You are on page 1of 27

CATEGORIA 8

NOVA SOLUO PARA REDES ETHERNET 40Gbps

Renato Flvio Cruz


Gerente Tcnico - Cabos
Agenda
Redes atuais para 40 Gbit/s Ethernet
Next Generation Cabling: 40GBASE-T
Category 8 - Cabos e Conectores
Concluses
Redes para 40 Gb/s Ethernet

SUPER DATA CENTERS

10 Gb/s 40 Gb/s 100 Gb/s 400 Gb/s 1.6 Tb/s

1T = 1 Terabits/sec = 1000G
Redes para 40 Gb/s Ethernet

Previso
Servidores x Velocidade

IEEE 802.3
Next Generation BASE-T
July 2012 Plenary
Redes para 40 Gb/s Ethernet

Ethernet BASE-T (IEEE 802.3)

Caractersticas
Compatibilidade x Categorias x RJ45
Canal 100m

Resultado Sucesso !
Baixo custo
Fcil instalao
Facilidade upgrade flexibilidade ...
Redes para 40 Gb/s Ethernet
Redes Ethernet 10GBASE-T opes em COBRE:
GIGALAN AUGMENTED CAT6A 23 AWG X 4P
Redes para 40 Gb/s Ethernet
Redes Ethernet 40GBASE opes em Fibras pticas:
FIBRAS MONOMODO (OS1 / OS2):
100GBASE-LR4
40GBASE-LR4 em 10 km
10 km
100GBASE-ER4
em 40 km

FIBRAS MULTIMODO (OM3 / OM4):


40GBASE-SR4 100GBASE-SR10
100 metros (OM3) em 100/150m
150 metros (OM4)
Redes para 40 Gb/s Ethernet
Redes Ethernet 40GBASE opes em COBRE:

COAXIAL PARALELO TWINAX: 40GBASE-CR4 100GBASE-CR10


em 7m
7 metros

4 PARES TRANADOS 100 :


Next Generation Cabling 40GBASE-T

10 Gb/s X 4 = 40 Gb/s
10GBASE-T 40GBASE-T

Largura banda: 400 MHz Largura banda: 1600 MHz

Capacidade canal: 25 bits/Hz Capacidade canal: 25 bits/Hz

100 metros 30 metros

4 conexes 2 conexes
Next Generation Cabling 40GBASE-T
TIA-942-A TELECOMMUNICATIONS
INFRASTRUCTURE STANDARD FOR DATA CENTERS

10 Gbps 40 Gbps

Fim
Do Jogo

Categoria 6A Categoria 8
100 metros 30 metros
Next Generation Cabling 40GBASE-T

TIA TR 42.7 - Copper Cabling System


Comit TR-42.7: Category 8 Cabling

Adendo ANSI/TIA-568-C.2-1
Next Generation BASE-T:
IEEE 802.3bq 40GBASE-T
Data Center, distncias curtas
Categoria 8: 2000 GHz
Cobre, par tranado
Conector RJ-45
Next Generation Cabling 40GBASE-T

TIA TR 42.7 - Copper Cabling System


2015
Next Generation Cabling 40GBASE-T

TIA TR-42.7 Norma para cabeamento em par tranado

Suportar: 40 Gb/s
Frequncia: 2 GHz
Denominao: CATEGORY 8 (Class I)
Foco aplicao em Data Center
Compatibilidade com Categorias anteriores (RJ-45)
Canal com duas conexes
Comprimento do canal : at 30m
Next Generation Cabling 40GBASE-T

Pesquisa TIA- TR 42.7-2013-02-10


Link em Data Center
Next Generation Cabling 40GBASE-T

Potncia requerida 40GBASE-T

Categoria 8 deve demandar mais potncia para


operar em 40Gbps que a fibra ptica

Resulta em maior aquecimento e maior necessidade


do sistema refrigerao em data centers
Next Generation Cabling 40GBASE-T

TIA TR-42.7 Grupo Estudo: Category 8 Class II

Harmonia com reviso ISO/IEC 11801 para


40Gbps: Category 8.2 Class II
Previsto 3 tipos interfaces :
IEC 60603-7-71 com 12 pinos (ex. GG-45)
IEC 61076-3-110 com 8 pinos (ex. ARJ-45)
IEC 61076-3-104 com 8 pinos (ex. Tera)
Comprimento de canal: pelo menos 30m
Category 8 Cabos e Conectores
Conectividade CATEGORY 8
CATEGORY 8 CLASS I

RJ45 (IEC 60603-7 8 pinos)

CATEGORY 8 CLASS II

IEC 60603-7-71 12 pinos


IEC 61076-3-110 8 pinos
IEC 61076-3-104 8 pinos
Category 8 Cabos e Conectores

Cabo CATEGORY 8
CATEGORY 8 CLASS I CATEGORY 8 CLASS II

Cat. 8 F/UTP Cat. 8 S/FTP


Category 8 Cabos e Conectores

Cabo CATEGORY 8

Dimetro externo: Pouco superior ao Cat 6A e Cat 7A


CATEGORY 8 CLASS I
Cat 6 A F/UTP 7,2 a 7,6mm
Cat 8 F/UTP 7,6 a 8,3mm (?)
CATEGORY 8 CLASS II
Cat 7A S/FTP 7,5 a 8,1 mm
Cat 8 S/FTP 7,8 a 8,5 mm (?)
Category 8 Cabos e Conectores

Parmetros de Transmisso at 2000 MHz


Attenuation, max dB NEXT, min dB PSNEXT, min dB ACRF, min dB PSACRF, min dB RL, min dB (8) PSANEXT, min dB PSAACRF

TIA-568- IEC TIA-CAT TIA-568- IEC TIA-568- IEC TIA-568- IEC TIA-568- IEC TIA-568- IEC TIA-CAT TIA-568- IEC TIA-CAT TIA-568- IEC TIA-CAT
Freq, TIA-CAT 8 TIA-CAT 8 TIA-CAT 8 TIA-CAT 8
C.2 61156-5 8 C.2 61156-5 C.2 61156-5 C.2 61156-5 C.2 61156-5 C.2 61156-5 8 C.2 61156-5 8 C.2 61156-5 8
MHz CAT 8
draft CAT 8 Class II CAT 8 Class II CAT 8 Class II CAT 8 Class II CAT 8 CAT 8
0.9d draft (oct draft (out draft (oct draft (oct draft draft CAT 8
CAT 6A CAT 7A (30m) CAT 6A CAT 7A 0.9d 2013) CAT 6A CAT 7A 0.9d 2013) CAT 6A CAT 7A 0.9d 2013) CAT 6A CAT 7A 0.9d 2013) CAT 6A CAT 7A 0.9d CAT 6A CAT 7A 0.9c CAT 6A CAT 7A draf 0.9
1 2,1 - 0,6 74,3 78,0 75,0 105,4 72,3 75,0 72,3 102,4 67,8 78,0 75,0 100,5 64,8 75,0 75,0 97,5 20,0 20,0 20,0 67,0 n/s 80,0 67,0 n/s 80,0
4 3,8 3,7 1,1 65,3 78,0 66,3 96,4 63,3 75,0 63,3 93,4 55,8 78,0 67,0 88,5 52,8 75,0 64,0 85,5 23,0 23,0 23,0 67,0 n/s 80,0 66,2 n/s 80,0
10 5,9 5,8 1,7 59,3 78,0 60,3 90,4 57,3 75,0 57,3 87,4 47,8 75,3 59,0 80,5 44,8 72,3 56,0 77,5 25,0 25,0 25,0 67,0 n/s 80,0 58,2 n/s 80,0
16 7,5 7,3 2,2 56,2 78,0 57,2 87,3 54,2 75,0 54,2 84,3 43,7 71,2 54,9 76,4 40,7 68,2 51,9 73,4 25,0 25,0 25,0 67,0 n/s 80,0 54,1 n/s 78,1
20 8,4 8,2 2,5 54,8 78,0 55,8 85,9 52,8 75,0 52,8 82,9 41,8 69,3 53,0 74,5 38,8 66,3 50,0 71,5 25,0 25,0 25,0 67,0 n/s 80,0 52,2 n/s 76,2
25 9,4 9,2 2,8 53,3 78,0 54,3 84,4 51,3 75,0 51,3 81,4 39,8 67,3 51,0 72,5 36,8 64,3 48,0 69,5 24,3 24,3 25,0 67,0 n/s 80,0 50,2 n/s 74,2
30,0 10,3 10,1 3,0 52,1 78,0 53,1 83,2 50,1 75,0 50,1 80,2 38,3 65,8 49,5 71,0 35,3 62,8 46,5 68,0 23,8 23,8 25,0 67,0 n/s 80,0 48,7 n/s 72,7
62,5 15,0 14,6 4,4 47,4 78,0 48,4 78,5 45,4 75,0 45,4 75,5 31,9 59,4 43,1 64,6 28,9 56,4 40,1 61,6 21,5 21,5 23,6 65,6 n/s 80,0 42,3 n/s 66,3
100 19,1 18,5 5,6 44,3 75,4 45,3 75,4 42,3 72,4 42,3 72,4 27,8 55,3 39,0 60,5 24,8 52,3 36,0 57,5 20,1 20,1 22,2 62,5 n/s 80,0 38,2 n/s 62,2
200 27,6 26,5 7,9 39,8 70,9 40,8 70,9 37,8 67,9 37,8 67,9 21,8 49,3 33,0 54,5 18,8 46,3 30,0 51,5 18,0 18,0 20,1 58,0 n/s 80,0 32,2 n/s 56,2
250 31,1 29,7 8,9 38,3 69,4 39,3 69,4 36,3 66,4 36,3 66,4 19,8 47,3 31,0 52,5 16,8 44,3 28,0 49,5 17,3 17,3 19,4 56,5 n/s 80,0 30,2 n/s 54,2
300 34,3 32,7 9,8 37,1 68,2 38,1 68,2 35,1 65,2 35,1 65,2 18,3 45,8 29,5 51,0 15,3 42,8 26,5 48,0 16,8 17,3 18,9 55,3 n/s 80,0 28,7 n/s 52,7
500 45,3 42,8 12,8 33,8 64,9 34,8 64,9 31,8 61,9 31,8 61,9 13,8 41,3 25,0 46,5 10,8 38,3 22,0 43,5 15,2 17,3 17,3 52,0 n/s 77,0 24,2 n/s 48,2
600 - 47,1 14,1 63,7 33,6 63,7 60,7 30,6 60,7 39,7 23,4 44,9 36,7 20,4 41,9 - 17,3 16,8 n/s 75,8 n/s 46,6
700 51,1 15,3 62,7 32,6 62,7 59,7 29,6 59,7 38,4 22,1 43,6 35,4 19,1 40,6 16,6 16,3 n/s 74,8 n/s 45,3
800 54,9 16,5 61,9 31,8 61,9 58,9 28,8 58,9 37,2 20,9 42,4 34,2 17,9 39,4 16,1 15,9 n/s 74,0 n/s 44,1
900 58,5 17,6 61,1 31,0 61,1 58,1 28,0 58,1 36,2 19,9 41,4 33,2 16,9 38,4 15,5 15,5 n/s 73,2 n/s 43,1
1000 61,9 18,6 60,4 30,3 60,4 57,4 27,3 57,4 35,3 19,0 40,5 32,3 16,0 37,5 15,1 15,2 n/s 72,5 n/s 42,2
1100 19,6 29,7 59,8 26,7 56,8 18,2 39,7 15,2 36,7 14,9 71,9 41,4
1200 20,5 29,1 59,2 26,1 56,2 17,4 38,9 14,4 35,9 14,7 71,3 40,6
1500 23,2 27,7 57,8 24,7 54,8 15,5 37,0 12,5 34,0 14,0 69,9 38,7
2000 27,2 25,8 55,9 22,8 52,9 13,0 34,5 10,0 31,5 13,1 68,0 36,2

Nota: TIA-CAT 8 draft 0.9d (Apr/2014) e Proposta TIA TG (grupo estudo) Class II Out/2013
Category 8 Cabos e Conectores

PSNEXT & PSACRF

Nota: TIA-CAT 8 draft 0.9d (Apr/2014) e Proposta TIA TG (grupo estudo) Class II Out/2013
Category 8 Cabos e Conectores

Desenvolvimento Furukawa: Testes CAT8 at 2 GHz


CONCLUSES

CANAL
CATEGORIA CABO CONECTIVIDADE APLICAO
(PL)

At 100m
CAT 5e/6/6A UTP RJ45
(mx. 90m)

At 30m
CAT 8 Class I UTP ou FTP RJ45
(mx. 24m)

Pelo menos
CAT 8 Class II FTP 3 TIPOS ?
30m
CONCLUSES

CATEGORIA 8 40GBASE-T

CAT 8 CLASS I LIMITAO COMPRIMENTO


Conectividade padro RJ45
Canal at 30m

CAT 8 CLASS II (em estudo) INTERFACE


Conectividade 3 tipos distintos
Canal pelo menos 30 m
Perguntas ?
VERDADEIRO OU FALSO ?

1. Cabo Cat8 apresenta maior dimetro que cabo Cat 6A VERDADE

2. O maior peso do Cat8 dever causar problemas de manuseio FALSO

3. Cat8 requer maior potncia que fibra ptica para 40 Gbit/s VERDADE

4. Cat8 dever ser padronizado para distncias curtas VERDADE

5. Cat8 no ter a mesma longevidade que cabeamento ptico VERDADE & FALSO

6. Cabo metlico mais fcil e melhor entendido que fibra ptica VOC DECIDE !
Muito
Obrigado !
RENATO FLVIO CRUZ
Gerncia Tcnica de Cabos GTC
55-41-3341-4052
55-41-9994-3860
rfcruz@furukawa.com.br