GENERAL NOTES
1. Definitions:

a) Specification refers to the General Specification for Electrical Works issued


by CPWD with amendments up to date.

b) Engineer-in-Charge shall mean the Executive Engineer (E/M) PWD of


respective division.

c) ISI, IS, BIS shall mean the relevant Indian Standards.

2. Only Copper conductor (ICPCI approved) multi-strand cable with PVC Insulated Fire
Retardant (FR) having minimum oxygen index value 29% is to be used. Where FRLS
PVC wires are proposed to be used in the wiring system in place of FR PVC wires by
the technical sanctioning authority, they may use the schedule of rates by suitably
modifying the description of item. No separate rate has been proposed, as the
variation in cost of the item is nominal.

3. The point wiring for light/fan/bell, socket outlet 6A, 16A includes switches, sockets,
ceiling rose, lamp holder conduit, copper multi strand FR wire with copper lugs (
required to be compulsorily used ), fixing and drawing of all items and green colour
PVC insulated Multi strand FR copper wire as earth wire. However, Switch Board with
sheet - modular or non-modular type is not included in the rates of point wiring and
shall be paid separately and switch boards should be selected so as to accommodate
at least similar one switch & socket in future.

4. Circuit wiring is to be done in 2.5 sq mm cable. The rates of the earth wire of green
colour of 2.5 sq mm copper Multi strand FR to be run inside the same conduit shall be
payable separately as per actual measurements. Similarly, green colour earth wire for
sub-main shall run inside the same conduit and shall be paid separately. Separate
conduit shall be used for point, circuit and sub-main wiring.

5. Modular accessories are to be used in residential buildings of "E type and above and
in case of non-residential buildings costing more than 50 Lac. All non-modular and
modular accessories are to be of polycarbonate material only.

6. The rates of wiring have been taken considering the FR wire only. If anywhere, the
FR-LSH wire is used, 3% rates may be paid additionally.3

7. Star rating ceiling fans confirming to IS: 374/1979 with amended up to date, ISI

SOR ELECTRICAL 2014

Page 3 of 114
marked and Star rated distribution Transformer, Arial Bunched cable of 1.1 KV, 11
KV, 33 KV, LED Luminaries, domestic & street lights, step light are added.

8. Only XLPE insulated LT/HT cables are to be used and rates have been provided
accordingly. Modular accessories, in addition to normal (non-modular), are also
introduced and rates have been given accordingly.

9. Chapter on overhead electrification is also enhanced covering as per Norms of


MPSEB.

10. The rates given in this SOR are based on the following classification:

CLASSIFICATION OF POINTS:

Point Light / Fan / Bell / 2 Way Points Power Wiring 16A


/ Socket 6A etc.

Short Up to 3m. Up to 3m.

Medium Above 3m up to 6m Above 3m up to 6m

Long Above 6m up to 10m Above 6m up to 10m

Extra Long-I Above 10m up to 15m

Extra Long-II Above 15m up to 20m

Extra Long-III Above 20m up to 25m

NOTE:

1) Special Points Actual material used above 10 m (Light Point etc)/ 25m
(Power Wiring) shall be paid as per actual measurements on linear basis.

2) Any special wiring not covered above shall be measured on the linear basis
and shall be paid as per SOR items.

11. In this S.O.R. on chapter No. 40 the rates of dismantling of wiring in F/G/H/I type qtrs
and rewiring of same have been taken as single item. The rate of item 40.1 does not
include service line, earthling system, Fans and light fixtures.

12. In this S.O.R. on chapter No. 40 the rates of new wiring in standard F/G/H/I type qtrs
have been taken as single item. The rate of item 40.2 include Fans and light fixtures. 4

13. The material is to be used as per List of approved electrical material annexed

SOR ELECTRICAL 2014

Page 4 of 114
CONTENTS
CHAPTER
DESCRIPTION PAGE No.
No.
1 WIRING IN SURFACE RIGID STEEL CONDUIT SYSTEM WITH 8
COPPER CONDUCTOR
2 WIRING IN CONCEALED RIGID STEEL CONDUIT SYSTEM 9
WITH COPPER CONDUCTOR
3 WIRING IN SURFACE RIGID P.V.C. CONDUIT SYSTEM WITH 10
COPPER CONDUCTOR
4 WIRING IN CONCEALED RIGID P.V.C. CONDUIT 11
(HMS)SYSTEM
5 WIRING IN SURFACE RIGID P.V.C. CASING-N-CAPING 12
SYSTEM WITH COPPER CONDUCTOR
6 POWER WIRING IN SURFACE RIGID STEEL CONDUIT 13
SYSTEM WITH COPPER CONDUCTOR
7 POWER WIRING IN CONCEALD RIGID STEEL CONDUIT 13
SYSTEM WITH COPPER CONDUCTOR
8 POWER WIRING IN SURFACE RIGID PVC CONDUIT SYSTEM 14
WITH COPPER CONDUCTOR.
9 POWER WIRING IN CONCEALED RIGID PVC CONDUIT 14
SYSTEM WITH COPPER CONDUCTOR
10 POWER WIRING IN SURFACE RIGID PVC CASING-N-CAPING 15
SYSTEM WITH COPPER CONDUCTOR
11 WIRING IN EXISTING CONCEALED RIGID CONDUIT SYSTEM 16
WITH COPPER CONDUCTOR
12 WIRING IN EXISTING SURFACE RIGID CONDUIT SYSTEM 17
WITH COPPER CONDUCTOR
13 SUPPLYING AND FIXING RIGID STEEL CONDUIT FOR 18
CONCEALED CONDUIT SYSTEM
14 SUPPLYING AND FIXING RIGID STEEL CONDUIT FOR 18
SURFACE CONDUIT SYSTEM
15 SUPPLYING AND FIXING PVC CONDUIT FOR SURFACE 19
CONDUIT SYSTEM
16 SUPPLYING AND FIXING PVC CONDUIT(HMS) FOR 19
CONCEALED CONDUIT SYSTEM
17 SUPPLYING AND FIXING PVC CASING - N - CAPPING ON 19
SURFACE SYSTEM
18 METALLIC SWITCH BOXES & MODULAR BOXES 20

19 WIRING IN EXISTING CONDUIT/ PVC CASING-N-CAPPING 21-22


WITH COPPER CONDUCTOR
20 MAINS AND SUB MAINS IN SURFACE STEEL CONDUIT WITH 23
COPPER CONDUCTOR
21 SUB-MAIN IN CONCEALED STEEL CONDUIT WITH COPPER 246
CONDUCTOR

SOR ELECTRICAL 2014

Page 6 of 114
22 SUB MAINS IN SURFACE PVC CONDUIT IN COPPER 25
CONDUCTOR
23 SUB-MAIN IN CONCEALED PVC CONDUIT IN COPPER 26
CONDUCTOR
24 REWIRING IN EXISTING RIGID STEEL / PVC NON- METALLIC 27-28
CONDUIT WITH COPPER CONDUCTOR
25 CONTROL SWITCH GEARS 29-33
26 BUSBAR CHAMBERS AND BUS TRUNKING 34-36
27 MCCBs, ISOLATORS ,MCBs ,RCBOs ,MCB DBs 37-42
28 FIXING OF SFU ,DBs ,BUSBAR ,MCCBs ,MCBs, ISOLATORs & 43-44
RCBOs
29 WIRING ACCESSORIES,PANELS,LAMPS, 45-49
30 FAN 50-51
31 LUMINAIRES 52-60
32 MISCELLANEOUS 61-63
33 LABOUR RATES FOR WIRING 64-65
34 PAINTING 66
35 DISMANTLING OF CIVIL & ELECTRICAL WORK 67-68
36 CIVIL WORK 68
37 EARTHING, LOOP EARTHING, LIGHTNING CONDUCTOR 69-73
38 TELEPHONE, LAN, TV CABLE 74-75
39 SINGLE / THREE PHASE SUBMERSIBLE / OPENWELL / 76-78
CENTRIFUGAL MOTOR PUMP SET.
40 WIRING OF OLD STANDARD F/G/H/I QTRS & NEW WIRING 79
OF NEW STANDARD F/G/H/I QTRS
41 UNDER GROUND CABLES 80-93
42 EXTERNAL ELECTRIFICATION AND OVERHEAD LINES 94-111
LIST OF APPROVED MATERIAL 112-113
ANNEXURE -1, GUIDE LINE FOR REWIRING 1147

SOR ELECTRICAL 2014

Page 7 of 114
CHAPTER 1
WIRING IN SURFACE RIGID STEEL CONDUIT SYSTEM WITH COPPER
CONDUCTOR
S.No. Description of Item Unit Rate (Rs)
1 Point wiring (excluding metallic switch box & sheet but Using Using
including switches, sockets, lamp holders/ceiling roses Flush Type Modular
etc) with 1.5 Sq. mm. PVC insulated cable FR with Normal Accessorie
copper multi strand conductor ISI marked in surface rigid Accessori s
steel conduit ISI Marked of suitable size and 1.5 Sq. mm. es
PVC insulated copper earth continuity conductor of green
colour inside conduit including painting, etc. as required
as per specification for :-
1.1 Light Point/Fan Points.
a) Short point Each 445 533
b) Medium point Each 959 1047
c) Long point Each 1546 1634
1.2 3 Pin 6 Amp socket outlet on Separate Board
a) Short point Each 453 647
b) Medium point Each 996 1189
c) Long point Each 1626 1820
1.3 Call Bell / Buzzer Points
a) Short point Each 417 526
b) Medium point Each 888 997
c) Long point Each 1424 1533
1.4 Twin Control light points
a) Short point Each 480 606
b) Medium point Each 1032 1158
c) Long point Each 1680 1807
1.5 Point wiring (excluding metallic switch box & sheet but Each
including switches, sockets ) for 3/5 pin 6 Amp. Socket
outlet point with 1.5 Sq. mm. PVC insulated cable FR
with copper multi strand conductor ISI marked in surface
rigid steel conduit ISI marked of suitable size and 1.5 Sq.
mm. PVC insulated copper earth continuity conductor of
green colour inside conduit with required materials as per
specification on same board 91 285
1.6 Wiring for circuit wiring with PVC insulated cable FR with
copper multi strand conductor ISI marked in surface rigid
steel conduit of ISI marked suitable size including painting
etc. as required as per specification
a) 2x2.5 Sq.mm. meter 182 182
b) 4x2.5 Sq.mm. meter 253 253
c) 6x2.5 Sq.mm. meter 304 304
d) 8x2.5 Sq.mm. meter 356 356
8

SOR ELECTRICAL 2014/CHAPTER-1

Page 8 of 114
CHAPTER 2
WIRING IN CONCEALED RIGID STEEL CONDUIT SYSTEM WITH COPPER
CONDUCTOR
S.No Description of Item Unit Rate (Rs)
2 Point wiring (excluding metallic switch box & sheet but Using Using
including switches, sockets, lamp holders/ceiling roses Flush Type Modular
etc) with 1.5 Sq. mm. PVC insulated cable FR with Normal Accessorie
copper multi strand conductor ISI marked in Concealed Accessori s
rigid steel conduit ISI Marked of suitable size and 1.5 Sq. es
mm. PVC insulated copper earth continuity conductor of
green colour inside conduit including painting, etc. as
required as per specification for :-

2.1 Light Point/Fan Points.


a) Short point Each 481 569
b) Medium point Each 1028 1116
c) Long point Each 1685 1772
2.2 3 Pin 6 Amp socket outlet on Separate Board
a) Short point Each 488 683
b) Medium point Each 1049 1258
c) Long point Each 1764 1959
2.3 Call Bell / Buzzer Points
a) Short point Each 439 556
b) Medium point Each 936 1054
c) Long point Each 1536 1654
2.4 Twin Control light points
a) Short point Each 498 616
b) Medium point Each 1060 1183
c) Long point Each 1732 1860
2.5 Point wiring (excluding metallic switch box & sheet but
including switches, sockets ) for 3 pin 6 Amp. Socket
outlet point with 1.5 Sq. mm. PVC insulated cable FR
with copper multi strand conductor ISI marked in
Concealed rigid steel conduit ISI marked of suitable size
and 1.5 Sq. mm. PVC insulated copper earth continuity
conductor of green colour inside conduit with required
materials as per specification on same board Each 91 285
2.6 Wiring for circuit wiring with PVC insulated cable FR with
copper multi strand conductor ISI marked in Concealed
rigid steel conduit of ISI marked suitable size including
painting etc. as required as per specification
a) 2x2.5 Sq.mm. metre 200 200
b) 4x2.5 Sq.mm. metre 270 270
c) 6x2.5 Sq.mm. metre 321 321
9
d) 8x2.5 Sq.mm. metre 373 373

SOR ELECTRICAL 2014/CHAPTER-2

Page 9 of 114
CHAPTER 3
WIRING IN SURFACE RIGID P.V.C. CONDUIT SYSTEM WITH COPPER
CONDUCTOR
S.No Description of Item Unit Rate (Rs)
3 Point wiring (excluding metallic switch box & sheet but Using Using
including switches, sockets, lamp holders/ceiling roses Flush Type Modular
etc) with 1.5 Sq. mm. PVC insulated cable FR with Normal Accessorie
copper multi strand conductor ISI marked in Surface rigid Accessori s
P.V.C. conduit (MMS) ISI Marked of suitable size and 1.5 es
Sq. mm. PVC insulated copper earth continuity conductor
of green colour inside conduit etc. as required as per
specification for :-

3.1 Light Point/Fan Points.


a) Short point Each 240 335
b) Medium point Each 432 548
c) Long point Each 736 842
3.2 3 Pin 6 Amp socket outlet on Separate Board
a) Short point Each 253 454
b) Medium point Each 498 723
c) Long point Each 824 1044
3.3 Call Bell / Buzzer Points
a) Short point Each 213 283
b) Medium point Each 399 474
c) Long point Each 615 696
3.4 Twin Control light points
a) Short point Each 258 381
b) Medium point Each 503 649
c) Long point Each 816 956
3.5 Point wiring (excluding metallic switch box & sheet but
including switches, sockets) for 3 pin 6 Amp. Socket outlet
point with 1.5 Sq. mm. PVC insulated cable FR with
copper multi strand conductor ISI marked in Surface rigid
P.V.C. conduit (MMS) ISI marked of suitable size and 1.5
Sq. mm. PVC insulated copper earth continuity conductor
of green colour inside conduit with required materials as
per specification on same board .
Each 91 285
3.6 Wiring for circuit wiring with PVC insulated cable FR with
copper multi strand conductor ISI marked in Surface rigid
P.V.C. conduit (MMS) of ISI marked suitable size etc. as
required as per specification
a) 2x2.5 Sq.mm. Metre 93 93
b) 4x2.5 Sq.mm. Metre 153 153
c) 6x2.5 Sq.mm. Metre 204 204
10
d) 8x2.5 Sq.mm. Metre 255 255

SOR ELECTRICAL 2014/CHAPTER-3

Page 10 of 114
CHAPTER 4
WIRING IN CONCEALED RIGID PVC CONDUIT(HMS) SYSTEM WITH COPPER
CONDUCTOR
S.No. Description of Item Unit Rate (Rs)
4 Point wiring (excluding metallic switch box & sheet but Using Using
including switches,sockes,lamp,holders,ceiling roses etc) Flush Type Modular
with 1.5 Sq. mm. PVC insulated cable FR with copper Normal Accessorie
multi strand conductor ISI marked in concealed rigid Accessori s
P.V.C. conduit (HMS) ISI Marked of suitable size and 1.5 es
Sq. mm. PVC insulated copper earth continuity conductor
of green colour inside conduit etc. as required as per
specification for :-

4.1 Light Point/Fan Points.


a) Short point Each 294 394
b) Medium point Each 564 671
c) Long point Each 942 1083
4.2 3 Pin 6 Amp socket outlet on Separate Board
a) Short point Each 302 503
b) Medium point Each 601 780
c) Long point Each 1022 1192
4.3 Call Bell / Buzzer Points
a) Short point Each 268 388
b) Medium point Each 509 637
c) Long point Each 821 983
4.4 Twin Control light points
a) Short point Each 335 486
b) Medium point Each 638 812
c) Long point Each 1048 1285
4.5 Point wiring (excluding metallic switch box & sheet but
including switches, sockets) for 3 pin 6 Amp. Socket outlet
point with 1.5 Sq. mm. PVC insulated cable FR with
copper multi strand conductor ISI marked in concealed
rigid P.V.C. conduit (HMS) ISI marked of suitable size
and 1.5 Sq. mm. PVC insulated copper earth continuity
conductor of green colour inside conduit with required
materials as per specification on same board . Each 91 285
4.6 Wiring for circuit wiring with PVC insulated cable FR with
copper multi strand conductor ISI marked in concealed
rigid P.V.C. conduit (HMS) of ISI marked suitable size
etc. as required as per specification
a) 2x2.5 Sq.mm. Metre 117 117
b) 4x2.5 Sq.mm. Metre 176 176
c) 6x2.5 Sq.mm. Metre 225 225
11
d) 8x2.5 Sq.mm. Metre 277 277

SOR ELECTRICAL 2014/CHAPTER-4

Page 11 of 114
CHAPTER 5
WIRING IN SURFACE RIGID PVC CASING AND CAPPING SYSTEM WITH COPPER
CONDUCTOR
S.No. Description of Item Unit Rate (Rs)
5 Point wiring (excluding metallic switch box & sheet but Using Using
including switches, sockets, lamp holders/ceiling roses Flush Type Modular
etc) with 1.5 Sq. mm. PVC insulated cable FR with Normal Accessorie
copper multi strand conductor ISI marked in Surface rigid Accessori s
P.V.C. CASING AND CAPPING ISI Marked of suitable es
size and 1.5 Sq. mm. PVC insulated copper earth
continuity conductor of green colour inside casing &
capping etc. as required as per specification for :-

5.1 Light Point/Fan Points.


a) Short point Each 228 339
b) Medium point Each 447 584
c) Long point Each 699 866
5.2 3 Pin 6 Amp socket outlet on Separate Board
a) Short point Each 236 453
b) Medium point Each 483 727
c) Long point Each 779 1053
5.3 Call Bell / Buzzer Points
a) Short point Each 235 332
b) Medium point Each 453 534
c) Long point Each 706 767
5.4 Twin Control light points
a) Short point Each 269 399
b) Medium point Each 521 677
c) Long point Each 808 994
5.5 Point wiring (excluding metallic switch box & sheet but
including switches, sockets ) for 3 pin 6 Amp. Socket
outlet point with 1.5 Sq. mm. PVC insulated cable FR
with copper multi strand conductor ISI marked in Surface
rigid P.V.C. CASING AND CAPPING ISI marked of
suitable size and 1.5 Sq. mm. PVC insulated copper earth
continuity conductor of green colour inside casing &
capping with required materials as per specification on
same board
Each 91 285
5.6 Wiring for circuit wiring with PVC insulated cable FR with
copper multi strand conductor ISI marked in Surface rigid
P.V.C. CASING AND CAPPING of ISI marked suitable
size etc. as required as per specification

a) 2x2.5 Sq.mm. Metre 102 102


b) 4x2.5 Sq.mm. Metre 153 153
c) 6x2.5 Sq.mm. Metre 204 204
12
d) 8x2.5 Sq.mm. Metre 254 254

SOR ELECTRICAL 2014/CHAPTER-5

Page 12 of 114
CHAPTER 6
POWER WIRING IN SURFACE RIGID STEEL CONDUIT SYSTEM WITH COPPER
CONDUCTOR
S.No Description of Item Unit Rate (Rs)
6.1 Using Using
Point wiring (excluding metallic switch box & sheet ) for 3 Flush Type Modular
Pin 16 Amp. Socket Outlet Point With 4 Sq. mm. PVC Normal Accessorie
insulated cable FR with copper multi strand conductor ISI Accessorie s
marked in Surface rigid Steel Conduit ISI Marked of s
suitable size including painting etc. with 16 Amp. Switch &
Socket / S.S.Combined 6/16 Amp. of ISI Marked and 4 Sq.
mm. PVC insulated copper earth continuity conductor of
green colour inside conduit as per specification for :-
On Separate Board
A. Short Point Each 659 914
B. Medium Point Each 1360 1615
C. Long Point Each 2173 2428
D. Extra Long I Each 3170 3425
E. Extra Long II Each 4287 4542
F. Extra Long III Each 5660 5915
6.2 Same board switch socket 6/16 Amp Each 213 468

CHAPTER 7
POWER WIRING IN CONCEALED RIGID STEELCONDUIT SYSTEM WITH COPPER
CONDUCTOR
S.No Description of Item Unit Rate (Rs)
7.1 Point wiring (excluding metallic switch box & sheet ) for 3 Using Using
Pin 16 Amp. Socket Outlet Point with 4 Sq. mm. PVC Flush Type Modular
insulated cable FR with copper multi strand conductor ISI Normal Accessorie
marked in Concealed rigid Steel Conduit ISI Marked of Accessori s
suitable size including painting etc. with 16 Amp. Switch & es
Socket / S.S.Combined 6/16 Amp. of ISI Marked and 4 Sq.
mm. PVC insulated copper earth continuity conductor of
green colour inside conduit as per specification for :-
On Separate Board
A. Short Point Each 691 950
B. Medium Point Each 1384 1645
C. Long Point Each 2194 2459
D. Extra Long I Each 3216 3486
E. Extra Long II Each 4349 4623
F. Extra Long III Each 5666 5944
7.2 Same board switch socket 6/16 Amp Each 213 468
13

SOR ELECTRICAL 2014/CHAPTER-6-7

Page 13 of 114
CHAPTER 8
POWER WIRING IN SURFACE RIGID P.V.C.CONDUIT (MMS) SYSTEM WITH
COPPER CONDUCTOR
S.No Description of Item Unit Rate (Rs)
8.1 Point wiring (excluding metallic switch box & sheet ) for 3 Using Flush Using
Pin 16 Amp. Socket Outlet Point With 4 Sq. mm. PVC Type Modular
insulated cable FR with copper multi strand conductor ISI Normal Accessories
marked in Surface rigid P.V.C, Conduit (MMS) ISI Marked Accessorie
of suitable size etc. with 16 Amp. F.T. Switch & Socket / s
S.S.Combined 6/16 Amp. of ISI Marked and 4 Sq. mm.
PVC insulated copper earth continuity conductor of green
colour inside conduit as per specification for :-
On Separate Board
A. Short Point Each 477 732
B. Medium Point Each 919 1174
C. Long Point Each 1442 1697
D. Extra Long I Each 2111 2366
E. Extra Long II Each 2846 3101
E. Extra Long III Each 3586 3841
8.2 Same board switch socket 6/16 Amp Each 213 468

CHAPTER 9
POWER WIRING IN CONCEALED RIGID PVC CONDUIT (HMS) SYSTEM WITH
COPPER CONDUCTOR
S.N. Description of Item Unit Rate (Rs)
9.1 Point wiring (excluding metallic switch box & sheet ) for 3 Using Using
Pin 16 Amp. Socket Outlet Point With 4 Sq. mm. PVC Flush Type Modular
insulated cable FR with copper multi strand conductor ISI Normal Accessorie
marked in Concealed rigid P.V.C Conduit (HMS) ISI Accessori s
Marked of suitable size etc. with 16 Amp. F.T. Switch & es
Socket / S.S.Combined 6/16 Amp. of ISI Marked and 4 Sq.
mm. PVC insulated copper earth continuity conductor of
green colour inside conduit as per specification for
On Separate Board
A. Short Point Each 574 816
B. Medium Point Each 1113 1335
C. Long Point Each 1730 1930
D. Extra Long I Each 2474 2643
E. Extra Long II Each 3280 3417
F. Extra Long III Each 4089 4193
9.2 Same board switch socket 6/16 Amp Each 213 468
14

SOR ELECTRICAL 2014/CHAPTER-8-9

Page 14 of 114
CHAPTER 10

POWER WIRING IN SURFACE RIGID PVC CASING AND CAPPING SYSTEM WITH
COPPER CONDUCTOR
S.N. Description of Item Unit Rate (Rs)
10.1 Point wiring (excluding metallic switch box & sheet) Using Flush Using
for 3 Pin 16 Amp. Socket Outlet Point With 4 Sq. Type Modular
Normal Accessories
mm. PVC insulated cable FR with copper multi Accessories
strand conductor ISI marked in Surface rigid
P.V.C.CASING AND CAPPING ISI Marked of
suitable size etc. with 16 Amp. F.T. Switch & Socket
/ S.S Combined 6/16 Amp. of ISI Marked and 4 Sq.
mm. PVC insulated copper earth continuity
conductor of green colour inside capping as per
specification for :-
On Separate Board
A. Short Point Each 493 747
B. Medium Point Each 963 1215
C. Long Point Each 1518 1768
D. Extra Long I Each 2231 2479
E. Extra Long II Each 3014 3259
F. Extra Long III Each 3797 4039
10.2 Same board switch socket 6/16 Amp Each 213 46815

SOR ELECTRICAL 2014/CHAPTER-10

Page 15 of 114
CHAPTER 11
WIRING IN EXISTING CONCEALED RIGID CONDUIT SYSTEM WITH COPPER
CONDUCTOR
S.N. Description of Item Unit Rate (Rs)
11 Point wiring (excluding metallic switch box & sheet Using Flush Using
but including switches, sockets, lamp holders/ceiling Type Modular
Normal Accessories
roses etc) with 1.5 Sq. mm. PVC insulated cable FR Accessories
with copper multi strand conductor ISI marked in
existing Concealed rigid conduit ISI Marked of
suitable size with PVC insulated copper earth
continuity conductor of green colour as per
specification including earthling of regulator etc as
required for :-
11.1 Light Point / Fan Points.
a) Short point Each 184 269
b) Medium point Each 350 435
c) Long point Each 542 627
11.2 3 Pin 6 Amp socket outlet on Separate Board
a) Short point Each 188 374
b) Medium point Each 354 540
c) Long point Each 545 731
11.3 Call Bell / Buzzer Points
a) Short point Each 157 242
b) Medium point Each 279 364
c) Long point Each 420 505
11.4 Twin Control light points
a) Short point Each 224 347
b) Medium point Each 395 518
c) Long point Each 589 71216

SOR ELECTRICAL 2014/CHAPTER-11

Page 16 of 114
CHAPTER 12
WIRING IN EXISTING SURFACE RIGID CONDUIT SYSTEM WITH COPPER
CONDUCTOR
S.No Description of Item Unit Rate (Rs)
12 Point wiring (excluding metallic switch box & sheet Using Flush Using
but including switches, sockets,lamp holders/ceiling Type Modular
Normal Accessories
roses etc) with 1.5 Sq. mm. PVC insulated cable with Accessories
Copper Stranded Conductor ISI marked in existing
surface rigid conduit ISI Marked of suitable size with
PVC insulated copper earth continuity conductor of
green colour as per specification including earthing of
regulator etc as required for :-
12.1 Light Point / Fan Points.
a) Short point Each 178 263
b) Medium point Each 344 429
c) Long point Each 535 620
12.2 3 Pin 6 Amp socket outlet on Separate Board
a) Short point Each 181 367
b) Medium point Each 347 533
c) Long point Each 539 725
12.3 Call Bell / Buzzer Points
a) Short point Each 150 235
b) Medium point Each 272 357
c) Long point Each 413 498
12.4 Twin Control light points
a) Short point Each 217 340
b) Medium point Each 388 511
c) Long point Each 582 70517

SOR ELECTRICAL 2014/CHAPTER-12

Page 17 of 114
CHAPTER 13

SUPPLYING AND FIXING RIGID STEEL CONDUIT FOR CONCEALED CONDUIT


SYSTEM

S.No Description of Item Unit Rate(Rs)


13
Supplying and fixing rigid steel conduit ISI marked along with
the accessories in concealed system including cutting the wall
and plastering & repainting the wall with matching colour to
bring in its original condition as required
13.1 H.G. Conduit 20 mm, wall thickness-1.6mm Metre 116
13.2 H.G. Conduit 25 mm, wall thickness-1.6mm Metre 137
13.3 H.G. Conduit 32 mm, wall thickness-1.6mm Metre 198
13.4 H.G. Conduit 40 mm, wall thickness-2.0mm Metre 307
13.5 H.G. Conduit 50 mm, wall thickness-2.0mm Metre 424

CHAPTER 14
SUPPLYING AND FIXING RIGID STEEL CONDUIT FOR SURFACE CONDUIT
SYSTEM
S.No Description of Item Unit Rate(Rs)
14 Supplying and fixing rigid steel conduit ISI marked along with
the accessories on surface including painting etc. as required
14.1 H.G. Conduit 20 mm, wall thickness-1.6mm Metre 99
14.2 H.G. Conduit 25 mm, wall thickness-1.6mm Metre 124
14.3 H.G. Conduit 32 mm, wall thickness-1.6mm Metre 180
14.4 H.G. Conduit 40 mm, wall thickness-2.0mm Metre 283
14.5 H.G. Conduit 50 mm, wall thickness-2.0mm Metre 39318

SOR ELECTRICAL 2014/CHAPTER-13-14

Page 18 of 114
CHAPTER 15
SUPPLYING AND FIXING PVC. CONDUIT FOR SURFACE CONDUIT SYSTEM
S.No Description of Item Unit Rate(Rs)
15 Supplying and fixing PVC conduit ISI marked along with the
accessories on surface etc. as required
15.1 PVC . Conduit 20 mm (MMS) Metre 39
15.2 PVC . Conduit 25 mm (MMS) Metre 51
15.3 PVC . Conduit 32 mm (MMS) Metre 72
15.4 PVC . Conduit 40 mm (MMS) Metre 103
15.5 PVC . Conduit 50 mm (MMS) Metre 151

CHAPTER 16
SUPPLYING AND FIXING PVC CONDUIT(HMS) FOR CONCEALED CONDUIT
SYSTEM
S.No Description of Item Unit Rate(Rs)
16 Supplying and fixing PVC conduit ISI marked along with the
accessories in concealed system etc. as required
16.1 PVC . Conduit 20 mm (HMS) Metre 61
16.2 PVC . Conduit 25 mm (HMS) Metre 72
16.3 PVC . Conduit 32 mm (HMS) Metre 108
16.4 PVC . Conduit 40 mm (HMS) Metre 137
16.5 PVC . Conduit 50 mm (HMS) Metre 196

CHAPTER - 17

SUPPLYING AND FIXING PVC CASING - N - CAPPING ON SURFACE SYSTEM

Rate( in
S.No Description of Item Unit
Rs)
17 Supplying and fixing PVC Casing-N-Capping (Double Fold)
ISI Marked along with accessories on surface etc. as
required
17.1 PVC Casing-N-Capping (Double Fold) 20 mm x 12mm Per Mtr 40
17.2 PVC Casing-N-Capping (Double Fold) 25 mm x 12mm Per Mtr 48
17.3 PVC Casing-N-Capping (Double Fold) 32 mm x 12mm Per Mtr 49
17.4 PVC Casing-N-Capping (Double Fold) 38 mm x 20mm Per Mtr 6619

SOR ELECTRICAL 2014/CHAPTER-15-17

Page 19 of 114
CHAPTER 18

METALLIC SWITCH BOXES & MODULAR BOXES

S.No Description of Item Unit Rate(Rs)


18.1 Supplying and fixing factory fabricated hot dip galvanized switch
box for normal flush type accessories of minimum 1.2 mm (18
SWG gauge) thickness with earth terminal stud with nut and
washer, with 3 mm thick synthetic phenollic resin bonded laminated
sheet conforming to grade P-I of IS:2036-1974 on surface /
concealed including painting etc. as required as per specification:
FOR SURFACE/CONCEALED
18.1.1 MS Box 100 mm X 100 mm X60mm deep Each 98
18.1.2 MS Box 200 mm X 150 mm X 60 mm Deep Each 181
18.1.3 MS Box 180 mm X 100 mm X 60 mm Deep Each 133
18.1.4 MS Box 125 mm X 300 mm X 60 mm Deep Each 237
18.1.5 MS Box 200 mm X 250 mm X 60 mm Deep Each 271
18.1.6 MS Box 250 mm X 300 mm X 60 mm Deep 1.6mm(16swg) Each 427
18.1.7 MS Box 300mm X 380 mm X 60 mm Deep 1.6mm(16swg) Each 594
18.2 Supplying and fixing of approved make modular type metal box
with modular frame/ base plate and cover plate including fixing in
concealed / surface excluding switch,socket etc. as required for:-
18.2.1 1 Or 2 Module Each 156
18.2.2 3 Module Each 208
18.2.3 4 Module Each 236
18.2.4 6 Module Each 326
18.2.5 8 / 9 Module Each 400
18.2.6 12 Module Each 487
18.2.7 16 Module Each 532
18.2.8 18 Module Each 560
18.3 Supplying and fixing of approved make modular type P.V.C. box
with modular base and cover plate including fixing on surface
excluding switch,socket etc. as required for:-
18.3.1 1 OR 2 Module Each 151
18.3.2 3 Module Each 184
18.3.3 4 Module Each 218
18.3.4 6 Module Each 280
18.3.5 8 / 9 Module Each 356
18.3.6 12 Module Each 453
18.3.7 16 Module Each 492
20

SOR ELECTRICAL 2014/CHAPTER-18

Page 20 of 114
CHAPTER -19
WIRING IN EXISTING CONDUIT / PVC CASING CAPPING WITH COPPER
CONDUCTOR
S.No Description of Item Unit Rate(Rs)
19 Supplying and drawing single core PVC insulated cable FR with
copper multi strand conductor ISI marked in existing rigid PVC
Casing-N-Capping / conduit in surface or concealed as per
specification.

19.1 1 X 1.5 sq mm
19.1.1 (a) 1 X 1.5 sq mm Per Mtr 21
19.1.2 (b) 2 X 1.5 sq mm Per Mtr 36
19.1.3 (c) 3 X 1.5 sq mm Per Mtr 51
19.1.4 (d) 4 X 1.5 sq mm Per Mtr 67
19.1.5 (e) 5 X 1.5 sq mm Per Mtr 82
19.1.6 (f) 6 X 1.5 sq mm Per Mtr 97
19.1.7 (g) 7 X 1.5 sq mm Per Mtr 113
19.1.8 (h) 8 X 1.5 sq mm Per Mtr 128
19.1.9 (i) 9 X 1.5 sq mm Per Mtr 143
19.1.10 (j) 10 X 1.5 sq mm Per Mtr 159
19.2 1 X 2.5 sq mm
19.2.1 (a) 1 X 2.5 sq mm Per Mtr 30
19.2.2 (b) 2 X 2.5 sq mm Per Mtr 54
19.2.3 (c) 3 X 2.5 sq mm Per Mtr 78
19.2.4 (d) 4 X 2.5 sq mm Per Mtr 103
19.2.5 (e) 5 X 2.5 sq mm Per Mtr 127
19.2.6 (f) 6 X 2.5 sq mm Per Mtr 151
19.2.7 (g) 7 X 2.5 sq mm Per Mtr 176
19.2.8 (h) 8 X 2.5 sq mm Per Mtr 200
19.2.9 (i) 9 X 2.5 sq mm Per Mtr 224
19.2.10 (j) 10 X 2.5 sq mm Per Mtr 225
19.3 1 X 4.00 sq mm
19.3.1 (a) 1 X 4.00 sq mm Per Mtr 41
19.3.2 (b) 2 X 4.00 sq mm Per Mtr 76
19.3.3 (c) 3 X 4.00 sq mm Per Mtr 111
19.3.4 (d) 4 X 4.00 sq mm Per Mtr 147
19.3.5 (e) 5 X 4.00 sq mm Per Mtr 182
21

SOR ELECTRICAL 2014/CHAPTER-19

Page 21 of 114
19.3.6 (f) 6 X 4.00 sq mm Per Mtr 196
19.3.7 (g) 7 X 4.00 sq mm Per Mtr 252
19.3.8 (h) 8 X 4.00 sq mm Per Mtr 288
19.3.9 (i) 9 X 4.00 sq mm Per Mtr 323
19.3.10 (j) 10 X 4.00 sq mm Per Mtr 358
19.4 1 X 6.00 sq mm
19.4.1 (a) 1 X 6.00 sq mm Per Mtr 58
19.4.2 (b) 2 X 6.00 sq mm Per Mtr 111
19.4.3 (c) 3 X 6.00 sq mm Per Mtr 163
19.4.4 (d) 4 X 6.00 sq mm Per Mtr 216
19.4.5 (e) 5 X 6.00 sq mm Per Mtr 269
19.4.6 (f) 6 X 6.00 sq mm Per Mtr 322
19.4.7 (g) 7 X 6.00 sq mm Per Mtr 374
19.4.8 (h) 8 X 6.00 sq mm Per Mtr 427
19.4.9 (i) 9 X 6.00 sq mm Per Mtr 480
19.4.10 (j) 10 X 6.00 sq mm Per Mtr 532
19.5 10.00 Sq mm cable
19.5.1 1 X 10.00 sq mm Per Mtr 88
19.5.2 2 X 10.00 sq mm Per Mtr 170
19.5.3 3 X 10.00 sq mm Per Mtr 252
19.5.4 4 X 10.00 sq mm Per Mtr 334
19.5.5 5 X 10.00 sq mm Per Mtr 416
19.5.6 6 X 10.00 sq mm Per Mtr 498
19.6 16.00 Sq mm cable
19.6.1 1 X 16.00 sq mm Per Mtr 136
19.6.2 2 X 16.00 sq mm Per Mtr 268
19.6.3 3 X 16.00 sq mm Per Mtr 399
19.6.4 4 X 16.00 sq mm Per Mtr 530
19.7 25.00 Sq mm cable
19.7.1 1 X 25.00 sq mm Per Mtr 207
19.7.2 2 X 25.00 sq mm Per Mtr 408
19.7.3 3 X 25.00 sq mm Per Mtr 610
19.7.4 4 X 25.00 sq mm Per Mtr 811
19.8 35.00 Sq mm cable
19.8.1 1 X 35.00 sq mm Per Mtr 288
19.8.2 2 X 35.00 sq mm Per Mtr 571
19.8.3 3 X 35.00 sq mm Per Mtr 854
22
19.8.4 4 X 35.00 sq mm Per Mtr 1136

SOR ELECTRICAL 2014/CHAPTER-19

Page 22 of 114
CHAPTER - 20

SUB MAINS IN SURFACE STEEL CONDUIT IN COPPER CONDUCTOR

S.No Description of Item Unit Rate(Rs)


20 Wiring for sub-mains with PVC insulated cable FR with
copper multi strand conductor ISI marked in surface rigid
steel ISI marked conduit of suitable size(conduit included)
including accessories long neck threaded type, connection
painting etc ,as required as per specification
20.1 2 WIRE SUB MAIN
20.1.1 a) 2.5 sq mm cable in 20 mm conduit Metre 177
20.1.2 b) 4.0 sq mm cable in 20 mm conduit Metre 193
20.1.3 c) 6.0 sq mm cable in 20 mm conduit Metre 236
20.1.4 d) 10.0 sq mm cable in 25 mm conduit Metre 314
20.1.5 e) 16.0 sq mm cable in 25 mm conduit Metre 412
20.1.6 f) 25.0 sq mm cable in 32 mm conduit Metre 589
20.1.7 g) 35.0 sq mm cable in 32 mm conduit Metre 744
20.2 3 WIRE SUB MAIN
20.2.1 a) 2.5 sq mm cable in 20 mm conduit Metre 195
20.2.2 b) 4.0 sq mm cable in 20 mm conduit Metre 235
20.2.3 c) 6.0 sq mm cable in 20 mm conduit Metre 271
20.2.4 d) 10.0 sq mm cable in 25 mm conduit Metre 396
20.2.5 e) 16.0 sq mm cable in 25 mm conduit Metre 543
20.2.6 f) 25.0 sq mm cable in 32 mm conduit Metre 790
20.2.7 g) 35.0 sq mm cable in 32 mm conduit Metre 1031
20.3 3 1/2 WIRE SUB MAIN
20.3.1 a) 3 x 2.5 + 1 x 1.5 sq mm cable in 20 mm conduit Metre 209
20.3.2 b) 3 x 4.0 + 1 x 2.5 sq mm cable in 25 mm conduit Metre 267
20.3.3 c) 3 x 6.0 + 1 x 4.0 sq mm cable in 25 mm conduit Metre 324
20.3.4 d) 3 x 10.0 + 1 x 6.0 sq mm cable in 25 mm conduit Metre 453
20.3.5 e) 3 x 16.0 + 1 x 10.0 sq mm cable in 32 mm conduit Metre 661
20.3.6 f) 3 x 25.0 + 1 x 16.0 sq mm cable in 40 mm conduit Metre 1004
20.3.7 g) 3 x 35.0 + 1 x 16.0 sq mm cable in 40 mm conduit Metre 1239
20.4 4 WIRE SUB MAIN
20.4.1 a) 2.5 sq mm cable in 20 mm conduit Metre 217
20.4.2 b) 4.0 sq mm cable in 25 mm conduit Metre 277
20.4.3 c) 6.0 sq mm cable in 25 mm conduit Metre 339
20.4.4 d) 10.0 sq mm cable in 25 mm conduit Metre 514
20.4.5 e) 16.0 sq mm cable in 32 mm conduit Metre 711
20.4.6 f) 25.0 sq mm cable in 40 mm conduit Metre 1075
20.4.7 g) 35.0 sq mm cable in 40 mm conduit Metre 138623

SOR ELECTRICAL 2014/CHAPTER-20

Page 23 of 114
CHAPTER - 21

SUB-MAIN IN CONCEALED STEEL CONDUIT IN COPPER CONDUCTOR

S.No Description of Item Unit Rate(Rs)


21 Wiring for sub-mains with PVC insulated cable FR with
copper multi strand conductor ISI marked in recessed /
concealed rigid steel ISI marked conduit of suitable
size(Conduit included) including accessories long neck
threaded type, connection painting etc ,as required as per
specification
21.1 2 WIRE SUB MAIN
21.1.1 2.5 sq mm cable in 20 mm conduit Metre 189
21.1.2 4.0 sq mm cable in 20 mm conduit Metre 209
21.1.3 6.0 sq mm cable in 25 mm conduit Metre 258
21.1.4 10.0 sq mm cable in 25 mm conduit Metre 331
21.1.5 16.0 sq mm cable in 25 mm conduit Metre 425
21.1.6 25.0 sq mm cable in 32 mm conduit Metre 607
21.1.7 35.0 sq mm cable in 40 mm conduit Metre 857
21.2 3 WIRE SUB MAIN Metre
21.2.1 2.5 sq mm cable in 20 mm conduit Metre 211
21.2.2 4.0 sq mm cable in 25 mm conduit Metre 259
21.2.3 6.0 sq mm cable in 25 mm conduit Metre 306
21.2.4 10.0 sq mm cable in 25 mm conduit Metre 410
21.2.5 16.0 sq mm cable in 32 mm conduit Metre 597
21.2.6 25.0 sq mm cable in 40 mm conduit Metre 897
21.2.7 35.0 sq mm cable in 50 mm conduit Metre 1200
21.3 3 1/2 WIRE SUB MAIN Metre
21.3.1 3 x 2.5 + 1 x 1.5 sq mm cable in 20 mm conduit Metre 225
21.3.2 3 x 4.0 + 1 x 2.5 sq mm cable in 25 mm conduit Metre 281
21.3.3 3 x 6.0 + 1 x 4.0 sq mm cable in 25 mm conduit Metre 338
21.3.4 3 x 10.0 + 1 x 6.0 sq mm cable in 25 mm conduit Metre 457
21.3.5 3 x 16.0 + 1 x 10.0 sq mm cable in 32 mm conduit Metre 679
21.3.6 3 x 25.0 + 1 x 16.0 sq mm cable in 40 mm conduit Metre 1041
21.3.7 3 x 35.0 + 1 x 16.0 sq mm cable in 50 mm conduit Metre 1336
21.4 4 WIRE SUB MAIN Metre
21.4.1 2.5 sq mm cable in 20 mm conduit Metre 235
21.4.2 4.0 sq mm cable in 25 mm conduit Metre 291
21.4.3 6.0 sq mm cable in 25 mm conduit Metre 353
21.4.4 10.0 sq mm cable in 25 mm conduit Metre 492
21.4.5 16.0 sq mm cable in 32 mm conduit Metre 728
21.4.6 25.0 sq mm cable in 40 mm conduit Metre 1098
21.4.7 35.0 sq mm cable in 50 mm conduit Metre 148324

SOR ELECTRICAL 2014/CHAPTER-21

Page 24 of 114
CHAPTER - 22

SUB MAINS IN SURFACE PVC CONDUIT IN COPPER CONDUCTOR

S.No Description of Item Unit Rate(Rs)


22 Wiring for sub-mains with PVC insulated cable FR with
copper multi strand conductor ISI marked in surface rigid
PVC conduit (MMS) ISI marked of suitable size(Conduit
included) including 2mm thick accessories, connection etc
,as required as per specification
22.1 2 WIRE SUB-MAIN
22.1.1 2.5 sq mm cable in 20 mm conduit Metre 93
22.1.2 4.0 sq mm cable in 25 mm conduit Metre 127
22.1.3 6.0 sq mm cable in 25 mm conduit Metre 143
22.1.4 10.0 sq mm cable in 25 mm conduit Metre 200
22.1.5 16.0 sq mm cable in 32 mm conduit Metre 336
22.1.6 25.0 sq mm cable in 32 mm conduit Metre 477
22.1.7 35.0 sq mm cable in 40 mm conduit Metre 668
22.2 3 WIRE SUB-MAIN
22.2.1 2.5 sq mm cable in 20 mm conduit Metre 117
21.2.2 4.0 sq mm cable in 25 mm conduit Metre 159
21.2.3 6.0 sq mm cable in 25 mm conduit Metre 191
21.2.4 10.0 sq mm cable in 25 mm conduit Metre 271
21.2.5 16.0 sq mm cable in 32 mm conduit Metre 320
21.2.6 25.0 sq mm cable in 32 mm conduit Metre 678
21.2.7 35.0 sq mm cable in 40 mm conduit Metre 933
22.3 3 1/2 WIRE SUB-MAIN
22.3.1 3 x 2.5 + 1 x 1.5 sq mm cable in 25 mm conduit Metre 141
22.3.2 3 x 4.0 + 1 x 2.5 sq mm cable in 25 mm conduit Metre 183
22.3.3 3 x 6.0 + 1 x 4.0 sq mm cable in 25 mm conduit Metre 222
22.3.4 3 x 10.0 + 1 x 6.0 sq mm cable in 32 mm conduit Metre 342
22.3.5 3 x 16.0 + 1 x 10.0 sq mm cable in 40 mm conduit Metre 580
22.3.6 3 x 25.0 + 1 x 16.0 sq mm cable in 40 mm conduit Metre 835
22.3.7 3 x 35.0 + 1 x 16.0 sq mm cable in 40 mm conduit Metre 1063
22.4 4 WIRE SUB-MAIN
22.4.1 2.5 sq mm cable in 25 mm conduit Metre 153
22.4.2 4.0 sq mm cable in 25 mm conduit Metre 195
22.4.3 6.0 sq mm cable in 25 mm conduit Metre 240
22.4.4 10.0 sq mm cable in 32 mm conduit Metre 367
22.4.5 16.0 sq mm cable in 40 mm conduit Metre 633
22.4.6 25.0 sq mm cable in 40 mm conduit Metre 915
22.4.7 35.0 sq mm cable in 40 mm conduit Metre 122025

SOR ELECTRICAL 2014/CHAPTER-22

Page 25 of 114
CHAPTER - 23

SUB-MAIN IN CONCEALED PVC CONDUIT IN COPPER CONDUCTOR

S.No Description of Item Unit Rate(Rs)


23 Wiring for sub-mains with PVC insulated cable FR with
copper multi strand conductor ISI marked in recessed /
concealed rigid PVC conduit (HMS) ISI marked of suitable
size(Conduit included) including 2mm thick accessories,
connection etc ,as required as per specification
23.1 2 WIRE SUB-MAIN
23.1.1 2.5 sq mm cable in 20 mm conduit Metre 111
23.1.2 4.0 sq mm cable in 25 mm conduit Metre 141
23.1.3 6.0 sq mm cable in 25 mm conduit Metre 172
23.1.4 10.0 sq mm cable in 25 mm conduit Metre 241
23.1.5 16.0 sq mm cable in 32 mm conduit Metre 376
23.1.6 25.0 sq mm cable in 32 mm conduit Metre 517
23.1.7 35.0 sq mm cable in 40 mm conduit Metre 708
23.2 3 WIRE SUB-MAIN
23.2.1 2.5 sq mm cable in 20 mm conduit Metre 140
23.2.2 4.0 sq mm cable in 25 mm conduit Metre 172
23.2.3 6.0 sq mm cable in 25 mm conduit Metre 219
23.2.4 10.0 sq mm cable in 32 mm conduit Metre 351
23.2.5 16.0 sq mm cable in 32 mm conduit Metre 498
23.2.6 25.0 sq mm cable in 40 mm conduit Metre 728
23.2.7 35.0 sq mm cable in 50 mm conduit Metre 1003
23.3 3 1/2 WIRE SUB-MAIN
23.3.1 3 x 2.5 + 1 x 1.5 sq mm cable in 20 mm conduit Metre 145
23.3.2 3 x 4.0 + 1 x 2.5 sq mm cable in 25 mm conduit Metre 192
23.3.3 3 x 6.0 + 1 x 4.0 sq mm cable in 25 mm conduit Metre 249
23.3.4 3 x 10.0 + 1 x 6.0 sq mm cable in 32 mm conduit Metre 396
23.3.5 3 x 16.0 + 1 x 10.0 sq mm cable in 32 mm conduit Metre 578
23.3.6 3 x 25.0 + 1 x 16.0 sq mm cable in 40 mm conduit Metre 857
23.3.7 3 x 35.0 + 1 x 16.0 sq mm cable in 50 mm conduit Metre 1132
23.4 4 WIRE SUB-MAIN
23.4.1 2.5 sq mm cable in 20 mm conduit Metre 153
23.4.2 4.0 sq mm cable in 25 mm conduit Metre 202
23.4.3 6.0 sq mm cable in 25 mm conduit Metre 264
23.4.4 10.0 sq mm cable in 32 mm conduit Metre 431
23.4.5 16.0 sq mm cable in 32 mm conduit Metre 627
23.4.6 25.0 sq mm cable in 40 mm conduit Metre 928
23.4.7 35.0 sq mm cable in 50 mm conduit Metre 127826

SOR ELECTRICAL 2014/CHAPTER-23

Page 26 of 114
CHAPTER -24
REWIRING IN EXISTING RIGID STEEL / PVC NON METALLIC CONDUIT WITH
COPPER CONDUCTOR

S.No Description of Item Unit Rate(Rs)


24 Rewiring in existing surface /concealed rigid steel /PVC non
metallic conduit with PVC insulated cable FR with copper
multi strand conductor ISI marked and other materials as
required including replacement of worn-out /damaged/missing
material, painting etc. complete as per specification. This shall
include all work, arrangement required for wiring but shall
exclude switch, ceiling rose fitting etc.
24.1 Light /Fan/3Pin 6AMP socket outlet on separate board /
Call Bell/ Buzzer Points :-
24.1.1 Short Point Each 188
24.1.2 Medium Point Each 378
24.1.3 Long Point Each 586
24.2 Twin Control Light Point
24.2.1 Short Point Each 218
24.2.2 Medium Point Each 438
24.2.3 Long Point Each 674
24.3 Circuit Wiring
24.3.1 2 X 1.5 Sq mm. Metre 46
24.3.2 2 X 2.5 Sq mm. Metre 64
24.4 3 Pin 5 Amp Socket Outlet Point on Same Board Each 56
24.5 2 WIRE SUB-MAIN
24.5.1 2 X 2.5 Sq mm Metre 64
24.5.2 2 X 4.00 Sq mm Metre 79
24.5.3 2 X 6.00 Sq mm Metre 121
24.5.4 2 X 10.0 Sq mm Metre 180
24.5.5 2 X 16.00 Sq mm Metre 278
24.5.6 2 X 25.00 Sq mm Metre 419
24.5.7 2 X 35.00 Sq mm Metre 591
24.6 3 WIRE SUB-MAIN
24.6.1 3 X 2.5 Sq mm Metre 89
24.6.2 3 X 4.0 Sq mm Metre 122
24.6.3 3 X 6.0 Sq mm Metre 174
24.6.4 3 X 10.0 Sq mm Metre 263
24.6.5 3 X 16.0 Sq mm Metre 409
24.6.6 3 X 25.0 Sq mm Metre 621
24.6.7 3 X 35.0 Sq mm Metre 87927
24.7 3 1/2 WIRE SUB-MAIN
24.7.1 a) 3 x 2.5 + 1 x 1.5 sq mm Metre 105

SOR ELECTRICAL 2014/CHAPTER-24

Page 27 of 114
24.7.2 b) 3 x 4.0 + 1 x 2.5 sq mm Metre 147
24.7.3 c) 3 x 6.0 + 1 x 4.0 sq mm Metre 210
24.7.4 d) 3 x 10.0 + 1 x 6.0 sq mm Metre 316
24.7.5 e) 3 x 16.0 + 1 x 10.0 sq mm Metre 492
24.7.6 f) 3 x 25.0 + 1 x 16.0 sq mm Metre 752
24.7.7 g) 3 x 35.0 + 1 x 16.0 sq mm Metre 1010
24.8 4 WIRE SUB-MAIN
24.8.1 4 X 2.5 sq mm Metre 114
24.8.2 4 X 4.0 sq mm Metre 158
24.8.3 4 X 6.0 sq mm Metre 228
24.8.4 4 X 10.0 sq mm Metre 345
24.8.5 4 X 16.0 sq mm Metre 541
24.8.6 4 X 25.0 sq mm Metre 823
24.8.7 4 X 35.0 sq mm Metre 115628

SOR ELECTRICAL 2014/CHAPTER-24

Page 28 of 114
CHAPTER-25

CONTROL SWITCH GEARS

Rate
S.No Description of Item Unit
(Rs)
25.1 Supplying of I.S.I. Marked Switch Fuse Unit (rewirable)
double pole conduit /cable gland entry with two earthing
terminals --
25.1.1 16 Amps. 250 Volts Each 547
25.1.2 32 Amps. 250 Volts Each 1371
25.2 Supplying and fixing of I.S.I. 32 Amps 240 Volts D.P. switch
flush / surface type with indicator fuse unit front operated
totally enclosed pattern ( suitable for main switch as well as
control switch for appliances ) D.P. with two earthing
terminals -- Each 124
25.3 Suppyling of ISI Marked Switch Fuse Unit (rewirable type )
triple pole with neutral link ,415 Volt having conduit / cable
gland entry with two earthing terminals confirming to IS :
13947(Part I & III) .
25.3.1 16 Amps. Each 1325
25.3.2 32 Amps. Each 1627
25.3.3 63 Amps. Each 3385
25.3.4 100 Amps. Each 6340
25.3.5 200 Amps. Each 9867
25.3.6 320 Amps. Each 12463
25.4 Supplying of ISI Marked iron clad / metal clad triple pole and
neutral switch fuse unit with two earthing terminals &
without HRC fuses --
25.4.1 16 Amps. 415/500 Volts. Each 1325
25.4.2 32 Amps. 415/500 Volts. Each 1678
25.4.3 63 Amps. 415/500 Volts. Each 3737
25.4.4 100 Amps. 415/500 Volts. Each 6847
25.5 Supplying of ISI Marked Change over switches in sheet
enclosure confirming to IS : 4064 / IS : 13947 (part I & III )
with side handle operated 4 pole with two earthing
terminals
25.5.1 16 Amps. 415/500 Volts. (off load ) Each 1944
25.5.2 32 Amps. 415/500 Volts.(off load ) Each 2340
25.5.3 63 Amps. 415/500 Volts.(off load ) Each 4759
25.5.4 100 Amps. 415/500 Volts.(off load ) Each 9547
25.5.5 200 Amps. 415/500 Volts.( off load ) Each 14141
25.5.6 320 Amps. 415/500 Volts.( off load ) Each 17338
25.5.7 400 Amps. 415/500 Volts.( off load ) Each 2265829
25.5.8 630 Amps. 415/500 Volts.( off load ) Each 35431

SOR ELECTRICAL 2014/CHAPTER-25

Page 29 of 114
25.5.9 800 Amps. 415/500 Volts.( off load ) Each 44172
25.6 Supplying of ISI Marked On-Load Change over switches
panel mouniting type confirming to IS : 13947 (part I & III )
with front operated 4 pole, 415 V with two earthing
terminals if required.
25.6.1 63 Amps. (open - execution ) Each 3901
25.6.2 100 Amps. (open - execution ) Each 5105
25.6.3 125 Amps. .(open - execution ) Each 7654
25.6.4 160 Amps. (open - execution ) Each 8405
25.6.5 200 Amps. (open - execution ) Each 10133
25.6.6 250 Amps. (open - execution ) Each 13731
25.6.7 320 Amps. .(open - execution ) Each 15631
25.6.8 400 Amps. .(open - execution ) Each 23150
25.6.9 630 Amps. .(open - execution ) Each 27027
25.6.10 800 Amps. .(open - execution ) Each 40052
25.6.11 63 Amps. (With enclosure ) Each 5516
25.6.12 100 Amps.(With enclosure ) Each 6926
25.6.13 125 Amps. .(With enclosure ) Each 10249
25.6.14 160 Amps. .(With enclosure ) Each 11249
25.6.15 200 Amps. .(With enclosure ) Each 12898
25.6.16 320 Amps. .(With enclosure ) Each 19188
25.6.17 400 Amps. .(With enclosure ) Each 28264
25.6.18 630 Amps. .(With enclosure ) Each 32542
25.6.19 800 Amps. .(With enclosure ) Each 48230
25.7 Supplying of ISI Marked Automatic Transfer Switches
(ATS) confirming to IEC : 60947-1 & IEC : 60947-6-1 with
automatic inbuilt time delay 4 pole, 415 V with two earthing
terminals if required.
25.7.1 100 Amp (open execution ) Each 40907
25.7.2 160 Amp (open execution ) Each 53525
25.7.3 200 Amp (open execution ) Each 68075
25.7.4 315 Amp (open execution ) Each 80577
25.7.5 400 Amp (open execution ) Each 100596
25.7.6 630 Amp (open execution ) Each 124194
25.7.7 100 Amp (with enclosure ) Each 46075
25.7.8 160 Amp (with enclosure ) Each 59059
25.7.9 200 Amp (with enclosure ) Each 74091
25.7.10 315 Amp (with enclosure ) Each 87058
25.7.11 400 Amp (with enclosure ) Each 110614
25.7.12 630 Amp (with enclosure ) Each 13710230
25.8 Supplying of Two Way Centre off MCB Changeover

SOR ELECTRICAL 2014/CHAPTER-25

Page 30 of 114
Switch confirming to IS:13947 (part III ) / IEC : 60947-3, 2/4
pole ,AC 240 / 415 Volt, 50 Hz
25.8.1 25 Amps, Double Pole (DP) Each 1204
25.8.2 40 Amps, Double Pole (DP) Each 1806
25.8.3 25 Amps, Four Pole (FP) Each 2299
25.8.4 40 Amps, Four Pole (FP) Each 3602
25.9 Supplying of ISI Marked Switch Disconnector Fuse (SDF),
open execution (Panel mounting cubicle type) confirming to
IS:13947 (part I & III ) 2 pole , AC -23A ,50 Hz , 415 Volt
with 2 HBC fuses complete.
29.9.1 32 Amps Each 1672
29.9.2 63 Amps Each 2529
29.9.3 100 Amps Each 4932
29.9.4 125 Amps Each 5673
25.10 Supplying of ISI Marked Switch Disconnector Fuse (SDF),
in sheet steel enclosure (Panel mounting cubicle type)
confirming to IS:13947 (part I & III ) 2 pole , AC -23A ,50 Hz ,
415 Volt with 2 HBC fuses complete.
25.10.1 32 Amps Each 2491
25.10.2 63 Amps Each 3257
25.10.3 100 Amps Each 6016
25.10.4 125 Amps Each 6208
25.11 Supplying of ISI Marked Switch Disconnector Fuse (SDF),
open execution (Panel mounting cubicle type) confirming to
IS:13947 (part I & III ) 3 pole and neutral , AC -23A ,50 Hz ,
415 Volt with 3 HBC fuses complete.
25.11.1 32 Amps Each 1990
25.11.2 63 Amps Each 2733
25.11.3 100 Amps Each 5962
25.11.4 125 Amps Each 6820
25.11.5 160 Amps Each 7811
25.11.6 200 Amps Each 9591
25.11.7 250 Amps Each 11541
25.11.8 320 Amps Each 15021
25.11.9 400 Amps Each 18073
25.11.10 630 Amps Each 27831
25.12 Supplying of ISI Marked Switch Disconnector Fuse (SDF),
in sheet steel enclosure (Panel mounting cubicle type)
confirming to IS:13947 (part I & III ) 3 pole and neutral , AC -
23A ,50 Hz , 415 Volt with 3 HBC fuses complete.

25.12.1 32 Amps Each 3780


25.12.2 63 Amps Each 4591
25.12.3 100 Amps Each 8237
25.12.4 125 Amps Each 9561
25.12.5 160 Amps Each 10360
25.12.6 200 Amps Each 1274831

SOR ELECTRICAL 2014/CHAPTER-25

Page 31 of 114
25.12.7 250 Amps Each 15017
25.12.8 320 Amps Each 18416
25.12.9 400 Amps Each 21582
25.12.10 630 Amps Each 32156
25.13 Supplying of ISI Marked Direct On-Line Starters confirming
to IS : 13947-4 with suitable over load relay range and
contactor size, 415 V , 3 -Phase with two earthing terminals
25.13.1 0.75 / 1.0 / 2.0 / 3.0 / 5.0 / 7.5 HP Each 2218
25.13.2 10 HP Each 3323
25.14 Supplying of ISI Marked Automatic Star-Delta Starters
confirming to IS : 13947-4 with suitable over load relay range
and contactor size & timer 415 V , 3 -Phase with two
earthing terminals
25.14.1 12.5 HP Each 7840
25.14.2 15.0 HP Each 7886
25.14.3 20 HP Each 9857
25.14.4 25 HP Each 11743
25.14.5 30 HP Each 12612
25.14.6 35 HP Each 20336
25.14.7 50 HP Each 31569
25.14.8 75 HP Each 54649
25.15 Supplying & fixing of High Breaking Capacity (HBC) Fuse
Links bolted connection type as per IS : 13703 : 1993 & IEC
: 60269 :1986 with 80 kA breaking capacity of approved
make
25.15.1 20 Amp. to 32 Amp Each 69
25.15.2 36 Amp to 63 Amp Each 100
25.15.3 80 Amp to 125 Amp Each 208
25.15.4 160 Amp to 250 Amp Each 313
25.15.5 300 Amp to 315 Amp Each 460
25.15.6 400 Amp to 500 Amp Each 945
25.15.7 630 Amp Each 1691
25.16 Supplying & fixing of High Breaking Capacity (HBC) Fuse
Links knife (DIN) type as per IS : 13703 : 1993 & IEC :
60269 :1986 with 80 kA breaking capacity of approved
make
25.16.1 20 Amp. to 100 Amp Each 261
25.16.2 125 Amp to 160 Amp Each 315
25.16.3 200 Amp to 315 Amp Each 599
25.16.4 350 Amp to 400 Amp Each 686
25.16.5 425 Amp to 630 Amp Each 1051
25.17 Supplying & fixing of ISI marked Porcelain Rewireable type
fuse carrier & base unit of approved make & confirming to
IS: 2086-1993
25.17.1 16 Amps./240 Volts Each 11132
25.17.2 16 Amps./415 Volts or 32 Amps/240 Volts Each 185

SOR ELECTRICAL 2014/CHAPTER-25

Page 32 of 114
25.17.3 32 Amps /415 Volts Each 192
25.17.4 63 Amps /415 Volts Each 337
25.17.5 100 Amps /415 Volts Each 609
25.17.6 200 Amps /415 Volts Each 1141
25.17.7 300 Amps /415 Volts Each 1646
25.18 Supplying & fixing of ISI marked DMC /Nylon Fuse holder
fitting / Fuse Base for knife type HBC fuse Links of approved
make & confirming to IS:13703-2-1
25.18.1 DMC /Nylon Fuse holder fitting 20 Amps /415 Volts Each 126
25.18.2 DMC /Nylon Fuse holder fitting 32 Amps /415 Volts Each 184
25.18.3 DMC /Nylon Fuse holder fitting 63 Amps /415 Volts Each 220
25.18.4 DMC /Nylon Fuse holder fitting 100 Amps /415 Volts Each 902
25.18.5 DMC /Nylon Fuse Base 160 Amps /415 Volts Each 273
25.18.6 DMC /Nylon Fuse Base 250 Amps /415 Volts Each 541
25.18.7 DMC /Nylon Fuse Base 400 Amps /415 Volts Each 721
25.18.8 DMC /Nylon Fuse Base 630 Amps /415 Volts Each 98433

SOR ELECTRICAL 2014/CHAPTER-25

Page 33 of 114
Chapter-26

BUSBAR CHAMBERS AND BUS TRUNCKING

Rate
S.No Description of Item Unit
(Rs)
26.1 Supplying of metal clad ISI Marked bus bar chamber made
of heavy gauge iron sheet complete with copper strip and
bus bar supports as per specification confirming to IS -4064
26.1.1 32 AMP 415 VOLTS, 4 way Each 1862
26.1.2 60/63 AMP 415 VOLTS, 4 way Each 2091
26.1.3 100 AMP 415 VOLTS, 4 way Each 2798
26.1.4 200 AMP 415 VOLTS, 4 way Each 6186
26.1.5 300 AMP 415 VOLTS, 4 way Each 6994
26.1.6 400 AMP 415 VOLTS, 4 way Each 11924
26.1.7 500 AMP 415 VOLTS, 4 way Each 15559
26.2 Supplying, erection and testing of out door Aluminium
Sandwich bus trunking System 415V 3P 4W comprising
of Aluminium Conductor processed with Copper & TIN
plated and Class B insulated, housing fabricated with 1.5mm
thick CRCA sheet enclosure IP 65 protection duly powder
coated. Every joint should be provided with monoblock joint
and shearoff nut. The mounting bracket shall be paid
seperately, including necessary material, anchor fastner,
bolt, nut, connection etc. complete as required for
mentioned below :-
26.2.1 630A 415V 3P 4W, 50 kA , Mtr 21483
26.2.2 800A 415V 3P 4W, 50 kA , Mtr 22044
26.2.3 1000A 415V 3P 4W, 50 kA , Mtr 22387
26.2.4 1250A 415V 3P 4W, 80 kA , Mtr 24838
26.2.5 1600A 415V 3P 4W, 80 kA , Mtr 29938
26.2.6 2000A 415V 3P 4W, 80 kA , Mtr 34954
26.3 Supplying, erection and testing of accessories for out door
Aluminium Sandwich bus trunking System 415V 3P 4W
comprising of Aluminium Conductor processed with Copper
& TIN plated and Class B insulated, housing fabricated with
1.5mm thick CRCA sheet enclosure IP 65 protection duly
powder coated. Every joint should be provided with mono
block joint and shear off nut including necessary material,
anchor fastener, bolt, nut, connection etc. complete as
required for mentioned below :-
26.3.1 HORIZONTAL ELBOW RH STD 630A each 22461
26.3.2 HORIZONTAL ELBOW RH STD 800A each 23157
26.3.3 HORIZONTAL ELBOW RH STD 1000A each 28112
26.3.4 HORIZONTAL ELBOW RH STD 1250A each 3091734

SOR ELECTRICAL 2014/CHAPTER-26

Page 34 of 114
26.3.5 HORIZONTAL ELBOW RH STD 1600A each 36998
26.3.6 HORIZONTAL ELBOW RH STD 20000A each 39869
26.3.7 VERTICAL ELBOW RH STD 630A each 32795
26.3.8 VERTICAL ELBOW RH STD 800A each 13375
26.3.9 VERTICAL ELBOW RH STD 1000A each 34069
26.3.10 VERTICAL ELBOW RH STD 1250A each 34913
26.3.11 VERTICAL ELBOW RH STD 1600A each 35756
26.3.12 VERTICAL ELBOW RH STD 2000A each 38060
26.3.13 TRANS FEED RH STD - BOARD 630A each 20412
26.3.14 TRANS FEED RH STD - BOARD 800A each 25466
26.3.15 TRANS FEED RH STD - BOARD 1000A each 26733
26.3.16 TRANS FEED RH STD - BOARD 1250A each 27095
26.3.17 TRANS FEED RH STD - BOARD 1600A each 30098
26.3.18 TRANS FEED RH STD - BOARD 2000A each 32796
26.3.19 ADAPTOR BOX each 12463
26.3.20 COPPER FLEXIBLES 630A each 25964
26.3.21 COPPER FLEXIBLES 800A each 31157
26.3.22 COPPER FLEXIBLES 1000A each 36350
26.3.23 COPPER FLEXIBLES 1250A each 41543
26.3.24 COPPER FLEXIBLES 1600A each 51929
26.3.25 COPPER FLEXIBLES 2000A each 67508
26.4 Supplying, erection and testing of indoor Aluminium
Sandwich bus trunking System 415V 3P 4W comprising of
Aluminium Conductor processed with Copper & TIN plated
and Class B insulated, housing fabricated with 1.5mm thick
CRCA sheet enclosure IP 55 protection duly powder coated.
Every joint should be provided with mono block joint and
shear off nut with 3 plug in provision per 3 mtr including
necessary material, anchor fastner, bolt, nut, connection etc.
complete as required for mentioned below :-
26.4.1 630A 415V 3P 4W, 50 kA , Mtr 20875
26.4.2 800A 415V 3P 4W, 50 kA , Mtr 21499
26.4.3 1000A 415V 3P 4W, 50 kA , Mtr 22901
26.4.4 1250A 415V 3P 4W, 80 kA , Mtr 24251
26.4.5 1600A 415V 3P 4W, 80 kA , Mtr 30108
26.4.6 2000A 415V 3P 4W, 80 kA , Mtr 3499035

SOR ELECTRICAL 2014/CHAPTER-26

Page 35 of 114
26.5 Supplying, erection and testing of accessories for indoor
Aluminium Sandwich bus trunking System 415V 3P 4W
comprising of Aluminium Conductor processed with Copper
& TIN plated and Class B insulated, housing fabricated with
1.5mm thick CRCA sheet enclosure IP 55 protection duly
powder coated. Every joint should be provided with
monoblock joint and shearoff nut with 3 plug in provision per
3 mtr including necessary material, anchor fastner, bolt, nut,
connection etc. complete as required for mentioned below :-
26.5.1 TRANS FEED RH STD - BOARD 630A each 20412
26.5.2 TRANS FEED RH STD - BOARD 800A each 25466
26.5.3 TRANS FEED RH STD - BOARD 1000A each 26733
26.5.4 TRANS FEED RH STD - BOARD 1250A each 27095
26.5.5 TRANS FEED RH STD - BOARD 1600A each 30098
26.5.6 TRANS FEED RH STD - BOARD 2000A each 32796
26.5.7 HANGER WITH BRACKET AND SPRING (RISER) each 3523
26.5.8 HANGER SUSPANSION each 339
26.5.9 END COVER each 12243
26.5.10 PLUG-IN BOX 125A IP55 EMPTY each 19860
26.5.11 PLUG-IN BOX 160A IP55 EMPTY each 19918
26.5.12 PLUG-IN BOX 250A IP55 EMPTY each 4523036

SOR ELECTRICAL 2014/CHAPTER-26

Page 36 of 114
CHAPTER 27
MCCBs, ISOLATORS, MCBs, RCBOs, MCB DBs
Description of Item Rate
S.No Unit
(Rs)
27.1 Supplying of ISI Marked and approved make of Moulded
Case Circuit Breaker (MCCB) suitable for 3 phase,3 pole,
50 Hz, 415 Volts, AC supply with respective interrupting
capacity (KA) at 415 Volts cited against their range standard
conforming to IS 8828
27.1.1 MCCB with Breaking Capacity 10 KA at 415 V
27.1.1.1 Current Rating -25 to100 Amps Each 1693
27.1.2 MCCB with Breaking Capacity 25 KA at 415 V
27.1.2.1 Current Rating -25 to100 Amps & 80% -100% adjustable Each 5601
27.1.2.2 Current Rating -125 Amps & 80% -100% adjustable Each 7229
27.1.2.3 Current Rating -160 Amps & 80% -100% adjustable Each 9879
27.1.2.4 Current Rating -200 Amps & 80% -100% adjustable Each 13219
27.1.3 MCCB with Breaking Capacity 35 KA at 415 V
27.1.3.1 Current Rating -160 Amps & Adjustable: 80% -100%
thermal Each 10927
27.1.3.2 Current Rating -200 Amps & Adjustable: 80% -100%
thermal Each 14289
27.1.3.3 Current Rating -250 Amps & Adjustable: 80% -100%
thermal Each 16615
27.1.3.4 Current Rating -315 Amps & Adjustable: 80% -100%
thermal Each 21632
27.1.3.5 Current Rating -400 Amps & Adjustable: 80% -100%
thermal Each 24115
27.1.3.6 Current Rating -500/630 Amps & Adjustable: 80% -100%
thermal Each 27988
27.1.4 MCCB with Breaking Capacity 50 KA at 415 V
27.1.4.1 Current Rating -800 Amps & Adjustable: 70% -100%
thermal & 4-10 times magnetic setting Each 45448
27.2 Supplying of ISI Marked and approved make of Moulded
Case Circuit Breaker (MCCB) Micro-Processor Release
( current setting for overload & short circuit ) suitable for 3
phase & Neutral, 3 pole, 50 Hz, 415 Volts, AC supply with
respective interrupting capacity (KA) at 415 Volts cited
against their range standard conforming to IS 8828
27.2.1 MCCB with Breaking Capacity 25 KA at 415 V
27.2.1.1 40 & 100 Amps 3 Pole & Micro-Processor Release, over
load 40% -100% x In. & short circuit 1.5 - 8 x Ir. adjustable Each 13325
27.2.1.2 160 Amps 3 Pole & Micro-Processor Release, over load
40% -100% x In. & short circuit 1.5 - 8 x Ir. Adjustable Each 1733437
27.2.1.3 250 Amps 3 Pole & Micro-Processor Release, over load Each 23831

SOR ELECTRICAL 2014/CHAPTER-27

Page 37 of 114
40% -100% x In. & short circuit 1.5 - 8 x Ir. Adjustable
27.2.2 MCCB with Breaking Capacity 36 KA at 415 V
27.2.2.1 40 & 100 Amps 3 Pole & Micro-Processor Release, over
load 40% -100% x In. & short circuit 1.5 - 8 x Ir. adjustable Each 14096
27.2.2.2 160 Amps 3 Pole & Micro-Processor Release, over load
40% -100% x In. & short circuit 1.5 - 8 x Ir. Adjustable Each 17352
27.2.2.3 250 Amps 3 Pole & Micro-Processor Release, over load
40% -100% x In. & short circuit 1.5 - 8 x Ir. Adjustable Each 25298
27.2.2.4 400 Amps 3 Pole & Micro-Processor Release, over load
40% -100% x In. & short circuit 1.5 - 8 x Ir. Adjustable Each 30635
27.2.2.5 630 Amps 3 Pole & Micro-Processor Release, over load
40% -100% x In. & short circuit 1.5 - 8 x Ir. Adjustable Each 33728
27.2.3 MCCB with Breaking Capacity 50 KA at 415 V
27.2.3.1 800 Amps 3 Pole & Micro-Processor Release, over load
40% -100% x In. & short circuit 1.5 - 8 x Ir. Adjustable Each 56970
27.2.3.2 1250 Amps 3 Pole & Micro-Processor Release, over load
40% -100% x In. & short circuit 1.5 - 8 x Ir. Adjustable Each 93204
27.3 Supplying of approved make Moulded Case Circuit
Breaker (MCCB) without protection release suitable for
3 phase, 3 pole, 50 Hz, 415 Volts, AC supply standard
conforming to IS 8828
27.3.1 MCCB with Breaking Capacity 36 KA at 415 V
27.3.1.1 MCCB Swtch Disconnector Rating -200 Amps 3 Pole
without protection Release Each 11839
27.3.1.2 MCCB Swtch Disconnector Rating -400 Amps 3 Pole
without protection Release Each 15909
27.3.1.3 MCCB Swtch Disconnector Rating -600 Amps 3 Pole
without protection Release Each 18187
27.3.1.4 MCCB Swtch Disconnector Rating -200 Amps 4 Pole
without protection Release Each 15193
27.3.1.5 MCCB Swtch Disconnector Rating -400 Amps 4 Pole
without protection Release Each 20464
27.3.1.6 MCCB Swtch Disconnector Rating -600 Amps 4 Pole
without protection Release Each 23637
27.4 Supplying of ISI Marked and approved make of Air Circuit
Breaker (ACB) with Microprocessor release with LCD
screen showing kW, kVA, PF, maximum demand with
breaking capacity of 50 kA , 4 pole , 415 Volts conforming
to IEC : 60947-2 / IS :13947-II
27.4.1 630 Amp,manual,fixed Each 105593
27.4.2 800 Amp,manual,fixed Each 107640
27.4.3 1000 Amp,manual,fixed Each 112884
27.4.4 1250 Amp,manual,fixed Each 130708
27.4.5 1600 Amp,manual,fixed Each 143289
27.4.6 2000 Amp,manual,fixed Each 15955338
27.4.7 630 Amp,manual,drawout Each 129299
27.4.8 800 Amp,manual,drawout Each 131803

SOR ELECTRICAL 2014/CHAPTER-26

Page 38 of 114
27.4.9 1000 Amp,manual,drawout Each 137717
27.4.10 1250 Amp,manual,drawout Each 151322
27.4.11 1600 Amp,manual,drawout Each 174201
27.4.12 2000 Amp,manual,drawout Each 189480
27.5 Supplying of ISI Marked and accepted standard of
Miniature Circuit Breaker (MCB) of 'C' series suitable for
240/415 Volts, 50 Cycle , 10 kA Value AC supply
confirming to IS : 8828 : 1996, IEC : 60898 :2002 but
without enclosures :-
27.5.1 SINGLE POLE (SP)
27.5.1.1 0.5 Amp to 5 Amp Rating Each 304
27.5.1.2 6 Amp to 32 Amp Rating Each 205
27.5.1.3 For 40 Amps. Rating only. Each 447
27.5.1.4 50 Amp to 63 Amp Rating Each 472
27.5.2 SINGLE POLE & NEUTRAL(SPN)
27.5.2.1 0.5 Amp to 5 Amp Rating Each 843
27.5.2.2 6 Amp to 32 Amp Rating Each 647
27.5.2.3 For 40 Amps. Rating only. Each 994
27.5.2.4 50 Amp to 63 Amp Rating Each 1031
27.5.3 DOUBLE POLE (DP)
27.5.3.1 0.5 Amp to 5 Amp Rating Each 811
27.5.3.2 6 Amp to 32 Amp Rating Each 617
27.5.3.3 For 40 Amps. Rating only. Each 982
27.5.3.4 50 Amp to 63 Amp Rating Each 1022
27.5.4 FOR TRIPLE POLE (TP)
27.5.4.1 0.5 Amp to 5 Amp Rating Each 1166
27.5.4.2 6 Amp to 32 Amp Rating Each 985
27.5.4.3 For 40 Amps. Rating only. Each 1483
27.5.4.4 50 Amp to 63 Amp Rating Each 1527
27.5.5 FOR TRIPLE POLE & NEUTRAL(TPN)
27.5.5.1 0.5 Amp to 5 Amp Rating Each 1668
27.5.5.2 6 Amp to 32 Amp Rating Each 1391
27.5.5.3 For 40 Amps. Rating only. Each 1991
27.5.5.4 50 Amp to 63 Amp Rating Each 2033
27.5.6 FOUR POLE(FP)
27.5.6.1 0.5 Amp to 5 Amp Rating Each 1607
27.5.6.2 6 Amp to 32 Amp Rating Each 1358
27.5.6.3 For 40 Amps. Rating only. Each 1923
27.5.6.4 50 Amp to 63 Amp Rating Each 1975
27.6 Supplying of MCB Isolators suitable for 240/415 Volts, 50
Hz AC supply with KA value rating 10 kA of approved
make confirming to IS :13947-Part III : 1993 & IEC :60947-
3:2001 (without enclosures ) :-
27.6.1 SINGLE POLE
27.6.1.1 40 Amps. Each 236
27.6.1.2 63 Amps. Each 26439
27.6.2 DOUBLE POLE

SOR ELECTRICAL 2014/CHAPTER-27

Page 39 of 114
27.6.2.1 40 Amps. Each 389
27.6.2.2 63 Amps. Each 505
27.6.3 TRIPLE POLE
27.6.3.1 40 Amps. Each 701
27.6.3.2 63 Amps. Each 802
27.6.4 FOUR POLE
27.6.4.1 40 Amps. Each 880
27.6.4.2 63 Amps. Each 926
27.6.4.3 80 Amps. Each 1052
27.6.4.4 100 Amps. Each 1132
27.7 Supply of approved make powder coated sheet steel
encloser SPN MCB DB inclusive of Bus bar, Neutral bar,
Earth bar & two earth terminals etc. complete as per
IS:13032( exclusive of MCB & isolator )-
27.7.1 2 way single door Each 150
27.7.2 4 way single door Each 905
27.7.3 4 way Double Door IP 43 protection Each 1185
27.7.4 6 way Double Door IP 43 protection Each 1280
27.7.5 8 way Double Door IP 43 protection Each 1478
27.7.6 12 way Double Door IP 43 protection Each 1794
27.7.7 16 way Double Door IP 43 protection Each 2228
27.8 Supplying of approved make TPN MCB DB Metal Double
Door IP 43 protection with provision for FP
MCB/Isolator/RCCB/RCBO as incomer and SP MCBs as
outgoing inclusive of Bus bar, Neutral bar, Earth bar & two
earth terminals etc. complete as per IS:13032( exclusive of
MCB & isolator ):
27.8.1 4 way (4+12) Each 2639
27.8.2 4 way (8+12) Each 2961
27.8.3 6 way (8+18) Each 3650
27.8.4 8 way (8+24) Each 4379
27.8.5 12 way (8+36) Each 6552
27.9 Supplying of approved make Vertical TPN MCB DB Metal
Double Door IP 43 protection with provision for FP
CB/Isolator/RCCB/RCBO as incomer and SP/TP MCBs as
outgoing inclusive of Bus bar, Neutral bar, Earth bar & two
earth terminals etc. complete as per IS:13032( exclusive of
MCB & isolator )
27.9.1 4 way (8+12) Each 7261
27.9.2 8 way (8+24) Each 9250
27.9.3 12 way (8+36) Each 12344
27.10 Supplying of approved make, powder coated Metal Double
Door Vertical TPN MCB DB IP 43 protection with provision
for MCCB up to 160A TP/ FP 36kA as incomer and space
for SP/TP MCBs as outgoing (without MCCB / MCBs)
inclusive of bus bar & connections etc
27.10.1 4 way without MCCB Each 852140

SOR ELECTRICAL 2014/CHAPTER-27

Page 40 of 114
27.10.2 8 way without MCCB Each 10815
27.10.3 12 way without MCCB Each 14341
27.11 Supplying of approved make, powder coated Vertical Metal
Double Door TPN MCB DB IP 43 protection with provision
for MCCB upto 250A TP /4P upto 50kA as incomer and
space for SP/TP MCBs as outgoing (without MCCB/MCBs)
inclusive of busbar &connections etc
27.11.1 4 way without MCCB Each 17233
27.11.2 8 way without MCCB Each 20166
27.11.3 12 way without MCCB Each 21201
27.12 Supplying & fixing of approved make Industrial type metal
plug & socket DBs (without MCB) SPN sheet encloser
(dust protected ) inclusive of 2 pole and earth metal plug
and socket and space to incorporate SP MCB complete as
per specification as required.
27.12.1 10 Amps Each 1036
27.12.2 20 Amps Each 1092
27.13 Supplying & fixing of ISI marked Industrial type metal plug
socket D.B.s (without MCBs) for TPN encloser three pole
and earth metal plug and socket including space
incorporating TP MCB complete as per specification as
required.
27.13.1 20 Amps Each 2341
27.13.2 30 Amps Each 2640
27.14 Supply & fixing of approved make Industrial type metal
plug & socket, 3 pin (2P + E) conforming to IEC : 60309 -
1&3 complete as per specification
27.14.1 10 Amps Plug only Each 145
27.14.2 10 Amps socket only Each 145
27.14.3 20 Amps Plug only Each 159
27.14.4 20 Amps socket only Each 169
27.15 Supplying and installing of RCBOs (Residual current
circuit breaker with overload and short circuit
protection) ISI marked complete as per I.S. standard
confirming to IEC:61009-2-1 & IS:12640-2:2001,240/415V
50 Hz with 10 kA short circuit withstand capacity for earth
leakage, overload & short circuit protection including
connection in existing enclosure in approved manner as
per specification.
27.15.1 DP(4 module)
27.15.1.1 2 pole 6 to 25 Amps, 30 mA sensitivity Each 3029
27.15.1.2 2 pole 32 Amps, 30 mA sensitivity Each 3029
27.15.1.3 2 pole 40 Amps, 30 mA sensitivity Each 3783
27.15.1.4 2 pole 63 Amps, 30 mA sensitivity Each 4527
27.15.1.5 2 pole 6 to 25 Amps, 100 mA sensitivity Each 3738
27.15.1.6 2 pole 32 Amps, 100 mA sensitivity Each 3597
27.15.1.7 2 pole 40 Amps, 100 mA sensitivity Each 413841

SOR ELECTRICAL 2014/CHAPTER-27

Page 41 of 114
27.15.1.8 2 pole 63 Amps, 100 mA sensitivity Each 4789
27.15.2 FP(8 module)
27.15.2.1 4 pole 16 Amps, 30 mA sensitivity Each 4092
27.15.2.2 4 pole 25-32 Amps, 30 mA sensitivity Each 4223
27.15.2.3 4 pole 40 Amps, 30 mA sensitivity Each 4287
27.15.2.4 4 pole 63 Amps, 30 mA sensitivity Each 5114
27.15.2.5 4 pole 16 Amps, 100/300 mA sensitivity Each 4666
27.15.2.6 4 pole 25-32 Amps, 100/300 mA sensitivity Each 4505
27.15.2.7 4 pole 40 Amps, 100/300 mA sensitivity Each 4641
27.15.2.8 4 pole 63 Amps, 100/300 mA sensitivity Each 5261
27.16 Supply & fixing of approved make accepted standard sheet
steel enclosure ( dust protected ) duly powder coated paint
Neutral bar suitable for MCB / RCBOs/MCCB of capacity as
required etc. complete as per specification ( exclusive of
M.C.B./ MCCB/RCBOs )
27.16.1 For MCB
27.16.1.1 DP/TP/FP Enclosure Each 537
27.16.1.2 FP RCBO Enclosure Each 910
27.16.2 For MCCB
27.16.2.1 63/100A 3P/4P Enclosure Each 1650
27.16.2.2 160A 3P/4P Enclosure Each 3091
27.16.2.3 250A 3P/4P Enclosure Each 5491
27.16.2.4 250A ER 3P/4P Enclosure Each 657542

SOR ELECTRICAL 2014/CHAPTER-27

Page 42 of 114
CHAPTER - 28

FIXING OF SFUs, DBs, BUSBAR, MCCBs, MCBs, ISOLATORs & RCBOs

Description of Item Rate


S.No Unit
(Rs)
28.1 Fixing of metal clad enclosure on 25 X 5 mm flat iron
clamps including supplying and fixing of clamps as
required duly embedded in masonry including cable
connection and other required material as per
specification :-
28.1.1 16 Amps SP/DP Switch /SPN DB up to 4 way Each 124
28.1.2 32 Amps DP switch /SPN DB up to 8 way /16 AmpTPN
DB up to 3 way per pole or 16 Amps TP or TPN switch /
16 Amps 415 V Isolator Each 155
28.1.3 32 Amps TP or TPN switch/ 32 Amps 415 V Isolator /
16 Amps TPN DB up to 6 way per pole /32 Amps 415
Volt bus bar 4 way Each 172
28.2 Fixing of metal clad enclosure on 25X 25 X 5 mm angle
iron clamps including supplying and fixing of clamps as
required duly embedded in masonary including cable
connection and other required material as per
specification :-
28.2.1 Fixing of 63 Amps TP or TPN main switches/ DB 63
Amps. 240/415 Volt 4 to 8 way or 63 Amps change over
switch /63 Amps 415 Volt Isolator /30 Amps 415V TPN
DB up to 6 way per pole and bus bar 4 way Each 266
28.2.2 Fixing of 100 Amps TP or TPN main switch or 100 Amps
change over switch /100 Amps 415 Volt Isolators and
busbar 4 way Each 296
28.2.3 Fixing of 200 Amps TP or TPN main switch or 200 Amps
change over switch /200 Amps 415 Volt Isolators and
busbar 4 way Each 320
28.3 Fixing of metal clad enclosure on 35X 35 X 5 mm angle
iron clamps including supplying and fixing of clamps as
required duly embedded in masonary including cable
connection and other required material as per
specification :-
28.3.1 Fixing of 300/400 Amps TP or TPN main switch or
300/400 Amps change over switch /300/400 Amps 415
Volt Isolators and bus bar 4 way Each 57243

SOR ELECTRICAL 2014/CHAPTER-28

Page 43 of 114
28.3.2 Fixing of 500/600 Amps TP or TPN main switch or
500/600 Amps change over switch 500/600 Amps 415
Volt Isolators and busbar 4 way Each 637
28.4 Fixing of MCB /MCCB/ Isolator in sheet steel enclosure
as required as per accepted practice, including mounting
on busbar and cable connection etc. complete (Labour
only )
28.4.1 MCB / Isolator SP/DP Each 11
28.4.2 MCB /MCCB Isolator TP /TPN/FP Each 22
28.5 Labour charges for fixing sheet steel enclosure, MCB
DB surface mounting type, as per accepted practice on
25x5mm flat iron clamps duly embedded in wall,cable
connection etc. complete.
FOR S.No :-
28.5.1 27.7.1 to.27.7.4 Each 135
28.5.2 27.7.5 & 27.8.1 to 27.8.2 Each 184
28.5.3 27.8.3 to 27.8.4 & 27.9.1 Each 201
28.6 Labour charges for fixing sheet steel enclosures, MCB
DB surface mounting type,as per accepted practice on
25x25x 5 mm angle iron clamp,including supplying and
fixing of clamps duly embedded in wall,cable connection
etc. complete :-
FOR S.No :-
28.6.1 27.7.6 & 27.7.7; 27.8.5 ; 27.9.2 & 27.9.3 & 27.10.1 to
27.10.3 ; 27.11.1 to 27.11.3 Each 334
28.7 Labour charges for fixing sheet steel enclosures, MCB
DB flush mounting type, as per accepted practice, duly
embedded and end plate completely flushed in wall,
cable connection etc.complete :-
FOR S.No :-
28.7.1 27.7.1 to 27.7.7 ; 27.8.1 to 27.8.3 & 27.9.1, Each 232
28.7.2 27.8.4 & 27.8.5 ; 27.9.2 to 27.9.3 ; 27.10.1 to 27.10.3 &
27.11.1 to 27.11.3 Each 27144

SOR ELECTRICAL 2014/CHAPTER-28

Page 44 of 114
CHAPTER - 29
WIRING ACCESSORIES,PANELS,LAMPS,
Rate
S.No Description of Item Unit
(Rs)
29.1 Supplying and fixing as per specification Polycarbonate
pendent Holder of approved make including flexible cord up
to 3 Meter length with necessary materials complete Each 31
29.2 Supplying and fixing as per specification Polycarbonate
Batten Holder / Angle Holder of approved make with
necessary materials complete Each 32
29.3 Supplying and fixing as per specification Call bell / buzzer of
approved make with necessary materials complete.
29.3.1 Buzzer Each 58
29.3.2 Ding Dong bell Each 107
29.3.3 Musical bell Each 248
29.3.4 Remote/cordless bell Each 1018
29.3.5 Gong bell Each 93
29.4 Supplying and fixing as per specification Modular Call bell
indicator 230 Volt A.C. including reset and buzzer of
approved make with necessary materials complete.
29.4.1 Bell Indicator with Reset( 1 Module) 250V Each 272
29.4.2 Buzzer Modular (2 Module) Each 174
29.5 Supplying and fixing of multi core round HRFR / FR PVC
insulated copper (flexible) conductor & PVC sheathed
cables 1100 Volts as per IS:694-1990 of approved make
29.5.1 ( 16 /0.2 mm )Three core 0.5 sq.mm. Metre 23
29.5.2 ( 24 /0.2 mm ) Three core 0.75 sq.mm. Metre 25
29.5.3 ( 30 /0.25 mm ) Three core 1.5 sq.mm. Metre 41
29.5.4 ( 50 /0.25 mm ) Three core 2.5 sq.mm. Metre 67
29.5.5 ( 56 /0.3 mm ) Three core 4.0 sq.mm. Metre 107
29.6 Supplying and fixing in position incandescent lamp of
approved make as per IS specification
29.6.1 15 Watt 250 Volt Each 20
29.6.2 25 Watt 250 Volt Each 21
29.6.3 40 Watt 250 Volt Each 21
29.6.4 60 Watt 250 Volt Each 21
29.6.5 100 Watt 250 Volt Each 23
29.6.6 200 Watt 250 Volt Each 31
29.6.7 15 Watt 250 Volt coloured lamp Each 20
29.7 Supplying and fixing as per specification Switch of approved
make ISI marked with necessary material complete.
29.7.1 6 Amp Flush type Each 23
29.7.2 20 Amp Flush type Each 9045

SOR ELECTRICAL 2014/CHAPTER-29

Page 45 of 114
29.7.3 6 Amp S.P. 250 Volt two way Flush type Each 31
29.7.4 6/10 Amps S.P.250 Volt Modular Switch Each 128
29.7.5 20/16 Amps S.P.250 Volt Modular Switch Each 190
29.7.6 6/10 Amps S.P.250 Volt Modular Switch 2 way Each 156
29.8 Supplying and fixing as per specification socket outlet of
approved make & ISI marked with necessary material
complete
29.8.1 6 Amp 250 Volt 3 / 5 Pin Flush type Each 44
29.8.2 16 Amp 250 Volt 3 / 6 Pin Flush type Each 105
29.8.3 10 Amps 3 Pin Uni Modular Socket Each 207
29.8.4 20 / 10 Amps Twin Modular Socket Each 333
29.9 Supplying and fixing as per specification 6 Amp 250 Volt
Bell Push switch of approved make ISI marked with
necessary material complete.
29.9.1 6/10 Amps S.P.250 Volt Modular Switch Bell Push Each 154
29.9.2 Flush Type Bell Push Each 35
29.9.3 Surface Bell Push 6A Each 35
29.10 Supplying and fixing as per specification switch socket
combined of approved make & ISI marked with necessary
material complete
29.10.1 20/10 Amp 250 Volt 3 / 6 Pin Flush type 182
29.11 Supplying and fixing as per specification Polycarbonate
Ceiling rose 3 Plate of approved make ISI marked with
necessary material complete. Each 22
29.12 Supplying and fixing of approved make 3 pin plug top ISI
marked
29.12.1 6 Amp 250 Volt 3 Pin Each 61
29.12.2 16 Amp 250 Volt 3 Pin Each 79
29.13 Supplying and fixing as per specification Ball Socket of
approved make with necessary material complete. Each 24
29.14 Supplying and fixing as per specification Caution / Danger
Board as required of approved make & design with
necessary material complete.
29.14.1 Small Size Each 80
29.14.2 Large Size Each 160
29.15 Supplying,Fixing and Testing of MPP condensor 440 Volt
Single Phase of approved make as required as per
specification
29.15.1 Condensor 2.5 mfd 440V Each 32
29.15.2 Condensor 3.15 mfd 440 V Each 38
29.15.3 Condensor 4.00 mfd 440 V Each 46
29.15.4 Condensor 6.00 mfd 440 V Each 86
29.15.5 Condensor 36.00 mfd 440 V Each 404
29.15.6 Condensor 45.00 mfd 440 V Each 437
29.15.7 Condensor 50.00 mfd 440 V Each 490
29.15.8 Condensor 60.00 mfd 440 V Each 51246
29.16 Supplying,Fixing and Testing of MPP condensor 250 Volt

SOR ELECTRICAL 2014/CHAPTER-29

Page 46 of 114
Single Phase of approved make as required as per
specification
29.16.1 Condensor 4 mfd 250 V Each 58
29.16.2 Condensor 8 mfd 250 V Each 78
29.16.3 Condensor 10 mfd 250 V Each 107
29.16.4 Condensor 15 mfd 250 V Each 136
29.16.5 Condensor 20 mfd 250 V Each 175
29.16.6 Condensor 33 mfd 250 V Each 234
29.16.7 Condensor 42 mfd 250 V Each 307
29.17 Supplying, Fixing and Testing of mixed die-electric ultra
heavy duty APP capacitor 440 Volt, 3 Ph., peak inrush
current upto 500 x In, over current upto 3 x In(normal
current), operating losses total not more than 0.35 W /
KVAr, operating life not less than 300000 hrs, switching
20000 operation / year, as per IS:13340-1993, IS:13341-
1992, IS:13585-1994, of approved make as required as per
specification
29.17.1 5 to 25 KVAr bank P KVAr 633
29.18 Supplying, Fixing and Testing of MPP - H heavy duty
capacitor 415 Volt, 3 Ph., peak inrush current up to 250 x
In, over current upto 1.8 x In(normal current), operating
losses total not more than 0.35 W / KVAr, switching 8000
operation / year, as per IS:13340-1993, IS:13341-1992 of
approved make as required as per specification
29.18.1 5 to 25 KVAr bank P KVAr 390
29.19 Supplying,Fixing and Testing of Flourescent Tube rod ISI
marked of approved make as required as per specification
29.19.1 4' X 40 Watt Each 50
29.19.2 4' X 36 Watt Each 50
29.19.3 2' X 20 Watt Each 45
29.19.4 2' X 18 Watt Each 48
29.19.5 T - 5 Lamp - 14 Watt Each 125
29.19.6 T - 5 Lamp - 24 Watt Each 166
29.19.7 T - 5 Lamp - 28 Watt Each 133

29.20 Supplying,Fixing and Testing of SV lamp SON-T (tubular


clear type) ISI marked of approved make as required as
per specification
29.20.1 70 Watt Each 444
29.20.2 150 Watt Each 577
29.20.3 250 Watt Each 643
29.20.4 400 Watt Each 754
29.21 Supplying, Fixing and Testing of MH lamp Single ended
type ISI marked of approved make as required as per
specification
29.21.1 70 Watt Each 832
29.21.2 150 Watt Each 94247

SOR ELECTRICAL 2014/CHAPTER-29

Page 47 of 114
29.21.3 250 Watt Each 1083
29.21.4 400 Watt Each 1090
29.22 Supplying, Fixing and Testing of MH lamp Double ended
type ISI marked of approved make as required as per
specification
29.22.1 70 Watt Each 643
29.22.2 150 Watt Each 665
29.23 Supplying, Fixing and Testing of Compact Fluorescent
Lamp (CFL) with inbuilt electronic ballast ISI marked BC /
ES cap of approved make as required as per specification
29.23.1 5 Watt Each 161
29.23.2 8 Watt Each 166
29.23.3 11 Watt Each 177
29.23.4 15 Watt Each 194
29.23.5 18 Watt Each 227
29.23.6 20 Watt Each 227
29.23.7 23 Watt Each 255
29.23.8 26 Watt Each 288
29.23.9 45 Watt Each 604
29.23.10 65 Watt Each 721
29.23.11 85 Watt Each 832
29.24 Suppling,Fixing and Testing of Compact ,Fluorescent Lamp
Non-Retrofit ISI marked of approved make as required as
per specification
29.24.1 9 Watt, 2Pin /4 Pin Each 107
29.24.2 11 Watt, 2Pin / 4 Pin Each 113
29.24.3 13 Watt, 2Pin Each 142
29.24.4 18 Watt, 2Pin / 4 Pin, D Type Each 148
29.24.5 18 Watt, 4Pin / 4 Pin, L Type Each 175
29.24.6 36 Watt, 4Pin L Type Each 180
29.25 Supplying, Fixing and Testing of Halogen Rod of approved
make as required as per specification
29.25.1 500 Watt Each 99
29.25.2 1000 Watt Each 110
29.26 Supplying, Fixing and Testing of Ball Bearing of approved
make as required as per specification
29.26.1 6201 Each 138
29.26.2 6202 Each 150
29.26.3 6203 Each 163
29.26.4 6204 Each 200
29.27 Supplying and fixing of approved make Resistance type
Fan regulator including connection etc. as required on
existing board Each 84
29.28 Supplying and fixing of approved make step type electronic
Fan regulator including connection etc. as required on
existing board
29.29.1 100 Watt (socket type) Each 29148

SOR ELECTRICAL 2014/CHAPTER-29

Page 48 of 114
29.30 Supplying and fixing of approved make electronic dimmer /
regulator including connection etc. as required on existing
board
29.30.1 450 Watt Each 228
29.30.2 1000 Watt Each 390
29.31 Supplying and fixing of approved make step type Modular
electronic Fan regulator including connection etc. as
required on existing board
29.31.1 100 Watt (1 Module) Each 574
29.31.2 100 Watt (2 module) Each 689
29.32 Supplying and fixing of approved make step type Modular
electronic dimmer including connection etc. as required on
existing board
29.32.1 650 Watt (1 Module) Each 567
29.32.2 1000 Watt (2 module) Each 842
Locking arrangement for Switch Gear Mounting
29.33 Supplying, fixing, testing & commissioning wall / floor
mounted LT Panel primer coated with powder coated paint
& provided with required gasket for dust / vermin proof with
degree of protection IP42 suitable for 415V 3 phase, 50 Hz,
4 wire system fabricated out of CRCA sheet up to 2 mm
thick (1.6 mm for doors) duly compartmentalized for
incomer, bus section, outgoings, cable alleys & CT, PT
Ampere Meter, Volt Meter, selector switches, Frequency
Meter, phase indicating lamps, Energy Meter complete
including cost of busbar supports, detachable cable gland
plates, 2 earthing terminals, internal wiring & fixing of
separately supplied MCBs, MCCBs , ACB, panel mounted
Changeover switch / SFUs, etc. as required but excluding
cost of bus bar strips, Ampere Meter, Volt Meter, Selector
switch as per approved design & specification Kg 180
29.34 Supplying and fixing of LT Panel accessories of approved
make in existing LT Panel including connections etc.as
required as per spececification
29.34.1 Digital Ampere Meter with CTs with selector switch per set 1950
29.34.2 Digital Volt Meter with selector switch & HRC fuse per set 2100
29.34.3 Frequency Meter Each 1200
29.34.4 Copper Bus bar strips with PVC sleeves Kg 650
29.34.5 Aluminium bus bar strips with PVC sleeves Kg 250
29.34.6 LED lamp indicator each 20049

SOR ELECTRICAL 2014/CHAPTER-29

Page 49 of 114
CHAPTER - 30
FAN
Rate
S.No Description of Item Unit
(Rs)
30.1 Supplying, erection and testing of approved make electric
Ceiling fan of double ball bearing complete with standard
down rod, canopy, hanging shackle, Aluminium blades,
without regulator, A.C. 230-250 volts including connections
with all necessary material complete of approved as required
confirming to IS :374/1979 with up to date ammendments.

30.1.1 Ceiling Fan (5 star & ISI)-1200 mm Sweep Each 2276


30.1.2 Ceiling Fan Ornamental (5 star)-1200 mm Sweep Each 2690
30.1.3 Ceiling Fan ( ISI )-1400 mm Sweep Each 2619
30.2 Supplying, erection and testing of approved make Wall
Mounting fan complete with Wall Bracket ,canopy, blades,
speed Regulator etc .A.C 230-250 volts with connections and
including raw bolt/Anchor hole fastener etc. complete finished
of approved as required.
30.2.1 300 sweep Each 2198
30.2.2 400 sweep Each 2771
30.3 Supplying, erection and testing of approved make Cabin fan
oscillating type with base, blades, guard, etc. AC 230-250
volts with connections and including raw bolt/Anchor hole
fastener etc. complete finished and as required.
30.3.1 300 sweep Each 2201
30.4 Supplying, erection and testing of approved make 'Fresh Air
Fan' AC 230-250 volts with connection and including frame
bolt/Anchor hole fasteners etc. complete finished of approved
as required.
30.4.1 150mm sweep Each 1264
30.4.2 225mm sweep Each 1368
30.4.3 300mm sweep Each 1437
30.5 Supplying and fixing of Deluxe fresh air fan with louvers (
ventilating fan ) with self closing louvers of decorative PVC
blades mounting square frame of approved make complete
with all necessary material as required
30.5.1 150mm RPM1300/1400 Each 1483
30.5.2 200mm RPM1300/1400 Each 1599
30.5.3 250mm RPM1300/1400 Each 1669
30.5.4 300mm RPM1300/1400 Each 179650

SOR ELECTRICAL 2014/CHAPTER-30

Page 50 of 114
30.6 Supplying, erecting and testing of approved make Exhaust
Fan heavy duty with mounting frame, blades AC 230-250
complete connection and including, frame bolt/ Anchor hole
fastners etc. complete finished of approved as required.
30.6.1 300mm sweep 900 RPM Each 2918
30.6.2 380mm sweep 900 RPM Each 3450
30.6.3 450mm sweep 900 RPM Each 4723
30.6.4 600mm sweep 900 RPM Each 7349
30.7 Supplying and testing of approved make Pedestal fan A.C.
230-250 volts with blades, inbuilt speed regulator, adjustable
height etc duly wired with all necessary material complete of
approved as required
30.7.1 400 mm Sweep Each 2979
30.8 Supplying and testing of approved make Air Circulator fan
A.C. 230-250 volts with blades etc duly wired with all
necessary material complete of approved as required as
mentioned below:
30.8.1 Air circulator Wall mounting
30.8.1.1 450 mm Sweep inbuilt speed regulator Each 6077
30.8.1.2 600 mm Sweep Each 7176
30.8.2 Air circulator Pedestal Adjustable height
30.8.2.1 450 mm Sweep inbuilt speed regulator Each 6768
30.8.2.2 600 mm Sweep Each 8388
30.9 supplying and replacement of cooler fan 500 mm (20") ISI
marked with all necessary material including connection
complete of approved as required Each 2073
30.10 supplying and replacement of cooler submersible water
pump complete with all necessary material including
connection of approved as required Each 581
30.11 Supplying and fixing of cooler / A.C. MS angle iron stand
including flat iron supports, including grouting in wall, if
required, welding and painting with primer and two coat of
superior quality paint complete.
Kg 8051

SOR ELECTRICAL 2014/CHAPTER-30

Page 51 of 114
CHAPTER - 31

LUMINAIRES
Rate
S.No Description of Item Unit
(Rs)
Fluorescent Tube Fitting
31.1 Supplying, fixing & testing of approved make of T- 5 lamp
channel luminaries with plastic extruded housing with
in-built electronic control gear, decorative end caps,
diffuser including necessary materials connection etc.
complete as required (without lamp)
31.1.1 T - 5 Lamp 1 X 14 watt 535
31.2 Supplying fixing and testing of T- 5 lamp Batten type Tube
fitting with epoxy white powder coated CRCA sheet steel
complete with electronic ballast (HF), rotor holders, duly
wired ( without tube rod ) fixing wall/ceiling on PVC
clamp/round plate with necessary materials complete as
required.
31.2.1 T - 5 Lamp 1 X 28 watt Each 535
31.3 Supplying, fixing & testing of approved make T- 5 lamp
channel luminary with epoxy white powder coated
CRCA sheet steel housing box type channel with
reflector cover including electronic ballast (HF), PF > 0.95,
THD <30% complete duly wired (with tube rod) as per
specification & fixing as below:
31.3.1 I) Fixing on wall/Ceiling on PVC plate Anchor fasteners
and other necessary materials including connections etc.
and as required. Each 1172
31.3.2 II) Fixing by stiff pendant arrangement with two pieces of
steel conduit 19/20 dia 16 SWG and other necessary
materials such as ball socket, wooden round block with 'J'
hook/Anchor hole fasteners fixed in Ceiling including
connection and as required for length upto 1.5 Meter
Each 1360
31.3.3 III) Fixing by pendant arrangement with two pieces of
approved metallic chain and other necessary materials
such as wooden block with 'J' hook Anchor hole fastner
fixed in Ceiling including connection as required for length
up to 1.5Metre Each 124752
T-5 Mirror Optics -Surface Mounted

SOR ELECTRICAL 2014/CHAPTER-31

Page 52 of 114
31.4 Supplying, fixing and testing of approved make surface
mounting mirror optics luminaries for single/twin 28 watt T-
5 fluorescent lamp comprising of white powder coated
CRCA sheet steel housing raw silk / navy brown / white
colour M.S. low profile flat housing complete with all
accessories i.e. electronic ballast (HF), PF > 0.95, THD
<30%, duly wired (without tube rod) and high purity
anodized aluminium reflector assembly along with cross
louvers as per specification and fixing as below.
31.4.1 Fixing on wall/Ceiling on wooden round block with 'J'
hook/Anchor hole fastener fixed in Ceiling and other
necessary materials including connections etc. and as
required.
31.4.1.1 1x28w 2463
31.4.1.2 2x28w 3584
31.4.2 Fixing by stiff pendant arrangement with two pieces of
steel conduit 19/20mm dia 16 SWG and other necessary
materials such as ball socket, T.W. block with 'J' hook/
Anchor hole fastener fixed in Ceiling including connections
and as required for length up to 1.5 Meter.
31.4.2.1 1x28w 2651
31.4.2.2 2x28w 3772
T-5 Mirror Optics (recessed/concealed)
31.5 Supplying, fixing and testing of approved make recess
mounting mirror optics luminaries for single/twin 28 watt
fluorescent lamp comprising of white powder coated CRCA
sheet steel housing raw silk / navy brown / white colour
M.S. low profile flat housing complete with all accessories
i.e.electronic ballast (HF), PF > 0.95, THD <30%, duly
wired (without tube rod) and high purity anodized
aluminium reflector assembly along with cross louvers as
per specification and fixing .
31.5.1 1x28w 2302
31.5.2 2x28w 3584
BULK HEAD
31.6 Supplying, fixing and testing of approved make bulk head
luminary consisting of pressure die aluminium housing
lamp holder, prismatic glass cover, rubber gasket and wire
guard, deluxe type, including fixing on wall as required,
with necessary material complete Fitting suitable for
Retrofit 10W CFL / GLS Lamp Each 594
31.7 Supplying, fixing and testing of approved make modular
integral step / skirt LED light suitable for 3 module box and
plate including fixing on wall as required, with necessary
material complete Each 66853
Street Lights

SOR ELECTRICAL 2014/CHAPTER-31

Page 53 of 114
H.P. SV / MH Fitting
31.8 Supplying, fixing & testing of approved make H.P. SV /
MH fitting consisting of single piece sheet aluminium alloy
deep drawn housing highly polished anodized aluminium
reflector clear acrylic cover, gasket and equipped with
accessories; such as ballast, condensor, ignitor, skirted
ceramic lamp holder (without lamp) suitable for end
mounting duly wired, including fixing with 32/38 mm dia
G.I. pipe Light 'A' class of required length upto 2 Meter for
mounting on wall/existing pole/on existing D bracket
including bending the pipe to required shape and
connections including all materials as required
31.8.1 70 watt Each 4753
31.8.2 150 watt Each 6014
31.8.3 250 watt Each 7703
31.9 Supplying ,fixing and testing of approved make of
H.PSV/MH side road lighting/ main road lighting lantern
consisting of single piece cast aluminium housing
complete with all accessories suitable for tubular 70W
/15OW /250W/HPSV / HPMH lamp pot type high purity
electromechanically brightened anodized aluminium
reflector/ with ripples embossing above the lamp, lamp
holder, clear toughend glass cover & 3/5 stainless steel
toggle, ignitor & ballast, condensor (without lamp) i/c fixing
with 32/38 mm dia G.I. pipe Light 'A' class of required
length upto 2 mtr. for mounting on wall/existing pole/on
existing "D" bracket i/c bending the pipe to required shape
and connections, i/c all material as required & suitable for:
31.9.1 70 Watt Each 5433
31.9.2 150 Watt Each 7217
31.9.3 250 Watt Each 9220
31.9.4 400 Watt Each 10998
Flood Lighting
31.10 Supplying, fixing & testing of approved make of integral
type SV / MH compact flood light fitting consisting of cast
aluminium housing complete with all accessories such as
aluminium reflector, lamp holder heat resisting toughned
clear glass cover and mounting bracket with aiming disc,
including fixing & connections as required position with all
necessary materials required, suitable for single / double
ended lamp (without lamp)
31.10.1 70 Watt S.V./ M.H. Lamp ( Tubular Lamp) Each 5664
31.10.2 70 Watt metal halide Lamp (Double ended) Each 5632
31.10.3 150 Watt S.V./ M.H. Lamp ( Tubular Lamp) Each 7269
31.10.4 150 Watt metal halide Lamp (Double ended) Each 683054

SOR ELECTRICAL 2014/CHAPTER-31

Page 54 of 114
31.10.5 250 Watt S.V./ M.H. Lamp ( Tubular Lamp) Each 9053
31.10.6 400 Watt S.V./ M.H. Lamp ( Tubular Lamp) Each 10496
31.11 Supplying, fixing & testing of approved make H.D.
asymmetrical / symmetrical beam flood light fitting suitable
for tubular single lamp consisting of cast aluminium
housing aluminium faceted reflector assly toughned glass
cover, mounting bracket and aiming disc, seperate control
gear box required for HPSV/M.H. Lamp (without lamp)
including fixing & connection as required in position with all
necessary material required
31.11.1 1 X 250 watt S.V. Lamp/Metal Halide with control gear
box. Each 9053
31.11.2 1 X 400 Watt S.V. Lamp/metal Halide with control gear
box Each 11040
31.11.3 1 X 400 Watt S.V. Lamp/metal Halide with control gear
box symmetrical Each 12567
31.11.4 2 X 400 Watt S.V. Lamp/metal Halide with control gear
box Each 22410
POST TOP LANTERNS
31.12 Supplying, fixing & testing of approved make of integral
type decorative post top lantern consisting of aluminium
canopy opal / clear acrylic bottom cover and cast
aluminium spigot complete with all accessories and control
gear box (without lamp) including fixing on gate pillers/
existing G.I. pipe, pole with connection and all required
material on required size of G.I. pipe, suitable for -
31.12.1 1 X 18 Watt CFL (Opal) Each 3145
31.12.2 1 X 18 Watt CFL (Clear) Each 4003
31.12.3 2 X 18 Watt CFL (Opal) Each 5666
31.12.4 2 X 18 Watt CFL (Clear) Each 6744
31.12.5 For 1 x 45W Retrofit CFL (Without control gear) Each 4652
31.12.6 LED 40 Watt Each
31.13 Supplying, fixing & testing of approved make globe type
polycarbonate post top lantern, consisting of cast
aluminium spigot complete with all accessories, lamp
holder, ( without lamp) including fixing on gate
Pillers/exiting G.I. pipe, pole with connection & all required
materials on existing required size of G.I. pipe, suitable
CFL for mentioned below sizes :-
31.13.1 200 mm ( 8" ) dia. 1205
31.13.2 250 mm ( 10" ) dia. 1596
31.13.3 300 mm ( 12" ) dia. 225055

SOR ELECTRICAL 2014/CHAPTER-31

Page 55 of 114
31.14 Supplying, fixing & testing of approved make of integral
type bollard cyclindrical shape housing cast aluminium
dome shape top cover fixed with cylindrical shape poly
carbonate cover having base plate with holes for direct
mounting complete with all accessories and control gear
box (without lamp) including preparatoion of foundation
including fixing with connection and all required material as
required.
31.14.1 2 X 18 Watt CFL Height > 700mm 9478
31.14.2 LED 9 Watt Height > 700mm 9214
31.14.3 LED 9 Watt Mashroom shape Height > 600mm 9702
LOW WATT MOUNTINGS
31.15 Supplying, fixing & testing of approved make of low watt
surface mounting luminaires, made of white powder
coated CRCA sheet steel housing with aluminium mirror
reflector complete with electronic ballast (HF), PF > 0.95,
THD <30% , wired upto terminal block on a detachable
tray including fixing on wall/ Ceiling on wooden round block
including wiring & connection as required and suitable for
CFL as follow :- (without lamp)
31.15.1 2 nos. 11 watt CFL aluminium mirror reflector Each 1756
31.15.2 2 no. 18 watt CFL aluminium darklight reflector( P 5
Louvers ) Each 2492
31.15.3 2 Nos 36 watt CFL (597 mm X 597 mm ) aluminium
darklight reflector( P 5 Louvers ) Each 4438
31.15.4 3 Nos 36 watt CFL (597 mm X 597 mm ) aluminium
darklight reflector( P 5 Louvers ) Each 4628
31.15.5 2 Nos 36W CFL Clean room clear acrylic cover Each 7629
31.16 Supplying, fixing & testing of approved make of low watt
recessed mounting luminary made of CRCA sheet steel
housing with false Ceiling clips, finished in stove enameled
white inside/outside fitted with high purity anodized
aluminium mirror reflector and complete with electronic
ballast (HF), PF > 0.95, THD < 30%, including fixing with
recessed mounting arrangement with necessary materials
connection etc. complete as required and suitable for
twin/three CFL as follows :-(without lamp)
31.16.1 2 nos. 18 watt CFL aluminium mirror reflector Each 1376
31.16.2 2 nos. 36 watt CFL aluminium reflector Each 2777
31.16.3 2 Nos 36 watt CFL (597 mm X 597 mm ) aluminium
darklight reflector( P 5 Louvers ) Each 3964
31.16.4 3 Nos 36 watt CFL (597 mm X 597 mm ) aluminium
darklight reflector( P 5 Louvers ) Each 4486
31.16.5 2 Nos 36W CFL Clean room clear acrylic cover Each 705956
31.17 Supplying, fixing & testing of approved make low watt

SOR ELECTRICAL 2014/CHAPTER-31

Page 56 of 114
surface mounting CFL down lighter luminaire with white
powder coated CRCA aluminium cover & opal acrylic
cover, wired with electronic ballast (HF), PF > 0.9
including necessary materials connection etc. complete as
required for mentioned below :- (without lamp)
31.17.1 CFL 2 X 18 watt Each 2444
31.18 Supplying, fixing & testing of approved make low watt
recessed mounting horizontal CFL down lighter
luminaire with white powder coated CRCA ring including
spring loaded adjustable mounting bracket & Satin brite -
Matt finish aluminium reflector, wired with suitable
electronic ballast (HF), PF > 0.9, including necessary
materials connection etc. complete as required for
mentioned below :- (without lamp)
31.18.1 CFL 1 X 18 watt Each 1067
31.18.2 CFL 2 X 18 watt Each 1352
31.19 Supplying, fixing & testing of approved make of low watt
CFL roadway / street light luminary with epoxy powder
coated sheet aluminium / steel housing with epoxy white
powder coated CRCA sheet steel gear tray, electronic
ballast (HF), PF > 0.95, THD <30%, clear acrylic cover
with necessary materials connection including mounting
with GI pipe Light 'A' class 25/32mm OD, clamps on
existing wall / pole etc. complete as required (without
lamp)
31.19.1 CFL 1 X 18 watt Each 1704
31.19.1 CFL 1 X 36 watt Each 1941
31.20 Supplying, fixing & testing of approved make CFL street
light fitting consisting of metallic sheet aluminium alloy
housing, highly polished aluminium reflector clear acrylic
cover, gasket and equipped with accessories; such as
lamp holder (without lamp) suitable for end mounting duly
wired, including fixing with 32/38 mm dia G.I. pipe LIght 'A'
class of required length upto 2 Meter for mounting on
wall/existing pole/on existing D bracket including bending
the pipe to required shape and connections including all
materials as required
31.20.1 Up to 85 watt CFL Each 2253
31.21 Supplying, fixing & testing of approved make of low watt T-
5 Lamp roadway / street light luminary with epoxy
powder coated sheet steel / Aluminum housing with epoxy
white powder coated CRCA sheet steel gear tray ,
electronic ballast (HF), PF > 0.95, THD <30% , clear
acrylic cover with necessary materials connection including
mounting with GI pipe Light 'A' class 32/38 mm dia, clamps
on existing wall / pole etc. complete as required (without
lamp)
32.21.1 T - 5 Lamp 2 X 24 watt 3535
31.21.2 T - 5 Lamp 4 X 24 watt 752357

SOR ELECTRICAL 2014/CHAPTER-31

Page 57 of 114
LED LIGHTING
31.22 Supply and fixing Led tube rod comprising of LED tube
with non integral / integral driver, 6500K color temp having
40000 burning hrs life with minimum @ L 70, system
lumen output should be minimum with efficacy > 80 lm/W.
LED driver PF 0.95 & THD < 20%. The colour rendering
index of LED light should be more than 70. Submission LM
80-08 Form LED Source Manufacturer & LM79-08 /
IS16106 from NABL approved lab. Manufacturer
mandatory i/c connection wire, testing etc. to complete the
job. 2 Yrs Guarantee certificate from manufacturer.
31.22.1 1 X 5/8W Integral Tube fitting complete 1620
31.22.2 1 X 18/20/22W, Integral 2208
31.22.3 1 X 18/20/22W, Non Integral with driver 3067
31.22.4 LED Retrofit tube only 18/20/22W 3 - 6K without box
suitable for replacing existing 36/40W FTL 2515
31.23 Supply & fixing Mounting rail / Batten made of CRCA
powder coated with suitable lamp holding brackets for LED
Tube rod 1200mm Single on wall / ceiling including
connection testing etc complete as required. 669
31.24 Supply and fixing of recessed mounting type Led light
fixture, LED of 1 to 3 W each assembled on single
MCPCB, having color temp 6500K & having 50000
burning hrs life with minimum @ L 70, system lumen
output should be minimum with efficacy>80lm/W. LED
driver, PF 0.95 & THD < 20%. The colour rendering index
of LED light should be more than 70. Housing made of
CRCA with glare free diffused polycarbonate cover.
Submission LM 80-08 Form LED Source Manufacturer &
LM79-08 / IS16106 from NABL approved lab.
Manufacturer manadatory i/c connection wire, testing etc.
to complete the job. 2 Yrs Guarantee certificate from
manufacturer.
31.24.1 Led luminiare 1' X 1', 24W , 4-6.5k Each 4753
31.24.2 Led luminiare 2' X 2', 36W, 4-6.5K Each 9811
31.24.3 Led luminiare 2' X 2', 45W, 4-6.5K Each 10226
31.25 Supply and fixing of surface mounting type Led light
fixture, LED of 1 to 3 W each assembled on single
MCPCB, having color temp 6500K & having 50000
burning hrs life with minimum @ L 70, system lumen
output should be minimum with efficacy>80lm/W. LED
driver, PF 0.95 & THD < 20%. The colour rendering index
of LED light should be more than 70. Housing made of
CRCA with glare free diffused polycarbonate cover.
Submission LM 80-08 Form LED Source Manufacturer &
LM79-08 / IS16106 from NABL approved lab.
Manufacturer manadatory. i/c connection wire, testing etc.
to complete the job. 2 Yrs Guarantee certificate from
manufacturer.58

SOR ELECTRICAL 2014/CHAPTER-31


Page 58 of 114
31.25.1 Led luminiare 1' X 1', 24W , 4-6.5k 4753
31.25.2 Led luminiare 2' X 2', 36W , 4-6.5k 11126
31.25.3 Led luminiare 2' X 2', 45W , 4-6.5k 10251
31.26 Supplying and fixing surface mounting LED down lighter, LED
of 1 to 3 W each assembled on single MCPCB, having color
temp 6500K & having 50000 burning hrs life with minimum
@ L 70, system lumen output should be minimum with
efficacy>80lm/W. LED driver PF 0.95 & THD < 20%. The
colour rendering index of LED light should be more than 70.
Housing made of CRCA powder coated frame with glare free
diffused polycarbonate cover. Submission LM 80-08 Form
LED Source Manufacturer & LM79-08 / IS16106 from NABL
approved lab. Manufacturer mandatory. i/c connection wire,
testing etc. to complete the job. 2 Yrs Guarantee certificate
from manufacturer.
31.26.1 7 W/8 W, 100/150mm 2348
31.26.2 15 W , 180/200mm 3822
31.26.3 30 W , 300mm 6955
31.27 Supplying and fixing recessed mounting LED down lighter,
LED of 1 to 3 W each assembled on single MCPCB, having
color temp 6500K & having 50000 burning hrs life with
minimum @ L 70, system lumen output should be minimum
with efficacy>80lm/W. LED driver PF 0.95 & THD < 20%. The
colour rendering index of LED light should be more than 70.
Housing made of CRCA powder coated frame with glare free
diffused polycarbonate cover. Submission LM 80-08 Form
LED Source Manufacturer & LM79-08 / IS16106 from NABL
approved lab. Manufacturer manadatory. i/c connection wire,
testing etc. to complete the job. 2 Yrs Guarantee certificate
from manufacturer.
31.27.1 8 W , 100/150mm 1657
31.27.2 12 W, 180/200mm 2348
31.27.3 15 W, 180/200mm 2763
31.28 Supplying and fixing integral post top lantern LED fitting
comprises of copper dust finish cast aluminium spigot and
spun aluminium canopy fixed with opal polycarbonate, pipe
arrangement for vertical mounting, open construction driver
and accessories are wired up to terminal block. LED of 1 to 3
W each assembled on single MCPCB, having color temp
6500K & having 50000 burning hrs life with minimum @ L
70, system lumen output should be minimum with
efficacy>80lm/W. LED driver PF 0.95 & surge protection 2KV.
The colour rendering index of LED light should be more than
70. Submission LM 80-08 Form LED Source Manufacturer &
LM79-08 / IS16106 from NABL approved lab. Manufacturer
manadatory. i/c connection wire, testing etc. to complete the
job. 2 Yrs Guarantee certificate from manufacturer.59
31.28.1 40 W LED 16654
31.29 Supplying and fixing street light with high power LED of 1
to 3 W each assembled on single MCPCB, system lumens

SOR ELECTRICAL 2014/CHAPTER-31

Page 59 of 114
output with efficacy>90 lm/W. luminiare having color temp
6500K & 50000 burning hrs life with minimum @ L 70,
The colour rendering index of LED light should be more
than 70. Luminiare comprises of driver, PF 0.95 & surge
protection 3KV. Housing made of pressure die cast
aluminium with heat resistant flat glass / Lens type, IP65
protection. Submission LM 80-08 Form LED Source
Manufacturer & LM79-08 / IS16106 from NABL approved
lab. Manufacturer manadatory i/c 50mm.dia G.I. Pipe
bracket upto 2 mtr. long in required angle/shape,
connection lead, testing etc to complete the job. 2 Yrs
Guarantee certificate from manufacturer.
31.29.1 24W / 25W 9138
31.29.2 40W / 48W 18634
31.29.3 60W, 22584
31.29.4 90W, 23923
31.29.5 120W, 35585
31.29.6 150W, 44283
31.30 Supplying and fixing flood light with high power LED of 1 to
3 W each assembled on single MCPCB, system lumens
output with efficacy>90 lm/W. luminiare having color temp
6500K & 50000 burning hrs life with minimum @ L 70,
The colour rendering index of LED light should be more
than 70. Luminiare comprises of driver, PF 0.95 & surge
protection 3KV. Housing made of pressure die cast
aluminium with heat resistant flat glass, IP65 protection.
Submission LM 80-08 Form LED Source Manufacturer &
LM79-08 / IS16106 from NABL approved lab.
Manufacturer manadatory i/c connection lead, testing etc
to complete the job. 2 Yrs Guarantee certificate from
manufacturer.
31.30.1 10W 4628
31.30.2 30W 10184
31.30.3 60W, 24048
31.30.4 90W, 25378
31.30.5 120W, 25378
31.30.6 150W, 34257
31.31 Supply, Installation testing and commissioning of Red
colour Aviation light LED integral type comprising of
Aluminium powder coated housing with polycarbonate
enclosure IP 65 on existing pipe/ support including
connection, testing etc. as required. 2 Yrs Guarantee
certificate from manufacturer. :-
31.31.1 180 LED Each 6053
31.31.2 300 LED Each 846560

SOR ELECTRICAL 2014/CHAPTER-31

Page 60 of 114
CHAPTER - 32

MISCELLANEOUS
Rate
S.No Description of Item Unit
(Rs)
32.1 Fixing of Fluorescent Tube fitting on wall /ceiling on wooden
round block with anchor fastener /J hook & necessary
material including connection with 3 core flexible wire etc.
complete as required.
Each 67
32.2 Fixing of Fluorescent Tube fitting with pendant arrangement
of two pieces of approved metallic chain with necessary
material including connection with 3 core flexible wire etc.
complete as required.
32.2.1 For pendent length up to 1.5 Metre Each 242
32.2.2 Add additional pendent length in excess of 1.5 Metre Metre 128
32.3 Fixing of Fluorescent Tube fitting with stiff pendant
arrangement of two pieces of steel conduit and with anchor
fastener /J hook & other necessary material including
connection with 3 core flexible wire etc. complete as required.
32.3.1 For pendent length up to 1.5 Metre Each 383
32.3.2 Add additional pendent length in excess of 1.5 Metre Metre 227
32.4 Fixing of Fluorescent Tube recessed / concealed mounting
Fitting in existing recesses with necessary material including
connection with 3 core flexible wire etc. complete as required. Each 107
32.5 Providing and fixing circular/Hexagonal cast iron or M.S.sheet
box for ceiling fan clamp of internal dia 140mm, 73mm height,
top lid of 1.5mm thick M.S. sheet with its top surface hacked
for proper bonding, top lid shall be screwed into the cast
iron/M.S. sheet box by mean of 3.3mm dia. round headed
screws, one lock at the corners. Clamp shall be made of
12mm dia M.S. bar bent to shape as per standard drawing.
Each 140
32.6 Supplying and fixing fan clamps of 12 mm dia steel bar as per
specification complete :-
32.6.1 For stone slab roof "J" Type hook Each 60
32.6.2 For R.C.C. Slabs / Beams Each 38
32.6.3 For existing old R.C.C. Slabs / Beams Each 95
32.7 Supplying and fixing fan clamps with hook on existing T.W.
beam/ trusses with required size flat iron etc.as per
specification complete :- Each 8161

SOR ELECTRICAL 2014/CHAPTER-32

Page 61 of 114
32.8 Erection of ceiling in in position with regulator on existing
switch board including wiring testing etc. with necessary
material complete as required. Each 95
32.9 Fixing of fan Regulator on existing switch board in position
with necessary material connection etc.complete as required. Each 23
32.10 Erection of exhaust fan on existing hole / wall bracket
fan/cabin fan in position with required PVC cable, rawl bolts
etc. complete including connections and making wall surface
good. Each 124
32.11 Supplying and fixing down rod of MS pipe for ceiling fan
including threading, painting, making holes etc. as required
complete :- metre 114
32.12 Numbering of ceiling fans or fittings with approved paint
including all labour material etc. complete as required :-
32.12.1 Lettering up to 7 cm height Each 3
32.12.2 Lettering above 7 cm but up to 15 cm height Each 5
32.13 Providing and fixing wooden board of suitable size (maximum
12" X 18" ) for fixing of house service Metre with necessary
materials and connection testing etc. complete as per
specification :
32.13.1 Single phase Meter Each 101
32.13.2 Three phase Meter Each 133
32.14 Shifting of Window Air Conditioning unit 1.0TR / 1.5 TR / 2 TR
capacity excluding facia and cutting, welding work complete
as required. Each 800
32.15 Shifting, Installation, testing & commissioning of Split Air
Conditioning unit 1.0TR / 1.5 TR / 2 TR capacity including
indoor/ out door unit complete as required Each 2000
32.16 Supply, Installation, testing & commissioning suction/
discharge copper pipe line in split Air Conditioning unit 1.0
/1.5 TR/2 TR /3 TR capacity including brazing, nitride rubber
insulation, etc complete as required.
32.16.1 Copper tube 1/4" P. Mt. 190
32.16.2 Copper tube 1/2" P. Mt. 250
32.16.3 Copper tube 3/8" P. Mt. 460
32.16.4 Copper tube 5/8" P. Mt. 400
32.17 Chemical Servicing of Window /Split Air Conditioning unit
1TR/ 1.5 TR/2 TR/3TR capacity including cleaning of cooling
& condensing units,filters,grills etc & all other parts oiling &
greasing of fan motor, testing of A.C unit etc. Each 800
32.18 Gas ( F 22 ) charging of Window /Split Air Conditioning unit
including flushing of cooling & condensing units with nitrogen
gas & rectification of leakage, replacement of filter, flair nut
etc. if any. P. Ton 1000
32.19 Gas charging of Refrigerator upto 300 Ltr capacity including
flushing of cooling & condensing units with nitrogen gas &
rectification of leakage, replacement of filter, etc. if any. Each 100062

SOR ELECTRICAL 2014/CHAPTER-32

Page 62 of 114
32.20 Providing, replacement & connection thermostat switch of
required size & capacity for Refrigerator upto 300 Ltr capacity
including all required material to complete the job. Each 450
32.21 Providing, replacement & connection starting relay of required
size & capacity for Refrigerator upto 300 Ltr capacity
including all required material to complete the job. Each 450
32.22 Providing & fixing of wood wool / Khas pads of normal size
desert / room cooler panels set of 3 Nos including fixing
wiremesh on pads. Each 105
32.23 Servicing & overhauling of cooler fan motor, pump including
replacemnt of distribution & delivery pipes, PVC elbows,
painting etc. as reqd. complete with necessary material &
labour Each 99
32.24 Rewinding of fans by copper enameled wire of suitable
gauge including all required material, insulation,
varnishing,connection leads,oiling .greasing etc complete
with testing including dismantling & refitting of fan at
site.Scrap old material is not returnable to the department.
32.24.1 Ceiling Fan 1400 mm sweep old model /Exhaust Fan 450 mm
sweep Each 546
32.24.2 Ceiling Fan 1400 mm sweep new model / Exhaust Fan 380
mm sweep Each 338
32.24.3 Ceiling Fan 1200 mm sweep old model / Cooler Fan 500 mm
( 20" )sweep Each 417
32.24.4 Ceiling Fan 1200 mm sweep new model / Exhaust Fan 300
mm sweep Each 298
32.24.5 Fresh Air Fan up to 300 mm sweep / Wall Bracket /Cabin Fan
400 mm sweep Each 211
32.25 Cleaning, overhauling, servicing of ceiling / Exhaust / Wall
bracket fan by applying grease & oil, including testing with
mounting / Hanging arrangement including replacement of
safety pins, check nuts,lock nut,nut bolts etc. making perfect
alignment & refitting at site as required.
Each 102
32.26 Supply and fixing of GI sheet 22 SWG Exhaust fan cowl
including grouting bolt, nut, & finishing etc on existing hole to
complete the job. Sq.Mt. 950
32.27 Supply and fixing of GI sheet 24 SWG Exhaust fan Louvers
including grouting bolt, nut, & finishing etc on existing hole to
complete the job as mentioned below :-
32.27.1 Sweep 300mm Each 750
32.27.2 Sweep 380mm Each 1000
32.27.3 Sweep 450mm Each 1500
32.27.4 Sweep 600mm Each 200063

SOR ELECTRICAL 2014/CHAPTER-32

Page 63 of 114
CHAPTER -33
LABOUR RATES FOR WIRING
Rate
S.No Description of Item Unit
(Rs)
33.1 Labour rate for point wiring a Light / Fan / Twin control light /
Socket out let on separate board / Call bell Point in (open)
surface rigid steel conduit system. 137
Each
33.2 Labour rate for point wiring a Light / Fan / Twin control light /
Socket out let on separate board / Call bell Point in
recessed/concealed rigid steel conduit system. Each 179
33.3 Labour rate for point wiring a Light / Fan / Twin control light /
Socket out let on separate board / Call bell Point in (open)
surface rigid PVC conduit / Casing- n- capping system. Each 98
33.4 Labour rate for point wiring a Light / Fan / Twin control light /
Socket out let on separate board / Call bell Point in
recessed/concealed rigid PVC conduit system. Each 143
33.5 Labour rate for point wiring a Power Point in surface rigid
steel / PVC conduit / Casing-N-Capping system including
labour for fixing earth continuity conductor . Each 208
33.6 Labour rate for point wiring a Power Point in recessed /
concealed rigid steel / PVC conduit system including labour
for fixing earth continuity conductor . Each 251
33.7 Labour rate for fixing rigid steel / PVC conduit in surface
/concealed conduit wiring system, as per specification .
33.7.1 20 mm Conduit Metre 13
33.7.2 25 mm & 32 mm Conduit Metre 15
33.7.3 40 mm & 50 mm Conduit Metre 25
33.8 Labour rate for rewiring a Light / Fan / Twin control light /
Socket out let on separate board / Call bell Point in rigid
steel / rigid PVC non metallic conduit / PVC Casing-N-
Caping in (open) surface conduit wiring system.
each 164
33.9 Labour rate for rewiring a Light / Fan / Twin control light /
Socket out let on separate board / Call bell Point in rigid
steel / rigid PVC non metallic conduit in recessed/concealed
conduit wiring system. each 174
33.10 Labour rate for fixing rigid PVC conduit as per specification
in recessed/concealed conduit wiring system.
33.10.1 20 mm Conduit Each 19
33.10.2 25 mm & 32 mm Conduit Each 23
33.10.3 40 mm & 50 mm Conduit Each 3664

SOR ELECTRICAL 2014/CHAPTER-33

Page 64 of 114
33.11 Labour rate for drawing cables in existing rigid steel / PVC
conduit / Casing-N-Capping (surface or
recessed/concealed)
33.11.1 "A" 2 Wires --
33.11.1.1 2.5 sq mm / 4 sq mm / 6 sq mm metre 29
33.11.1.2 10 sq mm / 16 sq mm / 25 sq mm metre 32
33.11.1.3 35 sq mm metre 33
33.11.2 "B" 3 Wires & 4 Wires
33.11.2.1 2.5 sq mm / 4 sq mm / 6 sq mm metre 31
33.11.2.2 10 sq mm / 16 sq mm / 25 sq mm metre 34
33.11.2.3 35 sq mm metre 34
NOTE
1. The socket outlet point on the same board shall be treated as 1/2 point in the
respective system of wiring
2. Labour rate for point wiring are inclusive of labour for fitting all accessories and
fitting such as conduit, switch, Ceiling rose sockets, brass lamp holders etc. as
required
3. Labour rate for each circuit shall be same as one point in respective system of
wiring .65

SOR ELECTRICAL 2014/CHAPTER-33

Page 65 of 114
CHAPTER- 34

PAINTING
Description of Item Rate
S.No Unit
(Rs)
34.1 Painting of ceilling fan including making surface clean and
spray painting of fan Motor, blades, etc. with two coat of
required shade complete with material and labour including
dismantling and erection, preparation of surface
Each 218
34.2 Painting of desert cooler including making surface even,
prima paint coat from inside & outside and spray painting of
body, fan Motor, blades, etc. with two coat of required
shade complete with material and labour.
Each 540
34.3 Painting of water cooler including scraping of old paint
making surface even, prima paint coat and spray painting of
body, etc. with two coat of required shade complete with
material and labour.
Each 649
34.4 PAINTING OF POLES :-
34.4.1 Removing of old paint from steel and other metallic surface per sq
and making surface even. Metre 18
34.4.2 Primer coat over new steel and other metallic surface with
red oxide/ zinc chromide paint complete with supply of per sq
material labour etc. including preparation of surface. Metre 47
34.4.3 Final coat with aluminium paint, brushing complete including per sq
material and labour. Metre66 59

SOR ELECTRICAL 2014/CHAPTER-34

Page 66 of 114
CHAPTER - 35

DISMANTLING OF CIVIL & ELECTRICAL WORKS

Rate
S.No Description of Item Unit
(Rs)
35.1 Dismantling of existing light / Fan / Bell / Socket out let point
on separate board / Wiring and circuit with insulated wire in
cassing / conduit / Batten complete with fitting and
accessories per point 17
35.2 Making the site clear of the dismentalled installation by
refilling the hole with cement mortor & finished with paint
gitties and replacing to match the colour of wall / ceilling. per point 30
35.3 Dismetalling of existing socket outlet point on same board in
any system of wiring per point 11
35.4 Dismentalling the existing armoured / unarmoured cable or
2/3/4 wires of submain, main , in any system of wiring per
including recoiling. meter 11
35.5 Dismentalling of existing undreground cable safely with its
accessories and refilling the trench to ground level including per
recoiling of dismentalled cable. meter 34
35.6 Dismentalling of D.F. Board, D.P. Switch, T.P. &T.P.N. Switch
or D.B. of any size complete with board or angle / flat iron
frame and making site clear including the refilling hole &
repainting to match colour of wall. Each 38
35.7 Dismentalling of D.F. Board , D.P.Switch , T.P. & T.P.N.
Switch or D.B. of any size only Each 15
35.8 Dismentalling the existing ceiling / exhaust / cabine fan with
complete accessories and making the site clear. Each 36
35.9 Dismentalling of existing steel pole, R.S.Joist, girder with
bracket clamps insulator or stay from the cement concrete
foundation and making the site clear by refilling the pit to
ground level i/c transportation to required destination within
township. Each 1066
35.10 Dismentalling of existing overhead ACSR, AAAC, GI ,
conductor and making the site clear i/c transportation to per
required destination within township. meter 4
35.11 Dismentalling of existing water tight flourescent tube fitting /
M.V. Lamp fitting with making the site clear. Each 30
35.12 Dismentalling of existing water tight fitting S.V/M.H/L.E.D
Lamp fitting with extension bracket, clamp from pole or wall
with making the site clear. Each 3967
35.13 Dismentalling of existing geyser or storage type water heater
and making the site good by colour wash etc.as required. Each 61

SOR ELECTRICAL 2014/CHAPTER-35

Page 67 of 114
35.14 Providing recess in brick wall suitable for erection of exhaust
fan up to 600mm sweep complete with grouting of nut bolts,
plastering and colour wash to match the colour of wall.
35.14.1 For wall thickness up to 9" Each 498
35.14.2 For wall thickness up to 15" Each 778
35.14.3 For the stone wall thickness up to 15" Each 907

CHAPTER - 36

CIVIL WORKS
Rate
S.No Description of Item Unit
(Rs)

Items regarding civil works shall be taken and


Note: executed on the basis of rates of current respective
civil S.O.R.

68

SOR ELECTRICAL 2014/CHAPTER-35-36

Page 68 of 114
CHAPTER - 37

EARTHING , LOOP EARTHING,LIGHTNING CONDUCTOR


Description of Item Rate
S.No Unit
(Rs)
37.1 Earthing with G.I. Earth pipe 4.5 Metre long and 40 mm dia
with masonary enclosure in cement mortor, cover plate
having locking arrangement on the top etc.(but without
charcoal or coke and salt) complete as required.
Each 3017
37.2 Add Extra for using salt and charcoal / coke for pipe earth
electrode as required including excavation & refilling.
37.2.1 Excavation 2.5 cum by manual labour Each 1572
37.2.2 Excavation by making hole with Auger Each 1068
37.3 Earthing with G.I. Earth plate 600mm X 600mm X 6mm
thick including accessories and providing masonary
encloser in cement mortor, cover plate having locking
arrangement on the top and G.I. watering pipe 20mm dia
2.7 Metre long etc. (but without charcoal or coke and salt )
complete as required. Each 2951
37.4 Earthing with Copper Earth plate 600mm X 600mm X 3mm
thick including accessories and providing masonary
encloser in cement mortor, cover plate having locking
arrangement on the top and G.I. watering pipe 20mm dia
2.7 Metre long etc. (but without charcoal or coke and salt)
complete as required. Each 8013
37.5.1 Add Extra for using salt and charcoal / coke for G.I. Plate or
Copper plate earth electrode as required including
excavation & refilling. Each 1841
37.5.2 Add Extra for using salt and charcoal / coke for G.I. Plate or
Copper plate earth electrode as required including
excavation in hard rock and refilling the pit with black soil. Each 3353
37.6 Supplying and laying 8 SWG (4 mm) copper wire at 0.5
Metre below ground level as conductor earth electrode
including soldering etc. as required. metre 85
37.7 Supplying and laying 6SWG (5.6mm) G.I. wire at 0.5 Metre
below ground level as conductor earth electrode including
soldering etc. as required. metre 23
37.8 Supplying and laying 25mm X 5mm G.I. strip at 0.5 Metre
below ground level as strip earth electrode including
soldering etc. as required. metre 9569

SOR ELECTRICAL 2014/CHAPTER-37

Page 69 of 114
37.9 Supplying and laying 25mm X 6mm G.I. strip at 0.5 Metre
below ground level as strip earth electrode including
soldering etc. as required. metre 113
37.10 Providing & fixing 25mm X 5mm copper strip in 40mm dia
G.I.pipe (B class) from earth electrode as required. metre 1043
37.11 Providing & fixing 25mm X 5mm G.I.strip in 40mm dia G.I.
Pipe (B class) from earth electrode as required. metre 423
37.12 Providing and laying earth connections from earth electrode
with 4.00 mm dia G.I. wire in 15mm dia G.I. Pipe (B class)
from earth electrode as required. metre 149
37.13 Providing and laying earth connections from earth electrode
with 4.00 mm dia copper wire in 15mm dia G.I. Pipe (B
class) from earth electrode as required. metre 204
37.14 Providing & fixing 25mm X 5mm copper strip on surface or
recessed for connection etc. as required. metre 808
37.15 Providing and fixing 25mm X 4mm G.I. strip on surface or in
recessed/concealed for connection etc. as required. metre 123
37.16 Providing and fixing 6 SWG (5.6mm) G.I. wire on surface or
in recessed/concealed for loop earthing as required. metre 19
37.17 Providing and fixing 4.00mm copper wire on surface or in
recessed/concealed for loop earthing as required. metre 86
37.18 Supplying and laying 50mm X 6mm G.I. strip at 0.5 metre
below ground level / surface as strip earth electrode
including jointing etc. as required. metre 95
LIGHTNING CONDUCTOR
37.19 Providing and fixing of lightning conductor finial made of
25mm dia 300mm long copper tube having single prong at
top with 85 mm dia 3 mm thick copper base plate including
holes complete as required. Each 2482
37.20 Providing and fixing of lightning conductor finial made of
25mm dia 300mm long G.I. tube having single prong at top
with 85 mm dia 6 mm thick G.I. base plate including holes
complete as required.
Each 1222
37.21 Fixing of lightning conductor finial made of 25mm dia
300mm long copper tube / G.I. tube having single prong at
top with base plate etc complete as required. Each 281
37.22 Rivetting / Sweating and soldering of copper / G.I. Tape
(with another copper / G.I. Tape, base of finial or any other
metallic object ) as required. Each 114
37.23 Providing and fixing copper tape 20mm X 3mm thick on
parapet and surface of wall of lightening conductor as
required ( for Horizontal runs ) metre 36870

SOR ELECTRICAL 2014/CHAPTER-37

Page 70 of 114
37.24 Providing and fixing copper tape 20mm X 3mm thick on
parapet and surface of wall of lightening conductor as
required ( for Vertical runs ) metre 411
37.25 Providing and fixing G.I. tape 20mm X 3mm thick on
parapet and surface of wall of lightening conductor as
required ( for Horizontal runs ) metre 71
37.26 Providing and fixing G.I. tape 20mm X 3mm thick on
parapet and surface of wall of lightening conductor as
required ( for Vertical runs ) metre 114
37.27 Fixing of copper / G.I. Tape 20mm X 3mm thick on parapet
and surface of wall for lightening conductor as required ( for
Horizontal runs ) metre 32
37.28 Fixing of copper / G.I. Tape 20mm X 3mm thick on parapet
and surface of wall for lightening conductor as required ( for
Vertical runs ) metre 75
37.29 Providing and fixing " Testing Joint" made by 20mm X 3mm
thick copper strip 125mm long with 4 Nos of tinned Brass
bolts, Nut, check nuts and spring washers etc. complete as
required . Each 287
37.30 Providing and fixing " Testing Joint" made by 20mm X 3mm
thick G.I. strip 125mm long with 4 Nos of G.I. bolts, Nut,
check nuts and spring washers etc. complete as required . Each 124
37.31 Providing and laying copper tape 32mm X 6mm thick for
earth electrode directly in ground as required metre 1283
37.32 Providing and laying G.I. tape 38mm X 6mm thick for earth
electrode directly in ground as required . metre 161
37.33 Laying of copper / G.I. tape 32mm X 6mm thick for earth
electrode directly in ground as required. metre 58
EARTHING FOR DOMESTIC ELECTRIC INSTALLATION
37.34 Providing and fixing earthing arrangement with 16mm dia
2.5 metre long galvanized iron or steel rod electrode
including packing of charcoal powder and salt as per
specification watering pipe 19mm dia G.I. Connection, cover
plate having locking arrangement on the top etc. complete
with refilling the pit as required, including excavation of
earth pit in soil/ soft rock. Each 2287
37.35 Providing and fixing earthing arrangement with 38.1mm dia
2.5 metre long galvanized iron pipe electrode including
packing of charcoal powder and salt as per specification
watering pipe 19mm dia G.I. Connection, cover plate having
locking arrangement on the top etc. complete with refilling
the pit as required, including excavation of earth pit in soil /
soft rock Each 272871
37.36 Supplying and laying G.I. earth lead duly installed on wall or
in G.I. Pipe including connections etc complete as required.

SOR ELECTRICAL 2014/CHAPTER-37

Page 71 of 114
37.36.1 13 sq mm ( 4 mm dia ) Metre 17
37.36.2 25 sq mm ( 5.6 mm dia ) Metre 26
37.36.3 40 sq mm ( 7.1 mm dia ) Metre 37
37.37 Providing and laying earth continuity conductor including
fixing with copper clamps and other necessary materials as
per specification along the run of conduit.
37.37.1 Aluminium Earth Continuity Conductor :-
37.37.1.1 6 Sq mm. Metre 17
37.37.1.2 10 Sq mm. Metre 28
37.37.1.3 16 Sq mm Metre 54
37.37.1.4 25 Sq mm. Metre 95
37.37.2 G.I. Or Steel Earth Continuity Conductor :-
37.37.2.1 6 Sq mm. Metre 12
37.37.2.2 10 Sq mm. Metre 15
37.38 Providing and laying earth Continuity Conductor of 4 Sq mm
Aluminium along the run of final sub circuit in PVC conduit
in an approved manner. Metre 13
37.39 Supplying and drawing PVC insulated copper cable ( Earth
Continuity Conductor ) of Green colour FR with copper
multi strand conductor ISI marked in existing conduit along
with other wires as required as per specification :
37.39.1 4 Sq mm Metre 41
37.39.2 6 Sq mm. Metre 58
37.39.3 10 Sq mm. Metre 88
37.39.4 16 Sq mm Metre 136
37.39.5 25 Sq mm. Metre 207
37.40 supplying and erecting earth pit of minimum bore dia.
150mm size , approved make Safe Earthing Electrode
consisting Pipe-in-Pipe technology as per IS 3043-1987
made of corrosion free G.I. Pipes with constant ohmic value
surrounded by highly conductive compound with high
charge dissipation suitable for effective and maintenance
free earthing as mentioned below :
37.40.1 With 2 mtr. G.I. Pipes having outer pipe dia of 50mm having
80-200 micron galvanizing, Inner pipe dia. of 25mm having
200-250 Micron galvanizing, connection terminal dia.of
12mm in nominal soil with 25 kg (one Bag) Back filling
Compound. Each 686372

SOR ELECTRICAL 2014/CHAPTER-37

Page 72 of 114
37.40.2 With 3 mtr. G.I. Pipes having outer pipe dia of 50mm having
80-200 micron galvanizing, Inner pipe dia. of 25mm having
200-250 Micron galvanizing, connection terminal dia.of
12mm in nominal soil with 50 kg (Two Bag) Back filling
Compound.
Each 10006
37.40.3 With 2 mtr. Pipe of 80mm outer dia. , 40mm inner dia and
14mm terminal dia. In soft rock/marshy soil with 25 kgs.
(one Bag) Back filling Compound. Each 16673
37.40.4 With 3 mtr. Pipe of 80mm outer dia. , 40mm inner dia and
14mm terminal dia. In soft rock/marshy soil with 50 kgs.
(Two Bag) Back filling Compound. Each 19195
37.41 Providing Back Filling Compound suitable for safe earthing
device. Kg 30
37.42 Supplying, installing, testing and commissioning of
Lightning protection system with Early Streamer Emission
(ESE), OPR (Optimized Pulse Rod) technology, of
protection level -1, having a coverage range and mounted
at a height as mentioned below including stainless steel
mast & mounting structure kit as per specifications.
37.42.1 OPR 30, radius 67Mt., Height 3 Mt Each 180000
37.42.2 OPR 60, radius 97Mt., Height 3 Mt Each 216000
37.43 Supplying, installing, testing and commissioning of Lightning
Discharging Counter to verify the lighting discharge
occurrence. Each 4500073

SOR ELECTRICAL 2014/CHAPTER-37

Page 73 of 114
CHAPTER - 38

TELEPHONE, LAN, TV CABLE

Rate
S.No Description of Item Unit
(Rs)
38.1 suppling and drawing Co-axial T.V. Cable RG-6 Grade , 0.7
mm Solid Copper conductor PF Insulated , Shielded with fine
tined copper braid and protected with PVC Sheathed in the
existing surface / concealed ,steel / PVC. Conduit as
required. Metre 28
38.2 Supplying and drawing following pair of 0.5 mm size solid
annealed copper conductor PVC Insulated telephone cable
as per DOT Specifications in existing surface / concealed
steel / PVC Conduit / Casing-N-Capping as required.
38.2.1 (i) 1 Pair Metre 7
38.2.2 (ii) 2 Pair Metre 11
38.2.3 (iii) 4 Pair Metre 22
38.2.4 (iv) 10 Pair Metre 53
38.3 Supply installation, testing commissioning of 0.5 mm size
Solid annealed copper, Jelly Filled Telephone Cables,
Polythene Insulated, Petroleum Jelly Filled with Poly-al
laminate moisture barrier, Polythene Sheathed, Unarmoured
Polythene Jacketed Telephone Cables as per DOT
Specifications of following sizes
38.3.1 10 Pair Metre 70
38.3.2 20 Pair Metre 126
38.3.3 50 Pair Metre 297
38.4 Supply, Installation testing and commissioning of telephone
Tag block Krone connector with enclosure and lock complete
as mentioned below :-
38.4.1 10 Pair each 263
38.4.2 20 Pair each 273
38.4.3 30 Pair each 297
38.4.4 50 Pair each 341
38.5 Supply, fixing and testing RJ - 11 Telephone Jack Single with
shutter F.T each 57
38.6 Supply, fixing and testing of RJ 11 telephone jack modular (1
Module) each 12974
38.7 Supply, fixing and testing of T.V. Outlet F.T 34

SOR ELECTRICAL 2014/CHAPTER-38

Page 74 of 114
38.8 Supply, fixing and testing of T.V. Outlet Modular (1Module) 129
38.9 Supply, Installation testing and commissioning RJ - 45
Computer Jack cat 6 with shutter Modular (1Module) each 491
38.10 Supply, Installation testing and commissioning RJ - 45
Computer Jack cat 6 with shutter Modular (2Module) each 501
38.11 Suppling and drawing 4 pair shielded, 0.5 mm PVC.Insulated
copper conductor un-armoured Cat-6 computer cable FR in
existing surface / concealed ,steel / PVC. Conduit/Casing-N-
Capping as required.
per Mtr 46
38.12 Supply, Installation testing and commissioning of patch cord
as mentioned below :-
38.12.1 CAT 6 RJ45 Patch Cord F/UTP 1 Mtr. each 407
38.12.2 CAT 6 RJ45 Patch Cord F/UTP 2 Mtr. each 450
38.12.3 CAT 6 RJ45 Patch Cord F/UTP 3 Mtr. each 585
38.12.4 CAT 6 RJ45 Patch Cord F/UTP 5 Mtr. each 698
38.13 Supply, Installation testing and commissioning of 19" Modular
Patch - 1 U Patch Panel 24, RJ 45 Cat-6 connector each 10926
38.14 Supply, Installation testing and commissioning of 19" Modular
telephone Patch Panel 24 - 1 U with RJ 11 connector each 20018
38.15 Supply, Installation testing and commissioning of wall
mounting rack, for computer switches complete as
mentioned below :-
38.15.1 6U cabinet 371.30X600X500, wall mounting with power
supply and Fan etc. each 13187
38.15.2 9U cabinet 504.65X600X500, wall mounting with power
supply and Fan etc. each 15809
38.15.3 12U cabinet 638X600X500, wall mounting with power supply
and Fan etc. each 1748775

SOR ELECTRICAL 2014/CHAPTER-38

Page 75 of 114
CHAPTER - 39
SINGLE / THREE PHASE SUBMERSIBLE / OPENWELL / CENTRIFUGAL MOTOR
PUMP SET.
Rate
S.No Description of Item Unit
(Rs)
39.1 Supplying & Installation of required capacity of single
phase, 50 Hz,220V, deep well submersible pump Stainless
Steel body, as per IS of approved Make, suitable for 4"/6 "
tube well with Control Panel Starter suitable for Submersible
pump with dry run protection, connections, including
clamps, bore cap etc. as required as per specifications but
excluding Pipe, SS/Nylon wire rope and connection cable.
0.5 H.P. with 6 to 7 stages, Head Mt 46-13, Discharge LPM
39.1.1.1 10-55 each 22837
1 H.P. with upto 5 stages, Head Mt 35-15, Discharge
39.1.1.2 LPM 40-125 each 24129
1 H.P. with 7 to 8 stages, Head Mt 61-18, Discharge
39.1.1.3 LPM 25-90 each 24539
1 H.P. with 10 to 11 stages, Head Mt 74-21, Discharge
39.1.1.4 LPM 15-55 each 25421
1 H.P. with 12 to 14 stages, Head Mt 91-28, Discharge
39.1.1.5 LPM 10-45 each 26209

1.5 H.P. with up to 6 stages, Head Mt 42-17, Discharge


39.1.2.1 LPM 65-150 each 28661
1.5 H.P. with 7 to 8 stages, Head Mt 56-21, Discharge
39.1.2.2 LPM 40-125 each 29449
1.5 H.P. with 10 to 11 stages, Head Mt 84-26, Discharge
39.1.2.3 LPM 25-90 each 28945
1.5 H.P. with 16 to 17 stages, Head Mt 114-33, Discharge
39.1.2.4 LPM 15-55 each 29039
1.5 H.P. with 18 to 20 stages, Head Mt 130-41, Discharge
39.1.2.5 LPM 10-45 each 31182

2 H.P. with 7 to 8 stages, Head Mt 56-16, Discharge LPM


39.1.3.1 65-205 each 32783
2 H.P. with 10 to 11 stages, Head Mt 77-30, Discharge
39.1.3.2 LPM 40-125 each 33067
2 H.P. with 14 to 15 stages, Head Mt 114-36, Discharge
39.1.3.3 LPM 25-90 each 31743
2 H.P. with 20 to 22 stages, Head Mt 147-42, Discharge
39.1.3.4 LPM 15-55 each 31271
2 H.P. with 25 stages, Head Mt 163-58, Discharge LPM 10-
39.1.3.5 45 each 3637676

SOR ELECTRICAL 2014/CHAPTER-39

Page 76 of 114
3 H.P. with 10 to 12 stages, Head Mt 84-23, Discharge
39.1.4.1 LPM 65-205 each 35178
3 H.P. with 15 to 17 stages, Head Mt 119-45, Discharge
39.1.4.2 LPM 40-125 each 36238
3 H.P. with 20 to 22 stages, Head Mt 167-51, Discharge
39.1.4.3 LPM 25-90 each 34800
39.2 Supplying & Installation of required capacity of Three
phase, 50 Hz,415V, deep well submersible pump Steel
body, as per IS of approved Make, suitable for 6 " tube well
with Control Panel Starter suitable for Submersible pump
with dry run protection, single phase preventer,
connections, including clamps, bore cap etc. as required as
per specifications but excluding Pipe and connection cable.
39.2.1.1 3 H.P. with up to 6 stages, Head Mt 55-7, Discharge LPM
60-510 each 39529

5 H.P. with up to 5 stages, Head Mt 55-13, Discharge LPM


39.2.2.1 120-510 each 44349
5 H.P. with 8 to 9 stages, Head Mt 83-32, Discharge LPM
39.2.2.2 60-270 each 47375
5 H.P. with 10 to 11 stages, Head Mt 101-40, Discharge
39.2.2.3 LPM 60-270 each 50022

7.5 H.P. with 8 to 10 stages, Head Mt 117-31, Discharge


39.2.3.1 LPM 60-420 each 55383
7.5 H.P. with 13 to 14 stages, Head Mt 129-52, Discharge
39.2.3.2 LPM 60-270 each 62999
7.5 H.P. with 15 stages, Head Mt 138-60, Discharge LPM
39.2.3.3 60-270 each 65426

10 H.P. with 16 stages, Head Mt 147-64, Discharge LPM


39.2.4.1 60-270 each 68956
10 H.P. with 20 stages, Head Mt 184-80, Discharge LPM
39.2.4.2 60-270 each 76015
39.3 Supplying and laying of submersible flat cable ISI marked 3
core copper wire of suitable size with proper clamping of
approved make.
39.3.1.1 2.5 Sq.mm multi strand per mtr 132
39.3.1.2 4.0 Sq.mm multi strand per mtr 185
39.3.1.3 6.0 Sq.mm multi strand per mtr 274
39.3.1.4 10.0 Sq.mm multi strand per mtr 442
39.4 Supplying and laying of approved Make HDPE pipe as per
IS : 4984 and IS : 14333 with latest amendment for
installation of submersible pump with necessary connection,
socket/couplings, Tees,etc. as required (PE-63 & working
Pressure 10 kgf/sq cm)77

SOR ELECTRICAL 2014/CHAPTER-39

Page 77 of 114
39.4.1.1 25 mm Outer Dia. per mtr 83
39.4.1.2 32 mm Outer Dia. per mtr 115
39.4.1.3 40 mm Outer Dia. per mtr 171
39.4.1.4 50 mm Outer Dia. per mtr 248
39.5 Supplying and laying of approved Make Nylon rope 12 mm
thick complete with binding for support of pump and motor. per mtr 75
39.6 Supplying and laying of approved Make Stainless Steel wire
rope 6 mm thick complete with binding for support of pump
and motor. per mtr 171
39.7 Supplying & Installation of approved Make required capacity
single phase, 50 Hz,220V, Centrifugal Mono-block pump
self priming, with Starter , connections, base channel
foundation etc. as required as per specifications but
excluding Pipe and connection cable.
39.7.1.1 1 H.P. Head Mt 6-30, Discharge LPH 2400-900 each 13114
1 H.P. Head Mt 21-45, Discharge LPH 1800-400 (Domestic
39.7.1.2 Model) each 8144
39.8 Supplying & Installation of approved Make required capacity
single phase, 50 Hz,240V, Centrifugal Mono-block pump,
with Starter , connections, base channel foundation etc. as
required as per specifications but excluding Pipe and
connection cable.
39.8.1.1 1 H.P. Head Mt 3-24, Discharge LPH 27000-1500 each 12572
39.8.1.2 1.5 H.P. Head Mt 3-21, Discharge LPH 39600-6000 each 15102
39.8.1.3 2.0 H.P. Head Mt 3-18, Discharge LPH 48600-3000 each 16764
39.9 Supplying & Installation of approved Make required capacity
3 phase, 50 Hz, 415V, Centrifugal Mono-block pump, with
Starter i/c single phase preventor, connections, base
channel foundation etc. as required as per specifications
but excluding Pipe and connection cable.

39.9.1.1 3.0 H.P. Head Mt 6-15, Discharge LPM 740-465 each 21195
39.9.1.2 5.0 H.P. Head Mt 6-33, Discharge LPM 1380-450 each 25967
39.9.1.3 7.5.0 H.P. Head Mt 24-37, Discharge LPM 780-320 each 33241
39.10 Supplying & Installation of approved Make required capacity
3 phase, 50 Hz, 415V, Open Well Submersible pump, with
Control Panel Starter with Dry Run Protection, single phase
preventer, connections, etc. as required as per
specifications but excluding Pipe and connection cable.

39.10.1.1 3.0 H.P. Head Mt 15-24, Discharge LPM 615-195 each 24724
39.10.1.2 5.0 H.P. Head Mt 15-24, Discharge LPM 930-420 each 2657478

SOR ELECTRICAL 2014/CHAPTER-39

Page 78 of 114
CHAPTER - 40
WIRING OF OLD STANDARD F/G/H/I QTRS & NEW WIRING OF NEW
STANDARD F/G/H/I QTRS
Rate
S.No. Description of Item Unit
(Rs)
40 Wiring of Old standard F/G/H/I qtrs and New wiring of Using Flush
new standard F/G/H/I qtrs. Type Normal
Accessories
40.1 Re-wiring of Old standard F/G/H/I qtrs
40.1.1 Dismentalling of wiring in "I" type quarter and rewiring in
same in surface Rigid PVC Conduit system. Each 26802
40.1.2 Dismentalling of wiring in "I" type quarter and rewiring in
same in surface Rigid PVC Casing-N- Capping system. Each 26833
40.1.3 Dismentalling of wiring in "H" type quarter and rewiring in
same in surface Rigid PVC Conduit system. Each 30268
40.1.4 Dismentalling of wiring in "H" type quarter and rewiring in
same in surface Rigid PVC Casing-N- Capping system. Each 30326
40.1.5 Dismentalling of wiring in "G" type quarter and rewiring in
same in surface Rigid PVC Conduit system. Each 35971
40.1.6 Dismentalling of wiring in "G" type quarter and rewiring in
same in surface Rigid PVC Casing-N- Capping system. Each 36426
40.1.7 Dismentalling of wiring in "F" type quarter and rewiring in
same in surface Rigid PVC Conduit system. Each 61944
40.1.8 Dismentalling of wiring in "F" type quarter and rewiring in
same in surface Rigid PVC Casing-N- Capping system. Each 62516
40.2 Wiring of newly constructed F/G/H/I qtrs.
40.2.1 Wiring in newly constructed "I" type quarter in surface Rigid
PVC Conduit system. Each 33749
40.2.2 Wiring in newly constructed "I" type quarter in surface Rigid
PVC Casing-N- Capping system. Each 33780
40.2.3 Wiring in newly constructed "H" type quarter in surface
Rigid PVC Conduit system. Each 38887
40.2.4 Wiring in newly constructed "H" type quarter in surface
Rigid PVC Casing-N- Capping system. Each 38757
40.2.5 Wiring in newly constructed "G" type quarter in surface
Rigid PVC Conduit system. Each 47240
40.2.6 Wiring in newly constructed "G" type quarter in surface
Rigid PVC Casing-N- Capping system. Each 47779
40.2.7 Wiring in newly constructed "F" type quarter in surface
Rigid PVC Conduit system. Each 76908
40.2.8 Wiring in newly constructed "F" type quarter in surface
Rigid PVC Casing-N- Capping system. Each 77480

Note:- Above comprehensive(composite) items include points as detailed in


Annexure-179

SOR ELECTRICAL 2014/CHAPTER-40


Page 79 of 114
CHAPTER -41 (External)
UNDER GROUND CABLES
S.No. Description of Item Unit Rate
1 2 3 4
41.1 Supply of XLPE Insulated power cable (confirming IS-7098
Part-I ) 1100 Volt grade, 1 core /2 core /3 core/4 core ISI
MARKED with Alu. Stranded /solid conductor
41.1.1 UNARMOURED 1 Core
41.1.1.1 16 Sq.mm. Metre 48
41.1.1.2 25 Sq.mm. Metre 61
41.1.1.3 35 Sq.mm. Metre 76
41.1.1.4 50 Sq.mm. Metre 98
41.1.1.5 70 Sq.mm. Metre 130
41.1.1.6 95 Sq.mm. Metre 168
41.1.1.7 120 S.qmm. Metre 210
41.1.1.8 150 Sq.mm. Metre 256
41.1.1.9 300 Sq.mm. Metre 316
41.1.2 ARMOURED 1 Core
41.1.2.1 16 Sq.mm. Metre 83
41.1.2.2 25 Sq.mm. Metre 101
41.1.2.3 35 Sq.mm. Metre 122
41.1.2.4 50 Sq.mm. Metre 148
41.1.2.5 70 Sq.mm. Metre 188
41.1.2.6 95 Sq.mm. Metre 212
41.1.2.7 120 Sq.mm. Metre 255
41.1.2.8 150 Sq.mm. Metre 303
41.1.2.9 300 Sq.mm. Metre 553
41.1.3 UNARMOURED 2 Core
41.1.3.1 2.5 Sq.mm. Metre 50
41.1.3.2 4 Sq.mm. Metre 77
41.1.3.3 6 Sq.mm. Metre 86
41.1.3.4 10 Sq.mm. Metre 110
41.1.3.5 16 Sq.mm. Metre 134
41.1.4 ARMOURED 2 Core
41.1.4.1 2.5 Sq.mm. Metre 8680

SOR ELECTRICAL 2014/CHAPTER-41

Page 80 of 114
41.1.4.2 4 Sq.mm. Metre 93
41.1.4.3 6 Sq.mm. Metre 109
41.1.4.4 10 Sq.mm. Metre 133
41.1.4.5 16 Sq.mm. Metre 159
41.1.5 UNARMOURED 3 Core
41.1.5.1 6 Sq.mm. Metre 78
41.1.5.2 10 Sq.mm. Metre 101
41.1.5.3 16 Sq.mm. Metre 130
41.1.5.4 25 Sq.mm Metre 180
41.1.5.5 35 Sq.mm Metre 231
41.1.5.6 50 Sq.mm Metre 299
41.1.5.7 70 Sq.mm Metre 414
41.1.5.8 95 Sq.mm. Metre 526
41.1.6 ARMOURED 3 Core
41.1.6.1 6 Sq.mm. Metre 127
41.1.6.2 10 Sq.mm. Metre 151
41.1.6.3 16 Sq.mm. Metre 168
41.1.6.4 25 Sq.mm Metre 219
41.1.6.5 35 Sq.mm Metre 277
41.1.6.6 50 Sq.mm Metre 348
41.1.6.7 70 Sq.mm Metre 468
41.1.6.8 95 Sq.mm. Metre 584
41.1.7 3 CORE UNARMOURED
41.1.7.1 25 Sq.mm Metre 210
41.1.7.2 35 Sq.mm Metre 262
41.1.7.3 50 Sq.mm Metre 345
41.1.7.4 70 Sq.mm Metre 477
41.1.7.5 95 Sq.mm. Metre 608
41.1.7.6 120 Sq.mm. Metre 765
41.1.7.7 150 Sq.mm. Metre 921
41.1.7.8 185 Sq.mm. Metre 1158
41.1.7.9 240 Sq.mm. Metre 1478
41.1.7.10 300 Sq.mm. Metre 1818
41.1.7.11 400 Sq.mm. Metre 2345
41.1.8 3 CORE ARMOURED
41.1.8.1 25 Sq.mm Metre 252
41.1.8.2 35 Sq.mm Metre 311
41.1.8.3 50 Sq.mm Metre 40181

SOR ELECTRICAL 2014/CHAPTER-41

Page 81 of 114
41.1.8.4 70 Sq.mm Metre 538
41.1.8.5 95 Sq.mm. Metre 677
41.1.8.6 120 Sq.mm. Metre 846
41.1.8.7 150 Sq.mm. Metre 1003
41.1.8.8 185 Sq.mm. Metre 1240
41.1.8.9 240 Sq.mm. Metre 1567
41.1.8.10 300 Sq.mm. Metre 1909
41.1.8.11 400 Sq.mm. Metre 2440
41.1.9 4 CORE UNARMOURED
41.1.9.1 6 Sq.mm. Metre 93
41.1.9.2 10 Sq.mm. Metre 121
41.1.9.3 16 Sq.mm. Metre 162
41.1.9.4 25 Sq.mm Metre 226
41.1.9.5 35 Sq.mm Metre 291
41.1.9.6 50 Sq.mm Metre 379
41.1.9.7 70 Sq.mm Metre 528
41.1.9.8 95 Sq.mm. Metre 675
41.1.9.9 120 Sq.mm. Metre 849
41.1.9.10 150 Sq.mm. Metre 1044
41.1.10 4 CORE ARMOURED
41.1.10.1 6 Sq.mm. Metre 140
41.1.10.2 10 Sq.mm. Metre 181
41.1.10.3 16 Sq.mm. Metre 197
41.1.10.4 25 Sq.mm Metre 272
41.1.10.5 35 Sq.mm Metre 345
41.1.10.6 50 Sq.mm Metre 443
41.1.10.7 70 Sq.mm Metre 591
41.1.10.8 95 Sq.mm. Metre 746
41.1.10.9 120 Sq.mm. Metre 923
41.1.10.10 150 Sq.mm. 1125
Metre
41.2 Supply of approved High-Tension XLPE cable (conforming
IS-7098/II/85 ) as per ISI standard single core Armoured
with Alu. Solid/stranded conductor ISI MARKED as
required
41.2.1 SINGLE CORE XLPE CABLE 11 KV GRADE
41.2.1.1 50 Sq.mm Metre 358
41.2.1.2 70 Sq.mm Metre 408
41.2.1.3 95 Sq.mm. Metre 45982

SOR ELECTRICAL 2014/CHAPTER-41

Page 82 of 114
41.2.1.4 120 Sq.mm. Metre 518
41.2.1.5 150 Sq.mm. Metre 571
41.2.2 SINGLE CORE XLPE CABLE 33 KV GRADE
41.2.2.1 95 Sq.mm. Metre 803
41.2.2.2 120 Sq.mm. Metre 884
41.2.2.3 150 Sq.mm. Metre 945
41.3 Supply of approved High-Tension XLPE cable (conforming
IS-7098/II/85 ) as per ISI standard 3 core Armoured with
Alu. Solid/stranded conductor ISI MARKED as required
41.3.1 3 CORE XLPE CABLE 11 KV GRADE
41.3.1.1 50 Sq.mm Metre 841
41.3.1.2 70 Sq.mm Metre 999
41.3.1.3 95 Sq.mm. Metre 1193
41.3.1.4 120 Sq.mm. Metre 1377
41.3.1.5 150 Sq.mm. Metre 1537
41.3.2 3 CORE XLPE CABLE 33 KV GRADE
41.3.2.1 95 Sq.mm. Metre 2057
41.3.2.2 120 Sq.mm. Metre 2362
41.3.2.3 150 Sq.mm. Metre 2562
41.4 Supply of XLPE Insulated power cable (conforming IS-
7098 ) 1100 Volt grade/Heavy duty power cable 2 core / 3
core ISI MARKED with copper Stranded /solid conductor
41.4.1 ARMOURED 2 Core
41.4.1.1 2.5 Sq.mm.(Heavy Duty) Metre 176
BRASS COMPRESSION GLAND
41.5 Supplying and fixing heavy duty cable gland for P.V.C.
insulated armoured cable with brass washer, Rubber ring
complete erected with cable and lead connection etc. as
per specification complete.
41.5.1 Gland Size 22mm suitable for cable 2,3,3 & 4 x up to 6
Sq.mm Each 34
41.5.2 Gland Size 22mm suitable for cable 2/3, 3, 2/4 x 10
Sq.mm or 2x 16 Sq.mm Each 46
41.5.3 Gland size 28mm for 3/4 x 16 Sq.mm Each 70
41.5.4 Gland size 32mm for 2/3, 3, 4 x 25 Sq.mm
OR 2/3, 3 x 35 Sq.mm OR 2/3 x 50 Sq.mm. Each 80
41.5.5 Gland size 38mm 3 x 70 Sq.mm, 3x95 Sq.mm
Each 115
41.5.6 Gland Size 45mm 3/3 x 120 Sq.mm, 3 x 95 Sq.mm
3 x 150 Sq.mm. Each 137
41.5.7 Gland Size 50 mm 3 x 150 Sq.mm, 3 x 185 Sq.mm Each 17783

SOR ELECTRICAL 2014/CHAPTER-41

Page 83 of 114
41.5.8 Gland Size 57mm 3 x 225 Sq.mm, 3 x 185 Sq.mm Each 244
41.5.9 Gland Size 70mm 3 x 240 Sq.mm, 3 x 300 Sq.mm Each 333
41.5.10 Gland Size 82mm 3 x 400 Sq.mm Each 433
41.6 Supplying and fixing ferrules as per IS - specification
suitable for following size of cable for circuit identification
including connection as required complete
For Conductor Size-
41.6.1 2.5 to 6.00 Sq.mm Each 1
41.6.2 10.00 Sq.mm Each 2
41.6.3 16.00 Sq.mm Each 2
41.6.4 25.00 Sq.mm Each 3
41.6.5 35.00 Sq.mm Each 3
41.6.6 50.00 Sq.mm Each 5
41.6.7 70.00 Sq.mm Each 8
41.6.8 95.00 Sq.mm Each 9
41.6.9 120.00 Sq.mm Each 13
41.6.10 150.00 Sq.mm Each 18
41.6.11 185.00 Sq.mm Each 22
41.6.12 240.00 Sq.mm Each 36
41.6.13 300.00 Sq.mm Each 52
41.6.14 400.00 Sq.mm Each 75
LUGS:-
41.7 Supplying and fixing cramping type Alum. lugs as per
I.S.S.
Specification suitable for following size of cable with Alu.
/Copper solid/stranded conductor evently cramped with
high/pressure tool and connected to switch
gear/Bus/M.C.C.B./ M.C.B. etc. as required complete.
For Conductor Size-
41.7.1 6mm to 16 Sq.mm Each 2
41.7.2 25 Sq.mm Each 4
41.7.3 35 Sq.mm Each 5
41.7.4 50 Sq.mm Each 8
41.7.5 70 Sq.mm Each 11
41.7.6 95 Sq.mm. Each 16
41.7.7 120 Sq.mm. Each 21
41.7.8 150 Sq.mm. Each 30
41.7.9 180 Sq.mm Each 40
41.7.10 240 Sq.mm. Each 5584

SOR ELECTRICAL 2014/CHAPTER-41

Page 84 of 114
41.7.11 300 Sq.mm. Each 72
41.7.12 400 Sq.mm. Each 115
41.8 Supplying & fixing pin terminal lugs as per ISS
specification suitable for cable evently cramped with high
pressure tool & connection to switch gear terminal.

41.8.1 Aluminum Lugs Pin Type


41.8.1.1 Up to 16 Sq.mm2 Conductor Size Each 7
41.8.1.2 Up to 25 Sq.mm2 Conductor Size Each 8
41.8.1.3 35 Sq.mm Conductor Size Each 11
41.8.2 Copper Lugs Pin Type
41.8.2.1 Up to 16 Sq.mm2 Conductor Size Each 17
41.8.2.2 Up to 25 Sq.mm2 Conductor Size Each 26
41.8.2.3 35 Sq.mm Conductor Size Each 28
41.8.3 Aluminum Lugs Tube Type
41.8.3.1 Up to 16 Sq.mm Conductor Size Each 1
41.8.3.2 25 Sq.mm Conductor Size Each 3
41.8.3.3 35 Sq.mm Conductor Size Each 5
41.8.3.4 50 Sq.mm. Conductor Size Each 8
41.8.4 Copper Lugs Tube Type
41.8.4.1 Up to 16 Sq.mm2 Conductor Size Each 6
41.8.4.2 25 Sq.mm2 Conductor Size Each 11
41.8.4.3 35 Sq.mm Conductor Size Each 15
41.8.4.4 50 Sq.mm. Conductor Size Each 23
Cable Jointing
41.9 Providing & Making cable end termination with HEAT
SHRINKABLE jointing kit complete with all accessories
including lugs suitable for 33 kV/11 kV single core XLPE
alum. conductor cable as required as per specification and
as per accepted standard including connection testing
complete.
41.9.1 Heat shrinkable joint,kit 11 kV XLPE Single Core
41.9.1.1 Heat shr.jointg. kit 11 kV XLPE cable O.D. termination
a. 1 x 16-35 sq.mm. Each 4082
b. 1 x 50-95 sq.mm. Each 4361
c. 1 x 120-185 sq.mm. Each 4770
41.9.1.2 Heat shr.jointg. kit 11 kV XLPE cable I.D. termination
a. 1 x 16-35 sq.mm. Each 2944
b. 1 x 50-95 sq.mm. Each 2988
c. 1 x 120-185 sq.mm. Each 339585

SOR ELECTRICAL 2014/CHAPTER-41

Page 85 of 114
41.9.1.3 Heat shr.jointg. kit 11 kV XLPE cable Straight Through
termination
a. 1 x 16-35 sq.mm. Each 7170
b. 1 x 50-95 sq.mm. Each 8353
c. 1 x 120-185 sq.mm. Each 9203
41.9.2 Heat shrinkable joint,kit 33 kV XLPE Single Core
41.9.2.1 Heat shr.jointg. kit 33 kV XLPE cable O.D. termination
a. 1 x 35-70 sq.mm. Each 7121
b. 1 x 95-150 sq.mm. Each 7959
c. 1 x 185-240 sq.mm. Each 8770
41.9.2.2 Heat shr.jointg. kit 33 kV XLPE cable I.D. termination
a. 1 x 35-70 sq.mm. Each 4484
b. 1 x 95-150 sq.mm. Each 5270
c. 1 x 185-240 sq.mm. Each 7063
41.9.2.3 Heat shr.jointg. kit 33 kV XLPE cable Straight Through
termination
a. 1 x 35-70 sq.mm. Each 17428
b. 1 x 95-150 sq.mm. Each 21861
c. 1 x 185-240 sq.mm. Each 25908
41.10 Providing & Making cable end termination with HEAT
SHRINKABLE jointing kit complete with all accessories
including lugs suitable for 33 kV/11 kV 3 core XLPE alum.
conductor cable as required as per specification and as
per accepted standard including connection testing
complete.
41.10.1 Heat shrinkable joint,kit 11 kV XLPE, 3 Core
41.10.1.1 Heat shr.jointg. kit 11 kV XLPE cable O.D. termination
a. 3 x 16-35 sq.mm. Each 10355
b. 3 x 50-95 sq.mm. Each 11768
c. 3 x 120-185 sq.mm. Each 13078
41.10.1.2 Heat shr.jointg. kit 11 kV XLPE cable I.D. termination
a. 3 x 16-35 sq.mm. Each 13570
b. 3 x 50-95 sq.mm. Each 14906
c. 3 x 120-185 sq.mm. Each 15691
41.10.1.3 Heat shr.jointg. kit 11 kV XLPE cable Straight Joint
a. 3 x 16-50 sq.mm. Each 20106
b. 3 x 70-95 sq.mm. Each 22009
c. 3 x 120-185 sq.mm. Each 26902
41.10.2 Heat shrinkable joint,kit 33 kV XLPE, 3 Core
41.10.2.1 Heat shr.jointg. kit 33 kV XLPE cable O.D. termination86

SOR ELECTRICAL 2014/CHAPTER-41

Page 86 of 114
a. 3 x 35-70 sq.mm. Each 21158
b. 3 x 95-150 sq.mm. Each 25166
c. 3 x 185-240 sq.mm. Each 31337
41.10.2.2 Heat shr.jointg. kit 33 kV XLPE cable I.D. termination
a. 3 x 35-70 sq.mm. Each 16745
b. 3 x 95-150 sq.mm. Each 17405
c. 3 x 185-240 sq.mm. Each 24135
41.10.2.3 Heat shr.jointg. kit 33 kV XLPE cable Straight Joint
a. 3 x 35-70 sq.mm. Each 47950
b. 3 x 95-150 sq.mm. Each 59503
c. 3 x 185-240 sq.mm. Each 81057
41.11 Supply and making cable straight joint / end termination
with HEAT SHRINKABLE jointing kit complete with all
accessories including lugs suitable for 1.1 kV XLPE/HD
alum. conductor cable as required as per specification and
as per accepted standard including connection testing
complete for (I.D../O.D.) termination.

41.11.1 Heat shr.jointg. kit 1.1 kV XLPE/HD cable end termination


jointing.kit (I.D../O.D.)
a. 6-16 sqmm 1 core Each 455
b. 25-50 sqmm 1 core Each 515
c. 70-150 sqmm 1 core Each 704
d. 185-300 sqmm 1 core Each 1074
e. 400-500 sqmm 1 core Each 1290
41.11.2 Heat shr.jointg. kit 1.1 kV XLPE/HD cable straight through
jointing.kit (I.D../O.D.)
a. 6-16 sqmm 1 core Each 851
b. 25-50 sqmm 1 core Each 921
c. 70-150 sqmm 1 core Each 1131
d. 185-300 sqmm 1 core Each 1337
e 400-500 sqmm 1 core Each 1548
41.11.3 Heat shr.jointg. kit 1.1 kV XLPE/HD cable I.D/O.D. end
ternmination
a. 6-50 sqmm 3 core Each 1665
b. 70-150 sqmm 3 core Each 1939
c. 185-300 sqmm 3 core Each 2534
d. 400-500 sqmm 3 core Each 3072
41.11.4 Heat shr.jointg. kit 1.1 kV XLPE/HD cable I.D./O.D. end
ternmination87

SOR ELECTRICAL 2014/CHAPTER-41

Page 87 of 114
a. 6-50 sqmm 4 core Each 1817
b. 70-150 sqmm 4 core Each 2120
c. 185-300 sqmm 4 core Each 2685
d. 400-500 sqmm 4 core Each 3292
41.11.5 Heat shr.jointg. kit 1.1 kV XLPE/HD cable straight through
jointing.kit (I.D../O.D.)
a. 6-16 sqmm 3 / 4core Each 1610
b. 25-35 sqmm 3 / 4core Each 1947
c. 50-95 sqmm 3 / 4core Each 2583
d. 120-185 sqmm 3 / 4core Each 3437
e. 225-300 sqmm 3 / 4core Each 4910
f. 400-500 sqmm 3 / 4core Each 7176
41.12 Suppying & installing G.I. Pipe for protection of
underground cable fixed on wall/support/in trench/fixed
between two rigid existing support of wall/beam for
erection of ceiling Fan/down rod for stiff pendent for light
luminaries /fan/protective for earthing, lightening conductor
down strip/overhead service line/for submersible cable or
centrifugal pump for water supply with necessary iron
clamp coupler, bend, tee, elbow, nuts and bolts etc.
complete in an approved manner as required to complete
excluding cost of excavation/dismentalling & other finshed
masonary Item complete.
41.12.1 For 'B' Class pipe ISI Marked (IS-1161-68)
41.12.1.1 15mm Metre 130
41.12.1.2 20.00mm Metre 168
41.12.1.3 25.00mm Metre 239
41.12.1.4 32.00mm Metre 301
41.12.1.5 40.00mm Metre 351
41.12.1.6 50.00mm Metre 465
41.12.1.7 65.00mm Metre 586
41.12.1.8 80.00mm Metre 761
41.12.1.9 100.00mm Metre 1070
41.12.1.10 150.00mm Metre 1753
41.12.2 A' Class G.I.Pipe ISI Marked (IS-1161-69)
41.12.2.1 15mm Metre 111
41.12.2.2 19/20mm Metre 155
41.12.2.3 25.00mm Metre 210
41.12.2.4 32.00mm Metre 271
41.12.2.5 40.00mm Metre 32788

SOR ELECTRICAL 2014/CHAPTER-41

Page 88 of 114
41.12.2.6 50.00mm Metre 414
41.12.2.7 65.00mm Metre 547
41.12.2.8 80.00mm Metre 658
41.12.2.9 100.00mm Metre 920
41.13 Supply and laying rigid PVC single socket and, non-
metallic pipe ISI Marked (IS-4985-2000) 10 Kg/sq.cm class
5 for protection of under ground cable/or for water pump
delivery side, for water supply complete with necessary
clamp coupler, band, Tee, Elbow etc. in an approved
manner excluding cost of excavation etc.
41.13.1 50.00mm O.D Metre 127
41.13.2 75.00mm O.D Metre 295
41.13.3 110.00mm O.D Metre 645
41.13.4 160.00mm O.D Metre 1274
41.13.5 200.00mm O.D Metre 1978
41.14 Supplying and installing Double wall corrugated pipes
(DWC) of HDPE ( IS 14930 Part II -marked ) for cable laid
under ground with necessary material and at required
depth upto 90cm. below road/ground surface, including
excavation, back filling with excavated material, ramming
and making the surface good.
41.14.1 50.00mm outside dia. Metre 137
41.14.2 63.00mm outside dia. Metre 180
41.14.3 90.00mm outside dia. Metre 233
41.14.4 110.00mm outside dia. Metre 264
41.14.5 120.00mm outside dia. Metre 299
41.14.6 180.00mm outside dia. Metre 412
41.14.7 210.00mm outside dia. Metre 554
CABLE LAYING
41.15 Laying of one number armoured / unarmoured power
cable 1.1kV grade of size not exceeding 25 Sq.mm direct
in ground including excavation in all soil / murrum / soft
rock, sand cushioining, protective covering and refilling the
pit etc. as required. Metre 202
41.16 Laying of one number armoured / unarmoured power
cable 1.1.kV grade of size exceeding 25Sq.mm but not
exceeding 120 Sq.mm direct in ground including
excavation in all soil / murrum / soft rock, sand cushioing,
protective covering and refilling the pit etc. as required. Metre 21189
41.17 Laying of one number armoured / unarmoured cable
1.1.kV grade of size exceeding 120 Sq mm but not
exceeding 400 Sq.mm direct in ground including
excavation in all soil / murrum / soft rock, and sand
Metre 229

SOR ELECTRICAL 2014/CHAPTER-41

Page 89 of 114
cushioning protective covering and refilling the pit etc. as
required.

41.18 Laying of one number additional armoured / unarmoured


power cable 1.1kV grade of size not exceeding 25Sq.mm
direct in ground in the same trench in one tier horizontal
formation including excavation in all soil / murrum / soft
rock, sand cushioing protective covering and refilling the
pit etc. as required. Metre 111
41.19 Laying of one number additional armoured / unarmoured
power cable 1.1kV grade of size exceeding 25 Sq.mm but
not exceeding 120 Sq.mm direct in ground in the same
trench in one tier horizotal formation including excavation,
sand cushioing, protective covering and refilling the pit etc.
as required. Metre 120
41.20 Laying of one number additional armoured / unarmoured
power cable 1.1kV grade of size exceeding 120 Sq mm
but not exceeding 400 Sq mm direct in ground in the same
trench in one tier horizotal formation including excavation,
sand cushioing, protective covering and refilling the pit etc.
as required. Metre 138
41.21 Laying of one number armoured / unarmoured power
cable 1:1 kV grade of size not exceeding 25 Sq.mm in the
existing RCC Hume/Stone ware/G.I. pipe / surface in
existing trench as required. Metre 25
41.22 Laying of one number armoured / unarmoured power
cable 1.1 kV grade of size exceeding 25 Sq.mm but not
exceeding 400 Sq mm in the existing RCC Hume /Stone
ware/G.I. Pipe/ surface in existing trench as required.
Metre 43
41.23 Laying of one number armoured / unarmoured power
cable 1.1 kV grade of size not exceeding 25 Sq.mm in th
existing masonary open duct as required. Metre 20
41.24 Laying of one number armoured / unarmoured power
cable 1.1kV grade of size exceeding 25Sq.mm but not
exceeding 400 Sq.mm in the existing masonary open duct
as required. Metre 43
41.25 Laying of one number single core H.T armoured /
unarmoured power cable of grade exceeding 1.1kV but not
exceeding 11kV of size not exceeding 150 Sq.mm direct in
ground including excavation in all soil / murrum / soft rock,
sand cushioning, excluding protective covering and refilling
the trench etc. as required. Metre 13890

SOR ELECTRICAL 2014/CHAPTER-41

Page 90 of 114
41.26 Laying of one number single core H.T armoured /
unarmoured power cable of grade 33kV of size not
exceeding 150 Sq.mm direct in ground including
excavation sand cushioning, excluding protective covering
and refilling the trench etc. as required Metre 138
41.27 Laying of one number single core H.T armoured /
unarmoured power cable of grade exceeding 1.1kV but not
exceeding 11kV of size not exceeding 150 Sq.mm in the
existing RCC / Hume / Stoneware / G.I. Pipe / surface in
existing trench as required. Metre 27
41.28 Laying of one number single core H.T armoured /
unarmoured power cable of grade exceeding 1.1kV but not
exceeding 11kV of size not exceeding 150 Sq.mm. in the
existing masonary open duct as requied.
Metre 31
41.29 Laying of one number single core H.T armoured /
unarmoured power cable 33kV grade of size not
exceeding 150 Sq.mm in the existing RCC / Hume /
Stoneware / G.I. Pipe / surface in existing trench as
required. Metre 31
41.30 Laying of one number single core H.T armoured /
unarmoured power cable 33kV grade of size not
exceeding 150 Sq.mm. in the existing masonary open duct
as requied. Metre 36
41.31 Laying of one number single core H.T armoured /
unarmoured power cable 11kV grade of size not
exceeding 150 Sq.mm on wall / pole etc. as required. Metre 63
41.32 Laying of one number single core H.T armoured /
unarmoured power cable 33kV grade of size not
exceeding 150 Sq.mm on wall / pole etc. as required.
Metre 22
41.33 Laying of one number 3 core H.T armoured / unarmoured
power cable of grade exceeding 1.1kV but not exceeding
11kV of size not exceeding 150 Sq.mm direct in ground
including excavation in all soil / murrum / soft rock, sand
cushioning, excluding protective covering and refilling the
trench etc. as required. Metre 188
41.34 Laying of one number 3 core H.T armoured / unarmoured
power cable of grade 33kV of size not exceeding 150
Sq.mm direct in ground including excavation in all soil /
murrum / soft rock, sand cushioning, excluding protective
covering and refilling the trench etc. as required
Metre 19791
41.35 Laying of one number additional 3 core H.T armoured /
unarmoured power cable of grade exceeding 1.1kV but not
exceeding 11kV of size not exceeding 150 Sq.mm direct in
ground in the same trench in one tier horizontal formation
including sand cusioning, excluding protective covering
and refilling the trench as required. Metre 130

SOR ELECTRICAL 2014/CHAPTER-41

Page 91 of 114
41.36 Laying of one number additional 3 core H.T armoured /
unarmoured power cable 33kV grade of size not
exceeding 150 Sq.mm direct in ground in the same trench
in one tier horizontal formation including sand cushioning,
excluding protective covering and refilling the trench etc.
as requied. Metre 139
41.37 Laying of one number 3 core H.T armoured / unarmoured
power cable of grade exceeding 1.1kV but not exceeding
11kV of size not exceeding 150 Sq.mm in the existing
RCC / Hume / Stoneware / G.I. Pipe / surface in existing
trench as required. Metre 52
41.38 Laying of one number 3 core H.T armoured / unarmoured
power cable of grade exceeding 1.1kV but not exceeding
11kV of size not exceeding 150 Sq.mm. in the existing
masonary open duct as requied.
Metre 52
41.39 Laying of one number 3 core H.T armoured / unarmoured
power cable 11kV grade of size not exceeding 150 Sq.mm
on wall / pole etc. as required.
Metre 108
41.40 Laying of one number 3 core H.T armoured / unarmoured
power cable 33kV grade of size not exceeding 150 Sq.mm
in the existing RCC / Hume / Stoneware / G.I. Pipe /
surface in existing trench as required.
Metre 52
41.41 Laying of one number 3 core H.T armoured / unarmoured
power cable 33kV grade of size not exceeding 150
Sq.mm. in the existing masonary open duct as requied. Metre 52
41.42 Laying of one number 3 core H.T armoured / unarmoured
power cable 33kV grade of size not exceeding 150 Sq.mm
on wall / pole etc. as required. Metre 52
41.43 Laying of one number armoured / unarmoured cable 1.1kV
grade of size not exceeding 25 Sq.mm on surface in
existing trench etc. as required. Metre 20
41.44 Laying of one number armoured / unarmoured cable
1.1kV grade of size exceeding 25 Sq.mm but not
exceeding 120 Sq.mm on surface in existing trench etc.
as required. Metre 34
41.45 Laying of one number armoured / unarmoured cable
1.1kV grade of size exceeding 120 Sq.mm but not
exceeding 400 Sq.mm on surface in existing trench etc.
as required. Metre 43
41.46 Excavation of the trenches in Hard Rock not exceeding 1.5
metre in width and lift upto 1.5 metre including getting out
the excavated metal and disposal of surplus excavated
soil/metal as directed within the lead of 50 metre (without
blasting) Cu. Mtr. 50692

SOR ELECTRICAL 2014/CHAPTER-41

Page 92 of 114
41.47 Laying of one number armoured / unarmoured cable 1.1kV
grade of size not exceeding 25 Sq.mm on wall/truss with
approved type of iron clamps etc. as required. Metre 40
41.48 Laying of one number armoured / unarmoured cable
1.1kV grade of size exceeding 25 Sq.mm but not
exceeding 120 Sq.mm on wall/truss with approved type of
iron clamps etc. as required.
Metre 90
41.49 Laying of one number armoured / unarmoured cable
1.1kV grade of size exceeding 120 Sq.mm but not
exceeding 400 Sq.mm on wall/truss with approved type of
iron clamps etc. as required.
Metre 105
41.50 Laying of underground cable armoured./ unarmoured as
per specification in air suspended on existing approved
type of iron clamps, G.I wire 7/1.6mm & shackle insulator /
insulated strip complete.
41.50.1 1/2 / 3 / 4 Core cable up to 16 Sq.mm Metre 11
41.50.2 1 / 2 / 3 / 3 / 4 Core cable 25 Sq.mm to 120 Sq.mm Metre 20
41.50.3 1 / 2 / 3 / 3 / 4 Core cable 150 Sq.mm and above Metre 34
41.51 Laying of cement concrete or approved type of cable
cover/flag stone over L.T. / H.T. cable & refill trench as per
specification. Metre 11
41.52 Supply of approved type cable cover flag stone 200mm
width & 32mm to 50mm thick of required length inclusive
of transport as required. Metre 45
41.53 Supply & Fixing Cable Route Marker round / square size
100mm, 5mm. Thick, G.I. Plate duly bolted/welded on
35mm x 35mm x 5mm angle iron 60cm long including
excavation, grouting in cement concrete 1:2:4 (1cement
and 2 coarse sand :4 graded stone aggregate 20mm
nominal size) foundation of size 20cm x 20cm x 30cm duly
embedded in ground 30cm depth or as required. Each 250
41.54 Supply and erection of hot dip G.I. cable tray perforation
not more than 17.5% for specific dimensions along with
tees, bends.. The cable tray shall be hang from ceiling/
fixed to wall with necessary angle/flat iron / hanging rod,
for ceiling suspensions, clamps, anchor fastner, nuts,
bolts, washers, not mor than 1.5 mtr. apart complete as
per specification to complete the job. The tray shall be as
follows :-
41.54.1 100 x 50 mm x 1.6mm thick per Mtr 495
41.54.2 150 x 50 mm x 1.6mm thick per Mtr 572
41.54.3 300 x 50 mm x 1.6mm thick per Mtr 844
41.54.4 450 x 50 mm x 2 mm thick per Mtr 1296
41.54.5 600 x 50 mm 2 mm thick per Mtr 160393

SOR ELECTRICAL 2014/CHAPTER-41

Page 93 of 114
CHAPTER-42 (External)

EXTERNAL ELECTRIFICATION AND OVERHEAD LINES


S.No. Description of Item Unit Rate
SUPPORT FOR OVER HEAD LINE
42.1 Supply of support for overhead line Rail pole of I.S.
standard including base plate, welding, drilling of required
hole etc. complete as required.
42.1.1 Rail pole standard weight 60 kg/per metre Metre 4116
42.1.2 Rail pole standard weight 52 kg/per metre Metre 3568
42.2 Supply of support for overhead line RS joist /'H' Beam of
I.S. standard including drilling of required hole etc. complete
as required.
42.2.1 R.S. Joist 100x200-25.4 kg/per metre Metre 1678
42.2.2 R.S. Joist 175 x 85 - 19.3 kg/per metre Metre 1275
42.2.3 R.S. Joist 150 x 100 - 17 kg/per metre Metre 1123
42.2.4 R.S. Joist 150 x 80 - 14.9 kg/per metre Metre 984
42.2.5 R.S. Joist 125 x 75 - 13 kg/per metre Metre 859
42.2.6 H - Beam 152 x 152mm, Std weight 37.1 Kg / Mtr Metre 2545
42.3 Supply of steel tubular pole swaged type as per IS:2713-
1980 Complete with base plate and top Canopy
42.3.1 410 SP-2 - 7.00 metre Each 7968
42.3.2 410 SP-5 - 7.50 metre Each 8623
42.3.3 410 SP-8 - 7.50 metre Each 11242
42.3.4 410 SP-11 - 8.00 metre Each 9059
42.3.5 410 SP-14 - 8.00 metre Each 12115
42.3.6 410 SP-17 - 8.50 metre Each 9714
42.3.7 410 SP-20 - 8.50 metre Each 12552
42.3.8 410 SP-23 - 8.50 metre Each 16154
42.3.9 410 SP-26 - 9.00 metre Each 10042
42.3.10 410 SP-29 - 9.00 metre Each 13643
42.3.11 410 SP-32 - 9.00 metre Each 16809
42.3.12 410 SP-35 - 9.50 metre Each 14080
42.3.13 410 SP-38 - 9.50 metre Each 17464
42.3.14 410 SP-41 - 10.00 metre Each 14735
42.3.15 410 SP-44 - 10.00 metre Each 18337
42.3.16 410 SP-47 - 10.00 metre Each 24122
42.3.17 410 SP-50 - 11.00 metre Each 1604594

SOR ELECTRICAL 2014/CHAPTER-42

Page 94 of 114
42.3.18 410 SP-53 - 11.00 metre Each 19974
42.3.19 410 SP-56 - 11.00 metre Each 26305
42.3.20 410 SP-59 - 12.00 metre Each 21502
42.3.21 410 SP-62 - 12.00 metre Each 28269
42.3.22 410 SP-65 - 12.00 metre Each 34163
42.3.23 410 SP-68 - 13.00 metre Each 30670
42.3.24 410 SP-71 - 13.00 metre Each 36346
42.3.25 410 SP-73 - 14.50 metre Each 34054
42.3.26 410 SP-76 - 14.50 metre Each 41476
42.3.27 410 SP-77 - 16.00 metre Each 37219
42.3.28 410 SP-80 - 16.00 metre Each 45405
42.3.29 410 SP-10 (Bend type) 8.00 metre Each 7640
42.3.30 410 SP-16 (Bend type) 8.50 metre Each 8186
42.3.31 410 SP-25 (Bend type) 9.00 metre Each 8514
42.3.32 410 SP-34 (Bend type) 9.50 metre Each 13316
42.3.33 410 SP-40 (Bend type) 10.00 metre Each 13971
42.3.34 410 SP-49 (Bend type) 11.00 metre Each 15281
42.4 Supplying of prestressed cement concrete (PCC) pole
conforming to IS: 785 at work site including required
transportation.
42.4.1 PCC pole 8 mtrs. Long 140 kg Each 2033
42.4.2 PCC pole 9.1 mtrs. Long 280 kg Each 3812
42.5 Supplying and drawing All Aluminum Alloy conductor
(AAAC) of approved make confirming to IS 398-1979 Pt. IV,
including binding at existing insulator, jointing, jumpering,
tearing off, connecting etc. as required including clearing of
obstacles (if any)
42.5.1 AAAC 0.03 sq inch (34 Sq.mm Al. EQ. ) - (Weasel) Km. 30876
42.5.2 AAAC 0.05 sq inch (55 Sq.mm Al. EQ. ) - (Rabbbit) Km. 51356
42.5.3 AAAC 0.075 sq inch (80 Sq.mm Al. EQ. ) - (Raccoon) Km. 64688
42.5.4 AAAC 0.1 sq inch (100 Sq.mm Al. EQ. ) - (Dog) Km. 77891
42.6 Supplying and drawing of stranded Aluminium Conductor
Steel Reinforced (ACSR) confirming to IS:398-1976 of
approved make, stringing, making off complete with binding
at existing insulator, jointing, jumpering, tearing off,
connecting etc. as required and clearing of obstacles (if
any) etc.
42.6.1 ACSR 0.02 Sq inch (20 Sq.mm Al. EQ. ) - (Squirrel) Km. 32227
42.6.2 ACSR 0.03 sq inch (34 Sq.mm Al. EQ. ) - (Weasel) Km. 39602
42.6.3 ACSR 0.05 sq inch (55 Sq.mm Al. EQ. ) - (Rabbit) Km. 49132
42.6.4 ACSR 0.075 sq inch (80 Sq.mm Al. EQ. ) - (Raccoon) Km. 73831
42.6.5 ACSR 0.1 sq inch (100 Sq.mm Al. EQ. ) - (Dog) Km. 8934695
42.7 Supplying and fixing guard insulator or split insulator

SOR ELECTRICAL 2014/CHAPTER-42

Page 95 of 114
complete:
42.7.1 25x25mm Pair 21
42.7.2 37x37mm Pair 26
42.7.3 50x50mm Pair 33
42.8 Supplying and drawing guard wire/earth wire/bearer wire
13mm2 (4mm. Dia) G.I. including stringing, binding at
existing insulators or brackets, jointing, jumpering,
connecting & cradle etc. as required and clearing of
obstacles (if any) Km. 14690
42.9 Supplying and drawing guard wire/earth wire/bearer wire
18.62 mm2 (4.87mm. Dia / 6swg) G.I. including stringing,
binding at existing insulators or brackets, jointing,
jumpering, connecting & cradle etc. as required and clearing
of obstacles (if any) Km. 17198
42.10 Supplying and drawing G.I. bearer wire 7/1.6mm including
stringing, binding at existing brackets / pole, etc. for cable
support in air as required and clearing of obstacles (if any) PM 17
42.11 Supplying and erection of guards for existing overhead lines
as required including split insulator required as per
specification:
42.11.1 Cradle type Each 25
42.11.2 Hexagonal type Each 18
42.11.3 Ring type Each 16
42.12 Supplying and erection of water tight terminal box made of
16 SWG M.S. Sheet (1.6mm thick) i/c rubber gasket of
required size suitable for kit kat/ MCB/ Switch including 2
Nos. pole clamp of M.S. flat iron size 32x3mm, nut and
bolts, 4 Pole epoxy connector nut & bolt type, 30Amp.,
500Volt. The box shall be powder coated. Excluding the
cost of the Kit Kat/MCB/Switch complete as per
specification.
42.12.1 20x15x10Cms. Each 730
42.12.2 30x20x10 Cms. Each 971
42.13 Erection of RS Joist pole / 'H' Beam / steel tubular / steel rail
pole of length 7 metres but not exceeding 10 metres in
cement concrete 1:3:6 (1 cement : 3 core sand: 6 graded
stone aggregate 40mm nominal size) base, foundation,
muffing including excavation and back refilling etc. as
required. Each 3316
42.14 Erection of RS Joist pole / 'H' Beam / steel tubular / steel rail
pole of length exceeding 10 metres but not exceeding 13
metres in cement concrete M-10 (1 cement:3 core sand: 6
graded stone aggregate 40mm nominal size) base,
foundation, muffing including excavation and back refilling
etc. as required. Each 402796

SOR ELECTRICAL 2014/CHAPTER-42

Page 96 of 114
42.15 Erection of R.C.C./P.C.C. pole of length 8 metres but not
exceeding 11 metres in brick ballast and ramming the
foundation including excavation and refilling etc.as required. Each 1555
42.16 Erection of metallic street light pole length upto 2 metres in
cement concrete M-10 (1cement:3coarse sand:6 graded
stone aggregate 40mm nominal size) foundation with
cement concrete coller of size 0.4 metres dia x 0.3 metres
height to accommodate the looping type cable end box
including excavation and refilling etc. as required.
Each 1027
42.17 Erection of metallic street light pole length 3 metres but not
exceeding 6 metres in cement concrete M-10
(1cement:3coarse sand:6 graded stone aggregate 40mm
nominal size) foundation with cement concrete coller of size
0.4 metres dia x 0.5 metres height to accommodate the
looping type cable end box including excavation and refilling
etc. as required. Each 1935
42.18 Erection of RS Joist pole / 'H' Beam / steel tubular / steel rail
pole strut in cement concrete 1:3:6 (1cement:3coarse sand:
6 aggregate 40mm nominal size) foundation including
excavation and refilling and secured with holding clamps,
nuts and bolts, etc. as required.
Each 2844
42.19 Erection of RCC/PCC pole strut in brick ballast and
ramming the foundation including excavation and refilling
and secured with holding clamps nuts and bolts etc. as
required. Each 1608
42.20 Supplying and erection of stay set complete (Galvanized)
19mm. Dia x 1.8 metre long stay rod anchor plate of size
300 mm x 300 mm x7.5mm, thimble, stay clamps, turn
buckle (19mm dia x 600mm),7/4.00mm dia G.I. Stay wire
etc. in cement concrete M-10 (1 Cement : 3 Coarse sand :
6 graded stone aggregate 40mm nominal size) foundation
including excavation and refilling etc. as required.
Each 3906
42.21 Supplying and erection of stay set complete (Galvanized)
with 16mm dia x1.8 metre long stay anchor plate of size
200mm x 200mm x 6.0mm, thimble, stay clamps, turn
buckle 19mmx600mm, 7/3.15mm dia G.I. stay wire etc. in
cement concrete M-10 (1 Cement : 3 Coarse and : 6
granded stone aggregate 40mm nominal size) foundation
including excavation and refilling etc. as required.
Each 313097

SOR ELECTRICAL 2014/CHAPTER-42

Page 97 of 114
42.22 Supplying and erection of stay set complete with
19/20mm.dia 1.8 metre long stay rod, turn buckle, ancher
plate of size 300mm x 300mm x 7.5mm, thimble, stay
clamps, bow tightener, 7/4.00 dia G.I. stay wire etc. in
cement concrete M-10 (1 Cement : 3 Coarse and : 6
granded stone aggregate 40mm nominal size) foundation
including excavation and back refilling etc. as required.
Each 3775
42.23 Supplying and erection of stay set complete with 16mm.dia
1.8 metre long stay rod, turn buckle, anchor plate of size
200mm x 200mm x 6.0mm, thimble ,stay clamps, bow
tightener, 7/3.15 dia G.I. stay wire etc. in cement concrete
M-10 (1 Cement : 3 Coarse and : 6 graded stone aggregate
40mm nominal size) foundation including excavation and
back refilling etc. as required.
Each 2994
42.24 Erection of stay set complete in cement concrete M-10 (1
Cement : 3 coarse sand : 6 graded stone aggregate 40mm
nominal size) foundation including excavation and back
refilling etc. as required.
Each 1818
42.25 Supplying and erection of bow stay set complete
(galvanized) with 19mm dia x 1.8m long stay rod, anchor
plate of size 300mmx300mm x 7.5mm, thimble, stay
clamps, turn buckle 19mmx600mm, 7/4.00mm dia G.I. stay
wire and bow tightener, etc. in cement concrete M-10 ( 1
Cement : 3 coarse sand : 6 graded stone aggregate 40mm
nominal size) foundation including excavation and back
refilling and also with 0.6m long brace of size 50mmx
50mmx6mm angle iron with 50mm dia pulley fixed at one
end of the brace as required. Each 4185
42.26 Supplying and erection of bow stay set complete
(galvanized) wiith 16mm dia. X 1.8m long stay rod, anchor
plate of size 200mmx200mmx6.0mm, thimble, stay clamps,
turn buckle 19mmx600mm, 7/3.15 mm dia G.I. Stay wire
and bow tightener, etc. in cement concrete M-10 (1cement :
3 coarse sand : 6 graded stone aggregate 40mm nominal
size) foundation including excavation and back refilling and
also with 0.6m long brace of size 50mmx50mmx6mm angle
iron with 50mm dia pulley fixed at one end of the brace as
required. Each 340898
42.27 Supplying and erection of bow stay set complete with 19mm
dia x 1.8m long stay rod, anchor plate of size
300mmx300mm x 7.5mm, thimble, stay clamps, turn buckle
19mmx600mm, 7/4.00mm dia G.I. stay wire and bow
tightener, etc. in cement concrete M-10 ( 1 Cement : 3
coarse sand : 6 graded stone aggregate 40mm nominal
size) foundation including excavation and back refilling and
also with 0.6m long brace of size 50mmx 50mmx6mm angle Each 4054

SOR ELECTRICAL 2014/CHAPTER-42

Page 98 of 114
iron with 50mm dia pulley fixed at one end of the brace as
required.
42.28 Supplying and erection of bow stay set complete wiith
16mm dia. X 1.8m long stay rod, anchor plate of size
200mmx200mmx6.0mm, thimble, stay clamps, turn buckle
19mmx600mm, 7/3.15 mm dia G.I. Stay wire and bow
tightener, etc. in cement concrete M-10 (1cement : 3 coarse
sand : 6 graded stone aggregate 40mm nominal size)
foundation including excavation and back refilling and also
with 0.6m long brace of size 50mmx50mmx6mm angle iron
with 50mm dia pulley fixed at one end of the brace as
required. Each 3239
42.29 Supplying and erection of 50mm x 65mm shackle insulator
with G.I. bolts, nuts and straps etc. as required. Each 71
42.30 Supplying and erection of 75mm x 90mm shackle insulator
with G.I. bolts, nuts and straps etc. as required. Each 78
42.31 Supplying and erection of 100mmx110mm shackle insulator
with G.I. bolts, nuts and straps etc. as required. Each 84
42.32 Supplying and erection of Aluminium Knob / bobin with nut,
bolts & straps etc. as required. Each 93
42.33 Supplying and fixing of 19mm/20mm dia. M.S. pipe 1 mtrs.
In length for CFL / LED street light / Bulkhead / water tight
bracket including bending to shape and wiring with
1.5sqmm W.P./PVC wire etc. as required.
Each 245
42.34 Supplying and fixing of 19mm/20mm dia. G.I. pipe 2 mtrs.
Long for CFL / LED street light / Bulkhead / water tight
bracket including bending to shape and wiring with
1.5sqmm W.P./PVC wire etc. as required.
Each 365
42.35 Supplying and fixing of 32mm dia. X 2.00 mtr. Long G.I.
pipe (Medium class) bracket for mounting of fluorescent /
S.V/ M.H/ L.E.D Lamp street light fittings on poles including
bending the pipe to the required shape and wiring with
1.5Sq.mm W.P. / PVC wire etc. as required.
Each 601
42.36 Supply, fabrication and erection of Angle/Chanel/Flat iron
fitting for over head line & sub-station etc such as 'D'
bracket, cross arms, top clamp, 'V' cross arms,
Back/Support clamps or other similar work etc. including
nut bolts of required size, making holes, fabrication,
welding, cutting, etc. and painting with one coat of red oxide
paint & two coat of aluminium paint as required as per
specification. Kg. 8099

SOR ELECTRICAL 2014/CHAPTER-42

Page 99 of 114
42.37 Labour charges for erection of Angle/Chanel/Flat iron fitting
for over head line & sub-station etc such as 'D' bracket,
cross arms, top clamp, 'V' cross arms, Back/Support clamps
or other similar work etc. including nut bolts of required
size, as required as per specification. Kg. 7
42.38 Supplying and erection of 11kV Porcelain pin insulator
complete with long steel head G.I. pin, nut, washer etc. as
required. Each 268
42.39 Supplying and erection of 11kV Porcelain disc insulator for
11kV overhead lines with galvanized insulator fittings, ball
and socket type, and complete with galvanized strain clamp,
bolts, nuts washer etc. as required.
Each 497
42.40 Supplying and erection of 33kV Porcelain pin insulator
complete with long steel head G.I. pin, nut, washer etc. as
required Each 503
42.41 Supplying and erection of a set of three 11kV porcelain disc
insulators for 33kV overhead lines with galvanized insulator
fittings, ball and socket type, and complete with galvanized
strain clamp, bolts, nuts, washers etc. as required.
Each 1212
42.42 Supplying and erection of a set of four 11kV porcelain disc
insulators for 33kV overhead lines with galvanized insulator
fittings, ball and socket type, and complete with galvanized
strain clamp, bolts, nuts, washers etc. as required.
Each 1788
42.43 Labour for erection of 11/33kV Porcelain pin insulator
complete with hardware as required. Each 91
42.44 Labour for erection of 11kV Porcelain disc insulator for 11kV
overhead lines complete with hardware as required. Each 91
42.45 Labour for erection of a set of three/ four 11kV porcelain
disc insulators for 33kV overhead lines complete with
hardware as required. Each 219
42.46 Supplying and erection of 11kV (5 KN) Polymer pin insulator
complete with long steel head G.I. pin, nut, washer etc. as
required. Each 295
42.47 Supplying and erection of 11kV (45 KN) Polymer disc
insulator for 11kV overhead lines with galvanized insulator
fittings, ball and socket type, and complete with galvanized
strain clamp, bolts, nuts washer etc. as required.
Each 404
42.48 Supplying and erection of 33kV (10 KN) Polymer pin
insulator complete with long steel head G.I. pin, nut, washer
etc. as required Each 430100
42.49 Supplying and erection of 33kV (45 KN) Polymer disc
insulators for 33KV overhead lines with galvanized insulator
fittings, ball and socket type, and complete with galvanized
strain clamp, bolts, nuts, washers etc. as required.
Each 661

SOR ELECTRICAL 2014/CHAPTER-42

Page 100 of 114


42.50 Labour for erection of 11/33kV Polymer pin insulator
complete with hardware as required. Each 91
42.51 Labour for erection of 11/33kV Polymer disc insulators for
11/33KV overhead lines complete with hardware as
required. Each 146
42.52 Supplying and erection of single piece non linear resistor
type lighting arrestor (Set of 3 Nos) for 3 wire, 11kV
overhead lines/sub-station with rated voltage of 9kV (rms)
with a nominal discharge current rating of 5 KA and
complete with galvanized clamping arrangement, G.I. bolts,
nuts, washer etc. as required. Set 3391
42.53 Supplying and erection of single piece non-linear resistor
type lightning arrestor (Set of 3 Nos.) for 3 wire, 33kV
overhead lines/sub-station with rated voltage of 30kV (rms)
with a nominal discharge current rating of 5 KA and
complete with galvanized clamping arrangement, G.I. bolts,
nuts, washer etc. as required. Set 31467
42.54 Supplying and erection of single piece non linear resistor
polymer type lighting arrestor (Set of 3 Nos) for 3 wire, 11kV
overhead lines/sub-station with rated voltage of 9kV (rms)
with a nominal discharge current rating of 10 KA and
complete with galvanized clamping arrangement, G.I. bolts,
nuts, washer etc. as required.
Set 3643
42.55 Supplying and erection of single piece non-linear resistor
polymer type lightning arrestor (Set of 3 Nos.) for 3 wire,
33kV overhead lines/ sub-station with rated voltage of 27kV
(rms) with a nominal discharge current rating of 10 KA and
complete with galvanized clamping arrangement, G.I. bolts,
nuts, washer etc. as required.
Set 36006
42.56 Supplying installing, testing & commissioning of outdoor
H.T., AB switch assembly set gang operated with brass
contact parts, including required GI pipe operating rod,
handle & locking arrangement on On-Off position
conforming to IS complete with required material and
installing on existing DP structure to complete the job as
required as per specification.(Set of 3 nos.)
42.56.1 11 kV, 400A. set 6843
42.56.2 33kV, 600A. set 21291
42.57 Supplying installing, testing & commissioning D.O. fuse
assembly with brass part contact for 33 or 11/0.4 KV DP
Structure set of 3 Nos. with fuse barrel i/c required fuse
element & other materials as per specification on existing
D.P. structure as required.101
42.57.1 11kV set 3275
42.57.2 33kV set 14485

SOR ELECTRICAL 2014/CHAPTER-42

Page 101 of 114


42.58 Supplying & replacement of D.O. fuse barrel with brass
parts for 33 or 11 KV i/c required fuse element according to
load as per specification on existing D.P. structure as
required.
42.58.1 11kV Each 295
42.58.2 33kV Each 769
42.59 Supplying & replacement of D.O. fuse barrel for 33 or 11 KV
as per specification on existing D.P. structure as required.
42.59.1 11kV 208
42.59.2 33kV 249
42.60 Supplying & replacement of D.O. fuse element according to
load for 33 or 11 KV as per specification on existing D.P.
structure as required.
42.60.1 11kV 66
42.60.2 33kV 79
42.61 Supply & fixing anti climbing device with 2 ply G.I. barbed
wire 1 Kg. per pole complete as per specification. Each 126
42.62 Supply, laying and fixing of G.I. earth coil of 4mm dia G.I.
wire having 120 turns of nearly 50mm dia. and 3 mt. long
tail in existing pit duly earthed with pole etc complete as
required as per specification.
Each 220
42.63 Supplying and fixing 33/11/0.4 KV enamel coated danger
board size 200x250mm with clamp on existing HT/LT
structure / poles. Each 148
42.64 Supplying, installing, testing and commissioning of 11/0.4
K.V. 3 Phase 50 Cycle oil immersed, naturally cooled, out
door type transformer connected delta on H.T. side and
star on L.T. side, hand operated off load Tap changer
switch above 100 kVA, oil conservator with drain valve, plug
63 KVA and above, dehydrating silica gel breather on eye
level, rating and diagram plate, two earthing terminal, lifting
lugs, oil level gauge, drain valve with plug, temperature not
exceeding 50C on load, oil filling hole with plug, four
unidirectional roller, arcing horns, explosion vent, terminal
arrangement bushing on H.V. side and cable box on LV
side, first filling of oil upto desired level and transformer
installing on existing structure with all required materials
arrangement as required as per IS specification. Marked ISI
& 3 Star rating
42.64.1 Aluminium wound
42.64.1.1 25 kVA Each 82986
42.64.1.2 63 kVA Each 142093
42.64.1.3 100 kVA Each 200006102
42.64.1.4 200 kVA Each 336138

SOR ELECTRICAL 2014/CHAPTER-42

Page 102 of 114


42.64.2 Copper wound
42.64.2.1 200 kVA Each 403804
42.64.2.2 315 kVA Each 656083
42.64.2.3 500 kVA Each 688687
42.65 Supplying, installing, testing and commissioning of 33/0.4
K.V. 3 Phase 50 Cycle oil immersed, naturally cooled, out
door type transformer connected delta on H.T. side and
star on L.T. side, hand operated off load Tap changer
switch above 100 KVA, rating and diagram plate, two
earthing terminal, lifting lugs, oil level gauge, drain valve
with plug, temperature not exceeding 50C on load, oil
conservator with drain plug, oil filling hole with plug,
dehydrating silica gel breather on eye level, four
unidirectional roller, arcing horns, explosion vent, terminal
arrangement bushing on H.V. side and cable box on LV
side, first filling of oil up to desired level and transformer
installing on existing structure with all required materials
arrangement as required as per IS specification. Marked ISI
& 3 Star rating
42.65.1 Copper wound
42.65.1.1 100 KVA Each 363434
42.65.1.2 200 KVA Each 479044
42.65.1.3 315 KVA Each 792148
42.65.1.4 500 KVA Each 880667
42.66 Supplying, installing, testing and commissioning of 33/0.4
K.V. 3 Phase 50 Cycle oil immersed, naturally cooled, out
door type transformer connected delta on H.T. side and
star on L.T. side, hand operated off load Tap changer
switch, rating and diagram plate, two earthing terminal,
lifting lugs, oil level gauge drain valve with plug,
temperature not exceeding 50C on load, temperature dial
gauge, bucholz relay, oil conservator with drain plug, oil
filling hole with plug, dehydrating silica gel breather on eye
level, four unidirectional roller, arcing horns, explosion vent,
terminal arrangement bushing on H.V. side and cable box
on LV side, first filling of oil up to desired level and
transformer installing on existing structure with all required
materials arrangements as required as per IS specification.
Marked ISI & 3 Star rating
42.66.1 Copper wound
42.66.1.1 630 KVA each 1064480
42.66.1.2 750 KVA each 1248293
42.66.1.3 1250 KVA each103 1658027

SOR ELECTRICAL 2014/CHAPTER-42

Page 103 of 114


42.67 Shifiting, erection, & commissioning of of 100/ 200 / 315 /
500 KVA (11/0.433 KV) distribution transformer on existing
structure including Bi-metallic clamp, ACSR/AAAC
Conductor i/c colour code sleeve, for connection from H.T.
Line to transformer as required as per specification.
each 8191
42.68 Supplying and fixing Limit switch with accessories &
arrangement on existing HT/LT structure / poles AB switch
handle for inter locking between distribution panel main
incoming LT switch gear/ system as required to complete
the job. each 1778
42.69 Supply & fixing fencing of chain link mesh 100 x 100 mm,
12 SWG GI wire for for D.P. structure electric sub-station
including single post of angle iron size 50x50x5mm, 2.5 mt
long should be provided up to 2.00 mt. apart or as required
.The panel frame with required angle iron/ flat iron members
/cross members including mesh welded in frame panel,
shall be erected between the post. The angle iron post shall
be erected in cement concrete 1:2:4 ( 20 mm graded metal )
foundation, including excavation of pit and refilling the same
. The fencing shall be provided with one entrance gate
including locking arrangement as required as per
specification. The height of fencing shall be 2 mt. above
ground level. Fencing shall be painted with required shade.
Sq.Mt 1110
42.70 Supply & fixing fencing of chain link mesh 100 x 100 mm,
12 SWG GI wire for electric sub-station switch yard
including single post of angle iron size 50x50x5mm, 2.5 mt
long should be provided up to 2.00 mt. apart or as required
with required angle iron/ flat iron members /cross members
for frame between the post & welded mesh including
cement concrete, excavation of pit and refilling the same .
The fencing shall be provided with one entrance gate
including locking arrangement as required as per
specification. The height of fencing shall be 2 mt. above
ground level. Fencing shall be painted with required shade. Sq.Mt 773
42.71 Supplying & fixing of Fire Extinguisher/Refills as per IS
specification
42.71.1 ABC type duly refilled 6 Kg & ready to use each 3616
42.71.2 ABC type duly refilled 4 Kg &ready to use each 3277
42.71.3 ABC type -Refill only- 6Kg each 1356
42.71.4 ABC type -Refill only- 4Kg each 1017
42.71.5 4 buckets set with sand, self supported M.S.stand i/c shed
duly painted with red colour as per IS. each 4407
42.72 Supply of Rubber mat 2 x 1.0Mtr, 1100V Tested each104 1582
42.73 Supply of Hand Gloves 11KV Tested pair 622
42.74 Supply of Hand Gloves 33KV Tested pair 938

SOR ELECTRICAL 2014/CHAPTER-42

Page 104 of 114


42.75 Supply of Fiber Discharge Rod I/C Connection copper Lead
Tested each 2995
42.76 Supply of Fiber D.O Operating Rod for 11 / 33KV Tested each 2656
42.77 Supply of First Aid Box complete with medicine & bandage
as per specification. set 565
42.78 Supply of shock instruction chart duly framed with glass, as
reqd. each 339
42.79 Supply and fixing transformer breather with silica gel
suitable for 100 -500 KVA as reqd. each 300
42.80 Supply and filling of new transformer oil of desired break
down value for topping as reqd. Ltr. 140
42.81 Filtration of transformer oil for 33/0.4 K.V., 11/0.4 K.V. 3
Phase 50 Cycle oil immersed, naturally cooled, distribution
transformer up to desired break down value. Ltr. 15
42.82 Designing and construction of Pedestal (Plinth) for
transformer of desired size including excavation in hard
rock/soft rock, base concrete 1:4:8, 20mm thick and
pedestal of RCC 1:2:4 including required tar steel
reinforcement for required height as per IE Rules from base
concrete including shuttering and finishing with 10mm thick
plaster in cement mortor 1:3 curing & white washing etc.
complete as per specifications. Cu. Mt. 8328
42.83 Collection and spreading of metal dust, Murom and 40mm
graded hard metal in sub-station yard or as required as
mentioned below -
42.83.1 (i) Metal Dust Cu. Mt. 860
42.83.2 (ii) Murom Cu. Mt. 602
42.83.3 (iii) Metal 40 mm Cu. Mt. 1087
42.84 Supplying & drawing / laying of PVC insulated XLPE Aerial
bunch power cable conductor H2/H4 grade Aluminium
Solid/stranded confirming to IS-7098 Part-ll, Alu. Alloy
messenger of approved make in Air with necessary material
as per specification of required size as mentioned below
42.84.1 11KV grade Arial Bunch Cable :-
42.84.1.1 3 x50 + 1 x 70 sq.mm. P.Mt. 911
42.84.1.2 3 x70 + 1 x 70 sq.mm. P.Mt. 1056
42.84.1.3 3 x95 + 1 x 80 sq.mm. P.Mt. 1233
42.84.1.4 3 x150 + 1 x 120 sq.mm. P.Mt. 1600
42.84.2 33KV grade Arial Bunch Cable :-105
42.84.2.1 3 X 50 sq.mm. P.Mt. 1579
42.84.2.2 3 X 95 sq.mm. P.Mt. 2002
42.84.2.3 3 X 150 sq.mm. P.Mt. 2459

SOR ELECTRICAL 2014/CHAPTER-42

Page 105 of 114


42.85 Supplying & drawing / laying of PVC insulated XLPE Aerial
bunch power cable conductor H2/H4 grade Aluminium
Solid/stranded confirming to IS-14255- 1995, Alu. Alloy
insulated messenger 1100 volts grade cable of approved
make in Air with necessary material as per specification of
required size as mentioned below
42.85.1 (i) Single Core cable( Insulated neutral messenger)
42.85.1.1 (a) 2x25 Sq.mm, 1x16( Insulated neutral messenger) P.Mt. 153
42.85.1.2 (b) 2x35 Sq.mm, 1x16( Insulated neutral messenger) P.Mt. 181
42.85.2 (ii) Single Core cable( Insulated neutral messenger)
42.85.2.1 (a) 3x25 Sq.mm, 1x16(St.Light), 1x35( Insulated neutral
messenger) P.Mt. 208
42.85.2.2 (b) 3x35 Sq.mm, 1x16(St.Light), 1x35( Insulated neutral
messenger) P.Mt. 211
42.85.2.3 (c) 3x50 Sq.mm, 1x16(St.Light), 1x35( Insulated neutral
messenger) P.Mt. 288
42.85.2.4 (d) 3x70 Sq.mm, 1x16(St.Light), 1x35( Insulated neutral
messenger) P.Mt. 390
42.85.2.5 (e) 3x95 Sq.mm, 1x16(St.Light), 1x50( Insulated neutral
messenger) P.Mt. 584
42.85.2.6 (f) 3x120 Sq.mm, 1x16(St.Light), 1x70( Insulated neutral
messenger) P.Mt. 703
42.85.2.7 (g) 3x150 Sq.mm, 1x35(St.Light), 1x95( Insulated neutral
messenger) P.Mt. 891
42.86 Supplying & fixing of Aerial bunch cable accessories
suspension clamps i/c required attachment for single core
cable of approved make on pole with clamp, necessary
material as per specification for required size.
Each 343
42.87 Supplying & fixing of Aerial bunch cable accessories
Tension clamps(Dead end) i/c required attachment for
single core cable of approved make in Air with clamp,
necessary material as per specification for required size.
Each 371
42.88 Supplying & fixing of waterproof Insulation Piercing
connector for Aerial bunch cable i/c required attachment for
single core cable of approved make in Air with necessary
material as per specification of required size as mentioned
below
42.88.1 Main: 16-95sq.mm, Tap: 1.5-50sq.mm Each 123
42.88.2 Main: 50-150sq.mm, Tap: 6-50sq.mm Each 153
42.89 Supplying & fixing of Spring loaded bus bar screw less
connector with enclosure of approved make including
required clamps, nut, bolt, connection, testing as per
specification to complete the job. 106

SOR ELECTRICAL 2014/CHAPTER-42

Page 106 of 114


42.89.1 Single Phase
42.89.1.1 1Ph, 1In+2Out Each 2144
42.89.1.2 1Ph, 1In+3Out Each 2204
42.89.1.3 1Ph, 1In+4Out Each 3190
42.89.1.4 1Ph, 1In+5Out Each 3365
42.89.1.5 1Ph, 1In+7Out Each 3541
42.89.1.6 1Ph, 1In+8Out Each 3668
42.89.2 Three Phase
42.89.2.1 3Ph, 1In+2Out Each 5194
42.89.2.2 3Ph, 1In+4Out Each 6352
42.89.2.3 3Ph, 1In+6Out Each 8334
42.89.2.4 3Ph, 1In+7Out Each 8566
42.89.2.5 3Ph, 1In+8Out Each 8797
42.90 Providing and erecting 12mt High Mast Lighting system
suitable to install 6 No. 2 x 400 w M.H / S.V flood light fitting
and control gear with integral Power tool, weight 340 kg.
comprising of 1 section of hot dipped galvanized materials
as per BSEN ISO 1461 thickness 3 mm, dia 100mm &
360mm for top and bottom respectively, stress fitting
arrangement on site with 350mm overlap dynamic loading
to withstand max wind pressure as per -IS 875 part III,
parameters for structural & foundation design must be taken
from Wind Tunnel test. Lightning protection of GI single
spike 800mm at top and at base inside compartment with
double internal lock with adequate size of MCB erected on
PVC board complete with base plate of 25mm thick 520mm
dia. and foundation bolts having 4 nos. bolts of 24mm dia,
750mm long (EN8 grade), Anchor plate 445 PCD, including
accessories viz.(1) Lantern carriage of 50 NB ERW class-B,
MS pipe covered with PVC sleeve suitable to carry 250kg.
load and upto 6 fittings symmetrically.(2) Trailing Copper
cable 5x2.5 sq.mm, EPR insulated PCP 107
Sheathed (3) Double Drum / 350Kg Winch having gear
53:1, oil bath (SAE90/140) arrangement. (4) 2 nos.
Stainless steel wire ropes 5mm dia (7/19) breaking load
capacity 1450 kg.x 2, (5) Integral power tool 3-phase, 0.75
HP 2m/min single speed. (6) Feeder pillar fabricated out of
14 SWG CRCA sheet and comprise of incoming MCB 32 A
TPN switch, HRC fuses, single dial timer, suitable size of
contactors for lighting and power tool, 2 nos. outgoing,
reversing switch for motor. (7) Foundation drawing, test
certificate and guarantee certificate shall be provided by
manufacturer. (Without fixture and lamp) each 332757

SOR ELECTRICAL 2014/CHAPTER-42

Page 107 of 114


42.91 Providing and erecting 16mt High Mast Lighting sytem
suitable to install upto 8 No. 2 x 250/ 400 w M.H / S.V flood
light and control gear with integral Power tool, weight 450
kg. comprising of 2 sections of hot dipped galvanized
materials as per BSEN ISO 1461 thickness 3 mm & 4 mm,
dia 150mm & 360mm for top and bottom respectively,
stress fitting arrangement on site with 500mm overlap
dynamic loading to withstand max wind pressure as per -IS
875 part III, parameters for structural & foundation design
must be taken from Wind Tunnel test. Lightning protection
of GI single spike 1200mm at top and at base inside
compartment having double internal lock with adequate size
of MCB erected on PVC board complete with base plate of
25mm thick 520mm dia. and foundation bolts having 6 nos.
bolts of 24mm dia 750 mm long (EN.8 grade) Anchor plate
445 PCD, including accessories viz. (1) Lantern carriage of
50 NB ERW class-B, MS pipe covered with PVC sleeve
suitable to carry 500kg. load and upto 8 fittings
symmetrically.(2) Trailing Copper cable 5x2.5 sq.mm, PVC
insulated PVC Sheathed (3) Double Drum 350Kg Winch
having gear 53:1, oil bath (SAE90/140) arrangement (4) 2
nos. Stainless steel wire ropes 5 mm dia (7/19) breaking
load capacity 1450 kg x 2, (5) Integral power tool 3-phase,
0.75HP 2m/min single speed .torque limiter up to 500 kg
adjustable (6) Single LED 300 Nos. aviation light (7)
Feeder pillar fabricated out of 14 SWG CRCA sheet and
comprise of incoming MCB 32 A TPN switch, HRC fuses,
single dial timer, suitable size of contactors for lighting and
power tool, 2 nos.outgoing, reversing switch for motor. (7)
Foundation drawing, test certificate and gurantee certificate
shall be provided by manufacturer. (Without fixture and
lamp) each108 447501

SOR ELECTRICAL 2014/CHAPTER-42

Page 108 of 114


42.92 Providing and erecting 20mt High Mast Lighting system
suitable to install upto 10 No. 2 x 250/ 400 w M.H / S.V flood
light and control gear with integral Power tool, weight 450
kg. comprising of 2 sections of hot dipped galvanized
materials as per BSEN ISO 1461 thickness 3 mm & 4 mm,
dia 150mm & 410mm for top and bottom respectively,
stress fitting arrangement on site with 500mm overlap
dynamic loading to withstand max wind pressure as per -IS
875 part III, parameters for structural & foundation design
must be taken from Wind Tunnel test. Lightning protection
of GI single spike 1200mm at top and at base inside
compartment having double thickness 3 mm & 4 mm, dia
150mm & 410mm for top and bottom respectively, stress
fitting arrangement on site with 500mm overlap dynamic
loading to withstand max wind pressure as per -IS 875 part
III, parameters for structural & foundation design must be
taken from Wind Tunnel test. Lightning protection of GI
single spike 1200mm at top and at base inside
compartment having double internal lock with adequate size
of MCB erected on PVC board complete with base plate of
25mm thick 570mm dia. and foundation bolts having 8 nos.
bolts of 30mm dia 850 mm long (EN.8 grade) Anchor plate
490 PCD, including accessories viz.(1) Lantern carriage of
50 NB ERW class-B ,MS pipe covered with PVC sleeve
suitable to carry 500kg. load and up to 10 fittings
symmetrically.(2) Trailing Copper cable 5x4.0 sq.mm, PVC
insulated PVC Sheathed (3) Double Drum 750Kg Winch
having gear 53:1, oil bath (SAE90/140) arrangement (4) 2
nos. Stainless steel wire ropes 6 mm dia (7/19) breaking
load capacity 2350 kg.x 2,(5) Integral power tool 3-phase,
1HP 2m/min single speed .torque limiter up to 500 kg
adjustable (6) 2 Nos. LED 300 Nos. aviation light (7)
Feeder pillar fabricated out of 14 SWG CRCA sheet and
comprise of incoming MCB 63 A TPN switch, HRC fuses,
single dial timer, suitable size of contactors for lighting and
power tool, 2 nos. outgoing, reversing switch for motor. (7)
Foundation drawing, test certificate and guarantee
certificate shall be provided by manufacturer. (Without
fixture and lamp) each 516348
42.93 Providing and erecting hot dipped galvanized octagonal
poles in single section made from 3mm thick sheet having
lockable weather proof flush door junction box complete
erected in an approved manner on provided foundation.
Suitable size & type of foundation bolts 4 nos. 'J' type (EN8
grade)
42.93.1 3 mtrs. Height 130 X 70mm A/F, 200x200x12mm base
plate, 4 nos X 16 x 450mm bolt each109 8125

SOR ELECTRICAL 2014/CHAPTER-42

Page 109 of 114


42.93.2 4 mtrs. Height 130 X 70mm A/F, 200x200x12mm base
plate, 4 nos X 16 x 450mm bolt each 10112
42.93.3 5 mtrs. Height 130 X 70mm A/F, 200x200x12mm base
plate, 4 nos X 16 x 450mm bolt each 12098
42.93.4 6 mtrs. Height 130 X 70mm A/F, 220x220x12mm base
plate, 4 nos. X 20 x 600mm bolt each 14797
42.93.5 7 mtrs. Height, 130 X 70mm A/F, 220x220x12mm base
plate, 4 nos. X 20 x 700mm bolt each 16783
42.93.6 8 mtrs. Height, 135 X 70mm A/F, 225x225x16mm base
plate, 4 nos. X 20 x 750mm bolt each 18988
42.93.7 9 mtrs. Height, 155 X 70mm A/F, 260x260x16mm base
plate, 4 nos. X 24 x 750mm bolt each 24908
42.93.8 10 mtrs. Height, 175 X 70mm A/F, 275x275x16mm base
plate, 4 nos. X 24 x 750mm bolt each 29403
42.94 Providing and fixing of sword canopy type single arm GI
bracket upto 2 Mtr. Long for 70mm A/F top octagonal pole each 3478
42.95 Providing and fixing of sword canopy type double arm GI
bracket upto 2 Mtr. Long for 70mm A/F top octagonal pole each 5645
42.96 Providing and fixing of ring carriage dia. not less than
600mm made of 50mm dia. GI pipe Light 'A' class for 70mm
A/F top octagonal pole with required clamps, nut, bolt etc as
required. each 2583
42.97 Providing and erecting black painted galvanized decorative
designer poles in different section, top 60mm dia., bottom
140mm dia. with gold colour painted ornamental cast
aluminium ring having lockable weather proof flush door
junction box in bottom section, base plate dia. 290mm
having 4 holes of 22mm dia. complete erected in an
approved manner on existing foundation. Suitable size &
type of foundation bolts 4 nos. X 16mm X 450mm 'J' type
(EN8 grade)
42.97.1 3 Mtr. Height each 31323
42.97.2 4 Mtr. Height each 34260
42.97.3 5 Mtr. Height each 43069
42.98 Designing & casting of Open raft shallow footing foundation
with M-20 cement concrete suitable for 12mtrs. High Mast
considering the safe soil bearing capacity at site as 10
T/sqm at 2mtrs. Depth including excavation, foundation nut
bolts in an approved manner. each 45000
42.99 Designing & casting of Open raft shallow footing foundation
with M-20 cement concrete suitable for 16mtrs. High Mast
considering the safe soil bearing capacity at site as 10
T/sqm at 2mtrs. Depth including excavation, foundation nut
bolts in an approved manner. each110 60000

SOR ELECTRICAL 2014/CHAPTER-42

Page 110 of 114


42.100 Designing & casting of Open raft shallow footing foundation
with M-20 cement concrete suitable for 20mtrs. High Mast
considering the safe soil bearing capacity at site as 10
T/sqm at 2mtrs. Depth including excavation, foundation nut
bolts in an approved manner. each 70000
42.101 Designing & casting with M-20 reinforcement cement
concrete foundation suitable for Octagonal poles
considering the safe soil bearing capacity at site as 10
T/sqm at 2 mtrs. Depth including excavation, foundation nut P.
bolts in an approved manner. Cu.M111 14435

SOR ELECTRICAL 2014/CHAPTER-42

Page 111 of 114


LIST OF APPROVED ELECTRICAL MATERIAL / ACCESSORIES TO BE USED
GROUP 'A'
S.No. ITEM MAKE REMARK
PVC insulated copper conductor , PVC Havell's , Finolex Anchor, standard,
1 insulated & Sheathed flexible copper polycab, HPL, RR Kabel,
conductor FR ISI marked
PVC insulated Telephone / Cat 6 / TV cable Havell's , Finolex, Anchor, standard,
2 polycab, RR Kabel, Legrand
ISI marked FR
BEC , Modi, Shrinath, Kent,
3 PVC conduit pipe ISI marked & accessories
Precision, Polycab,
PVC casing-N-capping ISI marked & Presto plast , Press fit, Shrinath,
4
accessories Modi, BEC, Precision,
5 Steel conduit pipe ISI marked & accessories BEC , AKG, Modi,
Non- Modular type flush type switch, socket , Anchor, SSK, HPL, CPL
6
ceiling rose, lamp holder , call bell,
Modular type flush type switch, socket , ceiling Legrand, Anchor Roma, C&S, L&T,
7 Wipro North West, HPL,
rose, lamp holder, call bell,
8 Phenolic laminated sheet Hylum, Anchor
9 MCB, Isolator, RCCB, RCBO, MCB-DB Legrand, L&T, C&S,
Finolex, Polycab, Havell's , RAVIN
Cables, Paramount, AEI, V-Mark,
10 XLPE insulated cable, Air Bunch Cable(ABC),
Gupta Power, Daimond Power, RR
Cable,
Philips, Bajaj, Crompton, osram,
11 GLS, CFL, SV,MH, Lamp
GEC,
Philips, Bajaj, Crompton, Wipro,
12 LED lamp osram, SYSKA
13 Luminaries SV, MH, CFL, FTL-T5 Philips, Bajaj, Crompton, Wipro,
Philips, Bajaj, Crompton, Wipro,
14 Luminaries LED,
SYSKA, Panasonic
15 GI pipe ISI Mark TATA, Swastik TT, Jindal, Surya
Grandlay , Bhopal Wires, Gupta
16 ACSR , AAAC conductor Power, Daimond Power,
17 Electronic ballast Philips, Bajaj, Crompton, Wipro,
Cromton , Bajaj, Usha, Orient,
18 Electric Ceiling fans
Havell's
Almonard, Crompton , Bajaj, Usha,
19 Wall mounting fan, Cabin fan, Exhaust fan,
Orient,
20 Steel tubular pole As per IS 2713-1980
21 Octagonal pole Bajaj, Philips, Valmont
22 High mast Bajaj, Philips, Valmont
23 Ornmental pole Bajaj, Dwarka, Homedec
Comet , Calter(National), Cosmos,
24 Cable gland Jainson, ascon, sigma
112

SOR ELECTRICAL 2014

Page 112 of 114


Annexure-1
Guide Line For Rewiring
1 The following provisions are being made for specified quarter
Details of Fans / Fixtures etc

S.No. Type of

Exhaust Fan Point


Ceiling Fan Point

Street light Point

Separate Socket

Socket on Same
Tube light Point

Bulk head Point

Call Bell Point


Qtr

Holder Point

Power Point

CFL 18 Watt
CFL 5 Watt
Board
Point
1 I- Type 2 3 1 6 1 0 2 2 4 1 3 4
2 H- Type 3 4 2 7 1 0 2 4 5 1 3 6
3 G- Type 4 5 2 8 2 2 3 5 6 1 3 7
4 F- Type 5 6 2 9 2 2 4 6 7 1 4 7

2 In Club housing including blocks, there shall be one pipe earthing. Hence
separate earthing will not be provided for each quarter.
3 Service line shall be taken in actually required length separately
4 Additional electrical point can be taken with the permission of Executive
Engineer
5 Extra required Fans, Fixtures etc can be taken with the permission of Executive
Engineer115