You are on page 1of 7

SIPROTEC 5/

DIGSI 5 BASIC-Course
02 Basic function of SIPROTEC 5
www.siemens.com/poweracademy Copyright Siemens AG 2012. All rights reserved.
Basic function of SIPROTEC 5

SIPROTEC 5

Protection 21 87L 50 51 50BF 25 79

Measurement
A V f P Q cos A max
Metering
+kWh -kWh

Copyright Siemens AG 2012. All rights reserved.


Self Monitoring SW HW I=0
Feeder Monitoring SF6 loss Pick up CB Live time
Control Local Remode SLD
Data Acquisition Trip log Status log Alarm log
Fault Recording

Automation-Logic Bay Interlocking Sequences


Time Synchronization GPS IRIG B DCF 77 IEC 103
Communication IEC 103 IEC 61850 GOOSE
Security Safe CT Interlock Passwort
Test BI BO Interfase I-Simulation

02 Basic function of SIPROTEC 5


Version: D_03_Page 2 Siemens Power Academy TD
SIPROTEC 5/ DIGSI 5 Basic Course
SIPROTEC 5 Protection Application

SIPROTEC 5

Protection SIPROTEC 5 includes all protection functions for transmission and subtransmission networks

Measurement
SIPROTEC 5 is applicable for different substation designs
Metering Single, double and triple busbar designs
1,5 CB schemes, .

Copyright Siemens AG 2012. All rights reserved.


Self Monitoring

Feeder Monitoring Application templates are available for different schemes


Pre configuration reduces the engineering efforts
Control
User defined standards leads simplification and repeatability
Data Acquisition Copying of functions and setting between the devices

Fault Recording
The library concept increases the flexibility
Automation-Logic Required functions can easily be loaded into the device
A wide range of proven protection functions are available
Time Synchronization
Possible extensions are made simple (add stages, zones,..)
Communication
A clear functional structure (function groups) clusters the functions, allows flexible
Security
applications and guarantees correct operation
Test

02 Basic function of SIPROTEC 5


Version: D_03_Page 3 Siemens Power Academy TD
SIPROTEC 5/ DIGSI 5 Basic Course
SIPROTEC 5 Control and Automation

SIPROTEC 5

SIPROTEC 5 includes all functions for Control and Automation of transmission


Protection
and subtransmission networks
Measurement
CFC (continuous function chart) includes all elements for interlocking
Metering Local control on the device
Remote control through DIGSI

Copyright Siemens AG 2012. All rights reserved.


Self Monitoring
Remote control from the SSA through serial interface
Feeder Monitoring
Application templates are available with predefined interlocking
Control Pre configuration reduces the engineering efforts
User defined standardization
Data Acquisition

Fault Recording Complete Station interlocking through IEC61850 and GOOSE

Automation-Logic Automation solutions


Time Synchronization
Tap changer control
Intelligent load shedding (active power + frequency)
Communication Network changeover, stability supervision
Management of distributed generation in Smart Grid plants
Security

Test

02 Basic function of SIPROTEC 5


Version: D_03_Page 4 Siemens Power Academy TD
SIPROTEC 5/ DIGSI 5 Basic Course
SIPROTEC 5 Monitoring

SIPROTEC 5

Protection SIPROTEC 5 includes all functions for effective monitoring of transmission


and subtransmission network
Measurement

Metering
Self supervision
All internal hardware components and external interfaces, runtime of software

Copyright Siemens AG 2012. All rights reserved.


Self Monitoring Clear text indication (cause of failure and countermeasure)
Feeder Monitoring
Monitoring of primary equipment
Control
Operational log records process data with a time stamp (up to 2000 events)
Data Acquisition Monitoring of the system through measurement supervision (voltage and frequency, power
and load) and through measuring transducer (analogue 4 to 20 mA ) inputs
Fault Recording (SF6 loss, gas pressure, temperature,)
Automation-Logic
Powerful fault analysis
Time Synchronization
Fault recording with a high sampling rate and a long period (8 kHz & 20s or 1 kHz & 160 s)
Communication Trip log with 1 ms resolution and up to 1000 events

Security

Test

02 Basic function of SIPROTEC 5


Version: D_03_Page 5 Siemens Power Academy TD
SIPROTEC 5/ DIGSI 5 Basic Course
SIPROTEC 5 Communication

SIPROTEC 5

Netzleitstelle
Protection
Redundant interfacing to control center,

Measurement e.g. with DNP3, (black)

Metering
SICAM PAS SICAM PAS Connection to both substation systems

Copyright Siemens AG 2012. All rights reserved.


Self Monitoring
IEC 61850 (blue)

Feeder Monitoring
IEC 60870-5-103 (rot)

Control SIPROTEC 5 SIPROTEC 5


Separate connection to field level for

Data Acquisition GOOSE communication IEC 61850 (grn)

Fault Recording

Automation-Logic Separate connection to DIGSI 5 PC with

Ethernet IEC 61850


Time Synchronization

Communication

Security

Test
DIGSI 5

02 Basic function of SIPROTEC 5


Version: D_03_Page 6 Siemens Power Academy TD
SIPROTEC 5/ DIGSI 5 Basic Course
SIPROTEC 5 Communication

SIPROTEC 5

Protection
SIPROTEC 5 includes powerful communication functionality
Measurement Flexible communication modules standard hardware components (physical hardware is independent
of software)
Metering Support of standard communication protocols
IEC 61850; IEC 60870-5-103
DNPi 3.0,.

Copyright Siemens AG 2012. All rights reserved.


Self Monitoring
Flexible communication solutions are possible
Feeder Monitoring Double 103 protocol
Redundant topologies with SSA
Control Powerful protection data interface (for differential protection, data exchange in substation, DIGSI 5
communication)
Data Acquisition
Communication is the key feature of all applications
Fault Recording Smart grid means flexibility in communication
Automation-Logic
SIPROTEC 5 supports Cyber Security requirements
Present standards are fulfilled (NERC CIP, BDEW,)
Time Synchronization
DIGSI 5 communication with encryption and strong password access
Communication

Security

Test

02 Basic function of SIPROTEC 5


Version: D_03_Page 7 Siemens Power Academy TD
SIPROTEC 5/ DIGSI 5 Basic Course