PART B: Answer 1 mark + Justification carries 1 mark (total 2 marks for each question)
11. If we increase the length of the transmission line, the charging current
a) Increases b)decreases c)remains unaffected d)none of these
12. Zero sequence currents can flow from a line into a transformer bank if the windings are in
a) Delta/star c) grounded star/delta
b) Delta/delta d) star/grounded star
13. An over current relay, having a current setting of 125% connected to a supply circuit through a
current transformer of ratio 500/5. The plug setting multiplier for a fault current of 5 kA is
a) 6 b) 5 c) 10 d) 8
14. In the following figure, which relays must be made directional to have selectivity? What is the
direction?
16. Power system A is operating in parallel with other power systems and has a frequency bias of 50 MW
per 0.1 Hz. For a loss of generation in one of the interconnected systems which results in a frequency
drop of 0.03 Hz , power system A should
a) Provide 30 MW of support
b) Not be affected
c) Provide 15 MW of support
d) Provide 5 MW of support
18. By increasing the transmission voltage to double of its original value, the same power can be
dispatched by keeping the line loss
a) Equal to original value c) 1/4th of the original value
b) Double the original value d) half the original value
Roll No:
Name: SET R
19. If all the sequence voltages at the fault point in a power system are equal, then the fault point is a
a) LL b) LG c) LLG d) LLL
20. Find the slope of the percentage differential relay, if the relay operates for a differential secondary
current of 1A and average secondary current of 2A.
a) 0.25 b) 2 c) 0.5 d) 1