Model RC-1 Retard Chamber


For Variable Pressure Wet Pipe Sprinkler Systems
300 psi (20,7 bar)
General Technical
Description Data
The Model RC-1 Retard Chamber is Approvals
required in installations that will be UL and ULC Listed, as well as FM,
subject to pressure variations, as are LPCB, and VdS Approved for use with
generally associated with public water the following Alarm Check Valves:
supplies in order to help prevent false
alarms. The RC-1 is specifically in- Model AV-1-175
tended for use as a separately ordered Gem Model F20/F200/F2001
item for the Model AV-1-300 (TFP910) Gem Model A
and AV-1-175 (TFP912) Alarm Check Star Model S30/S300/S3001
Valves. It can, however, also be used UL and ULC Listed, as well as FM
as a separately ordered item for Approved for use with the Model AV-
changing out older style Retard Cham- 1-300 Alarm Check Valves.
bers used with the Central Model F/G,
Gem Model A, or Star Model E/F Alarm Working Water Pressure
Check Valves. 300 psi (20,7 bar)
The Model RC-1 Retarding Chamber Construction
is a redesignation for the Gem Model The Model RC-1 Retard Chamber
F211 for use with Gem Model shown in Figure 1 is cast iron, and a matically drain out through the 1/8"
F20/F200/F2001 Alarm Check Valves, 3/4" x 1/2" x 3/4" Tee is provided at the (3,2 mm) drain orifice in the Restriction
as well as the Star Model S310 for use outlet (top) for connection of a pres- Assembly (Figure 2) when the Alarm
with Star Model S30/S300/S3001 sure alarm switch and/or water motor Valve Clapper closes (due to a discon-
Alarm Check Valves. alar m. The Restriction Assembly tinuation in the flow of water into the
shown in Figure 2 is comprised of sprinkler system).
WARNING
brass restrictions assembled to a cast
The Model RC-1 Retard Chamber de- In the case of variable pressure sys-
iron or malleable iron threaded tee fit-
scribed herein must be installed and tems, a transient surge in supply pres-
ting. The screen is stainless steel.
maintained in compliance with this sure that is sufficient to only momen-
document, as well as with the applica- tarily open the Alarm Valve Clapper
ble standards of the National Fire Pro-
tection Association, in addition to the
Operation will not cause a false alarm, since the
volume of the Retard Chamber is suf-
standards of any other authorities hav- When there is a steady flow of water ficiently large enough that it will not
ing jurisdiction. Failure to do so may into the sprinkler system due to a have filled to operate the connected
impair the integrity of this device. sprinkler operation, the Clapper in the alarm devices. Any water in the alarm
The owner is responsible for maintain- Alarm Check Valve opens as shown in line is then automatically drained, fur-
ing their fire protection system and de- Figure 3. Water is then permitted to ther reducing the possibility of a false
vices in proper operating condition. flow into the centrally located groove in alarm due to a successive transient
The installing contractor or sprinkler the Seat Ring and out through the surge in supply pressure.
manufacturer should be contacted alarm port towards the Restriction As-
relative to any questions. sembly (Figure 2). When the flow
through the inlet restriction of the Re-
striction Assembly exceeds the flow
out through the outlet restriction, the
Retard Chamber begins to fill. Sub-
sequently, the water motor alarm
and/or the pressure alarm switch will
be actuated. The alarms will continue
to be actuated as long as the Clapper
in the Alarm Check Valve remains
open. Water in the alarm lines will auto-

Page 1 of 4 JANUARY, 2004 TFP920


Close

Page 2 of 4 TFP920

1/2" NPT
Installation
WATERFLOW
PRESSURE
The Model RC-1 Retard Chamber
ALARM SWITCH SCREEN
must be installed in accordance with
CONNECTION INLET the specific instructions provided with
RESTRTICTION FITTING the Tyco Fire Products Model AV-1-
3/4" NPT WATER 3/4" x 1/2" x 3/4" WITH 0.219" (5.6 mm) 300 (TFP910) or Model AV-1-175
MOTOR ALARM REDUCING TEE ORIFICE (TFP912) Alarm Check Valves. The
CONNECTION standard trim for these Alarm Check
3/4" x 1-1/2" Valves includes all of the necessary
9-1/8" NIPPLE components including the Restriction
(232,0 mm) Assembly shown in Figure 2.
END-TO-END
1 GAL.
(3,8 L)
In the case of retrofitting Central Model
NOMINAL F/G Alarm Check Valves refer to Fig-
CAPACITY ure 4; In the case of retrofitting Gem
Model A Alarm Check Valves refer to
Figure 5; and, in the case of retrofitting
Star Model E/F Alarm Check Valves
refer to Figures 6 and 7.
NOTE
DRAIN When retrofitting per Figures 4, 5, 6, or
1/2" NPT INLET RESTRTICTION FITTING
CONNECTION
7, the Restriction Assembly, Y-
WITH 0.125" (3.2 mm) Strainer, and associated pipe nipples
ORIFICE and fittings must be ordered sepa-
8-1/8"
(206,0 mm)
rately to complete the installation.
DIA. Apply pipe thread sealant sparingly to
male threads only.

FIGURE 1 FIGURE 2
MODEL RC-1 RETARD RESTRICTION Care and
CHAMBER ASSEMBLY
Maintenance
The owner is responsible for the in-
WATERFLOW spection, testing, and maintenance of
PRESSURE 4 their fire protection system and de-
ALARM SWITCH
ONCE RETARD vices in compliance with this docu-
CHAMBER OVERFLOWS, ment, as well as with the applicable
WATERFLOW PRESSURE standards of the National Fire Protec-
ALARM SWITCH AND tion Association (e.g., NFPA 25), in
RETARD
WATER MOTOR 1 addition to the standards of any
ALARM ACTUATE
CHAMBER UPON SPRINKLER authority having jurisdiction. The in-
WATERFLOW FLOW, WATERWAY stalling contractor or product manufac-
TO WATER CLAPPER OPENS turer should be contacted relative to
MOTOR ALARM WATERFLOW any questions.
TO SYSTEM
7/32" It is recommended that automatic
(5,6 mm) SYSTEM
ORIFICE
sprinkler systems be inspected,
PRESSURE
INLET GAUGE
tested, and maintained by a qualified
RESTRICTION Inspection Service.
ASSEMBLY
Specific consideration must be given
1/8" to cleaning the Screen within the Re-
(3,2 mm)
ORIFICE
striction Assembly, as well as the Y-
SUPPLY Strainer. More frequent cleaning than
OUTLET PRESSURE
GAUGE
that required by NFPA 25 may be nec-
3 essary as determined after the first
WHEN FLOW THROUGH inspection and is a function of the
RESTRICTION ASSEMBLY water quality with respect to water
INLET EXCEEDS OUTLET, MAIN borne debris.
RETARD CHAMBER DRAIN 2
BEGINS TO FILL VALVE WATERFLOW
NOTES
THROUGH SEAT Before closing a fire protection system
RING GROOVE AND control valve for inspection or mainte-
ALARM PORT nance work on the fire protection sys-
tem that it controls, permission to shut
down the affected fire protection sys-
FIGURE 3 tem must first be obtained from the
MODEL RC-1 RETARD CHAMBER proper authorities, and all personnel
OPERATION
Close

TFP920 Page 3 of 4

1/2" NPT
WATERFLOW
PRESSURE
NIPPLES & FITTINGS 1 ALARM SWITCH
NO. DESCRIPTION QTY. CONNECTION
3/4" NPT WATER
1 3/4" x 1/2" 90 MOTOR ALARM
Reducing Elbow . . . . . . . . 1 CONNECTION
1/2" NPT 2 1/2" x 1-1/2" Nipple . . . . . 3
WATERFLOW 3 1/2" x 2" Nipple . . . . . . . . 1 REMOVE
PRESSURE 4 Select per Table . . . . . . . 1 GEM MODEL A-3
ALARM SWITCH RETARD CHAMBER
CONNECTION MODEL RC-1 1
Nipples & fittings WITH ALARM TRIM
RETARD CHAMBER may be acquired REFER TO DATA
P/N 52-211-1-002 2 from sources other SHEET TD1-1
than TFP.
3/4" NPT WATER GEM MODEL A
MOTOR ALARM 1/2" Y-STRAINER 2
Includes nipple and 1/2" NPT
ALARM CHECK VALVE
CONNECTION P/N 52-353-1-005 tee per Figure 1. WATERFLOW
WITH BASIC TRIM
(6"/DN150 SHOWN) PRESSURE
1
Valve Nipple 4 Size REFER TO DATA ALARM SWITCH
MODEL RC-1 CONNECTION
2 4" (DN100) 3/4" x 6" SHEET TD1 RETARD CHAMBER
4
2 6" (DN150) 3/4" x 4-1/2" P/N 52-211-1-002
2 8" (DN200) 3/4" x 1-1/2" (INCLUDES NIPPLE &
RESTRICTION 3 TEE PER FIGURE 1)
ASSEMBLY 3/4" NPT WATER
P/N 92-210-1-005 MOTOR ALARM
(SEE FIGURE 2) CONNECTION

RESTRICTION
ASSEMBLY
P/N 92-210-1-005
(SEE FIGURE 2)
CENTRAL MODEL F/G GEM MODEL A
ALARM CHECK VALVE ALARM CHECK VALVE REMOVE
ROTATE EXISTING WITH ALARM TRIM WITH BASIC TRIM ORIGINAL DRIP FUNNEL
RETARD CHAMBER DRAIN TRIM (6"/DN150 SHOWN) (6"/DN150 SHOWN) ALARM TRIM (IF REQUIRED)
TO ACCOMMODATE NEW REFER TO DATA REFER TO DATA TO THIS
RETARD CHAMBER TRIM SHEET 7-3.0 SHEET TD1 POINT

1/2" Y-STRAINER
P/N 52-353-1-005

FIGURE 4 FIGURE 5
MODEL RC-1 RETARD CHAMBER MODEL RC-1 RETARD CHAMBER
WITH CENTRAL MODEL F/G ALARM CHECK VALVES WITH GEM MODEL A ALARM CHECK VALVES

who may be affected by this action components which have been subject
must be notified. Limited to misuse, improper installation, corro-
sion, or which have not been installed,
After placing a fire protection system
in service, notify the proper authorities Warranty maintained, modified or repaired in ac-
cordance with applicable Standards of
and advise those responsible for moni- Products manufactured by Tyco Fire the National Fire Protection Associa-
toring proprietary and/or central sta- Products are warranted solely to the tion, and/or the standards of any other
tion alarms. original Buyer for ten (10) years Authorities Having Jurisdiction. Mate-
against defects in material and work- rials found by Tyco Fire Products to be
manship when paid for and properly defective shall be either repaired or
installed and maintained under normal replaced, at Tyco Fire Products sole
use and service. This warranty will ex- option. Tyco Fire Products neither as-
pire ten (10) years from date of ship- sumes, nor authorizes any person to
ment by Tyco Fire Products. No war- assume for it, any other obligation in
ranty is given for products or connection with the sale of products or
components manufactured by compa- parts of products. Tyco Fire Products
nies not affiliated by ownership with shall not be responsible for sprinkler
Tyco Fire Products or for products and
Close

Page 4 of 4 TFP920

NIPPLES & FITTINGS 1 NIPPLES & FITTINGS 1


NO. DESCRIPTION QTY. NO. DESCRIPTION QTY.
1 3/4" x 1/2" 90 1 3/4" x 1/2" 90
Reducing Elbow . . . . . . . . 1 Reducing Elbow . . . . . . . . 1
1/2" NPT 2 1/2" x 1-1/2" Nipple . . . . . 3 2 1/2" x 1-1/2" Nipple . . . . . 3 1/2" NPT
WATERFLOW 3 3/4" x 3-1/2" Nipple . . . . . 1 3 3/4" x 3-1/2" Nipple . . . . . 1 WATERFLOW
PRESSURE PRESSURE
ALARM SWITCH 1
ALARM SWITCH
CONNECTION MODEL RC-1 Nipples & fittings 1
Nipples & fittings MODEL RC-1 CONNECTION
RETARD CHAMBER may be acquired may be acquired RETARD CHAMBER
P/N 52-211-1-002 2 from sources other from sources other P/N 52-211-1-002 2
than TFP. than TFP.
3/4" NPT WATER 3/4" NPT WATER
MOTOR ALARM 1/2" Y-STRAINER 2
Includes nipple and 2
Includes nipple and 1/2" Y-STRAINER MOTOR ALARM
CONNECTION P/N 52-353-1-005 tee per Figure 1. tee per Figure 1. P/N 52-353-1-005 CONNECTION
1 1
REMOVE AND REMOVE AND
RESTRICTION 2 3 DISCARD EXISTING DISCARD EXISTING 3 2 RESTRICTION
ASSEMBLY 2 3/4" x 2" NIPPLE 3/4" x 2" NIPPLE 2 ASSEMBLY
P/N 92-210-1-005 2 2 P/N 92-210-1-005
(SEE FIGURE 2) (SEE FIGURE 2)

SEPARATE SEPARATE
EXISTING 1/2" EXISTING 1/2"
UNION HALVES UNION HALVES
TO FACILITATE TO FACILITATE
ASSEMBLY OF ASSEMBLY OF
NEW RETARD NEW RETARD
CHAMBER CHAMBER
TRIM TRIM
STAR MODEL F
STAR MODEL E ALARM CHECK VALVE
ROTATE EXISTING ALARM CHECK VALVE WITH ALARM TRIM ROTATE EXISTING
RETARD CHAMBER DRAIN TRIM WITH ALARM TRIM (6"/DN150 SHOWN) RETARD CHAMBER DRAIN TRIM
TO ACCOMMODATE NEW REFER TO DATA REFER TO DATA TO ACCOMMODATE NEW
RETARD CHAMBER TRIM SHEET 2-1.1.20 SHEET 2-1.1.10 RETARD CHAMBER TRIM

FIGURE 6 FIGURE 7
MODEL RC-1 RETARD CHAMBER MODEL RC-1 RETARD CHAMBER
WITH STAR MODEL E ALARM CHECK VALVES WITH STAR MODEL F ALARM CHECK VALVES

system design errors or inaccurate or ABILITY EXCEED AN AMOUNT clude the description and Part Number
incomplete information supplied by EQUAL TO THE SALES PRICE. (P/N).
Buyer or Buyers representatives.
THE FOREGOING WARRANTY IS
RC-1:
IN NO EVENT SHALL TYCO FIRE MADE IN LIEU OF ANY AND ALL
Specify: Model RC-1 Retard Chamber
PRODUCTS BE LIABLE, IN CON- OTHER WARRANTIES EXPRESS OR
w/galvanized steel fittings,
TRACT, TORT, STRICT LIABILITY OR IMPLIED, INCLUDING WARRANTIES
P/N 52-211-2-002.
UNDER ANY OTHER LEGAL THE- OF MERCHANTABILITY AND FIT-
ORY, FOR INCIDENTAL, INDIRECT, NESS FOR A PARTICULAR PUR- NOTE
SPECIAL OR CONSEQUENTIAL POSE. When retrofitting per Figures 4, 5, 6, or
DAMAGES, INCLUDING BUT NOT 7, the Restriction Assembly, Y-
LIMITED TO LABOR CHARGES, RE- Strainer, and associated pipe nipples
GARDLESS OF WHETHER TYCO Ordering and fittings must be ordered sepa-
FIRE PRODUCTS WAS INFORMED rately to complete the installation.
ABOUT THE POSSIBILITY OF SUCH Information
DAMAGES, AND IN NO EVENT
SHALL TYCO FIRE PRODUCTS LI- Orders for the RC-1 and additional
components, as applicable, must in-