MOLDED
CASE
CIRCUIT
BREAKERS E series Distribution breakers
F series
4-pole
S and E series
INDIVIDUAL
CATALOG Motor operated breakers LOW
VOLTAGE
from D&C CATALOG 19th Edition EQUIPMENT
Up to 600 Volts
Revised
06
D & C CATALOG DIGEST INDEX
Individual
catalog No. LOW VOLTAGE PRODUCTS Up to 600 Volts
DUO series
02 Manual Motor Starters and Contactors
Combination Starters
Circuit Protectors
08 Low Voltage Current-Limiting Fuses
Air Circuit Breakers
AC Power Regulators
10 Noise Suppression Filters
Control Power Transformers
Page
Used for equipment with a capacity Ideal for circuits with comparatively This breaker protects motors from This breaker is UL and CSA
range of 15 to 20kVA. Satisfies EN low short-circuit current. Satisfies overload and cables from approved.
(IEC) standards and bears CE EN (IEC) standards and bears CE excessive current. Satisfies EN (IEC) standards and
markings. markings. bears CE markings.
Enables the design of compact,
economical control panels. The
depth is 60mm for types with a
capacity range of 30 to 225A.
Varieties of MCCBs
IEC and CE marking conformed
Frame size 30AF 50AF 60AF 100AF 225AF 400AF 600AF 800AF
Line S series SA30C -CE SA50C -CE SA60C -CE SA100C -CE SA225C -CE SA400C -CE SA600RC -CE SA800RC -CE
protection SA50RC -CE SA60RC -CE SA100RC -CE SA225RC -CE SA400RC -CE
E series EA30AC -CE EA50AC -CE EA60C -CE EA100AC -CE EA225C -CE EA400C -CE EA600C -CE EA800C -CE
EA50C -CE EA100C -CE
Motor S series SA30CM -CE SA50CM -CE SA60CM -CE SA100CM -CE SA225CM -CE
protection SA50RCM -CE SA100RCM -CE SA225RCM -CE
E series EA30ACM -CE EA50CM -CE EA60CM -CE EA100CM -CE EA225CM -CE
Note: Type number with "-CE" indicates the IEC and CE marking conformed model,
but type number without "-CE" indicates also the same.
UL489 Listed
Frame size 30AF 50AF 60AF 100AF 225AF 400AF 600AF 800AF
EA-UL EA100CUL
JIS C8370
Frame size 30AF 50AF 60AF 100AF 225AF 400AF 600AF 800AF
S series
Design features
A vertical link mechanism is used for the switching mechanism Contact opening distance/Moving contact arm torque
to reduce the torque of the moving contact arm, serve as a
countermeasure against increased contact opening distance,
Moving contact
and improve contact opening speed.
arm torque
Conventional MCCB
Handle
Latch
0 Contact opening distance
Moving contact
06
Flat-Turn contact
Blow-out gas
Blow-out gas
Conventional MCCB
0 Time
100mm
Terminal
height 75mm
24mm
(Up to 225AF)
EA103C
CP-898
Depth
60, 103mm
Self-lifting terminal
NA-007
Long type
SA225C
SA225RC
SA30C
SA50C
EA225C Panel cutout
SA50RC
SA60C height 52mm
SA60RC
SA100C
EA30AC
Screw terminal (Hexagonal socket head bolt) SA100RC
EA50AC
EA50C
EA60C
EA100C Depth
EA100AC 60mm
F50B
F100B
Flat terminal
SDO-0190M
Internal and external accessories Two ways to connect lead wires or Terminal block types
A wider range of customer-mountable terminal blocks Terminal blocks are mounted on the side
accessories Lead wire types of the breaker case. Blocks are only
The range of cassette-type internal Leads are marked with to indicate the 12.5 or 19mm thick, minimizing panel
accessories has been greatly expanded correct terminal number of the accessory mounting space. Installed lead wires are
for MCCBs. This speeds up incorrect wiring is minimized. parallel to the side of the case.
and simplifies customer response to To make wiring easy and prevent to
specification changes. incorrect connection, the lead wires are
All accessories shown here can be provided with color coated tube and
mounted by the customer except for marking on it.
motor operating mechanism and plate
type padlocking device.
No adjustments
Accessory mounting is quick and easy
accessories adjust automatically at
the correct position when mounted.
Alarm switch Auxiliary switch Shunt trip device Undervoltage trip device Terminal block
Series Breaker Basic Pole Rated current Insulation Breaking capacity (kA)[Icu/Ics] IEC609472 JIS C8201-2
ampere type voltage AC DC
frame (A) Ui (V) 230V 380V 400V 415V 440V 500V 600V 250V
S 30 SA32C -CE 2 3, 5, 10, 15, 20, 30 690 5/3 2.5/2 2.5/2 2.5/2 2.5/2 1.5/1 2.5/2
30 SA33C -CE 3 3, 5, 10, 15, 20, 30 690 5/3 2.5/2 2.5/2 2.5/2 2.5/2 1.5/1 2.5/2
50 SA52C -CE 2 5, 10, 15, 20, 30, 40, 50 690 10/5 7.5/4 7.5/4 7.5/4 7.5/4 5/3 2.5/2 5/3
50 SA53C -CE 3 5, 10, 15, 20, 30, 40, 50 690 10/5 7.5/4 7.5/4 7.5/4 7.5/4 5/3 2.5/2 5/3
50 SA52RC -CE 2 10, 15, 20, 30, 40, 50 690 25/13 10/5 10/5 10/5 10/5 7.5/4 5/3 5/3
50 SA53RC -CE 3 10, 15, 20, 30, 40, 50 690 25/13 10/5 10/5 10/5 10/5 7.5/4 5/3 5/3
60 SA62C -CE 2 60 690 10/5 7.5/4 7.5/4 7.5/4 7.5/4 5/3 2.5/2 5/3
60 SA63C -CE 3 60 690 10/5 7.5/4 7.5/4 7.5/4 7.5/4 5/3 2.5/2 5/3
60 SA62RC -CE 2 60 690 25/13 10/5 10/5 10/5 10/5 7.5/4 5/3 5/3
60 SA63RC -CE 3 60 690 25/13 10/5 10/5 10/5 10/5 7.5/4 5/3 5/3
100 SA102C -CE 2 15, 20, 30, 40, 50, 60, 75, 100 690 50/25 30/8 30/8 30/8 25/7 15/4 15/8
100 SA103C -CE 3 15, 20, 30, 40, 50, 60, 75, 100 690 50/25 30/8 30/8 30/8 25/7 15/4 15/8
100 SA102RC -CE 2 15, 20, 30, 40, 50, 60, 75, 100 690 100/50 50/13 50/13 50/13 50/13 30/8 40/20
100 SA103RC -CE 3 15, 20, 30, 40, 50, 60, 75, 100 690 100/50 50/13 50/13 50/13 50/13 30/8 40/20
225 SA202C -CE 2 125, 150, 175, 200, 225 690 50/25 30/8 30/8 30/8 25/7 15/4 15/8
225 SA203C -CE 3 125, 150, 175, 200, 225 690 50/25 30/8 30/8 30/8 25/7 15/4 15/8
225 SA202RC -CE 2 125, 150, 175, 200, 225 690 100/50 50/13 50/13 50/13 50/13 30/8 40/20
225 SA203RC -CE 3 125, 150, 175, 200, 225 690 100/50 50/13 50/13 50/13 50/13 30/8 40/20
400 SA402C -CE 2 250, 300, 350, 400 690 50/25 35/18 35/18 35/18 35/18 22/11 20/10
400 SA403C -CE 3 250, 300, 350, 400 690 50/25 35/18 35/18 35/18 35/18 22/11 20/10
400 SA402RC -CE 2 250, 300, 350, 400 690 85/43 50/25 50/25 50/25 50/25 35/18 30/15 40/20 06
400 SA403RC -CE 3 250, 300, 350, 400 690 85/43 50/25 50/25 50/25 50/25 35/18 30/15 40/20
600 SA603RC -CE 3 500, 600 690 85/43 50/25 50/25 50/25 50/25 35/18 30/15 40/20
800 SA803RC -CE 3 700, 800 690 85/43 50/25 50/25 50/25 50/25 35/18 30/15 40/20
E 30 EA32AC -CE 2 3, 5, 10, 15, 20, 30 500 2.5/2 1.5/1 1.5/1 1.5/1 1.5/1
30 EA33AC -CE 3 3, 5, 10, 15, 20, 30 500 2.5/2 1.5/1 1.5/1 1.5/1 1.5/1
50 EA52AC -CE 2 5, 10, 15, 20, 30, 40, 50 500 2.5/2 1.5/1 1.5/1 1.5/1 1.5/1
50 EA53AC -CE 3 5, 10, 15, 20, 30, 40, 50 500 2.5/2 1.5/1 1.5/1 1.5/1 1.5/1
50 EA52C -CE 2 5, 10, 15, 20, 30, 40, 50 690 5/3 2.5/2 2.5/2 2.5/2 2.5/2 1.5/1 2.5/2
50 EA53C -CE 3 5, 10, 15, 20, 30, 40, 50 690 5/3 2.5/2 2.5/2 2.5/2 2.5/2 1.5/1 2.5/2
60 EA62C -CE 2 60 690 5/3 5/3 2.5/2 2.5/2 2.5/2 1.5/1 2.5/2
60 EA63C -CE 3 60 690 5/3 5/3 2.5/2 2.5/2 2.5/2 1.5/1 2.5/2
100 EA103AC -CE 3 60, 75, 100 500 5/3 1.5/1 1.5/1
100 EA102C -CE 2 50, 60, 75, 100 690 25/13 10/5 10/5 10/5 10/5 7.5/4 5/3 5/3
100 EA103C -CE 3 50, 60, 75, 100 690 25/13 10/5 10/5 10/5 10/5 7.5/4 5/3 5/3
225 EA202C -CE 2 125, 150, 175, 200, 225 690 35/18 18/5 18/5 18/5 15/4 10/3 10/5
225 EA203C -CE 3 125, 150, 175, 200, 225 690 35/18 18/5 18/5 18/5 15/4 10/3 10/5
400 EA402C -CE 2 250, 300, 350, 400 690 35/18 25/13 25/13 25/13 25/13 18/9 20/10
400 EA403C -CE 3 250, 300, 350, 400 690 35/18 25/13 25/13 25/13 25/13 18/9 20/10
600 EA603C -CE 3 500, 600 690 50/25 35/18 35/18 35/18 35/18 22/11 20/10
800 EA803C -CE 3 700, 800 690 50/25 35/18 35/18 35/18 35/18 22/11 20/10
Note: For details of breaking capacity, see page 06 /10 "Quick reference guide".
Series Breaker Basic Pole Rated current Insulation Breaking capacity (kA)[Icu/Ics] IEC60947-2
ampere type voltage AC DC
frame (A) Ui (V) 230V 400V 440V 500V 600V 250V
JIS C8370
Series Breaker Basic Pole Rated current Insulation Breaking capacity (kA)
ampere type voltage AC DC
frame (A) Ui (V) 220V 240V 380V 415V 500V 600V 660V 250V
H 100 H103R 3 40, 50, 60, 75, 100 660 125 125 100 85 42 35 40
225 H203R 3 125, 150, 175, 200, 225 660 125 125 100 85 42 35 40
Series Breaker Basic Pole Rated current Insulation Breaking capacity (kA)
ampere type voltage AC DC
frame (A) Ui (V) 220V 240V 380V 415V 500V 600V 660V 250V
S 50 SA54B 4 5, 10, 15, 20, 30, 40, 50 660 10 10 7.5 7.5 5 2.5
100 SA104R 4 15, 20, 30, 40, 50, 60, 75, 100 660 85 85 50 45 35 25
225 SA204R 4 125, 150 175, 200, 225 660 85 85 50 50 35 25
400 SA404HA 4 250 300, 350, 400 660 85 85 45 45 35 30
600 SA604H 4 500, 600 660 85 85 45 45 35 30
800 SA804H 4 700, 800 660 85 85 45 45 35 30
1000 S1004 4 1000 660 85 85 50 50 35 30 30
1200 S1204 4 1200 660 85 85 50 50 35 30 30
E 100 EA104B 4 50, 60, 75, 100 660 25 25 15 10 7.5 5
F 50 F51B 1 15, 20, 30, 40, 50 300 2.5 3 3
50 F52B 2 15, 20, 30, 40, 50 300 5 3 3
50 F53B 3 15, 20, 30, 40, 50 300 5 3
100 F102B 2 60, 75, 100 300 5.5 3
100 F103B 3 60, 75, 100 300 5.5 3
IEC 60947-2
Series Breaker Basic Pole Rated current Insulation Breaking capacity (kA)[Icu/Ics] IEC60947-2
ampere type voltage AC DC
frame (A) Ui (V) 230V 400V 440V 500V 600V 250V
H 50 H52BA 2 15, 20, 30, 40, 50 690 125/32 65/17 65/17 35/9 25/7 40/10
50 H53BA 3 15, 20, 30, 40, 50 690 125/32 65/17 65/17 35/9 25/7 40/10
100 H102BA 2 15, 20, 30, 40, 50, 60, 75, 100 690 125/32 65/17 65/17 35/9 25/7 40/10
100 H103BA 3 15, 20, 30, 40, 50, 60, 75, 100 690 125/32 65/17 65/17 35/9 25/7 40/10
225 H202BA 2 125, 150, 175, 200, 225 690 125/32 65/17 65/17 35/9 25/7 40/10
225 H203BA 3 125, 150, 175, 200, 225 690 125/32 65/17 65/17 35/9 25/7 40/10
400 H402B 2 250, 300, 350, 400 690 125/63 65/33 65/33 42/21 35/18 40/20
400 H403B 3 250, 300, 350, 400 690 125/63 65/33 65/33 42/21 35/18 40/20
400 H403R 3 250, 300, 350, 400 690 125/63 125/63 125/63 85/43 40/20
600 H603B 3 500, 600 690 125/63 65/33 65/33 42/21 35/18 40/20
600 H603R 3 500, 600 690 125/63 125/63 125/63 85/43 40/20
800 H803B 3 700, 800 690 125/63 65/33 65/33 42/21 35/18 40/20
800 H803R 3 700, 800 690 125/63 125/63 125/63 85/43 40/20
UL489 Listed
Series Breaker Basic Pole Rated current Insulation Breaking capacity (kA)[Icu/Ics] IEC609472 JIS C8201-2 UL489 (cUL)
ampere type voltage AC DC Rated voltage Breaking capacity (kA)
frame (A) Ui (V) 230V 380V 400V 415V 440V 500V 600V 250V (V) 240 480Y/277 480 06
S 50 SA52RCUL 2 3, 5, 10, 15, 20, 30, 40, 50 690 25/13 10/5 10/5 10/5 10/5 7.5/4 5/3 240 14
50 SA53RCUL 3 3, 5, 10, 15, 20, 30, 40, 50 690 25/13 10/5 10/5 10/5 10/5 7.5/4 5/3 240 14
100 SA102CUL 2 15, 20, 30, 40, 50, 60, 70, 75, 80, 90, 100 690 50/25 30/8 30/8 30/8 25/7 15/4 15/8 240 35
100 SA103CUL 3 15, 20, 30, 40, 50, 60, 70, 75, 80, 90, 100 690 50/25 30/8 30/8 30/8 25/7 15/4 15/8 240 35
100 SA102RCUL 2 15, 20, 30, 40, 50, 60, 70, 75, 80, 90, 100 690 100/50 50/13 50/13 50/13 50/13 30/8 40/20 480Y/277 85 25
100 SA103RCUL 3 15, 20, 30, 40, 50, 60, 70, 75, 80, 90, 100 690 100/50 50/13 50/13 50/13 50/13 30/8 40/20 480Y/277 85 25
225 SA202CUL 2 125, 150, 175, 200, 225 690 50/25 30/8 30/8 30/8 25/7 15/4 15/8 240 35
225 SA203CUL 3 125, 150, 175, 200, 225 690 50/25 30/8 30/8 30/8 25/7 15/4 15/8 240 35
225 SA202RCUL 2 125, 150, 175, 200, 225 690 100/50 50/13 50/13 50/13 50/13 30/8 40/20 480Y/277 85 25
225 SA203RCUL 3 125, 150, 175, 200, 225 690 100/50 50/13 50/13 50/13 50/13 30/8 40/20 480Y/277 85 25
400 SA402CUL 2 250, 300, 350, 400 690 50/25 35/18 35/18 35/18 35/18 22/11 20/10 480 42 25 25
400 SA403CUL 3 250, 300, 350, 400 690 50/25 35/18 35/18 35/18 35/18 22/11 20/10 480 42 25 25
400 SA402RCUL 2 250, 300, 350, 400 690 85/43 50/25 50/25 50/25 50/25 35/18 30/15 40/20 480 85 50 50
400 SA403RCUL 3 250, 300, 350, 400 690 85/43 50/25 50/25 50/25 50/25 35/18 30/15 40/20 480 85 50 50
600 SA603RCUL 3 500, 600 690 85/43 50/25 50/25 50/25 50/25 35/18 30/15 40/20 480 85 50 50
800 SA803RCUL 3 700, 800 690 85/43 50/25 50/25 50/25 50/25 35/18 30/15 40/20 480 85 50 50
E 100 EA102CUL 2 60, 70, 75, 80, 90, 100 690 25/13 10/5 10/5 10/5 10/5 7.5/4 5/3 240 14
100 EA103CUL 3 60, 70, 75, 80, 90, 100 690 25/13 10/5 10/5 10/5 10/5 7.5/4 5/3 240 14
S series/4-pole
Frame 50A 100A 225A
Pole 4 4 4
Type Page 06/43 SA54B SA104R SA204R
Rated current (Amps) 5, 10, 15, 20 15, 20, 30, 40 125, 150, 175
Ambient temp.: 40C for general use 30, 40, 50 50, 60, 75, 100 200, 225
Rated insulation voltage Ui (Volts) AC 660 660 660
Rated JIS C8370 sym 550V AC 2.5 35 35
breaking 460V AC 7.5 42 42
capacity 220V AC 10 85 85
(kA)
Dimensions a d a 100 120 140
c
(mm) b 130 155 165
c 60 82 82.5
b
S series/4-pole
Frame 400A 600A 800A
Pole 4 4 4
Type Page 06/43 SA404HA SA604H SA804H
Rated current (Amps) 250, 300 500, 600 700, 800
Ambient temp.: 40C for general use 350, 400
Rated insulation voltage Ui (Volts) AC 660 660 660
Rated JIS C8370 sym 550V AC 35 35 35
breaking 460V AC 42 42 42
capacity 220V AC 85 85 85
(kA)
Dimensions a d
c
a 185 280 280
(mm) b 257 275 275
c 103 103 103
b
b
Rated operating voltage [UL508] (V AC) Page 06/66 d 80
Dimensions (mm) a 210 Mass (kg) Front mounting type 1.0
a d
c b 275
Tripping device Hydraulic-magnetic
Page 06/66
b c 103
d 146 Trip button Provided
Mass (kg) Front mounting type 10 Front mounting, front connection No-mark
Tripping device Thermal-magnetic rear connection X
Front mounting, front connection No-mark Flush mounting, rear connection E
Front mounting, rear connection X top & bottom connection Y
Plug-in mounting P
Flush mounting, rear connection E
Draw-out D
Flush mounting, top & bottom connection Y 06
Internal accessories Pege 06/88
Plug-in mounting P
Alarm switch K BZ-K25B
IEC 35mm wide rail mounting Auxiliary switch W BZ-W25B
Internal accessories Page 06/88 Undervoltage trip R
Alarm switch K BZ-K70B Shunt trip F BZ-F25BT
Alarm switch with terminal block KA BZ-K70BA External accessories
Auxiliary switch W BZ-W70B Motor operating mechanism M
Padlocking device Q
Auxiliary switch with terminal block WA BZ-W70BA BZ-M120C-4
Mechanical interlocking device M1
Undervoltage trip R BZ-R70B- Operating handle N type N BZ-N20C
Shunt trip F BZ-F70B- Operating handle V type V BZ-V20C
Shunt trip with terminal block FA BZ-F70BA- Steel enclosure C
External accessories Steel enclosure with V type handle CV
Motor operating mechanism M Terminal cover Short TS BZ-TS20B-4
Handle padlocking device Cap type Q1 Terminal cover Long TB BZ-TB20B-4
Plate type Q2 Insulation barrier Interphase B
Insulation barrier Earth BL
Mechanical interlocking device M1 BZ-M170C
M2 BZ-M270C Available Not available Factory-mounted accessory
M3 BZ-M370C
Operating handle N-type N BZ-N70C
Operating handle V-type V BZ6V70C
Steel enclosure Direct operating C BZ-C70B
Dustproof steel enclosure Handle operating CV BZ-CV70C
Rainproof steel enclosure Handle operating CW
Terminal cover Short TS
Terminal cover Long TB BZ-TB70B
Insulation barrier Interphase *2 B B-43A
Insulation barrier Earth BL
Handle locking cover L BZ-L70B
Flat terminal S
Notes: *1 Icu: Rated ultimate short-circuit breaking capacity
Ics: Rated service short-circuit breaking capacity
*2 Interphase insulation barriers are standard provided for the front mounting
type breakers.
d 102 82 82 127
Mass (kg) Front mounting type 1.1 1.1 1.2 1.1 1.2 2.3
Tripping device Hydraulic-magnetic Thermal-magnetic Thermal-magnetic Thermal-magnetic
Trip button Provided Provided Provided Provided
Front mounting, front connection No-mark
rear connection X
Flush mounting, rear connection E
top & bottom connection Y
Plug-in mounting P
Draw-out D
Internal accessories Page 06/88
Alarm switch K BZ-K23B BZ-K35B BZ-K35B BZ-K50B
Auxiliary switch W BZ-W23B BZ-W35B BZ-W35B BZ-W50B
Undervoltage trip R BZ-R23BT BZ-R35BT BZ-R35BT BZ-R50BT
Shunt trip F BZ-F23BT BZ-F35BT BZ-F35BT BZ-F50BT
External accessories
Motor operating mechanism M
Padlocking device Q
Mechanical interlocking device M1 BZ-M120C-3 BZ-M130C-3 BZ-M130C-3 BZ-M140C
Operating handle N type N BZ-N20C BZ-N30C BZ-N30C BZ-N50C
Operating handle V type V BZ-V20C BZ-V30C BZ-V30C BZ-V50C
Steel enclosure C BZ-C30B-3 BZ-C30B-3 BZ-C50B
Steel enclosure with V type handle CV BZ-CV30C BZ-CV30C
Terminal cover Short TS BZ-TS30B-3 BZ-TS30B-3 BZ-TS50B
Terminal cover Long TB BZ-TB30B-3 BZ-TB30B-3 BZ-TB50B
Insulation barrier Interphase B BZ-B30B (Line), B35B (Load) BZ-B30B BZ-B30B BZ-B50B
Insulation barrier Earth BL BZ-BL20B-3 BZ-BL35B BZ-BL35B BZ-BL50B
H series/2, 3-pole
Frame 225A 400A
Pole 2 3 3 2 3 3
Type Page 06/43 H202BA H203BA H203R H402B H403B H403R
Rated current (Amps) 125, 150, 175 125, 150, 175 250, 300 250, 300
Ambient temp.: 40C for general use 200, 225 200, 225 350, 400 350, 400
45C for marine use
Rated insulation voltage Ui (Volts) AC 690 660 690 690
DC 250 250 250 250
Rated JIS C8370 sym 550V AC 35 42 42 85
breaking 480V AC 65 85 65 125
capacity 220V AC 125 125 125 125
(kA) 250V DC 40 40 40 40
IEC 609472 690V AC
[Icu/Ics] 660V AC
600V AC 25/7 35/18
500V AC 35/9 42/21 85/43
440V AC 65/17 65/33 125/63
400V AC 65/17 65/33 125/63
230V AC 125/32 125/63 125/63
250V DC 40/10 40/20 40/20
NK sym 500V AC 65 85 50
250V AC 100 125 125
250V DC
a d
Dimensions c a 105 105 140 140
(mm) b 165 165 257 257
Page 06/70 c 60 99 103 103
06
b
Notes: The breaking capacity for the 240V, 380V and 415V circuits are equivalent to that of 230V, 400V and 440V, resprctively.
Interphase insulation barriers are standard provided for the front mounting type breakers.
H series/3-pole
Frame 600A 800A
Pole 3 3 3 3
Type Page 06/42 H603B H603R H803B H803R
Rated current (Amps) 500, 600 500, 600 700, 800 700, 800
Ambient temp.: 40C for general use
45C for marine use
Rated insulation voltage Ui (Volts) AC 690 690 690 690
DC 250 250 250 250
Rated JIS C8370 sym 550V AC 42 85 42 85
breaking 480V AC 65 125 65 125
capacity 220V AC 125 125 125 125
(kA) 250V DC 40 40 40 40
IEC 60947-2 690V AC
[Icu/Ics] 660V AC
600V AC 35/18 35/18
500V AC 42/21 85/43 42/21 85/43
415V AC 65/33 125/63 65/33 125/63
380V AC 65/33 125/63 65/33 125/63
240V AC 125/63 125/63 125/63 125/63
250V DC 40/20 40/20 40/20 40/20
NK sym 500V AC 50 50
250V AC 125 125
250V DC
Dimensions a d a 210 210 210 210
c
(mm) b 275 275 275 275
c 103 103 103 103
b
Notes: Interphase insulation barriers are standard provided for the front mounting type breakers. Available Not available Factory-mounted accessory
Motor protection breakers of the motor and offers protection the rush current produced at the time of
Motors are normally controlled by against sustained overload currents. starting the motor. They will trip in the
MCCBs and magnetic starters. In this These are the motor breakers which face of sustained overcurrent when the
case the MCCB carries out overcurrent combine the two functions. integrated bimetal relay has operated.
or short-circuit current protection while FUJI motor breakers are designed to
the starter deals with ON-OFF switching eliminate erroneous operations due to
L and H series/3-pole
Frame 50A
Pole 3 3
Type Page 06/43 LA53BM H53BAM
Rated current (Amps) *1 5, 8, 10, 12 16, 24, 32, 40, 45
Ambient temp.: 40C for general use
45C for marine use
Rated insulation voltage Ui (Volts) AC 660 660
DC
Rated JIS C8370 sym 550V AC 42 42
breaking 480V AC 50 65
capacity 220V AC 100 125
(kA)
IEC60947-2 600V AC 35/9
[Icu/Ics] 500V AC 42/21 42/11
440V AC 50/25 65/17
400V AC 60/30 65/17
230V AC 100/50 125/32
NK sym 500V AC 50 65
250V AC 100 100
a d 75 90
Dimensions c a
(mm) b 150 155
Page 06/70 c 82 60
b
d 102 82
Mass (kg) Front mounting type 1.1 1.4
Tripping device Hydraulic-magnetic Thermal-magnetic
Trip button Provided
Front mounting, front connection No-mark
rear connection X
Flush mounting, rear connection E
top & bottom connection Y
Plug-in mounting P
Draw-out D
Internal accessories Page 06/88
Alarm switch K BZ-K23B BZ-K35B
Auxiliary switch W BZ-W23B BZ-W35B
Undervoltage trip R BZ-R23BT BZ-R35BT
Shunt trip F BZ-F23BT BZ-F35BT
External accessories
Motor operating mechanism M
Padlocking device Q
Mechanical interlocking device M1 BZ-M120C-3 BZ-M130C-3
Operating handle N type N BZ-N20C BZ-N30C
Operating handle V type V BZ-V20C BZ-V30C
Steel enclosure C BZ-C30B-3
Steel enclosure with V type handle CV BZ-CV30C
Terminal cover Short TS BZ-TS30B-3
Terminal cover Long TB BZ-TB30B-3
Insulation barrier Interphase B BZ-B30B (LINE), B35B (LOAD) BZ-B30B
Insulation barrier Earth BL BZ-BL20B-3 BZ-BL35B
Notes: *1 For further information related to motor capacity, see page 06/50. Available Not available Factory-mounted accessory
Circuit configuration and breaker application for control Item NEC430.53 Group Installation
panels of industrial machinery in North America.
UL508A (Industrial control panels) requirements UL489 UL508
Listed Listed Includes an isolating function.
1. The requirements of NFPA70 (NEC), NFPA79, and
applicable UL standards must be satisfied. SA/EA-UL
series 1 Applicable to motor loads
2. Positioning of protective equipment
Install branch circuit protection (BCP) for the main circuit at
the point of electrical inlet. 2 Applicable to other general use loads
Use equipment that is UL508 listed as applicable to each
kind of loads, installed under appropriate load conditions,
as protective equipment for load circuits used in branch 3 Applicable to resistance loads (heaters)
circuits downstream from the BCP.
Group Installation
Frame 60A
Pole 2 3 2 3
Type SA62C -CE SA63C -CE SA62RC -CE SA63RC -CE
Rated operating voltage (V AC) 600 600
Max. motor ratings Rated current (A) 60 60
(HP) 3-phase 550 (-600) V AC *2 25 25
1
UL508 [cUL] * 440-480V AC 20 20
220-240V AC 10 10
110-120V AC
Single- 550 (-600) V AC *2 15 15
phase 440-480V AC 10 10
220-240V AC 5 5
110-120V AC
Load (A) Resistance *3 60 60
UL508 [cUL] Discharge lamp *4 30 30
Incandescent lamp *3 60 60
Others *3 60 60
Notes: *1 The performance of UL508 approved models is indicated as applicable motor rating (HP).
*2 Rated operating voltage 550-600V AC: For SA50C, 50RC, 60C and 60RC.
*3 Rated current x 1
*4 Rated current x 1/2
BASIC DESIGN
Bar stud SA100C EA225C Bar stud SA100C EA225C Round stud SA100C
terminal SA100RC EA400C terminal SA100RC EA400C terminal SA100RC
SA225C EA600C SA225C EA600C
SA225RC EA800C SA225RC EA800C
SA400C SA400C
SA400RC SA400RC
SA600RC SA600RC
SA800RC SA800RC
Front
Front
Flat terminal Flat terminal
Self lifting screw Breaker type Size Hexagonal head bolt Breaker type Size
SA30C EA30AC M5 14 SA400C EA400C M12 35
SA50C EA50AC SA400RC
SA50RC EA50C
Direct connection
06
or
Front
Flat terminal
Flat terminal connection
Flat terminals are required.
Self lifting screw Breaker type Size
Breaker termination
MCCB type Front connection Rear connection Flush mounting Plug-in mounting
X E Y P
SA30AC, SA50C, SA50RC
EA30AC, EA50C, EA50AC
Self-lifiting
terminal
SA60C, SA60RC
EA60C, EA100C, EA100AC
SA100C, SA100RC
Flat terminal
SA225C, SA225RC
EA225C
Flat terminal
SA400C, SA400RC
SA600RC, SA800RC
EA400C, EA600C, EA800C
Flat terminal 90 rotational stud
SA 5 3 C M / 50 X Q2 M1 - CE (CCC)
Series Standard
SA: S series CE: IEC and CE marking conformed
EA: E series (CCC): CCC approved
External accessories
Operating handles (N and V-type), terminal covers, insulation
barrier, steel enclosures, handle locking covers, kits for mounting
modification, flat terminal, mechanical interlock device
Factory-mounted accessories
External accessories
Handle padlocking devices/Q1 and Q2, motor-operating
mechanism/M, under voltage trip device for SA100, SA225 and
EA225 only
SA 5 4 B / 50 E Q2 M W C
Series Enclosure
SA: S series C: Steel enclosure
EA: E series CV: Steel enclosure with V handle
F: F series
H: H series Accessory
L: L series W: With auxiliary switch
K : With alarm switch
Frame size F : With shunt tripping device
5: 50AF R : With undervoltage tripping device
10: 100AF (Provided terminal block)
20: 225AF
40: 400AF Operating device
60: 600AF Blank: Manual operation
80: 800AF M: Motor operating mechanism
100: 1000AF
120: 1200AF Handle padlocking device
160: 1600AF Q1: Cap type
Q2: Plate type
Number of poles
1: 1-pole Mounting and connection
2: 2-pole Blank: Front mounting, front connection
3: 3-pole X: Front mounting, rear connection
4: 4-pole (to either metal or insulating panel)
E: Flush mounting, rear connection
Operating characteristics Y: Flush mounting, top & bottom connection
Blank: For line protection P: Plug-in mounting
M: For motor protection D: Draw-out
Ordering information
Specify the following:
1. Type number
2. Optional accessories
Lead wire or terminal block connection
3. When ordering MCCB with shunt tripping device, undervoltage
tripping device or motor operating mechanism, specify rated
voltage and frequency.
4. Handle type if required
Padlocking device
Q1: Cap type padlocking device
Terminal combination
See table below.
Rated current
See page 06/51.
Terminal combination
Code Terminal position Applicable breaker type
Line Load SA50RCUL SA100CUL SA400CUL SA600RCUL SA800RCUL/800
EA100CUL SA100RCUL SA400RCUL SA800RCUL/700
SA225CUL
SA225RCUL
Blank Screw Screw
L Block terminal Block terminal
L1 Flat terminal Flat terminal
L3 Screw Flat terminal
L4 Flat terminal Screw
L5 Screw Block terminal
L6 Block terminal Screw
L7 Flat terminal Block terminal
L8 Block terminal Flat terminal
Available Not available
S series, 2-pole IEC and CE marking conformed S series, 3-pole IEC and CE marking conformed
Breaker Rated Type : Available Breaker Rated Type : Available
ampere current mounting and ampere current mounting and
frame (A) connection frame (A) connection
30 3 SA32C/3 -CE Blank, X, E, Y, P 30 3 SA33C/3 -CE Blank, X, E, Y, P
5 SA32C/5 -CE 5 SA33C/5 -CE
10 SA32C/10 -CE 10 SA33C/10 -CE
15 SA32C/15 -CE 15 SA33C/15 -CE
20 SA32C/20 -CE 20 SA33C/20 -CE
30 SA32C/30 -CE 30 SA33C/30 -CE
50 5 SA52C/5 -CE Blank, X, E, Y, P 50 5 SA53C/5 -CE Blank, X, E, Y, P
10 SA52C/10 -CE 10 SA53C/10 -CE
15 SA52C/15 -CE 15 SA53C/15 -CE
20 SA52C/20 -CE 20 SA53C/20 -CE
30 SA52C/30 -CE 30 SA53C/30 -CE
40 SA52C/40 -CE 40 SA53C/40 -CE
50 SA52C/50 -CE 50 SA53C/50 -CE
10 SA52RC/10 -CE Blank, X, E, Y, P 10 SA53RC/10 -CE Blank, X, E, Y, P
15 SA52RC/15 -CE 15 SA53RC/15 -CE
20 SA52RC/20 -CE 20 SA53RC/20 -CE
30 SA52RC/30 -CE 30 SA53RC/30 -CE
40 SA52RC/40 -CE 40 SA53RC/40 -CE
50 SA52RC/50 -CE 50 SA53RC/50 -CE
60 60 SA62C/60 -CE Blank, X, E, Y, P 60 60 SA63C/60 -CE Blank, X, E, Y, P
SA62RC/60 -CE Blank, X, E, Y, P SA63RC/60 -CE Blank, X, E, Y, P
100 15 SA102C/15 -CE Blank, X, E, P 100 15 SA103C/15 -CE Blank, X, E, P
20 SA102C/20 -CE 20 SA103C/20 -CE
30 SA102C/30 -CE 30 SA103C/30 -CE
40 SA102C/40 -CE 40 SA103C/40 -CE 06
50 SA102C/50 -CE 50 SA103C/50 -CE
60 SA102C/60 -CE 60 SA103C/60 -CE
75 SA102C/75 -CE 75 SA103C/75 -CE
100 SA102C/100 -CE 100 SA103C/100 -CE
15 SA102RC/15 -CE Blank, X, E, P 15 SA103RC/15 -CE Blank, X, E, P
20 SA102RC/20 -CE 20 SA103RC/20 -CE
30 SA102RC/30 -CE 30 SA103RC/30 -CE
40 SA102RC/40 -CE 40 SA103RC/40 -CE
50 SA102RC/50 -CE 50 SA103RC/50 -CE
60 SA102RC/60 -CE 60 SA103RC/60 -CE
75 SA102RC/75 -CE 75 SA103RC/75 -CE
100 SA102RC/100 -CE 100 SA103RC/100 -CE
225 125 SA202C/125 -CE Blank, X, E, P 225 125 SA203C/125 -CE Blank, X, E, P
150 SA202C/150 -CE 150 SA203C/150 -CE
175 SA202C/175 -CE 175 SA203C/175 -CE
200 SA202C/200 -CE 200 SA203C/200 -CE
225 SA202C/225 -CE 225 SA203C/225 -CE
125 SA202RC/125 -CE Blank, X, E, P 125 SA203RC/125 -CE Blank, X, E, P
150 SA202RC/150 -CE 150 SA203RC/150 -CE
175 SA202RC/175 -CE 175 SA203RC/175 -CE
200 SA202RC/200 -CE 200 SA203RC/200 -CE
225 SA202RC/225 -CE 225 SA203RC/225 -CE
400 250 SA402C/250 -CE Blank, X, E, P 400 250 SA403C/250 -CE Blank, X, E, P
300 SA402C/300 -CE 300 SA403C/300 -CE
350 SA402C/350 -CE 350 SA403C/350 -CE
400 SA402C/400 -CE 400 SA403C/400 -CE
250 SA402RC/250 -CE Blank, X, E, P 250 SA403RC/250 -CE Blank, X, E, P
300 SA402RC/300 -CE 300 SA403RC/300 -CE
350 SA402RC/350 -CE 350 SA403RC/350 -CE
400 SA402RC/400 -CE 400 SA403RC/400 -CE
600 500 SA603RC/500 -CE Blank, X, E, P, D
Mounting Connection 600 SA603RC/600 -CE
Front Front Blank 800 700 SA803RC/700 -CE Blank, X, E, P, D
Front Rear X 800 SA803RC/800 -CE
Flush Rear E
Flush Top and bottom Y
Plug-in P
Draw-out D
UL489 Listed
S and E series, 2-pole S and E series, 3-pole
Breaker Rated Type : Available Breaker Rated Type : Available
ampere current terminal combination ampere current terminal combination
frame (A) frame (A)
Dimensions, mm
Front mounting, front connection
17
43
Breaker
Breaker
CL 7
CL
R2 or less
ON
M5 x 14
40
52 or
more
CL
84
CL
24
100
C
50
84
24
42
.5
5
Max. 15
50 or more t4
7
25 51 Insulation barriers
47.5 Trip button 4 8 60 Standard provided: SA52C, SA52RC
50 84 Optional:SA32C
17
Counter bore 7.8 CL 43
Breaker Breaker 7
M4 or 5 CL CL
R2 or less
ON
M5 x 14
40
52 or
more
84
CL
24
100
CL
50
84
42
.5
5
Max. 15
25
74 or more t4
7
Trip button 51
50 Insulation barriers
4 8 60
72 Standard provided: SA53C, SA53RC
84
75 Optional: SA33C
CL or CL
le
ss
7
ON
40
M8 x 15
52 or
more
CL CL
84
CL
100
50
84
24
24
42
9
50 or more
Max. 15
25 51 t6
47.5 Trip button 4 8 60
50 84 7
Dimensions, mm
Front mounting, front connection
17
43
R2
or CL 7
M4 or 5 CL le
ss
ON M8 x 15
40
52 or
more
CL CL
84
100
CL
50
84
24
42
25 74 or more
9
Max. 15
50 51 t6
72 4 8 60
75 Trip button 84 7
SA102C -CE
Panel drilling Front panel cutting Terminal section
CL Insulation barrier
2.5 Detachable
56
06
17
Mounting hole 51 4.5
Breaker Breaker
50
C
L M4 or 5 C 10 8.5
L
8.5
4.5
R2
or
M8 x 14
les
47
s
ON
22
more
52 or
132
155
135
102
C C
50
L C L
24
L
17
C
L
22
Trip button
9
2
Max 16.5
30
6 60 t6
56 58 or more
82
60 8
SA103C -CE
Panel drilling Front panel cutting Terminal section
56
34.5 Insulation barrier 51 4.5
Mounting hole
17
C
L M4 or 5 C
L
R2
8.5
C
4.5
L 10 8.5
or
les
s
47 M8 x 14
ON
22
more
52 or
135
102
155
C
132
50
C
L C
L C
L L
17
24
37
Trip button
9
2
Max 16.5
60
85 6 60 30 87 or more
t6
90 82
8
Dimensions, mm
Front mounting, front connection
17
C C
50
L L
R2
C M4 or 5
8.5
L 4.5
or
les
s
10 8.5
47
ON M8 x 14
more
52 or
22 C
132
135
102
L
155
C
50
C C
L L
L
17
37
24
Trip button
60 2 9
30 87 or more
MAX. 16.5
85 6 60
90 82 t6
Note: 2-pole breaker is supplied in 3-pole frame with current
8
carrying parts omitted from center pole.
25.5
C
L C
L
C
L
8.5
4.5
R2
or
le 10.5 11
ss
47
M8 x 16
14.5
ON
more
52 or
126
165
144
C C
102
L L
50
C
L C
L
22
24
44
Trip button 9
Max.25
70 2 t6
35 M4 or 5 102 or more
100 6 60
8
105 84
Note: 2-pole breaker is supplied in 3-pole frame with current
carrying parts omitted from center pole.
CL CL Breaker
13.5
R
40.5
2
or
le
ss
51 84
ON
92 or more
24.5
214-216
C
L CL
C CL
102
L
90
225
257
44
53 8
40.5
Dimensions, mm
Front mounting, front connection
Panel drilling Front panel cutting
SA603RC -CE Insulation barrier
Detachable 7
C
L Mounting hole
38.5
Breaker M6 or 7 Breaker
105
87
14.5
C
L C
L
7
R2 or less
51 47
ON
24.5
92 or
more
102
243
C
L C
90
L
275
243
41.5
53 7
32 8
70 207 or more
87
15
44 94.5
Trip button
140 103
205 M12x 40 bolt 4.5 107
210 146
SA803RC -CE
Insulation barrier Panel drilling Front panel cutting
Detachable 10
CL Mounting hole
41.5
Breaker M6 or 7 Breaker
105
87
06
14.5
CL CL
7
R2 or less
51 47
ON
24.5
92 or
more
243
102
CL CL
90
275
243
44.5
53 10
32 8
87
70 207 or more
15
4-pole
3-pole
80
CL Breaker
13 N
Extension handle
Mounting hole
(Detachable)
78
310
370
338
CL CL CL CL
95
28 18
M8
Mounting
8 screw
70 9
80
105
45 70 70 70 14 29
140 105 175 17 120
210 280 80 171
Dimensions, mm
Front mounting, front connection
SA1603E, SA1604E
3-pole 4-pole
Panel drilling
CL CL 20 11
Insulation panel 4-pole
100
3-pole
30
CL Breaker
N
Extension handle
32.5
(Detachable)
78
310
370
338
CL CL CL CL
95
28 18
M8
Mounting
screw
20
8 70 9
100
105
32
20 46
15
45 70 70 70
17 140
70 70 105 13 80 191
210 280
SA54B
Panel drilling Front panel cutting Terminal section
56
Insulation barrier
Detachable 51 2.5
Mounting
17
hole
50
C
L
8
C C C
130
115
L L L
84
C
50
L M5 14
24
14 25
37.5 72 or more 5.5
Max.15
25 25 25
Trip button
70 3 60
100 4 80 7
SA104R
Insulation barrier Panel drilling Front panel cutting Terminal section
85 78
Detachable
73 4.5
Mounting
hole
50
C
L
4.5
17
8.5
Breaker R Handle
M4 or 5 C C Breaker
L 2 L
or 10 8.5
22 26 le
ss
52 or more
ON
16.5
132
C C M8 14
155
L L
50
102
C
135
C
L L
24
37 30 9
Max.16.5
45 87 or more
30 30 30 4 82 8
Trip button
120 4 104
Dimensions, mm
Front mounting, front connection
SA204R Mounting
hole Insulation barrier Panel drilling Front panel cutting Terminal section
Detachable
74 3
Trip button
80
23.5
C Handle Handle
L
8.5
Breaker R
4.5
M4 or 5 C C
L Breaker
L 2
or 10.5 11
le
ss
22
52 or more
26
M8 x 20
126
ON C
L C
L
16
102
165
144
50
24
L C
L
35
40 52.5 102 or more
10
Max.23
35 35 35 78
100 4 82.5 9
140 3.5 109
SA404HA
Handle
Panel drilling Front panel cutting
CL 45
25 8
Mounting hole
06
13.5
40.5
Handle
7
M6 or 7 Handle
Breaker Breaker
CL CL
62 84
R6
214 to 216
ON
97
257
120
99
CL CL CL CL
64.5
44 70.5 70.5
55 8
44 64
15
40.5
97
52.5 52.5 52.5 Trip button
7 103
185 M12 35 bolt 134
SA604H, 804H
Panel drilling Front panel cutting
Handle
C
L 38.5(41.5)
7(10) Handle Handle
Mounting hole
Extension M6 or 7 CL Breaker CL Breaker
70
14.5
handle
62 R6
47
243
99
120
97
275
C
L C
L C
L C
L
73
105
80 105
8
70
15 32
70 64
44 7(10)
70 70 70 41.5(44.5)
280 M12 40 bolt 97
7.5 103
Trip button
149
( ): For SA804H
240
Dimensions, mm
Front mounting, rear connection (type X)
Panel drilling
SA32C -CE, 52C -CE, 52RC -CE
Panel
Insulation base C
L
C Terminal cover M4 or 5 C
L L
3
ON
110
100
137
110
C
50
84
84
C
L C
L L
45
95
8
Trip button Breaker
47.5 50.5 25
22
8
50 59 14
4 8 68 6.5
92 M6 x 18 bolt 25
ON
110
100
137
110
84
CL CL CL
50
84
45
95
8
59 50
72 14
4 8 68 6.5
75 25 25
92 M6 x 18 bolt
Dimensions, mm
Front mounting, rear connection (type X)
Panel
Insulation base
CL
CL Terminal cover CL
M4 or 5
3
ON
100
110
137
110
84
50
84
CL CL CL
45
95
8
Trip button Breaker
47.5 25
50.5 22
8
50
59 14
4 8 68 6.5
92 M6 x 18 bolt 25
Terminal cover
Panel CL
M4 or 5 CL
CL
Insulation base 06
3
ON
110
84
CL
100
137
110
CL CL
50
84
45
95
8
75
59 14
4 8 68 6.5
92 M6 x 18 bolt 25 25
ON
22
15
37
135
132
155
135
C
102
50
C C L
L L
87
Trip button
15
16
8.5 18 30
5
56 M8 x 25 bolt 30 M4 or 5
56
2 60
60 Note: At shipment,studs are mounted on the MCCB unit as shown
6 82 in the figure for side view.
Studs for line side terminal : Mounted horizontally.
Studs for load-side terminal : Mounted vertically.
Each stud can be turned by 90.
Dimensions, mm
Front mounting, rear connection (type X)
5
5
ON
22
15
37
102
135
135
132
50
155
C C
L C
L
L
87
15
Trip 16
button
8.5
5
M8 x 25 bolt 18
85 56 30 30 30
M4 or 5
90 2 60 60
6 82
Note: At shipment, studs are mounted on the MCCB unit as shown in the figure for side view.
Studs for line side terminal : Mounted horizontally.
Studs for load-side terminal : Mounted vertically.
Each stud can be turned by 90.
Breaker
ON
22
15
37
102
135
135
132
50
155
C C
L C
L
L
87
15
Trip 16
button
5
8.5 18
85 56 30 30 30
M8 x 25 bolt M4 or 5
2 60 60
90
6 82
Note: At shipment, studs are mounted on the MCCB unit as shown in the figure for side view.
Studs for line side terminal : Mounted horizontally.
Studs for load-side terminal : Mounted vertically.
Each stud can be turned by 90.
2-pole breaker is supplied in 3-pole frame with current carrying parts omitted from center pole.
L
5
165
126
144
102
C C
144
C
50
L L L
57.5
20
93.5
Trip
button
14
22
9 35
5
100 56 Max. 6 24
35 35 M4 or 5
M8 x25 bolt 70
105 2 60
6 84 Note: At shipment, studs are mounted on the MCCB unit as shown in the figure for side view.
Studs for line side terminal : Mounted horizontally.
Studs for load-side terminal : Mounted vertically.
Each stud can be turned by 90.
2-pole breaker is supplied in 3-pole frame with current carrying parts omitted from center pole.
Dimensions, mm
Front mounting, rear connection (type X)
8
4.5
CL
5 5
15
51
ON Angle
225
CL
160
215
225
102
CL CL
266
257
90
CL
M12x 25 bolt M6 or 7
13
35
31
5
16
15
12 27 15 Insulation
5
4.5
SA603RC -CE
Panel drilling Angle mounting
Breaker
Panel Live section CL CL
Mounting hole
5
cover
CL Breaker 06
11
10
CL
10
15
51 243
CL
413
ON
160
CL
102
297
CL
275
90
243
10
CL Angle
5
48
15
M6 or 7 70
Insulation
43
140 Angle
125
barrier 178 7
11
Trip button 13
12 8 32 20
M12 x 40 bolt Note: At shipment, studs are mounted on the MCCB unit as shown in the figure for side view.
106.5 85 Studs for line side terminal : Mounted horizontally.
4.5 115 97 Studs for load side terminal : Mounted vertically.
4 Each stud can be turned by 90.
158 180
SA803RC -CE
Panel drilling Angle mounting
CL
11
15
11
10
51
243
ON
160
CL CL
243
413
CL
102
297
275
90
CL
Angle M6 or 7
10
15
5
45
125
7
Insulation 48 178
11
70 70 70
barrier
210 140
Angle
12 8 32 20 40x 40x 5
106.5 85 14
M12 x 40 bolt Note: At shipment, studs are mounted on the MCCB unit as shown in the figure for side view.
4.5 115 97
Studs for line side terminal : Mounted horizontally.
4
158 180 Studs for load side terminal : Mounted vertically.
Each stud can be turned by 90.
Dimensions, mm
Front mounting, rear connection (type X)
73
34
120
C C
172
338
L L C
L of window
258
15
98
L
32 8
111
6
140
R
73
13
13
15
45
70 70 70
70 70 81
Panel 50 Insulation tube
21 230 300
for center pole
Panel cutting dimensions include space
of 1.5mm to the handle window frame.
SA1603E, SA1604E
Panel drilling Panel cutting
4-pole 4-pole
3-pole 4-pole
3-pole 3-pole
Mounting angle CL CL CL 9 CL
M6 Mounting screw Breaker
73
12
34
65
30
45
CL of
172
338
CL CL CL
window
15
98
115
Connecting length 30
6
R
30
73
15
70 70 70
70 70 81
70
85 230 300
Insulation tube
115
130 Panel cutting dimensions include space
of 1.5mm to the handle window frame.
Dimensions, mm
Front mounting, front connection
17
Counter bore 7.8 43 M4 or 5
Breaker Breaker 7
CL CL
ON R2 or less
40
M5 x 14
52 or
more
CL
84
CL
100
CL
50
84
24
24
42
.5
5
Max. 15
50 or more t4
51 Insulation barriers
25
4 8 60 7
47.5 Trip button Standard provided: EA52C
84 Optional: EA32AC, EA52AC
50
17
Counter bore 7.8 CL 43
Breaker 7
M4 or 5 Breaker
CL CL
ON R2 or less
40
M5 x 14
52 or
more
CL
84
100
CL CL
50
84
24
42
.5
25 5
Max. 15
74 or More t4
50 51 Insulation barriers 7
Trip button 4 8 60
72 Standard provided: EA53C
84 Optional: EA33AC, EA53AC
75
EA62C -CE
46 2.5
Insulation barrier CL
Detachable Panel drilling Front panel cutting Terminal section
Mounting hole 4.9
50
CL or CL
le
ss
7
ON
40
M8 x 15
52 or
more
CL CL
84
CL
100
50
84
24
24
42
9
50 or more
Max. 15
25 51 t6
47.5 Trip button 4 8 60
50 84 7
Dimensions, mm
Front mounting, front connection
17
43
R2
or CL 7
M4 or 5 CL le
ss
ON M8 x 15
40
52 or
more
CL CL
84
100
CL
50
84
24
42
25 74 or more
9
Max. 15
50 51 t6
72 4 8 60
75 Trip button 84 7
EA103AC -CE, 103C -CE Panel drilling Front panel cutting Terminal section
Insulation barrier 46 2.5
Detachable
17
50
M8 x 15
2
R
ON
40
24
52 or
more
84
CL
100
CL
50
84
9
Max. 15
42
25 t6
74 or more 7
Trip button 51 Insulation barriers
50
4 8 60 Standard provided: EA103C
72
84 Optional: EA103AC
75
M5 x 14 for EA100C/ 50
EA102C -CE
Panel drilling Front panel cutting Terminal section
Insulation barrier C 46 2.5
Detachable L
17
50
M4 or 5 C C
or
L L M8 x 15
2
R
ON
40
24
52 or
more
84
C
L C
L
100
CL
50
84
24 9
Max. 15
42
t6
50 or more 7
Trip button 51
25
4 8 60
47.5
84
50
M5 x 14 for EA100C/ 50
Dimensions, mm
Front mounting, front connection
25.5
CL CL
CL
8.5
4.5
R2
or
le 10.5 11
ss
47
M8 x 16
14.5
ON
more
52 or
126
165
144
CL CL
102
CL
50
CL
22
24
44
Trip button
9
Max. 25
2 t6
70
6 35 M4 or 5 102 or more
100 60
8
105 84
Note: 2-pole breaker is supplied in 3-pole frame with current
carrying parts omitted from center pole.
CL CL Breaker
13.5
R
06
40.5
2
or
le
ss
51 84
ON
92 or more
24.5
214-216
C
L CL
C CL
102
L
90
225
257
44
53 8
40.5
EA603C -CE
Panel drilling Front panel cutting
Insulation barrier
Detachable 7
C
L Mounting hole
38.5
Breaker M6 or 7 Breaker
105
87
14.5
C
L C
L
7
R2 or less
51 47
ON
24.5
92 or
more
102
243
C
L C
90
L
275
243
41.5
53 7
32 8
70 207 or more
87
15
44 94.5
Trip button
140 103
205 M12x 40 bolt 4.5 107
210 146
Dimensions, mm
Front mounting, front connection
87
14.5 CL CL
7
R2 or less
51 47
ON
24.5
92 or
more
243
102
CL CL
90
275
243
44.5
53 10
32 8
87
70 207 or more
15
EA104B
Panel drilling Front panel cutting Terminal section
56
Insulation barrier
Detachable 51 2.5
Mounting
hole
50
C Handle R Handle
L M4 or 5 Breaker 2 Breaker
8
C
L or C
L 17
le
ss
52 or more
110 to 111
22 49 7.5 8.3
ON C
L C
L
15.7
C
130
115
L
84
C
50
L
25
M8 14
14 37.5 72 or more
24
9
25 25 t6
25
Max.15
Trip button
70 3 60
100 4 80 7
ON
110
C
84
100
137
L
110
50
84
C
L C
L
45
95
8
25 Breaker
Trip button 50.5 22
47.5
8
59 14
50
4 8 68 6.5
92 M6 x 18 bolt 25
Dimensions, mm
Front mounting, rear connection (type X)
3
ON
110
100
137
110
84
CL CL CL
50
84
45
95
8
72 Trip button 22 25
50.5 Breaker
8
75 50
59 14
4 8 68 6.5
92 M6 x 18 bolt 25 25
Panel
Insulation base
CL
CL Terminal cover CL
M4 or 5
06
3
ON
100
110
137
110
84
50
84
CL CL CL
45
95
8
50
59 14
4 8 68 6.5
92 M6 x 18 bolt 25
EA63C -CE
Panel drilling
Terminal cover
Panel CL
M4 or 5 CL
CL
Insulation base
3
ON
110
84
CL
100
137
110
CL CL
50
84
45
95
8
75
59 14
4 8 68 6.5
92 M6 x 18 bolt 25 25
Dimensions, mm
Front mounting, rear connection (type X)
EA102AC -CE
Panel drilling
Panel
Terminal cover C
L
Insulation base
CL M4 or 5 C
L
3
ON
100
137
110
110
C
50
84
84
CL CL L
45
95
8
47.5 Trip button 50.5 25 Breaker
22
8
50 59
14
4 8 68
6.5
92 25
M6 x18 bolt
ON
100
137
110
110
CL
50
84
84
CL CL
45
95
8
22 Breaker
72 Trip button 25
50.5
8
75 50
59 14
4 8 68 6.5
92 25 25
M6 x18 bolt
126
144
CL
165
102
CL
144
CL
50
57.5
20
93.5
14
Trip
button 22
9 24 35
5
100 56 Max. 6 M4 or 5
35 35 70
2 M8 x25 bolt
105 60
6 84 Note: At shipment, studs are mounted on the MCCB unit as shown in the figure for side view.
Studs for line side terminal : Mounted horizontally.
Studs for load side terminal : Mounted vertically.
Each stud can be turned by 90.
2-pole breaker is supplied in 3-pole frame with current carrying parts omitted from center pole.
Dimensions, mm
Front mounting, rear connection (type X)
8
4.5
CL
5 5
15
51
ON Angle
225
CL
160
215
225
102
CL CL
257
266
90
CL
M12 x 35 bolt M6 or 7
13
35
31
5
16
15
12 27 15 Insulation
5
4.5
EA603C -CE
Panel drilling Angle mounting
Breaker
Panel Live section CL CL
Mounting hole
5
cover
Breaker
CL
06
11
10
CL
10
15
243
51
CL
413
ON
160
CL
102
297
CL
275
90
243
10
CL Angle
5
48
15
M6 or 7 70
Insulation
43
140 Angle
125
barrier 178 7
11
Trip button 13
12 8 32 20
M12 x 40 bolt Note: At shipment, studs are mounted on the MCCB unit as shown in the figure for side view.
106.5 85 Studs for line side terminal : Mounted horizontally.
4.5 115 97 Studs for load side terminal : Mounted vertically.
4 Each stud can be turned by 90.
158 180
EA803C -CE
CL
11
15
11
10
51
243
ON
160
CL CL
243
413
CL
102
297
275
90
CL
Angle M6 or 7
10
15
5
45
125
7
Insulation 48 178
11
70 70 70
barrier
210 140
Angle
12 8 32 20 40x 40x 5
106.5 85 14
M12 x 40 bolt Note: At shipment, studs are mounted on the MCCB unit as shown in the figure for side view.
4.5 115 97
Studs for line side terminal : Mounted horizontally.
4
158 180 Studs for load side terminal : Mounted vertically.
Each stud can be turned by 90.
Dimensions, mm
Front mounting, front connection
LA53B 78
Terminal section
70 4.5
Insulation barrier
Load : 16
71
Line : 17
Detachable
Mounting
hole
50
7.5 8.3
C
8
5
Panel drilling Front panel cutting
M4 or 5
C
Load : 24
22 C
L L Breaker
Line : 46
ON R2 or less
Breaker
15.7
10
52 or more
110 to 111
135
150
84
50
C
L of handle C
L
C
L C C M5 14
L L
14
7
Max.12.5
25
72 or more
50 Trip button
70 82 5.5
Live t4
75 section cover 102
85 56
Panel drilling Front panel cutting Terminal section
34.5 51 4.5
Insulation barrier
Detachable
Mounting M4 or 5 Breaker Breaker M8 14
8.5
C
L C
L
hole
50
4.5
R
8.5
C
L
2
or
le
ss
10
17 24
52 or more
26
22
132
ON C
L C
L 9
16.5
Max.16.5
135
155
102
50
C
L C
L
t6
37
8
30 87 or more
60 4 60
90 Trip button 4 82
Note: 2-pole breaker is supplied in 3-pole frame with current
carrying parts omitted from center pole.
H202BA, H203BA
Insulation barrier
Detachable Panel drilling Font panel cutting Terminal section
52 3 Hexagonal head bolt
Mounting M8 20
Breaker
80
hole Breaker
11
C M4 or 5 C
L L
4.5
C
8.5
L
R
2
or
l es
10.5
24
s
22 47 25.5
52 or more
ON
14.5
9
102
144
165
50
126
C
L C
L C
L C
L
Max.25
44 t6
Trip button 8
70 56
4 35 102 or more
100 60
105 3.5 84
Dimensions, mm
Front mounting, front connection
H103R, H203R
Terminal section
Insulation barrier Panel drilling Front panel cutting
Detachable 90.5 3
80
23.5
Breaker Breaker C
Mounting hole L M4 or 5
C L
C R2 or
L
4.5
8.5
less 10.5 11
52 or more
126
C
L C
L
22 26
ON
24
16
M8 20
102
144
165
C C
50
L L Hexagonal
35
head bolt
40 102 or more
Max.23
8
Trip button 9
70 94.5 T6
100 4 99
Note: 2-pole breaker is supplied in 3-pole frame with current
3.5 carrying parts omitted from center pole.
105 126
M6 or 7 Breaker
13.5
Breaker
40.5
C
L R C
8
2 L
or
le
51 ss
84
24.5 *2
92 or more
ON
214 to 216
225
257
102
C
90
L C
L C
L C
L
53*1 44
8
50
44 137 or more
15
44 44 94.5
Trip button 103
56 56
135 M12 35 bolt 4.5 107
*1 46 for H403R Note: 2-pole breaker is supplied in 3-pole frame with
140 146
*2 42 for H403R current carrying parts omitted from center pole.
Breaker M6 or 7
70
14.5
C C
L Breaker
L
R
7
2
or
le
51 47 ss
92 or more
ON
24.5
275
243
243
102
C C
90
C
L L C
L L
41.5
53 7
8
44 207 or more
70
70
32
94.5
15
Dimensions, mm
Front mounting, front connection
Insulation barrier
H803B, H803R Detachable 10
Mounting hole
Panel drilling Front panel cutting
C
L 41.5
105
Breaker M6 or 7
70
14.5
C C
L Breaker
L
R
7
2
or
le
51 ss
47
92 or more
ON
24.5
275
243
243
102
C C
90
C
L L C
L L
44.5
53 10
8
44 207 or more
70
70
32
94.5
15
Terminal Panel
Mounting hole cover
C 37
L
5
132
135
37
22
15 15
87
ON
102
155
16
135
50
C
L C
L
8.5
30
M8 25 bolt 18
30 30 60 M4 or 5
L
5
144
126
ON
144
102
165
50
57.5
C
L C
L
93.5
14 20
9 22
Trip button M8 25 bolt 35 M4 or 5
35 35 24 70
105 56 Max. 6
5
Dimensions, mm
Front mounting, rear connection (type X)
Panel cutting
H103R, H203R C
L
Mounting hole C Breaker
Terminal Panel L
100 cover
C 37
5
144
126
ON
102
165
144
50
57.5
C
L C
L
93.5
14 20
9 22
M8 25 bolt 35 M4 or 5
35 35 24 70
105 94.5 Max. 6
5
Trip button 4 99 Note: 2-pole breaker is supplied in 3-pole frame with current
3.5 carrying parts omitted from center pole.
126
At shipment, studs are mounted on the MCCB unit as shown
in the figure for side view.
Studs for line side terminals : mounted horizontally
Studs for load side terminals : mounted vertically
Each stud can be mounted both horizontally or vertically.
5
Live section cover
15
8
5
51
ON
06
160
225
225
215
102
C C
266
C
257
90
L L L C
L
Angle 13
M12 25 bolt
31
13
15
16
5
4.5
140 12 27 Angle
44 108 7
40 40 5
15 44 44 35
Trip button 106.5 44 44
4.5 115 60 Insulation M6 or 7
4 158 110 tube Note: 2-pole breaker is supplied in 3-pole frame with current
carrying parts omitted from center pole.
H603B, H603R
Panel Panel cutting Angle mounting
Mounting hole Live section cover
C
L Breaker Breaker
11
C
L C
L
10
15
10
51
ON
243
160
243
413
102
297
275
C C
90
L C
L C
L L
Angle
45
Trip button
5 10
Insulation
15
70 70
125
barrier
178
11
70 Angle 7
210
M6 or 7 140 40 40 5
12 8 32 20 48
13
106.5 85 M12 40 bolt
4.5 Note: 2-pole breaker is supplied in 3-pole frame with current
115 96 carrying parts omitted from center pole.
4 158 180
At shipment, studs are mounted on the MCCB unit as shown
in the figure for side view.
Studs for line side terminals : mounted horizontally
Studs for load side terminals : mounted vertically
Each stud can be mounted both horizontally or vertically.
Dimensions, mm
Front mounting, rear connection (type X)
H803B, H803R
Panel Panel cutting Angle mounting
Mounting hole Live section cover
C
L Breaker Breaker
11
C
L C
L
11
15
10
51
ON
243
160
243
413
102
297
275
C C
90
L C
L C
L L
Angle
43
Trip button
5 10
Insulation
15
70 70
125
barrier
178
11
70 Angle 7
210
M6 or 7 140 40 40 5
12 8 32 20 48
13
106.5 85 M12 40 bolt Note: 2-pole breaker is supplied in 3-pole frame with current
4.5 115 96 carrying parts omitted from center pole.
4 158 180 At shipment, studs are mounted on the MCCB unit as shown
in the figure for side view.
Studs for line side terminals : mounted horizontally
Studs for load side terminals : mounted vertically
Each stud can be mounted both horizontally or vertically.
SA52RCUL
0.386 [9.8]
2.008 [51] 0.098 [2.5] Panel drilling Terminal section
CL
Terminal cover Mounting hole 1.693 [43]
Short type
0.164-32 tap or
0.197 dia.
0.669 [17]
Breaker [M4 or 5]
CL
ON 1.909 [48.5]
1.575 [40]
3.937 [100]
1.969 [50]
3.307 [84]
CL CL
3.307 [84]
0.945 [24] 0.315 [8] 0.327 [8.3]
CL
1.654 [42]
Trip button
M5 x 14
0.386 [9.8]
0.945 [24]
0.984 [25] 2.008 [51]
1.969 [50] 2.362 [60]
SA53RCUL
0.386 [9.8]
0.669 [17]
CL Breaker
1.575 [40]
ON 1.909 [48.5]
3.937 [100]
1.969 [50]
3.307 [84]
CL CL
0.315 [8] 0.327 [8.3]
3.307 [84]
1.654 [42]
CL
M5 x 14
Trip button
0.386 [9.8]
0.945 [24]
0.669 [17]
C
L C
L Breaker C
L
R0
.07
Breaker 8 [R
1.850[47] 2] o
0.177 dia [4.5]
r le
0.866[22] ss
ON
6.102[155]
5.315[135]
4.016[102]
1.969[50]
5.197[132]
0.079[2] 2.362[60]
2.362[60]
0.236[6]
3.543[90] Note: 2-pole breaker is supplied in 3-pole frame with current
3.228[82]
carrying parts omitted from center pole.
0.335Dia. [8.5]
Insulation barrier
1.004 [25.5]
3.150 [80]
.07
C
L Breaker CL Breaker CL
8[
R2
]o
r le
1.850 [47] 0.177Dia. [4.5]
ss
0.866 [22]
ON 0.413 0.433 [11]
4.016 [102]
5.669 [144]
6.496 [165]
4.961 [126]
1.969 [50]
[10.5]
C
L C
L CL M8 x 16
Trip button
0.945 [24]
1.380 [35]
2.205 [56] 4.016 [102] or more
SA202RCUL, SA203RCUL
2.303 [58.5] 0.039 [1]
Panel drilling Front panel cutting Terminal section
0.335Dia. [8.5]
Insulation barrier
3.543 [90]
1.004 [25.5]
Mounting hole
L
.07
Breaker CL Breaker CL
8[
R2
0.177Dia. [4.5]
]o
1.850 [47]
r le
0.866 [22]
ON
ss
4.016 [102]
5.669 [144]
6.496 [165]
1.969 [50]
C
L
CL [10.5]
M8 x 16
Trip button
2.205 [56]
0.945 [24]
1.380 [35]
4.016 [102] or more
0.531dia [13.5]
Insulation barrier
CL 1.732 [44] Panel drilling
4.134 [105]
8.425-8.504 [214-216]
2.008 [51]
3.307 [84]
10.118 [257]
8.858 [225]
Trip button
4.016 [102]
3.543 [90]
C
L C CL
L
0.965 [24.5]
2.087 [53]
SA603RCUL
Insulation barrier 0.275 [7]
Detachable
1.516 [38.5]
3.425 [87]
2.008 [51]
9.567 [243]
ON 1.85 [47]
4.016 [102]
9.567 [243]
3.543 [90]
10.83 [275]
C
L
C
L C
L
1.634 [41.5]
2.087 [53]
0.59 [15] 1.256 [32] 0.315 [8]
0.275 [7]
2.756 [70]
3.425 [87]
0.177 [4.5]
1.732 [44] 3.72 [94.5] Note: 2-pole breaker is supplied in 3-pole frame with current
Trip button
5.512 [140] 4.055 [103] carrying parts omitted from center pole.
8.071 [205] M12x 40 bolt 4.213 [107]
8.268 [210]
5.748 [146]
SA803RCUL
Insulation barrier
Detachable 0.394 [10] 06
0.571 dia. [14.5]
1.634 [41.5]
3.425 [87]
C
L [M6 or 7]
0.965 [24.5]
51
9.567 [243]
ON
9.567 [243]
1.85 [47]
4.016 [102]
10.83 [275]
3.543 [90]
C
L
CL CL
1.752[44.5]
2.087 [53]
0.59 [15] 1.256 [32] 0.315 [8]
0.394 [10]
3.425 [87]
2.756 [70]
1.732 [44] 3.72 [94.5] Note: 2-pole breaker is supplied in 3-pole frame with current
Trip button
5.512 [140] 4.055 [103] carrying parts omitted from center pole.
8.071 [205] 0.177 [4.5] 4.213 [107]
8.268 [210] M12 x 40 bolt
5.748 [146]
EA102CUL
0.386 [9.8]
2.008 [51] 0.098 [2.5]
CL Panel drilling Terminal section
Terminal cover 1.693 [43]
Mounting hole Short type
0.669 [17]
[M4 or 5]
1.575 [40]
CL CL
0.945 [24]
3.307 [84]
0.315 [8] 0.327 [8.3]
1.654 [42]
CL
Trip button M8 x 15
0.945 [24]
0.386 [9.8]
EA103CUL
0.386 [9.8]
0.669 [17]
[M4 or 5] Breaker
1.575 [40]
ON 1.909 [48.5] CL
3.937 [100]
1.969 [50]
3.307 [84]
CL
CL
0.315 [8] 0.327 [8.3]
1.654 [42]
3.307 [84]
CL
M8 x 15
Trip button
0.945 [24]
0.386 [9.8]
Minute
20 20
10 10 (40-100A)
6 6
4 4
2 2 Max. value
1 1
40 40
20
Reference temp.40C 20
Operating time
Operating time
400
10 10
6 350
6 Min. value Reference temp.40C
4 4
Max. value
correction ratio (%)
Second
2 300 2 150
Second
15-30A
Operating time
1 1 Instantaneous
Rated current
0.2 960 1440% 200 0.2 800 1500%
(5,10,40A) 100 40-100A
0.1 Instantaneous 0.1
150
0.06 tripping 0.06
0.04 characteristic 0.04
(3,15,20,30,50A) 100
0.02 0.02
0.01 50 0.01 50
1 1.5 2 3 4 5 6 78 10 15 20 30 4050 70 100 -10 0 10 20 30 40 50 1 1.5 2 3 4 5 6 7 8 10 15 20 30 40 506080100 0 10 20 30 40 50
Multiple of rated current (A) Ambient temp. (C) Multiple of rated current (A) Ambient temp. (C)
06
Minute
20 20
Minute
10 10
6 6
4 4
2 Max. value
2
1 1
40 40
20 Reference temp.40C 20
Operating time
Operating time
Reference temp.40C
correction ratio (%)
2 2 800 1400%
300
1 Max. value 1
150
Operating time
Multiple of rated current (A) Ambient temp. (C) Multiple of rated current (A) Ambient temp. (C)
20 20
Minute
10 10
6 6
4 4
Max. value
2 2
1 1
40 40
Reference temp.40C
20 20 Min. value
Operating time
Operating time
400
10 10
6 6 Reference temp.40C
350 Instantaneous
4 4
tripping
Second
Second
2 2 150
300 characteristic
Max. value
Operating time
1 1 800 1400%
correction ratio (%)
Multiple of rated current (A) Ambient temp. (C) Multiple of rated current (A) Ambient temp. (C)
10
6 Max. value
4
2
1
40
Min. value
20
Operating time
10
6 Reference temp.40C
4
Second
2 150
Instantaneous
1
correction ratio (%)
tripping
0.6 characteristic
0.4 800 1300%
Rated current
0.2
100
0.1
0.06
0.04
0.02
0.01 50
1 1.5 2 3 4 5 6 7 8 10 15 20 30 40 50 70 100 0 10 20 30 40 50
SA800RC
EA800C
180
120
60
40
20
Minute
Max. value
10
6
4
2
1
40
Min. value
20
Operating time
10
6 Reference temp.40C
4
Second
2 150
1 Instantaneous
correction ratio (%)
tripping
0.6 characteristic
0.4 600 1000%
Rated current
0.2
100
0.1
0.06
0.04
0.02
0.01 50
1 1.5 2 3 4 5 6 7 8 10 15 20 30 40 50 70 100 0 10 20 30 40 50
SA54B SA204R
180
120 180
120
60
40 60
40
Minute
Minute
20
20
10
10
6
4
6 Max. value
4
2
2
1
1
40
Max. value 40
Operating time
Operating time
20 20
10 Min. value Instantaneous
10
6
Instantaneous 6 tripping
4
tripping Reference temp.40C 4 characteristic Reference temp. 40C
Second
Second
2
Min. value characteristic 2 800% 1500%
300 150
1
0.6 200
0.6
0.4
Max. total 160 0.4
Operating time
Rated current
0.2 fault
120
100 0.2
Max. total
0.1 clearing
80
0.1
fault 100
60
0.06
time 0.06 clearing
0.04 0.04
40 time
0.02 0.02
50
0.01 0 10 20 30 40 50 0.01 0 10 20 30 40 50
1 1.5 2 3 4 5 6 7 8 10 15 20 30 40 50 70 100 1 1.5 2 3 4 5 6 7 8 10 15 20 30 40 50 70 100
Ambient temp. (C) Ambient temp. (C)
Multiple of rated current (A) Multiple of rated current (A)
EA104B SA404HA
180 180
120
90
60
40 40
Minute
Minute
20
20
10
6
10 06
6
4
4 Max. value
2
Max. value
2
1 1
40 40
Operating time
20 20
Instantaneous
Operating time
Second
2
Min. value 2 800% 1400%
1 300 150
1
correction ratio(%)
250
correction ratio (%)
0.6
0.4
Max. total 200 0.6
0.4
fault 160
Rated current
Operating time
0.2 120
clearing 100 0.2
0.1 80 100
0.06
time 60
0.1
0.06
0.04
40 0.04
0.02
0.02
0.01 50
0 10 20 30 40 50 0.01 0 10 20 30 40 50
1 1.5 2 3 4 5 6 7 8 10 15 20 30 40 50 70 100 1 1.5 2 3 4 5 6 7 8 10 15 20 30 40 50 70 100
Ambient temp. (C) Ambient temp. (C)
Multiple of rated current (A) Multiple of rated current (A)
SA104R SA604H
180 180
120
90
60
40 40
Minute
Minute
20 20
10 10
6
Max. value
6
4 4
2 2
1 1
40 40
Max. value
Operating time
Operating time
20 20
10 10
6 Instantaneous 6 Min. value
4 4 Reference temp. 40C
tripping Reference temp. 40C
Second
Second
2
Min. value characteristic
2
150
1 150 1
800% 1600% 15-30A
correction ratio (%)
0.6
correction ratio(%)
0.6
0.4 0.4 Instantaneous Max. total
Max. total
Rated current
tripping
Rated current
0.2
fault 0.2 fault
0.1 100 characteristic clearing
100
clearing 40-100A 0.1
0.06 0.06 800% 1300% time
0.04 time 0.04
0.02 0.02
0.01 50
50 0.01 0 10 20 30 40 50
1 1.5 2 3 4 5 6 7 8 10 15 20 30 40 50 70 100 0 10 20 30 40 50
1 2 3 4 5 6 7 8 10 20 30 40 50 60 80 100
Multiple of rated current (A) Ambient temp. (C) Ambient temp. (C)
Multiple of rated current (A)
S series, 4-pole
SA804H
180
120
40
Minute
20
10 Max. value
6
4
1
40
Operating time
20
10
Min. value
6
4 Reference temp. 40C
Second
1 150
correction ratio(%)
0.6
0.4 Instantaneous
Max. total
Rated current
0.2 tripping
0.1 characteristic fault 100
LA50B H225BA,
,
H225R
180 180
120 120
60 60
40 40
Minute
Minute
20 20
10 10
6 6
4 4
2 2 Max. value
1 1
40 Max. value 40
Instantaneous
Operating time
20 20 tripping
Operating time
10 10 characteristic
6 6 Min. value 800%-1400%
4 4
Reference temp.40C Reference temp. 40C
2
Second
Second
correction ratio(%)
0.6 200 0.6
0.4 160 0.4
Operating time
Rated current
0.2
Max. total 120
0.2
100
40 20
06
Minute
20 10
10 (H50BA: 40, 50A) 6 Max. value
6 (H100BA: 40-100A) 4
4
2
2 Max. value 1
1 40
Operating time
40
20
Operating time
20
10 Min. value
10
6
6
Min. value Instantaneous 4
4
tripping Reference temp. 40C Reference temp. 40C
Second
2
Second
2
(15~30A) characteristic 150 1 150
1
800% 1500% 15 to 30A
correction ratio (%)
correction ratio(%)
0.6
0.6
0.4
0.4
Max. total
Rated current
Rated current
0.2
Max. total 0.2
fault 100
Instantaneous fault
0.1 100
0.1
0.06 clearing 0.06
tripping clearing
0.04 time 40 to 100A 0.04 characteristic time
0.02 0.02 800% 1400%
0.01 50 0.01 50
1 1.5 2 3 4 5 6 7 8 10 15 20 30 40 50 70 100 0 10 20 30 40 50 0 10 20 30 40 50
1 1.5 2 3 4 5 6 7 8 10 15 20 30 40 50 70 100
Multiple of rated current (A) Ambient temp. (C) Ambient temp. (C)
Multiple of rated current (A)
20 20
10 10
6 6
Max. value
4 4
2 Max. value 2
1 1
40 40
Operating time
Operating time
20 20
Min. value
10 10
6 6
4
4
Min. value Reference temp. 40C
Reference temp. 40C
Second
Second
2 2
1 1
150 150
correction ratio(%)
0.6 0.6
correction ratio(%)
0.4 0.4
Instantaneous Max. total Max. total
Rated current
0.2
0.2
tripping Instantaneous
Rated current
fault fault
0.1
0.1 characteristic clearing 100 tripping 100
0.06 0.06 clearing
800% 1400% time 0.04 characteristic
0.04 time
0.02 0.02 800% 1300%
0.01 50 0.01 50
1 2 3 4 5 6 7 8 10 15 20 30 40 50 70 100 0 10 20 30 40 50 1 1.5 2 3 4 5 6 7 8 10 15 20 30 40 50 70 100 0 10 20 30 40 50
Multiple of rated current (A) Ambient temp. (C) Multiple of rated current (A) Ambient temp. (C)
H series, 3-pole
H800B, H800R
180
120
60
40
Minute
20
Max. value
10
6
4
1
40
Operating time
20
10
Min. value
6
4
Reference temp. 40C
Second
1
150
0.6
correction ratio(%)
0.4
0.2
Max. total
Rated current
fault
0.1 Instantaneous 100
clearing
0.06
tripping
0.04 time
characteristic
0.02
600% 1000%
0.01 50
1 1.5 2 3 4 5 6 7 8 10 15 20 30 40 50 70 100 0 10 20 30 40 50
S and E series
SA30CM, SA50CM, SA50RCM SA225CM, SA225RCM
EA30ACM, EA50CM EA225CM
180
180 120
120 90
60
60 40
40
20
Minute
Minute
20
10
10 6
6 4
4 Max. value
2
2
1
1 40
40
Max. value Reference temp.40C 20 Instantaneous
20 tripping
Operating time
Operating time
Second
Instantaneous Reference temp.40C
Second
2
correction ratio (%)
Rated current
200 0.2
0.2
0.1 100
0.1
150 0.06
0.06 0.04
0.04
100 0.02
0.02
0.01
0.01 50 1 1.5 2 3 4 5 6 7 8 10 15 20 30 40 50 80100 50
1 1.5 2 3 4 5 6 78 10 15 20 30 4050 70 100 -10 0 10 20 30 40 50 0 10 20 30 40 50
Ambient temp. (C) Multiple of rated current (A) Ambient temp. (C)
Multiple of rated current (A)
SA60CM
L and H series
EA60CM, EA100CM
180 LA50BM
120
180
60 120
40 60
06
Minute
20 40
Minute
10 20
6
10
4
6
2 4
1
2
40
Max. value Reference temp.40C 1 Max. value
20
Operating time
40
400
10
Operating time
20
6
4 Instantaneous 350 10
Reference temp. 40
Second
tripping
correction ratio (%)
2 6
Min. value characteristic 300 4
960 1440%
correction factor (%)
Operating time
1 300
Min. value
Second
0.6 2 250
250 200
0.4 1 160
Operating time
20 20
(4090A)
10 10
8
6 Max. 6 (40, 50A)
4 value 4
2 2 Max. value
1 1
40 40
Operating time
20 20
Operating time
10 10
6 8 Instantaneous
Min. Instantaneous Reference temp.40C 6 Reference temp.40C
4 value tripping 4
Min. value tripping
2 characteristic setting range
Second
150 150
Second
1000 2000% 2
1 16-32A (1632A) 1000% 2000% 16-32A
correction ratio (%)
0.8 1
(1632A) 0.8
0.6
0.4 0.4 Max. total
Rated current
Rated current
S series, 2, 3-pole
SA50RCUL
Rated current : 5, 10, 40A Rated current : 3, 15, 20, 30, 50A
180 180
120 120
60 60
40 40
Minute
Minute
20 20
10 10
6 6
4 4
Max. value Max. value
2 2
1 1
40 40
Instantaneous Instantaneous
20 20 Reference temp. 40
Operating time
tripping
Operating time
tripping
10 characteristic 10 400
6 characteristic
960%-1440% 6
4 4 800%-1200% 350
Second
Operating time
0.6 0.6
0.4 0.4 250
0.2 0.2 200
0.1 0.1
0.06 150
0.06
0.04 0.04
0.02 100
0.02
0.01 0.01 50
1 1.5 2 3 4 5 6 78 10 15 20 30 4050 60 80100 1 1.5 2 3 4 5 6 78 10 15 20 30 4050 60 80100
Multiple of rated current (A) Multiple of rated current (A) -10 0 10 20 30 40 50
Ambient temperature ( )
SA100CUL SA100RCUL
180 180
120 120
60 60
40 40
Minute
Minute
20 20
10 (40-100A) (40-100A)
10
6 6
4 4
Max. value Max. value
2 2
1 1
40 40
20 20
Operating time
Operating time
1 1
Second
Second
Rated current
SA225CUL SA225RCUL
180 180
120 120
90 90
60 60
40 40
30 30
Minute
Minute
20 20
10 10
8 8
6 6
4 Max. value 4 Max. value
2 2
1 1
40 Instantaneous 40 Instantaneous
20 tripping 20 tripping
Operating time
Operating time
10
characteristic 10
characteristic
8
6
Min. value 800%-1400% 8
6
Min. value 800%-1400%
4 Reference temp. 40 4 Reference temp. 40
2 150 2 150
correction ratio (%)
1 1
Second
Second
0.8 0.8
0.6 0.6
0.4 0.4
Rated current
Rated current
S series, 2, 3-pole
SA400CUL SA400RCUL
180 180
120 120
60 60
40 40
Minute
Minute
20 20
10 10
6 Max. value 6 Max. value
4 4
2 2
1 1
40 40
20 20
Operating time
Operating time
Second
Second
0.6 0.6
Rated current
Rated current
0.4 0.4
0.2 Max. total 100 0.2 Max. total 100
0.1 fault clearing 0.1 fault clearing
0.06 time 0.06 time
0.04 0.04
0.02 0.02
50 50
0.01 0 10 20 30 40 50 0.01 0 10 20 30 40 50
1 1.5 2 3 4 5 6 7810 15 20 30 4050 70 100 1 1.5 2 3 4 5 6 7810 15 20 30 4050 70 100
Multiple of rated current (A) Ambient temp. (C) Multiple of rated current (A) Ambient temp. (C)
SA600RCUL SA800RCUL
180 180
120 120
90 90
60 60
40 40
30
Minute
30
Minute
20 20
10
8
6
10
8
6
4
Max. value 06
4 Max. value Instantaneous
2 2 tripping
1 1 characteristic
40 Instantaneous 40 600%-1000%
20 tripping 20
Operating time
Operating time
10 characteristic 10
8 800%-1300% Reference temp.40C 8 Reference temp.40C
6 Min. value 6 Min. value
4 4
150 150
2 2
correction ratio (%)
1 1
Second
Second
0.8 0.8
0.6 0.6
Rated current
Rated current
0.4 0.4
0.2 100 0.2 100
Max. total
0.1 0.1 Max. total
0.08 fault clearing 0.08
0.06 0.06 fault clearing
0.04 time 0.04 time
0.02 0.02
0.01 50 0.01 50
1 1.5 2 3 4 5 6 78 10 15 20 30 40 5060 80100 0 10 20 30 40 50 1 1.5 2 3 4 5 6 78 10 15 20 30 405060 80100 0 10 20 30 40 50
Multiple of rated current (A) Ambient temp. (C) Multiple of rated current (A) Ambient temp. (C)
E series, 2, 3-pole
EA100CUL
Rated current : 5, 10, 40, 60, 70, 75, 80, 90A Rated current : 3, 15, 20, 30, 50, 100A
180 180
120 120
60 60
40 40
Minute
Minute
20 20
10 10
6 6
4 4
Max. value Max. value
2 2
1 1
40 40
Instantaneous Instantaneous Reference temp. 40
20 20
Operating time
tripping
Operating time
tripping
10 10 characteristic 400
characteristic 6
6 800%-1200%
4 960%-1440% 4 350
correction ratio (%)
2 2
Min. value Min. value 300
1 1
Second
Operating time
Second
Auxiliary switch (Type W) Alarm switch (Type K) Shunt trip device (Type F)
This switch is used for indicator lamp This switch can be connected to a The purpose of this accessory is to trip
or control circuit. warning lamp or buzzer to indicate the breaker from a distance.
when the breaker has been tripped.
IP
TR
breaker mount. An extension shaft
(sold separately) for the V type handle
OFF
allows the distance between the handle
ET
ES
and the breaker to be adjusted. The
/R
EN
OP
IP
TR
Handle
locking
OFF T
cover
SE E
R /
EN
OP
V type
O
N
O
F
F
Motor-operating mechanism
The lead wires are pulled out and terminal blocks are attached
on the same side of the internal accessory will be attached
Lead-wire wiring With terminal block
For the available configuration of internal accessory, see page
06/92 to 06/93.
11 12 14 21 22 24 11 12 14
AXcL AXbL AXaL AXcR AXbR AXaR AXc AXb AXa
2PDT: W2
11 12 14
11 12 14 21 22 24
AXc AXb AXa
AXcL AXbL AXaL AXcR AXbR AXaR
21 22 24
AXc AXb AXa
91 92 94 01 02 04 91 92 94
ALcL ALbL ALaL ALcR ALbR ALaR ALc ALb ALa
2PDT: K2
91 92 94 01 02 04 91 92 94
ALcL ALbL ALaL ALcR ALbR ALaR ALc ALb ALa
01 02 04
ALc ALb ALa
C2 C1
S2 S1
Undervoltage trip device : R U<
D2 D1
P2 P1
L series, H series
Accessory Terminal number
LA50B, H100R, H225R, H400R, H600R, H800R
H50BA, H100BA, H225BA, H400B, H600B, H800B
Auxiliary switch SPDT: W
AXa1
AXC1
AXb1
2PDT: W2
AXa1
AXC1
AXb1
AXa2
AXC2
AXb2
2PDT: K2
ALa1
ALC1
ALb1
ALa2
ALC2
ALb2
06
Shunt trip device : F With 1NO contact
to prevent coil
S1 S2
burn-out
Continuous rating
S1 S2
H225R, H225BA
H400R, H400B
H600R, H600B P2
H800R, H800B
Available configurations
3P 2P
Left Right Right Auxiliary switch: W Alarm switch: K
Undervoltage trip: R Shunt trip: F
Handle Handle
MCCB S series SA32C SA102C SA33C SA103C SA402C SA54B*1 SA404HA SA604H
SA52C SA53C SA102RC SA403C SA104R SA804H
SA52RC SA53RC SA103RC SA402RC SA204R
SA62C SA63C SA202C SA403RC
SA62RC SA63RC SA203C SA603RC
SA202RC SA803RC
SA203RC
E series EA32AC EA33AC EA202C EA402C EA104B *1
EA52AC EA53AC EA203C EA403C
EA52C EA53C, 63C EA603C
EA62C EA103AC EA803C
EA102C EA103C
HL LA53B H402B, H403B
series H103R, 203R H403R
H52BA, 53BA H603B, H603R
H102BA, 103BA H803B, H803R
H202BA, 203BA *3
Pole 2 2 3 2, 3 2, 3 2, 3 4 4 4
Auxiliary switch
SPDT W
Alarm switch
SPDT K
Shunt trip F
Undervoltage *2 *2 *2
trip R
W2
W+K
W2+K
K2
W+K2
W2+K2
W+F
W2+F
W+R *2 *2
*2
W2+R
*2 *2
K+F
K+R *2 *2 *2
W+K+F
W+K+R
*2 *2 *2
K2+F
K2+R
W2+K+F
*2
W2+K+R
*2
W+K2+F
W+K2+R
W2+K2+F
W2+K2+R
Notes: The lead wires are pulled out and terminal blocks are attached on the same side of the accessory.attached.
*1 The "W" and "K" of EA104B and SA54B are mounted on the left pole only. They cannot be mounted on the right side pole.
*2 The side on which the undervoltage trip device "R" is mounted has the terminal block.
*3 H400R, H600R, H800R: Factory-mounted
Fuji Electric FA Components & Systems Co., Ltd./D & C Catalog
06/92 Information subject to change without notice
Molded Case Circuit Breakers
Internal accessories
UL listed
Available configurations
3P 2P
Left Right Right Auxiliary switch: W Alarm switch: K
Undervoltage trip: R Shunt trip: F
Handle Handle
MCCB S series SA52RCUL * SA53RCUL * SA102CUL SA402CUL
SA103CUL SA403CUL
SA102RCUL SA402RCUL
SA103RCUL SA403RCUL
SA202CUL SA603RCUL
SA203CUL SA803RCUL
SA202RCUL
SA203RCUL
Pole 2 3 2, 3 2, 3
Auxiliary switch
SPDT W
Alarm switch
SPDT K
Shunt trip F
Undervoltage
trip R
W2 06
W+K
W2+K
K2
W+K2
W2+K2
W+F
W2+F
W+R
W2+R
K+F
K+R
W+K+F
W+K+R
K2+F
K2+R
W2+K+F
W2+K+R
W+K2+F
W+K2+R
W2+K2+F
W2+K2+R
Notes: The lead wires are pulled out and terminal blocks are attached on the same side of the accessory.attached.
* Terminal block connection is standard method
400AF to 800AF
BZ - WKF 70B - 24 - A (CCC)
Applicable breakers
70B : 400AF to 800AF
2PDT: W2
12/AXbL 12/AXbL
22/AXbR 22/AXbR
SPDT: K
92/ALbL 92/ALbL
2PDT: K2
92/ALbL 92/ALbL
01/ALcR 04/ALaR 01/ALcL 04/ALaL
02/ALbR 02/ALbL
AXb2 AXb1
Alarm ALc1 ALa1 ALc1 ALa1
switch
SPDT: K
ALb1 ALb1
ALb2 ALb2
2PDT: W2
12/AXbL 12/AXbL
22/AXbR 22/AXbR
SPDT: K
92/ALbL 92/ALbL
2PDT: K2
92/ALbL 92/ALbL
01/ALcR 04/ALaR 01/ALcL 04/ALaL
02/ALbR 02/ALbL
Standard type
MCCB AC DC Minimum
S series E series Voltage (V) Make/break Voltage (V) Make/break load current
current (A) current (A)
SA50RCUL EA100CUL 120 3.6 125 0.55 5V DC 160mA
240 1.8 250 0.27 30V DC 30mA
SA100CUL 120 5
SA100RCUL
SA225CUL 240 3
SA225RCUL
SA400CUL 120 5
SA400RCUL
SA600RCUL 240 5
SA800RCUL
UL Listed
MCCB type Power consumption Time rating Operating
S series E series H and L series AC DC of coil time
V VA V W (ms)
SA50RCUL EA100CUL 100-120 (50/60Hz) 150 100-110 150 Continuous 7-13
200-240 (50/60Hz) 150 With 1NO contact to
380-450 (50/60Hz) 200 prevent coil burn-out
SA100CUL 24 (50/60Hz) 30 24 35 Continuous 7-21
SA100RCUL 48 (50/60Hz) 48
SA225CUL 100-125 (50/60Hz) 100-110
SA225RCUL 200-240 (50/60Hz) 200-220
SA400CUL 24-48 (50/60Hz) 2 24-48 2 Continuous 8-20
SA400RCUL 100-240 (50/60Hz) 3 100-220 3
SA600RCUL
SA800RCUL
Note: Allowable voltage function AC voltage: 85% to 110% of coil rated voltage
DC voltage: 75% to 125% of coil rated voltage
Dimensions, mm
Shunt trip device "F" and undervoltage trip device "R"
S series E series Fig. Mass (kg)
CL
11
C
L 68
70
3
100
155
CL
128
C
L C
L C
L
41.5
63.5
M3.5 69
24
45 10.5 41
11
61 51 60
75 25 60
7 M3.5
77
90 25
Fig.1 Fig.2
CL
11
73
128
165
C
L CL
60.5
66
11
M3.5
60
7
105 25
Fig.3
53.7
77.2
30.2
CL CL
94
CL
94
CL
12.5 48 B 12.5
48 B
Fig.3 Fig.4 38 19
7 E Line
D 81.5
Line C 69
F
+A
94
77.2
53.7
30.2
100.5
CL
117.5
53.5
30.5
CL CL CL
77
M3.5 M3.5
8 9.5 80 11
Load 48 B
12.5
(Left) Load (Right)
Lead-wire extension type is not available.
(EA100CUL, SA50RCUL)
Type number
Auxiliary switches (W) and alarm switches (K)
MCCB type Type number
S series E series Auxiliary switch / W Alarm switch / K Auxiliary switch Mass
SPDT: W Mass(kg) 2PDT: W2 Mass(kg) SPDT: K Mass(kg) 2PDT: K2 Mass(kg) + Alarm switch / WK (kg)
SA30C * EA30AC * BZ6W 10C 0.01 BZ6K 10C 0.01 BZ6WK 10C 0.02
SA50C * EA50AC * BZ6W 10CA 0.04 BZ6K 10CA 0.04 BZ6WK 10CA 0.08
SA50RC * EA50C * (With terminal block) (With terminal block) (With terminal block)
SA60C * EA60C *
SA60RC * EA100AC *
EA100C *
SA100C BZ6W 30C 0.02 BZ6K 30C 0.02 BZ6WK 30C 0.04
SA100RC BZ6W 30CA 0.05 BZ6K 30CA 0.05 BZ6WK 30CA 0.07
(With terminal block) (With terminal block) (With terminal block)
SA225C EA225C BZ6W 40C 0.02 BZ6K 40C 0.02 BZ6WK 40C 0.04
SA225RC BZ6W 40CA 0.05 BZ6K 40CA 0.05 BZ6WK 40CA 0.07
(With terminal block) (With terminal block) (With terminal block)
SA400C EA400C BZ-W70B 0.02 BZ-W270B 0.04 BZ-K70B 0.02 BZ-K270B 0.04 BZ-WK70B 0.04
SA400RC EA600C BZ-W70B-A 0.11 BZ-W270B-A 0.22 BZ-K70B-A 0.11 BZ-K270B-A 0.22 BZ-WK70B-A 0.03
SA600RC EA800C (With terminal block) (With terminal block) (With terminal block) (With terminal block) (With terminal block)
SA800RC
UL Listed
MCCB type Type number
S series E series Auxiliary switch / W Alarm switch / K Auxiliary switch
SPDT: W SPDT: K + Alarm switch / WK
SA400CUL
SA600CUL
SA800CUL
Notes: Auxiliary switch and alarm switch for low level circuit are also available on request, Factory-mounted accessory
in this case add D to the type number when ordering. Example: WD, KD
Replace the mark by the R when an auxiliary switch or an alarm switch is mounted
on right hand side of the breaker. Enter the L when it is mounted on left hand side of the breaker.
* 2-pole types are mountable on right side only.
Type of accessory
Operating voltage
Terminal
Ordering information
Specifty the following.
1. Type number
2. Lead-wire connection or
terminal block type
Motor-operated breakers
Description
The breaker is fitted with a motor
operating mechanism which enables
ON, OFF and RESET operations to be
carried out electronically by remote
control.
4-pole motor operated breakers are also
available.
Ordering information
Specify the following:
1. Type number
2. Motor operating voltage
Dimensions, mm / Front mounting, front connection Wiring diagrams
SA33C/M, SA53C/M, SA53RC/M, SA63C/M, SA63RC/M 100/110V AC, 200/220V AC, 100V DC
EA33AC/M, EA53AC/M, EA53C/M, EA63C/M, EA103AC/M, EA103C/M
Panel drilling
Insulation barrier DRIVE CONTROL
Mounting hole C (Except EA33AC/M, 53AC/M, SA33C/M) M4 or 5
UNIT CIRCUIT
50
L
4.5
Operating handle CL
C 5 4 3 E 2 1
100
CL
75
CL
50
84
84
OFF ON
10
51 25
25 Trip button
Terminal cover 67
70 Power supply
135
75 Notes: Trip button operation can be (Non polarity)
4 139
carried out at right side of the
breaker.
IEC 35mm wide mounting rail
is not available.
Insuration
barrier
Detachable
50
Panel drilling
R65
L 2-M4 or 5 30
57
100
155
144
132
C
L
189
132
Max. 4
30 56
75 142
90
100/110V AC, 200/220V AC
4-M4 or 5 35
R65
57
189
138
165
126
100
126
Panel drilling
C
L
Panel
220 44
56 56 8
40.5
Manual/
motor
operation
indicator
215
257
327
C
L
44
M8 or 7
40.5
M6
8 18
15
25
44
140 Bolt
M12 x 35
216
256
C
L Panel drilling
220 A
140 C C
Panel L
Manual/
87
motor
operation
indicator
243
C
L
275
327
C
L C
L
M6
70
7
15 32 8
87
44
C
210 B 18
Bolt
M12 x 40 216
291
06
Wiring diagrams/400 to 800AF
BZ6M130C2 SA102C
BZ6M130C3 SA103C
SA102RC, SA103RC
BZ-M135C-4 SA104R
BZ-M150C-4 SA204R
Dimensions, mm
30AF to EA100AF
A Panel drilling
B
C BZ6M110C2 85
Breaker Breaker
C
L of slider
26
56
Breaker mounting hole
68
45
100
11
68
C
L of breaker CL of breaker
C
L C
L
C
L C
L
Padlock 2-4.5 mounting hole
2-4.5 or M4
(Not supplied)
35
13 BZ6M110C3 110
Breaker Breaker
45
68
88
100
CL of breaker
C
L 9 C
L
C
L CL
2-4.5 or M4
06
Type Breaker type Dimensions, mm Mass (kg)
S series E series A B C
9.5 14
3.5 3.5
14
12
20 25
Dimensions, mm
SA100AF to SA/EA225AF Panel drilling
BZ6M130C2 BZ6M130C3
J H J
A F
A' C E 6-M4 or 5 H CL of handle
N N
CL of slider
P
G
D
B
K
K
CL of breaker
Q
J' J'
Breaker 4-M4 or 5
Padlock
Mounting screw
(not supplied)
(provided)
400AF to 800AF
CL of handle
K
Q
CL of breaker CL of breaker
L
BZ6M130C3 SA103C 210 (45) 155 120 9 57.5 85 35 90 30 (45) 132 60 70 75 0.177
SA102RC
SA103RC
BZ6M140C SA202C EA202C 240 (52.5) 165 135 14 57.5 85 35 100 35 (52.5) 126 67.5 76 69 0.188
SA203C EA203C
SA202RC
SA203RC
BZ-M160C SA402C EA402C 355 (70) 257 215 0 94.5 126 54.5 171 44 (70) 215 38 0.56
SA403C EA403C
SA402RC
SA403RC
BZ-M170C SA603RC EA603C 500 (105) 275 290 20 94.5 126 54.5 220 70 (105) 243 38 0.64
SA803RC EA803C
Note: Applicable padlock(3.5) dimensions, mm
9.5
3.5
12
20
Description
Molded case circuit breaker handles are
generally directly manual-operated but
when mounted in motor control centers
or on control panels they are sometimes
required to be operated externally. To
meet such applications FUJI offers the
following three types of handles.
N type handle
This type has a knob handle directly
KK03-017 AF96-173 KK03-015 SG-602
attached to the breaker. It is easily fitted
by cutting a hole in the panel, which is BZ6N10C BZ-N C BZ6V10C G- A
provided with a door interlock. They N type handles V type handle G type handle
may be fitted to all breakers up to 1600
ampere frame sizes. N type handles for
SA/EA30AF to EA100AF are approved N type handles BZ-N C
by UL508. Breaker
V type handle
The V type handle may be fitted to
breakers of up to 800AF.
A separately sold extension shaft
(BZ-VS1)provides distance adjustment
between the handle and breaker.
Conformed to EN60947-1 isolation Decorative plate
function. N type handle on
Available for EN60204-1 power breaking breaker 06
device.
G type handles G- A
Breaker
G type handle on
panel
G type handles
Type Standard Cylinder key type
SA104R BZ-G35C BZ-G35C-K
SA204R BZ-G50C BZ-G50C-K
SA404HA G-22A G-22A-K
SA604H, 804H G-42A G-42A-K
Operating instructions
1. MCCB operation Mounting screw
Close the door with the handle in the OFF position. Turn the
handle to the ON position and the MCCB will be ON. Base plate
For N10C, N20C, N30C
Turn the handle to the OFF position and MCCB will be OFF.
When the breaker trips, the handle moves to the TRIP position.
To reset, move the handle to the RESET position.
2. Door locking
The door cannot be opened when the handle is in the ON, OFF
For N40C
or TRIP position, and can be opened only when the handle is in For N10C, N20C, N30C
the OPEN position.
The breaker cannot be ON when the door is open.
If it is necessary to open the door with the breaker closed, turn
the door lock release screw counterclockwise using a
screwdriver. Fig. 2
3. Handle locking
The handle can be locked in either the ON or OFF position when a
padlock (not supplied) is used . Pull out the handle lock plate and fit
your padlock to the lock plate. If the breaker trips while it is locked
in the ON position, the handle moves to the TRIP position.
MCCB
N handle
handle
arm
Installation Fig. 1
BZ-N60C, BZ-N70C
1. Drilling and cutting the door
Drill and cut the door. The dimensions for drilling and cutting are
the same whether the MCCB is installed horizontally or vertically.
Fig. 3 Fig. 4
Not correct
MCCB
N handle arm
Decorative
Handle plate
window
Decorative
plate MCCB
MCCB handle
Space
BZ N CTR
Installation
Blank: Vertically
R: Horizontally, right line side
L: Horizontally, left line side
Basic type
BZ6N10C
BZ-N C
N- A
Note:
To order an N handle for front-mounting rear connection breakers, add -X to the
type number, for plug-in mounting breakers, add -P to the type number.
Dimensions, mm
BZ6N10C to BZ-N50C (Dust proof paking: BZ-NP-1C, optional)
Line
Load
69 max.
Breaker type Handle A Mounting Mass Breaker type Handle A Mounting Mass
type Screw (kg) type Screw (kg)
SA30C, SA50C, 50RC, SA60C, 60RC BZ6N10C 103 M4 80 0.47 EA225C BZ-N40C 103 M4 85 0.56
SA50RCUL SA225C, 225RC, 225CUL, 225RCUL
EA30AC, EA50AC, 50C, EA60C H225BA
EA100AC, 100C, 100CUL H100R, H225R BZ-N50C 142 M4 125 0.62
LA53B BZ-N20C 125 M4 110 0.56
SA100C, 100RC, 100CUL, 100RCUL BZ-N30C 103 M4 85 0.56
H50BA, 100BA
150
Mounting screw Door panel cutting
06
Line
Decorative plate
4 -15 Handle
C/L
ON Lock plate
I P
96
R
T
38
1
F
OF
112
LE A S E
handle handle
ET
C/L C/L
RES
RE
EN
OP
150
96
(Only BZ-N70C)
BZ-N C-R..... Installed horizontally, the line positioned on the right side.
35
35
65
P
2. Breakers use different size screws for the P-type (Plug-in) breakers
Dimensions, mm
N-23A, N-41A (Dust proof packing: BZ-NPB, optional)
Door panel cutting
Decorative
plate
CL of
38
112
150
mounting 1
hole
200
10
4-15
51 A2 112
150 Auxiliary
handle
Door Hinge
Packing(Optional)
Approx. 13.5
10
Door
Latch 86
30
plate
4
10
Line 78
-
5
15
5
15
15
30
30
CL of
0
105
78
panel
9
cutting
100 100
150 150
Load 200 200
105 43 1252
Lock lever
Packing(Optional) Install the door hinge in the shaded area.
Mass: 0.45kg
Operating instructions
1. MCCB operation
Close the door and turn the handle to the ON position and the
breaker will be positioned at ON.
When the breaker is interrupted automatically the handle will
move to the TRIP position. Lock plate
To reset move the handle to the RESET position. Padlock
(Not supplied)
Terminal cover
2. Door panel locking
Turn the handle to the RESET position and the lock
mechanism will be released thus allowing the door to be
opened.
The door cannot be opened when the breaker is positioned at Fig. 3 Fig.4
ON.
3. Handle locking
The padlock can lock the handle in the OFF position.
Locking MCCB with the door open : Fig.1
Locking MCCB with the door closed : Fig.2
Pull out the lock plate and hook the padlock.
4. Interlock release
This type is provided with an interlock release screw. Turn this
screw if it is necessary to open the door in the ON position. This
release the lock and allows the door to be opened. When Fig. 5
reclosing the door, make sure the handle of the breaker
coincides with the position (ON or OFF) of the external handle
position. 06
Installation
For V10C to V30C
BZ6V10C to 50-VC
1. Drilling and cutting of the door panel Breaker
plate by tightening the four attached mounting screws. (Fig.5) Interlock-release screw
Shaft
Dimensions, mm
BZ6V10C, 6V30C, 6V40C
Door panel cutting
105 B
Door panel Handle
4-15 CL
Handle Handle 90
105
78
CL CL
78
Panel thickness
1.2-3.2
61 H
64
10
O
TR
25
X
P OF
Handle
105
CL
40
RE
20
O
55
120
Panel thickness The distance between the handle
1.2-3.2 and breaker can be shortened by
48.5 H cutting the optional shaft. Install the door hinge in the shaded area.
Breaker type Handle type Standard With the optional shaft (X=154) Mounting Mass
type H Area in which the hinge screw (kg)
S series E series L, H series H with H can be installed B
SA54B EA104B LA53B BZ-V20C 127 272 164 to 272 82 M4 x 110 0.67
Basic type
BZ6V C
BZ-V C
Note:
Fig. 8 To order a V handle for front-mounting rear connection breakers, add -X to the
type number; for plug-in mounting breakers, add -P to the type number.
Dimnsions, mm
BZ6V60C, 6V70C, BZ-V60C, V70C
150
Door panel cutting Optional shaft
( BZ-VS2)
Line
ON
I P
R
75
Breaker and
T
38
handle 1
F
OF
112
150
CL
SE
ET
RES
L EA
EN
RE
OP
75
x
150
55
100
200
Breaker Handle type Standard type With the optional shaft Mass
H H Area in which the hinge (kg)
S series E series H series with H can be installed
SA400C EA400C BZ6V60C 1902 2502 202 to 250 2.2
SA400RC
SA400CUL
SA400RCUL
Notes:
Handle protection degree IP54 (IEC60529, JIS C0920).
The handle cannot hold the door.
Breakers use different size screws for the X type (rear connection) or P-type (Pulg-in) breakers.
Adjusting screw
1 Handle
4. Interlock release
This type is provided with an interlock 3. Fit the decorative plate and handle
release screw. Turn this screw if it is mechanism to the door panel by means of
necessary to open the door at the ON the mounting screws as shown in the 2 Mounting
illustration. screw 3
position. This releases the lock and Set screw
allows the door to be opened. When
reclosing the door make sure the handle 4 Decorative
legend
of the breaker coincides with the position plate
en
(ON or OFF) of that of the external Decorative Lock
ON
TR
IP
OF
F
Re
se
to
p
Dimensions, mm
BZ-G35C, BZ-G50C
C/L
69 (76)
60 max.
Thickness 1.2-3.2 Handle lock plate
52.5 55 Panel for padlock
25
Line
side
max. 95
TR 78
max
OFF
105
C/L
4
11
9
22
max. 95
67.5
Lock lever
0
78
9
OPEN
Load
side
105 (A)
88 44 A
Thickness 3.2 Retaining plate
(Provided)
( ): BZ-G50C
G-22A
120
32
ON
Door panel drilling Panel drilling
3-5.5 20 80
A
Line side
25
10 9
7 2
29 29
110
45
E1
25
11
73
G
B
Interlock
CL of breaker release OFF
screw
2.3
30
21
OPEN
40
OPEN
Load side ON or OFF
F
max3.2
H
Breaker mounting hole
49
Door
25.70.5
30
(D+2.5)1
D1
Retaining C3
plate
CL of handle
Dimensions, mm
Retaining plate and supporter (Sold separately)
H-2 H-5
258
235 243
215
70
44
137
67
150
Breaker mounting hole Breaker mounting hole
4-8 4-7
117 45 75
128 to 141 14
102.5
Adjustable height
45 112
Adjustable height
127 to 140
2.3
25 57.5
3.2
06
Description
BZ-type enclosures are available in three types two with V and
G-type handle which allows the operation from the outside and
other with the operating handle of the breaker extending from it
to allow it to be directly switched ON or OFF from outside the
enclosure.
Enclosures with V and G-type handles are provided with a door
interlocking mechanism which prevents the door from being
opened in the ON condition. Standard Dustproof Rainproof
Knockout holes for wiring use are provided as shown in the AF90-780 AF96-175 CP97-2636
diagram.
(For G-type handles, contact FUJI.)
Type of enclosures
H103R BZ-C50B
H203R
Ordering information
Specify the following:
1. Type number of enclosures
Dimensions, mm
Standard With V type handle
BZ6CV10C to BZ-CV40C 178.5 : BZ6CV10C
206.5 : BZ6CV25C
A 191.0 : BZ-CV30C, 40C
CL C D C
OFF
CL
B
E
B
T
SE
RE
Mounting hole
7 : BZ6CV10C, BZ-CV20C
9 : BZ6CV25C to BZ-CV40C
D 17 : BZ6CV25C, BZ-CV30C, BZ-CV40C
Breaker 2-M lead hole
A Mounting hole 7
2-23 lead hole
M lead hole
4-M lead hole
Earth terminal M6
H
H
F G Earth terminal M6
G
BZ-CV60C, 70C
A
D 269
CL C
a b c d
CL
B
E
06
Line Line Load
Line
2-M lead hole Mounting hole 12
CL
2-28 lead hole
Terminal covers
Description
These terminal covers are used as guards to prevent accidental
touch with live line terminations.
These terminal covers can be fitted to either line or load side.
Up to 225AF
Short type BZ-TS
Snap-on fitting
Transparent and black(BZ6TS10 only), sealing possible
Long type BZ-TB
Crimp connection use
Transparent and black(BZ6TB10 only), sealing possible Short type Long type
400AF and larger
Long type BZ-TB
Transparent
B
Breaker
UL Listed
Breaker type Terminal cover Mass Terminal cover Mass Terminal cover Mass
S series E series Short type (g) Long type (g) For flat terminal (g)
SA52RCUL EA102CUL BZ6TS10C2U (Black)* 26.5 BZ6TB10C2U (Black) 69.5
SA53RCUL EA103CUL BZ6TS10C3U (Black)* 33.5 BZ6TB10C3U (Black) 88.5
SA102CUL, SA102RCUL BZ-TS30B-3 43 BZ-TB30B-3 86 BZ-TL30B-3 45
SA103CUL, SA103RCUL
SA202CUL, SA202RCUL BZ-TS40B 60 BZ-TB40B 107 BZ-TL40B 60
SA203CUL, SA203RCUL
SA402CUL, SA402RCUL BZ-TB60B 549
SA403CUL, SA403RCUL
SA602RCUL BZ-TB70B 568
SA803RCUL
Note: * Standard-provided
Insulation barriers
Description
The interphase barriers are provided on frame size of 30AF to
1200AF breakers for front mounting. The barriers are installed
in the molded slots between terminals.
The earth barrier is used to increase the insulation with the
mounting plate surface when two crimp terminals are wired.
Installation of these barriers after wiring is possible even when
an external accessory is installed.
Interphase barrier
Breaker type Interphase barrier Interphase barrier
Type Dimensions, mm Packing Mass B
S series E series L and H series A B quantity (g)
SA32C EA32AC BZ6B10C 50 49 4 23
SA52C, 52RC EA52AC, 52C
SA62C, 62RC EA62C
A
EA102C
SA33C EA33AC
SA53C, 53RC EA53AC, 53C
SA63C, 63RC EA63C
EA103AC, 103C
Breaker
SA102C, 102RC, 102CUL, 102RCUL LA53B(Line*1) BZ-B30B 50 51 4 29
SA103C, 103RC, 103CUL, 103RCUL H52BA, 53BA
H102BA, 103BA
SA102CUL, 103CUL BZ6B30CU 50 58 4 31
SA102RCUL, 103RCUL 58 58 4 06
SA202C, 202RC EA202C H202BA BZ-B40B 80 52 4 48
SA203C, 203RC EA203C H203BA
SA202CUL, 203CUL BZ6B40CU 80 58.5 4 52
SA202RCUL, 203RCUL 90 58.5 4
H103R BZ-B50B 80 90.5 4 82
H203R
SA402C, 402RC, 402CUL, 402RCUL EA402C H402B B-43A 105 95 4 131
SA403C, 403RC, 403CUL, 403RCUL EA403C H403B, 403R
SA603RC, 603RCUL EA603C H603B, 603R
SA803RC, 803RCUL EA803C H803B, 803R
S1003, 1203
SA404H B-44A 105 95 6 195
SA604H, 804H
Earth barrier
Breaker type Earth barrier Earth barrier
Type Dimensions, mm*2 Packing Mass A
S series E series L and H series A B quantity (g)
SA32C EA32AC BZ6BL10C2 100 43 2 33
SA52C, 52RC EA52AC, C (50, 75) (30)
B
Standard type breakers are front mounting front connections. For front mounting, rear connection (X type)
The standard breaker can easily be modified to become front Breaker type Kit type
mounting rear connection and flush mounting types by using the For 2-pole For 3-pole
modification kits. SA30C, 50C, 50RC BZ6X10C502 BZ6X10C503
EA30AC, 50AC, 50C
SA60C, 60RC BZ6X10C1002 BZ6X10C1003
EA60C,100AC, 100C
SA100C, 103RC BZ-X30C-1002 BZ-X30C-1003
SA102RC BZ-X31C-1002
SA225C, 225RC BZ-X40B-2252 BZ-X40B-2253
EA225C
H225BA
SA400C, 400RC BZ-X60B-4002 BZ-X60B-4003
EA400C
H50BA, 100BA BZ-X31C-1002 BZ-X30C-1003
H100R, 225R BZ-X50B-2253
H400B, 400R BZ-X60B-4002 BZ-X60B-4003
Note: BZ6X10C502 for EA102C/50, BZ6X10C503 for EA103C/50
Mass
For front mounting, For front mounting, For flush mounting,
front connection rear connection (X type) rear connection (E type)
Kit type Mass (kg) Kit type Mass (kg) Kit type (g) Mass (kg)
BZ-E50B-2253 1.27
BZ-E60B-4002 3.40
BZ-E60B-4003 3.67
06
Features
This breaker is used for protection of lighting and heating branch circuits.
Compact and light in weight
Large breaking capacity
80(F53B)
80(F52B)
10
Min
6
100
90
50
4
80
2
1
40 Reference temp. 40C
OFF
20
Operating time
150
10
6 25 50 75
4 75
correction ratio (%)
Max. value
2 (15, 20A)
25 M4 or 5
Sec
Rated current
1 12 50
6.5
0.6
0.4 100
Max. value
0.2 (30 to 50A)
Min. value
0.1 (15, 20A)
0.06
0.04
Min. value
107 to 109
F100B
180
120
90
60
Panel drilling
6.5
40
20
Min
10
6 M8 x 16
4 ON side M5 x 12 32
2
7.5
10
1
40 Max. value Reference temp. 40C
20
8.5
Operating time
6.5
150
10
6
4 17
correction ratio (%)
1
Sec
10 6.5
0.6
9.5
0.4 100
0.2
0.1
7.5
0.06 12 15
0.04 32
0.02
0.01 50 17 17
1 1.5 2 4 5 6 8 10 15 20 30 40 60 80 100 0 10 20 30 40 50
Multiple of rated current Ambient temperature (C) F50B F100B
Features
Equipped with a load current pre-trip alarm
Constantly monitors the load current, and outputs an alarm
when the set current is exceeded.
Adjustable rated current
The rated current is easy to vary in 5 to 6 steps using an
adjustment dial.
Wide-range-adjustable trip characteristics KKD06-133
The current and time for instantaneous tripping and short-/
long-time delay tripping can be set by the user. SA E
Adjustable ground fault tripping determinate and set a current
level for ground fault detection in the ranging between 10% to
40% of the rated CT current.
Operating device
Blank: Manual operation Protection function
M: Motor operating Adjustable pre-alarm
Adjustable ground fault current trip
Internal accessory
W: Auxiliary switch Operating voltage for accessory
K: Alarm switch F= : Shunt trip device
F: Shunt trip R= : Undervoltage trip device
R: Undervoltage trip M= : Motor operating mechanism
Ordering information
Specify the following:
1.Type number
S series
Frame 1000A 1200A 1600A
Pole 3 4 3 4 3 4
Type SA1003E SA1004E SA1203E SA1204E SA1603E SA1604E
Rated current(A) Adjustable Adjustable Adjustable
500-600-700-800 600-700-800-1000 800-900-1000-1200
-900-1000 -1200 -1400-1600
Rated insulation voltage(V) AC 690 690 690
DC - - -
Rated breaking JIS C8370 550V AC 50 50 65
capacity (sym) 460V AC 65 65 85
(kA) 220V AC 100 100 130
250V DC - - -
IEC 60947-2 690V AC 25/19 25/19 45/34
(Icu/Ics) 660V AC 25/19 25/19 45/34
BS 4752 (sym)* 600V AC 25/19 25/19 45/34
500V AC 45/34 45/34 65/49
440V AC 65/49 65/49 85/64
400V AC 65/49 65/49 85/64
230V AC 100/75 100/75 125/94
250V DC - - -
Dimensions a d a 210 280 210 280 210 280
c
(mm) b 370 370 370
b c 120 120 140
d 171 171 191
Protection function Long-time delay tripping time (s) 5-30 (at 6In) (Adjustable)
Short-time delay tripping current (A) 2In-10In (Adjustable)
Short-time delay tripping time (s) 0.1-0.3 (Adjustable)
Instantaneous tripping current (kA) 3.0-12 (Adjustable) 3.75-15 (Adjustable) 4.8-19.2 (Adjustable)
Ground fault current tripping or pre-alarm
Mass(kg) Front mounting, front connection 22 28 22 28 27 35
Tripping device Solid-state Solid-state Solid-state
Trip button Provided Provided Provided
Mounting
Front mounting, front connection No marrk Bar stud
Front mounting, rear connection X Bar Stud Bar stud Bar stud
Flush mounting, rear connection E Bar Stud Bar stud
Plug-in mounting P - - -
Internal accessories
Auxiliary switch W
Alarm switch K
Shunt trip F
Undervoltage trip R
External accessories
Motor operating mechanism M
Lead-wire terminal block -
Note: * For SA1200E and SA1600E Available Not available
Protection function
Long-time delay tripping (Rated current adjustable) Adjustable instantaneous tripping
800
6 9
700 1000
600 1200
3 12
I3 Ict
h RATED CUR. (A)
Tripping time
Tripping time
Instantaneous of rated primary current Ict
tripping current
adjustable range
15
10 20
5 30
SEC
T1 at 6 I1
0.03
Time setting range, 5 to 30s at
600% of the rated current I1
600 1200 600% [h] 300 1200
[A] % [lct]
6 6
4 8 OFF ON 4 8
OFF ON
T2 SEC 2 10
T2 SEC
at 10 l1 2 10
06
at 10 l1 I2 I1 I2 I1
Tripping time
2.5
0.2 0.2
0.15 0.25 0.15 0.25
0.1 0.1
Time setting range, 100 to Time setting range, 100 to
300ms 300ms. ramp characteristic
200 1000 200 1000
% [l1] % [l1]
0.7 1.0
0.1 0.4
IP I1 Instantaneous I6 Ict
tripping current
Tripping time
0.1
Time setting range, 100 to
800ms
10 40
% [lct]
Adj. long-time
Adj. delay tripping
pre-trip
alarm
Tripping time (s)
Adj. short-time
Tripping time delay tripping
40
70 80 90 100
Rated current (%) Adj. ground fault, tripping
Adj. instantaneous tripping
30
20 10
Minute
8
6
10 Pre-trip alarm 4 Ground fault tripping
8 pick up current current adj. range
Operating time
6 adjustable range 2
Operating time
40
6
4
20
10 15 20 30 40 50 60 70 80 90100 150 200 300 400 500 6007008001000 (%) 2
900
Percent of the setting current I1
1
Second
0.8
0.6
0.4
0.2
0.1
0.08
Ground fault tripping time
0.04 adj. range
100 200 300 400 800 [msec]
0.02
0.01
1 1.5 2 3 4 5 6 7 8 910 15 20 30 40 50 607080100 (%)
90
Percent of the CT rated current Ict
Operating characteristic
SA1000E SA1200E
120 120
90 90
60 60
40 40
30 30
20 20
Rated current 500, 600, 700, Rated current 600, 700, 800,
adjustable range 800, 900, 1000 [A] adjustable range 1000, 1200 [A]
Minute
Minute
10 10
Long-time delay 5, 10, 15, 20, 30 [s] Long-time delay 5, 10, 15, 20, 30 [s]
6 tripping time Operating time 6 tripping time Operating time
adjustable 20% adjustable 20%
4 range 4 range
Short-time delay 2, 4, 6, 8, 10 Short-time delay 2, 4, 6, 8, 10
2 tripping current x I1 [A] 2 tripping current x I1 [A]
adjustable Operating current adjustable Operating current
1 range 15% 1 range 15%
Max. value Max. value
40 Min. value Short-time delay 100, 150, 200, 40 Min. value Short-time delay 100, 150, 200,
tripping time 250, 300 [ms] tripping time 250, 300 [ms]
Operating time
Operating time
adjustable Operating time adjustable Operating time
20 range 20 range
+50 [ms] +50 [ms]
-20 [ms] -20 [ms]
10 10
Instantaneous 3kA to 12kA Instantaneous 3.75kA to 15kA
6 I 2t tripping current (3 to 12 x ICT [A] ) 6 I 2t tripping current (3 to 12 x ICT [A] )
adjustable Operating current adjustable Operating current
4 Switch 4 Switch
ON range 20% ON range 20%
Ict: CT current 1000A Ict: CT current 1250A
2 2
Second
Second
1 1
0.6 0.6
0.4 0.4
I2t I2t
0.2 Switch 0.2 Switch
OFF OFF
0.1 0.1
0.08 0.08
0.06 0.06
0.04 0.04
06
0.02 0.02
Max. total fault crearing time Max. total fault crearing time
0.01 0.01
1 1.5 2 3 4 5 6 7 8 10 15 20 30 40 50 8090100 1 1.5 2 3 4 5 6 7 8 10 15 20 30 40 50 8090100
Multiple of rated current(A) Multiple of rated current(A)
SA1600E
120
90
60
40
30
20
Rated current 800, 900, 1000,
adjustable range 1200, 1400, 1600 [A]
Minute
10
Long-time delay 5, 10, 15, 20, 30 [s]
6 tripping time Operating time
adjustable 20%
4 range
Short-time delay 2, 4, 6, 8, 10
2 tripping current x I1 [A]
adjustable Operating current
1 range 15%
Max. value
40 Min. value Short-time delay 100, 150, 200,
tripping time 250, 300 [ms]
adjustable Operating time
Operating time
0.6
0.4
I2t
0.2 Switch
OFF
0.1
0.08
0.06
0.04
0.02
Max. total fault crearing time
0.01
1 1.5 2 3 4 5 6 7 8 10 15 20 30 40 50 8090100
Multiple of rated current(A)
Dimensions,mm
SA1000E, 1200E
8 32 15
4-pole
3-pole
80
CL Breaker
13 N
Auxiliary handle
Mounting hole
(Detachable)
78
310
370
338
CL CL CL CL
95
28 18
M8
Mounting
8 screw
70 9
80
105
45 70 70 70 14 29
140 105 175 17 120
210 280 80 171
73
34
120
CL CL
172
338
CL of window
258
CL
15
98
32 8
111
140
R
73
13
13
15
45
70 70 70
70 70 81
Panel 50 Insulation tube
21 230 300
for center pole
Panel cutting dimensions include space
of 1.5mm to the handle window frame.
Dimensions, mm
SA1600E
100
3-pole
30
CL Breaker
N
Auxilliary handle
32.5
(Detachable)
78
310
370
338
CL CL CL CL
95
28 18
M8
Mounting
screw
20
8 70 9
100
105
32
20 46
15
45 70 70 70
17 140
70 70 105 13 80 191
210 280
12
34
65
30
45
CL of
172
338
CL CL CL
window
15
98
115
Connecting length 30
6
R
30
73
15
70 70 70
70 70 81
70
85 230 300
Insulation tube
115
130 Panel cutting dimensions include space
of 1.5mm to the handle window frame.
CCC approved
MCCB types
Series AF 2-poles 3-poles Rated breaking current (Icu/lcs) [kA] *1 Certificate No.
Ue: 230V AC Ue: 400V AC Ue: 440V AC
S 30 SA32C SA33C, SA33CM 5/3 2.5/2 2.5/2 2003010307063635
50 SA52C SA53C, SA53CM 10/5 7.5/4 7.5/4 2003010307063640
SA52RC SA53RC, SA53RCM 25/13 10/5 10/5 2003010307063643
60 SA62C SA63C, SA63CM 10/5 7.5/4 7.5/4 2003010307063646
SA62RC SA63RC 25/13 10/5 10/5 2003010307063647
100 SA102C SA103C 50/25 25/7 2004010307116286
SA103CM 50/25 25/7 2004010307116286
SA102RC SA103RC 100/50 50/13 2004010307116286
SA103RCM 100/50 50/13 2004010307116286
225 SA202C SA203C 50/25 25/7 2004010307116273
SA203CM 50/25 25/7 2004010307116273
SA202RC SA203RC 100/50 50/13 2004010307116273
SA203RCM 100/50 50/13 2004010307116273
400 SA402C SA403C 50/25 35/18 2003010307063390
SA402RC SA403RC 85/43 50/25 2003010307063390
600 SA603RC 85/43 50/25 2003010307063391
800 SA803RC 85/43 50/25 2003010307063391
E 30 EA32AC EA33AC, EA33ACM 2.5/2 1.5/1 1.5/1 2003010307063433
50 EA52AC EA53AC 2.5/2 1.5/1 1.5/1 2003010307063433
EA52C EA53C, EA53CM 5/3 2.5/2 2.5/2 2003010307063635
60 EA62C EA63C, EA63CM 5/3 2.5/2 2.5/2 2003010307063385
100 EA103AC 5/3 1.5/1 2003010307063440
EA102C EA103C, EA103CM 25/13 10/5 10/5 2003010307063647
225 EA202C EA203C 35/18 15/4 2004010307116273
EA203CM 35/18 15/4 2004010307116273
400 EA402C EA403C 35/18 25/13 2003010307063390
600 EA603C 50/25 35/18 2003010307063391
800 EA803C 50/25 35/18 2003010307063391
Note: *1 For rated breaking current and rated voltage, the values in this table are approved.
Internal accessories
Since the user's product information, specific use application, and conditions of use are all outside of Fuji Electric FA
Components & Systems'control, it shall be the responsibility of the user to determine the suitability of any of the
products mentioned for the user's application.
Except to the extent otherwise provided for in the Conditions of Sale issued by Fuji Electric FA, Fuji Electric FA warrants
that the Fuji Electric FA products identified in this catalog shall be free from significant defects in materials and
workmanship provided the product has not been: 1) repaired or altered by others than Fuji Electric FA; 2) subjected to
negligence, accident, misuse, or damage by circumstances beyond Fuji Electric FA's control; 3) improperly operated,
maintained or stored; or 4) used in other than normal use or service. This warranty shall apply only to defects appearing
within one (1) year from the date of shipment by Fuji Electric FA, and in such case, only if such defects are reported to
Fuji Electric FA within thirty (30) days of discovery by purchaser. Such notice should be submitted in writing to Fuji
Electric FA at 5-7, Nihonbashi Odemma-cho, Chuo-ku, Tokyo, Japan. The sole and exclusive remedy with respected to
the above warranty whether such claim is based on warranty, contract, negligence, strict liability or any other theory, is
limited to the repair or replacement of such product or, at Fuji Electric FA's option reimbursement by Fuji Electric FA of
the purchase price paid to Fuji Electric FA for the particular product. Fuji Electric FA does not make any other
representations or warranties, whether oral or in writing, expressed or implied, including but not limited to any
warranty regarding merchantability or fitness for a particular purpose. Except as provided in the Conditions of Sale, no
agent or representative of Fuji Electric FA is authorized to modify the terms of this warranty in writing or orally.
In no event shall Fuji Electric FA be liable for special, indirect or consequential damages, including but not limited to, loss
of use of the product, other equipment, plant and power system which is installed with the product, loss of profits or
revenues, cost of capital, or claims against the purchaser or user of the product by its customers resulting from the use
of information, recommendations and descriptions contained herein. The purchaser agrees to pass on to its customers
and users, in writing at the time inquiries and orders are received by buyer, Fuji Electric FA's warranty as set forth above.
Information in this catalog is subject to change without notice. Printed on 100% recycled paper using soy-based ink