You are on page 1of 11

MAINTENANCE

GENERAL REQUIREMENTS MAINTENANCE PLAN

The maintenance requirements for AHUs The following table ( see Table 1) gives
are shown below. The procedure is in the recommended maintenance intervals for
left-hand column, and the minimum the air handling unit. Intervals are base
required frequency is marked is described upon normal running conditions, in a
in the right-hand column. moderate climate, and assuming 24 hour
running. Units operating outside these
Refer to ANSI/ASHRAE Standard 62.1- guideline may require shorter or longer
2010 for startup and maintenance practices maintenance intervals.
related to achieving acceptable indoor air
quality. The maintenance interval periods are
stated, guidelines only. Any large
This documented program for regular deviations in the pattern of usage may
publication of including procedures for necessitate further maintenance attention.
timely, documented, consensus action on
requests for change to any part of the
standard. WARNING

STANDARD OPERATIONAL Disconnect electrical power and


PROCEDURES allow rotating parts to stop before
servicing the unit. Exercise caution if
All maintenance and repair process unit must be on for test or
implemented according to prescribed maintenance procedures. Failure to
procedures and SOPs : do so may result in injury or death
from electrical shock or moving part
Always coordinative with the leadership
in order to generate jobs as efficiently as
possible,

The scheduled maintenance, schedule WARNING


equipment and inspection equipment Disconnect electrical power prior to
specifications prepared so effective as access into fan or ductwork. Even
needed. when locked out electrically, fans
Completeness of materials that will be may cause injury or damage if the
used: materials cleaning fluid, cleaning impeller is subject to "windmilling".
cloth; if necessary, air compressor, The impeller should be secured to
inspected and sorted according to the physically restrict rotational
treatment procedure. movement can cause severe personal
injury or death.
disassembly tools and measuring
devices needed examined in order to work
properly and safely
PERIODIC MAINTENANCE Check damper linkages, set-screws and
blade adjustment for proper damper
Checklist The following checklist
operation.
describes the suggested maintenance
lnspect the control and power box wiring
schedule to maintain proper operation of
for secure connections and insulation.
the unit. Detailed procedures for
Rotate the fan wheel and check for
owneroperator maintenance checks are
obstruction in the fan housing. The wheel
given after this checklist
should not rub on the fan housing. Adjust
After 48 Hours Operation the center if necessary and tighten wheel
setscrews to the proper torque.
Fan and Direct drive Motor their Check condition of gasketing and
permanent tight. Readjust if not but dont insulation around unit, door and damper.
overtighten. Examine flex connections for cracks or
leaks. Repair or replace damage material.
Weekly
MAINTENANCE PLAN
Observe unit weekly for any change in
running condition and any unusual noise. The following table (see Table 1) gives
recommended maintenance intervals for
Every Month Or Weekly
the air handling unit. Intervals are base
Check air filters. Clean or replace if upon normal running conditions, in a
clogged or dirty. Change bag filters when moderate climate, and assuming 24 hour
pressure drop is till final resistance value. running.

Every Three to Six Months Units operating outside these guideline


may require shorter or longer maintenance
Check pulley on fan and motor. intervals.
Tighten electrical connection.
lnspect coils for dirt build-up or coil
freeze up

Every Year

lnspect the unit casing for corrosion. lf


damage is found, clean and repaint the
surface with a rust-resistant primer and
vinyl chlorinated lacquer.
Clean the fan wheels and fan shaft.
Remove rust with emery cloth and apply a
coat of LPS#3 or an equivalent.
lnspect the condensate drain pan and
drain line, remove sludge or foreign
materials that might obstruct proper
drainage. Remove obstacles.
Tabel 1 - Recommended Maintenance Intervals

36
Component Check the following Weekly Mounthly Annual
Mounthly
Fan in general
Connection
Fan and Pulley fan
Motor
Motor in general
Pulley motor
Clean/ replace Pre filter
Check the medium filter
Clean/ replace medium
Filter
filter*
Check the Hepa filter
Clean/ replace Hepa filter*
Visually inspect coils for
cleanliness and microbial
growth.
Coil Fin block/fin bundle
Frost
Drainage
Heater
Heater
Wiring
Damper Damper
Hood fresh air
Inlet/outlet
Louver
Piping drain
drainage
Drain pans
quantity of Aiflow
outdoor air Microbial contamination*
in the AHUs
Control box and wiring
Control
Sensor

*Minimum frequencies may be increased or decreased from what is indicated in this table.
INSPECT PARTS Hoods And Louvers

Inspect the following parts for damage, Inspect the air hoods and louvers for
dirt and debris. damage and debris. Remove debris as
needed.
Cabinet

Clean the exterior of the AHU with a mild,


environmental safe detergent and high-
pressure water at 2000 psi.

Fan

If Unit not daily operation Fan motors


must be operated for at least 2 hours every
month to prevent possible fan set failure.
The fan infrequently to dirty because
material fan is C-pro of Alumunium .

Door Hardware Check for soiling, damage, corrosion, and


any tendency to bind. Clean as necessary.
Inspect the doors, handles, latches and
hinges for proper operation, and the door Check that the flexible connection are
for damage and if they are properly sealed. securely fixed. Check the function of all
Secure any loose parts. antivibration mounts.

Check for any obstructions or blockages


of the air intakes and discharges.

Check the traps for leaks or blockages and


prime as necessary.

Panels Inspect

the panels for damage. If the panels show


signs of excessive pressure change, they
will appear to bulge inward or outward.
Refer to Troubleshooting on page 78
regarding excessive static pressure. If the
panel needs to be replaced, use the
instructions later in this section.

If using EC fans, it is possible to reverse


these using the designated input signal to
the fan set (view unit specific wiring Motor protection is PTC thermistor
diagram). The fans will operate as per the temperature sensors are predominantly
0 10 V input signal. To move as much used for thermistor motor protection
debris as possible, it is advisable to run the devices (alarm or shutdown) for motors.
fans at the maximum speed the application These thermistors are generally integrated
noise level will allow. For what this in the winding overhang. As a
voltage will be, with respect to the unit consequence, the stator windingis directly
noise level please contact us for protected. The temperature difference
representative. The fans do not need to between alarm and shutdown (trip) is 10K.
operate in reverse for longer than 2
minutes to move large debris and some When a limit temperature is reached
lightly applied particles on the fin surface. (nominal trippingtemperature), the
resistance of PTC thermistors will have a
Heavier fouling must be removed using a step change. This is evaluated by
pressure water/steam jet washer (Max atrippinunit and can be sued to open
pressure 3bar) against direction of airflow, auxiliary circuits
at a distance of 300 to 400mm using a
neutral cleaning agent if required. The Dirty motors run hot when thick dirt
spray should be even across the coil face insulates the frame and clogs cooling air
and as with a brush, applied in a passages. Motor exterior should be
longitudinal direction across the fins. periodically cleaned to remove
contaminants that can affect heat
Motor dissipation from the motor.

lnspect periodically for excessive vibration Check for signs of corrosion : Lubricate
or temperature. Operating conditions will the bearings only when scheduled or if they
vary the frequency of inspection and are noisy or running hot. Do not over-
lubrication. lubricate. Excessive grease and oil captures
Dirty motor run hot when thick dirt dirt and can damage bearings.
insulates the frame and clogs cooling
air passages. ( motor exterior should be Feel the motor frame and bearings for
periodically cleaned to remove excessive heat or vibration. Listen for
contaminants that can affect heat abnormal noise that may indicate a
dissipation from the motor. potential motor failure. Promptly identify
Check for signs of corrosion. and eliminate the source of the heat, noise,
Lubricate the bearings only when or vibration.
scheduled or if they are noisy or
running heat. Do not overl lubricate. Air Filters
Excessive grease and oil captures dirt
Every month, check the cleanliness of the
and can damage bearing.
filters, and if necessary, replace them.
Feel the motor frame and bearing for
excessive heat or vibration. Listen for Filters should be replaced when the
abnormal noise that may indicate a pressure drop, measured by a manometer,
potential motor failure. Promptly reaches the prescribed limits for the
identity and eliminate the source of the installation.
heat, noise or vibration.
Verify that belt and motor drive guards Filter types pre filter, medium filter and
are securely fastened so as not to cause HEPA filter are the typical filter types as
vibration and noise and possible damage
shown in Figure. If your AHU has HEPA
to equipment and personnel.
filters, the filter frames, bulkheads and gaskets are normally found on inside of
segment panels are factory sealed, and filter frame end covers.
must remain sealed for NO air bypass.
5. Slide the correct size new filters into
tracks.

7. Airflow arrows must point downstream


(in direction ofthe airflow).

8.Install all pleated filters with pleats


positioned vertically.

9.Reinstall the filter frame end cover.


Fig.1 Prefilter To clean permanent filters wash under a
stream of water to remove dirt and lint.
Remove oil filter (aluminum or grease
filter) with a wash of mild alkali solution.
Rinse in clean, hot water and allow to dry.
Coat both sides of the filter by immersing
or spraying it with Air Maze Filter Lote W
or equivalent. Allow to drain and dry for
about 12 hours.
Fig.2 Medium filter
Coil Segment Cleaning

Coils, whether for heating, cooling, or


dehumidifying, should be clean both
internally and externally, and the fins for
heat transfer should be intact and
undamaged.

Typically, coils (especially cooling coils)


Fig.3 Hepa filter are externally cleaned once a year, as this
side of the coil receives the most dirt (from
1. Check filter sizes anquantities. Refer to the air stream).
the filter label located oneach filter
Coils may be periodically pressure tested
segment.
for leaks.
2. Remove filter frame end cover as shown Control valves wear out over time due to
in Figure 66 on page 66and Figure 67 on constant modulation. These valves should
page 66. be included in a regularly scheduled
maintenance program.
3. Remove old filters, if present.
By treating heating steam and heat transfer
4. Make sure gaskets at both ends of the water, tubes of coils should remain clean,
side load filter tracks are in place.The and heat transfer capability should remain
high for a number of years.
Steam, hot water and chilled water coils Direct expansion coils
should be kept clean to maintain maximum
performance. lf fins become dirty, clean Never use hot water or steam to clean these
with steam and detergent, hot water spray coils. During normal opeartion, the fin
and detergent, or one of the commercially block must not ice up. If this occurs, check
available chemical coil cleaners. Rinse the refrigeration system.
coils throughly after cleaning.

If cleaning coil by periodically, clean dirty


coil with water and detergent because just
dust and mildew on coil, but if coil have
slag slould clean with chemical cleanser.

WARNING
Follow all directions provided with
chemical cleaners to avoid personal
injury and/or coil damage.
Commercially available chemical
cleaners may contain caustic or
hazardous agents For direct expansion coils, do not use hot
water or steam to clean these coils. During
normal operation, the fin block must not be
In the event of coils being out of ice up. If this occurs, check the
commission for some time, it is advisable refrigeration system. Check that drain pan
to completely drain down the coil. On each and drain trap are free from blockage and
occasion when refilling is undertaken, water accumulation at pan.
check that the coil is effectively vented.
Refrigerant coils should be kept clean to
Periodic cleaning of the coils is required. maintain maximum performance. If fins
Dirty coils have increased airside pressure become dirty, clean with cold water and
drops and reduced heat transfer,thus detergent or one of the commercially
unbalancing the cooling or heating system. available chemicals coil cleaners. Rinse
coils thoroughly after cleaning
Cleaning In the event that fin edges have
been bent, they can be straightened with
the aid of a coil comb. WARNING
Never use steam or hot water to
The cleaning is carried out with the unit
clean a refrigerant coil. Dangerous
intact using a powerful vacuum cleaner on
the dust-contamainated side. If the unit is pressures may be built up by
very dirty it will need to be removed and improper application of heat
wet cleaned. resulting in equipment damage oe
personal injury.
If required, soft cleaning brushes may be
used ensuring that the heat exchanger fin
are not damaged.
Damper

Prior to occupancy, test ventilation system


to ensure that outdoor air dampers operate
properly in accordance with the system
design.

Check for dirt accumulation, damage and


sign of corrosion. Clean with cloth or high
pressure air. Check damper blade turning
manually or central control for smooth
operation.

Cleaning procedure Cleaning of dampers


should be performed before operation is
hindered in any way. Maintenance
personnel must determine when cleaning is
necessary based on observation and
operation.

Electric Heater

Check for dirt accumulation and clean if


necessary with a soft brush. Check the
safety control, cables and connections
operation.

Heat Wheel & Heat Pipe

The unit should be maintained in line with


the manufacturer recommendation.
TROUBLE SHOOTING
Use the table 5 to assist in trouble-shoot the malfunction in Air Handling Unit operation.

Table 5 Trouble Shooting Analysis

Symptom Probable Cause Recommended Action


Motor Fail Start a) Blown fuse or open circuit a) Replace fuse or reset circuit
breaker breaker.
b) Improper wiring. b) Check wiring with diagram
supplied.
c) Mechanical Failure. c) Check motor & drive rotate
freely & bearing lubricant.
Motor overheats a) Overloaded motor a) Reduce load or replace larger
motor.
b) Motor Fan dirty/ damage. b) Clean/ replace motor fan.
Fan does work a) No Power Supply / power a) Check Power supply
Failure
b) Fan capacitor faulty b) Change switch
c) Fan motor faulty c) Operate when power supply
resume
d) Switch faulty d) Replace motor fan / clean
e) Start trip e) Contact Local dealer
f) Fuse blown in power switch or
operating unit
Low air volume after a) Fan rotating in wrong direction.a) Reverse any two phase
start up connection at motor terminal.
b) Air damper not properly set. b) Ensure system correctly
balance & set.
c) Pressure drop by filter above c) Change filters (complete
recommended level. bank).
d) Motor fan is clogged with dirt d) Remove fan cover, clean fan
preventing proper ventilation and replace cover
e) Reduce load or replace with
larger motor
Air Conditioner works a) thermostat setting too high a) Rest Thermostat
but cooling not
b) Doors and/or windows not b) Close doors and/or windows
satisfactory closed
c) Condenser coil dirty c) Contact local dealer
d) Some objects blocking the inlet d). Remove the object
and/or outlet of the unit
e) Indufficient refrigerant charge e) contact local dealer
Note: The table is intended as a diagnostic aid.
Symptom Probable Cause Recommended Action
Water present in cooling a) Drain trap clog. a) Clean & clear clog.
coil drain pan or b) Incorrect hydraulic trapping b) Resize trap and check air break
overflow arrangement
Filter collapsing a) Filter block with dirt. a) Replace at advised dirty
condition.
b) Air velocity too high. b) Check unit running conditions.
Damper seizing Blade bent Repair or replace blade
Spindle or mechanism loose Tighting lever fixings
Actuator loose Refit actuator correctly
Low coil capacity Air is by passing coil Prevent bypass with block-off
(Chilled Water)
Coil tubes are blocked Clean and unblock tubes
Incorrect airflow (CFM) Check water pumps, valves and
lines for obstructions
Incorrect water flow rate (GPM) Provide proper water temperature
Incorrect water temperature
Low coil capacity Air is by passing coil Prevent bypassing with block-off
(Refrigerant)
Coil tubes are blocked Clean and unblock tubes
Incorrect airflow Check fan-operating conditions
Expansion valve not operating Check sensing bulb location and
TXV operation
Poor refrigerant distribution Check for blockage in distributor
and tube
Leaking Coil Header / exposed pipe damage Repair damaged part
Cracks in joints due to strain of Check support and alignment of
pipework on headers pipework and rectify
Swelling of joints due to frost Check frost protection method
(Water-hammer Steam Coils) and correct, improve Trapping of
steaam supply
Drain pan overflow Incorrect hydraulic trapping Resize / fit trap and check air
break arrangement
Blockage in trap Clean trap and refit
Plugged Drain Line Clean drain line
Unit not level Level unit
Wet interior insulation Coil face velcity too high Reduce fan speed
Improper trap design Design trap per unit installation
instructions
Drain pan leaks / overflows Repair leaks
Condensation on surfaces Insulate surfaces
Note: The table is intended as a diagnostic aid.

You might also like