The electric motor is the workhorse of the modern industry. Its functions are almost unlimited. To control the motors that drive
SITE MENU machinery and equipment we must have electrical supply circuits that perform certain functions. They must provide electrical
current to cause the motor to operate in the manner needed to make it perform its intended function. They must also provide
STORE protection for the motor from adverse mechanical and electrical conditions. These functions are frequently combined within the
VIDEO ARCHIVE electrical equipment that we classify as motor control centers.
EVENT CENTER
A thorough understanding of the function of the various components of a motor control center is desirable from both a
FORUM maintenance and a troubleshooting standpoint. Properly maintained motor control centers ensure a minimum of downtime for
unscheduled repairs, increase productivity, and contribute to a safer working environment.

Menu
1 Terms and Definitions
2 Motor Fundamentals
2.1 Motor Enclosures
2.1.1 Open
2.1.2 Totally Enclosed
2.2 Nameplate Data
2.2.1 Rated Voltage
2.2.1.1 Nominal Rated Voltage
2.2.1.2 Minimum Starting Voltage
2.2.2 Rated Amperage
2.2.3 Rated Speed
2.2.4 Rated Horsepower
2.2.5 Rated Current
2.2.6 Full-load Amperes
2.2.7 Frame Sizes
2.2.8 Duty
2.2.9 NEMA Design Letter
2.2.10 Insulation Class
2.2.11 Service Factor
2.2.12 KVA Code Letter
2.2.13 Power Factor
2.2.14 Temperature Rise
2.2.15 Frequency
2.2.16 Bearings
2.2.17 Locked-Rotor Current
3 Motor Protection
3.1 Short-Circuit Protection of Stator Windings
3.1.1 Motors Other than Essential-Service
3.1.2 Essential-Service Motors
3.2 Stator-Overheating Protection
3.2.1 Motors Other than Essential Service
3.2.2 Essential-Service Motors
3.3 Rotor-Overheating Protection
3.3.1 Squirrel-Cage Induction Motors
3.3.2 Wound-Rotor Induction Motors
3.3.3 Synchronous Motors
3.4 Loss-of-Synchronism Protection
3.5 Undervoltage Protection
3.6 Loss-of-Excitation Protection
3.7 Branch Considerations
3.8 Thermal Protectors
4 Alternating Current Motors
4.1 AC Motor Theory
4.1.1 Rotating Fields
4.1.2 Rotor Behavior in a Rotating Field
4.1.3 Induction
4.2 Induction Motors
4.2.1 Construction
4.2.1.1 Stator
4.2.1.2 Rotor
4.2.1.2 Rotor
4.2.2 Torque
4.2.3 Starting Current
4.2.4 Power Factor
4.2.5 Speed Control
4.2.6 Reversing Rotation
4.3 Synchronous Motors
4.3.1 Construction
4.3.2 Synchronous Motor Operating Principles
4.3.2.1 Rotor Field Excitation
4.3.2.2 Synchronous Motor Pullout
4.3.2.3 Synchronous Motor Torque Angle
4.4 Wound Rotor Motors
4.4.1 Wound Rotor Speed Control
5 Direct Current Motors
5.1 Operating Principles
5.1.1 Armature Construction
5.1.2 DC Motor Ratings
5.1.3 Types of DC Motors
5.1.4 Torque
5.1.5 Starting Current and Counter EMF
5.1.6 Starting Resistance
5.1.7 Armature Reaction
5.1.8 Interpoles
5.1.9 Direction of Rotation of DC Motors
5.2 DC Shunt Motors
5.2.1 Torque
5.2.2 Speed Regulation
5.3 DC Series Motors
5.3.1 Torque
5.3.2 Speed Control and Speed Regulation
5.3.3 Motor Ratings
5.4 DC Compound Motors
5.4.1 Torque
5.4.2 Speed
5.4.3 Speed Regulation
5.4.4 Industrial Applications
6 Connections and Terminal Markings for AC Motors
6.1 Rotation
6.2 Double-Voltage Motors
6.2.1 Three-Phase Star Connection
6.2.2 Three-Phase Delta Connection
6.2.3 Two-Phase Double-Voltage Connection
6.3 Two-Speed Consequent-Pole Motors
6.3.1 Star Connection
6.3.2 Delta Connection
6.3.3 Delta Connection for Constant-Horsepower
6.3.4 Open-Delta Connection Constant-Torque

Talk Page

Terms and Definitions

Before studying the aspects of electric motor control, it is necessary to first study motors. Understanding the basic principles of
operation, terms, definitions, and nameplate information is the cornerstone of motor control fundamentals.
Ampacity: The current in amperes that a conductor can carry continuously under the conditions of use without exceeding its
temperature rating.
Branch Circuit: The circuit conductors between the final overcurrent device protecting the circuit and the outlet(s).
Circuit Breaker: A device designed to open and close a circuit by non-automatic means, and to open the circuit automatically o
a predetermined overcurrent without damage to itself when properly applied within it rating.
Controller: A device or group of devices that serves to govern, in some predetermined manner, the electric power delivered to th
apparatus to which it is connected.
Duty: Motor operational rating in terms of time.
Continuous Duty: Operation at a substantially constant load for an indefinite period of time.
Intermittent Duty: Operation for alternate intervals of (1) load and no-load; or (2) load and rest; or (3) load, no-load, and rest.
Periodic Duty: Intermittent operation in which the load conditions are regularly recurrent.
Short-time Duty: Operation at a substantially constant load for a short and definite, specified time.
Varying Duty: Operation at loads and for intervals of time which both may be subject to wide variation.
Equipment: A general term including material, fittings, devices, appliances, luminaires (fixtures), apparatus, and the like, used as a
part of, or in connection with, an electrical installation.
Ground Fault Circuit Interrupter: A device intended for the protection of personnel that functions to de-energize a circuit or portio
of a circuit within an established period of time when a current to ground exceeds the values established for a Class A device.
Ground Fault Protection of Equipment: A system intended to provide protection of equipment from damaging line to ground fault
currents by operating to cause a disconnecting means to open all ungrounded conductors of the faulted circuit. This protection is
provided at current levels less than those required to protect conductors from damage through the operation of supply circuit
overcurrent devices.
Interrupting Rating: The highest current at rated voltage that a device is intended to interrupt under standard test conditions.
Motor Circuit Switch: A switch, rated in horsepower, capable of interrupting the maximum operating overload current of a motor o
the same horsepower rating as the switch at the rated voltage.
Non-automatic: Action requiring personal intervention for its control. When applied to an electric controller, non-automatic contro
does not imply a manual controller, but only that personal intervention is necessary.
Overcurrent: Any current in excess of the rated current of equipment or the ampacity of a conductor. It may result from overload,
short circuit, or ground fault.
Overload: Operation of equipment in excess of normal, full load rating, or of a conductor in excess of rated ampacity that, when
persists for a sufficient length of time, will cause damage or dangerous overheating. A fault, such as a short circuit or ground fault,
not an overload.
Remote Control Circuit: Any electric circuit that controls any other circuit through a relay or an equivalent device.
Thermal Cutout: An overcurrent protective device that contains a heater element that operates a renewable fusible member to
open a circuit. It is not designed to interrupt short circuit currents.
Thermal Protector: (As applied to motors.) A protective device for assembly as an integral part of a motor or motor compressor
that, when properly applied, protects the motor against dangerous overheating due to overload and failure to start.

Talk Page

Motor Fundamentals

To inspect motors, it is important to know certain motor fundamentals such as nameplate data, construction, motor theory, and th
contributing factors to motor failures as studied and compiled by industry experts.

Talk Page

Motor Enclosures

Motors are usually designed with covers over the moving parts. These covers, called enclosures, are classified by NEMA (National
Electrical Manufacturers Association) according to the degree of environmental protection provided and the method of cooling.
the cover has openings, the motor is classified as an open motor; if the enclosure is complete, the motor is classified as an
motor. Each of these types of motors has many modifications. Table 1 lists the various types possible for both open and totally
enclosed motors.

The different standard types as explained and defined by NEMA are described below.

Talk Page

Open

The most common type of motor is the open motor. It has ventilating openings that permit the passage of external cooling air ove
and around its windings. If these are limited in size and shape, the motor is called a protected motor, since it is protected from any
large pieces of material that may somehow enter the motor, thus damaging its internal parts. A protected motor also prevents a
person from touching the rotating or electrically energized parts of the motor. Drip proof and splash proof motors are constructed
such that drops of liquid cannot enter the motor. The motors described below are all open motor types:
General purpose: Ventilating openings permit the passage of external cooling air over and around the windings of the machine.
Drip-proof: Ventilating openings are constrcuted so that successful operation is not interfered with when drops of liquid or solid
particles strike, or enter, the enclosure at any angle from 0 to 15 downward from the vertical.
Splash-proof: Ventilating openings are constructed so that successful operation is not interfered with when drops of liquid or solid
particles strike, or enter, the enclosure at any angle not greater than 100 downward from the vertical.
Guarded: Openings giving direct access to live or rotating parts (except smooth surfaces) are limited in size by the structural parts
or by screens, baffles, grills, expanded metal, or other means, to prevent accidental contact with hazardous parts.
Semiguarded: Some of the ventilating openings, usually in the top half, are guarded as in the case of a guarded machine, but the
others are left open.
Drip-proof guarded: This type of drip-proof machine has ventilating openings as in a guarded machine.
Externally ventilated: Designates a machine that is ventilated by a separate motor driven blower mounted on the machine
enclosure. Mechanical protection may be as defined above. This machine is sometimes known as a blower ventilated or
ventilated machine.
Pipe ventilated: Openings for the admission of ventilating air are arranged so that inlet ducts or pipes can be connected to them.
Weather protected:
Type I: Ventilation passages are designed to minimize the entrance of rain, snow, and airborne particles to the electrical parts.
Type II: In addition to the enclosure described for a Type I machine, ventilating passages at both intake and discharge are
arranged so that high velocity air and airborne particles blown into the machine by storms or high winds can be discharged
without entering the internal ventilating passages leading directly to the electric parts.
Encapsulated windings: An AC squirrel cage machine having random windings filled with an insulating resin, which also forms a
protective coating.
Sealed windings: An AC squirrel cage machine making use of form wound coils and an insulation system which, using materials,
processes, or a combination of materials and processes, seals the windings and connections against contaminants.

Talk Page

Totally Enclosed

A totally enclosed motor is designed to prevent the free exchange of air between the inside and outside of the actual motor
housing. It is used where hostile environmental conditions and the motor application require maximum protection of the internal
parts of the motor.
The motors described below are all open motor types:
Non ventilated: Not equipped for cooling by means external to the enclosing parts.
Fan cooled: Equipped for exterior cooling by means of a fan or fans, integral with the machine but external to the enclosing parts
Fan cooled guarded: All openings giving direct access to the fan are limited in size by design of the structural parts or by screens,
grills, expanded metal, etc., to prevent accidental contact with the fan.
Explosion-proof: Designed and constructed to withstand an explosion of a specified gas or vapor which may occur within it and to
prevent the ignition of the specified gas or vapor surrounding the machine by sparks, flashes, or explosions of the specified gas or
vapor which may occur within the machine casing.
Dust ignition proof: Designed and constructed in a manner that will exclude ignitable amounts of dust or amounts which might
affect performance or rating, and which will not permit arcs, sparks, or heat otherwise generated or liberated inside the enclosure
to cause ignition of exterior accumulations or atmospheric suspensions of a specific dust on, or in the vicinity of, the enclosure.
Pipe ventilated: Openings arranged so that when inlet and outlet ducts or pipes are connected to them, there is no free exchang
of the internal air and the air outside the case.
Water cooled: Cooled by circulating water, the water, or water conductors, comes in direct contact with the machine parts.
Water air cooled: Cooled by circulating air which, in turn, is cooled by circulating water.

Talk Page

Nameplate Data

The National Electrical Code (NEC) in Section 430.7 has specified information that must be on a motor nameplate based on its typ
(see Figure 1 and Figure 2). Requirements can also be found in NEMA standards MG 1 and MG 2.

Figure 1: Motor Nameplate Information


Figure 2: Nameplate Data

Talk Page

Rated Voltage

The rated or nameplate voltage is the voltage at which the motor operates most effectively. The nameplate rated voltage is
usually lower than the system voltage. For example, in a 480-volt system, the motor nameplates associated with that system would
likely indicate the rated voltage as being 460 volts. The manufacturers make an assumption that there will be a voltage drop of 20
volts from the transformer output to the motor input terminals. When the actual voltage differs from the nameplate, performance
and motor life may be reduced. This is not necessarily true in all cases. It depends on the design of the motor and, specifically,
whether the motor was designed as an energy efficient motor.

Talk Page

Nominal Rated Voltage

Nominal rated voltage is defined as "the voltage rating of the insulation to which the motor is designed to operate."

Talk Page

Minimum Starting Voltage

Minimum starting voltage may be defined as "the lowest voltage at which a motor will start without drawing an excessive/trip
current."

Talk Page

Rated Amperage

Rated amperage may be defined as "the full load current that is required to produce full rated horsepower at the motors rated
voltage and frequency."

Talk Page

Rated Speed

The rated speed of a motor is the speed at which the shaft will turn at rated horsepower if the motor is also running at rated voltag
and frequency. This value is given in revolutions per minute (RPM). This value is not the synchronous speed of the machine, unless o
course, the motor is a synchronous motor.

Talk Page

Rated Horsepower

An induction motor is really a torque generator. It delivers a needed torque to a driven machine at a certain speed. Thus:
For induction motors built to NEMA® standards, the ratings range from 1/2 to 400 hp - 24 in all. If horsepower requirements fall
between any two ratings, the larger motor size should be selected.
Remember, an induction motor will try to deliver any amount of horsepower the load requires. If properly sized, most motors
operate at something less than the motor nameplate horsepower. Standard motors are designed to operate at nameplate value
from sea level up to an altitude of 3,300 feet if the ambient temperature does not exceed 104F (40C). Above this altitude, the
nameplate horsepower no longer applies.
NEMA standards provide a method for determining the proper temperature rise, or the new maximum ambient temperature, at
higher elevations. However, the standards do not provide a direct method for deriving the horsepower. Several methods are
available to estimate true motor horsepower output.

Talk Page

Rated Current

This is the full-load current of a motor that operates under rated frequency and voltage conditions at rated load (HP).

Talk Page

Full-load Amperes

Full-load amps (FLA) on the nameplate indicate the current the motor will draw at full rated load. This value should be valid if the
motor is running at rated horsepower, voltage, and frequency. The full-load amps given on the nameplate is the information used
to determine overload selection.
When the voltage or frequency is not what is indicated on the motor nameplate, the full-load current will change. It is possible to
damage a motor when it is operated below its rated voltage or frequency, since motor current increases in both cases.

At 110% of rated voltage, the motor shows a 7% decrease in FLA.


At 90% of rated voltage, the motor shows an 11% increase in FLA.
At 105% of rated frequency, the motor shows a 5-6% decrease in FLA.
At 95% of rated frequency, the motor shows a 5-6% increase in FLA.

Voltage and frequency change the full-load amps drawn by the motor due to its inherently inductive characteristics.

Talk Page

Frame Sizes

Frame sizes were developed by NEMA to ensure interchangeability of motors among manufacturers, and appear on motor
nameplates to give information about the machines physical dimensions. Key dimensions are:

Distance from motor feet to shaft centerline.


Bolt hole center-to-center distance between front and back feet.
Exposed shaft distance from shaft end to shaft shoulder.

Talk Page

Duty

This block on the nameplate defines the length of time during which the motor can carry its nameplate rating safely. Most often,
this is continuous ("Cont"). Some applications have only intermittent use and do not need motor full-load continuously. Examples
are crane, hoist, and valve actuator applications. The duty on such motors is usually expressed in minutes.

Talk Page

NEMA Design Letter

The NEMA design letter identifies the starting torque characteristics of an induction motor. Do not neglect this information when
replacing motors, because ignoring the letter may lead to misapplication and overload coordination problems. Fans and
centrifugal pumps have starting torque requirements that increase and vary with the square of the change in speed. However,
mixers and conveyors have starting torque requirements that change little with changes in speed.
NEMA letters A, B, C, D, and F account for difference in starting torque requirements among motors. In practicality, these
differences are manifested in the design and construction of the rotor. Most industrial motors are NEMA Design B motors because
they drive conventional loads such as fans, blowers, and pumps. Most electricians estimate starting current drawn by a motor as
being approximately six times the normal full-load current.
Table 2 shows an example of how starting current can vary significantly from the 6X value, and could conceivably cause
unacceptable voltage drops or brown outs if the motor is large enough.
Talk Page

Insulation Class

Often abbreviated "INSUL CLASS" on nameplates, it is an industry standard classification of the thermal tolerance of the motor
winding. Insulation class is a letter designation such as A, B, or F, depending on the windings ability to survive a given operating
temperature for a given life. Insulations of a letter higher into the alphabet perform better. For example, class F insulation has a
longer nominal life at a given operating temperature than class A, or for a given life, it can survive higher temperatures.
Operating temperature is a result of ambient conditions plus the energy lost in the form of heat (causing the temperature rise) as
the motor converts electrical to mechanical energy.

Talk Page

Service Factor

Service factor is a measure of the extra horsepower a motor can deliver if it is operating under rated conditions and is located in a
acceptable ambient environment. A common service factor is 1.15. This means that a motor could deliver 115% of the horsepowe
indicated on the nameplate.

Talk Page

KVA Code Letter

When a motor is started, it draws higher current than it delivers under full-load. This starting current is referred to as inrush current
also called locked-rotor current. While most electricians estimate inrush current as being six times full-load current, this is not alway
the case. The amount of current drawn by a particular motor is determined from the KVA code letter on the motor nameplate.
Table 3 shows KVA code letters and the corresponding KVA required per horsepower.
This letter may become important when a 20 HP motor must be replaced. If the motor being replaced had a KVA code letter of
and was being replaced by a 20 HP motor found in a storage area with a KVA code letter of R, the replacement motor would pu
much higher starting current than the motor being replaced. This situation may cause electricians to think the replacement motor
has bearing problems or other problems that would cause such a high inrush current. Overloads may trip, and anxieties and
confusion may result.

Talk Page

Power Factor

A motors power factor is the ratio of kilowatt input to the kilovolt-ampere input. The number is expressed as a percentage. The
electric motor manufacturers compute the power factor of a number of motors that are loaded at a rated load and a rated
voltage. The power factors of all these motors are then averaged.

Talk Page

Temperature Rise

This is the heat produced by the motor itself. It is the temperature rise above the ambient temperature in which the motor is
physically located. For example, a motor rated at 40C rise operating in a 20C environment should not indicate over 60C when a
direct contact temperature indicating device, or thermal probe, is used. As an electrician, you may use thermal devices to
determine motor temperatures and you should know the conditions under which a motor develops temperature in excess of its
temperature rise. You should know that the majority of motor losses are caused by a breakdown of the insulation system, whether
rapid or progressive. Heat-related breakdowns are common, and must be monitored and corrected by the actions of inspectors.
There will be more information on temperature rise and the variables that affect it later in this article.

Talk Page

Frequency

Frequency is given for AC motors in hertz. Standard frequencies for AC motors are 50 and 60 Hz (cycles per second). Alternating
current in the US has a standard frequency of 60 Hertz per second.

Talk Page

Bearings

Polyphase induction motors require either anti-friction or sleeve bearings. Anti-friction bearings are standard in medium (integral)
horsepower motor sizes through 125 hp/1800 RPM. They are optional in 150 to 600 hp/1800 RPM sizes. Sleeve bearings are standard
in 500 hp/3600 RPM and larger sizes.
Since radial loads are higher at the drive end of the motor, the drive-end bearing has a higher load rating than the bearing at the
opposite end. A typical nameplate might depict both bearing duties as:
Drive shaft brg: 6309 (medium duty)
Opp dr shaft brg: 6207 (light duty)

Bearing internal clearances are C1, C2 (smaller than normal clearance), standard clearance (normal), C3, C4, and C5 (larger tha
normal clearance). Electric motors usually require a C3 internal clearance. Some bearing manufacturers have a different
designation for motor bearings that have a larger-than-normal internal clearance.

Talk Page

Locked-Rotor Current

Locked-rotor current is the steady state current of a motor with the rotor locked and with rated voltage applied at rated frequenc
NEMA has designated a set of code letters to define locked-rotor kilovolt-amperes-per-horsepower (see Table 4). This code letter
appears on the nameplate of all AC squirrel cage induction motors. KVA (thousands of volts multiplied by amperes) is an indicatio
of the current drawn and, indirectly, the impedance of the locked-rotor.

These nameplate code ratings give a good indication of the starting current the motor will draw if the motor cannot turn. These
code letters are sequenced so that a letter at the beginning of the alphabet indicates a relatively low locked-rotor current, and a
letter at the end of the alphabet indicates a high current per horsepower rating of the motor.
Computation of the starting current can be accomplished using the formula:

Example:
What is the approximate starting current of a 7 hp, 220-volt motor with a nameplate code letter of G?
Solution:
The kVA/hp for a code letter of G is 5.6 to 6.3. Taking a number approximately halfway in between and substituting in the formula,
we get:

Therefore, the locked-rotor current is approximately 118 amperes. This locked-rotor current characteristic is important when
purchasing a motor because the buyer must know what current-carrying capacity and overload protection to provide. The buye
must install branch circuit lines large enough to carry the required currents and put in fuses or circuit breakers of the proper size.

Talk Page

Motor Protection
This section deals with the protection of attended synchronous motors, induction motors, synchronous condensers, and the motors
of frequency converters. Motors in unattended stations must be protected against all harmful abnormal conditions. The protection
of very small motors is not specifically described, although the same basic principles apply; this subject is treated in detail in the
National Electrical Code. The practices described here for large motors are at least equal to those covered by the Code, and are
generally more comprehensive. However, it is recommended that the Code be consulted whenever it applies.
The starting energy requirements of AC motors are spread over seconds rather than milliseconds, and vary considerably with the
type of load and with the inertia of the load. However, the peak amplitude of the starting current is generally within reasonable
values.
The table below provides some typical figures as observed on motors selected at random. Note that single-phase induction moto
are the worst, usually having a starting winding that can draw 7 or 8 times the running current for the better part of a second. A 75
millisecond surge duration was observed on several of the various horsepower ratings.
Most magnetic breakers exhibit a reasonably flat frequency response - trip point versus frequency - in applications between 20 an
200Hz. For any response beyond 200Hz, up to 440Hz, special design considerations are required. Beyond 440Hz, the breaker supplie
must be consulted.
A thermal device imbedded inside the motor usually protects induction motors. Most protectors that will handle the starting surge
will not trip out soon enough on lesser overloads to prevent damage to the motor. Here, you are protecting the power wiring rathe
than the device. Magnetic protectors are available which offer a better compromise. Figure 3 shows three delays for several
different motors. The marginal position of single-phase induction motors is obvious.

Figure 3: Time Position of Various Motors on Start

Talk Page

Short-Circuit Protection of Stator Windings

Overcurrent protection is the basic type that is used for short-circuit protection of stator windings. The equipment for this type of
protection ranges, from fuses for motor voltages of 600-volts and lower, through direct-acting overcurrent tripping elements on
circuit breakers, to separate overcurrent relays and circuit breakers for voltages of 2200-volts and higher.
Protection should be provided against a fault in any ungrounded conductor between the interrupting device and the motor,
including its stator windings. Where fuses or direct-acting tripping devices are used, there must be one protective element in each
ungrounded conductor. Where relays and current transformers are used with so-called "AC tripping" from the output of the curren
transformers, a CT and relay are required for each ungrounded conductor. However, if battery or capacitor tripping is provided,
three current transformers with two-phase relays and one ground relay will suffice for a three-phase circuit whether or not the
source neutral is grounded.

Talk Page

Motors Other than Essential-Service

For all except "essential-service" motors, it is the practice to provide both inverse-time and instantaneous phase and ground
overcurrent relays for automatic tripping. The inverse-time phase relays are generally adjusted to pick up at less than about 4 time
rated motor current, but to have enough time delay so as not to operate during the motor-starting period. The instantaneous pha
relays are adjusted to pick up a little above the locked-rotor current. The inverse-time ground relays are adjusted to pick up at no
more than about 20% of rated current or about 10% of the maximum available ground-fault current, whichever is smaller. The
instantaneous ground-relay pickup should be from about 2.5 to 10 times rated current; this relay may be omitted if the maximum
available ground-fault current is less than about 4 times rated current, or if the pickup has to be more than about 10 times rated
current to avoid undesired tripping during motor starting or external faults. If a CT, like a bushing CT, is used with all three-phase
conductors of the motor circuit going through the opening in the core, a very sensitive instantaneous overcurrent relay can be
used that will operate for ground faults within about 10% of the winding from the neutral end.
Percentage-differential relaying is provided for large motors. It is the practice of manufacturers to recommend such protection fo
motors of the following ratings:
2200- to 4999-volts, inclusive, 1500 hp and higher
5000-volts and higher, 501 hp and higher

The advantage of percentage-differential relaying is that it will provide faster and more sensitive protection than overcurrent
relaying, but at the same time, it will not operate on starting or other transient overcurrents.

Talk Page

Essential-Service Motors

For essential-service motors, the inverse-time phase overcurrent relays are usually omitted, leaving the instantaneous phase relays
and the inverse-time and instantaneous ground relays, or the differential relays if applicable. The reason for the omission is to trip
the motor breaker automatically only for short circuits and not to trip for any other reason. This is because the tripping of such a
motor may force a partial or complete shutdown of a generator or other service with which the motor is associated. Any
unnecessary tripping must be avoided. As will be seen when we consider stator overheating protection, supplementary protection
against phase overcurrents less than locked-rotor values is provided.

Talk Page

Stator-Overheating Protection

All motors need protection against overheating resulting from an overload, a stalled rotor, or unbalanced stator currents. For
complete protection, three-phase motors should have an overload element in each phase; this is because an open circuit in the
supply to the power transformer feeding a motor will cause twice as much current to flow in one phase of the motor as in either o
the other two phases, as shown in Figure 4. Consequently, to be sure that there will be an overload element in the most heavily
loaded phase no matter which power-transformer phase is open-circuited, one should provide overload elements in all three
phases. In spite of the desirability of overload elements in all three phases, motors rated about 1500 hp and below are generally
provided with elements in only two phases on the assumption that the open-phase condition will be detected and corrected
before any motor can overheat.

Figure 4: Illustrating the Need for Overcurrent Protection in Each Phase


Single-phase motors require an overload element in only one of the two conductors.

Talk Page

Motors Other than Essential Service

Except for some essential-service motors, whose protection will be discussed later, it is the practice for motors rated less than abou
1500 hp to provide either replica-type thermal-overload relays or long-time inverse-time overcurrent relays or direct-acting tripping
devices to disconnect a motor from its source of supply in the event of overload. Which type of relay to use is largely a matter of
personal preference.
Other things being equal, the replica type will generally provide the best protection because, as shown in Figure 5, its time-current
characteristic more nearly matches the heating characteristic of a motor over the full range of overcurrent. In addition, it may tak
into account the heating effect of the load on the motor before the overload condition occurred.
Figure 5: Typical Motor-Heating and Protective-Relay Characteristics (A) Motor; (B) Replica Relay; (C) Inverse-Time Relay
The inverse-time overcurrent relay will tend to "overprotect" at low currents and to "under protect" at high currents, as shown in
Figure 5. However, the overcurrent relay is very easy to adjust and test, and it is self-reset.

For continuous-rated motors without service factor or short-time overload ratings, the protective relays or devices should be
adjusted to trip at not more than about 115% of rated motor current.
For motors with 115% service factors, tripping should occur at not more than about 125% of rated motor current.
For motors with special short-time overload ratings, or with other service factors, the motor characteristic will determine the
required tripping characteristic, but the tripping current should not exceed about 140% of rated motor current.

Obtain the manufacturers recommendations in each case.


The overload relays will also provide protection in the event of phase-to-phase short circuits, and in practice, one set of such relay
serves both purposes wherever possible.
A survey of the practice of a number of power companies (45) showed that a single set of long-time inverse-time overcurrent
relays, adjusted to pick up at 125 to 150% of rated motor current, is used for combined short-circuit and overload protection of no
essential auxiliary motors; they are supplemented by instantaneous overcurrent relays adjusted as already described. Such inverse
time overload relays must withstand short-circuit currents without damage for as long as it takes to trip the breaker. In addition, the
minimum requirements as to the number of relays or devices for either function must be fulfilled.
Motors rated higher than about 1500 hp are generally provided with resistance temperature detectors embedded in the stator slo
between the windings. If such temperature detectors are provided, a single relay operating from these detectors is used instead o
the replica-type or inverse-time overcurrent relays. In addition, current-balance relays capable of operating on about 25% or less
unbalance between the phase currents should be supplied. If the motor does not have resistance temperature detectors, but is
provided with current-balance relays, a single replica-type thermal overload relay may be substituted for the resistance-
temperature-detector relay.
Specially cooled or ventilated motors may require other types of protective equipment than those recommended here. For such
motors, the manufacturers recommendations should be obtained.

Talk Page

Essential-Service Motors

The protection recommended for some essential-service motors is based on minimizing the possibility of unnecessarily tripping the
motor, even though such practice may sometimes endanger the motor. In other words, long-time inverse-time overcurrent-relays
are provided for all motor ratings, but they merely control an alarm and leave tripping in the control of an operator. Then, for
motors that can suffer locked rotor, supplementary instantaneous overcurrent relays adjusted to pick up at about 200 to 300% of
rated motor current are used, and their contacts are connected in series with the contacts of the inverse-time-overcurrent relays t
trip the motor breaker automatically. The instantaneous relays should be of the high-reset type to be sure that they reset when the
current returns to normal after the starting inrush has subsided. The protection provided by this type of equipment is shown in
6.
Figure 6: Protection Characteristic for Essential-Service Motors (A) Motor; (B) Inverse-Time Relay; (C) Instantaneous Relay
For essential-service motors for which automatic tripping is desired in addition to the alarm for overloads between about 115% of
rated current and the pickup of the instantaneous overcurrent relays, thermal relays of either the replica type or the resistance-
temperature detector type should be used, depending on the size of the motor. Such relays permit operation for overloads as far
as possible beyond the point where the alarm will be sounded, but without damaging the motor to the extent that it must be
repaired before it can be used again.

Talk Page

Rotor-Overheating Protection

Talk Page

Squirrel-Cage Induction Motors

The replica-type or the inverse-time overcurrent relays, recommended for protection against stator overheating, will generally
protect the rotor except where high-inertia load is involved; such applications should be referred to the manufacturer for
recommendations. Where resistance-temperature detector relaying is used, a single replica-type or inverse-time overcurrent relay
should be added for rotor protection during starting.

Talk Page

Wound-Rotor Induction Motors

General recommendations for this type of motor cannot be given except that the stator-overheating protective equipment that
has been described may not protect the rotor. Each application should be referred to the manufacturer for recommendations.

Talk Page

Synchronous Motors

Amortisseur-overheating protection during starting or loss of synchronism should be provided for all "loaded-start" motors. (A
loaded-start motor is a motor other than a synchronous condenser or a motor driving a generator; it includes any motor driving a
mechanical load even though automatic unloading means may be employed.) Such protection is best provided by a time-delay
thermal overload relay connected in the field-discharge circuit.
Amortisseur-overheating protection is not required for "unloaded-start" motors (synchronous condensers or motors driving
generators). An unloaded-start motor is not likely to fail to start on the application of normal starting voltage. In addition, loss-of-
synchronism protection that is provided either directly or indirectly will provide the necessary protection. An exception to this is a
condenser or a motor that has an oil-lift pump for starting.
Where stator-overheating protection is provided by current-balance relaying equipment, the amortisseur is also indirectly protecte
against unbalanced phase currents.
Protection against field winding overheating because of prolonged over-excitation should be provided for synchronous motors or
condensers with automatic voltage regulators without automatic field current-limiting features. A thermal overload relay with time
delay or a relay that responds to an increase in the field-winding resistance with increasing temperature may be used. In an
attended station, the relay would merely control an alarm.

Talk Page

Loss-of-Synchronism Protection

All loaded-start synchronous motors should have protection against loss of synchronism generally arranged to remove the load an
the excitation temporarily and to reapply them when permissible. Otherwise, the motor is disconnected from its source.
For unloaded-start motors, except the synchronous motor of a frequency converter, the combination of undervoltage protection,
loss-of-excitation protection, and the DC generator overcurrent protection that is generally furnished will provide satisfactory loss-o
synchronism protection. Should additional protection be required, it can be provided by an inverse-time overcurrent relay
energized by the current in the running connection and arranged to trip the main breaker. Usually, automatic resynchronizing is n
required. All frequency converters interconnecting two systems should have loss-of-synchronism protection on the synchronous
machine side. With synchronous-synchronous sets, protection may be required on both sides. The protective relaying equipment
should be arranged to trip the main breaker on its side.

Talk Page

Undervoltage Protection

All AC motors, except essential-service motors, should have protection against undervoltage on at least one phase during both
starting and running. For polyphase motors larger than about 1,500 hp, polyphase undervoltage protection is generally provided.
Wherever possible, the protective equipment should have inverse-time delay characteristics.
"Undervoltage release", which provides only temporary shutdown on voltage failure and which permits automatic restart when
voltage is re-established, should not be used with such equipment as machine tools, etc., where automatic restart might be
hazardous to personnel or detrimental to process or equipment.

Talk Page

Loss-of-Excitation Protection

All unloaded-start synchronous motors that do not have loss-of-synchronism protection, as described elsewhere, and that do not
have automatic voltage regulators, should have loss-of-excitation protection in the form of a low-set, time-delay-reset undercurre
relay whose coil is in series with the field winding.
If a motor has loss-of-synchronism protection, amortisseur-overheating protection, and stator-overheating protection, this
equipment indirectly provides loss-of-excitation protection.

Talk Page

Branch Considerations

When a single motor is supplied from a branch circuit, the ampacity of the branch circuit must be 125 percent of motor full-load
current. Overcurrent protection must include up to a 20-second time delay forinduction motors. If a multi-speed motor is used, the
ampacity shall be based on the largest sized motor. Where motors have unusual duty cycle requirements, use the requirements as
listed in Table 5.

Note: Any motor application shall be considered as continuous duty unless the nature of the apparatus it drives is such that the
motor will not operate continuously with load under any condition of use.
If there are several motors on one circuit, the ampacity shall be equivalent to the sum of the individual motor ampacity plus 25
percent of the full-load current rating of the largest motor. Several motors or loads are permitted to be provided for on one branc
circuit if:

System voltage is 600 volts.


The branch protective device protects the smallest installed motor.
All motors are 1HP, 20A (15A) on 120V (600V) circuits where each motor draws 6A, overloads are installed on the motor
and short circuit current and ground fault current do not exceed the branch circuit rating.
It is part of a factory-listed assembly.

In instances where taps are used, short circuit current and ground fault current protection may not be required for the taps used.
This is true if the tap used has the same ampacity as the branch circuit it is connected to. Additionally, the tap cannot be longer
than 25 feet and it must be physically protected from damage.

Talk Page

Thermal Protectors

Thermal protectors are used to protect the motor from overloads and starting failures. All motors with a voltage rating greater than
600V must have a thermal protector, and their overload must not have an automatic reset feature. They shall be set as follows:

Motor full-load current not exceeding 9 amperes 170 percent


Motor full-load current 9.1 to and including 20 amperes 156 percent
Motor full-load current greater than 20 amperes 140 percent
This requirement is based on the maximum full-load motor current as listed in tables provided in Section 430 of the NEC.
Motors that are rated 1500 HP include an RTD in their design which is set to de-energize the motor once the actual
temperature rise of the motor equals the rated temperature rise of the motors insulation.

Talk Page

Alternating Current Motors

Alternating current (AC) motors can be divided into two major types: single-phase and polyphase motors. A single-phase motor is
normally limited to fractional horsepower ratings up to five horsepower. They are commonly used to power such things as fans,
small pumps, appliances, and other devices not requiring a great amount of power. Single-phase motors are not likely to be
connected to complicated motor control circuitry, and will not be discussed in this text.
Polyphase motors comprise the majority of motors needed to drive large machinery such as pumps, large fans, and compressors
found in industrial facilities. These motors have several advantages over single-phase motors in that they do not require a separate
winding or other device to start the motor; they have relatively high starting torque and good speed regulation for most
applications.
There are two classes of polyphase motors: induction and synchronous. The rotor of a synchronous motor revolves at synchronous
speed, or the speed of the revolving magnetic field in the stator. The rotor of an induction motor revolves at a speed somewhat le
than synchronous speed. The differences in rotor speed are due to differences in construction and operation. Both are discussed i
depth after a review of motor theory.

Talk Page

AC Motor Theory

AC motors consist of two parts: the stator, or stationary part, and the rotor, or revolving part. The stator is connected to the
incoming three-phase AC power. The rotor in an induction motor is not connected to the power supply, whereas the rotor of a
synchronous motors is connected to external power. Both induction and synchronous motors operate on the principle of a rotating
magnetic field.

Talk Page

Rotating Fields

This section shows how the stator windings can be connected to a three-phase AC input to create a magnetic field that rotates.
Another magnetic field in the rotor can be made to chase it by being attracted and repelled by the stator field. Because the roto
is free to turn, it follows the rotating magnetic field in the stator.
Polyphase AC is brought into the stator and connected to windings that are physically displaced 120 degrees apart. These
windings are connected to form north and south magnetic poles, as shown in Figure 7. An analysis of the electromagnetic polarity
of the poles at points 1 through 7 in Figure 7 shows how the three phase AC creates magnetic fields that rotate.
Figure 7: AC Generation
At point 1, the magnetic field in phase 1 is at maximum. Negative voltages are shown in phases 2 and 3. The negative voltages in
these windings create smaller magnetic fields, which will tend to aid the field set-up in coil 1-1A.
At point 2, phase 3 creates a maximum negative flux in coil 3-3A. This strong negative field is aided by the weaker magnetic fields
developed by phases 1 and 2.
The three-phase AC input rises and falls with each cycle. Analyzing each point on the voltage graph shows that the resultant
magnetic field rotates clockwise. When the three-phase input completes a full cycle at point 7, the magnetic field has completed
an entire revolution of 360 degrees.

Talk Page

Rotor Behavior in a Rotating Field

An oversimplification of rotor behavior shows how the magnetic field of the stator influences the rotor. First, assume that a simple
bar magnet were placed in the center of the stator diagrams shown in Figure 7. Also, assume that the bar magnet is free to rotate
It has been aligned so that at point 1, its south pole is opposite the large North of the stator field.
Unlike poles attract and like poles repel. As the AC completes a cycle, going from point 1 to point 7, the stator field rotates and
pulls the bar magnet with it because of the attraction of unlike poles and the repulsion of like poles. The bar magnet would be
rotating at the same speed of the revolving flux of the stator. This speed is known as synchronous speed. Synchronous speed of a
motor is given by the equation:

Talk Page

Induction

Current flowing through a conductor sets up a magnetic field around the length of the conductor. Conversely, a conductor in a
magnetic field will produce a current when the magnetic lines of flux cut across the conductor. This action is called induction
because there is no physical connection between the magnetic field and the conductor. Current is induced in the conductor.
In motors, the rotating magnetic field of the stator induces a magnetic field in the rotor. This is simply because it first induces a
voltage in the rotor, and since the rotor is made up of conductors, a current is induced. The induced current in the rotor sets up its
own magnetic field.
The voltage induced by the action of the rotating magnetic field of the stator cutting across the rotor bars is also known as
electromotive force or EMF.
In order for an EMF to be induced, three conditions must be present:

A magnetic field
A current-carrying conductor
Relative motion between the two

This does not mean that the conductor must be carrying current. It simply means that the conductor must consist of a closed path
capable of carrying current.
An equation for EMF is:

This EMF, or induced voltage, and the resultant current flow sets up its own magnetic field. The interaction of the magnetic field of
the stator and the magnetic field of the rotor causes motor rotation and delivers torque. Torque is produced by the interaction of
the stator and rotor fluxes. Torque in an induction motor is discussed in detail later in this article.

Talk Page

Induction Motors

Three-phase squirrel cage induction motors are perhaps the most commonly used motors in industrial applications. They are
relatively small for a given horsepower and have good speed regulation under varying load conditions. They are simple in
construction and rugged; they cost little to manufacture. The induction motor has a rotor that is not connected to any external
sources of power. It derives its name from the fact that the AC voltages are induced in the rotor due to the rotating magnetic field
of the stator.

Talk Page

Construction

Three-phase squirrel cage induction motors consist of a stator, a rotor, and two end shields, which house the bearings that suppor
the rotor shaft. The frame is usually made of cast steel. The stator core is pressed into the frame. The bearings can be either sleeve
or ball bearings. Figure 8 shows the main components of an induction motor.

Figure 8: Components of Induction Motors

Talk Page

Stator

The stator contains a three-phase winding mounted in the slots of a laminated steel core. The winding consists of formed coils of
wire that are spaced so that they are 120 electrical degrees apart. These three windings can be connected wye or delta. To
facilitate this, nine leads are usually brought out of the motor into the motor terminal box. Many motors have two windings per
phase, which allows the motor to be connected to either low-voltage (phase windings in parallel) or high-voltage (phase winding
in series).

Talk Page
Rotor

An induction rotor is composed of a laminated cylinder with slots in its surface. The windings in these slots are one of two types, as
shown in Figure 9. The most common is the squirrel cage rotor. This entire winding is composed of heavy copper bars imbedded
near the outer surface of the rotor. These copper bars are brazed or welded to two copper (or brass) end rings at the end of the
rotor drum. No insulation is required between the core and the rotor bars because of the very low voltages generated in the rotor
bars. The copper bars and the end rings resemble a squirrel cage, thus the name.

Figure 9: Induction Motor Rotor


The rotor may also have fan blades to circulate cooling air through the motor frame, and the shaft of the rotor contains the
necessary keyway or splines to connect pulleys, gears, or other devices to transmit the motor torque to its load.
Regardless of which type of rotor is used, the principle of operation is essentially the same. The AC applied to the stator creates a
revolving magnetic field, which induces an EMF and current in the copper bars of the rotor. This, in turn, creates its own magnetic
field. These two fields then interact to produce rotation and torque. The air gap between the rotor and stator is small, in order to
produce a maximum interaction between these two fields.
Lenz's law states, "An induced EMF tries to oppose the changing field that induces it." In an induction motor, the changing field is
the motion of the resultant stator field. A force is exerted on the rotor by the induced EMF and the resultant magnetic field. This
force tends to cancel the relative motion between the rotor and stator fields. The result is that the rotor moves in the same directio
as the rotating stator field.
It is impossible for the rotor in an induction motor to rotate at synchronous speed (the speed of the revolving field of the stator). If
the speeds were the same, there would be no relative motion between the two and an EMF would not be developed. This is
because the rotating magnetic field of the stator must cut the rotor bars to cause an EMF and create the rotor field.
In order for relative motion to remain between the two, the rotor will always revolve at a speed slightly less than synchronous spee
The difference between the speed of the rotor and the synchronous speed is called slip.
If a three phase induction motors rotor speed is subtracted from the motors synchronous speed, the difference is the slip. Percent
slip is then the ratio of slip to synchronous speed and is expressed by the formula:

The range of percent slip for induction motors is between 2 and 6 percent. As load is applied to a motor, slip increases almost
linearly up to the breakdown torque of the motor, at which time the slip increases non-linearly with increases in torque beyond tha
point. If the motor is loaded beyond this point, there will be a corresponding decrease in torque until the point is reached where
the motor stalls.

Talk Page

Torque

As previously stated, torque in an induction motor is caused by the interaction of the rotor and stator fields. In order that an EMF
and corresponding currents are induced in the rotor, it rotates at a slip. At no-load, the rotor will lag behind the stator flux by a sma
amount necessary to produce the minimum torque required to overcome the rotor weight and motor losses. As load is added, the
rotor speed will naturally increase. This decrease in speed (increase in slip) allows the stator field to rotate past the rotor bars at a
faster rate, inducing larger rotor currents and a larger rotor field. The result is a larger torque at a slower speed.
Since the rotor impedance is low, a small decrease in rotor speed results in a large increase in rotor current and a large increase in
the strength of the rotor field. As the load increases, the larger rotor currents are in such a direction as to decrease the stator flux.
This results in a temporary decrease in counter EMF in the stator windings. This, in turn, allows more current to flow into the stator an
increases the power input to the motor.
The strength of the rotor and stator fields, as well as the phase relationships between them, governs torque.
The power factor of the rotor is dependent on the phase relationship, since power factor is the cosine of the phase angle.
During normal operations, K, , and pf are nearly constant. The torque will increase directly with the rotor current. The roto
current increases almost directly with slip. Increases in slip cause an increase in rotor frequency and rotor reactance.
To understand this, consider a two-pole induction motor. Synchronous speed is calculated at 3,600 rpm. If this motor operates at a
percent slip, then the slip in rpm is:

3,600 x .05 = 180 rpm

Physically, this means that a pair of stator poles will pass a certain rotor conductor 180 times a minute, or three times a second.
Each time a pair of poles moves across a certain conductor, one cycle of EMF will be induced, resulting in a frequency of three
cycles per second. If the slip were to increase to ten percent, or 360 rpm, the frequency of the rotor voltage and current is
increased to six cycles per second. If the slip were to increase to 100 percent, the rotor frequency would be 60 Hz.
From this, you can see how rotor frequency is dependent on slip.

The frequency of the rotor is important insofar as its affect on rotor reactance. Rotor reactance will be almost directly proportiona
to rotor impedance, thus:

From this, we see how increases in slip cause an increase in rotor frequency and rotor reactance. The rotor resistance will be
constant, so an increase in rotor reactance means a decrease in rotor power factor since:

During normal operations, the change in slip is very small as load is added from an unloaded to a fully loaded condition. This mea
that changes in rotor impedance and reactance are tactically negligible. However, as the load is increased beyond rated and fu
load values, the slip increases appreciably. This increase will lower the rate that rotor current increases in such a manner as to resu
in a torque that does not increase directly with slip.
The decreasing power factor and the lowered rate of current increase will result in torque increases that become less rapid and w
finally reach a maximum value. This is usually about 20 percent slip in squirrel cage induction motors. This maximum value of torque
is known as pullout torque. If the load increases even further, the rotor power factor will decrease faster than the rotor current
increases, resulting in a decreasing torque and stalling the motor. Figure 10 shows the relationship between torque and slip.

Figure 10: Torque vs. Slip

Talk Page

Starting Current

At the moment a three-phase induction motor is started, the current supplied to the motor stator terminals may be as high as six
times the motor full-load current. This is because at starting, the rotor is at rest; therefore, the rotating magnetic field of the stator
cuts the squirrel cage rotor at the maximum rate, inducing large amounts of EMF in the rotor. This results in proportionally high
currents at the input terminals of the motor, as previously discussed. Because of this high inrush, current starting protection as high
300 percent of full-load current must be provided to allow the motor to start and come up to speed.
Since there exists 100 percent slip at the instant the motor is energized, the rotor current lags the rotor EMF by a large angle. This
means that the maximum current flow occurs in a rotor conductor at a time after the maximum amount of stator flux has passed
by. This results in a high starting current at a low power factor, which results in a low value of starting torque.
As the rotor speeds up, the rotor frequency and rotor reactance decrease, causing the torque to increase up to its maximum
value, then decrease to the value needed to carry its load.

Talk Page

Power Factor

The power factor of a squirrel cage induction motor is poor at no-load and low load conditions. At no-load, the power factor can
be as low as 15 percent lagging. However, as load is increased, the power factor increases. At high rated load, the power factor
may be as high as 85 to 90 percent lagging.
The power factor at no-load is low because the magnetizing component of input current is a large part of the total input current o
the motor. When the load on the motor is increased, the in-phase current supplied to the motor increases, but the magnetizing
component of current remains practically the same. This means that the resultant line current is more nearly in-phase with the
voltage and the power factor is improved when the motor is loaded, compared with an unloaded motor, which mainly draws
magnetizing current.
Figure 11 shows the increase in power factor from a no-load condition to full-load. In the no-load diagram, the in-phase current
(IENERGY) is small when compared to the magnetizing current (IM); thus, the power factor is poor at no-load. In the full-load
diagram, the in-phase current has increased while the magnetizing current remains the same. As a result, the angle of lag of the
line current decreases and the power factor increases.

Figure 11: PF vs. Load for an Induction Motor

Talk Page

Speed Control

The speed of a three-phase squirrel cage induction motor depends on the synchronous speed of the applied voltage and the
number of poles in the motor, therefore this type of motor has virtually no speed control. As a result, these motors are used in
applications where speed remains constant and where it can be controlled by other means such as variable speed drives.

Talk Page

Reversing Rotation

The direction of rotation of a three-phase induction motor can be readily reversed. The motor will rotate in the opposite direction
any two of the three incoming leads are reversed, as shown in Figure 12.
Figure 12: Three-Phase Induction Motor Rotational Direction Change

Talk Page

Synchronous Motors

The synchronous motor is a three-phase motor that operates at synchronous speed from no-load to full-load.
This type of motor has a revolving field that is energized from a separate source than the stator winding. The rotor is excited by a
direct current source. The magnetic field set up by the direct current on the rotor then locks in with the rotating magnetic field of
the stator and causes the rotor to revolve at synchronous speed. By changing the magnitude of DC excitation, the power factor o
the motor can be changed and can, in fact, be changed over a wide variety of power factors from leading to lagging. Because
of the unique ability to change power factors, synchronous motors are often used as power factor correctors. They are most often
used in applications that require precise speed regulation from no-load to full-load.

Talk Page

Construction

The construction of synchronous motors is essentially the same as the construction of three-phase generators. It has three stator
windings that are 120 electrical degrees apart and a wound rotor that is connected to slip rings where the rotor excitation current
applied.
When three-phase AC is applied to the stator, a revolving magnetic field is created just as it is in induction motors. The rotor is
energized with DC, which creates a magnetic field around the rotor. The strong rotating magnetic field of the stator attracts the
rotor field. This results in a strong turning force on the rotor shaft.
This is how the synchronous motor works once it is started. However, one of the disadvantages of this type of motor is that applying
only DC to the stator cannot start it. When AC is applied to the stator, the high-speed rotating magnetic field rushes past the rotor
poles so quickly that the rotor does not have a chance to get started. The rotor is locked; it is repelled in one direction and then in
another direction. In its purest form, the synchronous motor has no starting torque.
This is easier to understand using Figure 13. When the stator and rotor fields are energized, the poles of the rotating field approach
the poles of the rotor poles of opposite polarity. The attracting force will tend to turn the rotor in a direction opposite that of the
rotating field. As the rotor starts to move in that direction, the rotating field moves past the rotor poles and tends to pull the rotor in
the same direction as the rotating field. The result is no starting torque.
Figure 13: Three-Phase Induction Motor Rotational Direction Change
To allow this type of motor to start, a squirrel cage winding is added to the rotor to cause it to start like an induction motor. This
winding is called an amortisseur winding. The rotor windings are constructed such that definite north and south poles are created
that these poles, when excited by DC, will lock in with the revolving field. The rotor windings are wound about the salient field pole
which are connected in series for opposite polarity. The number of field poles must equal the number of stator poles. The rotor field
windings are brought out to slip rings that are mounted on the rotor shaft. The field current is supplied through carbon brushes to th
field windings.
Figure 14 shows a simplification of a synchronous motor. Figure 15 shows the construction of the rotor pole assembly.

Figure 14: Simplification of a Synchronous Motor


Figure 15: Pole Assembly

Talk Page

Synchronous Motor Operating Principles

When a synchronous motor is started, current is first applied to the stator windings. Current is induced in the amortisseur winding an
the motor starts as an induction motor. The motor then comes up to near synchronous speed to about 5-10 percent slip. At that
point, the field is excited and the motor, turning at high speed, pulls into synchronism. When this occurs, the rotor is turning at
synchronous speed and the squirrel cage winding will not be generating any current and, therefore, not affecting the synchronou
motors operation. The amortisseur windings serve an additional purpose. When the load changes frequently, the motors speed is
not as steady, as the torque angle (discussed later) oscillates (or hunts) back and forth, trying to settle at its required value. This
momentary change in speed creates a current due to induction, and there will be torque in the amortisseur winding. This
momentary torque serves to dampen or stabilize the oscillating torque angle. That is why amortisseur windings are sometimes
referred to as damper windings.

Talk Page

Rotor Field Excitation

The rotor must be excited from an external DC source. Figure 16 shows a simplified synchronous motor excitation circuit. Notice tha
the rheostat can vary the DC field current. However this does not change the speed of the motor. It only changes the power fact
of the motor stator circuit. If full resistance is applied to the rotor field circuit, then the field strength of the rotor is at minimum and
the power factor is extremely lagging. As the DC field strength is increased, the power factor improves and, if current is increased
sufficiently, the power factor can be increased to near unity or 100 percent. This value of field current is referred to as normal
excitation. By increasing the rotor field strength further, the power factor decreases but in a leading direction; that is, the stator
circuit becomes capacitive and the motor is said to be overexcited. The synchronous motor can be used to counteract the
lagging power factor in circuits by adding capacitive reactance to the circuit, thereby bringing the overall power factor closer to
unity.
Figure 16: Simplified Synchronous Motor Excitation Circuit
If the rotor DC field windings of a synchronous motor are open when the stator is energized, a high AC voltage will be induced in i
because the rotating field sweeps through the large number of turns at synchronous speed.
It is therefore necessary to connect a resistor of low resistance across the rotor DC field winding during the starting period. During
the starting period, the DC field winding is disconnected from the source and the resistor is connected across the field terminals. Th
permits alternating current to flow in the DC field winding. Because the impedance of the winding is high compared with the
inserted external resistance, the internal voltage drop limits the terminal voltage to a safe value.

Talk Page

Synchronous Motor Pullout

When a synchronous motor loses synchronism with the system to which it is connected, it is said to be out-of-step. This occurs when
the following takes place singly or in combination:

Excessive load is applied to the shaft.


The supply voltage is reduced excessively.
The motor excitation is lost or too low.

Torque pulsations applied to the shaft of a synchronous motor are also a possible cause of loss of synchronism if the pulsations
occur at an unfavorable period relative to the natural frequency of the rotor with respect to the power system.
A prevalent cause of loss of synchronism is a fault occurring on the supply system. Underexcitation of the rotor is also a distinct
possibility.
Synchronous motor pullout is significant in that the squirrel cage or amortisseur winding is designed for starting only. It is not as hard
as those found in induction motors. The amortisseur winding will not overheat if the motor starts, accelerates, and reaches
synchronous speed within a time interval determined to be normal for the motor. The motor must continue to operate at
synchronous speed. If the motor were to operate at a speed less than synchronous, the amortisseur winding may overheat and
suffer damage.
Protection against a synchronous motor losing synchronism can be provided by polarized field frequency relays and out of step
relays as well as various digital methods. These will be discussed in the motor control center section.

Talk Page

Synchronous Motor Torque Angle

Once the rotor speed is close to synchronous speed at about 90-95 percent of maximum running speed, it will lock on to the
rotating magnetic field. Under these conditions, a running torque will be developed. The rotor will rotate at synchronous speed in a
direction and at a speed determined by synchronous speed.
While the motor is running, the two rotating fields may not line up perfectly. The rotor pole will always lag behind the stator pole by
some angle. This angle is called the torque angle and is shown in Figure 17.

Figure 17: Torque Angle


As the load on the shaft increases, the torque angle increases even though the rotor continues to turn at synchronous speed. This
behavior continues until the torque angle is approximately 90 degrees. At that point, the motor is developing a maximum torque.
Any further increase in load will cause either of the following to occur:
If the increase in load is momentary or very little, the rotor will slip a pole. In other words, the stator field will lose hold of the rotor an
grab onto it again the next time around.
If the increase in load is large enough and not momentary, the motor will lose synchronism and will either stall or cause the rotor to
suffer thermal damage.
In both cases, a noticeable straining sound will be heard.

Talk Page

Wound Rotor Motors

The rotor of a wound rotor motor is wound with insulated windings similar to the stator windings. This three-phase winding is wye-
connected, with the ends of each phase winding being connected to three slip rings. Connected to the rotor circuit through the
slip rings is a wye-connected variable resistance. Figure 18 shows the circuits of a wound rotor motor.

Figure 18: Wound Rotor Motor Circuits


The stator windings of a wound rotor motor are three sets of windings connected 120 electrical degrees apart. These may be
connected either wye or delta. The rotor is a laminated steel cylinder that is slotted to contain the rotor field windings. There are
three-phase windings on the rotor which are also 120 electrical degrees apart and can be connected either wye or delta. The
ends of the phase windings terminate at three slip rings mounted on the rotor shaft. These slip rings are connected through carbon
brushes to speed control equipment external to the rotor. These brushes are held in brush holders that are rigidly attached to the
motor end bell assembly, or end cover.

Talk Page

Wound Rotor Speed Control

The insertion of resistance in the rotor circuit not only limits the starting surge of current, but also produces a high starting torque an
provides a means of adjusting the speed. If the full resistance of the speed controller is cut into the rotor circuit when the motor is
running, the rotor current decreases, and the motor slows down. As the rotor speed decreases, more voltage is induced in the roto
windings and an increase in rotor current is developed to create the necessary torque at the reduced rotor speed.
If all the resistance is removed from the rotor circuit, the current and the motor speed will increase. However, the rotor speed will
always be less than the synchronous speed of the field developed by the stator windings. Recall that this fact is also true of the
squirrel cage induction motor. The speed of a wound rotor motor can be controlled manually or automatically with timing relays,
contactors, and pushbutton speed selection. Figure 19 shows a cutaway view of a wound rotor induction motor.

Figure 19: Cutaway View of Wound Rotor Induction Motor

Talk Page
Direct Current Motors

The operation of DC motors is based on the same principles as AC motors. A current-carrying conductor placed in a magnetic fie
perpendicular to the lines of flux will tend to move in a direction perpendicular to the magnetic lines of flux.

Talk Page

Operating Principles

Stated simply, DC motors rotate because of the two magnetic fields interacting with each other. The DC motor armature acts like
an electromagnet when current flows through its coils. Since the armature (rotor) is located within the magnetic field of the field
poles (stator poles), these two fluxes will interact. Like poles will repel each other and unlike poles will attract one another. The
armature of a DC motor has windings on it that are connected to commutator segments. Figure 20 shows a DC motor field
structure and armature assembly.

Figure 20: DC Motor Field Structure and Armature Assembly

Talk Page

Armature Construction

The armature is a cylindrical iron structure mounted directly on the motor shaft. The armature windings are imbedded in slots in the
surface of the armature, and the ends of the conductors that make up the windings terminate on copper segments on one end o
the armature shaft. Current is applied to these windings through carbon brushes that press against the commutator segments. The
commutator segments change the direction of current in the armature windings as they pass across the poles of opposite polarity
This results in continuous torque in one direction, which causes the armature to rotate.

Talk Page

DC Motor Ratings

DC motors are rated according to their voltage, current, speed, and horsepower output.

Talk Page

Types of DC Motors

There are three types of standard DC motors: series, shunt, and compound. Figure 21 shows the schematic diagrams of these type
The selection of the proper type of motor is based on the type of load that the motor is intended to operate. Note that a series
motor has the field winding in series with the armature, and a shunt motor has the field winding in parallel with the armature. A
compound motor has both a series and a shunt connected field winding.
Figure 21: Standard DC Motor Schematic Diagrams

Talk Page

Torque

Torque of the motor is the twisting force applied to the shaft of the motor by the magnetic field interaction between the field and
the armature. The magnitude of torque depends on the magnetic strengths of those two fields, which is then dependent on the
current flowing through them.

Talk Page

Starting Current and Counter EMF

When a DC motor is in operation, it acts much like a DC generator. The stator produces a magnetic field (field poles), and a loop
wire in the rotor (armature) turns and cuts this magnetic field. To understand counter EMF, first disregard the fact that external
current is being applied to the rotor via the carbon brushes on the commutator segments. As the rotor wires rotate and cut the
magnetic field of the field poles, a voltage is induced in them similar to that discussed in induction motors. This induced voltage
(EMF) causes a current to flow in them, and a resulting magnetic field is created.
Before analyzing the relative direction between the current induced in the armature windings and the current that caused it in the
field poles, first remember the left-hand rule. Using your left hand, hold it so that your index finger points in the direction of the
magnetic field (north to south) and your thumb points in the direction of rotational force on a given conductor. Your middle finge
will now point in the direction of current flow for that conductor. This current would be in opposition to the current that is flowing
from the battery. Since this induced voltage and induced current is opposite to that of the battery, it is called counter EMF
currents are flowing in opposite directions. This would mean that the battery voltage and the counter EMF are opposite in polarity
When first discussing counter EMF, we began by disregarding the fact that external DC was being applied to the armature via the
brushes. The induced voltage and resulting current flow was then shown to flow opposite to the externally applied current. This wa
an oversimplification, because only one current flows at a time. Since the counter EMF can never become as large as the externa
applied voltage, and since they are opposite in polarity, the counter EMF works to cancel only a part of the applied voltage. The
single current that flows is smaller due to the counter EMF.
Since counter EMF of a motor is generated by the action of the armature windings cutting the lines of force set up by the field
poles, the value of it will depend on the field strength and the armature speed.
The effective voltage acting in the armature is the applied voltage minus the counter EMF. Ohms law gives the value of a current
by:

Example: Find the value of counter EMF of a DC motor when it is known that the terminal voltage is 240 V and the armature curren
is 60-amps. The armature resistance has been measured at .08 ohms.

Talk Page

Starting Resistance
Large DC motors require that starting resistance be inserted in series with the motor armature. As seen by the previous equation, th
current drawn by the motor reactance was high as was the case in AC induction motors. This means that the starting current will b
abnormally high unless limited by external starting resistance.
Figure 22 shows a shunt coil that is connected directly across a 250-volt line. The armature resistance is known to be 0.5 ohms. The
full-load current of the motor is known to be 25 amps, and the shunt field current is 1 amp. The resulting armature current under ful
load conditions would, therefore, be 24-amps.

Figure 22: Shunt Motor


If starting resistance is not used, the value of armature current can be found using the following equation:

This amount of starting current is too high and may result in excessive torque and heat, which may cause damage to the motor.
When starting resistance is added in series with the armature, the starting current can be limited to 1.5 times the full-load current
value. After starting, this external resistance can be removed from service.
If we desire to limit starting current to 1.5 times the full-load value, we can solve for the size of resistance that would be required
using the previous equations.
Rstarting = (Vterminal - VCEMF) - IARA

At the moment of motor start, when the rotor is at standstill and the CEMF is zero, the series resistance will be:

To find the wattage required in the starting resistance watts loss is calculated by the I2R method: [(362) (6.44 ) = 8,346].
Example: Find the power developed in both watts and horsepower in a DC motor that has a terminal voltage of 240 volts and an
armature current of 60 amps. The armature resistance is known to be 0.08 ohms.
Answer:

Talk Page

Armature Reaction

When there is no current flowing through the armature of a DC motor, the magnetic line of flux created by the field poles is
undistorted, as shown in Figure 23. The lines of flux run parallel from north to south.
Figure 23: Magnetic Flux
In this case, if a line were drawn in the center of the armature perpendicularly, this line would represent the neutral plane, or
position where the lines of force would have the least effect.
Figure 24 shows current flowing in the armature, but no current flowing in the main field windings. The resulting armature windings
lines-of-flux surround the armature windings in a manner according to Flemings right hand rule.

Figure 24: Armature Reaction


When current flows in both the armature and in the main field windings, as shown in Figure 25, it is clear that the two fields interact
This interaction is called armature reaction. It tends to weaken the main field produced by the main field windings, distort the mai
field, and result in shifting the position of the neutral axis.

Figure 25: Neutral Plane Shift


Armature reaction has a significant effect on the operation of DC motors as well as DC generators. The brushes on the commutat
must be so mounted that they contact the commutator at the neutral plane under load. This is known as the running neutral plane
It is at this point that sparkless commutation can be best obtained, because at this position, the armature coil is undergoing
commutation at a minimum flux.
In DC motors, armature reaction may cause instability of speed with load variations and sparking at the brushes if they are not in
the proper position. Compensating windings and interpoles are often used to counteract armature reaction.

Talk Page
Interpoles

Interpoles provide a commutating flux that generates an EMF necessary to neutralize the EMF of self-induction in the armature coi
undergoing commutation. Since the field flux in the DC motor is distorted by the armature flux, the interpoles are of a polarity
opposite that of the following main pole in the direction of armature rotation.

Talk Page

Direction of Rotation of DC Motors

The direction of rotation of a DC motor is dependent on the relative direction of current flow between the armature windings and
the field windings. Reversing the direction of either of these windings will then change the direction of rotation of the motor. Simply
reversing the input leads to a DC motor will not change the direction of rotation since the input is common to both the armature
and the main field windings.

Talk Page

DC Shunt Motors

A shunt motor is a constant speed motor. If load is increased on a shunt motor, the motor speed will tend to decrease, causing a
decrease in counter EMF, which will then result in an increase in armature current. This continues until the increase in current is
enough to meet the increased torque requirements for the new load condition. The result is that the motor tends to stay in a state
of constant equilibrium.
Figure 26(A) shows a basic diagram of a shunt motor. Note that Figure 26(B) shows a winding in series with the armature. This
winding has only a few turns in series with the armature and is there to counteract armature reaction.

Figure 26: Shunt Motor Configurations


It is important to note that the shunt field circuit of a DC motor should never be opened when the motor is operating, especially
when unloaded. This is because an open field may cause the motor to rotate at dangerously high speeds. Large DC shunt motors
have a field rheostat with a no-field release feature which disconnects the motor from the power source if the field circuit opens.
DC motors have excellent speed control. To operate the motor above rated speed, a field rheostat is used to reduce the field
current and field flux. To operate below rated speed, resistors are used to reduce the armature voltage.

Talk Page

Torque

A DC shunt motor has high torque at any rated speed. At startup, a DC shunt motor can develop up to 150 percent of its normal
running torque as long as the resistors in the starting circuit can withstand the heating effect of the current.

Talk Page

Speed Regulation

The speed regulation of a shunt motor drops from 5 to 10 percent from no-load to full-load. As a result, a shunt motor is superior to
the series DC motor.

Talk Page

DC Series Motors

Talk Page

Torque
A DC series motor develops 500 percent of its full-load torque at starting. Therefore, this type of motor is used in applications where
large amounts of starting torque are needed such as in cranes, railway applications, and other high starting torque demands. Wit
a series motor, any increase in load causes an increase in both the armature current and the field current. Since torque depends
on the interaction of these two flux fields, the torque increases as the square of the value of the current increases. Therefore, series
motors produce greater torque than shunt motors for the same increase in current. The series motor shows a greater reduction in
speed for an equal change in load.

Talk Page

Speed Control and Speed Regulation

The speed control of a series motor is poorer than that of a shunt motor because if the load is reduced, a simultaneous reduction
current occurs in both the armature and field windings, and therefore there is a greater increase in speed than would be in a shun
wound motor.
If the mechanical load were to be disconnected completely from a series motor, the motor would continue to accelerate until th
motor armature self-destructed. For this reason, series wound motors are always permanently connected to their loads.
Varying the applied voltage controls the speed of a series DC motor. A series motor controller usually is designed to start, stop,
reverse, and regulate speed. By reversing either the armature or the field winding current flow, you change the direction of rotatio
of a series motor.

Talk Page

Motor Ratings

Series DC motors are rated for voltage, current, horsepower, and maximum speed.

Talk Page

DC Compound Motors

Compound DC motors are used whenever it is necessary to obtain speed regulation characteristics not obtainable with either the
shunt of series wound motor. Since many applications require high starting torque and constant speed under load, a compound
motor is used. Some industrial applications include drives for elevators, stamping presses, rolling mills, and metal shears.
The compound motor has a normal shunt winding and a series winding on each field pole. They may be connected long shunt
(Figure 27A) or short shunt (Figure 27B). When the series winding is connected to aid the shunt winding, the machine is a cumulativ
compound motor. When the series field opposes the shunt field, the machine is a differential compound motor. Based on practica
experience, all compound DC motors are cumulatively compounded.

Figure 27: Long and Short Shunt Connections

Talk Page

Torque

The operating characteristics of a cumulative compound wound motor are a combination of the series motor and the shunt moto
A cumulative compound wound motor develops high torque for sudden increases in load.

Talk Page

Speed

Unlike the series motor, a cumulative compound wound motor has definite no-load speeds. It will not build up self-destructive
speeds if the load is removed. Inserting resistors in the armature circuit to reduce the applied voltage can control speed control o
a cumulative compound wound motor.
When the motor is reversed frequently, such as for installations in elevators, hoists, and railways, the controller should have voltage
dropping resistors and switching arrangements to reverse the motor direction.
Talk Page

Speed Regulation

The speed regulation of a cumulative compound wound motor is inferior to that of a shunt motor and superior to a series motor.

Talk Page

Industrial Applications

Synchronous motors rated at 20 hp or more are used for constant speed applications. They are used to drive large air and gas
compressors that must be operated at fixed speeds to maintain a constant output at the maximum efficiency. Synchronous moto
are used to drive DC generators, fans, blowers, and large pumps in water pumping stations.
Some industrial applications use three-phase synchronous motors to drive mechanical loads and correct power factor values.
Figure 28 shows a typical industrial feeder. The feeder has a lagging power factor condition due to two induction motors. A
synchronous motor is connected to this same feeder and is operated with an overexcited field. The synchronous motor supplies
leading reactive kilovars to compensate for the lagging kilovars due to the induction motors or other inductive load on the same
three-phase distribution system. The DC field of the synchronous motor can be over-excited enough to supply a value of leading
kilovars equal to the lagging kilovars. As a result, the power factor of the distribution system is corrected to unity.

Figure 28: Synchronous Motor used to Correct Power Factor


The synchronous motor may be used only to correct the power factor and not for driving any mechanical load. It then has the
same function as a bank of capacitors. When used to correct the power factor only, the synchronous motor is called a synchrono
capacitor or a synchronous condenser.
The following example shows how a synchronous motor is used to overcome the lagging kilovars due to induction motors on a
three-phase distribution system.
Example: A three-phase, 220-volt feeder supplies two motors. One motor is a three-phase, wound rotor induction motor. It takes 40
amperes at 81 percent lag power factor. The other motor is a three-phase, synchronous motor that takes 30 amperes at 65 perce
lead power factor. Determine the:
# Watts, volt-amperes, and lagging vars of the wound-rotor induction motor.
# Watts, volt-amperes, and leading vars of the synchronous motor.
# Total load, in kilowatts, supplied to the two motors.
# Power factor of the three-phase feeder circuit.
Solution:
#The apparent power in volt amperes taken by the wound rotor induction motor is:

*The input in watts to the induction motor is:

*The vars taken by the motor is:


2. The apparent power, in volt amperes, taken by the synchronous motor is:

*The input in watts to the synchronous motor is:

*The vars for the synchronous motor is:

3. The total true power, in kilowatts, taken by the two motors in the arithmetic sum of the individual power values for the two moto

4. The reactive power for the entire three-phase feeder is the difference between the lagging and leading vars:

Thus, 254 vars of lagging quadrature power are not overcome by the synchronous motor. This value of lagging vars, combined wit
the total power in watts, gives the apparent power in volt-amperes:

The power factor of the entire system is the ratio of the total true power, in kilowatts, to the total apparent power, in kilovolt-
amperes:

Talk Page

Connections and Terminal Markings for AC Motors

The markings on the external leads of an induction motor are sometimes removed or defaced. Proper identification must be mad
before the motor can be connected to the line. This identification requires only a lighting or ringing circuit, a voltmeter with a rang
covering the motor operating voltage, and a means of measuring approximate resistance.

Take care to prevent short-circuits between leads of the same group, as these leads are all live. Failure to heed this warning can
cause severe personal injury or death, and damage to property!
Talk Page

Rotation

A three-phase motor with three leads brought out can be connected to the line in any convenient way, and then if it rotates in th
wrong direction, any two leads can be interchanged to correct the rotation. If the motor is connected to a gearbox or other
mechanical load that might be damaged by improper rotation, the correct lead sequences should be determined by use of a
phase rotation meter.
A two-phase motor with four leads may be lighted out to determine which leads belong to one phase. These two leads are then
connected to one phase of the line and the other two leads to the other phase. If the motor rotates in the wrong direction, the tw
leads of either phase can be interchanged. The real problem comes with double-voltage and consequent-pole motors, which
have more leads and circuits.

Talk Page

Double-Voltage Motors

Double-voltage motors can be either three-phase or two-phase and can be connected either wye or delta, depending on the
manufacturer.

Talk Page

Three-Phase Star Connection

This type of motor has nine leads and four separate circuits, as shown in Figure 29. Three circuits have two leads each, and the
fourth has three leads. The circuits should be tested out with a lamp or buzzer, and the three leads on a common circuit forming th
internal star should be permanently tagged T7, T8, T9, in any order. The other leads should be temporarily tagged T1, T4 for one
circuit; T2, T5 on the second circuit; and T3, T6 on the third circuit. It will be assumed here that in all cases of double voltage the
motor is wound to operate on 220-440 volts, as this is the most common voltage range. For any other voltages, all of the following
test voltages should be changed in proportion to the motor rating.

Figure 29: Dual-Voltage Three-Phase Star Connection


The motor may be started on 220 volts, with leads T7, T8, and T9 connected to the source of power and all other leads
disconnected. If the motor is too large to be started by connecting it directly to the line, the starting voltage should be reduced a
in the regular operation of the motor. With the motor running light, the voltage across each of the three open circuits should be
measured. This voltage should be slightly under 127 volts and should be the same on all three circuits. With the motor still running,
connect T7 to T4 and measure the voltage across leads T1 and T8, and also across leads T1 and T9. If these voltages are both the
same value and equal about 335 volts, tags T1 and T4 should be marked permanently.
If the two voltages are of the same value and equal about 127 volts, interchange T1 and T4. If the voltage indications between
terminals T1, T8 and T1, T9 are unequal, then disconnect T4 from T7 and connect T4 to T8, measuring the voltages between T1, T7
and T1, T9.
Changes and measurements should be made in this way until a position is found at which both voltages are equal and of a value
of about 335 volts. With the motor still running light, and with leads T7, T8, T9 used as terminals, leads T4, T5, and T6 may be
connected together and the voltage read between leads T1, T2, and T3. The voltage read should equal approximately 220 volts.
For a further check, the motor should be shut down and reconnected, using leads T1, T2, and T3 as terminals, with T4, T5, and T6
connected together and leads T7, T8, and T9 disconnected. Care should be taken to connect the line that was on T7 to T1, the on
that was on T8 to T2, and the one that was on T9 to T3. The direction of rotation should be the same as with the previous
connection. The motor is now ready to operate on 220 volts by connecting T4, T5, and T6 together and using T1, T7 as one lead; T2
T8 as another; and T3, T9 as a third. By connecting T4 to T7, T5 to T8, and T6 to T9, and using T1, T2, and T3 as leads, the motor should
operate on 440 volts.
The connection plate mounted on the motor may disagree with the lead markings as determined herein and shown on Figure 29
indicating that markings T4 and T7 are interchanged, as well as T5 and T8, and T6 and T9. Lead markings as shown in Figure 29A
the present NEMA standard, whereas Figure 29B illustrates the lead marking as formerly used on some dual-voltage star connecte
motors. When remarking motor leads, it is recommended that the present standard marking be adhered to in every case, and,
where necessary, the connection plate be revised or replaced.
Talk Page

Three-Phase Delta Connection

This motor will also have nine leads but only three separate circuits; three leads are connected to each circuit. In this case, it is also
necessary to have an instrument for measuring resistance in addition to other equipment. Only comparative values, not actual
values, are required. Such values can be obtained with a Wheatstone Bridge, or comparative results can be obtained by taking
the voltage drop over the various parts of the circuit with a millivolt meter. There should be a constant value of direct current in th
windings, which should not exceed the current rating of the motor.
It is necessary to find leads T1, T2, and T3, as shown in Figure 29. They can be found by an approximate measurement of resistance
since the resistance from T4 to T9 is twice that from T4 to T1. T2, and T3 are similarly located by corresponding measurements in the
other circuits. These leads should then be permanently marked. The remaining leads in the circuit containing T1 should be
temporarily marked T4 and T9; those in the same circuit with T2 should be marked T5 and T7; and those in the same circuit with T3
should be marked T8 and T6 in any order.

Figure 30: Dual-Voltage Three-Phase Delta Connection


After leads T1, T2, and T3 have been located, the motor should be started and run on 220 volts, using T1, T4, and T9 as leads and
leaving all other terminals disconnected. T4, T7 should then be connected together and the voltage read between T1 and T2. If th
voltage equals approximately 440 volts, the marking is correct. If this voltage is approximately 380 volts, interchange T5 and T7 or T
and T9 and measure the voltage again. If it is approximately 220 volts, interchange T5, T7, and T4, T9. When this voltage equals
approximately 440 volts, mark T4, T9, T7, and T5 permanently, taking care that leads are marked T4 and T7 which, when connecte
together, gives 440 volts between T1 and T2. A similar procedure should then be followed, connecting T6 to T9 and measuring the
voltage between T1 and T3. When the markings are all correct, the voltages between T1, T2, and T3 should equal approximately
440 volts.
As a check, the motor should be shut down and reconnected, using T2, T5, and T7 as leads. Care should be taken that T7 is
attached to the line previously connected to T9, T2 attached to the line previously connected to T1, and T5 to the line previously
connected to T4. When the motor is again started, the direction of rotation should be in the same direction as with the previous
connection. If the direction of rotation is correct, the motor should again be reconnected using T3, T6, and T8 as leads and
connecting the line from T5 to T6, the line from T2 to T3 and the line from T7 to T8.
When the motor is again started, the direction of rotation should be in the same direction as with the previous connections. When
the above tests have been completed, the motor is ready to be connected permanently. If it is desired to run the motor on 220
volts, connect T6, T1, and T7 together and use them as one lead; T4, T2, and T8 as a second lead; and T3, T9, and T5 as a third lead
If it is desired to run the motor on 440 volts, connect T4 to T7, T5 to T8, and T6 to T9 using T1, T2, and T3 as leads. Permanent marking
should be made on all leads.

Talk Page

Two-Phase Double-Voltage Connection

The two-phase, double-voltage motor can always be distinguished by its eight leads (see Figure 31). There are four separate circu
with two leads to a circuit. Trace out the circuits by a lamp or buzzer as in the previous case. Temporarily tag the leads on the first
circuit T1, T5; those on the second circuit T2, T6; those on the third circuit T3, T7; and those on the fourth circuit T4, T8. Start the moto
and run it single phase on 220 volts, using any pair of leads from a single circuit. To do so it will be necessary to bring the motor up
speed by externally applied power. The preferred method is by belting it to another motor. However, any available means of givin
the motor a slight start is satisfactory, as it will come up to speed single phase if given a sufficient start. Connect T7 to T5 and
measure the voltage from T1 to T3. If the voltage equals 440 volts, mark T1, T5, T3, and T7 permanently. If this voltage is zero,
interchange either pair of leads.

Figure 31: Two-Phase Double-Voltage Motor Connection


If the voltage measured equals approximately 310, disconnect T7 and try leads from another circuit until one is found that will give
440 volts from T1 to the lead on the other end of the circuit. When such a circuit is found, mark the leads permanently T1, T5, and T
T3, being careful that leads marked T6 and T7 are those which, when connected, give 440 volts between T1 and T8. This procedure
should then be followed with the other four leads, making final markings as shown in Figure 22.
When all the leads have been permanently marked, the motor may be connected for 440-volt operation by connecting T5 to T7,
to T8 and using T1, T3 as leads for one phase and T2, T4 as leads for the second phase. For operation on 220 volts, connect T1 to T7
T2 to T8, T3 to T5, and T4 to T6. Use T2, T8, and T4, T6 as leads on one phase and likewise for T3, T5, and T1, T7 as leads on the second
phase.

Talk Page

Two-Speed Consequent-Pole Motors

An induction motor using the consequent-pole principle to obtain two speeds with a single winding requires that six leads be
brought out. In this case, all leads are interconnected, so that it is not necessary to test for separate circuits. In the following
discussion, it will be assumed that the motor is wound to run on 220-volts. If it is wound for any other voltage, the test voltages give
should be changed in proportion to the change in rating.

Talk Page

Star Connection

The star-connected motor shown in Figure 32 is used for variable torque ratings having a high-speed horsepower rating four times
the low-speed horsepower rating. If this fact is not apparent from the nameplate reading, the motor can be identified as star-
connected by measuring the resistance between the various leads.

Figure 32: Two-Speed Variable-Torque Star-Connected Motor


Referring to Figure 32A, it can be seen that regardless of between which two leads the resistance is measured, a relative value of
either 1, 2, 3, or 4 must be obtained. For example, if the resistance between T1 and T4 is 1, then between T4 and T6, the resistance
will be 2; between T1 and T6, it will be 3, and between T1 and T2, it will be 4. Hence, the three leads having the highest resistance
(relative value of 4) between them should be located and permanently marked T1, T2, and T3. Then, the resistance between T1
and each of the remaining three unmarked leads should be measured, and the lead that gives lowest resistance (relative value o
1) should be marked T4. Similarly, the resistance between lead T2 and each of the two remaining unmarked leads should be
measured, and the lead that gives a relative resistance of 1 should be marked T6. The final remaining lead should be marked T5.
With the lead marking determined, it should then be checked by running the motor at normal voltage, with T1, T2, and T3
connected to the line and leads T4, T5, and T6 left open. The motor should run at its normal slow speed, this being the series star
connection shown in Figure 32A. The direction of rotation should be noted.
Finally, leads T1, T2, and T3 should be connected together and leads T4, T5, and T6 connected to the line, with T4 to the same line
lead previously used for T1, T5, the line lead previously used for T2, and T6 to the lead used for T3. The motor should run at its norma
high speed and have the same direction of rotation as before, this being the parallel-star connection shown in Figure 32B

Talk Page

Delta Connection

The delta-connected motor shown in Figure 33 for constant torque ratings has a high speed horsepower rating twice the low-spee
horsepower rating. It can be distinguished from the star-connected motor by measuring the resistances. Referring to Figure 33A
can be seen that regardless of between which two leads the resistance is measured, a relative value of either 1, 1.6, or 1.8 must b
obtained. For example, if the resistance between T1 and T6 is 1, then between T1 and T5 it must be 1.8. The lowest value of
resistance obtainable (relative value of 1) between any two leads should be found, and if the motor is delta-connected, it will be
possible to go through all the leads measuring the lowest value of resistance from lead to lead, and ending up at the lead at whic
the start was made.
Figure 33: Two-Speed Constant-Torque Delta-Connected Motor
Start with the first pair of leads that give the lowest resistance (relative value of 1) between terminals, mark them temporarily T1 an
T6. The lead should then be found which will give a resistance to T6 equal to that between T6 and T1. When this lead is found, it
should be marked T2. The lead should then be found which will give the same resistance to T2 as that between T2 and T6, and this
lead should be marked T5. This procedure should be followed until all the leads have been used. They should be marked from the
beginning and in the order in which they are found T1, T6, T2, T5, T3, and T4. When all leads have been marked as described, the
motor should be started and run single phase, applying 110 volts across T1 and T6. The voltage should then be measured between
T1 and T2, between T2 and T3, and between T3 and T1. If each of these readings is 220 volts, then the leads are correctly marked
and the markings should be permanently affixed. If these readings are 110 volts, then permanently re-mark all leads, changing T6
T1, T2 to T6, T5 to T2, T3 to T5, T4 to T3, and T1 to T4. Start up again and with 110 volts single-phase impressed on T1 and T6, check th
voltage from T1 to T2, from T2 to T3, and from T3 to T1, each of which should equal 220 volts.
To operate the motor at slow speed, use T1, T2, and T3 as line leads with leads T4, T5, and T6 disconnected, giving a series delta
connection as shown in Figure 33A. Note the direction of rotation.
To operate at high speed, connect leads T1, T2, and T3 together and connect T4, T5, and T6 to the line, using the same line lead fo
T4 as previously used for T1, similarly for T5 and T2 and for T6 and T3. This should give the same direction of rotation as on previous
slow speed operation and is the parallel star connection shown in Figure 33B.

Talk Page

Delta Connection for Constant-Horsepower

The delta-connected motor for constant horsepower has the same relative resistances between leads as its constant-torque
counterpart; hence, it can be distinguished from the latter only by observing the nameplate rating. The determination of proper
lead marking for the two types of connections is essentially the same.
Referring to Figure 34, first locate any pair of leads that give the lowest resistance between terminals and temporarily mark them T
and T1. The lead should then be found which gives a resistance to T1 equal to that between T4 and T1, and this lead should be
marked T6. The lead should then be found that gives a resistance to T6 equal to that between T6 and T1, this lead being marked T
This procedure should be followed until all the leads are used, and they should be temporarily marked from the beginning and in
the order in which they are found as T4, T1, T6, T2, T5, and T3.

Figure 34: Delta-Connected Motor for Constant-Horsepower


When all leads have been marked as described, the motor should be started and run single phase with 110 volts impressed across
T4 and T1. The voltage should then be measured between T4 and T6, between T6 and T5, and between T5 and T4. If each of these
readings is 220 volts, then the leads are correctly marked and the markers should be permanently affixed. If these readings are 11
volts, then permanently re mark all leads, changing T1 to T4, T6 to T1, T2 to T6, T5 to T2, T3 to T5, and T4 to T3. Start up again, and wit
110 volts single phase applied across leads T4 and T1, check the voltage between T4 and T6, between T6 and T5, and between T5
and T4. Each reading should now be 220 volts.
To operate the motor at high speeds, connect leads T4, T5, and T6 to the line with leads T1, T2, and T3 disconnected, giving the
series-delta connection shown in Figure 34A. Note the direction of rotation.
To operate the motor at slow speed, connect leads T4, T5, and T6 together and T1, T2, and T3 to the line, using the same line lead
for T1 as previously used to T4, and similarly for T2 and T5 and for T3 and T6. This should give the same direction of rotation as
obtained in previous high-speed operation and is the parallel-star connection shown in Figure 34B.

Talk Page

Open-Delta Connection Constant-Torque


The open-delta connection is frequently used for consequent-pole motors, particularly for four-speed, two-winding motors to avoi
the possibility of harmful circulating currents being induced in the idle winding while the other is energized. The connections are
identical to the previously discussed closed-delta connections, except that one corner of the delta is opened and an extra lead,
T7, is provided.
Figure 35 shows the lead markings for the open-delta constant-torque connection. There are six relative values of resistance
between leads, these being 1, 2, 3, 4, 5, or 6, depending upon which pair of leads is used. First, locate the pair of leads that give th
highest resistance (value of 6) and mark these leads T3 and T7. Then, the lead should be located that gives the lowest resistance
(relative value of 1) to T3, and this lead should be marked T4. Then the unmarked lead should be located that gives the lowest
resistance (relative value of 1) to T4, and this lead should be marked T1. This procedure should be followed until all leads are used,
and they should be marked from the beginning and in the order in which they are found as T3, T4, T1, T6, T2, T5, and ending with T7
The connections for a two-speed motor are shown in Figure 35.

Figure 35: Open-Delta Constant-Torque Connection