre-stressed NOTE The combination procedures of 8.3.2.1.1 and 8.3.2.1.2
concrete structures, the following load combinations apply to the same response quantity (say, moment in a column
about its major axis, or storey shear in a frame) due to different
shall be accounted for: components of the ground motion. These combinations are to
be made at the member force/stress levels.
a) 1.5 (DL + SIDL + IL)
b) 1.2 (DL + SIDL + IL EL) 8.4 Seismic Weight
c) 1.5 (DL + SIDL EL) 8.4.1 Seismic Weight of Floor
d) 1.5 (0.6 DL EL) Seismic weight of each floor is its full Dead Load (DL)
NOTE Imposed load (IL) in load combination shall not + Superimposed Dead Load (SIDL) + appropriate
include erection load and crane payload. amount of Imposed Load (IL). Weight of piping, cable
8.3.2.1 In case of industrial structures, the plan wise trays, any other such utility that runs across the floors
distribution of mass and stiffness of the structural system shall be included in the seismic weight of upper and
may or may not be symmetrical about two lateral lower floors using law of statics.
directions that is, X and Y directions (Z axis being 8.4.2 Seismic Weight of Structure
vertical). When responses from the three earthquake Seismic weight of structure is sum of seismic weight
components are to be considered, the response due to of each floor.
each component may be combined as under.
8.5 Importance Factor ( )
8.3.2.1.1 Where the plan wise distribution of mass and
stiffness of the structural system is not symmetrical about It is relative importance assigned to a structure to take
two lateral (X and Y) directions, the response due to into account consequences of its damage. Importance
each component may be combined using the assumption factors for structures in different categories are given
that when the maximum response from one component in Table 3. Higher importance factor may however be
occurs, the responses from the other two components assigned to different structures at the discretion of the
are 30 percent of the corresponding maximum. project authorities.

All possible combinations of the three components Table 3 Importance Factor for Various
(EL x, ELy, EL z) including variations in sign (plus or Categories of Industrial structures
minus) shall be considered. Thus, the response due to (Clause 8.5)
earthquake force (EL) is the maximum of the following
cases: Sl Categories of Structures Importance Factor1)
No. (see 8.1)
EL x 0.3EL y 0.3ELz (1) (2) (3)
EL = EL y 0.3EL x 0.3ELz i) Category 1 2.00
EL z 0.3EL x 0.3EL y ii) Category 2 1.50
iii) Category 3 1.25
iv) Category 4 1.00
As an alternative to the procedure in 8.3.2.1, the 1)
Whenever structures are analyzed for site specific spectra
response (EL) due to the combined effect of the three corresponding to MCE, importance factor shall be considered
components can be obtained on the basis of square as unity for all structures.
root of the sum of the squares (SRSS), that is
8.5.1 Categorization of individual structure and
2 2 2
EL = EL x EL y EL z components applicable to all typical industries are
given in Table 6.
8.3.2.1.2 Where the plan wise distribution of mass and 8.6 Response Reduction factor ( )
stiffness of the structural system is symmetrical about
two lateral directions that is X and Y directions, the Response reduction factor, R takes into account the
structure shall be designed for the effects due to full margins of safety, over strength redundancy and
design earthquake load in one horizontal direction at a ductility of the structure. For industrial structures,
time. response reduction factor is given in Table 4. These
factors shall be used only for steel and RCC structures/
Thus, the response due to earthquake force (EL) is the support structures and not for design of equipment.
maximum of the following cases: For equipment (I/R) = 1 is recommended.

EL x 0.3 EL z 9 MATHEMATICAL MODELLING


EL = EL y 0.3ELz 9.1 Modelling Requirements
EL z 0.3EL x or 0.3EL y
The mathematical model of the physical structure/
10

IS 1893 (Part 4) : 2015

Table 4 Response Reduction Factor1), for and stiffness of the structures as well as mass of
Industrial Structures equipment, cable trays and piping system along with
(Clause 8.6) associated accessories. Fifty percent (50 percent) of
the imposed load shall also be included as suitably
Sl Lateral Load Resisting System R distributed mass on the structure.
No. (2) (3)
(1) 9.1.1 Soil-Structure Interaction
i) Building frame systems:
a) Ordinary RC moment - Resisting frame 3.0
The soil-structure interaction refers to the effects of
(OMRF)2) the supporting foundation medium on the motion of
b) Special RC moment - Resisting frame 5.0 structure. The soil-structure interaction may not be
(SMRF)3) considered in the seismic analysis for structures
c) Steel frame :
1) with concentric braces 4.0 supported on rock or hard soil or rock-like material
2) with eccentric braces 5.0 (N > 50, Vs = 760 m/s).
3) Special moment resisting frame designed 3.0
as per IS 800 without ductile detailing 9.2 Interaction Effects between Structure and
4) Steel special concentric braced frame 4.5
designed as per IS 800 (limit state Equipment
design)
ii) Building with shear walls4): Interaction effects between structure (primary system)
a) Load bearing masonry wall buildings5): and equipment (secondary system), for Categories 2,
1) Un-reinforced 1.5 3 and 4 structures, shall be considered as per 9.2.1 and
2) Reinforced with horizontal RC bands 2.5
3) Reinforced with horizontal RC bands 3.0
for Category 1 structures as per 9.2.2.
and vertical bars at corners of rooms 9.2.1 For Category 2, 3 and 4 structures, interaction
and jambs of openings
b) Ordinary reinforced concrete shear walls6) 3.0 effects between structure and equipment shall be
c) Ductile shear walls7) 4.0 considered as under:
iii) Buildings with dual systems 8):
a) Ordinary shear wall with OMRF 3.0 For the purpose of this clause, the following notations
b) Ordinary shear wall with SMRF 4.0 shall be used:
c) Ductile shear wall with OMRF 4.5
d) Ductile shear wall with SMRF 5.0 MS = total mass of the primary system (structural
1)
The values of response reduction factors are to be used for system) on which the secondary system is
structures with lateral load resisting elements, and not just for supported,
the lateral load resisting elements built in isolation.
2) MR = total mass of all the equipment that are
OMRF are those designed and detailed as per IS 456 or IS 800
(see 4.15.1). rigidly mounted at different locations in the
3)
SMRF has been defined in 4.15.2. structure, and
4)
Buildings with shear walls also include buildings having shear MF = total mass of all the equipment that are
walls and frames, but where: flexible mounted (on isolators) at different
a) frames are not designed to carry lateral loads, or
locations in the structure.
b) frames are designed to carry lateral loads but do not
fulfill the requirements of Dual-System. 9.2.1.1 Wherever equipment are rigidly fastened to the
5)
floor, the equipment mass (MR) shall be taken as lumped
Reinforcement should be as per IS 4326.
6)
mass at appropriate locations. No interaction between
Prohibited in Zones IV and V.
7)
the structures and equipment shall be considered.
Ductile shear walls are those designed and detailed as per IS
13920. 9.2.1.2 For flexible mounted equipment, if
8)
Buildings with dual systems consist of shear walls (or braced
frames) and moment resisting frames such that, MF
a) the two systems are designed to resist the total design < 0.25 no interaction between the structures
force in proportion to their lateral stiffness considering
Ms M R
the interaction of the dual system at all floor levels; and equipment shall be considered. In such a case MF
and should be considered as lumped mass at appropriate
b) the moment resisting frames are designed to locations (decoupled analysis).
independently resist at least 25 percent of the design
seismic base shear.
MF
9.2.1.3 If 0.25 interaction between the
Ms M R
equipment shall include all elements of the lateral isolators (Flexible mount for support of equipment)
force-resisting system. The model shall also include and the structure shall be considered by suitably
the stiffness and strength of elements, which are modeling the isolators support system while
significant to the distribution of forces. The model shall considering the equipment as lumped mass (coupled
properly represent the spatial distribution of the mass analysis).

11

IS 1893 (Part 4) : 2015

10.1.2 Response Spectrum Analysis Method = circular frequency, in ith mode.


i

Response spectrum analysis shall be performed using Alternatively, the peak response quantities may be
the design spectrum. combined as follows:

10.1.3 Sufficiently large number of modes shall be used a) If the structure does not have closely-spaced
for both time history as well as response spectrum modes, then the peak response quantity ( )
analysis to include the influence of at least 90 percent due to all modes considered shall be obtained
of the total seismic mass. The modal seismic mass shall as:
be calculated as per the provisions of 10.1.4. r
2
k
10.1.4 Modal Mass k 1

where
The modal mass Mk in mode k is given as:
k = absolute value of response quantity, in mode
2
n k; and
Wi ik
i 1 r = number of modes being considered
Mk = n
2 b) If the structure has a few closely-spaced
g Wi
i 1
ik modes (see 3.1), then the peak response
quantity * due to these modes shall be
where obtained as :
g = acceleration due to gravity, *
c
ik = mode shape coefficient at floor i, in mode k, c

Wi = seismic weight of floor i of the structure, where


and c = absolute value of quantity, in closely spaced
n = number of floors of the structure. mode c (The summation is for the closely
spaced modes only). This peak response
10.1.5 Modal Combination quantity due to the closely spaced modes
The peak response quantities should be combined as ( *) is then combined with those of the
per complete quadratic combination (CQC) method remaining well-separated modes by the
as follows: method described in 10.1.5 (a).

r r 10.2 Simplified Analysis


= i ij j
i 1 j 1
Simplified analysis shall be carried out by applying
equivalent static seismic forces along each of the three
where principal directions one at a time. The horizontal
= peak response quantity; seismic coefficient A h shall be determined in
accordance with 7.3.1 for site specific DBE spectra or
i = response quantity, in mode i (including 7.3.2 for standard specific spectra as the case may be
sign); using time period T as per 9.3.2.
j = response quantity, in mode j (including Sa I
sign); a) For site specific spectra for DBE, Ah
g R
ij = cross-modal correlation co-efficient;
Z Sa I
2 1.5
b) For standard specific spectra, Ah
8 (1 ) 2 g R
ij
2 2 2 2 Vertical acceleration values shall be taken as 2/3 of
1 4 1
horizontal acceleration values.
r = number of modes being considered; The seismic force at each node in each of the three
= modal damping coefficient as specified in directions shall be equal the product of its mass and
9.4; corresponding seismic coefficient.

10.3 Effect
j
= frequency ratio =
i
Structures in all categories and in all zones shall be
analysed to take into account the influence of P
j = circular frequency, in jth mode; and effect.

13

IS 1893 (Part 4) : 2015

10.4 Torsion 11.2 Separation Between Adjacent Units


The effect of accidental eccentricity shall be Two adjacent buildings, or adjacent units of the same
considered only for structures of category 4 in all structure with separation joint in between shall be
seismic zones. separated by a distance equal to the amount R
(Reduction factor) times the absolute sum of the
This effect shall be considered for with rigid floors/
maximum calculated storey displacements as per 11.1
diaphragms. This shall be applied as an additional
of each of them, to avoid damaging contact when the
torsional moment equal to product of the seismic force
two units deflect towards each other. When floor levels
at floor level and 5 percent of the structure dimension
of two adjacent units or structures are at the same
perpendicular to the earthquake direction at the centre
elevation levels, separation distance shall be R/2 times
of mass of the floor.
the absolute sum of the maximum calculated storey
10.4.1 The design eccentricity edi, to be used at floor i, displacements +25 mm.
shall be taken as:
12 MISCELLANEOUS
(a ) 1.5 esi 0.05 bi
edi ; 12.1 Foundations
(b ) esi 0.05 bi
The stability of foundations vulnerable to significant
Analysis is to be done for both the cases and at the differential settlement and or overturning due to ground
member force level, whichever gives more severe effect shaking shall be checked for structures in Seismic
is to be considered. Zones III, IV and V. In Seismic Zones IV and V,
esi = static eccentricity at floor i, defined as the individual spread footings or pile caps shall be
distance between center of mass and center interconnected with ties (see 5.3.4.1 of IS 4326) except
of rigidity when individual spread footings are directly supported
on rock. All ties shall be capable of carrying, in tension
bi = floor plan dimension of floor i perpendicular
and in compression, an axial force equal to Ah/4 times
to direction of force
the larger of the column or pile cap load, in addition to
The factor 1.5 represents dynamic amplification factor, the otherwise computed forces. Here, A h is design
while the factor 0.05 represents the extent of accidental horizontal acceleration coefficient evaluated as per 10.1
eccentricity. or 10.2.
NOTES
1 For the purpose of this clause, all steel or aluminium flooring
12.2 Cantilever Projections
system may be considered as flexible unless properly designed 12.2.1 Vertical Projections
floor bracings have been provided.
2 RCC flooring systems in steel str uctures shall be Towers, tanks, parapets and other vertical cantilever
considered flexible unless properly designed floor bracings projections attached to structures and projecting above
are provided.
the roof, shall be designed for five times the design
3 Reinforced concrete flooring system at a level shall be
horizontal acceleration spectrum value specified
considered rigid only, if the total area of all the cut-outs at that
level is less than 25 percent of its plan floor area. in 7.3.1 and 7.3.2.
12.2.2 Horizontal Projections
11 DEFORMATIONS
All horizontal projections like cornices and balconies
11.1 Drift Limitations shall be designed for five times the design vertical
The storey drift in any storey due to the minimum acceleration spectrum value specified in 7.4.
specified design lateral force, with partial load factor 12.2.3 The increased design forces specified in 12.2.1
of 1.0, shall not exceed 0.004 times the storey height. and 12.2.2 are only for designing the projecting parts
There shall be no drift limit for single storey and their connections with the main structures. For the
structure which has been designed to accommodate design of the main structure, such increase shall not
storey drift. be considered.

14

IS 1893 (Part 4) : 2015

Table 6 (Concluded) Design of equipment (listed above), its supporting structure


and foundation.
Sl No. Structures/Equipment Category 4 For the structures/equipment not included herein, the category
(1) (2) (3) shall be selected by the designer considering the classification
defined in 8.1
58) Piping 3
59) Process gas compressor 2
60) Pump house (Water and effluents, etc) 3 SECTION 2 STACK - LIKE STRUCTURES
61) Road/Rail loading gantry handling non-inflammable, 3
non-hazardous material 13 DESIGN CRITERIA
62) Road/Rail loading gantry handling LPG, hydrocarbon 2
63) Switch-gear building/Substations 3 Stack like structures are those in which the mass and
64) Switchyard structures 3 stiffness is more or less uniformly distributed along
65) Technological structures in RCC/steel or both 2
66) Transformers and radiator bank 3 the height. Cantilever structures like reinforced or pre-
67) Wagon tippler 4 stressed cement concrete electric poles; reinforced
68) Water Intake structure 3 concrete brick and steel chimneys (including multi-
69) Water treatment plant 3 flue chimneys), ventilation stacks and refinery vessels
70) Water/Effluent Storage tank (dome/cone roof) 3
iii) Storage and handling are examples of such structures. Guyed structures are
(Raw material, Intermediate Product, Final Product, not covered here.
Bulk Storage of Chemicals):
1) Bagging and palletizing 3 14 TIME PERIOD OF VIBRATION
2) Catalyst storage building 2
3) Chemical house 3 Time period of vibration, T of such structures when
4) Cryogenic bulk storage tank (double walled) with 1 fixed at base, shall be calculated using either of the
refrigerated liquefied gases (e.g. ethylene, LNG,
NH3 etc.) following two formulae given (see 14.1 and 14.2). The
5) Hazardous chemical house 1 formulae given at 14.1, is more accurate. Only one of
6) Hydrocarbon storage tanks (Cone/ Floating roof) 2 these two formulae should be used for design. Time
7) Hydrocarbon storage tanks (Dome roof) 2
8) Hydrogen bullet 1
period of structure, if available, through vibration
9) LPG storage shed 1 measurement on similar structure and foundation soil
10) Mounded LPG bullet 1 condition can also be adopted.
11) Pipe rack 2
12) Process water storage tank 3 14.1 The fundamental time period for stack like
13) Product storage sheds/building 3 structures, T is given by:
14) Road/Rail loading gantry handling non- 3
inflammable, non hazardous material Wt .h
15) Road/Rail loading gantry handling LPG, hydrocarbon 2 T CT
16) Sphere/bullets storing hydrocarbon/with liquefied 1 Es .A.g
gases
iv) Infrastructure where
(Administrative Block, Laboratory Building, Service
Buildings, Road Crossings, etc) CT = coefficient depending upon the slenderness
1) Administration building 4 ratio of the structure given in Table 7,
2) Bridges over rivers/canal/drain 2
3) Canteen building 4 Wt = total weight of the structure including weight
4) Communication building/repeater station/ 2 of lining and contents above the base,
telephone exchange h = height of structure above the base,
5) Gate and gate house 4
6) Hospital 2 Es = modulus of elasticity of material of the
7) Laboratory building, MCC Room 3 structural shell,
8) Maintenance stores 4
9) Maintenance Workshop 4 A = area of cross-section at the base of the
10) Medical center/First aid center 2 structural shell,
11) Other non-plant buildings and utility structures 4
12) Service building 4 For circular sections, A = 2 rt, where r is
13) Warehouse 4 the mean radius of structural shell and t is
NOTES
thickness, and
1 Equipment containing LPG, compressed gas of explosive g = acceleration due to gravity.
nature or any other content whose failure/leakage can lead
directly or indirectly to extensive loss of life/property to NOTE This formula is only applicable to stack-like structure
population at large in the areas adjacent to the plant complex. in which the mass and stiffness are more or less uniformly
distributed along the height.
2 Equipment containing gases of explosive nature or any other
content whose failure/leakage can lead directly or indirectly 14.2 The fundamental time period, T of a stack like
to serious fire hazards/extensive damage within the plant
complex. Structures, which are required to handle emergencies
structure can be determined by Rayleighs
immediately after an earthquake, are also included here. approximation for fundamental mode of vibration as
3 The above recommended category will be applicable to: follows :

16

IS 1893 (Part 4) : 2015

2 Table 8 Material Damping Factors for Design


T Basis Earthquake
g.
(Clause 15)
s
Wi Sl No. Material For Design
i
i 1 Earthquake
s (1) (2) (3)
2
Wi i i) Steel 0.05
i 1 ii) Reinforced concrete 0.05
where iii) Brick masonry and plain concrete 0.07

Wi = weight lumped at ith location with the 16 HORIZONTAL SEISMIC FORCE


weights applied simultaneously with the
force applied horizontally, Using the period T, as indicated in 14, the horizontal
seismic coefficient A h shall be obtained from the
i = lateral static deflection under its own lumped
spectrum given in Fig. 1.
weight at ith location (chimney weight
lumped at 10 or more locations), The equivalent static lateral loads shall be determined
from design acceleration spectrum value Ah, calculated
n = Number of locations of lumped weight, and
from the following equation (for site specific spectra
g = Acceleration due to gravity. (see 7.3.1) or standard specific spectra (see 7.3.2), as
NOTES the case may be using time period T from 14.1 or 14.2.
1 Any elastic analysis procedure like moment area theorem or Sa I
matrix method may be used for determining the lateral static For site specific spectra : Ah
deflection d value. g R
2 For determining the time period of vibration of structures
resting on frames or skirts like bins, silos, hyperbolic cooling Z Sa I
For standard specific spectra : Ah
towers, refinery columns, only the formula given at 14.2 should 2 g R
be used. Approximate methods may be adopted to estimate
the lateral stiffness of the frame or skirt in order to determine
the lateral static deflection. Dynamic response spectrum modal
The horizontal earthquake force shall be assumed to
analysis will be necessary in such cases. act alone in one lateral direction at a time.
The effects due to vertical component of earthquakes
Table 7 Values of T and v are generally small and can be ignored. The vertical
(Clauses 14.1 and 17.1) seismic coefficient where applicable may be taken as
2/3 of horizontal seismic coefficient, unless evidence
Sl = / e Coefficient C Coefficient of factor larger than above is available.
No.
(1) (2) (3) (4)
The effect of earthquake and maximum wind on the
structure shall not be considered simultaneously.
i) 5 14.4 1.02
ii) 10 21.2 1.12 Table 9 Importance Factor ( ) Applicable to
iii) 15 29.6 1.19
Stack Like Structures
iv) 20 38.4 1.25
v) 25 47.2 1.30 (Clauses 7.3.2 and 16)
vi) 30 56.0 1.35 Sl Type of Structure Category Importance
vii) 35 65.0 1.39 No. Factor
viii) 40 73.8 1.43 I
ix) 45 82.8 1.47 (1) (2) (3) (4)
x) 50 or more 1.8 k 1.50
i) Reinforced concrete ventilation 2 1.5
NOTES stacks
ii) Reinforced concrete chimneys 2 1.5
1 k = slenderness ratio, and iii) Reinforced brick masonry chimney 2 1.5
2 re= radius of gyration of the structural shell at the base section for industry
iv) Un-reinforced brick masonry 4 1.0
chimney for industry
15 DAMPING v) Reinforced concrete T.V. towers 2 1.5
vi) Electric/traffic light poles 4 1.0
The damping factor to be used in determining Sa /g vii) Steel stack 2 1.5
depends upon the material and type of construction of viii) Silos 2 1.5
the structure and the strain level. The following NOTE The values of importance factor, (I) given in this
damping factors are recommended as guidance for table are for guidance. The designer may choose suitable values
different materials for fixed base condition and are depending on the importance based on economy, strategy and
other considerations.
given in the Table 8.
17

IS 1893 (Part 4) : 2015

Table 12 Values of m and v


(Clauses 17.1)
Sl Soil Foundation Condition m v
No.
(1) (2) (3) (4)
i) Fixed base or raft on hard soil 1/ 2 4
x
1/ 2
x x
4
x x 1.1 0.75 0.9
(based on N values) 0.4 0 .6
h h h h h
but 1
ii) Raft on soil 1/ 2 4
x
1/ 2
x x
4
x x 1.1 0.75 0.65
(based on N values) 0.6 0.4
h h h h h
iii) Pile foundation 1/ 2 4
x
1/ 2
x x
4
x x 0.66 0.20 0.54
0.5 0.5
h h h h h

Table 13 Foundation Soil and Foundation Pile Group Stiffness


(Clauses 7.3.2 and 17.1)

Sl No. Type of Foundation Stiffness


(1) (2) (3)
i) Circular raft foundation on soil:
1) Horizontal soil stiffness Kh = 32 (1 ) Gr0/(7 8 )
2) Rocking soil stiffness (full circular raft) K = 8 Gr03/3(1 )
ii) Annular raft :
1) Friction pile foundation (under reamed piles not covered)
2) Translational stiffness of piles at the base of pile cap Kh = nEpIm/1.2T13 + h d2/2 and T1 = (EpIm/ h)1/5

where
G = shear modulus of foundation soil = Vs2 ,
Vs = shear wave velocity of the medium,
= soil density
r0 = radius of circular raft foundation,
= poissons ratio of soil,
n = number of piles,
Ep = modulus of elasticity of pile material,
Im = moment of inertia of pile section,
T1 = characteristic length of pile,
d = thickness of pile cap or raft, and

h = modulus of sub-grade reaction of soil in horizontal direction.


NOTES
1 For rectangular foundation effective radius r0 ab may be taken, where a and b are the dimension of the rectangular foundation.
2 For N values > 50, fixed base condition may be assumed.
3 Classification of soil shall be as per IS 1893 (Part 1).
4 When soil structure interaction effects are to be considered; shear wave velocities are to be determined by suitable methods.

shell), lining mass and foundation modeling (that is NOTE Minimum number of elements should be adequate
foundation stiffness, soil deformations). The number to ensure that the model represent the frequencies up to 33 Hz.
of elements should be such as to capture the variation 18 SPECIAL DESIGN CONSIDERATIONS FOR
of stiffness and mass of the system. A minimum of ten REINFORCED CONCRETE STACKS
beam elements should in general be sufficient. For axi-
symmetric structures axi-symmetric finite elements 18.1 The total vertical reinforcement shall not be less
shall be used. than 0.25 percent of the concrete area. When two layers
of reinforcement are required, the outside vertical
In case of chimneys, no stiffness is considered to be reinforcement shall not be less than 50 percent of the
provided by the lining, however, the mass of lining reinforcement.
above any corbel is assumed to be lumped at the corbel
level. 18.2 The total circumferential reinforcement shall not

19


IS 1893 (Part 4) : 2015

ANNEX C
(Clause 9.2.2)
C-0 For Category 1 structures, decoupling criteria as output motions from the first analysis as input at the
given below shall be used for the interaction effects points of connectivity.
between primary system (structure) and secondary
C-7 For applying the criteria of this section to have a
system (equipment).
modal mass greater than 20 percent of the total system
C-1 For the purpose of this clause, the following mass, the total system mass is defined by:
notations shall be used.
m
2
T M j
j M Ub j 1
j T
M = Participation factor for jth mode
j j
C-8 When detailed analysis is to be carried out for
where structures with equipment attached at a single point,
M = mass matrix of the structural system. the coupling criteria shown in Fig. 2 shall be used.
The mass ratio in Fig. 2 is the modal mass ratio
j = jth normalized mode shape.
computed as per section C-9 and the frequency ratio is
T
j M j=1 the ratio of uncoupled modal frequencies of the
Ub = Influence vector (displacement vector) of the secondary and primary systems.
structural system when the base is displaced
C-9 For a secondary system dominant mode and the
by unity in the direction of earthquake
primary system mode i, the modal mass ratio can be
motion.
estimated by:
C-2 All combinations of the dominant secondary
system modes and the dominant primary system modes Ms
mri
must be considered and the most restrictive M pi
combination shall be used.
where
C-3 Coupled analysis of primary structure and secondary
system shall be performed when the effects of interaction 2

are significant based on sections C-9 and C-10. 1


Mpi
ci
C-4 Coupling is not required, if the total mass of the
equipment or secondary system is 1 percent or less of = mode vector value from the primary
ci
the mass of the supporting primary structure. However, systems modal displacement at the location
the requirements of section C-10 regarding the multiple where the secondary system is connected,
supports should be considered. from the ith normalized modal vector, ( ci),
T
C-5 In applying sections C-9 and C-10, one sub- ci Mp ci = 1
system at a time may be considered, unless the Mp = mass matrix of the primary system; and
subsystems are identical and located together, in which Ms = total mass of the secondary system.
case the subsystem masses shall be lumped together.
C-10 Multi-support secondary system shall be
C-6 When coupling is required, a detailed model of reviewed for the possibility of interaction of structure
the equipment or secondary system is not required, and equipment stiffness between the support points,
provided that the simple model adequately represents and for the effect of equipment mass distribution
the major effects of interaction between the two parts. between support points. When these effects can
When a simple model is used, the secondary system significantly influence the structure response, reference
shall be re-analyzed in appropriate detail using the shall be made to specialized literature.

22

You might also like