Professional Documents
Culture Documents
Contents
Relationship between the breaking No. and the breaking current ................................................ 6
The copyright belongs to CooperNature Electric (Ningbo) Co., Ltd. Dont supply any content included in this book
to others. Only the company has the right of revising and explanation.
VN2-24E
Medium-voltage Embedded Vacuum Circuit-breaker
1
Cooper Nature ( Ningbo ) Electric Co., Ltd.
2
VN2-24E
Medium-voltage Embedded Vacuum Circuit-breaker
3
Cooper Nature ( Ningbo ) Electric Co., Ltd.
Type specifications
VN2 24E 630 20 210 D
V: Vacuum Rated voltage: 24kV Rated current Rated short-circuit Poles center Type
circuit-breaker E: Embedded pole 630A breaking current distance D: Withdrawable
N: CooperNature 1250A 20kA 210mm F: Fixed
1600A 25kA 275mm
2000A 31.5kA
2500A
3150A
4
VN2-24E
Medium-voltage Embedded Vacuum Circuit-breaker
Technical parameters
Rated Voltage
Rated Voltage Ur[kV] 24
1min power frequency withstand voltage(effective value) Ud(1min)[kV] Between phase 65 Isolated 79
Lightning impulse withstand voltage(peak value) Up[kV] or phase to the earth 125 joints 145
1min power frequency voltage of the secondary controlling circuit [V] 2000
Rated Current
Rated current Ir[A] 630, 1250, 1600, 2000, 2500, 3150
Mechanical character
Electrical lifetime E2
Special voltage degree is available on request;
Must be with forced cooling.
5
Cooper Nature ( Ningbo ) Electric Co., Ltd.
Breaking No.
6
VN2-24E
Medium-voltage Embedded Vacuum Circuit-breaker
Overall dimension
Overall dimension for fixed circuit-breaker (Fig1 & Fig2)
Unit: mm
Parameters
Rated current
Rated short-circuit P W1 W
breaking current
Fig 1 Overall Dimension for Fixed Circuit-breaker with 630A~1250A & 20kA~25kA
Fig 2 Overall Dimension for Fixed Circuit-breaker with 1600A~3150A & 20kA~31.5kA
7
Cooper Nature ( Ningbo ) Electric Co., Ltd.
Unit: mm
Parameters
Rated current
Rated short-circuit P P1 W W1 W2 A B C
breaking current
Fig 3 Overall Dimension for Withdrawable Circuit-breaker with 630A~1250A & 20kA~25kA
Fig 4 Overall Dimension for Withdrawable Circuit-breaker with 1600A~3150A & 20kA~31.5kA
8
9
VN2-24E
Technical Requirement
1. The state of circuit breaker: no energy storage, opened position of the
circuit breaker, test position of the truck.
2. Use 1 mm2 wire for control loop while 2.5 mm2 wire for grounding use.
3. XT selects 58-pin hole aviation plug.
4. Y7, Y8, Y9, Y1 and K0 are optional.
5. When DC power supplied, cancel rectifier cell (V1-V4), the function in
broken line should be same.
6. Optional function configuration. (Note:KO, V1~V4, L1~L11, A1~A14,
Medium-voltage Embedded Vacuum Circuit-breaker
Technical Requirement
1. The state of circuit breaker: no energy storage, opened position of the circuit
breaker, test position of the truck.
2. Use 1 mm2 wire for control loop while 2.5 mm2 wire for grounding use.
3. XT selects 58-pin hole aviation plug.
4. Y7, Y8, Y9, Y1 and K0 are optional.
5. When DC power supplied, cancel rectifier cell (V1-V4), the function in broken line
should be same.
6. Optional function configuration. (Note:KO, V1~V4, L1~L11, A1~A14, B1~B15,
R0-R1 are the cell in the)
WirinWire
XT Aviation Plug Header of control wires Confi g
gurati
on ba gh fe dc af fg cb ij kL Lm pq
LX Wiring Terminal Connect to truck wires
KO Anti-pumping Relay Prevent circuit breaker release With with locking
antipumping
SP1~SP3 Micro Switch Shift after closing spring energy is stored without
function locking
SP5 Limit Switch Locking function
S8 Auxiliary Switch in the chassis Shift at test position Without anti- with locking
S9 Auxiliary Switch in the chassis Shift at working position pumping
without
function locking
Y1 Locking Magnet Contorl locking loop
RO~R1 Resistance Divided resistance AC/DC 110V
Y7~Y9 Over-current Release Over-current protection
AC/DC 220V
L1~L11 Connecting Wire Transfer function
10
VN2-24E
Medium-voltage Embedded Vacuum Circuit-breaker
Order table
Customers:
Ordering Quantity:
Main parameter:
Note: 1) The price of circuit-breaker has included standard accessories but not included optional accessories;
2) For withdrawable circuit-breaker, the handle used for moving truck and the charging handle
are standard accessories;
3) circuit-breaker with rated current 3150A must be forced cooling;
4) Please consult manufacturer if have any other special requirements.
11
Cooper Nature ( Ningbo ) Electric Co., Ltd.
Marketing Department Switchgear Sales Department
Tel: +86-574-63486522 Tel: +86-574-63486388 63486702
Fax: +86-574-63486919 Fax: +86-574-63486388 63486503
June, 2009