Professional Documents
Culture Documents
INPUT
General Input
OUTPUT
Required thickness 16.68 mm
Check for deflection
Permissible Deflection 5.00 %
Percentage Deflection 7.86 %
NOT OK
Height of Cover H 10 m
Pipe lining
Lining thickness 50 mm
Governing thickness
Bedding constant K
Pipe Stiffness EI
Deflection x
Date :
Developed by :
Checked by :
Approved by :
36.26 ksi
50 % of min. yield
18.1297125 ksi
Refrences
75 % of min. yield
27.19456875 ksi Formulas
Soil Column Load
Cement mortar lining
Deflection
1.97 inch
Water buyoncy factor
0.623 inch Allowable Buckling Pressure
0.415 inch
0.623 inch
0.657 inch
0.657 inch
120.95 pcf
- lb/in
4288.74 lb/in
4288.74 lb/in
90.00 degree
0.100
2.00
76.5016666667 inch
1,015.26 psi
30,022,803.90 psi
4,003,040.52 psi
3258837.83 in-lb
12.39 inch
18-Oct-17
PRS
Results
Required thickness
0.657 inch
16.679 mm
lb/in3
psi
psi
Formulas Remarks
Iowa
Formul
a
Conversion Factors to be used
Units Notes
SN From To From-To Multiplication Factor 1.) As per the American Spiralwe
1 mm inch mm-inch 0.0394 Normal Live Loads at depth e
2 N/mm2 psi N/mm2-psi 145.0377
3m f m-f 3.280839895
4 N/mm2 ksi N/mm2-ksi 0.1450377
5 kN/m3 pcf kN/m3-pcf 6.3659
6 N/mm lb/in N/mm-lb/in 5.71
7 kN/m3 lb/in3 kN/m3-lb/in3 0.00368
As per the American Spiralweld Pipe Literature
Normal Live Loads at depth exceeding 8 f are insignificant