You are on page 1of 15

1148 TAYLOR: REVERSE-POWER.

ALTERNATING-CURRENT RELAYS

REVERSE-POWER ALTERNATING-CURRENT RELAYS FOR 3-PHASE


GENERATOR AND FEEDER PROTECTION.*
By G. E. TAYLOR, Associate Member.
{Paper first received 2Zrd February, and in final form 30th June, 1928.)
SUMMARY. to utilize reverse-power relays, and these notes are in-
This paper discusses the behaviour of reverse-power a.c. tended to assist all those engaged in the operation or
relays of the wattmeter and allied types when applied to the construction of such instruments in appreciating the
protection of 3-phase generators and feeders, and it shows: shortcomings of this class of apparatus.
(a) The differences in behaviour produced by various A consideration of the various faults covered by the
systems of connections; requirements discussed in the foregoing paragraphs will
(b) The improper operations inevitable with each system show that reverse-power relays are intended to remain
of connections; inoperative so long as the average value of the power
(c) The difficulties to be overcome in order to produce a transmitted during any one cycle by the apparatus to
reverse-power relay which will be stable with all which they are connected is in the forward direction (i.e.
conditions of forward power and whose operation is being supplied by the generating plant towards the
will yet be certain under all conditions of reverse consuming plant), and operation is required in the event
power. of the power becoming reversed in direction (i.e. fed back
In addition, the paper shows that the most satisfactory towards, or into, the generating plant from the con-
results available with this class of instrument will be obtained suming end).
if the potential coils of the relay be connected between line On any system, however, reversals of small magnitude
and neutral when used for generator protection, or between may be of frequent occurrence, even under normal
line and leading phase when used for feeder protection. operating conditions, and in order to prevent operation
of the relays under these transient conditions the relays
INTRODUCTION. are provided with a scale setting, which is intended to
render the instruments inoperative even when a reversal
Reverse-power a.c. relays were at one time employed of power is present, so long as the magnitude of such
on generators to trip the automatic switch or circuit reversal is less than the value to which the relays are set
breakers in the event of power being fed back from other on the scale. (Such transient reversals and reversals of
synchronous plant connected to the system into the small magnitude may result from faults on other por-
machine owing to a breakdown on the windings of the tions of the system, or from bad synchronizing of an
machine, and, although more satisfactory apparatus is incoming generator, or even from sudden fluctuations in
now available for this purpose, such relays are still fre- load.)
quently employed and are indeed highly essential (if they
can be relied upon) as a means of disconnecting the It is the purpose of this paper to show that the value
machine in the event of its being run as a motor from the of the reverse power necessary to operate these relays
line upon a failure of the prime mover, or in the event of . under many fault conditions does not coincide'with the
the machine being mistakenly switched in when at rest value indicated on the scale; that, owing to this inac-
or not in synchronism. curate characteristic, these relays may frequently cause
the "shut down" of quite healthy plant; and that little
Such relays were also used to protect each of two or reliance can be placed on their powers of discrimination
more feeders serving in parallel and were intended to unless the various points dealt with in this paper are
open the circuit breaker at the consuming end of the complied with.
affected feeder in the event of a fault thereon and thus to
interrupt any flow of current from the consuming end On any phase of an alternating-current system "for-
into the fault and otherwise supplied by way of the ward power" is always obtained so long as the current in
parallel feeder. that phase is not more than 90 displaced with regard to
the voltage impressed on that phase by the apparatus at
As in the case of generator protection, improved the supply end; "reverse power" results, however,
apparatus for performing this function with greater dis- whenever the current and voltage are more than 90
crimination and reliability can now be obtained, but displaced.
such apparatus is very much more expensive than these
simple relays and in most cases involves the use of pilot Turning now to the relays; these are, in principle,
wires, the cost of which on a large system may be pro- simple single-phase wattmeters. In fact, if an ordinary
hibitive. In such cases, therefore, endeavour is still made single-phase wattmeter be equipped with a central zero
and arranged to indicate forward power on the right-
* The Papers Committee invite written communications (with a view to hand side of the zero line and reverse power on the left-
publication in the Journal if approved by .the Committee) on papers published
in the Journal without being'read at a meeting. Communications should reach hand side and be then fitted" with a pair of tripping
the Secretary of the Institution not later than one month after publication of
the paper to which they relate. contacts on the latter side so that when the pointer
FOR 3-PHASE GENERATOR AND FEEDER PROTECTION. 1149

reaches their positions it completes the tripping circuit, of the relay in line A and its potential coil across phases
then an instrument equivalent in all respects to a reverse- B and C, as shown in Fig. 3, thus giving a 90 phase dis-
power relay will be obtained, and the behaviour of such placement (at unity power factor in the main circuit)
relays can, therefore, readily be followed by considering between the current in the series coil and the voltage
them as ordinary central-zero single-phase wattmeters. across the shunt circuit, and, to compensate for this, a
Now it is well known that either two or three single- condenser is inserted in series with the shunt coils and
phase wattmeters can be utilized to indicate the total serves to bring the pressure actually applied to these
power in a 3-phase circuit. into phase with the current in the series coil.
If three instruments be used they are connected as The behaviour of the relays varies considerably when
shown in Fig. 1, the current coils being arranged one in under both normal and fault conditions, according to
each line and the potential coils of each instrument being which system of connections is adopted, and it is the
3 single-phase wattmeters
C \ iA

FIG. 1.Three single-phase wattmeters. FIG. 2.Two single-phase wattmeters.


current in phase" A " Ipe = current in phase" C "
fc:
'pa '
: current in series coil of relay " A "
= voltage across phase" A "
In = current in series coil of relay " C "
Epc = voltage across phase" C ."
voltage across potential coil of relay " A " Ere = voltage across potential coil of relay " C "
: angle of displacement between Ipa and Epa <f> = angle of displacement between Tpc and Epe
angle of displacement between Im and Era <t>n = angle of displacement between Irc and Erc

connected between the line which carries the associated intention of this paper to show that none of the systems
current coil and the neutral point. results in thoroughly reliable discriminative action under
If only two instruments be used, then the current coil all conditions, and for ease of reference it is proposed
of the first must be connected in line C and that of the to refer to the various schemes in the following manner:
second instrument in line B, whilst the potential coils of
the instruments must be connected between lines A and When connected as shown in Fig. 1, as "Star connection."
C, and B and A respectively, as shown in Fig. 2. When connected as Relay B in Fig. 2, as "Leading
Reverse-power relays are connected exactly similarly, connection."
both as shown in Fig. 1 and as shown at A and B in When connected as Relay C in Fig. 2, as " Lagging
Fig. 2, whilst, in addition, a fourth system was proposed connection."
by Wedmore,* and has also been tried. When connected as suggested by Wedmore (Fig. 3), as
The latter method consists in connecting the series coil " Quadrature connection."
See E. B. WEDMORE and H. TRENCHAM : " Switchgear for Electric Power
Control," page 124 ; also British Patent 4595/1915. Now, although three reverse-power relays are usually
VOL. 66. 74
1150 TAYLOR: REVERSE-POWER ALTERNATING-CURRENT RELAYS
installed, one in each phase, on any circuit which it is . Pa, Pb or P c = power energizing relay A, B or C.
desired to protect, and although each carries only the Pr = power necessary to operate relay at setting value.
current in a single phase, it is customary to equip these Ira, 1^ or Irc = current in series coil of relay A, B or C.
relays with a scale calibrated in kilowatts in terms of the Era, Eri or Erc = voltage across shunt coils of relay A,
3-phase power in the main circuit, the intention being B or C.
to facilitate their being set for main circuit values without <f>r = angle of phase displacement between Ir and ET.
reference to the effects within the relay itself, and, in Pf power in fault.
order to compare the curves given later on, it is necessary If = current in fault.
to bear this point in mind. Ef = voltage across fault.
Considering now the behaviour of the relays under <f)j angle of phase displacement between / / and Ef.
normal and fault conditions, the actual relationship
BEHAVIOUR ON 3-PHASE LOADS OR REVERSALS..
For star-connected instrument, as in Fig. 1 (a).The
power in the 3-phase main circuit
= P3 = SEpIp cos <f>
and the power energizing each instrument A, B or C
= P = ErIr COS <f>r
but, as will be" obvious, and as is shown on the vector
diagram, Fig. 1 (6),
Er = Ev; I r = I p; a n d (f)r = <f>
Therefore, P = EVIP cos <f>
90 ahead of Epb'JSpc P 3 _ 3EpIp cos (f>
owing to condenser
and the ratio
P EpIpcos<f> ~

If, therefore, the relay is to operate when the value


of the 3-phase reverse power in the main circuit is
Ps, then its tripping contacts must be closed when
its coils are energized by power
Pr = ~ (1)
(The negative sign before the term Ps is used, since
operation is required only when the power is reversed.)
For an instrument with leading-phase connections [as
o *
90nhend of Epa-Epi 90 ahead Relay B in Fig. 2 (a)].As before, the power in the
owing- to condenser owing- to of Epc-Ep
condenser
3-phase main circuit
FIG. 3." Quadrature "-connected reverse-power relays.
Jpa current in phase " A " = P 3 = SEPIP cos <f>
/ r a = current in series coil of relay " A "
Epa = voltage across phase" A " and the power energizing the relay
Ern = voltage across potential coil of relay " A "
$ = angle of displacement between Ipaand Epa
<\>ra = angle of displacement between Iraand Era
= P = ErIT cos <j>r
But here Er = -\/ZEp, Ir = Ip, and (f>r = 30 + <f>, as
between the 3-phase power in the line and the power will be seen from the vector diagram [Fig. 2 (6)].
indicated by a wattmeter (or the power active in a
reverse-power relay) when connected in either of the Therefore P = y/ZEpIp cos (30 -f <f>)
four methods referred to can be calculated as follows: and the ratio
Let
El p p 3E I cos <j> -\/3 cos cf>
P 3 = total power in the 3-phase main circuit.
Ps = power at which the relay is set to operate. P \/3EpIp cos (30 + cf>) cos (30 + <f>)
Ep = voltage across any one phase. so that, fOr any given value of P 3 ,
E = voltage between any two lines (= -\/BEp).
Ip = current in any one phase. cos (30 + <f>)
<f> = angle of phase displacement between Ep and Ip, P =
y/3 cos (f>
considered positive when Ip leads with respect
to Vp, or negative when Ip lags with respect Now obviously a wattmeter type of instrument can
to V.v only move its pointer to a given position when it is
FOR 3-PHASE GENERATOR AND FEEDER PROTECTION. 1151

energized by a given amount of true power, and each for, although the potential CB (Fig. 3) is normally 90
mark on the scale corresponds to a definite amount behind Ep in phase A, this is compensated for by the
of true power at the instrument terminals. If, there- effect of the condenser which is specially designed to
fore, the instrument be connected with leading-phase produce this result.
potential coils, the above equation shows that, since Therefore
the power P energizing the relay is not dependent P = ^/ZEPIp cos (f>
merely upon the value P 3 , then the indications of a 3EpIp cos
wattmeter will not necessarily be P 3 but may be any 3 = ^
other value, depending upon the power factor. Similarly, cos V

the fact that power to the value P 3 flows in the main and = P3/y'3
circuit is no guarantee that the moving element of a Therefore, if the instrument be set to operate at a
reverse-power relay will reach the tripping position. value of P 8 , the power required in the relay circuit
Manufacturers, however, universally equip their must be Pr = P/-\/ 3 a n d this will always be pro-
instruments with scales which indicate the position duced by power P s regardless of power factor.
reached by the moving element when power to the
value stated thereon is present in the 3-phase main BEHAVIOUR UNDER SINGLE-PHASE FAULT CONDITIONS.
circuit and is accompanied by unity power factor (i.e.
when <f> = 0) and therefore, if the instrument be set to Turning now to the behaviour of the relays undei
operate at a value of 3-phase power equal to P 3 , the fault conditions, and treating first the case of single-
power required to operate the relay will be phase faults to earth, then:
With a star-connected relay.The value of the power
cos (30 + cf>) in the fault circuit
P 3
V3 cos
<f> Pf = Eflf cos (f>
and, since <j> = 0 at unity power factor, we have
The value of the power in the relay circuit
cos30 0-866 P = ErIr cos <j>r
F732 and it will be seen from Fig. 4 (a) that
It will be obvious,' however, that this immediately
introduces an undesirable feature into the operation of Er = Ef) Ir = Ij; a n d <j>r = <f>
the instrument, for if reverse power of value" P 3 Therefore P = EfIf cos </>/
become present and be accompanied by a value of <p
Pf = EfIf cos <f>f = 1
which is not zero (i.e. if the power factor of the reversal
be other than unity), then the power fed to the relay P EfIf cos 0/
is no longer equal to P 3 but will be and P = Pf
cos (30 + </)) The relay was, however, set for a value Pr = ^Ps
-P, and, therefore, the power P in the relay circuit, due to
cos
Pf, must equal this value P r if the relay is to be operated.
This latter figure must, however, be equal to the Therefore, writing Pf = $PS we have that the
value Pr before the relay will operate, and therefore, fault must cause the power to be negative or " reversed "
writing P 3 cos (30 + </>)/(V3 c o s $) ~ ~ \^s, we have and requires to be one-third, gi_the-setting^yalue of the
relay in order to cause operation. ^
_ P _ _ p V 3 cos <j> 0 866 cos <f>
With a relay having leading connections.As before,
3 S = - P,
2 cos (30 + </>) cos (30 + cf>)
the power in the fault
and the value of the power in any reversal must, there- Pf = EfIf cos fa
fore, be P 8 (0-866 cos 0)/{cos (30 + cf>)} before the and the power in the relay
relay will be operated, and this value is not constant
but varies with the power factor. P = ErIr cos cf>r
For an instrument with " lagging phase " connections but, as will be seen from Fig. 5 (a) and from the vector
[as Relay C in Fig. 2 (a)\.This case is similar in all diagram Fig. 5[{b),
respects to the preceding one, except that <f>r now equals
(30 cf)), as will be seen from the vector diagram, Er = ^/3Ef; Ir = / / ; and ^ = 30 + <j)f
Fig. 2 (b), and in consequence the power Pr necessary to Therefore P = y/ZEfIf cos (30 + <f>f)
operate the relay when set at a value Ps is not merely
Ps but is actually p cos (j>f COS (f>f
0-866 cos <f> and -j = cos Cos
3
cos (30 - <f>) and therefore the power P in the relay circuit due to a
For an instrument with " quadrature " connections (as fault to earth of magnitude Pf is
in Fig, 3).Here r _ P/V3 cos (30 + <f>f)
Er = IT = I v\ and COS <f)f
1152 TAYLOR: REVERSE-POWER ALTERNATING-CURRENT RELAYS
But the relay was set to operate with a value of point of operation, since it is impossible to foretell what
P = Pr = PS, therefore when the value produced by the power factor of the fault will be.
Pf reaches this magnitude the relay will trip. Thus, With a relay having lagging connections.Reference to

Reverse

FIG. 4.Single-phase fault to earth. Star-connected relays.


Ep = phase voltage Ip = phase current <>
/ = angle between En and /.
p p p p
E/ = voltage across fault If = fault current <j>/ = angle between Ef and If
Er = voltage across potential coil of relay Ir = current in series coil of relay <j>r = angle between E, and Ir

Fault

tends to
become
60+ <f>f

(6) (c)
Voltage maintained Voltage collapsed

FIG. 5.Single-phase fault to earth. " Leading phase " connections to relay potential coils.
voltage across fault / / = fault current (j>f = angle between Ef and If
voltage across potential coil of relay " A " Ira = current in series coil of relay " A " <j:ra = angle between Era and !

(6) (O
Voltag-e maintained Voltage collapsed

FIG. 6.Single-phase fault to earth. " Lagging phase " connections to relay potential coils,
Ef voltage across fault / / = fault current <f>f = angle between Ef and It
Era voltage across potential coil of relay " A " Ira = current in series coil of relay " A " <j>ra = angle between Era and In

writing P/\/S cos (30 -f- <^y)/cos <f>f = %Ps, a n d solving Figs. 6 (a) and 6 {b) will show that in this case
for Pj, we find (f)r = (30 <J)f) instead of (30 + (f>f) as is the case with
COS <j)f 0-288 cos 4>f leading connections, and in consequence the power in
; S =,"- p., the fault Pj necessary to produce operation is
2V3 cos (30 + <f>f) ' * "COG (30 + <pf)
_ _ 0-288 cos 4>f
and it is seen that the magnitude of the fault necessary 1 s
to operate the relay depends upon the power factor, and ~ cos (30 - (f>})
that the actual seating is of little value in fixing the With a relay having quadrature connections.Referring
FOR 3-PHASE GENERATOR AND FEEDER PROTECTION. 1153
to Figs. 7 (a) and 7 (b) and proceeding as in the previous rru x r Eflf COS <f>f)
cases, it will be seen that Therefore Pn = -^- V3
cos \ / 3 cos
and p =
as in the case of a star-connected instrument. a {EfIf cos (30 + </)}/V3 ~ cos (30 +

BEHAVIOUR UNDER CONDITIONS OF FAULT BETWEEN and _


c o s <f>f
Two PHASES.
The behaviour of the relays when a fault involving The relay is set to operate when energized by power
two phases develops has now to be considered, and having a value Pr = $PS; therefore, when the above

Fault

Era

(6)
Voltag'e maintained Voltage collapsed

FIG. 7.Single-phase fault to earth. " Quadrature " connections to relay potential coils.
voltage across fault If = fault current <f>f = angle between Ej and / /
Era voltage across potential coil of relay " A " Ira = current in series coil of relay " A " <bra = angle between Era anc ^ In

Fault

-X-

Reverse
power
relays

(a) (6) / % (C)

Voltag-e maintained Voltage collapsed

FIG. 8.Fault between phases " A " and " B." Star-connected relays.
voltage across fault / / = fault current <j>f = angle between Ef and If
voltage across potential coil of relay " A " Ira current in series coil of relay " A " <j>ra = angle between Era and / ,

here, as in the previous cases, the power in the fault is, value for Pa becomes equal to this setting, the relay will
of course, Pf = Eflf cos </>/; but now Ef is the voltage close its tripping contacts. Thus, writing
between lines instead of the phase voltage, and is there-
fore greater in magnitude than the latter and is removed Pf cos (30 + (f>f) _ .
therefrom by 30. The power energizing the relay circuit \/3'Cos (bf
under the fault conditions will again be ErIr cos cf>r
and the relationship between these two values will, of and solving for Pf, we have
course, vary according to the scheme of connections
adopted, and these variations will now be shown, the V 3 ( Ps) cos $] COS <f)f
fault being assumed to be between phases A and B.
1
3 cos (30 + = _ V 3 cos 30
( + <f>f)
For star-connected relays.Figs. 8 (a) and 8 (b) will
show that, with regard to relay A (in phase A), and in this case also the magnitude of the fault per-
missible is seen to depend on the power factor. It will
Era = J
ra = If, and <j)m = 30 + </./ be apparent also from Figs. 8 (a) and 8 (b) that the relay
1154 TAYLOR: REVERSE-POWER ALTERNATING-CURRENT RELAYS

w
Fault

A Reverse
ff.fr

ra tends to
li power
relays
become

(6) (C)
(a)
Voltag-e maintained Voltag-e collapsed

FIG. 9.Fault between phases " A " and " B . " " Leading phase " connections to relay potential coils.
Ef = voltage across fault If = fault current <j>/ = angle between Ef and / /
En, = voltage across potential coil of relay " A " Ira = current in series coil of relay " A " <ra = angle between Era and Ira

ute
beco

to) (6) (C)


jyAi\J| Voltage maintained Voltag-e collapsed

FIG. 10.Fault between phases " A " and " B." " Laggingfphase " connections to relay potential coils.
Ef = voltage across fault / / = fault current (j>f = angle between Ef and / /
Era = voltage across potential coil of relay " A " Ira = current in series coil of relay " A " $m = angle between Era and /

approaches <f>f

(6) (c)
Voltag-e m a i n t a i n e d Voltag-e collapsed

FIG. 11.Fault between phases " A " and " B . " " Quadrature " connections to relay potential coils.
Ef = voltage across fault If = fault current <j>f = angle between Ef and / /
Era = voltage across potential coil of relay " A " Ira = current in series coil of relay " A " <j>ra angle between Em and IT
Erb = voltage across potential coil of relay " B " Irb = current in series coil of relay " B " <\>rb angle between E,t, and /,*
FOR 3-PHASE GENERATOR AND FEEDER PROTECTION. 1165
B on phase B will also be affected and that the current Relay B, however, requires that the power in the fault
in its series coils will be If, as in relay A and as in the shall be
fault, but, since its direction in phase B must be opposite
= p s
to its direction in phase A, the vector representing this P ; f
- cos (60 - fa)
current in the diagram, for relay B must be moved
through 180 with regard to its direction in the diagram For relays with quadrature connections.
for relay A, and thus <j)rb = 30 <f>j, as will be seen from
Fig. 8(6). Relay A.From Figs. 11 (a) and 11 (b) we have:
Erb = Etfy/Z and Irb = If Era = Ef (in magnitude) ; Ira = If; faa = (30 +
__ EfIf cos (30 - fa) and Pa = Eflf cos (30 + fa)
Therefore
Pf Eflf cos <f>f cos fa
Eflf cos fa -\/3 co Pa Eflf cos (30 + fa) cos (30 + fa)
Pb cos (30 - </)}/V3 c o s ( 3 0 ~ cos (30 + fa)
and a
~ }. cos fa
_ _ cos (30 - fa)
and-
\/3 cos fa
Letting - Ps = p cos (30 + fa)
Pr, however, has been shown to be equal to \PS.
V3 f
cos fa
Therefore, when Pr^f
J
^JnL =
3 cos
-s the relay will COS fa
V 0 / 3 then Pf= - p,
cos (30 + fa)
operate, and the value of Pf necessary to produce this
is obtained by solving this equation for Pf. Relay B.In a similar manner it will be found that
Therefore Pr= -P. cos fa cos fa
cos (30 fa) P,= -
V 3 cos (30 - fa)
For. relays with leading-phase connections.
Relay A.From Figs. 9 (a) and 9 (b) we have: EFFECT OF COLLAPSE OF VOLTAGE.
Era = Ef\ ITa = If] faa = (60 + fa) In addition to the effects so far considered, it may
and Pa = Eflf cos (60 + fa) happen that a fault having very low impedance may
develop in any one of the cases given, and in such an
Pf Eflf cos fa cos fa event the voltage across the fault (and therefore across
Pa (60 + <f)f) ~ cos (60 + <f>f) the potential coils of the relay) may collapse owing to
cos (60 + fa) the inability of the generating plant to maintain its
*
1
? voltage when delivering the current demanded by the
COS (pf short-circuit, and also owing to the drop produced in the
The relay is set to operate when the power in the relay line by the passage of this abnormally high current.
circuit = Pr = | P S . In such a case it will be obvious that, since the voltage
Therefore, letting across the potential coils of the relay has been lowered,
cos (60 + cf>f) considerably more current than normal must flow in
~ *Ps ~ f
cos fa the series coil if the necessary power is to be produced
to operate the relay; and, in addition, reference to the
COS
we have vector diagrams, Figs. 4 (c), 5 (c), 6 (c), 7 (c), 8 (c), 9 (c),
10 (c) and 11 (c), will show that a displacement of up to
Relay B.From Figs. 9 (a) and 9 (6) we have: 30 from normal may also be brought about in the phase
Erb = Ef ; Ira = If; faa = fa; and Pb = EfIf cos fa relationship of the voltage applied to the terminals of
the potential coil.
Pf = Eflf cos fa = j
In cases where the fault is directly across the lines
Pb EfIf cos fa to which the terminals of the relay potential coils are
Pb = Pf and PTb = - \ connected it is possible that, if the voltage falls to a
Tb
Therefore low enough value, the relay will become inoperative,
\P8 = Pf even with abnormally high current values. Where,
and therefore the relay will operate at 50 per cent of the however, relays are connected with their potential coils
setting value, regardless of power factor, so long as the across two lines, at least one of any two affected will
power be reversed. retain "l/-\/3 of its normal voltage, unless the collapse
For relays with lagging-phase connections.Proceeding be on all three phases. Owing to the phase displace-
as in the previous case, it will be seen from Figs. 10 (a) ment previously referred to and shown in the figures
and 10 (6) that, for relay A, Pf = %PS and this mentioned above, the calculations previously made
relay also is thus seen to operate at 50 per cent of the require modification in some cases. These will be
setting value, regardless of power factor, and only on obvious from the diagrams, and it is not, therefore,
true reverse power. proposed to consider them in detail.
1156 TAYLOR: REVERSE-POWER ALTERNATING-CURRENT RELAYS
SUMMARY OF FOREGOING RESULTS.
A summary of all the foregoing results is given in
3 -e- Table 1. The modifications for voltage collapse have been
made in this table where necessary, and these modified
equations are given in their appropriate columns, with
suitable notes showing to what extent the voltage
collapse may necessitate increase of current.
If now various values be inserted in each of the equa-
tions given in the table for <f> and <j)f and the setting value

TJ
200

Rela r ha v\ng p o t ;ntia 1 coils


160

:)o. a :ros : lag: phas


120
T
ower
a. i
80-
a
i
Forvva
40

i \

I\
- 1 -I iC 3 m
Zero
2

40
i y/
A
ower

\
8 0 - 0. J . Star-and- quad rature
\ connected
\ ^potential coils
% / \
-e- V I \
120 X 1
\

160 1 I

Phag e dis>plac emerit (d<.gree sfbe "weer volt age


and current in mam, circuit g>
"<jj 30 60 co 60 30 30 60 60 30
-- <s Forward ^ Reverse Reverse v Forward
_ (leading) c (leading-) S (lag-ging-) _

FIG. 12.Operating curves for reverse-power relays. Three-


phase load or fault.

Ps be kept constant, values can be obtained for P or


Pf, as the case may be, and these will show what value
of 3-phase power or of fault power will be necessary to
operate the relay with any given setting. If these values
be plotted, curves similar to those in Figs. 12, 13, 14, 15
and 16 will be obtained.
In the case of between-phase faults, it must be remem-
bered that two relays will be affected with instruments
having between-phase connections to the potential coils,
and, since the operation of either relay is sufficient to
trip the circuit breaker, the value of the power necessary
to accomplish this will be that needed by the relay
calling for the least value of Pf, and the more stable
FOR 3-PHASE GENERATOR AND FEEDER PROTECTION. 1157

conditions of the second relay will, of course, be useless. and incoming machines, and these currents may be
This fact has been taken into account in compiling the considerably out of phase with the machine e.m.f.'s.
curves in Figs. 14, 15 and 16. At the instant of paralleling, the machine is excited
From these curves it will be seen that, no matter to produce line voltage with no load on the machine
how the relays may be connected, certain conditions, and is, therefore, under-excited for load conditions. If
either of fault or of normal running, can in every case the machine immediately picks up load it will give for-
produce irregular operation of the relays, causing either ward power with leading current, whereas if it be
motored from the line it will absorb reverse power
(a) The relay to remain stable when reverse power with lagging current.
in excess of the setting value flows in the circuit, Now, it will be seen from Fig. 12 that under these
or conditions a relay having its potential coils connected
(b) The relay to operate even when forward power is to the leading phase is definitely unstable and tends to
being supplied by the circuit.
200 zoo
R( lay ( n ph ase" 3"
po tent al c<>ils
-- CO nnec ted eithe r
160 ar o Qutid rat ure

Rel \y on pha se A
do.
120

power
80
Forwar

40

t
If 1
i \
R jlay witl-
CO
oltag"e ^;ollaf
V
dra "ure
nnecl ions./only and

jjj s &
0
\
80 a
iverse

\
/

PS
120 / \

/1 \

1 Cft \i 1
1
?00
CJ
Phase displa :emeiit (d
ac ross atid' ct rren fiT faul
i
30 60 tn 60 30
1
s)ib
30 |60
etwe

m 60 30
r
30 60 60 30 g % Forward 2 Reverse Reverse <8 Forward
ts Reverse ii Forward s (leading C (lag-g-ing;) _ (leading) g (lading)
a. (leading-) J (lag-g-ing) %
c g C
FIG. 13.Operating curves for reverse-power relays, Single- FIG. 14.Operating curves for reverse-power relays. Poten-
phase fault. tial coils star- or quadrature-connected. Fault between
two phases.
It is thus necessary to look closely into the conditions operate with practically no load, and thus synchronizing
which are to be guarded against, in order to decide must be done with great exactitude if the circuit breaker
which type of connection is the most suitable for any is to remain closed. This method of connecting the
given case. relays is, therefore, undesirable for these particular
conditions.
PROTECTION OF GENERATORS. The lagging-phase connection is also undesirable,
Let us consider first the question of generator pro- since it, too, produces instability in the relay under
tection. Now it is well known that at the instant of conditions of hunting, which may occur due to any
synchronizing an incoming generator there 'is usually an surge arising out of, say, a sudden fluctuation in load,
exchange of synchronizing currents between the running or to a fault on some remote part of the system. In this
1158 TAYLOR: REVERSE-POWER ALTERNATING-CURRENT RELAYS
case, since the machine is excited for about full load, it at the moment of synchronizing an incoming machine
is over-excited during those periods of hunting, when it always resulted in the incoming machine being tripped.
tends to become motored by the remaining machines. Both these effects might, however, be overcome by
In consequence its power factor will be very low, and if fitting a time delay in the instrument, but this would, of
it continues to give forward power this will be accom- course, be detrimental to the action of the relays under
panied by low, lagging power factors, whereas if it be fault conditions and is not, therefore, a real solution to
motored the reverse power consumed will have a low, the difficulty.
leading power factor, and reference to Fig. 12 will show Stability up to the setting value of the relay is thus
that under these conditions a relay connected across seen to be essential for generator protection and, 'there-
the lagging phase tends to operate with practically no fore, the star or quadrature connections offer the best

200

160

\
120 -\- r Rela y on pha se "A Vo tag-e maintained \-
collapsed
t
\ I Voltaere maintained
It0 \
n
L1T^~- collapsed
\ \ |
2*
1
gin
40 n
A
I
y
\ V

Y\ Relay o: n pha se"B

a \N \ A
o
\ \
80 0111 \
in \
<U

I \
\
\
\
l
i Phase d splacem nt (degrees) between voltag-.
Pha:>e di splac,etne i t j(d eg-'re ss) h etwe :n v< 'tag- I I across and current in fault - fa | |
7.00
across and current in fault <pr j 30 60 <g 60 30 v 30 60 <g 60 30
1
30 60 in 60 30 CO0) 30 60 60 30 Forward *> Reverse J Reverse .2 Forward J
Forward Reverse Reverse Forward (leading-) (lag-g-ing-) o. (leading-) (lag-g-ing) -g.
(leading-) a
(lag-g-ing) 1 (leading-) Uag-g-ingO g? c 0 c
I c I
FIG. 15.Operating curves for reverse-power relays. Poten- FIG. 16.Operating curves for reverse-power relays. Poten-
tial coils connected to leading phase. Fault between tial coils connected to lagging phase. Fault between
two phases. two phases.

power, and the healthy machine may in consequence be solution (as will be seen from Fig. 12). Even these
cut off from the bars. connections do not, however, demand constant power
The author has attempted to run a large traction with between-phase faults, as will be seen from Fig. 14,
station with the generator reverse-power relays arranged but this is of no importance, since, if the machine be
first with lagging phase connections and later with really faulty, the earlier operation of the relay at low
leading phase connections. With the first arrangement, power factors becomes an advantage.
any fault on the system invariably caused at least one Furthermore, in the case of faults outside the station
machine to be tripped off the bars, although the relays and calling for forward power at low power factor, if the
were set at 40 per cent of the full-load rating of the fault be a 3-phase symmetrical one there is no tendency
generators, and the relays were, therefore, almost useless for the relays so connected to operate (see Fig. 12),
as protective devices against faults in the generator; whereas with leading or lagging connections the relays
whilst, with the second arrangement, any drop in load may require but little power to trip the machine.
FOR 3-PHASE GENERATOR AND FEEDER PROTECTION. 1159
This advantage is-even more marked in the case of any extra power which the relay may prove to need will
single-phase faults (see Fig. 13) and, since these are sdon be forthcoming.
perhaps the most frequent type of failure, this fact alone Apart, however, from the desirability of limiting the
is sufficient reason for the adoption of the star or quadra- fault to the smallest magnitude consistent with the
ture system of connection. satisfactory " surge " setting of the relay, there must
With between-phase faults beyond the relay, even also be considered the question of the effect on the relays
star or quadrature relays may be in danger of operating, on other parts of the system.
but, again, they have the advantage over relays with Most systems using reverse-power relays on feeders
leading or lagging phase connections, since the danger usually employ overload and earth leakage relays at the
point is not reached until the power factor has dropped " supply " end of the feeder, in order to cut out a faulty
to a much lower value than that which renders the latter cable at that end, and Fig. 17 shows the arrangement in
types unsafe, and this advantage becomes more marked diagrammatic form.
if the voltage tends to collapse. Now suppose a single-phase fault to develop on
A further examination of Figs. 12, 13 and 14 will show feeder " A " (Fig. 17) at the point indicated, then the
that the quadrature type of connection has little advan- earth leakage relay "a." will operate, thus cutting off
tage to offer over the simple star connection, except the direct supply to the fault; power will, however,
in the case of a short-circuit between two phases with continue to be fed thereto by way of the parallel feeder
collapse of voltage. This is only of importance,- " B , " and will thus cause the necessary reversal at " R "
however (in the case of generators), if no other pro- and tend to produce operation. There is, however,
tection gear be installed; and, where such additional a tendency also for the earth leakage relay " b " to

TABLE 2.

Values below which reverse-power relays must be set if they are to operate
before earth leakage, relay " b "
Current to operate Power factor of fault Power in fault (single-
earth leakage relay circuit (lagging
current) phase, voltage G 350) Leading Lagging
Star or quadrature cos (SO P cos (80-^/)
s
0-2SScos$/ * 0-288 cos ^ /

amps. kVV kW kVV kW


14-25 1-0 271-5
90-5 271-5 271-5
14-25 0-866 235-2
78-4 3130 156-5
14-25 0-5 135-75
45-25 271-5 Zero

gear is provided, the author considers the additional operate, and it depends entirely upon the value of the
expense and complication incurred by reason of the power required to operate " R " to decide which relay
condenser to be unjustified and he recommends the shall operate first.
adoption of simple star connections for generator Let feeder " B " be assumed to be a 0-2 sq. in. 11 000
protection. volt 3-phase cable and the earth leakage relay to be
set to operate at 5 per cent of normal full load (i.e.
PROTECTION OF FEEDERS. 5 per cent of 285 amperes, E.R.A. rating), then a leakage
Turning now to the protection of parallel feeders, in of 14-25 amperes will be necessary to produce operation.
this case two conditions are of primary importance: If this current be present and the fault circuit be assumed
for the moment to be non-inductive, then the value of the
(1) The relays must remain inoperative in the event single-phase reverse power which tends to affect relay
of small 3-phase reversals, such as might result " R " on the faulty phase will be 6 3 5 0 x 1 4 - 2 5
from a surge, regardless of the power factor = 90-5 kW.
accompanying such surge, or otherwise the Now it has been shown (see Table 1) that the power
protected feeder will be put out of action with in the fault (Pf) necessary to operate a star- or quadra-
surges of only small magnitude, provided the ture-connected relay = P / = %PS- Therefore P8 = 3P/
power factor is low enough. and the relay must therefore be set at less than 3 X 90-5
(2) The relays must operate at their setting value and = 271-5 kW if it is to operate before the leakage relay " b . "
must not require any excess of power above this Had the potential coils of the relay been connected
figure (regardless of power factor). across the leading phase, then, since
This second requirement may not at first sight appear 0-288 cos 0 /
s
to be of much importance, and it may be felt that a fault 'cos (30 + <f>f)
which- permits the passage of power equal to the setting cos
cos (30 +
+ 6r)
6r)
value will very soon develop to such proportions that Pss must be made equal to Pt
J n nnn ^j-
^ 0-288 cos (f>f
1160 TAYLOR: REVERSE-POWER ALTERNATING-CURRENT RELAYS
and since we are, for the moment, dealing with unity of between unity and 0 5 lagging, star- or quadrature-
power factor, <f> = 0, and Ps must equal P/cos 30/0-288 connected instruments may be set at only 50 per cent
= P/X 0-866/0- 288 = 3 X 90-5 = 271-5 kW as before. of the setting permissible with instruments having
Now it is extremely unlikely that the power factor leading-phase connections. Thus the tendency of the
of the fault will be unity, and, therefore, if some other latter type of instrument to become unstable with low
value be assumed, say 0-5(0/ = 60) or 0-866(0/ = 30) power factors is largely offset by the higher setting
(both lagging), then Table 2 will show the values below permissible; in fact, this connection has the advantage
which the reverse-power relays must be set if they are in this respect for power factor values between unity
to operate without affecting the earth leakage relay " b." and 60 lagging (reverse power).
A study of Table 2 will show that the power required It will thus be seen that for feeder protection the
to operate relays having leading-phase connections to leading-phase connection gives the most satisfactory
the potential coils is a more constant function of the behaviour possible, so far as single-phase faults and
earth leakage current throughout the range of power stability are concerned.
Considering between-phase faults, it will be appre-
ciated that these do not affect the earth leakage relays,
Generators and in consequence the faulty feeder is not disconnected
at the supply end until the overload relays come into
ow action; thus a considerable amount of power may be fed
OOverload relays6
to the fault, and power may also be fed back thereto from
Earth leakage relays^|
any synchronous plant beyond the fault, such as the
synchronous motors " X " and " Y " in Fig. 17.
Fault Under these circumstances, relays " 1 " and " m "
will also have a tendency to operate, in addition to relay
" R," and forward power (influenced largely by the
power factor of the fault) will flow past relay " S."
The effect of these conditions upon relays connected
according to the four methods under discussion will be
as given in Table 3, the current in the fault being assumed
to lag behind the fault voltage.
RQ~-Reverse-power relaysT|S
The most important requirements demanded by these
loverloadi conditions are that relay " R " should definitely be
O relays VJ
fc-Earth \
leakage
operated and that relay " S " should remain stable.
relays Thus, so far as relay " S " is concerned, the leading
connection is again the most suitable, since it fulfils this
condition under all conditions of voltage. In the case
of relay " R," this connection results in very sensitive
operation and is, therefore, satisfactory, but there is
danger of the relays " 1 " and " m " also being caused to
operate with very low values of power if this type of
connection be used. It is true that this undesirable
feature could be obviated by the use of the lagging-phase
connection (or, if the voltage collapse, by the use of the
quadrature connection also), but, from what has been
said before, this would result in very poor behaviour
under the conditions considered earlier on, and therefore
cannot be obviated. Thus, although the leading-
factors usually accompanying a single-phase fault than phase connection gives the best possible means of
is the case with either star-, quadrature- or lagging- utilizing this type of relay for feeder protection, the
connected instruments, and it is, therefore, more nearly behaviour leaves a considerable amount to be desired,
possible to obtain properly correlated settings between and a further advance in the design is thus seen to be
earth leakage relays and reverse-power relays if the desirable.
latter have their potential coils connected to the leading
phase. CHANGING CONNECTIONS.
With regard to stability under conditions of momen- It is perhaps necessary to point out at this stage that
tary 3-phase reversals, it will be seen from Fig. 12 that the potential coils of a relay cannot be changed indis-
star- or quadrature-connected instruments are definitely criminately from one system of connection to another,
stable up to the setting value throughout the entire for the following reasons:
range of power factor, but reference to Table 2 will show From what has been said earlier on, it will be seen
that relays so connected may not be set at so high a that, if the connections of the potential coils of a given
value as is possible with leading-phase instruments, if relay were to be changed from star to either the leading
satisfactory discrimination in respect of earth faults is to or lagging phase, then the setting values marked on the
be obtained. scale would automatically become untrue, for with
To obtain absolute reliability with power factors star-connected potential coils the pointer must reach
FOR 3-PHASE GENERATOR AND FEEDER PROTECTION. 1161

the setting value when energized by only one-third of of tripping contacts shall be closed or not. At first
the 3-phase power in the main circuit, whilst for leading sight this appears to be a very near approach to a true
or lagging connections the pointer (i.e. the moving con- a.c. reverse-current device. Consider the instrument
tact for the tripping circuit) is influenced by half of the as an ammeter capable of indicating correctly the main
total 3-phase power. (The latter statement is true only current and having tripping contacts in series with
for unity power factor load in the main circuit, but it is those of a central-zero wattmeter, the latter contacts
for this condition only that the scale of an instrument being fixed at the first division on the reverse side

TABLE 3.

Relay " S " Relays " 1 , " "m" and ' R"

Type of connection
Behaviour Operating Power required Behaviour Operating Power required
limits limits

degrees % of setting % of setting


Star May operate 60-90 Inf.-zero Operate Throughout Zero to 66
Quadrature (voltage maintained) .. May operate 60-90 Inf.-zero Operate Throughout Zero to 66
Quadrature (voltage collapsed) Stable Operate Throughout 57
Leading (voltage maintained) Stable Operate Throughout Zero to 50
Leading (voltage collapsed) Stable Operate Throughout Zero to 50
Lagging (voltage maintained) May operate 45-90 Inf.-zero Operate Throughout 50
Lagging (voltage collapsed) May operate 45-90 Inf.-zero Operate Throughout 50

Required condition Stability " 1 " and " m " to be ; stable.


'' R " to operate.

working with either leading or lagging connections is of the wattmeter scale. It would now appear that, so
true.) long as the power is forward, the ammeter may reach
Now, where relays are energized by potential trans- the tripping value and close the contacts and yet not
formers, this effect is subject to a still further variation,
since, in order to keep the voltage across the coils at the
value for which they were designed, the ratios of the
transformers must be different.
For star-connected relays the ratio must be:
Main phase voltage/relay coil voltage.
For relays whose potential coils are between phases
the ratio must be: , "RELAY R E Q U I R E D \ x> Y
, TO BE STABLE W H I L S T X ^ N
Line voltage (i.e. -\/3 x main phase voltage) CURRENT VECTOR OCCUPIES"
THIS SEMICIRCLE UNOER
' relay coil voltage. CONDITIONS lOF 3-PHASE
NORMAL |WORKING
AND WITH SINGLE-PHASE FAULT
TO EARTH
DIRECTIONAL A.C. RELAYS.
RELAY REQUIRED TO OPERATE
So far, consideration has been given only to true IF CURRENT VECTOR
wattmeter-type relays, but the same arguments can OCCUPIES THIS SEMICIRCLE
be applied to almost all classes of so-called reverse-power UNOER ABOVE
CONDITIONS
relays.
In a later type of instrument the disadvantages of non-
opsration due to failing voltage are claimed to have been
overcome by applying the scheme outlined below.
An overload mechanism, operated purely by current, is
arranged under the same cover as an extremely sensitive
directional element, and each of these devices is fitted
with tripping contacts wired in series. The directional FIG. 18.Diagram showing conflicting requirements in
element is not required to be quantitative, but is merely behaviour of reverse-power relays when under normal
required to close its tripping contacts when the power is or fault conditions.
" reversed," and it can, therefore, be made so that only
1 per cent or less of the normal voltage will produce open the switch, since the wattmeter contacts are not
discriminative action, and it then remains for the quanti- yet closed. Furthermore, in the event of reverse power,
tative, current device to decide whether the second set even if the voltage be reduced almost to zero, it will
1162 TAYLOR; REVERSE-POWER ALTERNATING-CURRENT RELAYS.
require but little current to bring the wattmeter finger must remain stable so long as the vectors representing
over to the operating position, equal to, say, only phase current and phase voltage are not displaced by
10 watts, and thus, if the current ever reaches the figure more than 90, and must operate at the setting value
at which the ammeter contacts are closed, the switch when this displacement is exceeded.
will be tripped, since then the tripping circuit will be For between-phase faults, however, stability is
completed at both sets of contacts. The instrument required so long as the vector representing fault
thus appears to be remarkably efficacious, yet a little current is not displaced by more than 90 from the
consideration will show that, as in the case of wattmeter- vector representing fault voltage. The voltage across
type relays, the directional element will not operate a fault between phases may, however, be either 30
correctly with single-phase, 2-phase and 3-phase faults, ahead of or 30 behind the phase voltage (according
no matter how connected, but will in some cases close to which of the two remaining phases is involved
the contacts with forward power, so that, if the current in the fault) and thus three sets of conditions are seen
be of sufficient magnitude, inaccurate operation will to call for consideration in any one relay, and, more-
result, whilst also, in some cases of reverse power, the over, the requirements of each case are opposed to each
directional element will still remain open in exactly other at power factors of less than 0 5.
the same manner as has been shown to occur with This is shown in Fig. 18, where the full lines repre-
wattmeter-type instruments. This obtains, no matter sent the conditions under single-phase and 3-phase
what scheme of connections is adopted, and the points operation, the chain-dotted lines representing condi-
at which incorrect operation can be produced are exactly tions involving the leading phase, and the plain
as given in Figs. 12, 13, 14, 15 and 16 for wattmeter- dotted lines showing the conditions when the lagging
type instruments; the power values indicated by the phase is concerned.
curves require modification, however, and the current
curve is a straight line having a value equal to the In view of these conflicting requirements, it is small
setting of the overloador ammeterelement for all wonder that the simple instruments treated of in this
values of power factor and voltage collapse. paper fail to give the degree of protection really necessary,
The instrument does represent a marked advance, but if due consideration be given to the points which
and enables correlated settings with earth leakage relays the author has attempted to set out in this paper much
to be made with great accuracy, but the wattmeter can be done to obtain more satisfactory results than
element is still responsible for incorrect discrimination. appear to be common.
That the problem is a difficult one will be appreciated In conclusion, the author would like to express his
from the following epitomized statement of the con- appreciation of the assistance so readily afforded him
ditions : in the preparation of this paper by his colleague, Mr.
For 3-phase and single-phase conditions the relays H. C. Smith.

You might also like