INSTALLATION AND MAINTENANCE INSTRUCTIONS

12 Clintonville Rd

FDM-1 Dual Monitor Module Northford, CT 06472-1653


(203) 484-7161

Specifications
Normal Operating Voltage: 15 to 32 VDC
Maximum Current Draw: 5.7 mA (LED on)
Average Operating Current: 750A (LED flashing)
EOL Resistance: 47K Ohms
Maximum IDC wiring resistance: 1,500 Ohms
Temperature Range: 32F to 120F (0C to 49C)
Humidity: 10% to 93% Noncondensing
Dimensions: 41/2 H x 4 W x 11/4 D (Mounts to a 4 square by 21/8 deep box.)
Accessories: SMB500 Electrical Box

Before Installing
This information is included as a quick reference installation avoid duplicate addressing of modules on the system.
guide. Refer to the control panel installation manual for detailed 3. Secure module to electrical box (supplied by installer), as
system information. If the modules will be installed in an existing shown in Figure 2A.
operational system, inform the operator and local authority that
Figure 1. Removing
the system will be temporarily out of service. Disconnect power to
Rotary Switch Stop:
the control panel before installing the modules.
NOTICE: This manual should be left with the owner/user of this
equipment.
9 67 8 9
0
General Description 8 4
5 10
11 1
3 12
The Dual Monitor Module is intended for use in intelligent, two 7
2 13
1 0 15 14 2
TENS
wire systems. It provides two independent 2-wire initiating device 6
8
3
6
circuits (IDC), at two separate, consecutive addresses. It is capable 4
5 2 4
of monitoring normally open contact fire alarm and supervisory ONES
0
ADDRESS
LOOP
devices, or either normally open or normally closed security de-
vices. The module has a single panel controlled red LED.
Compatibility Requirements A78-2318-13
To ensure proper operation, this module shall be connected to a
compatible Notifier system control panel (list available from Noti- Figure 2A. Module mounting:
fier).
Mounting
Mounts directly to 4 square electrical boxes (see Figure 2A). The
box must have a minimum depth of 21/8. Surface mounted elec-
trical boxes (SMB500) are available from Notifier.
Wiring Figure 2B:
NOTE: All wiring must conform to applicable local codes, or-
dinances, and regulations. This module is intended for
power limited wiring only. 7T
8
3
9
4 5 6 78
9
6 EN 21 1 0
1. Install module wiring in accordance with the job drawings and 1 0
LO S 0
OP 5 6 8 15 1 1 12 11
4 4 3
ON 2
ES 0
2
3
appropriate wiring diagrams. 0
1
AD
DR
ES
S
4

2. Set the address on the module per job drawings. 2


10
9

11
8

15 1 12
4 5 67

3
14 3

9
8 4
3

0
2
NS 1

7 SS

Note: Some panels support extended addressing. In order


E
8
TE

DR
6 AD
6
4

0
2

5 ON
ES

to set the module above address 99 on compatible systems,


carefully remove the stop on the upper rotary switch with
thumb in the direction shown in Figure 1.
Note: Monitor module L (using terminals 6 and 7) re-
sponds at the address set on the code switches. Monitor
A78-2611-19
module H (using terminals 8 and 9) will automatically re-
spond at the next higher address. For example, if the code
switches are set to 76, module L will respond at address 76
and module H will respond at address 77. Use caution to A78-2610-14

N500-75-00 1 I56-1463-02
www.PDF-Zoo.com
Figure 3. Typical 2-wire initiating circuit configuration, NFPA Style B:

)( )(
TO NEXT FROM PANEL OR
)+( )+( PREVIOUS DEVICE
DEVICE
TWO INITIATING DEVICE CIRCUITS (L & H),
EACH POWER LIMITED TO 230 A @ 12VDC MAX. MONITOR
MODULE CONNECT MODULES TO LISTED COMPATIBLE
NOTIFIER CONTROL PANELS ONLY
47 K EOL
RESISTOR H
ELR-47K
9
5
67 8 9
10
0 )( ALL WIRING SHOWN IS SUPERVISED AND POWER LIMITED
4 11
8 3 12 1
7
2 13
1 0 15 14 2
)+(
TENS
8
6 6 3
47 K EOL 5
4
4 COMMUNICATION LINE
L
2
0
RESISTOR LOOP
ONES
ADDRESS 32 VDC MAX.
ELR-47K SHIELDED-TWISTED PAIR
IS RECOMMENDED

ANY NUMBER OF UL LISTED CONTACT CLOSURE


DEVICES MAY BE USED. DO NOT MIX FIRE
ALARM INITIATING, SUPERVISORY, OR SECURITY MONITOR A (TERMINALS 6 & 7) RESPONDS AT ADDRESS
DEVICES ON THE SAME INITIATING DEVICE CIRCUIT. SET ON CODE SWITCHES. MONITOR B (TERMINALS 8 & 9)
RESPONDS AT NEXT HIGHER ADDRESS.
INSTALL CONTACT CLOSURE DEVICES PER
MANUFACTURERS INSTALLATION INSTRUCTIONS. A78-2280-39