PROYEK PEMBANGUNAN

PABRIK MINYAK GORENG


KAP. 600.000 TON CPO/TH
Document No.
Rev. 3
FIRE FIGHTING & SAFETY EQUIPMENT DATASHEET
PMG-ENG-O-DSH-U00-001-W
Page 8
GENERAL INFORMATION
Equipment : Pillar Hydrant Tag : PH-001~017
Location : Note 3 Quantity : 17
Manufacturer : (*) Dimension : (*)
Model : (*)
TECHNICAL DATA
Environmental Data Location : Offshore Onshore Other
Atmosphere : Salt Laden Tropical Other
o
Ambient Temperature: 24-32 C Humidity : 59-92 %
Wind Speed : 120 km/hour

Equipment Data Type : Pillar hydrant, 4" with a single


hydrant valve, and 2 x 2-1/2" outlets
with chained caps
Inlet size : 4" 150# FF
Outlet connection : 2-1/2" Instantaneous
Flowrate : 2 x 946 lpm
Range of Throw : 30 m
Dimension : Note 1 mm
Weight : Note 1 kg
Working pressure : 7 barg
Max pressure : 16 barg
Material : Cast Iron
Color : Red
Valve : Two units 2-1/2" hydrant valves
& pressure control valve
Cap & chain : Two 2-1/2" caps (bronze/brass)
& chains (Stainless Steel)
Hand-wheel direction : Clockwise to close
Marking : "OPEN" & "CLOSED" on the wheel
Applicable Standards : NFPA 14; NFPA 24; NFPA 1963

Hose Cabinet Description : Fire hydrant cabinet consists of two 30 meters (100 ft) of 2-1/2" fire
hoses and two nos jet nozzles with 2-1/2" french symetric coupling
Material : U/V resistant glass fiber or epoxy coated steel construction
Door : Double swing fitted with a quick release non-lockable handle
Quantity : 17 (one (1) for each pillar hydrant)
Color : Red
Standard : NFPA 24

Hose, Nozzle & Adapter Hose Material : Collapsible rubber coated, heat and oil resistant
Max hose opt press. : 20 barg (*)
Hose Length : 30 m
Hose Quantity : 2 each per cabinet
Nozzle Material : Pyrolite (*)
Nozzle inlet pressure : 3.5 bar
Nozzle Quantity : 2 each per cabinet
Adapter : 2-1/2" adapter to connect 2 hoses
Adapter Material : Note 1
Adapter Quantity : 1 each per cabinet

Marking "FIRE HOSE" (in white letter)

NOTE
* Vendor to specify and verify data.
1. Vendor to advise as per manufacture standard
2. Instruction for use to be included
3. The location of hydrant pillar shall refer to Fire Fighting & Safety Equipment Layout (PMG-ENG-O-GEN-U00-001-W)